1/2/2013 Exel6n-Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Chemical & Volume Control System (CV)
S fion Xl : Component ID I the N umber : Rel ef' re ti cai 1 } ctt et ;^ ^R+^^.
IDescr Cori: Requests ;Note . c erag , ,,. ,
Comments R-A R1.11 1CVA3AA-2/W-06 1 CVA3AA-2 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-001 R-A R1.11 1CVA3AA-2/W-07 1CVA3AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-002 R-A R1.11 1CVA3B-2/W-74 1CVA3B-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-003 R-A R1.11 1CVA3B-2/W-75 1CVA3B-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-004 R-A R1.11 1CVA3B-2/W-76 1CVA3B-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-005 R-A R1.11 1CVA3B-2/W-77 1CVA3B-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-006 R-A R1.11 1 CVA3B-2/W-84 1 CVA3B-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-007 R-A R1.11 1CVA3B-2/W-85 1CVA3B-2 13R-02 B9.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-008 R-A R1.11 1CVA5AA-2/W-04 1CVA5AA-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-009 R-A R1.11 1CVA5AA-2/W-05 1CVA5AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-010 R-A R1 .11 1CVA6AA-2/W-04 1CVA6AA- 2 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-011 1
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Chemical & Volume Control System (CV) section XI Rem, ;.tec ni al Cade:. ; 1ctcal Results Cate Requests : Notes j Coverage
.Comments R-A R1 .11 1CVA6AA-2/W-05 1 CVA6AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-012 R-A R1.11 1 CVA7AA-2/W-08 1 CVA7AA- 2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-013 R-A R1.11 1CVA7AA-21W-09 1CVA7AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-014 2
1/2/2013 ExeIon_
Byron Station Unit 1 B1R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Feedwater System (FW)
Component ID Relief Technical _ == Cvtl Ac#trsl iResultS Description : ° . Requests A f' Notes , Coverage F, : Exam R-A R1.11 1 FW03DB-16/C01 1 FW03DB-16 13R-02 C5.51 100 UT NRI R1.18 Valve-Pipe 13T-01 13T-02 OBS18-106 R-A R1.11 1FW03DB-16/C02 1FW03DB-16 13R-02 C5.51 100 UT NRI R1.18 Pipe - Penetration 13T-01 13T-02 OBS18-107 R-A R1.11 1 FW87CB-6/C07A 1 FW87CB-6 13R-02 C5.51 100 UT NRI R1.18 Elbow -Pipe 13T-01 13T-02 OBS18-108 R-A R1 .11 1FW87CB-6/C08A 1FW87CB-6 13R-02 C5.51 100 UT GEOM R1.18 Pipe - SOS 13T-01 13T-02 OBS18-109 Root Geometry 360° Intermittent.
3
1/2/2013 Exeknt Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC)
Section Xi Component ID Line Number Reii+ Technical Code (Description Requests; Notes Coverage Cat.'
Comments R-A R1.20 1 RC04AA-12/J02 1 RC04AA-12 13R-02 89.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-110 R-A R1 .11 1 RC04AA-12/J03 1 RC04AA- 12 13R-02 89.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-111 R-A R1.11 1 RC04AA-12/J04 1 RC04AA-12 13R-02 89.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-112 R-A R1.11 1 RC04AA-12/J05 1 RC04AA-12 13R-02 89.11 100 UT NRI Pipe - Tee 13T-01 13T-02 OBS18-113 R-A R1.20 1 RC04AB-12/J02 1 RC04AB-12 13R-02 89.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-118 R-A R1.20 1 RC04AB-12/J03 1 RC04AB-12 13R-02 89.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-119 R-A R1.20 1RC04AB-12/J04 1RC04AB-12 13R-02 89.11 98 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-120 Scanning obstructed by permanent support structure adjacent to piping.
R-A R1.20 1RC04AB-12/J05 1RC04AB-12 13R-02 89.11 91 UT NRI Pipe - Tee 13T-01 13T-02 OBS18-121 Scanning obstructed by permanent support structure adjacent to piping.
R-A R1.20 1 RC05AB-6/J02 1 RC05AB-6 13R-02 89.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-122 R-A R1.20 1 RC05AB-6/J03 1 RC05AB-6 13R-02 89.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-123 4
Exekn _
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC) motion Xt `;Component i D l to Number : Relief Technical ; Code Actual (Results
[ escriptsan.. <l l equ #sts. r. Noted Coverage = : Exam Comments R-A R1.20 1 RC05AB-6/J04 1 RC05AB-6 13R-02 89.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-124 R-A R1.20 1 RC05AB-6/J05 1 RC05AB-6 13R-02 89.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-125 R-A R1.20 1RC13AA-2/W-01 1RC13AA-2 13R-02 B9.40 VT-2 NRI SOL - Pipe 13T-01 13T-02 OBS18-015 R-A R1.20 1 RC13AA-2/W-02.01 1 RC13AA-2 13R-02 89.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-016 R-A R1.20 1 RC13AA-2/W-03 1 RC13AA-2 13R-02 89.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-017 R-A R1.20 1RC13AA-2/W-04 1RC13AA-2 13R-02 B9.40 VT-2 NRI Tee - Pipe 13T-01 13T-02 OBS18-018 R-A R1.20 1RC13AA-2/W-05 1RC13AA-2 13R-02 B9.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-019 R-A R1.20 1 RC13AB-2/W-01 1 RC13AB-2 13R-02 89.40 VT-2 NRI SOL - Pipe 13T-01 13T-02 OBS18-020 R-A R1.20 1 RC13AB-2/W-09 1 RC13AB-2 13R-02 B9.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-021 R-A R1.20 1RC13AC-2/W-01 1RC13AC-2 13R-02 B9.40 VT-2 NRI SOL - Pipe 13T-01 13T-02 OBS18-022 R-A R1.20 1 RC13AD-2/W-01 1 RC13AD-2 13R-02 89.40 VT-2 NRI SOL - Pipe 13T-01 13T-02 OBS18-023 5
1/2/2013 Exek,ri _
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC) echnicei=": ` Code " ctu 0e Notes" j Coverage _ } Bann R-A R1.11 1 RC14AA-2/W-02 1 RC1 4AA-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-024 R-A R1.11 1RC14AA-2/W-03 1RC14AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-025 R-A R1.11 1RC14AA-2/W-03A 1RC14AA-2 13R-02 89.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-026 R-A R1.11 1 RC14AA-2/W-03B 1 RC14AA-2 13R-02 B9.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-027 R-A R1.11 1RC14AA-2/W-03C 1RC14AA-2 13R-02 89.40 VT-2 NRI Tee - Pipe 13T-01 13T-02 OBS18-028 R-A R1.11 1 RC14AA-2/W-04 1 RC14AA-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-029 R-A R1.11 1 RC14AA-2/W-05 1 RC14AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-030 R-A R1.11 1 RC14AA-2/W-06 1 RC14AA -2 13R-02 69 .40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-031 R-A R1.11 1 RC14AA-2/W-07 1 RC14AA-2 13R-02 B9.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-032 R-A R1.11 1 RC14AA-2/W-08 1 RC14AA-2 13R-02 89.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-033 R-A R1.11 1 RC14AA-2/W-09 1 RC14AA-2 13R-02 B9.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-034 6
1/2/2013 Exekn Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC)
Section° Xl component ID ;Line Number Relief Technical . 1. , Coda,< i Actual Fes cat, Description I ecfr gists = . dotes Coverage 1 Eta .
