MONTHYEARML13310A9171983-08-26026 August 1983 Notifies That Proposed Change to Tech Specs Re Battery Surveillance Requirements Will Be Submitted in Oct 1983. Results of Recent 60-month Battery Performance Test Will Also Be Delayed Due to Efforts Involved Project stage: Request ML13310B0951983-11-28028 November 1983 Application to Amend License DPR-13,consisting of Proposed Change 126 to Tech Specs,Revising Limiting Conditions for Operation & Corresponding Surveillance Requirements for Electrical Supplies Project stage: Request ML13310B0921983-11-30030 November 1983 Forwards Application to Amend License DPR-13,consisting of Proposed Change 126 to Tech Specs,Specifying Limiting Conditions for Operation & Surveillance Requirements for Electrical Supplies for Each Mode of Operation Project stage: Request ML13310B0971983-11-30030 November 1983 Existing & Proposed Tech Specs 3.7, Auxiliary Electrical Supply, & 4.4, Emergency Power Sys Periodic Testing Project stage: Other ML13316A5731983-12-22022 December 1983 Advises That Proposed Change 126 to Tech Specs to Delete Existing Auxiliary Feedwater Pump Requirements in Section 4.4.E Does Not Provide Adequate Justification for Deletion of Provisions of Spec Project stage: Other ML13310B1341983-12-30030 December 1983 Submits Addl Info to Support Util 831130 Proposed Change 126 to Delete Tech Spec 4.4.E Re Operability of Auxiliary Feedwater Sys.Surveillance Requirements in Tech Spec 4.4.E Superseded by Tech Spec 4.1.9 Issued in Amend 65 Project stage: Request ML13310B1421984-01-13013 January 1984 Requests No Addl Consideration Be Given to Removal of Tech Spec 4.5.E as Part of Proposed Change 126 Submitted on 831130.Removal of Surveillance Requirement for Auxiliary Feedwater Sys Will Be Handled in Future Proposed Change Project stage: Request ML13310B2891984-03-0909 March 1984 Forwards Request for Addl Info Re Proposed Changes 76 & 126 to Tech Specs.Info Requested within 30 Days of Ltr Date Project stage: RAI ML13310B3241984-04-12012 April 1984 Addl Info Re Proposed Changes 76 & 126 to License DPR-13. Response to NRC 840309 Request for Info Will Be Submitted in 45 Days,Following Replacement of Dc Battery Bank 1 Due to End of Svc Life Project stage: Request ML13310B6031984-07-27027 July 1984 Forwards Addl Info Re Proposed Changes 76 & 126 to Tech Specs,In Response to NRC 840309 Request.Calculation Sheets Encl.W/Three Oversize Drawings.Aperture Cards Available in PDR Project stage: Request ML13330A4461984-10-15015 October 1984 Application to Amend License DPR-13,revising Proposed Change 126,to Maintain Battery Charger Output Current Consistent W/Existing Tech Specs & to Omit Operability Contingency That Battery Parameters Must Be within Allowable Values Project stage: Request ML13316A7431984-11-14014 November 1984 Amend 84 to License DPR-13,approving Changes to Tech Specs & Bases to Incorporate Mods to Operability & Surveillance Requirements for Auxiliary Electric Supplies Project stage: Other ML13316A7461984-11-14014 November 1984 Safety Evaluation Supporting Amend 84 to License DPR-13 Project stage: Approval ML13316A7401984-11-14014 November 1984 Forwards Amend 84 to License DPR-13 & Safety Evaluation. Amend Approves Tech Spec Changes & Bases Incorporating Mods to Operability & Surveillance Requirements for Auxiliary Electric Supplies Project stage: Approval 1984-01-13
[Table View] |
Text
0- tpj REG UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION SUPPORTING AMENDMENT NO. 84 TO PROVISIONAL OPERATING LICENSE NO. DPR-13 SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO.1 DOCKET NO. 50-206
1.0 INTRODUCTION
1.1 Description of the Proposed Action The proposed action would amend Section 3.7 of the facility technical specifications (TS) to clarify equipment operability requirements for the various operating modes, and Section 4.4 of the specifications such that the surveillance requirements for electrical systems conform more closely to the requirements of the Standard Technical Specifications (STS).
Notices of Consideration of Issuance of Amendment to License and Proposed No Significant Hazards Consideration Determination and Opportunity for Hearing related to the requested action were published in the Federal Re ister on August 22, 1984 (49 FR 33370), March 22, 1984 (49 FR 10743),
and August 23, 1983 (48 FR 38421). A request for hearing and public comments were not received.
1.2 Background Information By letter dated October 20, 1978, Southern California Edison Company (the licensee) requested changes to two sections of the facility TS.
This evaluation addresses the section of that subr 1tal (Section 4.4.D) pertaining to surveillance of D.C. power systems By letter dated November 30, 1983, the licensee requested additional changes to the TS governing plant electrical systems.
These changes included revisions to Section 3.7 to expand and clarify equipment operability requirements for various operating modes, and to Section 4.4 to.revise the surveillance requirements for A.C.. and D.C. electrical systems, and to delete the.
surveillance requirements for the Auxiliary Feedwater (AFW) pumps.
The other portion of the request was addressed by Amendment No.. 56 to the 1icense.
. 411210093 841114 PDR ADOCK 05000206 PD
-2
- 2. Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and Paragraph 3.B of Provisional Operating License No. DPR-13 is hereby amended to read as follows:
B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.
84, are hereby incorporated in the license. Southern California Edison Company shall operate the facility in accordance with the Technical Specifications.
- 3. This license amendment is effective the date of its issuance.
FOR THE NUCLEAR REGULATORY C MMISSION John A. Zwolinski, Chief Oper ting Reactors Branch #5 Division of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: