NL-08-1166, Inservice Inspection Summary Report, Refueling 14, Interval 3, Period 1, Outage 1

From kanterella
(Redirected from ML082490465)
Jump to navigation Jump to search
Inservice Inspection Summary Report, Refueling 14, Interval 3, Period 1, Outage 1
ML082490465
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 07/23/2008
From: Ajluni M
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-08-1166
Download: ML082490465 (173)


Text

Southern Nuclear Operating Company, Inc.

Post Office Box 1295 Birmingham, Alabama 35201-1295 Tel 205.992.5000 SOUTHERN COMPANY July 23, 2008 Energy to Serve Your World" Docket No.: 50-424 NL-08-1166 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant - Unit 1 Inservice Inspection Summary Report Ladies and Gentlemen:

Southern Nuclear Operating Company,(SNC) submits herewith the Vogtle Electric Generating Plant Unit 1, Interval 3, Period 1, Outage 1 (1 R1 4) Inservice Inspection (ISI) Summary Report (Enclosure). This report describes and summarizes the ISI activities performed in the third ISI interval during the spring 2008 maintenance/refueling outage. Paragraph IWA-6230 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, 2001 Edition with the 2003 Addenda (Code) requires submittal of the enclosed report.

In addition to examinations credited for the third ISI interval, this report also includes those examinations, tests and Code-applicable repair and/or replacement activities performed in 1 R1 4, which are credited to complete the second ISI interval. Even though the second ISI interval ended May 30, 2007, the Code has provisions for extending, by as much as one year, that portion of an inspection interval, described as an inspection period, to enable an inspection to coincide with a plant outage. 1R14 occurred in March and April of 2008 which is within one year of the end of the second ISI interval. A separate form NIS-1 is included in the report which addresses applicable information to the specific ISI intervals.

The supporting ISI documentation, e.g., examination plans and schedules, examination results and reports, examination methods and procedures, evaluation results, and corrective action and repairs, is available for review upon request at Vogtle Electric Generating Plant.

XW67

U. S. Nuclear Regulatory Commission NL-08-1166 Page 2 This letter contains no NRC commitments. If you have any questions, please advise.

Sincerely, M. J. Ajuni Manager - Nuclear Licensing MJA/DRG/daj

Enclosure:

Vogtle Electric Generating Plant - Unit 1 Inservice Inspection Summary Report Refueling Outage (1 R14) cc: Southern Nuclear Operating Company Mr. J. T. Gasser, Executive Vice President Mr. T. E. Tynan, Vice President - Vogtle Mr. D. H. Jones, Vice President - Engineering RType: CVC7000 U. S. Nuclear Regulatory Commission Mr. L. A. Reyes, Regional Administrator Mr. R. A. Jervey, NRR Project Manager - Vogtle Mr. G. J. McCoy, Senior Resident Inspector - Vogtle

Vogtle Electric Generating Plant - Unit 1 Enclosure Inservice Inspection Summary Report

SOUTHERNAM SOUTHERNAEN.

COMPANY COMPANY Energy to Serve Your World* Energy to Serve Your World' INSERVICE INSPECTION REPORT REFUELING 14 INTERVAL 3 PERIOD I, O UTAG E "I Vogtle Electric Generating Plant UniftI (7821 River Road, P.0. Box, 1600, Waynesboro, Georgia 30830)

Soluthlern Nuclelar Operating Corn; )any 40 In~verness Parkway Birlmingham, Alabama 35242 COMMERCIAL OPERATION DATE:- May 31, 1987 DOCUMENT COMPLETION DATE: June 2008

VOGTLE ELECTRIC GENERATING (VEGP)

PLANT 1R14 FINAL REPORT TABLE OF CONTENTS SECTION TAB VOLUME I (OWNER'S REPORT)

  • INTRODUCTION AND ABBREVIATIONS A

" ASME FORM NIS-1 AND ABSTRACT B

" INSERVICE INSPECTION (OWNER'S REPORT) EXAMINATION

SUMMARY

CLASS 1 AND 2 WELDS AND SUPPORT EXAMINATIONS C SYSTEM PRESSURE TESTS D REPORTABLE INDICATION

SUMMARY

E

  • OWNER'S REPORT FOR REPAIRS AND REPLACEMENTS (FORM NIS-2) F VOLUME 2 (ISI EXAMINATION DATA)

" EXAMINATION PROGRAM PLAN (TOTAL SCOPE

SUMMARY

) G

  • ISI EXAMINATION DATA H VOLUME 3 (CERTIFICATIONS)
  • PERSONNEL CERTIFICATIONS I
  • EXAMINATION PROCEDURES (LISTING) J

" EQUIPMENT CERTIFICATIONS & CALIBRATION BLOCKS (LISTING) K VOLUME 4 (FLOW ACCELERATED CORROSION - FAC)

" FAC EXAMINATION

SUMMARY

L

  • FAC EXAMINATION DATA M VOLUME 1 CONTAINS THE INFORMATION TO MEET THE REQUIREMENTS OF ASME CODE 2001 EDITION w 2003 ADDENDA, SECTION XI, SUBSECTION IWA-6230 FOR SUBMITTAL OF A

SUMMARY

REPORT TO THE NRC FOLLOWING EACH REFUELING OUTAGE.

VOLUMES 2 AND 3 CONTAIN THE SUPPORTING DOCUMENTATION FOR THE EXAMINATIONS PERFORMED (RETAINED ON SITE BY VEGP)

VOLUME 4 CONTAINS DOCUMENTATION OF THE FLOW ACCELERATED CORROSION (FAC) INSPECTIONS PERFORMED (RETAINED ON SITE BY VEGP)

SOUTHERN Z** SOUTHERN Euk COMPANY COMPANY Energy to Serve Your World' Energy to Serve Your World*

SOUTHERN NUCLEAR§ OPERAVTING C OMPANY MA TERIALS A.ND INSPECTION SER VICES INSERVICE INSPECTIONS PLANT VOGTLE UNIT 1 REFUELING OUTAGE 144 SPRING 2008 Volumes R Owner's Rep'ort,

TAB A INTRODUCTION & ABBREVIATIONS

INTRODUCTION This report documents the examinations and tests performed at Vogtle Electric Generating Plant, Unit 1 (VEGP-1) between October 27, 2006 (date of last examination performed during the thirteenth (13 th) maintenance/refueling outage, 1R13) and April 24, 2008 (end of the fourteenth ( 14th) maintenance/refueling outage, 1R14) to meet the requirements of Article IWA-6000 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, 2001 Edition with 2003 Addenda (Code).

This report also addresses Code-applicable repairs and/or replacements, which were documented since the last maintenance/refueling outage at VEGP-1 through the completion of the fourteenth maintenance/refueling outage in April 24, 2008. The Owner's Reports for Repairs and Replacements (Form NIS-2) are included herein.

In addition to examinations credited for the third inspection interval, this report also includes those examinations, tests and Code-applicable repair and/or replacement activities, which are credited to the second inspection interval. Even though the second inspection interval ended May 30, 2007, the Code has provisions for performing examinations within one year after the end of the inspection interval to coincide with a plant outage. The 1R14 outage occurred in March and April of 2008 which is within the one year. A separate form NIS-1 is included which addresses applicable information to the specific intervals. The specific exams and NIS-2 forms are itemized and identified in the pressure tests and NIS-2 summary sections.

This report does not include Steam Generator Tube Inspections which are required per VEGP Technical' Specification 5.6.10. This information will be provided in a separate report one hundred eighty (180) days after the initial entry into MODE 4 following completion of an inspection performed in accordance with Technical Specification 5.5.9. The ASME Code requirements were met and the separate report will provide the details for these examinations.

This report also does not address pressurizer weld overlay application and post overlay examinations.

The results of the overlay project have been submitted under a separate cover letter (NL-08-0667 dated May 2, 2008).

1-1

LIST OF ABBREVIATIONS ACC Acceptable AD Anchor/Darling AFW Auxiliary Feedwater System Al GPC Action Item (followed by unique no. denoting Action Item number)

ANII Authorized Nuclear Inservice Inspector ASME American Society of Mechanical Engineers ASNT American Society for Nondestructive Testing ASTM American Society for Testing and Materials BC Branch Connection CCSS Centrifugally Cast Stainless Steel CCW Component Cooling Water CE Combustion Engineering CH Closure Head CR Condition Report CS Containment Spray CVCS Chemical and Volume Control System DS Downstream ET Eddy Current Examination EVAL Evaluation FAC Flow-Accelerated Corrosion (may also be referred to as "erosion/corrosion")

FB Flange Bolting FNF FAC Notification Report FW Feedwater System FSAR VEGP Final Safety Analysis Report (includes updates thereto)

GEO Geometric Indications GPC Georgia Power Company HHSI High Head Safety Injection HL Hanger Lug HX Heat Exchanger HYD Hydraulic Snubber IEN NRC Information Notice (may also be shown as "IN" followed by unique no. denoting notice number)

IND Indication INF Indication Notification Form ISI Inservice Inspection IST Inservice Testing ITS VEGP Improved Technical Specification ID Inside Diameter IR Inside Radius LB Large Bore LD Longitudinal Seam Weld Extending Downstream LD-I Longitudinal Seam Weld Downstream Inside Radius of Elbow LD-O Longitudinal Seam Weld Downstream Outside Radius of Elbow LMT Lambert, MacGill and Thomas LU Longitudinal Seam Weld Extending Upstream LU-I Longitudinal Seam Weld Upstream Inside Radius of Elbow LU-O Longitudinal Seam Weld Upstream Outside Radius of Elbow MECH Mechanical Snubber MS Main Steam System MT Magnetic Particle Examination NCI Nonconformance Item NDE Nondestructive Examination 1-2

LIST OF ABBREVIATIONS - (continued)

NI No Indication NRC United States Nuclear Regulatory Commission NRC-B NRC Bulletin (followed by unique no. denoting Bulletin number)

NRI No Recordable Indication NSCW Nuclear Service Cooling Water System OR Outside Radius PL Pipe Lug PM Paul-Munroe ENERTECH PR Pipe Restraint PROF Profile PS Pipe Support PSA Pacific Scientific PSI Preservice Inspection PT Liquid Penetrant Examination RCS Reactor Coolant System RCP Reactor Coolant Pump RHR Residual Heat Removal System RI Recordable Indication RLW Refracted Longitudinal Wave RL Restraint Lug RPV Reactor Pressure Vessel RR Relief Request (followed by unique no. denoting relief request number)

RWST Refueling Water Storage Tank SAT Satisfactory Examination Results SB Small Bore SCS Southern Company Services SI Safety Injection System SNC Southern Nuclear Operating Company SUP Supplemental Data T&C Thickness and Contour TDAFW Turbine Driven Auxiliary Feedwater (Pump)

UNSAT Unsatisfactory Examination Results US Upstream UT Ultrasonic Examination VEGP Vogtle Electric Generating Plant (common unless followed by "-1" or "-2" to designate a specific plant unit)

VT Visual Examination W Westinghouse 1-3

TAB B ASME FORM NIS-1 AND ABSTRACT

  • Form NIS-1
  • Abstract

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 3"3 Interval

1. Owner: Georgia Power Company, 241 Ralph McGill Blvd., N. E.

P. 0. Box 4545, Atlanta, Georgia 30308-3374

2. Plant: Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830
3. Plant Unit: One
4. Owner Certification of Authorization: N/A
5. Commercial Service Date: 05/31/87
6. National Board Number for Unit: N/A
7. Components Inspected:

Component or Manufacturer or Manufacturer or Installer State or National Board Appurtenance Installer and Serial Number Province Number Address Number Reactor Combustion Eng. 7372 N/A 22004 Pressure Inc.,

Vessel Chattanooga, TN Steam Westinghouse GAGT 1881, GAGT 1882, N/A NA Generators 1 Elec., GAGT 1883, GAGT 1884, thru 4 Pensacola, FL Residual Heat Ingersoll-Rand 087728 N/A 510 Removal Co., Phillipsburg, Pump, Train NJ "A"

Centrifugal Pacific Pumps 52233 N/A 410 Charging Division, Pump, Train Huntington Park, "A" CA Selected Pullman Power System Numbers 1201, N/A N/A Piping, Products, 1204, 1205, 1208.

Components, Williamsport, PA and Supports 2-1

FORM NIS-1 (Back) 3'd Interval

8. Examination Dates: October 27, 2006 to April 22. 2008
9. Inspection Period Identification: First Period
10. Inspection interval Identification: Third Inspection Interval
11. Applicable Edition of Section XI 2001 Addenda 2003
12. Date/Revision of Inspection Plan: July 21. 2008 / Version 2.0
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)
14. Abstract of Results of Examinations and Tests. (See Abstract)
15. Abstract of Corrective Measures. (See Abstract)

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Pian as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section Xl.

Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date: 2-3 J-ý 20 08 Signed: Southern Nuclear By:

l ~Operatingq Company, Inc.

for a a Georgia Power Company Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler Insoection and Insurance Company of Connecticut of Hartford, CT have inspected the components described in this Owner's Report during the period October 27, 2006 to April 24. 2008, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commission: 6-A .

Ingpector's ignature National Board, State, Province, and Endorsements Date: fT7LY , ,2 20 cir 2-2

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 2 nd Interval Credit

1. Owner: Georgia Power Company, 241 Ralph McGill Blvd., N. E.

P. 0. Box 4545, Atlanta, Georgia 30308-3374

2. Plant: Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830
3. Plant Unit: One
4. Owner Certification of Authorization: N/A
5. Commercial Service Date: 05/31/87
6. National Board Number for Unit: N/A
7. Components Inspected:

Component or Manufacturer or Manufacturer or Installer State or National Board Appurtenance Installer and Serial Number Province Number Address Number Reactor Combustion Eng. 7372 N/A 22004 Pressure Inc.,

Vessel Chattanooga, TN Steam Westinghouse GAGT 1881, GAGT 1882, N/A NA Generators 1 Elec., GAGT 1883, GAGT 1884, thru 4 Pensacola, FL Residual Heat Ingersoll-Rand 087728 N/A 510 Removal Co., Phillipsburg, Pump, Train NJ "A"

Centrifugal Pacific Pumps 52233 N/A 410 Charging Division, Pump, Train Huntington Park, "A" CA Selected Pullman Power System Numbers 1201, N/A N/A Piping, Products, 1204, 1205, 1208.

Components, Williamsport, PA and Supports 2-3

FORM NIS-I (Back) 2n Interval Credit

8. Examination Dates: October 27, 2006 to April 22. 2008
9. Inspection Period ldentification: Third Period Credit
10. Inspection Interval Identification: Second Inspection Interval Credit
11. Applicable Edition of Section XI 1989 Addenda N/A
12. Date/Revision of Inspection Plan: May 29, 2007 / Version 1.0
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)
14. Abstract of Results of Examinations and Tests. (See Abstract)
15. Abstract of Corrective Measures. (See Abstract)

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Section Xl, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date: JJ 20 Signed: Southern Nuclear By:

Operating Company, Inc.

for Georgia Power Company Z liat Owner CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler Inspection and Insurance Company of Connecticut of Hartford, CT have inspected the components described in this Owner's Report during the period October 27, 2006 to Aprl 24, 2008, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code, Section X1.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commission: 6A 7e&

Irrspecto AP*ignature b National Board, State, Province, and Endorsements Date: 0ZPLr ai 3 20-&

2-4

ABSTRACT - ASME CLASS 1 AND 2 Introduction/Status The ASME Boiler and Pressure Vessel Code,Section XI, 2001 Edition (Code), with the 2003 Addenda, is the applicable code for conducting inservice inspection activities during the third ten-year inspection interval at VEGP-1. Examinations and tests required by the Code are scheduled in accordance with "Inspection Program B" as defined in Code paragraphs IWB-2412 and IWC-2412. This "Owner's Report for Inservice Inspection" is for those third inspection period examinations and tests which were performed between October 27, 2006 (date of last examination performed during 1R13) and April 24, 2008 (end of 1R14 maintenance/refueling outage).

VEGP has implemented ASME Section XI, Appendix VIII, "Performance Demonstration for Ultrasonic Examination Systems," as required by 10CFR 50.55a, amended by the FederalRegister Notices 64 FR 51370 dated September 22, 1999, as later modified by 69 FR58804, dated October 1, 2004. The initial Rule specified the 1995 Edition with Addenda through 1996 as the applicable edition of ASME Section XI, Appendix VIII. The 2004 Rule incorporated the 2001 Edition with NRC caveats. VEGP has, except where requests for relief, technical alternatives or exemptions have been approved, complied with the requirements for expedited implementation of the applicable Appendix VIII supplements using the EPRI Performance Demonstration Initiative (PDI).

In addition to the summary of inservice inspection activities, this report addresses Code-applicable repairs and replacements documented at VEGP-1 since 1R13 through the end of 1R14. Class 1 and Class 2 Owner's Reports for Repairs or Replacements (Form NIS-2) are provided herein.

It should be noted that Authorized Nuclear Inservice Inspector (ANII) inspection services were provided for those examinations and tests required by the Code. ASME Section XI examinations and tests are itemized in the applicable sections by reference to Examination Category. Examinations which do not meet the Code-required coverage either reference request(s) for relief or indicate that additional relief is required.

Class 1 Examinations Selected Class 1 components were examined by Southern Nuclear Operating Company (SNC) personnel utilizing ultrasonic testing (UT), magnetic particle testing (MT), liquid penetrant (PT), and visual testing (VT) methods, as applicable. Specific components and examination areas are itemized in the applicable portions of this document.

  • During the scope of VEGP-1 examinations conducted, no Class 1 components were observed to have UT, PT or MT reportable indications.

Six (6) Class 1 piping welds had limited volumetric coverage during UT examinations because of physical limitations due to the geometric configuration of the welded areas. More than ninety percent (90%) of the required volume must be examined as addressed in ASME Section XI Code Case N-460 for adequate ASME Section XI Code-required examination coverage to be attained. As noted herein, the subject code case has been approved by the NRC for use as documented in NRC Regulatory Guide 1.147. It is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.

2-5

Class 1 Pressure Test This summary report documents the pressure test performed for completion of Second Ten Year Interval requirements for a system hydrostatic test (IWB-5222) as required the 1989 Edition of Section Xl. This summary report also documents the system leakage test performed at the end of the refueling/maintenance outage for the current interval which is the Third Ten Year Interval. The applicable code for the Third Ten Year Interval is the 2001 Edition with Addenda through 2003.

For the Second Ten Year Interval, Table IWB-2500-1, Examination Category B-P, of the 1989 Edition of Section Xl requires the performance of a system hydrostatic test (IWB-5222) once at or near the end of each inspection interval. This test is identified as the Class 1 hydrostatic test (HT-1) and it extends to the Class 1 pressure boundary extremity (i.e., second isolation valve) and also includes selected adjacent Class 2 components which are typically isolated from the Class 1 boundary by check valves. As an alternative to ASME Section XI requirements, Code Case N-498-4, which was conditionally accepted for use in Revision 14 of Regulatory Guide 1.147 dated August 2005, was used. Code Case N-498-4 deleted the elevated pressure requirement for the hydrostatic test and reduced the holding time requirement but retained the requirement to extend the boundary subject to test pressurization to include each of the Class 1 pressure-retaining components. To assure that all Class 1 pressure retaining components and selected adjacent Class 2 pressure retaining components are pressurized requires, for some isolated boundaries, that valves be aligned to positions other than their normal alignment and, in some cases, requires the use of a hydrostatic test pump for isolated boundaries. Portions of this test were not completed during the 1R1 3 maintenance / refueling outage, which was the last maintenance/refueling outage of the Second Ten Year Interval. However, as allowed by IWB-2412, the remaining portions were performed in maintenance / refueling outage 1R1 4, which was the first maintenance/refueling outage of the Third Ten Year Interval.

For the Third Ten Year Interval, Table IWB-2500-1, Examination Category B-P of the 2001 Edition with Addenda through 2003 of ASME Section XI requires the performance of a system leakage test (IWB-5221) each maintenance/refueling outage. This system leakage test (LT-1) was performed prior to plant startup following the refueling outage. These visual examinations revealed minor leakage and boron residue at mechanical connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.

Class 2 Examinations Selected Class 2 Piping welds were examined utilizing UT and PT. Specific components and examination areas are itemized in the applicable portions of this report document.

  • During the scope of VEGP-1 examinations conducted, no Class 2 components were observed to have reportable indications.

Two (2) class 2 piping welds had limited volumetric coverage during UT examinations because of physical limitations due to the geometric configuration of the welded areas. As with the Class 1 examinations, it is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.

2-6

Class 2 Pressure Tests This summary report documents the system pressure tests performed for completion of the Second Ten Year Interval requirements per the 1989 Edition of Section XI. This summary report also documents the system leakage tests performed for the current interval which is the Third Ten Year Interval. The applicable code for the Third Ten Year Interval is the 2001 Edition with Addenda through 2003.

For the Second Ten Year Interval, Table IWC-2500-1, Examination Category C-H, of the 1989 Edition of Section X1 requires system pressure testing. Some of the system pressure tests for the Second Ten Year Interval were not completed during the 1R1 3 maintenance / refueling outage which was the last maintenance/refueling outage of the Second Ten Year Interval. However, as allowed by IWA-2430, the remaining portions were performed in maintenance / refueling outage 1R1 4, which was the first maintenance / refueling outage of the Third Ten Year Interval. The specific system pressure tests performed are itemized in the "Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests found only minor leakage or residue at mechanical joints such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.

For the Third Ten Year Interval, Table IWC-2500-1, Examination Category C-H of the 2001 Edition with Addenda through 2003 of ASME Section XI requires system leakage tests. The specific system pressure tests performed are itemized in the "Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests found only minor leakage or residue at mechanical joints, such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.

Class MC Containment Examinations and Tests (IWE)

During the VEGP-1 Spring 2008 maintenance/refueling outage, VT-3 and VT-1 examinations were performed on Class MC Pressure retaining components with their integral attachments and metallic shell and penetration liners of Class CC pressure retaining components with their integral attachments. These examinations were performed in response to the NRC rulemaking to 10 CFR 50.55a that invoked the requirements of Subsections IWE of the 1992 Edition of ASME Section Xl with 1992 Addenda and were performed using VEGP procedure 85053-C, "Visual Examinations for ASME Xl Subsection IWE and IWL and General Visual Examinations". Per procedure 85053-C, the VEGP-1 components were examined for deviations or departures from their normal or common order, form, and rule, with evidence of degradation that may affect either the containment structural integrity or leak tightness.

Personnel performing the examinations were qualified in accordance with VEGP procedure NMP-ES-024-100, "Qualification and Certification of Nondestructive Examination and Testing Personnel". Optical aids such as flashlights, mirrors and binoculars were used when performing the examinations that included both direct and remote visual examination methods.

Cateaory E-A, Containment Surfaces A VT-3 examination of 100% of the accessible portions of the containment surfaces was performed and documented under Surveillance #84303-101-1070868801. All anomalies consisted of surface rust, scratches, discolorations, etc. and were dispositioned as "hardware not affected" since the liner plate's minimum design thickness was maintained at all anomaly locations. The acceptance criteria used to disposition the recorded anomalies was provided in SCS letters SG-1 8218 dated February 28, 2001 and SG-17755 dated September 19, 2000.

2-7

Category E-B, Pressure-Retaining Welds The rulemaking (10 CFR 50.55a(b)(2)(ix)(C)) contains a modification that makes examinations of Subsection IWE, Category E-B optional. SNC has chosen to not examine category E-B welds at VEGP.