Comments R-A R1 .11 1RC14AA-2/W-10 1 RC14AA-2 13R-02 B9.40 VT-2 NRI Reducer - Pipe 13T-01 13T-02 OBS18-035 R-A R1.11 1RC14AA-2/W-11 1RC14AA-2 13R-02 B9.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-036 R-A R1.11 1 RC14AA-2/W-12 1RC14AA-2 13R-02 B9.40 VT-2 NRI Pipe - Coupling 13T-01 13T-02 OBS18-037 R-A R1.11 1RC14AA-2/W-13 1RC14AA-2 13R-02 B9.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-038 R-A R1.11 1 RC14AB -2/W-07 1 RC14AB-2 13R-02 B9.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-039 R-A R1.11 1RC14AB-2/W-08 1RC14AB-2 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-040 R-A R1.11 1 RC14AB-2/W-09 1 RC14AB-2 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-041 R-A R1.11 1 RC14AB-2/W-10 1 RC14AB-2 13R-02 B9.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-042 R-A R1.11 1RC14AB-2/W-11 1RC14AB-2 13R-02 B9.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-043 R-A R1.11 1 RC14AC-2/W-08 1 RC14AC-2 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-044 R-A R1.11 1 RC14AD-2/W-08 1 RC14AD-2 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-045 7
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC) iC ponent I ' Linn Number Fief Techn al : Code Actual pR sul Descriptio Requests:, Notes , j coverage 1 ,,:= Exam R-A R1.11 1 RC14AD-2/W-09 1 RC14AD-2 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-046 R-A R1.11 1 RC14AD-2/W-10 1 RC14AD-2 13R-02 89,40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-047 R-A R1.11 1 RC14AD-2/W-11 1 RC14AD-2 13R-02 89.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-048 R-A R1.11 1 RC14AD-2/W-12 1 RC1 4AD-2 13R-02 89.40 VT-2 NRI Tee - Pipe 13T-01 13T-02 OBS18-049 R-A R1.11 1 RC14AD-2/W-13 1RC14AD-2 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-050 R-A R1.11 1 RC16AA-2/W-02 1 RC16AA-2 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-051 R-A R1.11 1 RC16AA-2/W-03 1 RC16AA-2 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-052 R-A R1.11 1 RC16AA-2/W-04 1 RC16AA-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-053 R-A R1.11 1 RC16AA-2/W-05 1 RC16AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-054 R-A R1.11 1 RC16AA-2/W-06 1 RC16AA-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-055 R-A R120 1 RC16AA-2/W-07 1 RC16AA-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-056 8
1/2/2013 Exekn,.
