GNRO-2013/00067, LAR Application for Technical Specification Changes; Technical Specification Task Force (TSTF) Improved Standard Technical Specification Change Traveler, TSTF-535, Revise Shutdown Margin Definition to Address Advanced Fuel

From kanterella
(Redirected from ML13337A592)
Jump to navigation Jump to search

LAR Application for Technical Specification Changes; Technical Specification Task Force (TSTF) Improved Standard Technical Specification Change Traveler, TSTF-535, Revise Shutdown Margin Definition to Address Advanced Fuel
ML13337A592
Person / Time
Site: Grand Gulf 
(NPF-029)
Issue date: 11/08/2013
From: Kevin Mulligan
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GNRO-2013/00067
Download: ML13337A592 (10)


Text

Ent~

GNRO-2013/00067 November 8, 2013 U.s. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 Entergy Operations. Inc.

P.O. Box 756 Port GibsonJ Mississippi 39150 Kevin J. MoUigan Site Vice President Grand Gulf Nuclear Station Tel: 601-437-1500

SUBJECT:

License Amendment Request Application for Technical Specification Changes; Technical Specification Task Force (TSTF) Improved Standard Technical Specification Change Traveler, TSTF-535, "Revise Shutdown Margin Definition to Address Advanced Fuel Designs" Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. 29

REFERENCE:

Traveler, TSTF-535 Revision 0, "Revise Shutdown Margin Definition To Address Advanced Fuel Designs"

Dear Sir or Madam:

In accordance with the provisions of Section 50.90 of Title 10 Code of Federal Regulations (10 CFR), Entergy Operations, Inc. (Entergy) is submitting a request for an amendment to the Technical Specifications (TS) for Grand Gulf Nuclear Station, Unit 1.

The proposed amendment modifies the TS definition of "Shutdown Margin" (80M) to require calculation of the SDM at a reactor moderator temperature of 68 degrees Fahrenheit (OF) or a higher temperature that represents the most reactive state throughout the operating cycle. This change is needed to address new Boiling Water Reactor (BWR) fuel designs which may be more reactive at shutdown temperatures above 68°F. provides a description of the proposed change. Attachment 2 provides the existing TS pages marked up to show the proposed change.

GNRO-2013/00067 Page 2 of 2 Although this request is neither exigent nor emergency, your prompt review is requested.

Once approved, the amendment shall be implemented within 60 days.

This letter contains no new commitments. If you have any questions or require additional information, please contact Mr. Jeffery A. Seiter at (601) 437-2344.

I declare under penalty of perjury that the foregoing is true and correct. Executed on November 8, 2013 Sincerely, KJM/jas Attachments:

1.

Analysis of Proposed Technical Specification Change 2.

Proposed Technical Specification Changes (mark-up) 3.

Proposed Technical Changes (clean page) cc: U.S. Nuclear Regulatory Commission ATTN: Mr. Mark Dapas, (w/2)

Regional Administrator, Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 NRC Senior Resident Inspector Grand Gulf Nuclear Station Port Gibson, MS 39150 U. S. Nuclear Regulatory Commission ATTN: Mr. Alan Wang, NRRlDORL (w/2)

Mail Stop OWFN 8 B1 Washington, DC 20555-0001 Dr. Mary Currier, M.D., M.P.H State Health Officer Mississippi Department of Health P. O. Box 1700 Jackson, MS 39215-1700 GNRO*2013/00067 Analysis of Proposed Technical Specification Change to GNRO-2013/00067 Page 1 of 3

1.0 DESCRIPTION

The proposed amendment modifies the Technical Specifications (TS) definition of "Shutdown Margin" (SOM) to require calculation of the SDM at a reactor moderator temperature of 68 degrees Fahrenheit (OF) or a higher temperature that represents the most reactive state throughout the operating cycte. This change is needed to address new Boiling Water Reactor (BWR) fuel designs which may be more reactive at shutdown temperatures above a8°F.