Category E-C, Containment Surfaces Requiring Augmented Examination Identified surface areas likely to experience accelerated degradation and aging require the performance of augmented examinations as defined in Examination Category E-C. There are no existing areas in VEGP-1 requiring Category E-C examination.

Category E-D, Seals, Gaskets, and Moisture Barriers A VT-3 examination of 100% of the moisture barrier was performed under Surveillance #85053-102-1070869101 in which four anomalies were found at the liner plate to moisture barrier interface. The moisture barrier was removed at the four anomaly locations per MWO 1080525801, and a VT-3 exam was performed on the exposed liner plate per Surveillance #85053-102-1080604601 (IR# 41568 and IR#

41569). All anomalies were dispositioned as "hardware not affected" since the liner plate's minimum design thickness was maintained. The anomalies were recoated and the moisture barrier was then restored per MWO 1080525801. A satisfactory VT-3 examination was performed per 85053-102-1080604601 (IR# 41601) on the restored moisture barrier.

SNC has chosen to implement Request for Relief (RR-E-1) to allow leak tightness of seals and gaskets to be verified by 10 CFR 50, Appendix J Type B testing (LLRT). The NRC approved SNC's use of RR-E-1 in its June 16, 2000 letter to SNC (TAC Nos. MA5314 and MA5315). The Type B test results, along with the Type C test results, are available at the plant site for review upon request in accordance with 10 CFR 50 Appendix J Option B.

Category E-F, Pressure-Retaining Dissimilar Metal Welds The rulemaking (10 CFR 50.55a(b)(2)(ix)(C)) contains a modification that makes examinations of Subsection IWE, Category E-F optional. SNC has chosen to not examine category E-F welds at VEGP.

Category E-G, Pressure-Retaining Bolting The following VT-1 examinations of the accessible containment pressure-retaining bolting necessary to achieve the 100% required during the interval were performed with no anomalies found as documented on Surveillance # 85053-101-1070869001.

11818H3P01 11818H3P13 11818H3P25 11818H3P40 11818H3P58 11818H3P02 11818H3P14 11818H3P26 11818H3P41 11818H3P59 11818H3P03 11818H3P15 11818H3P27 11818H3P42 11818H3P60 11818H3P04 11818H3P16 11818H3P28 11818H3P43 11818H3P61 11818H3P05 11818H3P17 11818H3P29 11818H3P44 11818H3P62 11818H3P06 11818H3P18 11818H3P30 11818H3P51 11818H3P63 11818H3P07 11818H3P19 11818H3P31 11818H3P52 11818H3P64 11818H3P08 11818H3P20 11818H3P32 11818H3P53 11818H3P65 11818H3P09 11818H3P21 11818H3P33 11818H3P54 12101R2014 11818H3P10 11818H3P22 11818H3P34 11818H3P55 12101R2015 11818H3P11 11818H3P23 21818H3P38 11818H3P56 11818H3P12 11818H3P24 11818H3P39 11818H3P57 A VT-1 examination was also performed on outage penetration 55-M under MWO# 1070814601 since it was disassembled. No anomalies were found.

2-8

CLASS CC Containment Examinations (IWL)

None performed in 1R14 Status of Examinations Required for the current Interval This 1R14 Outage was the 1 st Outage, 1st Period of the 3fdInterval. The results from this outage, combined with the "scheduled" examinations for the next refueling outage (1 R1 5, Fall 2009) will represent 100% of the total Class 1 and 2 scope for the current period and interval. VEGP Unit 1 is within ASME Code compliance, pending NRC approval of the volumetric and/or surface examination limitations.

Requests for relief will be submitted within the required time frame specified by 10 CFR 50.55a.

2-9

TAB C INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

CLASS 1 AND 2 WELDS AND SUPPORT EXAMINATIONS

<yogtle Unit 1- Examination SummaryGass1 and 2 hComponents)

  • ASME.* , ExaminationlAre-a iExamination - Exam/Cal Sheet Results, Remarks,
Section.Xl -.  ; Procedure.,. No(s)."

B-D 11201 -B6-002-IR-01 NMP-ES-024-513 S08V1 U028, 029 NRI N/A B3.140 INLET NOZZLE INNER RADIUS & 030 B-D 11201-B6-002-IR-02 NMP-ES-024-513 S08V1U031, 032 NRI N/A B3.140 OUTLET NOZZLE INNER RADIUS & 033 C-A 11201-B6-001-WOI NMP-ES-024-516 S08V1U053, 054, UT RI UT RI - ASME C1.20 UPPER HEAD TO UPPER SHELL BARREL '0' WELD 055 & 056 Code Acceptable C-B 11201-B6-001-W18 NMP-ES-024-401 SO8V1M001, NRI N/A C2.21 32" STEAM OUTLET NOZZLE TO UPPER HEAD WELD NMP-ES-024-516 U057, 058 & 059 C-C 11204-006-51 NMP-ES-024-301 SO8V1P003 NRI N/A C3.20 SUPPORT H006 C-C 11204-007-5 NMP-ES-024-301 SO8V1P007 NRI N/A C3.20 SUPPORT H003 C-C 11205-003-41 NMP-ES-024-301 S08VIP002 NRI N/A C3.20 SUPPORT H019 C-C 11205-007-70 NMP-ES-024-301 SO8V1P004 NRI N/A C3.20 SUPPORT H032 C-C 11205-007-74 NMP-ES-024-301 SO8V1P005 NRI N/A C3.20 SUPPORT H033 C-C 11205-P6-001-WOI NMP-ES-024-301 SO8V1P001 NRI N/A C3.30 INTEGRALLY WELDED SUPPORT ATTACHMENT C-C 11208-P6-002-W03 NMP-ES-024-301 S08V1P006 NRI N/A C3.30 INTEGRALLY WELDED PUMP SUPPORT BRACKET R-A 11201-005-8-RI NMP-ES-024-506 S08V1U042 & 043 NRI UT - Limited exam (58%)

R1.11 31" ELBOW TO NOZZLE due to nozzle config.

Relief Required R-A 11201-006-1-RI NMP-ES-024-506 S08V1U026 & 027 NRI UT- Limited exam (31%)

31" NOZZLE TO ELBOW due to nozzle config.

Relief Required R-A 11201-029-1-RI NMP-ES-024-501 S08V1U066 & 067 NRI N/A R1.11 4" BRANCH CONNECTION TO PIPE R-A 11201-053-4-RI NMP-ES-024-501 S08V1U044 & 045 NRI N/A R1.11C 16" PIPE TO REDUCER R-A 11201-053-5-RI NMP-ES-024-501 S08V1 U046 & 047 NRI N/A R1.11C 14" REDUCER TO PIPE 3-1

Vogtle Unit l- Examination Summary (Class I and 2 C6mponents)

ASME' " ExaminationlArea f Examination , Exam/Cal Sheet Results'-' Remarksi

'-Sectio XI iK~' ~'<~ .- Procedure(s) No(s): . . -

R-A 11204-001-9-RI NMP-ES-024-501 S08V1 U001 & 002 NRI UT - Limited exam (50%)

R1.11 12" PIPE TO VALVE (Al 87-0131) due to valve config.

Relief Required R-A 11204-023-21-RI NMP-ES-024-501 S08V1 U060, 061 NRI UT - Limited exam (50%)

R1.11 6" PIPE TO TEE (Al87-0131) & 002 due to tee config.

Relief Required R-A 11204-039-1-RI NMP-ES-024-501 S08V1 U068 & 069 NRI UT - Limited exam (50%)

R1.11 8" VALVE TO PIPE (Al 87-0131) due to valve config.

Relief Required R-A 11204-076-2-RI NMP-ES-024-501 S08V1U005 & 006 RI UT RI - Geometry.

R1.11 3" PIPE TO ELBOW R-A 11204-076-42-RI NMP-ES-024-501 S08V1U007 & 008 NRI UT - Limited exam (50%)

R1.11 1.5" PIPE TO FLANGE (Al 87-0131) due to flange config.

Relief Required R-A 11204-077-9 B-RI NMP-ES-024-501 S08VIU009, 010 NRI N/A R1.11 1.5" ELBOW TO PIPE & 034 R-A 11204-078-10-RI NMP-ES-024-501 S08V1 U01 1, 012 NRI UT - Limited exam (62%)

R1.11 1.5" PIPE TO ELBOW & 013 due to support interference.

Relief Required R-A 11204-079-10-RI NMP-ES-024-501 SO8V1U014, 015 NRI N/A R1.11 1.5" PIPE TO ELBOW &016 R-A 11204-243-34-RI NMP-ES-024-501 S08V1 U051 & 052 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-244-28-RI NMP-ES-024-501 S08V1U017 & 018 NRI N/A -

R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-245-33-RI NMP-ES-024-501 S08V1U024 & 025 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-246-36-RI NMP-ES-024-501 S08V1U040 & 041 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11205-010-7-RI NMP-ES-024-501 S08V1 U003 & 004 NRI N/A R1.11 12" PIPE TO ELBOW (Al 87-0131)

R-A 11208-009-6-RI NMP-ES-024-501 S08VIU063 & 065 NRI N/A R1.11 3" PIPE TO BRANCH CONNECTION 3-2

-oi6U~

....... *, 0g~ unit~l1, Etxamination"Smay Exam at Sum m ar ( u pqSrsy,. ,.*.*.. . ,. * ..

ASME Examinat'ion/Airea ~.~ 7 Examination Exam/Cal Sheet ReutRmak

ýSection XI, (Sort) -1 Procedure(s) No(s)..

F-A 11201-030-H023 NMP-ES-024-203 S08VIV159 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H035 NMP-ES-024-203 S08V1V054 Sat N/A Fl.10S MECH SNUBBER F-A 11201-030-H036 NMP-ES-024-203 S08V1V080 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H037 NMP-ES-024-203 S08V1V084 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H039 NMP-ES-024-203 S08V1V085 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H040 NMP-ES-024-203 S08V1V086 Sat N/A F1.10 LIN RESTRAINT F-A 11201-030-H041 NMP-ES-024-203 S08V1V079 Sat N/A F1.10 CON SPRING F-A 11201-030-H042 NMP-ES-024-203 S08V1V053 Sat N/A FI.10S MECH SNUBBER F-A 11201-030-H043 NMP-ES-024-203 S08V1V087 Sat N/A F1.10 RIGID STRUT F-A 11201-059-H003 NMP-ES-024-203 S08V1V088 Sat N/A F1.10 LIN RESTRAINT F-A 11201-059-H005 NMP-ES-024-203 S08V1V089 Sat N/A F1.10 LIN RESTRAINT F-A 11202-001-H003 NMP-ES-024-203 S08V1V093 Sat N/A F1.20 RIGID STRUT F-A 11202-001-H004 NMP-ES-024-203 S08V1V095 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H006 NMP-ES-024-203 S08V1V096 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H008 NMP-ES-024-203 S08V1V097 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H012 NMP-ES-024-203 S08V1V098 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H021 NMP-ES-024-203 S08V1V099 Sat N/A F1.20 LIN RACK 2-D F-A 11202-001-H024 NMP-ES-024-203 S08VlV100 Sat N/A F1.20 LIN RESTRAINT IIIII 3-3

  • .*~

~*><**,*>;'

~ ~ >*;~ '.~~~-

  1. , . i,*Yotle uniit,! Exami-ýnation Summary (S6`iprts),-,** r "{ q ..

Ui -Examination Exmmr

~ASME CExaminationlAre'a ExaInato ~Eam/Cal Sheet Resuilts -Remarks,,'

',Section X(Sr)Poeue) .No(s).2 F-A 11202-001-H025 NMP-ES-024-203 S08V1V11 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H602 NMP-ES-024-203 S08V1V094 Sat N/A F1.20 RIGID STRUT F-A 11202-196-H003 NMP-ES-024-203 S08V1V105 Sat N/A F1.20 RIGID STRUT F-A 11202-196-H005 NMP-ES-024-203 S08V1V106 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H007 NMP-ES-024-203 S08V1V107 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-HO10 NMP-ES-024-203 S08V1V108 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H012 NMP-ES-024-203 S08V1V1O9 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H014 NMP-ES-024-203 S08V1V110 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H016 NMP-ES-024-203 SO8VIVIl Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H020 NMP-ES-024-203 S08V1V112 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H602 NMP-ES-024-203 S08V1V113 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H001 NMP-ES-024-203 S08V1V102 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H002 NMP-ES-024-203 S08V1V166 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H003 NMP-ES-024-203 S08V1V167 Sat N/A F1.20 LIN RACK 1-D F-A 11202-197-H004 NMP-ES-024-203 S08V1V165 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H603 NMP-ES-024-203 S08V1V165 Sat N/A F1.20 RIGID STRUT F-A 11202-197-H604 NMP-ES-024-203 S08VIV168 Sat N/A F1.20 LIN RESTRAINT F-A 11202-223-H002 NMP-ES-024-203 S08V1V141 Sat N/A F1.20 RIGID STRUT 3-4

Vogtle Unit 1 -ý Examinaton Summary (Supports)

ýASME ASMEc ' ..

~ 'Exam EJ....

ination/Area Sti ea -Exa Exaimi'nation->

iati Exam/Cal xa l Sheet S.Results R  :, Remarks :

F-A 11202-223-H004 NMP-ES-024-203 S08V1V142 Sat N/A F1.20 LIN RESTRAINT F-A 11202-223-H010 NMP-ES-024-203 S08V1V143 Sat N/A F1.20 RIGID STRUT F-A 11204-006-H006 NMP-ES-024-203 S08V1V025 Sat N/A F1.20 LIN RACK 2-D F-A 11204-006-H013 NMP-ES-024-203 S08VlV172 Sat N/A F1.20 LIN RESTRAINT F-A 11204-006-H027 NMP-ES-024-203 S08V1V173 Sat N/A F1.20 VAR SPRING F-A 11204-007-H001 NMP-ES-024-203 S08V1VO19 Sat N/A F1.20 LIN RACK 1-D F-A 11204-007-H003 NMP-ES-024-203 S08V1V162 Sat N/A F1.20 LIN RACK 3-D F-A 11204-007-H006 NMP-ES-024-203 S08V1V163 Sat N/A F1.20 LIN RESTRAINT F-A 11204-007-H008 NMP-ES-024-203 S08VlVO18 Sat N/A F1.20 RIGID STRUT F-A 11204-008-H004 NMP-ES-024-203 S08V1V050 Sat N/A F1.20 LIN RESTRAINT F-A 11204-008-HO10 NMP-ES-024-203 S08V1V049 Sat N/A F1.20 LIN RESTRAINT F-A 11204-008-HO0l NMP-ES-024-203 S08VlVO51 Sat N/A F1.20 RIGID STRUT F-A 11204-021-H002 NMP-ES-024-203 S08VlV122 & 175 Unsat Loose jam nut. Acceptable "as-is".

F1.10 RIGID STRUT Sat MWO generated to address.

F-A 11204-021-H008 NMP-ES-024-203 S08V1V157 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H012 NMP-ES-024-203 S08V1V158 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H014 NMP-ES-024-203 S08VIV137 Sat N/A F1.10S MECH SNUBBER F-A 11204-021-H015 NMP-ES-024-203 S08V1V005 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H021 NMP-ES-024-203 S08V1V138 Sat N/A F1.1S MECH SNUBBER III 3-5

VogtleUnt E m Into Summary (Supports),U >0 ASMEo. ExaminationlArea . ,Examination Exam/Cal Sheet Results Remarks

,'Section Xl( Procedure(s) No(s).

F-A 11204-021-H022 NMP-ES-024-203 S08V1V139 Sat N/A FI.10S MECH SNUBBER F-A 11204-038-H601 NMP-ES-024-203 S08V1V152 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H001 NMP-ES-024-203 S08V1V026 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H007 NMP-ES-024-203 S08V1V027 Sat N/A F1.20 ANCHOR F-A 11204-057-H012 NMP-ES-024-203 S08V1V028 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H024 NMP-ES-024-203 S08V1V048 Sat N/A F1.20 LIN RACK 2-D F-A 11204-057-H032 NMP-ES-024-203 S08V1V029 Sat N/A F1.20 LIN RESTRAINT F-A 11204-076-H011 NMP-ES-024-203 S08V1V114 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H012 NMP-ES-024-203 S08V1V115 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H013 NMP-ES-024-203 S08V1V116 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H015 NMP-ES-024-203 S08V1V117 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H022 NMP-ES-024-203 S08V1V116 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H023 NMP-ES-024-203 S08V1V119 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H025 NMP-ES-024-203 S08V1V120 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H026 NMP-ES-024-203 S08V1V121 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H028 NMP-ES-024-203 S08V1V122 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H030 NMP-ES-024-203 S08V1V123 Sat N/A Fi11 LIN RESTRAINT F-A 11204-076-H031 NMP-ES-024-203 S08V1V154 Sat N/A F1.10 LIN RESTRAINT 3-6

Vogle) Unhit 1 -~ Examination SummaryJM(upprs >s ASME - ExaminationiArea' Examination ExamICal Sheet R - Remarks Sec-,

tion'XI (sort). >Proceclure(s) .,,No(s)

F-A 11204-076-H034 NMP-ES-024-203 S08V1V124 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H036 NMP-ES-024-203 S08V1V125 Sat N/A FI.10 LIN RESTRAINT F-A 11204-076-H038 NMP-ES-024-203 S08V1V126 Sat N/A F1.10 LIN RESTRAINT F-A 11205-003-H005 NMP-ES-024-203 S08V1V071 Sat N/A F1.20 LIN RESTRAINT F-A 11205-003-H019 NMP-ES-024-203 S08V1V030 Sat N/A F1.20 LIN RESTRAINT F-A 11205-003-H027 NMP-ES-024-203 S08V1V031 Sat N/A F1.20 RIGID STRUT F-A 11205-005-H004 NMP-ES-024-203 S08V1V078 Sat N/A F1.20 VAR SPRING F-A 11205-005-H013 NMP-ES-024-203 S08V1V073 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H012 NMP-ES-024-203 S08V1V032 Sat N/A F1.20 RIGID STRUT F-A 11205-007-H032 NMP-ES-024-203 S08V1V075 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H033 NMP-ES-024-203 S08V1V076 Sat N/A F1.20 LIN RESTRAINT F-A I 1205-007-H037 NMP-ES-024-203 S08V1V033 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H041 NMP-ES-024-203 S08V1V072 Sat N/A F1.20 VAR SPRING F-A 11205-007-H060 NMP-ES-024-203 S08V1V058 Sat N/A F1.20 LIN RACK 2-D F-A 11205-007-H061 NMP-ES-024-203 S08V1V057 Sat N/A F1.20 RIGID STRUT F-A 11206-0011-012 NMP-ES-024-203 S08V1V017 Sat N/A F1.20 VAR SPRING F-A 11206-001-H018 NMP-ES-024-203 S08V1V024 Sat N/A F1.20 LIN RESTRAINT F-A 11206-001-H022 NMP-ES-024-203 S08V1V023 Sat N/A F1.20 LIN RESTRAINT 3-7

-.. Vogtle UnitlI -ExaminationriSumma-ry (Supports)

"ASME ExmntolýaExaminaktioný-' Exam/Cal SheetRsut Se'c'tion X I ~(oit) ,o Pce P dudre(s) No(s). Veak F-A 11206-001-H024 NMP-ES-024-203 S08V1V022 Sat N/A F1.20 LIN RESTRAINT F-A 11206-003-H001 NMP-ES-024-203 S08V1V014 Sat N/A F1.20 LIN RESTRAINT F-A 11206-003-H005 NMP-ES-024-203 S08V1V015 Sat N/A F1.20 VAR SPRING F-A 11206-005-H013 NMP-ES-024-203 S08V1V021 Sat N/A F1.20 LIN RESTRAINT F-A 11206-005-H019 NMP-ES-024-203 S08V1V020 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H014 NMP-ES-024-203 S08V1V034 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H018 NMP-ES-024-203 S08VlV035 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H045 NMP-ES-024-203 S08VlV153 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H050 NMP-ES-024-203 S08VlV055 Sat N/A F1.20 LIN RESTRAINT F-A 11208-007-H001 NMP-ES-024-203 S08VIV160 Sat N/A F1.10 LIN RESTRAINT F-A 11208-099-H009 NMP-ES-024-203 S08VlV068 Sat N/A F1.20 LIN RACK 3-D '

F-A 11208-137-H603 NMP-ES-024-203 S08VlV082 Sat N/A F1.20 LIN RESTRAINT F-A 11208-141-H002 NMP-ES-024-203 S08V1V069 Sat N/A F1.20 LIN RACK 2-D F-A 11208-411-H017 NMP-ES-024-203 S08VlV074 Sat N/A F1.20 LIN RACK 2-D F-A 11301-104-H007 NMP-ES-024-203 S08VlV169 Sat N/A F1.20 VAR SPRING F-A 11302-109-H008 NMP-ES-024-203 S08V1V140 Sat N/A F1.20 RIGID STRUT F-A 11302-109-H012 NMP-ES-024-203 S08V1V103 Sat N/A F1.20S MECH SNUBBER F-A 11302-109-H014 NMP-ES-024-203 S08V1V170 Sat N/A F1.20 VAR SPRING 3-8

TAB D INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

SYSTEM PRESSURE TESTS

SYSTEM PRESSURE TESTS The following pressure tests on Class 1 and Class 2 components were performed after the last maintenance/refueling outage (1 R1 3) through the completion of the fourteenth maintenance/refueling outage (1R14). As indicated in the pressure test listings some of these tests are for the Second Ten Year Interval and some are for the Third Ten Year Interval. The pressure tests indicated for the Second Ten Year Interval include system functional and system hydrostatic tests. It should be noted that the hydrostatic tests identified were performed to satisfy the "once per ten year" requirements described in ASME Section XI, Code Case N-498-4. The pressure tests indicated for the Third Ten Year Interval include system functional tests, system inservice tests, and system leakage tests. Boundaries for the pressure tests are described in the VEGP-1 Inservice Inspection Plan - Second 10-Year Interval document. Examination results are discussed in the applicable sections of this report document. The examination data for these pressure tests is available at the plant site for review upon request.

System Functional Tests (FTs) for Second Ten Year Interval FT Exam. Test Description Number Cat.

14 C-H Turbine Driven Auxiliary Feedwater (TDAFW) Pump 1302-P4-001 Functional Test System Functional Tests (FTs) for Third Ten Year Interval IFT Exam. Test Description Number Cat.

1 C-H Reactor Head Vent Functional Test 4 C-H Safety Injection Pump 1204-P6-003 Discharge Functional Test 5 C-H Safety Injection Pump 1204-P6-004 Discharge Functional Test 8 C-H Penetration 30 (SI to Cold Legs) Functional Test 12 C-H Containment Spray Train "A"Functional Test 13 C-H Containment Spray Train "B"Functional Test 17 C-H Line 1208-133 (HV-8104 to Valve 185 Flow Test) Functional Test System Hydrostatic Tests for Second Ten Year Interval (HTs)

HT Exam. Test Description Number Cat.

1 B-P Class 1 Hydrostatic Test (Partially performed in 1R13 - Test completed in 1R14)

C-H 3 C-H SI, Normal Charging & CS Pump Suction Hydrostatic Test 5 C-H RHR Train A Suction Hydrostatic Test 6 C-H RHR Train B Suction Hydrostatic Test 4-1

System Inservice Tests for Third Ten Year Interval (ITs)

IT Exam. Test Description Number Cat.