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC)
Relief Technical code Ac rat:: iResutts
_........-..,t.Xt"` Componentt:ID Section umber Lin Ca [Descripti r Requests tote 1" Coverage J.; ' Exam Comments R-A R1.20 1 RC16AA-2/W-08 1 RC1 6AA-2 13R-02 89.40 VT-2 NRI Pipe - SOL 13T-01 13T-02 OBS18-057 R-A R1.11 1 RC16AB-2/W-02 1RC16AB-2 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-058 R-A R1.20 1 RC22AA-1.5/W-01 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Reducer - Coupling 13T-01 13T-02 OBS18-059 R-A R1.20 1RC22AA-1.5/W-02 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-060 R-A R1.20 1RC22AA-1.5/W-03 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-061 R-A R1.20 1RC22AA-1.5/W-04 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-062 R-A R1.20 1 RC22AA-1.5/W-05 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-063 R-A R1.20 1RC22AA-1.5/W-06 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-064 R-A R1.20 1 RC22AA-1.5/W-07 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-065 R-A R1.20 1RC22AA-1.5/W-08 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-066 R-A R1.20 1 RC22AA-1.5/W-09 1 RC22AA-1.5 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-067 9
1/2/2013 Exek,n Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC) e ton ponent lC Jane Numbe Rlf Technical , .:..Coda A tua 'Results
- ..: De cri tiorl ; .. Requests ; Notes Coves am omm[ents R-A R1.20 1 RC22AA-1.5/W-10 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-068 R-A R1.20 1 RC22AA-1.5/W-11.01 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-069 R-A R1.20 1 RC22AA-1.5/W-12.01 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-070 R-A R1.20 1RC22AA-1.5/W-13.02 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-071 R-A R1.20 1 RC22AA-1.5/W-14.02 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-072 R-A R1.20 1 RC22AA-1.5/W-15.02 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-073 R-A R1.20 1RC22AA-1.5/W-16.02 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-074 R-A R1.20 1 RC22AA-1.5/W-17.01 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Coupling 13T-01 13T-02 OBS18-075 R-A R1.20 1RC22AA-1.5/W-18 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-076 R-A R1.20 1RC22AA-1.5/W-19 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Flange 13T-01 13T-02 OBS18-077 R-A R1.20 1RC22AA-1.5/W-20 1RC22AA-1.5 13R-02 89.40 VT-2 NRI Flange - Pipe 13T-01 13T-02 OBS18-078 10
1/2/2013 Exek,n Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC) 1, Section X1 Component ID Line Number Relief Techriical Code Ache ' ` Results Description Requests Notes Coverage E1trs Comments R-A R1.20 1 RC22AA-1.5/W-21 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-079 R-A R1.20 1 RC22AA-1.5/W-22 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-080 R-A R1.20 1 RC22AA-1.5/W-23 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Tee - Pipe 13T-01 13T-02 OBS18-081 R-A R1.20 1 RC22AA-1.5/W-24 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Tee 13T-01 13T-02 OBS18-082 R-A R1.20 1RC22AA-1.5/W-25 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Tee - Reducer 13T-01 13T-02 OBS18-083 R-A R1.20 1 RC22AA-1.5/W-26 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Tee - Pipe 13T-01 13T-02 OBS18-084 R-A R1.20 1RC22AA-1.5/W-27 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-085 R-A R1.20 1 RC22AA-1.5/W-28 1 RC22AA-1.5 13R-02 B9.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-086 R-A R1.20 1 RC22AA-1.5/W-29 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-087 R-A R1.20 1RC22AA-1.5/W-30 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-088 R-A R1.20 1RC22AA-1.5/W-31 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-089 11
1/2/2013 Exek,n _
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RC)
Secti on XI iCorr ponent IE ji inn Number Cade;: - 11 Actual Description Coverage i Exam R-A R1.20 1 RC22AA-1.5/W-32 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-090 R-A R1.20 1 RC22AA-1.5/W-33 1 RC22AA-1.5 13R-02 89.40 VT-2 NRI Pipe - WOL 13T-01 13T-02 OBS18-091 N/A N/A 1 RC28A-3/Zone 1 1 RC28A-3 100 UT NRI Elbow - SOL 100 UT GEOM VE NRI OBS18-145 UT and VE examinations of the weld (1 RC28A-3/J07) and elbow base materials per MRP-146 requirements.
R-A R1.20 1 RC35AA-6/J02 1 RC35AA-6 13R-02 139.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-114 R-A R1.20 1RC35AA-6/J03 1 RC35AA-6 13R-02 139.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-115 R-A R1.11 1 RC35AA-6/J04 1 RC35AA-6 13R-02 139.11 100 UT NRI Pipe - Elbow 13T-01 13T-02 OBS18-116 R-A R1.11 1RC35AA-6/J05 1RC35AA-6 13R-02 B9.11 100 UT NRI Elbow - Pipe 13T-01 13T-02 OBS18-117 N/A N/A 1 RC37A-3/Zone 2 1 RC37A-3 100 UT NRI Elbow - SOL 100 UT NRI VE NRI OBS18-146 UT and VE examinations of the weld (1 RC37A-3/J05) and elbow base materials per MRP - 146 requirements.
12
1/2/2013 Exelon-Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Pressure Vessel (RPV) ci o 7f cor anent IDLit Number Re ief Tee ft le '. Actual,- Results Description hues ,:' Notes oven Ecatt Comment N/A B15.80 1 RC-01-R/RPV BMI 1 RC-01 -R VE NRI RPV Bottom Mounted Instruments OBS18-147 Examination per N-722-1 requirements, see WO 01419629.
N/A B4.20 1 RC-01-R/RPV HEAD 1 RC-01 -R 13R-18 UT RI PEN J-WELD RPV Head Penetrations J-Weld 13R-19 100 PT RI 13R-20 100 PT RI OBS18-148 Examination per N-729-1 requirements of 100% of the RPV Head penetrations. See WDI-PJF-1306901-FSR-002 Revision 0 for reports.
UT and ET examinations of 100% of the RPV Head penetrations and PT of P31 and P43 under WO 01442525.
Penetration PT exams rejected due to rounded indications, reference IR 01413371.
P31 and P43 repaired by metal removal (blending) under WO 01478855.
P43 repaired by blending, re-examined (report 903963-002), and accepted.
P31 repaired by blending, re-examined, (report 903963-001) and accepted on the second attempt (report 903963-003).
See 13R-18 for volumetric examination coverage of individual penetrations.
N/A B4.10 1RC-01-R/RPV HEAD 1RC-01-R 100 VE NRI PEN SURFACE RPV Head Penetrations OBS18-149 Visual Examination per N-729-1 requirements, see WO 01435830-01.
13
1/2/2013 Byron Station Unit 1 B1R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Reactor Coolant System (RY)
Sectio XI = Component to Reef :Technical 1:
pat. t escriptior> Requests Notes,., t Covers Exam ""
EComments R-A R1.11 1RY18A-2/W-05A.01 1 RY18A-2 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-092 R-A R1.11 1RY18A-2/W-06.01 1 RY18A-2 1319-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-093 R-A R1.11 1RY18A-2/W-07 1RY18A-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-094 R-A R1.11 1RY18A-2/W-08 1RY18A-2 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-095 R-A R1 .11 1RY18A-2/W-09 1RY18A-2 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-096 R-A R1.11 1RY18A-2/W-10 1 RY18A-2 1319-02 89.40 VT-2 NRI Pipe - WOL 13T-01 13T-02 OBS18-097 14
1/2/2013 Exekn s Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Steam Generator (SG) section Xt- Component iD Re[e; ehiI;:: Code : ' all Cat.: , escription Reque; Notes 1 Coverage Exam B-D 83.140 1 RC-01-BA/N-1-NIR 1 RC-01-BA UT NRI SG Inlet Nozzle Inner Radius OBS18-130 1 RC-01-BA B-D 83 .140 1 RC-01-BA/N-2-NIR UT NRI SG Outlet Nozzle Inner Radius OBS18-131 C-A C1.20 1 RC-01-BA/SGW-08 1 RC-01-BA 100 UT NRI Steam Drum Head - Steam Drum OBS18-132 B-D 83.140 1 RC-01-BD/N-1-NIR 1 RC-01-BD UT NRI SG Inlet Nozzle Inner Radius OBS18-128 B-D 83.140 1RC-01-BD/N-2-NIR 1 RC-01-BD UT NRI SG Outlet Nozzle Inner Radius OBS18-129 15
1/2/2013 Exekri.