The availability of the model safety evaluation for this TS improvement was announced in the Federal Register as part of the Consolidated Line Item Improvement Process (CLIIP).

2.0 BACKGROUND

The background for this application is adequately addressed by the U.S. Nuclear Regulatory Commission (NRC) Notice of Availability of Model Safety Evaluation on Technical Specification Improvement to modify the requirements regarding Technical Specifications (TS) definition of "Shutdown Margin" (SDM).

Entergy Operations, Inc" (Entergy) is not proposing any variations or deviations from the TS changes described in the TSTF-535, Revision 0, "Revise Shutdown Margin Definition to Address Advanced Fuel Designs, ft or the applicable parts of the NRC stairs model safety evaluation.

3.0 TECHNICAL ANALYSIS

3.1 Applicability of Published Safety Evaluation Entergy has reviewed the model safety evaluation as part of the Federal Register Notice of Availability. This review included a review of the NRC stairs evaluation, as well as the information provided in TSTF-535. Entergy has concluded that the justifications presented in the TSTF-535 proposal and the model safety evaluation prepared by the NRC staff are applicable to Grand Gulf Nuclear Station, Unit 1 (GGNS), and therefore justify this amendment for the incorporation of the proposed changes to the GGNS TS.

Entergy is not proposing any variations or deviations from the TS changes described in the TSTF-535, Revision 0, or the NRC staffs model safety evaluation.

3.2 CONCLUSION

S In conclusion, based on the considerations discussed above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the NRC*s regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.

to GNRO-2013/00067 Page 2 of 3 4.0 REGULATORY SAFETY ANALYSIS 4.1 No Significant Hazards Consideration Determination Entergy requests adoption of TSTF-535, Revision 0, "Revise Shutdown Margin Definition to Address Advanced Fuel Designs," which is an approved change to the standard technical specifications (STS), into the GGNS TS. The proposed amendment modifies the TS definition of "Shutdown Margin" (80M) to require calculation of the 80M at a reactor moderator temperature of 68°F or a higher temperature that represents the most reactive state throughout the operating cycle.

Entergy has evaluated whether or not a significant hazards consideration is involved with the proposed amendment(s) by focusing on the three standards set forth in Title 10 of the Code of Federal Regulations (10 CFR) 50.92, "Issuance of amendment," as discussed below:

1. Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?

Response: No.

The proposed change revises the definition of SOMa 80M is not an initiator to any accident previously evaluated. Accordingly, the proposed change to the definition of 80M has no effect on the probability of any accident previously evaluated. 80M is an assumption in the analysis of some previously evaluated accidents and inadequate 80M could lead to an increase in consequences for those accidents. However, the proposed change revises the 80M definition to ensure that the correct SOM is determined for all fuel types at all times during the fuel cycle. As a result, the proposed change does not adversely affect the consequences of any accident previously evaluated.

Therefore, the proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.

2. Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?

Response: No.

The proposed change revises the definition of SOMa The change does not involve a physical alteration of the plant (Le., no new or different type of equipment will be installed) or a change in the methods governing normal plant operations. The change does not alter assumptions made in the safety analysis regarding 80M.

Therefore, the proposed change does not create the possibility of a new or different kind of accident from any accident previously evaluated.

to GNRO-2013/00067 Page 3 of 3

3. Does the proposed change involve a significant reduction in a margin of safety?

Response: No.

The proposed change revises the definition of 80M. The proposed change does not alter the manner in which safety limits, limiting safety system settings or limiting conditions for operation are determined" The proposed change ensures that the SOM assumed in determining safety limits, limiting safety system settings or limiting conditions for operation is correct for all BWR fuel types at all times during the fuel cycle.

Therefore, the proposed change does not involve a significant reduction in a margin of safety" Based on the above, Entergy concludes that the proposed change presents no significant hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a finding of "no significant hazards consideration" is justified.