1 C-H Charging Line Inside Containment Inservice Test 2 C-H Letdown Line Inside Containment Inservice Test 3 C-H Reactor Coolant (RC) Pumps 1, 2, 3, and 4 Seal Leakoff Inside Containment Inservice Test 4 C-H RC Pump 1 Seal Injection from Penetration 54 to Valve 006 Inservice Test 5 C-H RC Pump 2 Seal Injection from Penetration 53 to Valve 359 Inservice Test 6 C-H RC Pump 3 Seal Injection from Penetration 52 to Valve 360 Inservice Test 7 C-H RC Pump 4 Seal Injection from Penetration 51 to Valve 361 Inservice Test 8 C-H Reactor Coolant System (RCS) Hot Leg Sample Lines to Penetration 24 Inservice Test 9 C-H Sample Line from Valve 101 to Valve HV-3514 Inservice Test 10 C-H CVCS Inservice Test with Normal Charging Pump Operating (Outside Containment) 11 C-H Centrifugal Charging Pump 1208-P6-002 (Train "A") Discharge Inservice Test 12 C-H Centrifugal Charging Pump 1208-P6-003 (Train "B") Discharge Inservice Test 14 C-H Accumulator Tank 1 (1204-V6-002) Inservice Test 15 C-H Accumulator Tank 2 (1204-V6-003) Inservice Test 16 C-H Accumulator Tank 3 (1204-V6-004) Inservice Test 17 C-H Accumulator Tank 4 (1204-V6-005) Inservice Test 23 C-H Refueling Water Storage Tank (RWST) Inservice Test 24 C-H Sample Line from Valve 097 to Valve HV-3508 Inservice Test 25 C-H Penetration 24 Outside Containment Inservice Test (Post-Accident Sampling) 26 C-H Nuclear Service Cooling Water (NSCW) Train "A" Inservice Test (Outside Containment) 30 C-H NSCW Train "B" Inservice Test (Outside Containment) 34 C-H Containment Coolers 1501-A7-001 and 1501-A7-002 Inservice Test 35 C-H Containment Coolers 1501-A7-003 and 1501-A7-004 Inservice Test 36 C-H Containment Coolers 1501-A7-005 and 1501-A7-006 Inservice Test 37 C-H Containment Coolers 1501-A7-007 and 1501-A7-008 Inservice Test 38 C-H Cooling Coils 1511-E7-001 and 1515-A7-001 Inservice Test 4-2

IT Exam. Test Description Number Cat.

39 C-H Cooling Coils 1511-E7-002 and 1515-A7-002 Inservice Test 45 C-H Steam Generator 1201-B6-001 Inservice Test 46 C-H Steam Generator 1201-B6-002 Inservice Test 47 C-H Steam Generator 1201-B6-003 Inservice Test 48 C-H Steam Generator 1201-B6-004 Inservice Test 49 C-H Penetration 7 Inservice Test (Outside Containment Steam Generator 1 Blowdown to Heat Exchanger) 50 C-H Penetration 8 Inservice Test (Outside Containment Steam Generator 2 Blowdown to Heat Exchanger) 51 C-H Penetration 9 Inservice Test (Outside Containment Steam Generator 3 Blowdown to Heat Exchanger) 52 C-H Penetration 10 Inservice Test (Outside Containment Steam Generator 4 Blowdown to Heat Exchanger) 53 C-H Penetration 11 B Inservice Test (Outside Containment Steam Generator 1 Blowdown to Sample) 54 C-H Penetration 11C Inservice Test (Outside Containment Steam Generator 2 Blowdown to Sample) 55 C-H Penetration 12B Inservice Test (Outside Containment Steam Generator 3 Blowdown to Sample) 56 C-H Penetration 12C Inservice Test (Outside Containment Steam Generator 4 Blowdown to Sample) 57 C-H Main Steam Loop 1 Inservice Test (Outside Containment) 58 C-H Main Steam Loop 2 Inservice Test (Outside Containment) 59 C-H Main Steam Loop 3 Inservice Test (Outside Containment) 60 C-H Main Steam Loop 4 Inservice Test (Outside Containment) 71 C-H Main Feedwater Loop 1 Inservice Test (Outside Containment) 72 C-H Main Feedwater Loop 2 Inservice Test (Outside Containment) 73 C-H Main Feedwater Loop 3 Inservice Test (Outside Containment) 74 C-H Main Feedwater Loop 4 Inservice Test (Outside Containment) 79 C-H Excess Letdown Heat Exchanger Inservice Test System Leakage Test Schedule (LT)

[LT Exam. Test Description Number Cat.

1 B-P Class 1 System Leakage Test 4-3

TAB E INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

REPORTABLE INDICATION

SUMMARY

REPORTABLE INDICATION

SUMMARY

The following indication identified on the Condition Report was issued due to reportable indications or conditions being observed during the examination of either Class 1 or 2 components during the fourteenth

( 14 th) maintenance/refueling outage at VEGP-1 (referenced attachments'are available at the VEGP plant site for review upon request):

INF No. Affected

  • INF Disposition (108V1) Component/Area 001 11204-021-H002 Loose "jam" nut.

(Rigid Strut) Per the disposition of Condition Report 2008103578, the loose jam nut did not prevent the support from performing its intended function.

A Work Order was written to correct the condition.

The Indication Notification Form(s) constitute only those reportable indications or conditions observed during the SNC M & IS Department scope of work. Any reportable indications or conditions observed by VEGP Site personnel or outside contractors during their scope of work should be identified by/to the VEGP Site in report document(s) which are referenced herein.

5-1

TAB F OWNER'S REPORT FOR REPAIR AND REPLACEMENTS (ASME FORM NIS-2)

OWNER'S REPORTS FOR REPAIRS OR REPLACEMENTS (FORM NIS-2)

The following Owner's Reports for Repairs or Replacements (Form NIS-2) are provided for work activities documented at VEGP-1 since the last maintenance/refueling outage (1R13) through the completion of the fourteenth maintenance/refueling outage (1R14). Reports are identified by their respective traveler number which is denoted on each of the NIS-2 reports. The originals of the NIS-2 reports are filed with their respective traveler packages at the plant site. Only those NIS-2 reports applicable to VEGP-1 are included in this report document. Any attachments, e.g., code data reports, etc., referenced in the NIS-2 reports will be made available for review upon request at the plant site. This report includes the outstanding NIS-2s from the end of the Second Inspection Interval which ended May 30, 2007 and those NIS-2s which were performed during the Third Inspection Interval which began on May 30, 2007.

The NIS-2s listed below were performed during the Second Inspection Interval for the following travelers which are included herein:

01071** 06020 06042 06049** 06057** 06079 06090 01102** 06027 06043 06051 06058 06081** 06091 04110 06036 06045 06052** 06059 06082 07052 04115** 06039 06046 06053 06062 06086**

05124 06040 06047 06054 06068 06087 06009 06041 06048 06055 06075 06088 The NIS-2s listed below were performed during the Third Inspection Interval for the following travelers which are included herein:

06094** 07154 07165 07181 07221 08035 08044 07138 07156 07166 07183 08009 08036 08045 07145 07158 07167 07187 08010 08037 08046 07147 07159 07168 07195 08011 08038 08047 07148** 07160 07169** 07197 08012 08039 08050**

07149** 07161 07170 07203 08013 08040 08054 07150 07162 07171 07205 08014 08041 08055 07152 07163 07172 07206 08020 08042 07153 07164 07180 07209 08034 08043**

Traveler 01071 is certified on the same NIS-2 report as traveler 06086.

Traveler 01102 is certified on the same NIS-2 report as traveler 06057.

Traveler 04115 is certified on the same NIS-2 report as traveler 06049.

Traveler 06081 is certified on the same NIS-2 report as traveler 06052.

Traveler 06094 is certified on the same NIS-2 report as traveler 07169.

Traveler 07149 is certified on the same NIS-2 report as traveler 07148.

Traveler 08050 is certified on the same NIS-2 report as traveler 08043.

6-1

.. .4 ORIGINAL ASME SECTION XI TRAVELER S

9 TRAVELER:

SECTION XI REPAIRIREPLACEMENT TRAVELER 01071 PAGE 1 OF 3 REPAIR I] REPLACEMENT [

.... ASSOCIATED DOCUMENTS ----- ------- COMPONENT----I MWO: A0100517 CODE CLASS: ASME III Class 1 DC: N/A TAG NO: A2117SnubberQ DCP: N/A DESCRIPTION Snubber PSA-3 OTHER: * .AL'4A-,3.*I*3 SERIAL NO: 269.%9 S5.1 (4.&l DESCRIPTION: Reolace parts of snubber. I I-EXAMINATION / TEST REQUIREMENTS .......

N/A VT-1 N/A VT-2. N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement I Z No Normal / Expected Wear E ALARA El DCP L EQ Checklist I L] Yes Justification:

Intended life of-if less than design life of repaired item: _

REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operatinq Co.

- INITIAL @EVIEW -----

6 REPATEHOLD POINTS INITIATOR . . . 1 00 YES

[] ZNO E QUALITY CONTROL & 0 1 YES LJNONE ANII ElYES NONE


FINALR _VIEW -----

REMARKS..Z*"

    • ,,.velet olo- -"rl tt " I 0,

1

ORIGINAL ASME SECTION Xl TRAVELER INSTRUCTION SHEET ASME SECTION XI TRAVELER INSTRUCTION SHEET TRAVELER NO: 01071 MWO: A0100517 PAGE 2 OF 3 STEPi - TRAVELER WORK, aiP . I Maint P3 ANII*

NO..NO RWO' W/H, 'INIT/DATEK W/l14 1INITiD)ATE,.

1. Ensure the serial number, heat Maint. _,-zjp.olI_

and/or trace code number of the _

replacement part(s) is entered on _

the MER. Ensure ASME code class _

of the replacement part(s) is entered _

on the MER. _

2. Verify the serial number, heat 0C .

and/or code number of the _ _ LC; ______

replacement recorded on thepart(s) matches what's _

MER or the applicable documentation.

3. Verify that the ASME code class for thatthe replacement of the part(s) matches -' _

component or piping in which it is being installed.

4. Install replacement part(s). Maint. t __-_

4L 9-___-_ 1

  • -** 6 ORIGINAL ASME SECTION XI BILL OF MATERIALS SHEET ASME SECTION Xl BILL OF MATERIALS TRAVELER 01071 MWO -AEeJ4 U iIb/ , PAGE A O0F 3 Telescoping AX4AQ418 26 1977W1977 A:514 101%

Cylinder -168\_ ___ _ _ VIM _," A -sic__ ___ _,

COMMENTS: -

  • 1 0

.1

Jr~

ORIGINAL 0 ASME SECTION Xl TRAVELER SECTION Xl REPAIRIREPLACEMENT TRAVELER PAGE 1 OF 3 1 TRAVELER: 01102 REPAIR Li REPLACEMENT [

-ASSOCIATED DOCUMENTS-- -COMPONENT--

MWO: A0000644 CODE CLASS: ASME III CLASS 1 DC: N/A TAG NO: A2117SNUBBERQ DCP: N/A DESCRIPTION SNUBBER PSA-i6 OTHER: N/A SERIAL NO: 15477 WORK DESCRIPTION: SNUBBER BEING REBUILT FOR RETURN TO WAREHOUSE STOCK NEEDS PARTS REPLACED EXAMINATION / TEST REQUIREMENTS -'

N VT-1 N VT-2 N VT-3 OTHER N N NOMINAL OPERATING PRESSURE N PNEUMATIC N HYDROSTATIC PRESSURE N TEMPERATURE N HOLD TIME N FAILURE Evaluation for Suitability of Repair or Replacement

  • No Normal I Expected Wear -- ALARA L] DCP [] EQ Checklist El Yes Justification:

Intended life of if less than design life of repaired item:

REPAIR/REPLACEMENT ORGANIZATION: SNC MAINT.

-IITIAL IfVIEW -

fGl E DATE HOLD POINTS INITIATOR . 9/1.7101 r] YES__ZNONEl QUALITY CONTROL I Z 'ZZ _[Z YES_1NONEi ANII .JYESAJONE 1X-


F1AL LREVIEW-REMARKS: iirem ~i-dec ~a -on Snsb&er Sg( 5 4 0 R WE~

  • 1 ORIGINAL TRAVELER NO: 01102 SECTION XI TRAVELER INSTRUCTION SHEET MWO: A0000644 PAGE 2 OF 3i I

Il 4 4 *

-I 4 4. 4 4 i

i: REPLAC

)ON THE ~~~IMAINTI I~-~~L2 I_______

2 VERIFY THE SERIAL NUMBER,HEAT _

AND/OR TRACE CODE NUMBER OF _

THE REPLACEMENT PART(S) _

MATCHES WHAT'S RECORDED ON _

THE MER OR THE APPLICABLE _-__

DOCUMENT. aC H b NI -

3 VERIFY THAT THE ASME CODE CLASS .__

FOR THE REPLACEMENT PART(S) _

MATCHES THAT OF THE COMPONENT _

OR PIPING SYSTEM IN WHICH IT IS _

BEING INSTALLED. QC H _____

4 INSTALL REPLACEMENT PART(S) MAINT H X- f'-, I FIGURE 2

'I.'.

  • r)QIrJN~Al I TRAVELER 01102 ASME SECTION X BILLIOF MATERIALS MWO A00006 4 PAGE 3 OF 3

.I BALL £CflW ACCY. ~AQ4 0160 ff 1977 1977 wi? W.q lcq Re~~c-reGUR R 3~L~

0

  • 1 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 04110

-3.

1. Owner Southern Nuclear OperatingCompany Date 10/31/06 Name 40 Inverness Center Parkway, Birmingham, AL Sheet I of Address
2. Plant Vogtie Electric GeneratingPlant Unit Name Waynesboro, GA 30830 wc* 10401oaa.

WOO 104010M -

Address Repair Organization P.O. No., Job No., etc.

3. Work Performed by Maintenance Department Type Code Symbol Stamp W/A Name Authorization No. AN/A Plant Voatle Expiration Date N/A Address
4. Identification of System 1208 / Chemical and Volume ControlSystem
5. (a) Applicable Construction Code ASME SEC //1 19 74 Edition, Summer 1975 Addenda, .L/A Code Cat e (b)Appilcable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stompec" Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

VALVE DRESSER H207ABH AL/A 1-1208-U4-033 1982 REPLACEMENT YES I INDUSTRIES INC. _

7. Description of Work Seal welded valve body to bonnet.
8. Test Conducted: Hydr ostatic E] Pneumatic[] Nominal Operating Pressure[J NA [] Other 5 Pressure NOP PSI Test Temp. NOT -F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A 4.

Certificate of Authorization No.' N/A Expiration Date N/A Signed A weoOn's Des e Team Leader Date to p6 O~wner or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala and employed by Harilford Steam Boiler Insoection and Insurance Co. of Connecticut I of Hafggrtor o ecticut have Inspected the components described In this Owner's Report during the period 06/14/e4 I to II&XL1190(a . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with' the requirements of the ASME Code, Section Al By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examlnatlons and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions O;4. 7'SC,

'- -M pectc5Sl5gnature National Board, State, Province and Endorsements Date IA 4tezj. ,,fe l a

ORIGINAL it 3

SECTION XI REPAIR/REPLACEMENT TRAVELER PAGE 1 OF 3 TRAVELER: 04115 REPAIR LI REPLACEMENT I

-ASSOCIATED DOCUMENTS-- ---- COMPONENT-----

WO: A0400541 CODE CLASS: ASME III-Cl. 1 NF CR: N/A TAG NO: A-2117zSNUBBERQ DCP: N/A DESCRIPTION Spare Snubber (AD-151)

OTHER: AX4AQ56-10006 SERIAL NO: 588 WORK DESCRIPTION: Replace snubber flanged end sub-assembly.

EXAMINATION / TEST REQUIREMENTS -

N/A VT-1 N/A VT-2 N/A VT-3 OTHER N/A NIA NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement

[] No _M Normal / Expected Wear [] ALARA [] DCP I] EQ Checklist

[-] Yes Justification:

Intended life if less than design life of repaired item:

REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operating Co.

INITIAL REVIEW IGNA U E DA HOLD POINTS AWE lba_4 061/9 El YES 19 NONE ISI ENGINEER , ,- it E] YES . NONE SEC. Xl EXAMINER cipU4I-YS 12NONE ANII []YES NONE

- FINAL REVIEW SIGbIATUJRE PATE I GNAT DATE ISI ENGINEER I/0,/7 /* AWE l/ý Z (,

REMARKS: 1.- 660119 NI -"v-2__.'ZS2.

M1 rIMM' 1INUIAL Qe DATE IfLudo.

ORIGINAL TRAVELER NO: 04115 ASME SECTION Xl TRAVELER INSTRUCTION SHEET WO: A0400541 PAGE 2 OF 3 N2-R >~N STRUTIOS RO WI MIT.

INTIDTE.

1,_ WI - NITIDATE'

1. Ensure the serial number, heat Maint. ". .. ......... . _.... .

and/or trace code number of the _ __ __

replacement part(s) is entered on _-_ _ _ _ __

the MER. If the part does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the MER.

2. Verify the serial number, heat and/or QC /W trace code number of the replacement _ ___"_"___/

part(s) matches what is recorded on ___. __

the MER or the applicable documen- -____

tation. If the part has no markings, utilize the PO, MIR and Line Item numbers on the warehouse identifi-cation label.

3. Verify that the ASME Code Class QC N A,/

for the replacement part(s) matches or ___ _. /

exceeds that of the component in ____b f___-

which it is being installed.

4. Install replacement part(s) in spare Maint.e- Ar fl/ 11 Ad/Q/

snubber...

0 O RI(AL ASME SECTION Xl BILL OF MATERIALS TRAVELER 04115 W6 A0400541 PAGE 3 OF 3 MATRILICMPREFE.RENCE IEM RIGINAL&_`:K.`. OIIA ET RCECD - IULEAIE DESRIPION

-DA~iG 'O~'-~+RELAEMENT K EPLACEMENT ý REIL#- ~ 'EII I Flanged Fixed AX4AQ56- 81 1977W1 977 SA564 TY 630 1 i y/

End 10006 Iq77LWlq77 sA5*1TY6;s3,'- -

  • Fixed End AX4AQ56- 83 1977W1 977 SA564 TY 630 Guide Sleeve 10006 Jam Nut AX4AQ56- 84 1977W1 977 SA564 TY 630 -37

,, .. 10006 1'977Li77 _S4& .- 37.

COMMENTS:

  • These are parts of the flanged end sub-assembly.

. I/

7/ V E/

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI

'Y Traveler# 05124

1. Owner Southern Nuclear Operating Company Date 10300 I Name 40 Inverness Center Parkway,Blrmingham, AL Address Sheet 1 of L L
2. Plant Vopte ElectrIc GeneratingPlant Unit 1 L Name Waynesboro, GA 30830 WO# 1051668001 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Type Code Symbol Stamp NAV Name Authorizaion No. N/A Plant Vogte Expiration Date N/A Address
4. Identification of System 1511 / ContainmentCoalina System is 11 / ContainmentCooling Svstsm
5. (a) Applicable Constructlon Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N/A Code Cade (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19f8
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No) 1511 PIPING CWI N/A N/A 1V4-1511-O03-01 1987 REPLACEMENT YES [

SYSTEM INCORPORATED 1-1511-E7-001

7. Description of Work Replaced studsand nuts In the 2-II2 Inlet and outlet header flanges to ContainmentCooler 1-151 I-E7-001.
8. Test Conducted: Hydrostatic [3 Pneumatic Nominal Operating PressureD WA[1 Other [] Pressure N/A PSI Test Temp. N/A OF
9. Remarks See Item 7 Applicable Manufacturer's Date Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Data N/A I

-fix Signed Owneo Team Leader Date CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut I of Ha" necticut have Inspected the components described In this Owner's Report during the period 11/28/05 I to aand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shaell be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this I1--

, D Commissions C(-A ZrS".

Wrspe6(or's Signature National Board, State, Province and Endorsements Date .1;, =

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06009

1. Owner Southern NuclearOperating Company Date 01/05/07 Name 40 Inverness Center Parkway,Birmingham, AL Sheet I of _

Address 2'. Plant Vontla Electric GeneratinaPlant Unit Name Waynesboro, GA 30830 WO# 1054155901 Address -Repair Organization P.O. No., Job No., etc.

3. Work Performed by, Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A PlantVoatle Expiration Dafte N/A Address
4. Identification of System 1205/ Residual Heat Removal Systemn S. (a) .Applicable Construction Code ASME SEC Ill 19 71 Edition, Summer 1972 Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 198
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stomped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

RELIEF VALVE CROSBY VALVE & N56904-00-0037 N/A 1PSV-8708A 1977 REPLACED YES GAGE CO.

RELIEF VALVE CROSBY VALVE & N56904-00-0017 N/A IPSV-8708A 1975 REPLACEMENT YES GAGE CO.

7. Description of Work Replaced relief valve. The replacement relief valve, serialnumber N56904-00-0017, Is a rotatingspare and was originally Installedas 2PSV-8708B during construction;
8. -Test Conducted: Hydrostatic [] Pneumatic-- Nominal Operating Pressure[M]

NA- Other E] Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached.

CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. - N/A Expiration Date N/A o1\

Signed f A J-9 Team Leader Date l z- 0 "

\l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by HartfordSteam Boiler Ins-ection and Insurance Co. of Connecticut of Haifford. Connecticut have Inspected the components described In this Owner's Report during the period 04/0306 to /-,.$ - 4007 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ingl_____________________Commissions 1 ..

  • _" ' ,,: &ias ,

Inspecta e Signature National Board, State, Province and Endorsements Date It I.T^0 MO07

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 1

Traveler0 06020

1. Owner Southern Nuclear Operating Comoany Date 10/31/06 Name 40 Inverness CenterParkway, Birmingham, AL Sheet t of t T Address
2. Plant Vogtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 WO# 1053338301 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootte Expiration Date N/A Address
4. Identification of System 1206 / ContainmentSpray System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appliceble Edition of Section Xl -Utilized for Repairs or Replacements l98f9i
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Coie Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Nok PIPE PULLMAN POWER N/A N/A Vl-1206-006-H020 1987 REPLACEMENT YES SUPPORT PRODUCTS
7. Description of Work Snubber PSA-1, serial#24337A was replacedwith a Lisega Type 30 snubberserial# 305002621043.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[]

NlA'] Other 5 Pressure N/A PSI Test Temp. .N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement, Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A -

$1" Signed L6 Team Leader Data L ( z t 1Q

\Owner or Owner's Designee, Title

. CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connectiut! of Hack% Connecticut have Inspected the components described in this Owner's Report during the period 02/23/06 I to /111IAQand l* state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ithe examinationsand corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a lose of any kind arising from or connected with this Insoetlon.

91 " &u Commissions &oinl InpetaftSigntureNational 13oard, State, Province and Endorsements Data .2'9 b~_ *ýfteo

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS 4/

As Required By The Provisions Of The ASME Code Section Xi Traveler# 06027

1. Owner Southern Nuclear Operating Company Date 10/31/06 Ntam 40 Inverness CenterParkway. Blrminanha. AL Sheet 1 of Address Unit 1
2. Plant Votjtle Electric GeneratingPlant Name Waynesboro, GA 30830 WO# 1053341101 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootle Expiration Date N/A Address
4. Identification of System 1301 /Main Steam System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Coa a (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification Built or Replacement Ls or N60 PIPE PULLMAN POWER N/A N/A VI-1301-107-HO06 1987 REPLACEMENT YES I SUPPORT PRODUCTS _
7. Description of Work SnubberAD-5501, serial#239 was replaced with a snubberAD-5501, seral# 229 to supportsurveillance testing.