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Safety Injection System (SI)
. r r i% .i cc a ;; Actual ° IRes rlts Requests.; Nate ; Coverage E am R-A R1.11 1SI08GC-1.5/W-01 1 S108GC-1.5 13R-02 89.40 VT-2 NRI Reducer - Coupling 13T-01 13T-02 OBS18-098 R-A R1.11 1 SI08GC-1.5/W-02 1 SI08GC-1.5 13R-02 89.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-099 R-A R1.11 1SI08GC-1.5/W-03 1S108GC-1.5 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-100 R-A R1.11 1SI08GC-1.5/W-04 1SI08GC-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-101 R-A R1.11 1SI08GC-1.5/W-05 1SI08GC-1.5 13R-02 89.40 VT-2 NRI Pipe - Reducer 13T-01 13T-02 OBS18-102 R-A R1.11 1SI08HA-2/W-01 1SI08HA-2 13R-02 89.40 VT-2 NRI Reducer - Pipe 13T-01 13T-02 OBS18-103 R-A R1.11 1SI08HA-2/W-02 1SI08HA-2 13R-02 B9.40 VT-2 NRI Pipe - Flange 13T-01 13T-02 OBS18-104 R-A R1.11 1SI08HA-2/W-03 1S108HA-2 13R-02 89.40 VT-2 NRI Flange - Pipe 13T-01 13T-02 OBS18-105 R-A R1.11 1SI08HA-2/W-04 1S108HA-2 13R-02 89.40 VT-2 NRI Pipe - Reducer 13T-01 13T-02 OBS18-150 R-A R1.11 1SI08JA-1.5/W-06 1SI08JA-1.5 13R-02 89.40 VT-2 NRI Pipe - Valve 13T-01 13T-02 OBS18-151 R-A R1.11 1SI08JA-1.5/W-07 1S108JA-1.5 13R-02 89.40 VT-2 NRI Valve - Pipe 13T-01 13T-02 OBS18-152 16
1/2/2013 Exekn.
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary SYSTEM: Safety Injection System (SI) cat.
comments R-A R1.11 1 SI08JA-1.5/W-08 1 SI08JA-1.5 13R-02 89.40 VT-2 NRI Pipe - Coupling 13T-01 13T-02 OBS18-153 R-A R1.11 1 S108JA-1.5/W-09 1 SI08JA-1.5 13R-02 89.40 VT-2 NRI Coupling - Pipe 13T-01 13T-02 OBS18-154 R-A R1.11 1 SI08JA-1.5/W-10 1 SI08JA-1.5 13R-02 89.40 VT-2 NRI Pipe - Flange 13T-01 13T-02 OBS18-155 R-A R1.11 1SI08JA-1.5/W-11 1SI08JA-1.5 13R-02 89.40 VT-2 NRI Flange - Pipe 13T-01 13T-02 OBS18-156 R-A R1.11 1SI08JA-1.5/W-12 1SI08JA-1.5 13R-02 B9.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-157 R-A R1.11 1S108JA-1.5/W-13 1SI08JA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-158 R-A R1.11 1SI08JA-1.5/W-14 1S108JA-1.5 13R-02 89.40 VT-2 NRI Pipe - Elbow 13T-01 13T-02 OBS18-159 R-A R1.11 1SI08JA-1.5/W-15 1SI08JA-1.5 13R-02 89.40 VT-2 NRI Elbow - Pipe 13T-01 13T-02 OBS18-160 NA ECCS 1SI09BA-10/J09 1SI09BA-10 100 UT NRI Elbow - Pipe OBS18-126 Examination for IN 79-19 requirements.
NA ECCS 1SI09BA-10/J11 1S109BA-10 100 UT NRI Elbow - Pipe OBS18-127 Examination for IN 79-19 requirements.
17
1/2/2013 Exekn.
Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary (Preservice Inspections)
SYSTEM: Reactor Coolant System (RC)
Section Xi Component 10 ;tine Number ' fRelief Technical A.Code: Required !Actual Results Cat. item looscription. (Requests Notes Coverag Exam !Exam Corm R-A R1.20 1 RC22AC-1.5/W-16.01 1 RC22AC-1.5 13R-02 B9.40 100 SURF PT NRI Pipe - Valve 13T-01 VT-2 VT-2 NRI 13T-02 Baseline exams of socket weld W1 with valve 1 RC8042C replacement. See WO 01549925 for reports.
R-A R1.20 1 RC22AC-1.5/W-17.01 1 RC22AC-1.5 13R-02 B9.40 100 SURF PT NRI 13T-01 Valve - Pipe VT-2 VT-2 NRI 13T-02 Baseline exams of replacement socket weld W2 with valve 1 RC8042C. See WO 01549925 for reports.
R-A R1.20 1 RC22AC-1.5/W-18.01 1 RC22AC-1.5 13R-02 B9.40 100 SURF PT NRI Pipe - Elbow 13T-01 VT-2 VT-2 NRI 13T-02 Baseline exams of socket weld W3 with valve 1 RC8042C replacement. See WO 01549925 for reports.