4.2 Applicable Regulatory Requirements/Criteria A description of the proposed TS change and its relationship to applicable regulatory requirements was prOVided in the NRC Notice of Availability of the Model Safety Evaluation.

5.0 ENVIRONMENTAL CONSIDERATION

Entergy has reviewed the environmental evaluation included in the safety evaluation, as part of the CLIIP Notice of Availability of the Model Safety Evaluation. Entergy has concluded that the staffs findings presented in that evaluation are applicable to GGNS and the evaluation is hereby incorporated by reference for this application.

6.0 REFERENCES

1. Technical Specifications Task Force (TSTF) 535, "Revise Shutdown Margin Definition to Address Advanced Fuel Designs" Revision 0 Dated February 26, 2013. (Accession Number ML112200436)
2. NRC Model Safety Evaluation, Federal Register dated February 26, 2013. (Accession Number ML12355A772)

GNRO*2013/00067 Proposed Technical Specification Changes (mark-up)

Note, markup deletions identified by strikethrough (4eIete) and additions identified by underline (addition).

1.1 Definitions (continued)

SHUTDOWN MARGIN (SOM)

~ 68 0Ft corresponding to the most reactive state;

.-~----

STAGGERED TEST BASIS THERMAL POWER Definitions 1.1 throughout the operating cycle SOM shall be the amount of reactivity by whic the reactor is subcrit1cal or would be subcritical assuming that:

~~""""'-,and c.

All control rods are fully inserted except for the single control rod of highest reactivity worth, which is assumed to be fully withdrawn.

With control rods not capable of being fully inserted, the reactivity worth of these control rods must be accounted for in the determination of SOMe A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.

THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

GRAND GULF 1.0-6 Amendment No. ~

1.1 Definitions (continued)

SHUTDOWN MARGIN (SOM)

Insert:

68 0 Ft corresponding to the most reactive state; STAGGERED TEST BASIS THERMAL POWER Definitions

1.1 Insert

throughout the operating cycle SOM shall be the amount of reactivity by whic the reactor is subcritical or would be subcritical assuming that:

The reactor is xenon free; b.

The moderator temperature;' ~~..., and c.

All control rods are fully inserted except for the single control rod of highest reactivity worth, which is assumed to be fully withdrawn.

With control rods not capable of being fully inserted, the reactivity worth of these control rods must be accounted for in the determination of SDM.

A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.

THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

GRAND GULF 1.0-6 Amendment No. ~

GNRO-2013/00067 Proposed Technical Specification Changes (clean page)

The reactor is xenon free; moderator corresponding is

~

68 F,

reactive state; and c.

are inserted rod of highest is assumed to fully withdrawn.

control rods being fully

inserted, the these rods must be accounted in the determination of SDM.

TEST BASIS shall consist of the

systems, designated by the
systems, shall be the total reactor core heat transfer rate to the reactor coolant.

1.. 0-6 The reactor is xenon free; moderator corresponding is

~

68 F,

reactive state; and c.

are inserted rod of highest is assumed to fully withdrawn.

control rods being fully

inserted, the these rods must be accounted in the determination of SDM.

TEST BASIS shall consist of the

systems, designated by the
systems, shall be the total reactor core heat transfer rate to the reactor coolant.

1.. 0-6 Definitions 1.1 1.1 Definitions (continued)

SHUTDOWN MARGIN (SDM)

STAGGERED TEST BASIS THERMAL POWER SOM shall be the amount of reactivity by which the reactor is subcritical or would be subcritical throughout the operating cycle assuming that:

a.

The reactor is xenon free; b.

The moderator temperature is 268°F, corresponding to the most reactive state; and c.

All control rods are fully inserted except for the single control rod of highest reactivity

worth, which is assumed to be fully withdrawn.

With control rods not capable of being fully

inserted, the reactivity worth of these control rods must be accounted for in the determination of SDM.

A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems,

channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems,
channels, or other designated components in the associated function.

THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

GRAND GULF

1. 0-6 Amendment No. ~