S. Test Conducted: Hydrostatic [- Pnaumatic[] Nominal Operating Pressure[]

NIA E] Other I] Pressure N/A PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the"statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A -

Certificate of Authorization No. N/A Expiration Date N/A I Signed _040%-. Team Leader Date di, A i Owner or Owner's Designee, 11dte CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GGac l and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut of Harod* Conectiut have Inspected the components described In this Owner's Report during the period 02'23/06 to .Z_*&lk 49=&andI state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &,A "


. "- pect Signature National Board, State, Province and Endorsements Data &I OW OL. AO*rC.

ORIGINAL

.1 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Travelero 06036 Vt:

1. Owner Southern NuclearOperating Company Date 11/01/06 Name 40 Inverness Center Parkway,Birmingham, AL Sheet I of 1 Address
2. Plant Voatle Electric GeneratingPlant Unit 1 Name Wnvn...... ,~ ....... WO# 1053342101 Address. Repair Organization P.O. No., Job No., etc.

3.. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A PlantVoatle Expiration Date N/A Address

4. Identification of System 1301/Main Steam System
5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components Nationali Repaired, ASME Code Name of Name of Manufacturer Board . Other Year Replaced, StampedI Component Manufacturer Serial No. No. Identification Built or Replacement so or No)

PIPE PULLMAN POWER /A IVA V.l-301-139-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-1L, serial#600 was replaced with a snubber PSA-IL, serial# 595 to supportsurveillance testing.
8. Test Conducted: Hydrostatic [] Pneumsaticlr Nominal Operating Pressure[]

N/A [] Other E Pressure N/A PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached .

CERTIFICATE OF COMPLIANCE I We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Aiphorlzation No. N/A Expiration Date N/A Signed Team Ledera Data I , C.

,Iloilo, ]Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by HartfordSteam Boiler Insoection and Insurance Co. gf Connecticut I of HartfordC Cortcu have Inspected the components described In this Owner's Report during the period 02/23M/06 I to .Zy* army , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor, his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspcin

  • , j~42~.Commissions -

-Ispectors Signature National Board, State, Province and Endorsements Date a/ r -

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI I Traveler# 06039 I

1. Owner Southern NuclearOperatingCompany Date 1Gi oa'0 Name 40 Inverness Center Parkway,Birmingham, AL Sheet oL Of Address
2. Plant Voatle Electric GeneratingPlant Unit 1 1 Name Waynesboro, GA 30830 WO# 1060055801 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. M/A PlantVoctle Expiration Date N/A Address
4. Identification of System 1201 / Reactor Coolant System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cat 9 (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19-0
6. Identification Of Components Repaired or Replaced and Replacement Components
7. Description of Work SnubberAD-501, serial#552 was replaced with a snubberAD-501, serial# 364 to support maintenanceon valve 1PVO455B.

S. Test Conducted: Hydrostatic Q Pneumatic[] Nominal Operating Pressure((]

N/A FXJ Other I] Pressure N/A PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of ti ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed " Ž -- f'k Team Leader Date , f lot w-ner or Owner's Desinee, Title U-CERTIFICATE OF INSERVICE INSPECTION i I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomfa and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harford. neticut have Inspected the components described In this Owner's Report during the period 0=/1/6 to UU&. Ata(A I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section IXi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inp i Commissions Cw. Tg..

I8psp-e'or's Signature National Board, State, Province and Endorsements I Date 1& A100. Ab:hf

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler# 06040

1. Owner Southern Nuclear OperatingCompany Date 11/01/06 Name 40 Inverness CenterParkway. Birmingham,AL Sheet 1 of I Address
2. Plant Vogqte Electric Generating Plant Unit I Name Waynesboro, GA 30830' WO# 1060107701 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDeparnment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voofle Expiration Date N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 198Q
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement aYes or No)

PIPE PULLMAN POWER AL/A AN/A V1-1201-031.HOOl 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work -SnubberPSA-1, serial#24106 was replaced with a snubberPSA-1, serial# 21682 to support surveillance testft,.
8. Test Conducted: Hydrostatic E] Pneumetic[] Nominai Operating Pressure[]

N/A Other Pressure NA PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Date Report. to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed w (Awr tA).* Titl Team Leader Date 0 k .Pwneror Owner's Designee, TitieI I CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harfd Connecticut have Inspected the components described in this Owner's Report during the period 02/23/06 to 1- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In ton.

C31E Commissions C_ Go ;3176

"* lnpectft Signature National Board,-State, Province and Endorsements Date .. 9 bao_. AJ,,.)

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl I !uVWWla ff I if Owner Southern NuclearOperatingCompany Date 11/01/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet of I Address

2. Plant Vogtie Elect ic'GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1060107801 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by ý Maintenance Department Type Code Symbol Stamp N/A Name Authodzation No. N/A PlantVogtle Expiration Date N/A Address
4. Identification of System 1201 / Reactor CoolantSystem
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement as or No PIPE PULLMAN POWER N/A N/A VI-1201-036-H010 1987 REPLACEMENT YES SUPPORT PRODUCTS
7. Description of Work Snubber PSA-35, sedal #11507 was replacedwith a snubber PSA-35, sedal # .11236to support surveillance testing.
8. Test Conducted: Hydrostatic [) PneurcaticQ' Nominal Operating Pressurefl NIA [] Other [] Pressure N/A PSI Test Temp. N/A IF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp NAV Certificate of Authorization No. N/A Expiration Date N/A Signed Qrkj^ L.^ Team Leader Date

~. I Owner at Ownera Dmnlanee. Titli Owner or Owner's Desionse Titid CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the State or Province of Georla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Halfor. onncut have Inspected the components described In this Owner's Report during the period 02123/06 to z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspect~on.

___t___.___ ,__. _ _ Commissions (GA In*pect*'s Signa'ture -National Board, State, Province and Endorsements Date &I.ba?,.. **,

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler# 06042 Y

1. Owner Southern NuclearOperating Company Date 11/01/06 Name' 40 Inverness CenterParkwav, Birmingham, AL Sheet of 1 I" I r Address
2. Plant Vogtle ElectricGenerating Plant Unit 1 Name Waynesboro, GA 30830 WOO 1060107901 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by
  • Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voatle Expiration Date N/A Address
4. Identification of System 1201 / Reactor Coolant System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section Xl Utilized for Repaire or Replacements 19,V
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No PIPE PULLMAN POWER N/A N/A VI-1201-049-H002 1987 REPLACEMENT YES SUPPORT PRODUCTS
7. Description of Work Snubber PSA-35. serial #11248 was replacedwith a snubber PSA-35. serial# 11250 to support surveillance testing.
8. Test Conducted: Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[]

N/A M] Other 5 Pressure N/A PSI Test Temp. NIA OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct end this r placement conforms to the rules of the ASME Code, Section Xl. repal r or replacement Type Code Symbol Stamp N/A Certificate of athorization No. N/A Expiration Data NWA Signed ok,4JJv -

7 1 Owner or Owner's Designee, Title Team Leader Date I "LVI / i) C, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boiler Insoecticn and Insurance Co. of Connecticut of Harr Connic have Inspected the components described In this Owner's Report during the period 02/23/06 to 0" and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for.any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions C.* '(

In111pectrV¢Sgnature National Board, State, Province and Endorsements Date 2 1 t)0- &*MO(.

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl.

Traveler# 06043. q

1. Owner Southern Nuclear Operating Company Date 10130105 Name 40 Inverness Center Parkway, Birmingham,AL Sheet I of 1 Address
2. Plant Vogile Electric Generating Plant Unit Name Waynesboro, GA 30830 WO# 1060108301 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Autliarboalofl No. N/A PlantVootle Expiration Data N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19.0
6. identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer" Serial No. No. Identification Built or Replacement (Yea or N PIPE PULLMAN POWER N/A N/A VI-1201-097.H601 1987 REPLACEMENT YES SUPPORT PRODUCTS
7. Description of Work SnubberAD-73, serial#435 was replaced with a snubberAD-73, serial# 1202 to supportsurveillance testing.
8. Test Conducted: Pneumatic[]

Aydroatatic M Nominal Operating Pressureed WAj1 Other [] Pressure NIA PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Q.,Vj. Team Leader Date / 1!(,

Owner or Owner's Designee, TI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeoMMl and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut ot Ha" have Inapected the components described In this Owner's Report during the period 02123/06 to . /.ap-7 .fL-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning, the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In-" &,*A." -- Commissions 6qr. - ýr'&

Inilpectoea Signature National Board, State, Province and Endorsements Date DateA r? si/a. .'ogo.

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS £7'

. As Required By The Provisions Of The ASME Code Section XI Traveler# 06045

1. Owner Southern Nuclear OperatingCompany Date 10131106 Name 40 Inverness CenterParkway, Birmingham. AL Sheet 1 .I 1 Address
2. Plant Vogte Electric Generating Plant Unit Name Waynesboro, GA 30830 WO# 1060108601 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Slamp N/A Name Authorizaton No. N/A Plant Vogtie Expiration Date N/A Address
4. Identification of System 1204 / Safety InjectionSystem
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition. Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or No)

PIPE PULLMAN POWER N/A N/A V1-1204.0214H022 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-10, serial#15478 was replaced with a PSA-tO, serial#14986 to support surveillance testing.

S. Test Conducted: Hydrostatic Pneumatic[] Nominal Operating Pre-sure[]

NWA[] Other fl Pressure N/A PSI Test Temp. N/A -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ne n') Team Leader Date Et L. (

Owner or Owner's Deslgnee, Title%

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeorOla and employed by HartfordSteam Boiler Inspection and Insurence Co. of Connecticut of

-arfo. nnecticut have Inspected the components described In this Owner's Report during the period 02/23/06 to 1, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a lose of any kind arising from or connected- with this Commissions i-, "r'7 Inspettor's Signature National Board, State, Province and Endorsements

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler# 06046

1. Owner Southern NuclearOperatingCompany Date 10131/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1 of I Address
2. Plant Voogle Electric GeneratingPlant Unit Name Waynesboro GA 30830 WOfE 1060108701 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A PlantVootle Expiration Date N/A Address 4, Identification of System 1204 /Safety Injection System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Appllcable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

PIPE PULLMAN POWER N/A N/A Vl1-204-023-H002 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber AD-1603, serial #681 was replaced with a snubber AD-1601, serial # 531 to supportsurveillance testing.
8. Test Conducted: Hydrostatic r Pneumatic'] Nominal Operating Pressure-'

WA [f] Other 5 Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp IVA I Certificate of Authorization No. N/A Expiration Date N/A C8110 las Signed

. LI

. '-J,-**

Owner or Owner's Designee, Titfd Team Leader Deft+/-L CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georiala and employed by Hartford Steam Boiler Insoection and Insurance Co of Connecticut of Hartfor. Cncticu have Inspected the components described In this Owner's Report during the period 02/23106 to 1a nd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Coda,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report.. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions , -rt.

lnespectf's Sgnature National Board, State, Province and Endorsements Date D29b~Q2bist.

9. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS '7 As Required By The Provisions Of The ASME Code Section XI Traveler# 06047
1. Owner Southern Nuclear OperatingCompany Date 11/13/06 Name 40 Inverness CenterParkway. Blimingham, AL Sheet I of I Address
2. Plant Voglie Electric GeneratingPlant Unit 1 Name Waynesbomr, GA 30830 WON 1060108801 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voptle Expiration Date N/A Address
4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME SEC I11 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

PIPE PULLMAN POWER N/A N/A VI-1204-024-H029 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-3, serial #26805 was replacedwith a snubber PSA-3, serial# 28341 to support surveillance testing.
e. Test Conducted: Hydrostatic Q Pneumatic[-] Nominal Operating Pressure[]

N/A Other E Pressure N/A PSI Test Temp. N/A *F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed - CgMAJ*.* t( Team Leader Date i / I ,/

\jOwner or Owner's Designee, Tite

( CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Htfd Con have inspected the components described in this Owner's Report during the period 02/23/06 to0 Mand state that to the best of my knowledge and beliefi the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this aw-&-0 Commissions (LA PCY47-

,,A*u. ,*ob*

- F

- Iffspectd-iff Signafure National Board, State, Province and Endorsements Dete IS" Date I .4MI.

A 'Aobta

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler I 06048 Ll

1. Owner. Southern Nuclear OperatingCompany Date 10/31/06 Name 40 Inverness CenterParkway, Birmingham. AL Sheet of I Address
2. Plant Vogte Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 WO# 1060108901 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Cods Symbol Stamp N/A Name Authorization No. N/A Plant Votle Expiration Dote N/A Address
4. Identification of System 1204 / Safety Injection System,
5. (a) Applicable Construction Code ASME SEC /iI 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 19f89
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASM E Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

PIPE PULLMAN POWER N/A N/A VI-1204-047-HO03 1987 REPLACEMENT YES SUPPORT PRODUCTS 7.' Description of Work Snubber PSA. 1/4, serial #26457 was replacedwith a PSA-1/4, serial#35110 to support surveillancetesting, The transitiontube bolting was also replaced.

8. Test Conducted: Hydrostatic [] Pneumatlcr] Nominal Operating Pressure[]

N/A[s] Other [] Pressure N/A PSI Test Temp. N/A

9. Remarks See Item 7ý Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signedad *(L.JD/ .* 0 Team Leader Dateat ("L. 10 i Owner or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued'by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut of

-aro. Conecticut have Inspected the components described In this Owner's Report during the period 02123106 to IA( and state that to the "best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &19 75e.

Insi-etor's Signature National Board, State, Province and Endorsements Date J90 tem 4tnnt

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06049

1. Owner Southern Nuclear OperatingCompany Date 10/30/06 Name 40 Inverness Center Parkway, Birmingham,AL Sheet I of I Address
2. Plant . Vogitle Electric Generating Plant Unit 1 Nome Waynesboro, GA 30830 WO#A0400541 and 1060109001 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A PlantVoatle Expiration Date N/A Address 1208 / Chemical and Volume ControlSystem
4. Identification of System
5. (a) Applicable Construction Code ASME SEC ill 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board. Other Year Replaced, Stamped Component. Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

PIPE PULLMAN POWER N/A N/A Vl-1208-488-H021 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Descrlption of Work SnubberAD- 151, serial#416 was replacedwith a snubberAD-151, serial# 588 to supportsurveillance testing.

The flanged end sub-assembly was previously replacedin the replacement snubberserial# 588 under Traveler # 04115 and WO# A0400541.

8. Test Conducted: Hydrostatic C] Pneumatic[] Nominal Operating Pressure[]

N/Ax- Other 5 Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XL. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ ( L.--* Team Leader Date 1.iLLL/...,

4 Owner or Owner's Designee, TitieO CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia - and employed by HartfordSteam Boiler Insoactionand Insurance Co. of ConnecticA# 'of Hartford onecticut have Inspected the components described In this Owner's Report during the period 06/21/04 to ad and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, conderning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &if 7;M ispecls Signature National Board, State, Province and Endorsements Date iI*- j/ _

'ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06051 y

1. Owner Southern Nuclear OperatingCompany Date 11/01/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1 of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesbom, GA 30830 WO# 1060109401 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootle Expiration Date N/A Address
4. Identification of System 1301 / Main Steam System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)App!lcable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. identification Built or Replacement (Yes or No)

PIPE . PULLMAN POWER N/A N/A VI-1301-104-HO06 1987 REPLACEMENT YES SUPPORT RODUCTS

7. Description of Work Snubber PSA-35, serial#1 144a was replaced with a PSA.35 serial#11484 to support surveillancetesting.
8. Test Conducted: Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[]

NIA' Other 5 Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date A/A Signed w no Team Leader Data A Owner or Owner's Designee, Titib CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boller and Pressure Vessel inspectors and the State or Province of Georala and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Ha=% nncticut have Inspected the components described in this Owner's Report during the period 02123/06 to Z. and state that to the best of my knowledge and belief, the ,Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspaln Ins*----- -____,________Commissions C-^,. v'.

li-fpect~r'8 Signature National Board, State, Province and Endorsements Dote A a t.&~~

I.l ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS

-I As Required By The Provisions Of The ASME Code Section Xi 4/t Traveler# 06052

' 1. Owner Southern NuclearOperating Company. Date I0/30/06 Name 40 Inverness Center Par*WaY, Birmingham. AL _.Sheet 1of Address

2. Plant Voglie Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 WO# A051767536 and 1060109501 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorztlon No. N/A Plant VogUe Explrtion Date N/A Address
4. Identification of System 1301/Main Steam SYstem
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1§ CodeCas A (b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 19§1
6. Identification Of Components Repaired or Replaced and Replacement Components Nenal Nj Repaired, ASME Cod Name of Name of Manufacturer - Other Year Replaced, Stampedi Component Manufacturer Serial No. No. identification Built or Replacement .(Yes or No PIPEORTN U OL UTPOWER NuAcIe A VI-1301-105-HO03 1987 REPLACEMENT YES SUPPORT P FRODUCTS
7. Description of Work SnubberAD-12501. serial#132 was replaced with a snubberAD-12501, serial# 18 to supportsurveillance testinqg The planetarystandoff flat head screws were previously replacedin the replacementsnubber serial# 18 under Traveler # 06081 and I WO# AO5176 7536.
8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Pressure[]

WA [] Other Q Pressure N/A PSI Teat Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Data N/A Signed , , Team Leader Date II / l/l ,

Owner or Owner's Designee, TitIel 1=

F CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the Stste or Province of Geornla and employed by Hartford Steam Boiler Inspectlon and Insurance Co. of Connecticut l ol Hartord..Coninecficut have Inspected the components described in this Owner's Report during the period - -02120 to 0 and state that to the beat of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xh.

By signing this certificate, neither, the Inspector nor his employer-makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &#* T.45'fI

--- In6spectofi Signature National Board, State, Province and Endorsements Datea

)

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS 4 As Required By The Provisions Of The ASME Code Section XI Traveler# 06053 I

1. Owner Southern Nuclear Operatin Company Date 11/01/06 Name 40 Inverness Center Parkmav. Blrminoham. AL Sheet 1 off Address Unit 1
2. Plant Vogtle Electric GeneratingPlant Name Waynesboro, GA 30830 WO 1060109601 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorizatdon No. NAM Plant Vootle Expiration Date N/A Address
4. Identification of System 1301 / Main Steam System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, "N-249-1 Code Cas D (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 19g S. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampedl Component Manufacturer Serial No. No. Identification Built or Replacement (Ye or NoL 0

PIPE PULLMAN POWER N/A N/A V1-1301-106-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber AD-5501, serial #333 was replaced with a snubber AD-5501, senal# 242 to support surveillance testing..
8. Test Conducted: Hydrostatic Q Pneumatic[] Nominal Operating Pressurefl N/A{[ Other El Pressure N/A PSI Test Temp. N/A *F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A -

Signed ln Team Leader Date 'Lo

( Owner or Owner's Designee, Tlt14I CERTIFICATE OF INSERVICE INSPECTION -

I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Gporala and employed by Hartford Steam Boiler Insoectlon and Insurance Co. of Connecticut 1of Hartford, C u have Inspected the components described In this Owner's Report during the period 0 120/061 to ZQa and state that to the best of my knowledge and belief, the Owner has performed examinations and takten corrective measures described in Athis Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins **. Commissions C!4. " ."I Inspectors Signat9e National Board, State, Province and Endorsements Date Al: boa. - AOe*:

4 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI y/

Traveler# 06054

1. Owner Southern Nuclear Operating Company Date 11/01/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1060109701 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A

. Name AuthorizatIon No. N/A Plant Vogtle Expiration Date N/A Address.

4. Identification of System 1301 /Main Steam System
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1
  • Code Cas 9 (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19f8
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampeds Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or NO)

PIPE PULLMAN POWER N/A N/A VI-1301-110-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS

7. Description of Work Snubber AD-151L, serial#700 was replacedwith a snubberAD-151L, serial # 486 to support surveillance testing.

I

5. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating PresaureQ NIA Other Pressure N/A PSI Test Temp. N/A -F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE V We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of A~thorization No. N/A Expiration Date N/A -

Signed )4oj.vý( A U -s Team Leader Date it__________

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of - Georala and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut Iof Hartford Qonnectlcut have Inspected the components described In this Owner's Report during the period 020 to and state that to the 'best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this CM ts1a ACommissions (go ?Jrtf, In~boectorrg Signature National Board, State, Province and Endorsements IDate ,,29 J . o_. .

I. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI e

Traveler # 06055

1. Owner Southern Nuclear OperatingCompany Date 10/3/6 I Name 40 inverness CenterParkway, Blrmlngham, AL Sheet 1 of L Address
2. Plant Vogtle ElectricGeneratinoPlant Unit I' Name Waynesboro, GA 30830 WO# 1060109901 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp W/A Name Authorization No. N/A Plant Voctle Expiration Data W/A Address
4. Identification of System 1302/Auxiliary Feedwater System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, " N-249-1 Code Cas a

(b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 1989

6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Nol PIPE PULLMAN POWER N/A N/A VI-1302-107-H01 1 1987 REPLACEMENT YES SUPPORT PRODUCTS

.7. Description of Work Snubber AD-503, serial#313 was replacedwith a snubber AD-503, serial # 201 to support surveillance

& Test Conducted: Hydrostatic [ Pneumatic[] Nominal Operating Pressure[]

NIAE] Other I Pressure N/A PSI Test Temp. N/A -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xh repair or replacement I Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A I P Signed STeneador Date #I k*wner or Owner's Designeb, Tide CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georcia and employed by Hartford Steam Boiler Insoection and Insurance Co. af Connecticut of

-lafo. Coe have Inspected the components described in this Owner's Report during the period 02-20/06 tond stats that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinatIons and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall K =Commissions be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this

&A.

Inslfector*pV1gnntune National Board, State, Province and Endorsements

>e te 7 ,L.~ ' tl,

ORIGINAL FORM NIS-2 OWNER'S REPORT-FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi ,-

Traveler# 06057

1. Owner Southern Nuclear OperatingCompany Date 11/07/06 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of I Address
2. Plant Vootle Electric GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1060110101 and A0000644 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogte Exopilron Date NALI Address
4. Identification of System tqn~ IA. .viIInr.j nwtu~ntnr ~utt4n1 1302IAuxilia Feedwater-q-tem S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applilcable Edition of Section Xl Utilized for Repairs or Replacements 19.6
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampsed Component Manufacturer Serial No. No. Identification Built or Replacement or No) aYes PIPE SUPPORT PULLMAN POWER PRODUCTS N/A N/A VI-1302-109-HOO9 1987 REPLACEM&ENT YES I.
7. Description of Work Snubber PSA-lO, serial#15950 was replaced with a snubberPSA-1O, serial# 15477 to support surveillance 1 testing. The telescoping cylinder In the replacementsnubber serial# 15477 was also replacedunder Traveler# 01102 and I WO# A0000644.

?