1 1/2/2013
1/2/2013 Exeknt Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary (Preservice Inspections)
SYSTEM: Safety Injection System (SI)
Section Xt"`" Component I to t rnt e _ tReli ITschnicaf Code [Required'.- Actual C Description Requests Notes Coverage .Exerts; Exam Comments 77 R-A R1.20 1 S I08B-4/C03.01 1 SI08B-4 13R-02 C5.21 100 VOL-E UT NRI Pipe - Pipe 13T-01 13T-02 Baseline exam of replacement weld W8. SI modification per WO 01430317.
R-A R1.20 1 SI08B-4/C04.01 1 S108B-4 13R-02 C5.21 100 VOL-E UT GEOM Pipe - Tee 13T-01 13T-02 Baseline exam of replacement weld W7. SI modification per WO 01430317. Root Geometry 360° intermittent.
R-A R1.20 1SI08CA-4/C01A 1SI08CA-4 13R-02 C5.21 100 VOL-E UT NRI Tee - Pipe 13T-01 13T-02 Baseline exam of new weld W6. SI modification per WO 01430317.
R-A R1.20 1SI08CA-4/C01B 1SI08CA-4 13R-02 C5.21 100 VOL-E UT NRI Pipe - Elbow 13T-01 13T-02 Baseline exam of new weld W5. SI modification per WO#01430317.
R-A R1.20 1S108CA-4/C01C 1SI08CA-4 13R-02 C5.21 100 VOL-E UT NRI Elbow - Elbow 13T-01 13T-02 Baseline exam of new weld W4. SI modification per WO#01430317.
R-A R1.20 1 S108CA-4/C01 D 1 SI08CA-4 13R-02 C5.21 50 VOL-E UT NRI Elbow - Valve 13R-22 13T-01 13T-02 Baseline exam of new weld W3. SI modification per WO 01430317. UT unable to achieve coverage with elbow-to-valve configuration.
R-A R1.20 1SI08CA-4/C02.01 1S108CA-4 13R-02 C5.21 50 VOL-E UT NRI Valve - Pipe 13R-22 13T-01 13T-02 Baseline exam of replacement weld W2. SI modification per WO 01430317. UT unable to achieve coverage with valve-to-pipe configuration.
R-A R1.20 1SI08CA-4/C03.01 1S108CA-4 13R-02 C5.21 100 VOL-E UT NRI Pipe - Pipe 13T-01 13T-02 Baseline exam of replacement weld W1. S1 modification per WO#01430317.
R-A R1.20 1SI08CB-4/COA 1SI08CB-4 13R-02 C5.21 100 VOL-E UT GEOM Tee - Pipe 13T-01 13T-02 Baseline exam of new weld W9. SI modification per WO#01430317.
Root Geometry recorded.
R-A 1SI08CB-4 R1.20 1SIO8CB-4/COB 13R-02 C5.21 100 VOL-E UT GEOM Pipe - Elbow 13T-01 13T-02 Baseline exam of new weld W10. SI modification per WO#01430317.
Root Geometry recorded.
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Weld / Component Outage Summary (Preservice Inspections)
SYSTEM: Safety Injection System (SI)
Seaton lComponentlo Li ne Number > - <'1RCtief Tech nical code Required Actual a Results ft Cat. Itemm . i0escription !Requests ;Notes ;coverage,t~catrt: Eacarn orrmments R-A R1.20 1 SI08CB-4/COC 1 SI08CB-4 13R-02 C5.21 50 VOL-E UT GEOM Elbow - Valve 13R-22 13T-01 13T-02 Baseline exam of new weld W11. SI modification per WO 01430317. UT unable to achieve coverage with elbow-to-valve configuration.
Root Geometry 360° intermittent.
R-A R1.20 1 SI08CB-4/COD 1SI08CB-4 13R-02 C5.21 50 VOL-E UT GEOM Valve - Pipe 13R-22 13T-01 13T-02 Baseline exam of new weld W12. SI modification per WO 01430317. UT unable to achieve coverage with valve-to-pipe configuration.
Root Geometry 360° intermittent.
R-A R1.20 1 SI08CB-4/COE 1 SI08CB-4 13R-02 C5.21 50 VOL-E UT NRI Pipe - Valve 13R-22 13T-01 13T-02 Baseline exam of new weld W13. SI modification per WO 01430317. UT unable to achieve coverage with pipe-to-valve configuration.
R-A R1.11 1SI08JB-1.5/W-27. 01 1SI08JB - 1.5 13R-02 69.40 100 SURF PT NRI Pipe - Elbow 13T-01 VT-2 VT-2 NRI 13T-02 Baseline exams of replacement socket weld W6 removed for interference with LSIV work. See WO 01344060 for reports.
3 1/2/2013
1/2/2013 Exekn _
Byron Station Unit 1 B1 R18 ISI Outage Report Detailed Inservice Inspection Bolts, Pumps, and Valves Listing (PSI)
SYSTEM: Reactor Coolant System (RC)
Relief. ;Technla ^:, Actual Requests ;Notes jExarrl B-G-1 B6.230 1 RC8002B/NBW 1-24 VT-1 NRI Valve Nuts, Bushings, and Washers Baseline examination of replacement nuts and washers under WO 01560319.
B-G-1 B6.210 1RC8002B/STUDS 1-24 PT NRI Valve Studs 1-24 Baseline examination of replacement stud #23. See WO 01344060. Vendor fabrication examination used in lieu of site baseline examination.
1 1/2/2013
1/2/2013 Exekn Byron Station Unit 1 B1 R18 ISI Outage Report Detailed Inservice Inspection Bolts, Pumps, and Valves Listing (PSI)
SYSTEM: Reactor Coolant System (RY)
S tion Xt Component ID ER r = Te chn ic a l Actual C It Description ; Requester ?Notes Exam B-G-2 B7.50 1 RY03BA-6/FLG 1-12 PFB-RY VT-1 NRI Piping Flange Bolting Baseline exam for 1 RY801 OA replacement under WO#01468290.
