Text
Mitman, Jeffrey From:
Wilson, George Sent:
Friday, December 18, 2009 6:55 AM To:
Mitman, Jeffrey I)%)~'
Subject:
RE: Comparison of risk reduction frorfi various modifications thanks From: Mitman, Jeffrey I
Sent: Thursday, December 17, 2009 6:58 PM To: Wilson, George
Subject:
Comparison of risk reduction from various modifications George, you've asked for my assessment of the risk reduction from various modifications that Duke is considering. Here are my estimates. They are estimates based on my incomplete knowledge of what is being developed by Duke. To refine them, I would need significantly more information about each modification and how it changes the existing design.
Jeff Risk Comparison of ONS Modifications Estimated Risk Modification Reduction (delta CDF per year)
Increase SSF Flood Protection 1.5E-4 Total of Currently Planned Modification (sum of values below) 8.1E-5 Tornado 6.8E-6 Internal Events 1.4E-5 HELB 1.OE-5 Fire 5.OE-5 1