6. Teat Conducted: Hydrostatic [] Pneumatic[] Nominal 'Operating Pressure[]

I NAI Other [] Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached I

CERTIFICATE OF COMPLIANCE We certify that the atements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed LearneaderDate 0I JjOwner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the Slate or Province of GeoR7ia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. Conneccut have Inspected the components described In this Owner's Report during the period 09/10/01 I to M * - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section 1Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins

  • Commissions Goi 7T5 IribpectWSlgnature National Board, State, Province and Endorsements Date.AM&=AID&

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 06058

1. Owner Southern Nuclear Operating Company Date 10/31/06 Name 40 Inverness Center Parkway,Birmingham, AL Sheet _ __ of Address
2. Plant Vogtle Electic GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1060110201 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voctle Expiration Date N/A Address
4. Identification of System 1302/Aux~liary Feedwater System _
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cas (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components Descriptlon of Work SnubberAD-501, serial #574 was replaced with a snubber AD-501, serial# 567 to support surveillance testing.
8. Test Conducted: Hydrostatic [] Pneumatic[:] Nominal Operating Pressure[

NIA1 Other [] Pressure N/A PSI Test Temp. A/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE i We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/AI Signed a L Team Leader Date loc.*

1111,1101 Owe r Owner's Dein ttl e,

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ge0o1ia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartord. Connect have inspected the components described In this Owner's Report during the period 020/

to. a= and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section!Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning .the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with ihis in eoon.

Ida- - Commissions (&4- 7:TtA

'MarpecteA Signature National Board, State, Province and Endorsements Date .2* L _.. Anate

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI -1/

Traveler# 06059

1. Owner Southern Nuclear Operating Company Date 11/01/06 Name 40 Inverness CenterParkway,Birmingham, AL Sheet 1 of 1 1 Address
2. Plant Vogie Electric GeneratingPlant Unit 1 Name WaynisboWo GA 30830 WO# 1060110301 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Me intenance Department Type Code Symbol Stamp N/A Name Authorizatlon No. N/A P1ent Vootle Expiration Date AVA-Address
4. Identification of System 1RN* / I~n~rnt,}nh, .*u~atnr 1305 / Feedwafor Q-tem
5. (a) Applicable Construction Code " ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Cat a (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19A2
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampem Component Manufacturer Serial No. No. Identification Built or Replacement as or No)

PIPE PULLMAN POWER N/A N/A VI-1305-058-HO03 1987 REPLACEMENT YES I SUPPORT PRODUCTS _

7. Description of Work Snubber PSA-100, serial #2505was replaced with a snubberPSA-100, serial # 2402 to support surveillance testing.
8. Test Conducted: Hydrostatic Q] Pneumatic[ Nominal Operating PressureD NfA[ Other [] Pressure N/A PSI Test Temp. N/A'
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. AVA Expiration Date N/A -

CL.. \ . I Signed Team Leader Date  %

I _ k Owne or Oner's Designee, TilteI CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of - Geomia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hardon c have Inspected the components described in this Owner's Report during the period 02/20/06 1 to / 2 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section fXl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Ig on.

Date* be'--'d*'* of~ectSl***--*-* "-Commissions ,gnatu "SSt c d 11setf intr National Board, State, Province and Endorsements Date AS t b;_ae b

FORM NIS-2 OWNER'S RQ W M 4 TS 6TC~OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 06O62L1

1. Owner Southern Nuclear OperatingCompany Date 11102/06 Name 40 Inverness Center Parkway, Birmingham,AL. Sheet of Address
2. Plant Vogte Electric Generating Plant Unit Name Waynesboro, GA 30830 WO# 1060321601 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorizatlon No. N/A Plant Voatle Expiration Date W/A -

Address I

4. Identification of System 1302 / Auxiliary FeedwaterSystem i
a. (a) Applicable Construction Code ASME SEC III 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 1989
6. . Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Manufacturer Board Other Year Replaced, Stomped Name of Name of Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or NO' PIPE PULLMAN POWER N/A N/A VI-1302-107-H014 1987 REPLACEMENT YES I SUPPORT PRODUCTS _
7. Description of Work Snubber AD.501, serial #166 was replacedwith a snubberAD-501. serialN689 to supportsurveillance testirl.

Test Conducted: [. Hydrosatic [] Pneumatic[] Nominal Operating PresaureQ-Other [] Pressure N/A PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp V/A Certificate of Authorization No. N/A Expiration Date MIA -

Signed or Date &

CERTIFICATE OF INSERVICE INSPECTION i I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala - and employed'by HartfordSteam Boiler 'Inspection and Insurance Co of Connecticut I of Harford, Connecticut have inspected the components described In this Owner's Report during the period 02/23/06 to *a and state that to the best of my knowledge and belief, the Owner has performed examinations and tsaken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section 1XI.

~I/

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer laill be liable.in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions LA . 1&1 r npedis Signature National Board, State, Province and Endorsements Date At bi. O ,,(a L

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 06068 I/

1. Owner Southern Nuclear OperatingCompany Date 11/15/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1 of Address 1L
2. Plant Vogtle Electric GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1060344801 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenancebepartment Type Code Symbol Stamp N/A Name Authorhadon No. W/A PlantVootfe Expiration Datm N/A Address
4. Identification of System Sr., /.d~~

0 ý ,D.uf ~ a

% UM=111 exe.1-1111 I S. (a) Applicable Construction Cede ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements l98f

6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Stamped Name of Manufacturer Board Other Year Replaced, Name of Component Manufacturer Serial No. No. Identification Built or Replacement or NP4 aYes PIPE PULLMAN POWER N/A N/A Vl-1204-023-HO10 1987 REPLACEMENT YES SUPPORT PRODUCTS -
7. Description of Work Snubber PSA-1O, serial #15827 was replacedwith a snubber PSA-1O, seratl# 16100 to supportsurveillance testing,
8. Test Conducted: Hydrostatic [ Pneumatic[] Nominal Operating Pressure[J WAE'J Other ] Pressure N/A PSI Test Temp. N/A OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement I Type Code Symbol Stamp N/A L Certificate of Authorization No. N/A Expiration Date N/A Signed Team

........ Leader Date k I..

r ~ & n~L WTFfA&eiF INPRI IJPIT -

CBRTII:I*ATB d3F INSBRVICF IN*;PIF*TION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by HartfordSteam Boiler Ins"ection and Insurance Co. of Connecticut I of Hartfd n have Inspected the components described In this Owner's Report during the period 03/16M6 I to a( and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of. any kind arising from or connected with this

~P~M~a-.~AL 4 .. eO-~Commissions irv v"- i InspeDt -r's Signature - National Board, State, Province and Endorsements Date A10V~. 7006

FORM NIS-2 OWNER'S REQ 91Q 4JRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06075

1. Owner Southern Nuclear Operating Company oDat 11/O8/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet of Address
2. Plant Voglie Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 WO# 1049001003 andPO# 7063483 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. A/A Plant Vogtie Expiration Data N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Constuction Code ASME SEC III 19 71 Edition, Summer 1972 Addenda, N/A Code Cas 0 (b)Applilcable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification 1u3it or Replacement e REACTOR COMBUSTION 8971 21668 1-1201-V6-001 1076 REPLACEMENT YES VESSEL ENGINEERING,*

INC. _

7. Description of Work The male flange assembly on the Instrumentport column was replacedby a new design core exit thermocouple I no*de assembly (CE7NA). The CETNA assembly was Installed on vessel penetrations75, 77, and 78 in accordance with DCP -

1049001001.

8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Preasure[']

NIA[' Other [] Pressure N/A PSI Test Temp. N/A

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _~1 " i~o WA.)A.L Owner or Owner's Designee, Titt 4 Team Leader Date LL 1 1_

kX..

i .

I S. -

CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel inspectors and the State or Province of Georgila and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut I of Hatrdn have Inspected the components described In this Owner's Report during the period 05/09/06 I to d and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer s~hal be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with Ihis In/LLI44iA,9 Commissions e-*. 7..-6

'--1urfpectoftSignature National Board, State, Province and Endorsements Date -7 7 AV ja.,

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler#- 06079 9

1. Owner Southern NuclearOperating Company Date 1013/015 Name 40 Inverness Center Par*way,Birmingham, AL Shest I of Address
2. Plant Vogile Electric Generating Plant Unit I Name Waynesboro, GA 30830 WO# 1053519701 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authoriation No. N/A Plant Vogtle Expiration Date N/A Address
4. identification of System 1201 / Reactor Coolant System
5. (a) Applilcable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cal a (b)Appticable Edition of Section XI Utilized for Repairs or Replacements 19&9 S. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No PIPE PULLMAN POWER N/A N/A VI-1201-030-H601 1987 REPLACEMENT YES SUPPORT P RODUCTS

/ 1-

7. Description of Work Snubber AD-151, serial #482 was replacedwith a snubberAD-151, serial # 133 to facilitate removal andinstallation of the Pressurizercode safety valves. I
8. Test Conducted: Hydrostetlic Q Pneumatic[- Nominal Operating Presaure--

N/A[ Other [] Pressure N/A PSI Teat Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A L Certificate of A thorization No. N/A Expiration Date N/A Signed ,ATmLeader Datea Owner or Owner's Designee, Thse Ie.

CEiTIFICATE OF INSEHVI;E INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boilor and Pressure Vessel Inspectors and the S or Province of Gearola . and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut Hartfrd Connecticut have inspected the components described In this Owner's Report during the period 05/WW to L and state that to the best of my knowledge and belief, the Owner has performed examinations and ta ken corrective nmeasures described in this Owners Report in accordance with the requirements of the ASME Code, Section SXl.

r By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning Ithe examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer sh all be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with titis In _________________

Commissions &0 ZX&.

- t~apector's~ignature National Board, State, Province and Endorsements Date It4 Aoi.Ae1

1 ORIGINAL 5 SECTION Xl REPAIR/REPLACEMENT TRAVELER PAGE 1 OF 3 TRAVELER: 06081 REPAIR E5 REPLACEMENT I


ASSOCIATED DOCUMENTS-- COMPONENT -------

WO: A051767. 36 s"V%-g CODE CLASS: ASME III Ci. 1 NF CR: 2006105749 TAG NO: A-2117-SNUBBERQO DCP: N/A DESCRIPTION Spare Snubber (AD-1250*l1411

-"6THER: AX4AQ56-10006 SERIAL NO: 18 WORK DESCRIPTION: Install replacement Planetary standoff flat head screws.


EXAMINATION / TEST REQUIREMENTS -------

N/A VT-1 N/A VT-2 N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement No [ Normal / Expected Wear [JALARA LI DCP N EQ Checklist 5 Yes Justification:

Intended life if less than design life of repaired item:

REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operatina Co.


INITIAL REVIEW-EGN DATE, HOLD POINTS AWE - E051,W66 YES Z NONE ISI ENGINEER IUqMCNN(MMNER *X,* E YES YES *. NONE IR-*_J NONE HOLD PO ANII j *, []j YES NONE


FINAL REVIEW -----

SIGNATURE DATE "NT R DkTE4 D

ISI ENGINEE AWE 4 REMARKS: _See. .*t-, . -Tr..,,eerd -c'or ,'-.S-.

rIll E [-

rANI--nn! i LDATEur

Il I

1 ORIGINAL t TRAVELER NO: 06081 ASME SECTION Xl TRAVELER INSTRUCTION SHEET I

-WO: A051767536 PAGE 2 OF 3 SEC. XI:*

STEP TRAVELER.WORK EXAMINERI ANI.....I..

MAINY ,, ,_,.,

NO.. '...INSTRUCTIONS. RWO W/Hi INIT/DATE W/l. INIT/DATE,

1. Ensure the serial number, heat Maint.

and/or trace code number of the __-__

replacement part(s) is entered on _

the JML. If the part does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the JML. _

2. Verify the serial number, heat and/or COC H , _

trace code number of the replacement

_ / _ __

part(s) matches what is recorded on M ______-,

the JML or the applicable documen- S '.1, 5 _

tation. If the part has no markings, _

utilize the PO, MIR and Une Item _

numbers on the warehouse identifi- _

cation label. _

3. Verify that the ASME Code Class CQC H _

for the replacement part(s) matches or ___

exceeds that of the component in _

which it is being installed. .

4. Install replacement part(s) in spare Maint. ",_,_ ' _'__

snubber per procedure 27362-C. CQC , _/-__ -__

O

O ORIGINAL 0 ASME SECTION XI BILL OF MATERIALS TRAVELER 06081 WO A051767536 PAGE 3 OF 3 REPLACEMENT.- CODE ED., ADD. &CASES MATERIAL SPEC REPLACEMENT ITEM. ASME SECTION XI -t

.MATERIALICOMP REFERENCE ITEM ORIGINAL .INL-- OG HEAT, TRACE CODE. VISUAL EXAMINER DESCRIPTION -DRAWING NO. REPLACEMENT REPLACEMENT OR SERIAL# VERIFIC# 110 3 ea. Flat Head AX4AQ56- 136 1977W1977 SA564 TY 630 v-. ao.t,/t, Screws 10006 ___T7 W [q77

_ SA &-T5 W,6W/J COMMENTS: -)o,,e_

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06082

1. Owner Southern Nuclear OperatingCompany Date 03/05/07 Name 40 Inverness CenterParkway, Birmingham, AL Sheet of 3 Address
2. Plant Vogtle ElectricGenerating Plant Unit 1 Name WO# 1061048701 Waynesboro, GA 30830 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant VogUe Expiration Date N/A Address
4. Identification of System 1208 / Chemical and Volume Control System
5. (a) Applicable Construction Code ASME SEC I11 19 74 Edition, N/A Addenda, N/A Code Case (b)Aopllcable Edition of Section Xi Utilized for Repairs or Replacements 198L9
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampeod Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

VALVE FISHER 6499458 4704 IFV0121 1979 REPLACEMENT YES I CONTROLS CO.

7. Description of Work Valve plug was replaced.A copy of Form N-2 for the replacement plug Is attached.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[]

NIA] Other Q Pressure N/A PSI Test Temp. W/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Team Leader Date

'~OA I Ownr D ln .Ti Owner or Owner's Dasianee. Title I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the St'ate or Province of Geomla aand employed by HartfordSteam Boiler Insoection and Insurance Co. of Connectwlcu of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 07/31/06 to 7 - o - eand state that to the best of my knowledge and belief, .the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section !Xl.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ihe examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this

_ _ _ _ Commissions. 7s.4 l rpector'sgnature - National Board, State, Province and Endorsements Date 2,w 9~ 6

STr"e~eA4'X-2.4 FORM N-2 CERTIFICATE HOLDERS DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by tie Providous of the ASME Code, Section m Not to exceed One Day's Production Pg. 1 of I 25-N230123557 I. Manuikctured and cetfled by wrutle~ rVI?,?,a C hW'l mir. 1564 anirr TTU PbiC rrc 1 CfEACA IWU A tAB CO (nunu and addres afNFT Cartificate Holder)

2. Mamadhctred for muckor 3850 1-if eld QA ww"4 (namne and address of puihas)
3. Location oftsimtllation V-#U Electric Gamatina PIS Q2 7921 Rim Road w ..POD- GA 30RIn (name an address) r nA47O []I6tf 75 IC*t W/A 2ont
4. Type i2A657£ mov.

w1k 2001 12A6S76 Rev. C (drawin3 no.) QnwIr spee no.) (tesie -mmo) (CMN (yearbuill)

IA*A lr- A ,, J-

5. ASME Code. Section III: I,.,. "mS~ fflE I (afition) (addenda date) (Cio) (Code Cue no.)
6. Fabrlcated in accordance with Cust. Spec. (Div. 2 only) N/A Revision H/A Dole N/WA (no.)
7. Rwemb: Des:.l ASME BYFC. SEC. MI1974 Ed iton. No Addatded C=a 2 Other: ASM. B-Vc, SEC. 0 1919 Edid, No dde!d, Clau 2
8. Noa. thicknme (in.) N/A Min. deslI Odtcla (n.) N/A Dia. ID (ft &in.) N/A Length ovewall (ft & in.) N/A
9. What applicabte. Cerifcate Holders' Dat Reportsreus eahied for each item of this report:

ha or Apputenancc Heat Number Part or Appurtfnance Heat Number I Serial Number Salal Number (1) A17258-1 721402-1 (26)

(2) 4 (27)

(3) .5 (2C)

(4) (29)

(5) (30) ________________ I (6) (31)

(V) (32)

(0) (33)

(9) (34)

(10) (35)

(13) (36)

(12) (37)

(13) (38)

(14) (39)

(15) (40)

(41)

(42)

(43)

(44)

(20) (45)

(21) (46)

(22) (47)

(23)

(24)

(25)

(48)

(49)

(5O) 4 1_____________________

10. Design Pmeum 2735 Psi. Temp. 200 OF. Hydra. test pressure N/A at temp. 'P (when applicable)
  • Supplenmional hioromtiom in the form of M, sketches. or drawnns may be ucd provided (1) siue is ! 112xIi, (2) Infom idonIn ttent 2 and 3 on this Data Report a included onMaC sheek ()mech sheet Is numced and the number ofsheets is recorded at the top ofthis fann.

See+ 3oQ3 FORM N-2 (back)

Mft. Serial No. A17258-I CERTIFCATION OF DESIGN Design specificatito certified by Heavy P. Leonard P.A. State PA PC& no. 23938-B (when almicab"e)

Deaign remt*certified by WA P.E. State NA Re. no. MIA

(,wm applicable)

CERTIFICATE OF SHOP COMP'IANCE We einuify dug the statamets mnde in ths rempoare aem et and "hanthis (these) Plug/Sten canrmn to the rules of tnsus ion ofdOe ASME Code. Section M.

NPT Certfiate ofAutlmrinon No. - 1930 Uste 11-11-2001 Dafte oM301 Name FISHER 0 ONTROLS INT'L INC Sg WP Cutifleata Holder)

CERIIFICATE OF SHOP INSPECTION I. theund -gilndI holding a valid osmsoaiason Ismued by the National Board of Boller and Pressure Vessel Iuspectors and the statc or Province of JOWAI mud egleyed by HARTFORD S.A.L & L CO I of HARTFORD.C ONN have inspected themeier. descrbed in this Data Report an P-7an-Wste---5 a E dim to the best ofnW kmwedgn end belief, the Cutifie Holder has fWbricsted these parse or apputenaness In accordance-with the ASME Code. Section Ill. Each parlisted has bern atorimed for atuulng on the date shown above.

By signpin this eollficaWe neither the Inmpect nor his employer wakes any vamnty.expressed or implied, concaning the equipment desm'bed in this Data Repmt Fwtammoe neither dt inspectornor his eunplor shall be liable in my mnaner for any pesonal injury or pmiroty damage or imo ofany kind arising frn or connected

'Jith this inspection.

(Authiorized Inspector) (Nal. Bd. and. endorsements) state or peav. uud no.)!

2-36-6.doc

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 06086. '1

1. Owner Southern NuclearOperatingCompany Date 11/07/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I of Address ,
2. Plant Vogde Electric GeneratingPlant Unit Name Waynesboro, GA 30830 WO# 1061721901 andA0100517 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp WAL Name Authoriation No. N/A PlantVoatole Expiration Data N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Cat D (b)Applicable Edition of Section Xi Utilized for Repairs or Replacelments 1989
6. Identification Of Components Repaired or Replaced and Replacement Components Name-of Name of I-National Manufacturer .Board Other Year Repaired, Replaced, ASME Code Stamps Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

PIPE PULLMAN POWER N/A AL/A VI-1201-030-H020 1987 REPLACEMEN7*d YES I SUPPORT PRODUCTS

7. Description of Work Snubber PSA-3. seri*l 129749 was replaced with a snubberPSA-3, serial# 26939 to supportsurvellance testing. The telescoping cylinder in the replacement snubber serial# 26939 was also replacedunder Traveler#01071 and WO# A0100517.
8. Test Conducted: Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[]

N/A [x] Other 5 Pressure N/A PSI Test -Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE -

We certify that the statements made In the report are correct and this replacement conforms to the rules of t e ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp WA 4A~

Certificate of Authorization No. N/A Expiration Date N/A "

Signed Teem Leader Date .:

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors: and the Ste or Province of Georole end employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 06I06/01 to *and state that to the best of my knowledge and belief, the Owner has performed examinations and talEon corrective measures -described In this Owners Report In accordance with the requirements of the ASME Code,.--"Section -Xl" By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inslne~ton ...

p Commissions- o B t nt It4 11-ý ectot%

ignaureNational Board, State, Province and Endorsements ante "A sy. eof.

ORIGINAL

.I FORM NIS-2 OWNER'S REPORT FOR REP4IRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 06087 9

1. Owner Southern Nuclear Operating Company Date 10123/06 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit I I

Name Waynesboro, GA 30830 WO# 1061761501 Address Repair Organization P.O. No. Job No., etc.

3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtile Expiraton Date N/A Address
4. Identification of System 1208 / Chemicaland Volume Control System
5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, N/A (b)Applicable Edition of Section Xi Utilized for Repairs or Repiacements 1989 Code Case I
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, StampeZ Component Manufacturer Serial No. No. Identification Built or Replacement or N)

PIPE PULLMAN POWER N/A N/A V1-1208-001-HO28 1987 REPLACEMENT YES I SUPPORT RODUCTS I

7. Description of Work Snubber PSA-3, serial#20228 was replaced with a PSA-3 serial #25504 to facilitatemaintenance on valve 1LV0460.

S. Test Conducted: Hydrostatic [] Pneumatic[- Nominal Operating Pressurefl N/A j*] Other [] Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A I Signed 0j.A-S-u Team Leader Date

\J Owner or Owner's Designee, Tile CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeorIa and employed by Hartford Steam Boiler Inspection and insurance Co. of Connecticut I of

-etfo. Connecticut have Inspected the components described In this Owner's Report during the period 09128/06 .

to *and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, SectionI X.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a losq of any kind arising from dr connected with this In .WA# J Commissions .Ah (_ 7&'AI IThspe~PsSlgnitu'i - National Board,-9tote, Province and Endorsements Date Jo ,JI. ,,oof.

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Cede Section XI Traveier# 06088

1. Owner Southern Nuclear OperatingCompany Date 12/13(06 Name 40 Inverness CenterParkway, Birmincham,AL Sheet of 1 Address
2. Plant Vogte Electric Generating Plant Unit

-Name Waynesboro. GA 30830 WO# 1054157401 Address Repair Organization P.O. No., Job No., etc.

3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootle Expiration Date N/A Addresis *
4. Identification of System 1202 / NuclearService Cooling Water System 1516-2, 1567, 163541, 1649,
5. (a) Applicable Construction Code ASME SEC III 19 74 Edition, Summer 1975 Addenda, 1677& 1712 Code Case
  • (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampesd Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or No)

VALVE ANCHORIDARLING E9001-133-4 N/A 1-1202-U4-471 1984 REPLACEMENT YES VALVE CO.

7. Description of Work A valve bonnet stud was replaced.
8. Test Conducted: Hydrostatic j] Pneumatic[] Nominal Operating Pressure[]

N/A (K Other E] Pressure N/A PSI Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A' Certificate of Authorization No. N/A Expiration Date N/A qi*

Signed Owner o rl r Team Leader Data Owner or Own er's Designed, Title V-CE*RTIFIC*ATIE OF INSERHVICE INSPIECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georal " and employed by HartfordSteam Boiler Insoectlon and Insurince Co. of Connecticut of Hartford. Connecticut have Inspected .the components described In this Owner's Report during the period 09/28/06 to ' /-I_n-r. - , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer slal be liable In any manner for any personal Inlury or property damage or a loss of any kind arising from or connected with this Commissions &*.  ?'"&-

-' i~speo&r's Signature National Board, State, Province and Endorsements Onts as MAt 2.OD'

ORIGINAL 5 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Travelar# 06090

1. Owner Southern Nuclear Operatinr Company Date 1/2/7 Name 40 Inverness Center Parkway.Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle ElectricGenerating Plant. Unit 1 Name Waynesboro, GA 30830 WO# 106176"01

. Address Repair Organization P.O. No., Job No., etc.