B-G-2 B7.50 1RY03BB-6/FLG 1-12 PFB-RY VT-1 NRI Piping Flange Bolting Baseline exam for 1 RY801 OB replacement under WO#01287364.
2 1/2/2013
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Containment Spray System (CS)
Section r x#; 7c6i^p^^ Resu Ca Item Comments C-H C7. 10 1-CS-2-1 VT-2 NRI VT-2 NRI C-H C7.10 1-CS-2-2 VT-2 NRI VT-2 NRI C-H C7. 10 1-CS-2-3 VT-2 NRI VT-2 NRI C-H C7.10 1-CS-2-4 VT-2 NRI VT-2 NRI C-H C7. 10 1-CS-2-5 VT-2 NRI VT-2 NRI 1 1/2/2013
1/212013 Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Chemical & Volume Control System (CV) al .., Re su lt s R Technical Ac tu sewn I Cnix pe ent Ia s
Requests: t Notes,,,, 11 Exam C^ Item, Comments VT-2 NRI C-H C7.10 1-CV-2-1 VT-2 NRI VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-10 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-2 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-3 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-4 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-5 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-6 VT-2 NRI C-H C7.10 1-CV-2-7 VT-2 NRI VT-2 NRI C-H C7.10 1-CV-2-8 VT-2 NRI C-H C7.10 1-CV-2-9 2 1/2/2013
1/2/2013 Exeln _
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Fuel Pool Cooling System (FC) f', Secttan I :;,:;Component 10 ' echnical Actual N tea Exam cat. item Comments VT-2 NRI C-H C7.10 1-FC-2-1 VT-2 NRI 3 1/2/2013
1/2/2013 Exekn _
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Feedwater System (FW)
'ecl ni al Actual <: Results Notes Exam I eat.Item 1-FW-2-1 VT-2 NRI C-H C7. 10 C7.10 1-FW-2-2 VT-2 NRI C-H 4 1/2/2013
1/2/2013 Exelon..
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Main Steam System (MS)
Sect io n t I om onen ID Ret st : Technical :, ft,t ual ° : Results I equests.., .Notes ; : Exam ten Comments VT-2 NRI C-H C7. 10 1-MS-2-1 VT-2 NRI C-H C7. 10 1-MS-2-2 5 1/2/2013
1/2/2013 Exek,n.
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Off Gas System (OG)
C-H C7.10 1-OG-2-1 VT-2 NRI 6 1/2/2013
1/2/2013 Exe1^n_
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Process Sampling System (PS) sect rcm pcrsent ltd Technic A teal R ulte a > Item ' : f Reques ts^t
. .: ,.. Each Comments C-H C7. 10 1-PS-2-3 VT-2 NRI VT-2 NRI C-H C7.10 1-PS-2-4 VT-2 NRI VT-2 NRI C-H C7.10 1-PS-2-5 VT-2 NRI VT-2 NRI C-H C7. 10 1-PS-2-6 VT-2 NRI VT-2 NRI 7 1/2/2013
1/2/2013 Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Reactor Coolant System (RC)
Section-Xi component lD Actual Results Exam Gat. , ittt comments B-P 815 .10 1-RC-1-1 VT-2 NRI C-H C7. 10 1-RC-2-1 VT-2 NRI 8 1/2/2013
1/2/2013 Exeknt Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Residual Heat Removal System (RH)
Section Xt -: t Component ID i , Relief Actual Cat. Item E Requests Exam Comments C-H C7.10 1-RH-2-1 VT-2 NRI VT-2 NRI C-H C7. 10 1-RH-2-2 VT-2 NRI VT-2 NRI C-H C7. 10 1-RH-2-3 VT-2 NRI VT-2 NRI C-H C7. 10 1-RH-2-4 VT-2 NRI C-H C7.10 1-RH-2-5 VT-2 NRI C-H C7. 10 1-RH-2-6 VT-2 NRI VT-2 NRI 9 1/2/2013
1/2/2013 Pressure Test Outage Summary SYSTEM: Safety Injection System (SI)
Co ponent ID; >:: Rel1 :. T I nlcal ' ^ t : l . POW" do au^ Ndtes,"'-^J, Exam a r Comments VT-2 NRI C-H C7.10 1-SI-2-1 VT-2 NRI VT-2 NRI C-H C7.10 1-SI-2-2 VT-2 NRI VT-2 NRI C-H C7. 10 1-SI-2-3 VT-2 NRI VT-2 NRI C-H C7.10 1-SI-2-5 VT-2 NRI C-H C7. 10 1-SI-2-6 VT-2 NRI 1-SI-2-7 VT-2 NRI C-H C7.10 VT-2 NRI VT-2 NRI C-H C7. 10 1-SI-2-8 10 1/2/2013
1/2/2013 Exekn.