3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voctle Expiration Date N/A Address
4. Identification of System 1201/Reactor Coolant System 1484-1, 1484-2
5. (a) Applicable Construction Code ASME SEC III. 19 71 Edition, Summer 1972 Addenda, 1528-3 Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1982
6. identification Of Components Repaired or Replaced end Replacement Components National Repaired, ASME-Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

STEAM WESTINGHOUSE GAGT 1881 11 1-1201-B6-002 1981 REPLACEMENT YES GENERATOR ELECTRICCORP.

7. Description of Work Steam generator #2 hot leg primary manway stud numbers 9, 10, and 14 were replaced.
0. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating PressureX' Other C] Pressure N/A PSI Test Temp. N/A "F
9. Remarks See Item 7 Applicable Manufacturer's Dats Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Cse 0IT-I07 Signed l Team Leader Date I SOwner or Owner's Designee, Tfle "

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut of Hartford. Connecticut have Inspected the components described in this Owner's Report during the period 10/03/06 to i -,l -- aob1, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins _______--____________Commissions fir4. 2!,V4 0 Date MIspec

",.f-bb'7

'a Signature National Board, State, Province and Endorsements

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler# 06091 (A)

1. Owner Southern Nuclear OperatingCompany Date 11/06/06 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I Of 4-e3 01 Address
2. Plant Vogtle Electric Generating Plant Unit Name Waynesboro. GA 30830 WON 1051821701 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp NWA Name Authorization No. W/A Plant Voqtle Expiration Date NI/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME SEC III 19 71 Edition, Summer 1972 Addenda, 1501, N-3-10 Code Ca.

I (b)Appllcable Edition of Section XI Utilized for Repairs or Rplacements 19&9'

6. Identification Of Components. Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yeas or No)

VALVE FISHER 5909459 3253 1PV0455B 1981 REPLACEMENT YES CONTROLS CO.. __"

7. Description of Work Valve vee-ball was replaced.A copy of Form N-2 for the replacement yea-ball is attached.
8. Test Conducted: Hydrostatic [ Pneumatic[] Nominal Operating Pressurel]

NIA [X] Other Q] Pressure N/A PSI Test Temp. N/A

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Owner kJ T.t Team Leader Date it 'Le

\,I Owner or Owner's Designee, TitfibU

.CERTIFICATE OF INSERVICE INSPECTION I 1, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessei Inspectors and the State or Province of Geor&Al and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut

.Harr Conctut have Inspected the components described In this Owner's Report during the period 10/05/06 ..

to IX vi *, and state that to the best of my knowledge .and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.

'By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his.employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with Wehl Ine - - . -, . Commissions u , -e". " I

ýý l*eto--"l. Signature vNational Board, State, Province and Endorsements Date .9 'AMJo jc "

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL 1AMme5ICr 0609 1 NUCLEAR PARTS AND APPURTENANCES* S teet 2-4 f3 As Required by the Provisions of the ASME Code,Section III Not to exceed One Day's Production Pg. I of I.

025-N230173824 I. Manufisacred and certified by FISHER CONTROLS INT'L LLC. 205 SOUTH CENTER STREET, MARSHALLTOWN. IA. 50158 (name ed address ofNPT Certificate Holder)

2. Manuf*ctured for Control Southern Nuclear Plants, 3850 Lakefield Dr. Strwmni, GA 30024 (name and address of purchase)
3. Locationofinstallation Voldc Electric Gen. Plant. 7821 Rivet Rd. Wayneboro. GA 30330 (name and address)
4. Type I V9098 Rev. H SA351 CF8M 70 KSl N/A 2005 (drawing no.) (mat'l. spec. no.) (tensile Strength) (CRN) (year built)
5. ASME Code, Section I1:

'97'7 Summer 1972 N/A 1971 Sumiaw 1977 (edition) (addenda due) (class) (Code Case no.)

6. Fabricated in accordance with Consl. Spec. (Div. 2 only) N/A Revision N/A Date N/A (no.)
7. Remarks: Design: ASME BPVC Sec 111.1971 Edition, Summer 1972 Addenda, Class I Othe.: ASME BPVC Sec 0111989 Edition, No Addenda, Class I
8. Nomr. thickness (in.) N/A Min. design thickmess (in.) NIA Dia. ID (ft &un.) N/A Length overall (ft &.in.) N/A I
9. When applicable. Certficate Holders' Date Reports re atarched for each item of this report

-Y --

Part or Appurtenance Heal Number Par or Appurtenance He Number Serial Number Serial Number (I) A!H6399-1 MXIO SN W35" (26)

(2) (27)

(3) (28) 4 --

(4) (29)

(5) (30)

(6) (31)

(7) 02)

(8) (33)

(9) (34)

(10) (35)

(11) (36)

(12) (37)

(13) (38)

(14) (39)

(IS) (40)

(16) (41)

(17) (42)

(I8)

(43)

(19)

(44)

(20) (45)

(21) (46)

(22) (47)

(23) (48)

(24) (49)

(25) (50) _ _ _ __ _ _ _ _ _ _ _

10. Design Pressure 2485 psi. Temp. 650 OF. Hydro, test pressure N/A at temp. OF (when applicable1 OSupplenental information in the form of lists. sketches, or drawings may be used provided (1) size is 8 1/2 x II, (2) information in items 2 and 3 an this Data Report is included on each sheet, (3) each sheet is numbered end the number of'sheets is recorded at the top of'this form.

-rave Ier,# 06091 "FORM N-2 (back) ~ISVer+ 3 .

(S Mfi. Serial No. AH6389-! I CERTIFICATION OF DESIGN Design specifications certified by Henry P. Leonard P.E. State PA: Reg, no. 23938-E (who applicable)

Design repone cenified by N/A. PL, State N/A R . no. N/A (when applicable)

CERTIFICATE OF SHOP COMPIdANCE I We certify tht dhestatements made in this report arecorrect and.tdat this (then) Ven-Ball Sub Aýy contiomua to dle rule of construction of dte ASME Code, Section M.

NPT Certificate of Authorizaion No. 193.0 Expires tO-27-20Q7 Date 12/7/05 Name FTSHERCONTROLSfl0("L LLC Sim tN"Cra.iscaft Holder) (aut(a

,orized meprts9sweW CERTIFICATE OP SHOP INSPECTION I, the undesigwed, holding a valid conmmission isued by theNational Baoad ofBoilae.and Pressure Vessel ispec'tof and the state or Province of Iow and employed by Haitffrd Steam Boiler of CT . I of Hartfrd, CT ban inspected dine items decribed in this Data Report on - - and statmme liato the be of my knowledbe and belief, i* Cenfloaw Holder has &hricated these pts or appurtlnances in accordance with the ASME.Code, Section IlL Each.*r liHted has bee authomrizd far stmping on the date shown above.

Dyslptigng dibicatifimle, neither the ihtpector nor his employer makes any warrany. expreased or implied. concerningithe equipmemn described in.dths Data R:po -.

Furthenrmore neither the inspector nor his employer ah be liable in any manner for any peisonal injury or Property damage or loss of any kind aising frm or cornncted with this inspection.

DameP D Signed ~ st 'Commissfions X' (Authorized I *spetot) (Nat'l. Rd. (incl. endorsements) state or proy. and no,)

2-36-6.do<

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler # 07052 i

1. Owner Southern Nuclear Operating Company Date 09/17/07 Name 40 Inverness Center Parkway, Birmingham, AL Sheet I of 3 Address
2. Plant Voatle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 WO# 1070278101 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voage Expiration Date N/A Address
4. Identification of System 1301/Main Steam Svstem
5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N/A Code Ca'se (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Noj VALVE CONTROL 23468-1.4 N/A IPV3030 1982 REPLACEMENT YES COMPONENTS INC.

& & .1

7. Description of Work Valve plug was replaced. A copy of Form N-2 for the replacementplug (S/V 154041-2)is attached. I
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[]

WA[K Other [] Pressure N/A PSI Test Temp. N/A F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Aut Irzation No. N/A Expiration Date N/A 1 Signed . = Team Leader Date nher or Owner's Designee, WIItie
  1. 16ý CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. oI Connecticut ol Hartord. Co c have Inspected the components described In this Owner's Report during the period 02/26/07 I to .0 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section IXI.

I

,Br lng this certifie, npither the inspector nor his employer makes any warranty, expressed or Implied, concerning fthe m o nd corrqt saures described in thE Owners Report. Furthermore, neither the Inspector nor his employer shall liable

~jaa(Commissions a an rror= *n personal lnlu (4- o0 o1I.

property damage or a loss of any kind arising from or connected with this

-liispecfor's Signiture National Board, State, Province and Endorsements Data -a`O 0

Trueterw 01OS5-skeeti 20431 Form -.2

1) FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of th ASME Code, Section I1.

Not to Exceed One Dav's Production Pa.1 of 2

1. Manufactured and certfied by Control Components Inc. (CCI) 22591 Avenida Ernymsa. Rancho Santa MaMarfia, CA 92688 t (nana and address of Crtificate Holder)
2. Manufactured for GEORGIA POWER COMPANY, ALVIN VOG7LE PLANTAAUGUSTA. GEORGIA (name and address of purchaser)
3. Location of Installaton ALVIN VOGTLE PLANT, AUGUSTA, GEORGIA (name and address)
4. Type 320601696 SA-182-F11 70 K.S.I. N/A 2002 (drawing no.) (mall Spec. no.) (tensile strngth) (CRN) (year built)

S. ASME Code.Section III. Division 1: .1977 WINTER 1977 2 N/IA (edition) (addends date) (class) (Code Case no.)

6. Fabiricated In accordance with ConAt Spec. (dliv. 2 only) N/A Revision N/A Date NWA (no.)
7. Remdrils FOR ATMOSPHERIC DUMP VALVE CCI PROJECT 100456 8.Nom. thickness (in.) 3.2 Min. design lulchness 1.8 D. ID((R&In.) 1.5 Length overatll(ft A n.) 11.1'1
9. When applicable. Certificate Holders' Daa Reports are atched for each item of the this report I Part or Appurtenance Serial Number National Board NO.

i Numerical Orter Part or Appurtanm, Serial Number National Boarnd No.

in Numerical Order N/A (1.) 1!i 1~.1 (26.)

(2.) 154041-2 N/A (27.)

I --

(3.) 15404143 N/A (28.) i I -

(4.) 154041-4 N/A (29.)

I (5.) (30.) 4. -I (6.) (31.)

1* --

(7.) (32.) 4. --

(8.) il I I (33.)

(9.) (34.)

4. --

(10.)

4 (35.) -4 --

(11.) (36.)

(12.) 4.

I.

(37.) i.i--

(13.) (38.)

4 (14.) (39.)

4 (15.) (40.)

4 (41.)

(21.) 4.- 4. --

(42.)

(18.) 4 (43.)

(16.)

(19.) 4. 4 4

(44.)

4.

(20.)

4.

(45.) 4 I

(23.) (40.)

4 (22.) (47.)

(23.) (46.) _________ ________ I, (24.) 4.

(49.)

(25.)

~1*

(50.)

10. Design pressure 1640 psi Temp. 600 Deg. F Hydra test pressure N/A at temp. 0 3g. I
  • Supplemental information in the form r of ists. sketches. or drswings may be used provided (t) sze is 112x 11. (2) information in items I Ihrough 4 on this Dea Report is inluded on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the too of this form. I This farm (E00037) may be obtained from the Orer Oept., ASME, U Law Drive. Boa Z=30.Fairlield. NJ 07007-2300.

r-S~neet 3oP3 Form N-2 S FORM N-2 (Back - Pg. 2 of .2)

CeiMcate HaIslet'a Serial No. 154041-1 thru though N/A 154041-4 CERTIFICATE OF DESIGN Design Specification certified by MARK Z. JEIRC P.E. State CA Reg. no. 12217 Design Rapo"

  • cerlified by N/A P.E. State N/A Reg. no. N/A (when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) PLUG conforms to the rules of construction of the ASME Code,Section III, Division 1.

NPT Certificate of Authorization N-2696 Expires JUNE 7. 2003 No.

Date */-4., Name Control Components Inc. (CCI) Signed (NPT Cetificate Holder) (Auf*lrfel n-tve)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Provinc of CALIFORNIA and employed by HSBCT of HARTFORD- CONNECTICUT have Inspected these Items described in this Data Report on 4t X',c - , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with ASME Section III, Division 1. Each part listed has been authorized for stamping on the date shown above. I By signing this certificate, neither the inspector nor his employer makes warranty. expressed or implied, concerning the equipment describe in this Data Report. Furthennore. neither the inspector nor his employer shall be liable In any manner for any personail injury or property damage orof any kind arising from or connected with this Inspection.

Date A - OL Signed =t "'7/ ,--, - Commlsslons 4 14"-4-,

(Authoruized Inpecixr) (Nati 6d. (Including ansdrsanw*i) and Mst or pmv.. rnd no.) I

ORIGINAL 40 SECTION XI REPAIR/REPLACEMENT TRAVELER PAGE 1 0F3 TRAVELER: 06094 REPAIR E5 REPLACEMENT Z

, ----ASSOCIATED DOCUMENTS---- ------COMPONENT ------

WO: A061951201 CODE CLASS: ASME III CI. 1 NF CR: N/A TAG NO: A-21 17-SNUBBERQ DCP: N/A DESCRIPTION Spare Snubber (PSA-1I)-

OTHER:. AX4AQ18-168 SERIAL NO: 12859 WORK DESCRIPTION: Install replacement telescopina sleeve.

-EXAMINATION/TEST REQUIREMENTS -------

N/A VT-i N/A VT-2 N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A ýTEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement

. No. Normal / Expected Wear E ALARA DCP Z EQ Checklist Yes Justification:

Intended life ifless than design life of repaired item:

REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Ooeratinq Co.


INITIAL REVIEW-.--

GNADAT ~ HOLD POINTS A.WE 1 176A~ ElYES- 0 NONE ISI ENGINEER AW IEl YES NONE HOLD POIl fl#MEPXAMINER __________ . YES 5NONE ANI I -NONE*5YES FINAL REVIEW---

~SIcATU RE DATE SLGNA1IUR.E DATE 181 ENGINEEW'-7l' .s4-16-2do a AWE ~ ~ 2t REMARKS: I~iS4-~ &e K)-TS-z

S.

ORIGINAL TRAVELER NO: 06094 ASME SECTION Xl TRAVELER INSTRUCTION SHEET WO: A061951201 PAGE 2 OF 3 and/or trace code number of the 4

replacement part(s) is entered on 4 4 +

the JML. If the Dart does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the JML.

2. Verify the serial number, heat and/or COC . £i fL/k trace code number-of the replacement part(s) matches what is recorded on the JML or the applicable documen-tation. If the part has no markings,

_ utilize the PO, MIR'and Line Item

__ numbers on the warehouse identifi-cation label.

3. Verify that the ASME Code Class. CQC , b __________

for the replacement part(s) matches or .....

exceeds that of the component in which it is being installed.

4. Install replacement part(s) in spare Maint. "5"CT JhiF,_,_

snubber. CaC 1

U -

ASME SECTION Xl BILL OF MATERIALS TRAVELER 06094 WO A061951201 PAGE 3 OF 3 RE,.*G .,.N, " w * *, XSE § E~~TIE Telescoping AX4AQ18- 26 1977W1977 wo- A-519 Gr. 1018 Sleeve. . . ... 168 .. .. 44-)~q 7v, . .A.*II* ,IO ,g-'.23,*.. __.______r.*'**/a 0

5 z

COMMENTS: *7r*. . * ( 7 So) kA t'o TERI 2- _,*e I

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRPREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07138

1. Owner Southern Nuclear Operating Company Date 06/19/08 Name 40 Inverness Center Parkway,Birmingham,AL Sheet I of 1 Address
2. Plant Vogtle Electdric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1062002601 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp NAV Name Authorization No. NIA Plant Vogtle Expiration Date N/A Address
4. Identification of System 1201 /Reactor Coolant System
5. (a) Applicable Construction Code ASME Sec. I/i, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thr2063Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No PIPE PULLMAN POWER N/A N/A V1-1201-030-H601 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work SnubberADo-151, serial #133 was replaced with a snubber AD-151, serial#482.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptnX Other [] Pressure psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Au~ IN/A Expiration DateNA Signed T eam Leader Date Z&(o Owne'r Owntr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartford Coecticut have inspected the components described In this Owner's Report during the period 08/06107 to / and state that to the beat of my knowledge and belief, the Owner has performed examinations and taken correclve measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions C.A 7_r%4 fInspec s Signature National Board, State, Province and Endorsements Date E!ýw."'

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07145

1. Owner Southern Nuclear OperatingCompany Date 07/02/08 Name 40 Inverness CenterParkwav. Birminiham, AL Sheet .1 Of 7 Address
2. Plant Vogtlie Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1060178403 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vot/le Expiration Date N/A Address
4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No) 1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-015-01 1987 INSTALLED YES SYSTEM PRODUCTS I F09651
7. Description of Work Flow orifice assembly 1F09651 was installed.Installationrequiredwelding to the existing piping system. Installation of this orifice was in accordance with DCP 10601784. Copies of the data reportsfor the orifice assembly are attached.
8. Test Conducted: Hydrostatic E] Pneumatic[] Nominal Operating Pressure['J Exempt[]

Other [] Pressure _ psi Test Temp.

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of n No. ,NA Expiration Date N/A Signed ~ Team Leader Date " 7-Dlii,' Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Ins.oction and InsuranceCo. of Connecticut of .ar Ord, QCnnecticut have Inspected the components described in this Owner's Report during the period 07/16/07 to

  • and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions &.4 Z"-

lInspi*Wr's Signature National Board, State, Province and Endorsements Date -.Tut-Y 4Q:. acc&

Tr.,'e I e r - 07(4 +

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production pg. I of 2

1. Manufactured and cert~ied by tonics. Incorporated, Bridgeville Division, 30 Curry Avenue, Cononsburq, Pennsylvania, 15137 (name and dnm of NPTCar~cAs Holde)
2. Manufactured for West nghouse Electric Co.. 4350 Northern Pike, Monroeville, PA. 15146 (WareWr4 adiur d-pWue)
3. Location of Installation -VtleElectric Generating Plant - Unit 1,(raw 7821 River Road. Waynesboro, GA 30830 andadrml SA-312 TP 316 75.00
4. Type I0N25E50 Rev. 3 SA 182 TP 316 75-O.D N/A 2007 (dravt~lnumber) (min.19Mc no.) (es $n"(CF"(yarbol
5. ASME Code, Section IlI,Division 1: 1974 Summer 1975 2 N/A (eodsmb (aldarda 4) (du-I (Cd.ou no.)
6. Fabricated in accordance with Const. Spec. (Div. 2 only) N/A (no.) Revision N/A Date N/A
7. Remarks IHS( Multi-Stage 8reakdown Orifice consisting of two weld neck flanoes welded to two pipe sections and two orifice odoaters.

Manufactured on tonics Contract 1665. Supolied on Westinahouse Contract 4500208455. The WestinChouse controct removes from Ionics ony Design Renort resDonsibilites for the Apourtenances.

8. Norn. Thickness (in.)_.337 in. design thickhess (in.) ---- Dia. ID (ft & In.) 0'- 83.22" Length overall ( ft &In.) W-3.8
9. When applicable. Certificate Holders! Data Reports are attached for each Item of this report Pari or Appurten'ance National Part or Appurionance Natitonbt Serial Number Board No. Serial Number Board No.

in Nlumertcal order la, Nwriedfal Order (1 I-FO-9651 (26)

(2) (27M______________

(3) (28) __________

(4) (29) ___________

(5) ________________________ (30) __________

(6) ________________________ (31)

(7) __________________________ (32)

(8) __________________________ (33) ___________

(9) ___________(34)

(10) ___________ (35) ____________ ________________

(11) ___________________________ (36) ______________

(12) ____________(37) ___________

(13) ___________ (38) ____________

(14) ________________________ (39)

(15) (40)

(18) (A1) _________

(17) ______________ (42) _______________

(18) _____________ (43)

(19) (44) ___________

(20) (45) ___________

(21) __________ (46) ___________

(22) (47) ___________

(23) ________________________ (48) __________ _______________

(24) __________ _____________ (49) __________ _______________

(25) ________________________ (50) _________________________

10. Design pressure. Iw psi. Temp. 250 *-F. Hydro. Test pr'essure 2800 at temnp. .,.L F teMM swcba
  • Supplemnental infonrmation in the form of llsts, sethesoe. or drawinrgs may be uaed Prdovdd (1) size Is 8 'A xl1i. (2) Informnationr in Itoens2asnd 3on WeiDats Report is inctluded on each sheet. (3) eachi sheet is numbered and the number of sheeta Iarecorded at ttu top of this foirm.

(?~9fJ This form(E00040) may bieobtained froms the Order dept.. AS$4E.

22 Law Drtve. Sax 2300, Fairftlod. NJ 07007,2300.

Page 10 of 177

5'ee'e 3o-C 7 FORM N-2 (Back - Pg 2 of 2)

Certificate Holders Serial Nos. I-FO-9651 through CERTIFICATION OF DESIGN Design specifcations certified by John L. Robinson P.E. State PA _Reg. No. 072588 (when applicble)

Design report' certified by NIA P.E. State N/A Reg, No. N/A (When applcable)

CERTIFICATE OF COMPUANCE We certify that the statements made In this report are correct and thal this (these) IHSI Mull-Stace Breakdown Orifce conforms to the rules of consbuction of the ASME Code, Section I11,Division 1.

NPT Certificate of Authorization No. N-2974 Expires March 2e. 2008 Date 2 - 2 S-* Name Ionics. Incorporated - Bridgeville Division Signed (NPT Critflcate Makler) taullbornzd repreeantaove)

CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.

of Boston. MA have inspected these Items described in this Date Report on 6 2.- Z- .-",AA7 , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated thse parts or appurtenances In accordance with the ASME Code, Section 1li, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or imptled, concerning the equtpment described In this Data Report. Furthermore, neither the Inspector nor lls employer shalt be liable In any manner for any personal njury or property damage or loss of any kind arising from or connected with this Inspection.

Date OZ-_2-2c"7 Sign7ý Commissios P1**-m

,lzed lud.lnape f (Nail. Od. (inri. andorsemente) and sMe or prow. and nol Page 11 of 177

T~vI~r~/0714 S S6,eei 4ofi 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production P9. i of 2

1. Manufactured and certiid by Ionics, Incorporated, 8ridgeyfile Divison.. 30 Curry Avenue. Canonsburg, Pennsylvania, 1513 7 (Pnm adSsWidaa NPTC*Vtw H*i
2. Manufactured for Westinqh0-se Electric Co., 4350 Northern Pike, Monroeville, PA. 15146 (ra* KWafum d pwchaW)
3. ~vnrtle FI,,trie (Senerrttinf PRant - Unit 1. 7821 RIver Road. Wavnesboro. GA 30830 Location ot In IdUaLlun Vonde Elettric Gpneratina Plant - Unit 1 7821 Piver Rood Wavilesboro GA 30630
4. Type 10025E50 Rev. 3 SA-312 TP 316 75,000 N/A 2007

( drming Srunte) fin'I. Specno.) (lantsla ngtr) ICRNI) (e bIall

5. ASME Code.Section III.Division 1: 1974 Summer 1975 2 N/A (Wall) IE 1Ira dab) Was,) iamr
6. Fabricated in accordance with Const, Spec. (Div. 2 only) N/A Revision N/A Date N/A Inc.)
7. Remarks IHSI multi-Stage Breakdown Orifice Extension Adapters consistinr of a oioe welded to o weld neck flange, 1 Monufactured on lonics Contract 166S. Suootied on Wesrinahouse Contract 4500208455, The Westinghouse controct removes from Ionics any Design RePOrt resoC  ; for I .5.
8. Nom. Thickness (In.)_,21.fln. design thilcitwes (in.) - Dia. ID (It & in.) 0'- 3.822= Length overall (&in.) 0'-17.12'
9. When applicable, Certificate Holders' Data Reports are attached for each Rtem of this report:

Part orAppurtenance National Part or APPWUntance National Senal Number Board No. Seral Number Board No.

InNurnerical order in N"Wricarl order

() 1-F0-9651-A (26)

(2) _____________ _ (27)

(3) (28)

(4) (29)

(5) ___________ _____________ _

(30)

(31) +

(6) __________________________

(32) 'I.

(7) ____________ ______________

(33) 4-(34)

(35)

(11) ________________ (36)

(12) ___________ (37)

(13) ___________ _____________ (38)

(14) ___________ (39)

(40)

(41)

(17) __________

(42) i (43)

(17) __________ ____________

(44)

(218) __________

(45)

(19) ___________

(46)

(47)

(40)

(49)

(25) (50)

10. Design pressure 1860 psi. Temp. 250 *F. Hydro. Test pressure 2800 at tamp. .5i* F

-wa appale "Supplemental Infaormation in the farm of lists. sketches, or drawings may be used provided (1) size IsA x 11, (2) Innftmon In items 2 and 3 on til Date Report is included an each 13)each sheet is numbered and ft number of slheaelI rcorded o " top of thllsform.

0 1heel.

iistT his form (E00040) may be oblalned romn the Order dept. ASME. 22 Law Drive, Bax 2300. Fairfeld, NJ 07007-2300.

I Page 12 of 177

Tr&,e~r$'07145 c3kefA 5 o-( 7 FORM N-2 (Back - P9 2 of 2)

Certificate Holdees Serial Nos. 1-FO-96S1-A through_

CERTIFICATION OF DESIGN Oesign specifications centifled by John L Robinson P.E. State PA Reg. No. 072588 (when appliable)

Design report certified by .N/A P.E. State N/A Reg. No. N/A (when appilabua)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) IHSI Multi-Staoe Breakdown Odlfce Extension Adapter conforms to the rules of construction of the ASME Code, Section Ill, Division 1.

NPT Certificate of Authorization No. N-2974 Expires March 265 2008 Date Z, gi'O- Name 1onics. Incorporated- Brid eville Division SIgned *,.f*jZ (NPT Cerdficate Holder) (authorized reprmntadve)

CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.

of Boston, MA have Inspected these Items described In this Data Report on , Z -2 0 -*M-- and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section ill, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipmlent described In this Data Report. Furthermore, neither the inspector nor his employer shalh be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection.

Date 02 2 . 00-7 Signea Commissions PA 44' Nuclear inspeemrI e- -zed lNatl. 8d. (incl. endorsermnts) and state or prov. end not Page 13 of 177

.==50i

07145 S~tee4+ 4of 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production Pg. 1 of 2

1. Manufactured and certified by lnics. Incorporoted. Bri.dgeviile Division. 30 CurryAvenue. Cononsbua . Pennsylvanio. 15137 (unit andasis of NPTC *tlr.

Hakd} I Manufactured for Westinghovuse Electric Co./4350 Northern Pike, Monroeville. PA, 15146 2.

mr amd (infrm adisa wipivf

, ... , .,..,u,.,; WUrntloI~,rnfrir Connrntinn Plrrnt - Unit 1. 7821 River Road. Wovnesboro. GA 30830 f*tJt*=lu UI * - a on t' El-tric Ganerobrin Plmnt - Linit 1- 7821 River Road WovnL-sborci GA 30830

-11 41 a*-d )

-(ri*anud

4. Type 10025E50 Rev. 3 SA-31Z TP 316 75,000 N/A ?007 I diiAnt; ruirdiat (fW1. SPIC110.) lfmsif fbsntlr (CRN) (yesrnbig
5. ASME Code. Section Ill, Division 1: 1974 Summer 1975  ? N/A (eadith) (adda dab) (des) (Cod.Cal M)
6. Fabricated in accordance wilh Const. Spoc. (Div. 2 only) N/A Revision N/A Oata N/A (no.)
7. Rema
  • MltihStnrne Breaikdown cIi;l Orifice Extension Adooters consisting ofo Dioe welded to o weld neck flrnce.

Mc]inufacturt II ContrOCt 1665. Supplied on Westinghouse Con ,500208455. The Westinnhouse contract removes from Ionics any Design Report reso r the Appurtenonces.

S. Nomn.Thickness(i.l .37Iln. deslgn thicnessOn.j-_--_ Dla.ID(ft&InM) Y'.3.827 Length overall(fM&mn.) 0'-17.12'

9. When applicable, Certificate Hoders' Data Reports are attached for each teom of thi report, National Pad to Appurteanances National Serial Number Doard NO. Serial Number Boased No.

in Numerecal order InNumerical Order I-FO-965 1-8 _ _ _ _ _ _ _ _

(1) (26) _ _ _ _ _ _

(2) (27)

(3) (28)

(4)

(5)

(6)

(7) (32) _ _ _ _ _ _ _ _ _ _ _

(8) (33) _______________

(9) (34)__ _ _ _ _ _ _ _

(35)__ _ _ _ _ _ _ _

(35) _ _ _ _ _ _

(12) (37)

(13) (38) ___________

(14) (39) ______________ __________________

(15) (40)__ _ _ _ _ _ _

(41)_______ _____ ________ __ __ __ _

(17)

(42) ______________________________

(18)

(43) ____________ _______________ _

(44)__ _ _ _ _ _ _ _ _ _ _ _ _ _

(20) (45) _ _ _ _ _

I (21) (40) _ _ _ _ _ _ _ _ _ _ _ _ _

(22) (47) ____________ _______________ _

(23) (48) _ _ _ _ _ _ _ _ _ _ _ _ _

(24) (49) _ _ _ _ _ _ _ _ _ _ _ _ _

(25) (50)

10. Design pressure 1860 psi. Temp. 260 'F. Hydro. Test pressure 2800 at temp. _5" F

'Suppdemental information in (he form of IsmI sketches, or drawings may be used prvided (1) ize Is 8A x 11, (2) informnatlon in items 2 and 3 on tils Data Report Is inculued on each sheet. (3) each sheet Is numbered and tie number of sheeft is recorded at eth lop of is form.

l9fi8 This form OE00040) may be obitined from the OrdardeptL, ASME. 22 Law Drive, Box 2300. Fafriteld, NJ 07007-2300.

Page 14 of 177

TrmoedIerhe e-707 07/4-:5 FORM N-2 (Back - Pg 2 of 2)

Certificate Holder's Serial Nos. - 1-FO-9651-B through-CERTIFICATION OF DESIGN Design specifications certified by John L Robinson P.E. State PA Reg. No. 072588 (when applicable )

Design report' certified by NIA P.E. State N/A Reg. No. NIA (when applicale )

CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) IHSI Mul-Staoe Breakdowm Orifice Extension Adapter conforms to the rules of construction of the ASME Code.Section III, DIvision 1.

NPT Certificate of Authorization No. JH-2974 Expires March 26. 2008 Date z. ' Name Ionics. Inconmorated - Bridgeville Division Signed _ ._______,_

(NPT Certificate Holder) Cauthorized repreentlative)

CERTIFICATE OF INSPECTION I, the undersigned, holding a vatld commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pgennsylvania and employed by One Beacon America Insurance Co.

of Boston. MA have Inspected these Items described In this Data Report on QZ-Z- - r0'7 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code. Section Il, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore, neither the Inspector nor his employer shah be liable Inany manner for any personal injury or property damage or loss of any kind adsing from or connected with this inspection, Date Q?2&b *- 7 Signed Commlssion P,24

-( '-r horized Nuclear inspetor) (Nell. Bd. (nci. ridorsernenla)and astrate or prov. aMdnol Page 15 of 177

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler# 07147

1. Owner Southern NuclearOperating Company Date 07/02108 Name 40 Inverness CenterParkway. Birminnham. AL Sheet 1_ _ _ _ Of Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1060178403 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootle Expiration Date Address
4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. I11.1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2O03 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No) 1204 PIPE PULLMAN POWER N/A N/A V1-1204-015-H006 1987 CORRECTED YES SUPPORT PRODUCTS _
7. Description of Work Pipe support was modified parDCP 1060178401.
8. Test Conducted: Hydrostatic F] Pneumatic[] Nominal Operating Pressurejj Exempt[K Other [] Pressure psi Test Temp. -F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auth1 ation No. N/A Expiration Date N/A Signed .. Team Leader Date Owner-of"Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Oeorala and employed by Hartford Steam Boiler Ins.ectlon and Insurance Co. of Connecticut of H o Cnnecticut have inspected the components described In this Owner's Report during the period 07/16/07 to

  • and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

-Inpoc9A igntur Commissions G 4 . )Z lnspect Signature National Board, State, Province and Endorsements Date 7ZALY gf .10CR

FORM NIS-2 OWNER'S * 'ILACEMENT FC ACTIVITY As Required I EIr~f Section XI lravelerw 7i1, 48

1. Owner Southern Nuclear Operating Company Date July 22. 2008 Name 40 Inverness Center Parkway, Birnmingham, AL Sheet __ _ _ _ _ _ Of I
  • 7__eat,"_

Address

2. Plant Vogtle Electric GeneratingPlant Unit Waynesboro, GA 30830 WO 1060178402 Address RepairlReplacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1214 / Safety Iniection System 1204 / Safetv Ini lion Svstern
6. (a) Applicable Construction Code ASME Sec. III 1977 Edition, Winter 1977 Addenda, n/a Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 d. 2003 add.

(c) Applicable Section Xi Code Case(a)

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped' Comeonent Manufacturer Serial No. No. identification Built Installed Yes or No) 1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-057-01 1987 INSTALLED YES SYSTEM PRODUCTS 1F09650

) 7. Description of Work A flow orifice IF09650 was Installed. Installationrequired welding to the existing piping system and the additioln of spacers. One of the spacers was replaced by an orifice plate due to flow test results under Traveler #07149.

6 8. Test Conducted:

Installation of this orifice was In accordance with DCP 1060178401. Copies of the data reports for the orifice assembly are attached.

Hydrostatic [] Pneumatic[] Nominal Operating Presaure*] Exempt[]

I Other [] Pressure _pal Test Temp.

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANC '

I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbo Stamp N/A Certif icate I oriz ~n of 9 NIA Expiration Date W/A 4~~

Signed oJ Cvinr'sDesignee, Title Team.Leader Oat TIz4Ge CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Bolier and Pressure Vessel Inspectors I and the state or Province of Geaoria and employed by HartfordSteam Boiler Insoecfion and Insurance Co. of Connecticut of o ctit have Inspected the components described in this Owner's Report during the period 7/16007 "

to 4ad.

_ - and state that to the best of my knowledge and belief, the Owner has performed examinations and 6ken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer ihall be liable In any manner for any personai Injury or property damage or a lose of any kind arising from or connected withl this Inspection.

I __ .. _ _ .._ .. .. _ _ _ _ _ _ Commissions .

I Date ,,

"lnspectoW'Signature*

.zL'_. I

'- National Board, State, Province and Endorsements

$~ea~L 2a47 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production P9. I of 2

1. Manufactured and certifled by Ionics, Incorporated, Bridgeville Division, 30 Curry Avenue. Cononsburo. Pennsylvarna. 15137 (nme aridade ofNPTCwtflicale Holdel
2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA, 15146 (Who4 Widudrees orpuilmeoor
3. Location of installation Voctde Electric Generatina Plant - Unit 1.7821 River Road Woynesboro, GA 30830 (hworand ddremi)

SA-312 TP 316 75,000

4. Type 10025E50 Rev. 3 SA 182 TP 316 75.0 N/A 2007 Idtamfsi number Irsaf spec; sa.) (leasi.Masgdl( (CRN) 6-e buI
5. ASME Code.Section III.Division 1: 1974 Summer 1975 2 N/A (aftil) (aderedeleJ (dma) (Cedc" no.)
e. Fabricated in accordance wlh Const. Spec. (DIv. 2 only) N/A (noj Revislon N/A Date N/A
7. Remar(s HHSI Multi-Stoge Breakdlown Orifice consistina of twq weld neck flanges welded to two pipe sections and two orifice adopters.

Mnnufnctured on Ionics Contract 1665, Supplied on Westinghouse Contract 4500208455. The Westinahouse contract removes from Ionics ony Design Report I r the Appurtenances.

B. Norn. Thickness (in.)_.5M1jn. design thicknes (Itn.) --- DIa. ID (ft & In.) 09-3.438 Length overall (ft &in.) 4'-3.80 When applicable. Certificate Holders' Data Reports are attached for each Item of this report:

Aat Nalursoian or FoetSerial or Apu*rtenance National Serial Number Board No. Number Board No.

in Numerkoat order In Numerical Order 1-FO-9650 (26)

(1) I (2) (27)

(3) (28)

(4) (29)

(5) (30)

(6) (31)

(7) (32)

(8) (33)

(9) (34)

(10) (35)

(11) (36)

(12) (37)

(13) (38)

(14) (39)

(40)

(17) (41)

(16) (42)

(43)

+

(44)

(20) (45)

(21) (46) 4-(22) (47)

(23) (48)

(24) (49)

(25) (50)

10. Design pressure 3100 psi. Temp. 250 "F. Hydro. Test pressure 4700 at temp. _5" F heMaSpcble)

'Supplemental information in Ibheform of lIts. Slelctles, or drawings may be used provided (1) *i'e is 8 A x 11. (2) information in Item 2 and 3 on this Data Report Is Incmucleo on each sheet. (3) each aheet is numbered and the number of shedls 1Arecorded at the top of aft form.

(7198) This form (E00040) may be obtained f(Mmthe Order deptl, ASME. 22 Law Orte. Box 2300. Fairfield, NJ 07007.2300.

Page 4 of 177

-rwiele(2il 0148 Sheet 34 1 FORM N-2 (Back - Pg 2 of 2)

CertIficate Holder's Serial Nos. 1.F0-96gS through.

CERTIFICATION OF DESIGN Design speciications certified by John L. Robinson P.E. Slate PA Reg. No. 0725B8 (wher applicable)

Design report' certified by NIA PE. State N/A Reg. No. N/A (when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) HHSI Multi-Stage Breakdown Orifice conforms to the rules of construction of the ASME Code.Section III, Division 1.

NPT Certificate of Authorization No. N-2974 Expires Match 26- 2008 Date 2 - Z If- 7 Name Ionics. Incorprted - Bridfevjlle Division Signed - f Z .. ,

(NPT CeIllftCat Holder) (authortzed represenlatve)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of PcnnsiYlvania and employed by Onc Beacon America Insurancc Co.

of Bopton. MA have Inspected these Items described in tis Data Report on 60-Z tl .Cb -.. and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code, Section IlI, Division 1. Each part listed has been authorized for stamping on the date Mown above.

By signing this certificate, neither the Inspector nor his employer makes any varranty, expressed or Implied, concerning the equipment described in this Data Report Furthermore, neither the inspector nor his employer shall be table In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection.

oate OZZ 2(-0-7 Sine Commissions P~~

,/~54A"hodld Nuclear Inspector) (NtlN,8d. (Ind. endorwments) end state or prIy. and no)

' Page5 of 177

,Shee 4,(7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III.

Not to Exceed One day's production Pg. i of 2

1. Manufactured and certified by Ionics, Incorporated, Bridgeville Division, 30 Curry Avenue. Canonsburg, Pennsylvania, 15137 (wren 4 oird esa d NPTCerika.eHolder)
2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA, 1S14§ oarnei alrdam of uriaser
3. Location of Installation Voqtle Electric Generatino Plant - Unit 1. 7821 River Rood, Woynesboro, GA 30830 (nafie a adreen)
4. Type 10025E50 Rev. 3 SA-312 TP 316 75.0 . MIA 2007 (idre",n nuber) (marl spec na. (lensils siremptlij (CN) (yeabull)
5. ASM. Code, section III, Division 1: 1974 Summer 1975 2 N/A (ad"ton (aiiG8G8W) (Ciacss (Gods cueno)
6. Fabricated in accordance with Const Spec. (Dlv. 2 only) N/A Revision N/A Date NIA rno.)
7. Remarks HH1S Mult-Stocme Breakdown Orifice Extension Adopter consisting of a pive welded to a weld neck flange.

Monufactur.ed on Ionics Contract 1665. Supplied on Westinghouse Contract 4500208455. The Westinghouse controct removes from Ionics Ony Design Report resoonsibilities for the Aoourtenances.

8. Nom.Thickness(tn.) ji.5 tn. design thlicneas (in.)_ Dia.IO(ftiln.) 0'-3.43r Length overafl(ft&ln.) 0'-17.38"
9. When applicable, Certificate Holders Data Reports are attached for each item of this report Part or Appurtenance National Serial Number Board No, Serial Number Board No.

in Numernicl order in NumenincOrder (1) (26)

(-FO-9650-A (2) (27)

(3) 1 (28)

(4) (29)

(5) (30)

(6) (31)

(7) (32)

(8) (33)

(9) (34)

(10) (35)

(11) (36)

(12) (37)

(13) (38)

(14) (39)

(15) -_(40)

(16) (41)

(17) (42)

(18) (43)

(19) ,, (44)

(20) (45)

(21) (48)

(22) (47)

(23) (48)

(24) (49)

(25) (50)

10. Design pressure 3100_ psi. Temp. 250 "F. Hydro. Test pressure -47.0 at temp. 6 , F

'Supplemental Inlormation In l/a form toraisi.sketch-es. or drawings may be used proirded (1) l*le is a V.X 11. (2) information in temsr2 and 3on thitsOats Reor ts included on each helel.(3) each sheet is numbered and the number of sheoets i recorded at toelop of thisform, 7/95) This form (EO0040) may be obtelned from the Order dept., ASME, 22 Law Drive, Box 2300. Fakiteld. NJ 07007.2300.

Page 6 of 177

--rriv ter W 0O7i4-Slhert 5e47 FORM N-2 (Back - Pg 2 of 2)

Carnlfl'cate Holder's Sergal Nos. I-FO-9650-A through CERTMFICATION OF DESIGN Design specJficallons certified by John L. Robinson P.E. State PA Reg. No. 072588 (Ywhenapplicable)

Design report' certifed by NIA P.E. State N/A Reg. No. N/A (when applicable)

CERTIFICATE OF COMPLIANCE We certiif that the statements made In this report are correct and that this (these) HHSI Multi-Stame Breakdown Orifice Extensiorn Adapter conforms to the rules of construction of the ASME Code. Section iII, Division 1.

NPT Certificate of Authorization No. N-2974 Expires March 28. 2008 Date 2'2-o" Name Ionics. Incorporated - Bndaevilce Division Signed <---

(NPT Cerfricate Holder) (authorized represtaUve)

CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One BaacoD Am-bica Insurance Co.

of Boston- MA have inspected these items described kI this Data Report on 0 Z-?"2- "7 , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code. Section ifi. Division I. Each part listed has been authorized for stamping an the date shown above.

By signing this ceritficata, neither the Inspector nor his employer makes any warrranty. expressed or Implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection.

Date S*gnd or N rpor Commissions - PAZ(n4t

(ý~ oie Nula Nall. ad. Oncl. endorsements) arnd Iselr state or pov. and rio]

Page 7 of 177

l-rAve c-r 0*£714-8 5reet d 7 FORM N-2 CERTIFICATE HOLDERS' DATA REI'ORT FOR IDEN*ICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production Pg.l of 2

1. Manufactured am certified by lonics. Incorporoted. Bridgeville Division., 30 Curry Avenue. Cononsbura. Pennsylvonior 15137 (mae wid aftrag of NPT Curiltcab hktr)
2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA. 15146 Iname andrrAvM ofpurdmwa)
3. Location of installation Vogtle Electric Generoting Plant - Unit 1. 7821 River Road Woynesboro, GA 30830 aImes aid adfrtos
4. Type 1002SESORev. 3 SA-312 TP 316 750MO -N/A 2W07 (dreaoignumbee) (mail.1ws Me.) taballlluirgir) (CRNI I(ebut)
5. ASME Code, Section Ill. Division 1: 1974 Summer 1975 2 N/A (adika) igdftxbdatei) Melas) (Codecue nyo
6. Fabricated in accordance with Coast. Spec. (Div. 2 only) N/A Revision N/A Date NIA (ra)
7. Remarks .HHSI Multi-Stoae Breakdown Orifice Extension Adopter consisting of a lpie welded to a weld neck flanQe, Manufactured on Ionics Contract 1665. Supplied on Westinghouse Contract 4500208455. The Westinghouse contract removes from Ionics any Design Reoort responsibilities for the Appurtenonces,
8. Nom. Thickness (in.)531i.n. design thickness (In.) ---. Dia. ID (t &a In.) 0- 3.43r Length overall (ft &in,) a-17.38.
9. When applicable, Certificate Holders' Data Reports are attached for each item of this raport:

Part Or Appurtenance National Serial Number Board No.

tn Numarical order (1)

(2)

(3) 4.

(4)

(5)

(6)

(7)

(8)

(9)

(10) 4.

(11)

(12)

(13) 114)

(16)

(IT)

(17)

(18)

(19)

(20)

(21)

(22)

(23)

(24)

(25)

10. Design pressure - 100 psi. Temp. 250 *F. Hydro. Test pressure 4700 at temp... 'LF Supplemental ninformation in the form of iisis. sketches. or dmrwings may be used prOvided (1) sl2b Is a A x 11, (2) information in Items 2 end 3 on this Date Report is inOuded on each sheel, (3) each sheet is numbered and fe numberer 'iseets i recorded ati Uelop of pia form.

171%) This form (E00040) may be obtained trom the Order dept., ASME. 22 Law Drive. BoX2300, Faitld. NJ 07007-2300.

Page 8 of 177

Sheet 7o4 7 FORM N-2 (Back - Pg 2 of 2)

Certiicate Holder's Serial Nos. 1-FO-9650-B through.

CERTIFICATION OF DESIGN Design specifications certified by John L. Robinson P.E. State PA Reg. No. 07258M (when applicable)

Design reporr certified by NIA , P.E. State N/A -Reg. No. NWA CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) _ HHSI Multi-Staoe-Breakdown Oriflce Extension Adapter conforms to the rules of construction of the ASME Code.Section III, Diviston 1.