Byron Station Unit 1 B1 R18 ISI Outage Report Pressure Test Outage Summary SYSTEM: Essential Service Water System (SX)
ResultsSection I : Component 10 Actual':° Exam P menu C-H C7. 10 1-SX-2-1 VT-2 NRI C-H C7. 10 1-SX-2-2 VT-2 NRI 11 1/2/2013
1/2/2013 Exekn _
Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Auxiliary Feedwater System (AF)
Actual Exam Description F-A F1.20 1AF02DA-4/1AF06046G 1 AF02DA-4 VT-3 NRI Guide F-A F1.20 1AF02EB-4/1AF04077R 1AF02EB-4 VT-3 NRI Rigid F-A F1.20 1 FW87BA-3/1 FW 14001 R 1 FW87BA-3 VT-3 NRI Rigid 1
1/2/2013 Exeknt Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Chemical & Volume Control System (CV)
Seetii F ^ : lComponent ID Bel ie . Actual Results Description Requests Exam t Comments F-A F1.40 1 CV-01-PA/L1 1 CV-01-PA VT-3 NRI CV PUMP A LUG 1 F-A F1.40 1CV-01-PA/L2 1 CV-01 -PA VT-3 NRI CV PUMP A LUG 2 F-A F1.40 1 CV-01-PA/L3 1 CV-01-PA VT-3 NRI CV PUMP A LUG 3 F-A F1.40 1CV-01-PA/L4 1CV-01-PA VT-3 NRI CV PUMP A LUG 4 F-A F1.20 1 CV05CB-6/1 CV08005X 1 CV05CB-6 VT-3 NRI SEISMIC F-A F1.20 1CV08BA-4/1CV01004X 1CV08BA-4 VT-3 NRI SEISMIC F-A F1.10 1 CVA3B-2/1 CV25035X 1 CVA3B-2 VT-3 NRI SEISMIC F-A F1.10 1 CVA5AA-2/1 CV 15022X 1 CVA5AA-2 VT-3 NRI SEISMIC F-A F1.10 1 CVA7AA-2/1 CV25017X 1 CVA7AA-2 VT-3 NRI SEISMIC F-A F1.10 1CVB7A-3/1CV06009C 1CVB7A-3 VT-3 NRI CONSTANT 2
1/2/2013 Exekn Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Main Steam System (MS) ec# c xE Component ID Actual ;., Results cat:. Item ; Descrlp ion Exam I Comments F-A F1.20 1MS07AA-28/1MS01205X 1 MS07AA-28 VT-3 NRI SEISMIC 3
1/2/2013 Exek n Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Reactor Coolant System (RC) tom. Numbw ,:, fets ,Technical ,. ,Actual S cti xi Gc>ir tcsnsrtt Exam I,Req ests: tote Cat. Item : Description Comments 1 RC-01-PC VT-3 NRI F-A F1.40 1 RC-01-PC/L1 RC PUMP C SUPPORT 1 RC-01 -PC VT-3 NRI F-A F1.40 1RC-01-PC/L3 RC PUMP C SUPPORT 1 RC21 AA-8 VT-3 NRI F-A F1.10 1 RC21 AA-8/1 RC01004V VARIABLE 1 RC24AA-4 VT-3 NRI F-A F1.10 1 RC24AA-4/1 RY06017X SEISMIC 4
1/2/2013 Exekn..
Byron Station Unit 1 B1R18 ISI Outage Report Component Support Outage Summary SYSTEM: Residual Heat Removal System (RH)
Une Number Relief `echnical component ID eq Description.:;
1 RHO1 AA-12 VT-3 NRI F-A F1.10 1 RH01 AA-12/1 RH02065X SEISMIC 5
1/2/2013
&elej n Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Safety Injection System (SI)
Felt :_,.(...-
Une Ni mber nnlc tua :. F ea uit , :l s ct On X j omponent It) rce+quests note .,1 scam Cat. Ite . ;Description C! '+nL+a VT-3 NRI F-A F1.40 1 RHO1 SA/1 SI06AO01 X 1RH01SA SEISMIC 1RH01SA VT-3 NRI F-A F1.40 1 RHO1 SA/1 SI06A002R RIGID VT-3 NRI F-A F1.20 1 S I02BA-6/1 S 115002X 1 S102BA-6 SEISMIC 1 SI02BB-6 VT-3 NRI F-A F1.20 1SI02BB-6/15118062X SEISMIC 1 S10413-12 VT-3 NRI F-A F1.20 1 SI04B-12/1 RHO2100X SEISMIC 1 S 104D-8 VT-3 NRI F-A F1.10 1 SI04D-8/1 RH02021 X SEISMIC 1 S 104D-8 VT-3 NRI F-A F1.10 1S104D-8/1RH02023X SEISMIC 1 SI05AA-8 VT-3 NRI F-A F1.20 1 SI05AA-8/15118082X SEISMIC 1 SI05CA-8 VT-3 NRI F-A F1.20 1 SI05CA-8/l 5102002V VARIABLE 1 SI05CA-8 VT-3 NRI F-A F1.20 1 SI05CA-8/l SI03008C CONSTANT 1 SI05DA-6 VT-3 NRI F-A F1.10 1SI05DA-6/15101030X SEISMIC 1 S106BB-24 VT-3 NRI F-A F1.20 1 SI06BB-24/1 SI06150X SEISMIC 1 SI08FA-3 VT-3 NRI F-A F1.10 1 SI08FA-3/1 5121 01 8X SEISMIC 1 SI08FA-3 VT-3 NRI F-A F1.10 1 SI08FA-3/15123001 X SEISMIC 1SI08GB-1-1/2 VT-3 NRI F-A F1.10 1SI08GB-1-1/2/1SI25026X SEISMIC 1SI08GB-1-1/2 VT-3 NRI F-A F1.10 1SI08GB-1-1/P/1SI25027X SEISMIC 1SI08GB-1-1/2 VT-3 NRI F-A F1.10 1SI08GB-1-1/2/b5125028X SEISMIC 1SI08JA-1-1/2 VT-3 NRI F-A F1.10 1SI08JA-1-1/2115125025X SEISMIC 6
1/2/2013 E
Byron Station Unit 1 B1R18 ISI Outage Report Component Support Outage Summary SYSTEM: Safety Injection System (SI)
Component ID ,Relief ' echnical Secti AEI~.
Request ' , N tt >
Cat,Item ; ; Descripti Commenis 1 SIA4A-8 VT-3 NRI F-A F1.20 1 SIA4A-8/1 RH02106X SEISMIC 7
1/2/2013 Exekn Byron Station Unit 1 B1 R18 ISI Outage Report Component Support Outage Summary SYSTEM: Essential Service Water System (SX)
Section Xt. lComponent I D Line Its Relief % ,Technic .] Actual Cat Item Description eques s :^ Notes Exam Co menu ...
F-A F1.20 1 SX06BB-16/1 PC-7A 1 SX06BB-16 VT-3 NRI ANCHOR F-A F1.20 1 SX07FA-16/1 PC-14A 1 SX07FA-16 VT-3 NRI ANCHOR F-A F1.20 1 SX08AD-10/1 SX07013A 1 SX08AD-10 VT-3 NRI ANCHOR F-A F1.20 1 SX08BA-10/1 SX06032X 1 SX08BA-10 VT-3 NRI SEISMIC 8
1/2/2013 Exekn.
Byron Station Unit 1 Byron Station Outage B1 R18 Snubber Outage Summary (Page 1 of 5)
SYSTEM: Chemical & Volume Control System (CV)
Section XI Component ID Gat^ Item, Des rlptton C omments F-A F1.20 1 CV05CB-6/1 CV08021 S 1 CV05CB-6 VT-3 NRI SNUBBER SR FT PASS NA NA 1 CV1 5AD-3/4/1 CV30002S 1CV15AD-3/4 VT-3 NRI SNUBBER SR FT PASS F-A F1.10 1 CVA3B-2/1 CV09050S 1 CVA3B-2 VT-3 NRI SNUBBER SR FT PASS Note: Section XI Category numbers N/A-ed are exempt from IWF-1220 and IWF-2500 tables 1
1/2/2013 Exen. l Byron Station Unit 1 Byron Station Outage B1 R18 Snubber Outage Summary (Page 2 of 5)
SYSTEM: Main Steam System (MS)
Section XI [Component ID iLine Number Relief : Technical 1 Requests:: Notes Cat. Item . ! scriptio Ct311' ments 1 MS07BA-28/1 MS01074-S1 1 MS07BA-28 VT-3 NRI NA SNUB SNUBBER SR FT PASS 1 MS07BA-28 VT-3 NRI NA SNUB 1 MS07BA-28/1 MS01074-S2 SR FT PASS SNUBBER Note: Section XI Category numbers N/A-ed are exempt from IWF-1220 and IWF-2500 tables 2
1/2/2013 Exeknt Byron Station Unit 1 Byron Station Outage B1R18 Snubber Outage Summary (Page 3 of 5)
SYSTEM: Reactor Coolant System (RC)
!Line Number ; Relief Technical Section XI component ID Notes Requests,:
Cat. Itecr, iDescription
- comments VT-3 NRI F-A F1.40 1 RC01 BA-1 A/1 RC06S 1 RC01 BA-1 A SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BA-1 A/1 RC07S 1 RC01 BA-1 A SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BB-1 B/1 RC08S 1 RC01 BB-1 B SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BB-1 B/1 RC09S 1 RC01 BB-1 B SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BC-1 C/1 RC10S 1 RC01 BC-1 C SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BC-1 C/1 RC11 S 1 RC01 BC-1 C SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BD-1 D/1 RC12S 1 RC01 BD-1 D SR SNUBBER VT-3 NRI F-A F1.40 1 RC01 BD-1 D/1 RC13S 1 RC01 BD-1 D SR FT PASS SNUBBER VT-3 NRI NA NA 1 RC08AC-3/4/1 RC1 8020S 1 RC08AC-3/4 SR FT PASS SNUBBER VT-3 NRI F-A F1.10 1 RC14AB -2/l CV15014S 1 RC1 4AB-2 SR FT PASS SNUBBER VT-3 NRI NA SNUB 1 RC1 4AB-2/1 CV1 5041 -S1 1RC14AB-2 SR FT PASS SNUBBER VT-3 NRI NA SNUB 1RC14AB-2/1CV15041-52 1RC14AB-2 SR FT PASS SNUBBER VT-3 NRI F-A F1.10 1 RC14AD-2/1 CV25001 S 1RC14AD-2 SR FT PASS SNUBBER VT-3 NRI NA NA 1 RC20AD-3/4/1 RC19024S 1 RC20AD-3/4 SR FT PASS SNUBBER VT-3 NRI F-A F1.10 1 RC22AB-1.5/1 RC1 7015S 1 RC22AB-1.5 SR FT PASS SNUBBER VT-3 NRI F-A F1.10 1 RC24AA-4/1 RY06055S 1 RC24AA-4 SR FT PASS SNUBBER 0 and IWF-2500 tables Note
- Section XI Category numbers N/A-ed are exempt from IWF-122 3
1/2/2013 Exek,n..
Byron Station Unit 1 Byron Station Outage B1 R18 Snubber Outage Summary (Page 4 of 5)
SYSTEM: Reactor Coolant System (RY)
`Section XI Component in Cat. Iteern rc Comments 1 RY01 B-6 VT-3 NRI F-A F1.10 1 RY01 B-6/1 RY06076S SR FT PASS SNUBBER 1 RY01 B-6 DBL VT-3 NRI NA SNUB 1 RY01 B-6/1 RY06118-S1 SR FT PASS SNUBBER 1 RY01 B-6 DBL VT-3 NRI NA SNUB 1 RY01 B-6/1 RY06118-S2 SR FT PASS SNUBBER 1 RY02B-3 VT-3 NRI F-A F1.10 1 RY02B-3/1 RY09077S SR FT PASS SNUBBER 1 RY06A-3 VT-3 NRI F-A F1.10 1 RY06A-3/1 RY09101 S SR FT PASS SNUBBER Note: Section XI Category numbers N/A-ed are exempt from IWF-1220 and IWF-2500 tables 4
1/2/2013 Exekn _
Byron Station Unit 1 Byron Station Outage B1 R18 Snubber Outage Summary (Page 5 of 5)
SYSTEM: Safety Injection System (SI)
Section XI ° 1IComponent ID Relief Technical Requests: Notes C t.:> item' ` JDescription; Comments `,
NA SNUB 1 SI09BA-10/1 S101 004S 1 SI09BA-10 VT-3 NRI SNUBBER SR FT PASS Note: Section XI Category numbers N/A-ed are exempt from IWF-1220 and IWF-2500 tables 5