NPT Certificate OfAuthorizatnon NO. N-2974 Expires March 26 200W Date ,-Z'-o0* Name Ionics. Incormorated - Bridgevflle DLvision Signed (NPT Certificate Holder) (authoriz redosentatiwe)

C1RN'FICATE OF INSPECTION i, the undersigned, holding a valid Commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania - and employed by One Beacon AmericA Insurance Co.

of Boston. MA have Inspected these items described in this Data Report on -0 Z . 2 b- 2.0*'7 and state that to the oest of my knowledge and belief, the Certfilcate Holder has fabriceted these parts or appurtenances In accordance with the ASME Code, Section Ili, DIvision 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any vrranty. expressed or Implied, concerning the 'equipment described In this Data Report. Furthermore. neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection.

Date o -. o-. _7 Signed :7-- inzedNuclear Inspector)

--- Commissions PA'2-f;,*,9 WNatl.8d. (ind. endomecents) and state or prov. and riol Page 9 of 177

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 07150

1. Owner Southern Nuclear Operating Company Date 07/02/08 Name 40 Inverness CenterParkway, Birmingham, AL Sheet Of 7 Address
2. Plant Vogtle Electrc GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1060178404 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDeDartment Type Code Symbol Stamp NIA l

Name Authorization No. N/IA Plant Voglie Expiration Oate N/A Address

4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. 11i,1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A S. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Ytes or No) 1204 PIPING PULLMAN POWER N/A N/A IK3-1204-014-01 1987 INSTALLED YES SYSTEM PRODUCTS IIF09652

7. Description of Work Flow orificeassembly 1F09652 was Installed. Installationrequiredwelding to the existing piping system. Copies of the data reports for the orifice assembly are attached.
8. Test Conducted: Hydrostatic [] PneumaticE Nominal Operating Pressure'x] ExemptE]

Other [] Pressure _psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASM E Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Autiza* n No . . NaA Expiration Date N/A Signed J "Q Team Leader Date Owner oJr Ownei's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by HartfordSteam Boiler Inspection and InsuranceGo. of Connecticut of Hjatord, C.nnecticut have Inspected the components described in this Owner's Report during the period 08/06/07 to ra and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions &4. 756.

linspeca-s Signature National Board, State, Province and Endorsements Date 2;t *"JLP/*-~;ý"*-,0

~2oa s~reest FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production Pg. 1 of z

1. Manufactured and cerlfled by Ionics, Incorpqrnted. Bridgeville Divj~ion, 30(arne Curry Avenue. Cononsburg. Pennsylvania, 15137 andxun ol NPTC40cals HOW
2. Manufactured for Westinghouse Electric Co.,/4350 Northiern Pike, Monroeville. PA. 15146 Ina" ad edmf ofwcilwwa)
3. Location of Installation Voqtie Electric Generatinq Plant - Unit 1.7821 River Rood, Waynesboro, GA 30830 ren and addrss)

SAo312 TP 316 75,000 Type 100Z5E90 Rev. 3 SA 182 TP 316 75.000 N/A ;g07 4.

I daoirgrrluber (me spec roi (lmntifrn1"01h ICRNI (Yom kd ASME Code, Section Ill. Division 1: 1974 -Summer 1975. 2 N/A 5.

(dmon) (adcrdedaat (darl (Code Ca no.)

6. Fabricated in accordance Wth Const. Spec. (Div. 2 only) N/IA Revision N/A Date N/A
7. Remarks IHSI Multi-Stoge areakdown Orifice consisting of twA weld neck flanqes welded to two pi0e sections and two orifice adopters.

M,,n,,fnrtured on Ionics Contract 1665. SuoDqied on Westinghouse Contract 450028455. The Westinghouse contract removes from lonics any Design Report resp[ or I Length overall (ft &in.) V'-3.80",

8. Noam, Thickness (in.)_.3jUn. design thickness (in.) ---- Dia. ID (ft &In.) 0- 3.82g "
9. When applicable, Certicate Holders' Data Reports are attached far each Item of this report:

Part or Appurtanairm National Pad or Appurtenance National Beoar No. Sedal Number Board No.

Serial Number in Nu-mrical order In Numerical Order 1-FO-9652 (1) (26)

(2) (27)

(3) (28)

(29)

(4)

(5)

(30)

(8) (31)

(7) (32)

(8) (33)

(9) (34)

(10) (3-5)

(11) (36)

(12) (37)

(13) (38)

(14) (39)

(15) (40)

(41)

(17) (42)

(18) (43) +

(44)

(20) (45) +

(21) (46)

(22) (47)

(23) (48)

(24) (49)

(25) (50)

10. Design pressure 1060 1psi. Temp. 250 'F. Hydro. Test pressure 2800 at temp. jj "F t" aw)catl)

'Supplemental iform*nbon in the form of lsts. sketches, or drawivgs may be used prvided (1) sIze Is 8a xi11, (2) in iftoms2 and 30n nfonrmalion IhS Matn Report Is included on each sheet. (3) each sheet is numbered and the number of sheets Is recorded at the lop of this "orm.

a7/9B) This form (EO0040) may be obtained from the Order dept., ASME, 22 Law Drive. Box 2300. Failield, NJ 07007.2300.

Page 16 of 177

6ee-t 3,47 FORM N -2 (Back - Pg 2 of 2)

Certtficate Holdefs Serial Nos. 1-FO-9652 through..

CERTIFICATION OF DESIGN Design specifications cartified by John L. Roblnson P.E. State PA Reg. No. 072588 (wtmn appllcaGe )

Design report! certified by N/A P.E. State N/A Reg. No. N/A (when appl*cable)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report ate correct and that this (these) IHSI Muli-S iae Breakdown Orifice conforms to the ru)es of construction of the ASME Code,Section III, DivWon 1.

NPT Certificate or Authorization No. N-2974 Expires March 28. 2008 Date Z-2T-o) Name tonics, Incomorated- Brideeville Division Signed _ ---- ____,__

(NPT Certfcate Holder) (authorized (epTeseat5MUV)

CERTIFICATE OF INSPECTION I. the undersigned. holding a valid commission Issued by the National Board of Bol*er and Pressure Vessel Inspector$ and the Stale and Province of PennsylvaniA and employed by One Beacon America Insurance Co-of Boston. MA have Inspected these Items descrbed in this Data Report on *.-.020-,1 end state that to the best of my knowledge and belief, the CertIriate Holder has fabricated these parts or appurtenances In accordance with the ASME Code, Section ill, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or loss of any kind arising from or connected with this inspection.

Date 6 2-2~j-  ?.'ZOO1 Sins commissions 'Z6(

5hylrisd Nuclehr Inspector) (Nail.. So. (md. endontements) and slt.t or prov. andinol Page 17 of 177

-Fr*./ele #/ 09160 Skeet A-r l FORM N-2 CERTIFICATE HOLDERS' DATA RETORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production -. Pg.lIof

1. Manufactured and cserfied by Ionics. Incorooroted. Bridgeville Oivislon. 30(rame Curry Avenue. Canonsbura.Holder) Pennsylvania. 15137 wb didressOfNPTCarfia
2. Manufactured for Westinghouse Electric Co.. 4350 Northern Pike. Monroeville, PA. 15146
3. Location of Installation Voqtle Electric Generotin Plont - Unit 1.(noam 7821andRiver Roaod. Woyesboro GA 30830 addres)

SA-312 TP 316 75,000 N/A 2007

4. Type 10025E50-Rev. 3 JCRNI) /arkl

(&aw-ig nwbi) (imaftlS roe.) (itithsfhogi

_ 1974 Summer 1975 2 N/A

5. ASME Code,Section III,Division 1. (Cwdcme no.)

(ediloa) (Addends dos) (d-)

N/A - Revislon _NA Oato N/A

6. Fabricated in accordance with Conat Spec. (Div. 2 only)
7. Remarcs iHSI MuWti-Stoae Breakdown Orifice Extension Adodters consi stinoof a-pile welded to oweWd neck fion-g. removes from Ionics any Desion Manufactured on Ionics Controct 1665. Supplied on Westinqhoqe Contra.t 4500208455. The Westinahouse controct Report responsibi.ities for the Anourtenonces.
8. Non. Thickness(in.) .337,In. design thickness (In.)=--- Dfa. i(ftAln.) 0'-3.82,2 Lengthoveralli(ft8ln.)0Q"o.2"
9. When applicable, Certificate Holders' Data Reports are attached for each em of this report P eart o ubr Nao.

Boardeanc Part OrAppurtemance National InalNffa NoardteNo. Sadal Number Bowd Nm In Nuerica orde Nwnewlcs Oqdii

()(27)

(6) ___________ (31) ________ ___ ___________

(7) ___________ ______________ (32)____ ___ ____ _ ___ __ ____

(33)____ ___ ____ __ _____ ___

(8) ___ ________ ___ __________

(9) ___________ _____________ (34) _ _________ __________

(10) ___________ _____________ (35) ___________

_ (38)___ __ __ __ ___ ___ _____ __ _

(13) ___________ ____________

(14) (39)____ ___ ____ _

(15) (0 (16) (41) __________ _________

(17) 142)

(18) ~~~~~~(43)

(20) _________ _ (45) ___________

(21) 46) 4_________

(22) (47)

(23) _________ _ (48)____ ___ ____ _

(24) ___________ (49)

(25) E M___________ (50)

10. Design pressure .... IAD pal. Temp. 260 -'F. Hydro. Teat pressure 2800 at temp. _Ljj F totes ipm*

Provided (1) sin is 8a. x11. (2) infoi*ratton In items2and 3on Ot Data Reportis "Supplervn ntal information in the form of tlle. skletches. or drawings mns be Used this form.

included on each Sheet. 131each sheet is nwubered and the nunber of she*ts is oroded at the top of Thil form (E00040) may be obai-ed fron theOrder dept. ASAAE,22 Law Drtve. Box 2300, Fairinaid, NJ 07007-2300 17M)

Page 18 of 177

0760Q Sbee L 5o-C 7 FORM N -2 (Back - Pg 2 of 2)

Certificate Holder`s Serial Noe. 1-FO-9652-A through..

CERTIFICATION OF DESIGN Design spelacications certified by John L. Robinson P.E. State PA _Reg. No. 072588 (when applIcaible)

Design reporr certified by NAh e P.E. State N/A Rag. No. WA (wtlen appl~cable )

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are corrictand that this (these) IHSI Muil-Staos Breakdown Orifice Extension Adaoter.

conforms to the rules of construction of the ASME Code,Section III, Division 1.

NPT Certificate of Authorization No. N-2974 Expires March 26. 2008 Date F- -11 0 Name lonics. Incorporated - Birideville Division Signed Z -

(NPT Cerlflicale Holder ) (,utihorizad represertav)

CERTlFICATE OF INSPECnTON I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State and Provinrc of Pennsylvania and employed by One Beacon America Insurance Co.

of Boston. MA have inspected these Items descibed In this Date Report on c ) - fm - ZC07 and state that to the best of my knowledge and belief, the Certificate Holder lhas fabricated these parts or appurtenances In accordance with dhe ASME Code. Section Ill, Division 1. Each part liled has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore. neither the Inspector nor his employer shali be liable Inany manner for any personal injury or property damage or loss of any kind arising ftm or connected with this Inspection.

Date 02-~ Z -2Ax- Sign Commissions AG~(

L' fllýlzd IudeZ Inspector) (Nat'l. Rd. (Ind. eridorserresnits and stile or pray. aridriol Page 19 of 177

-Tr~elerW6#760O ed(. f 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code,Section III Not to Exceed One day's production Pg. I of 2

1. Manufactured and certified by tonics, Incorporated, Bridaevifle pIvision. 30 Curry Avenue. Cqnorlburcl. Pennsylvania. 15137 (name and~addai ofNPT Cari11 Holder)
2. Man,,facluredlot Westinghouse Electric Co, 4350 Northern Pike. Monroeville. PA. 15146
3. Location of installatlon Voatle Elecric Generating Plant- Unit 1. 7821 River Rood, Woynesboro, GA 30830

~rare and drssa)

4. Type 10025ESORev.3 SA-312 TP 316 NLA 2007 I "Wingevmbe (mall, tpec no.) IM)~ b 1A~
5. ASME Code,Section III.Division 1: 1W74 Summer 1975 2 NIA w- (addenaldab) Mdiss) ICed.cuteno.)

Fabricated if)accordance weit Const. Spec. (Div. 2 only) NIA Revision N/A Date N/A 6.

7. Remarks 1HSI Multi-Slope Breakdown Orifice Extension AdoPters consistino of a pipe weLded to a weld neck flonQe.

M.nufactured on Ionics Contract 1665. Supolied on Westinghouse Contract 4500208455_ The Westinghouse contract removes from Ioni;s any feninn rkdbeu rs--Km MFd - kimmurn.-gg.

Dil. 10 (ft &in.) 0-- 3.822- Length overall(ft&In.) U-1

8. Nom. Thickness (in.)-.Ljl.n design thickness On.) --
9. When applcable, Certificate Holdars' Data Reports are attached for each Itarn of this report Part orAppurtearlnce National Pat or Appi~rtesnance Nadoanal Serial Number Board No. Serial Nurnber Board No.

in Numerical order InNumeriall order 1-FO-9652-B (2) ___________ (28)

(3) (29) ___________ _

(4) ___________

(5)_____________________________

(6) ___________ ______________ (31) ___________

(7) ____________________________ (32)__ _ _ _ _ _ _ _ _ _ _ _ _ _

(33)__ _ _ _ _ _ _ _

0(8) _____________ ______________ (34) _ _ _ _ _ _

(35) _____________

(36)__ _ _ _ _ _ _ _ _ _ _ _ _ _

(37) ____________

(38) _____________ _________________

(114) __________ _ (39) _____________ _________________

(40) ____________

(41) ____________

(17) (42) ____________

(43)

(44)__ _ _ _ _ _

(45) _____________

(21) (48) _____________

(22) ____________ (47) _____________

(23) (48)

(24) __________________________ (49)

(25) (50)

10. Design pressure____ 11§Q psi. Temp.20 F-.. Hydrol. Test pressure 2800 at lamp. -IL P aima is a Xx I1. (2) Informatl, In items 2 and 3On this Date Report is
  • Supplarenlaw information in the form of lists, sketches. or dral*,ris may be used provided (1) included on each sheet. (3) each sheet is numbered and the numbern f shoeelsisrecordedat the opof this formi (71981 This form (EO0040) may beobtained from the Order ftpL, ASME. 22 Law Drive. Box 2300. Fairfiedl. NJ 07007-2300 I Page 20 of 177

Trce ler // 0'ITSO FORM N -2 (Back - Pg 2 of 2)

Certificate Holder's Serial Nos. 1-FO.9652-8 through CERTIFICATION OF DESIGN Design specifications certified by .John L Robinson P.E. State PA _Rog. No. Q02568 (when spplIcaile)

Design repor" certified by NIA , P.E. State N/A tReg. No. NIA (when applicoble)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) IHSI Muki-Staoe Breakdown Orifice Extension Adaoter conforms to the rules of construction of the ASME Code. Section itl, Division 1.

NPT Certificate of Authonzation No. N-2974 Expires March 28. 2008 Date L - Name Ionics. Incopormted - Bridgeville Division Signed _---"_ _ _

INPT Certifcate Holder) (authoriza: 'epdeentetve)

CERTIFICATE OF INSPECTION

f. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.

of Boston. MA have Itspected theme Items described in this Data Report on e7-,2 ,- Z<A>? and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code.Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Impl*ed, conceming the equipment descibed In this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or loss of any kind arising from or conn" th this inspection.

Date 62-7 3,2(-Vx'7 Signed Commissions PA-*26'.

udNuclar Inspectr) (Nul. 8d. (Incl. edorseemanlt) and state or prov. and no)

Poge 21 of 177

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07152

1. Owner Southern NuclearOperatingCompany Date 07/02108 Name 40 Inverness Center Parkway. Birnincham, AL Sheet Of 1 Address
2. Plant Voajte Electric Generating Plant Unit Name Wavnesboro, GA 30830 1060178404 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Aulthorization No. N/A Plant Vogtfe Expiration Date N/A Address
4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Comronent Manufacturer Serial No. No. Identification Built Installed (Yes or No) 1204 PIPE PULLMAN POWER N/A N/A VI-1204-014-H005 1987 CORRECTED YES SUPPORT PRODUCTS
7. Description of Work Pipe support was modified per DCP 1060178401.
8. Test Conducted: Hydrostatic [] Pneumatie[] Nominal Operating Pressure[] Exempt[o Other [ Pressure psi Test Temp. -F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Autho 5iatlon No... N/A Expiration Date N/A Signed 1*a4.1 Team Leader Date

,Owner or Ownertl DesigneeTitle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia , and employed by. Harfford-Steam Boiler Inspection and InsuranceCo. of Connecticut

,of _HsrflordL Conecitfcut.. have Inspected the components described in this Owner's Report during the period 8/06/07 to 7 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ilnspection.

Commissions e;4 *,o -.

npec"-s Signature National Board, State, Province and Endorsements Date "7 :T-,., *, NA.

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI L/

Traveler# 07153

1. Owner Southern Nuclear Operating Company Date 04/18/08 Name 40 Inverness CenterParkway, Blrmingham,AL Sheet of _ __
2. Plant Address Vogtle Electric Generating Plant Unit

, I1.

Name Wavnesboro, GA 30830 1070954401 Address Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed by MaintenanceDeDarlnent TypeI Code Symbol Stamp NIA Name Authorization No. N/A I Plant Vootle Expiration Date NIA Address
4. Identification of System 120A / Chemh~al nnd Va/urns tanimi .~v.tsm I 1208 / Chemical and Volume Control S-tern S. (a) Applicable Construction Code ASME Sec. Il, 1977 Edition, Winter 1977. Addenda, 1644-5 Code Cas (b) Applicable Edition of Section Xl Used for Repalr/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year -Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (es or No)

PIPE PULLMAN POWER N/A N/A V1-1208-009-HOO1 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-3, serial#29037 was replaced with a snubberPSA-3, serial #28344. A replacementload stud wasl also installed.
  • I
8. Test Conducted:- Hydrostatic E] Pneumatic[] Nominal Operating Pressurej] Exempt[X Other [] Pressure -psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the-requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Aut"Izatl an No. NWA Expiration Date.N/A ,

Signed Owner or Titi Team Leader Date CERTIFICATE OF INSERVICE INSPECTION -

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geoorola and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartfor.g ConncticuL have Inspected the components described In this Owner's Report during the period 07/1/07 I to " and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section lXi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. " I

__________________Commissions &A .

firspector'-51lnature National Board, State, Province and Endorsements 0 Date S- Miay' 2=w -

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl I Traveler# 07154

1. Owner Southern Nuclear OperatingCompany Date 0;V15/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1- of I Address
2. Plant Vogtle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1070956301 Address Repalr/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDeoartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voctle Expiration Date N/A Address Steam System*

1301/Main

4. Identification of System 1301/ Main Steam SystemL
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped.

Component Manufacturer Serial No. No. Identification Built Installed ( Yes or No)

PIPE PULLMAN POWER NA/A AI VI-1301-109-HO02 1987 INSTALLED YES SUPPORT PRODUCTS _

7. Description of Work Snubber AD-73, serial # 1197 was replacedwith a snubberAD-73, serial#472.
8. Test Conducted: Hydrostatic [] PneumaticQ Nominal Operating Pressure[] Exemptrxo Other [] Pressure -psi Test Temp. _ OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the r'eport are coriect and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Au rIzation No N/A Expiration Date N/A Signed Team Leader Date' 4i-t/,o 2 -crF$i

"-OwneFor'lwher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and Insurance Co.of ConnectictA of arffrd Lonnectdcut have inspected the components described In this Owner's Report during the period 07/16/07 to V..t -k=& and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectionl Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerningi the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer s'hall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with 'this Ins action.

I __ ___ __ ___ __ Commissions 6^. 7-Se "Inspectofet Signature National Board, State, Province and Endorsements Date /_ AP* ,

S-- . ~1

J.

ORIGINAL

  • 1' FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI I/

Traveler# 07156

1. Owner Southern Nuclear.OperatingCompany Date 04/17/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1 of Address
2. Plant Vogtle Electuic Generating Plant Unit Name Waynesboro, GA 30830 1070955901 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A I Name Authorization No. N/A Plant Vootle Expiration Date N/A Address
4. Identification of System 1208 / Chemical and Volume ControlSystem S. (a) Applicable Construction Code ASME Sec. I11,1977 Edition, Winter 1977 Addenda; N-249-1 Code Ca. 0 (b) Applicable Edition of Section Xt Used for Repair/Replacement Activity 2001 Ed, thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Coale Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6L PIPE PULLMAN POWER N/A N/A V1-1208-001-H032 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work Snubber AD-503, serial#241 was replacedwith a snubberAO-503, serial#658. I
8. Test Conducted: Hydrostatic E] Pneumatic[] Nominal Operating Pressure-] Exemptfx' Other [] Pressure _psi Test Temp. OF'
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE

.1certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of AIlorization O,, N/A Expiration Date N/A Signed 71 Team Leader Date __ _ _

"rwne'ir orOneAis Designee, Title CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors.

and the state or Province of Georia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Harflorgd, ut have inspected the components described In this Owner's Report during the period 07/16/07 I to &- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerningI the examinations end corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any'personal injury or property damage or a loss of any kind arising from or connected with !this Inspection.

, . .Commissions 64,

" I-'Inspecor's Signature National Board, State, Province and Endorsements Date 9 A,*Pk.Aw

ORIGINAL FORM NIS-2 OWNER'S 'As Required REPORT FOROfREPAIR/REPLACEMENT By The Provisions The ASME Code Section XI ACTIVITY

- ~Traveler# 07158

1. Owner Southem Nuclear Operating Company Date 04/14/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1070956701 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant VoQtie Expiration Date N/A Address
4. identification of System 1204 /Safety Injection System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1204-025-H012. 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber AD-1601, serial#50 was replaced with a snubberAD-1601, serfal #112.

B." Test Conducted: Hydrostatic F1 Pneumatic[] Nominal Operating PressureE Exempt9 Other [] Pressure _psi Test Temp.' _F

9. Remarks See Item 7 S Applicable Manufacturer'e Data Reports to be attached CERTIFICATE OF COMPLIANCE certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
  1. Type Code Symbol Stamp CefllfIbete of A. oriz tiN N/

N/A Expiration Date NAV Signed: 'Team Leader Date ___ -______

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by Hartford Steam Roller Inspection and Insurance Co. of Connecticut of Hartfor onnecticut have Inspected the components described In this Owner's Report during the period 07/161/07 to V and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section, XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concernlngi the examinations and corrective measures described in this Owner's Report Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 7,r6 S I nspabr's Signature National Board, State, Province and Endorsements Date: /"S I I

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07159

1. Owner Southern Nuclear ODeratinaComranv Date 04/10/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet Iof Address
2. Plant Voatle Electric Generating Plant Unit Name Waynesboro, GA 30830 1070956901 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1301/Main Steam System
5. (a) Applicable Construction Code ASME Sac. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped!:

Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A A/A V1-1301-107-H004 1987 INSTALLED YES I SUPPORT PRODUCTS _

7. Description of Work SnubberAD-5501, seanal #488 was replaced with a snubber AD-5501, serial#239. I

@ 8. Test Conducted: Hydrostatic ] Pneumatic[]

Other [] Pressure Nominal Operating Pressure[]

psi Test Temp. OF Exempto]

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Autorization No N/A Expiration Date NI/A

. SOwn lrnor1Owner's Designee, Team Leader Date Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geornia and employed by HartfordSteam Boiler Insoectlon andInsurance Co. of ConnectIcut of Haford, Connecticut have inspected the components described In this Owner's Report during the period 07/16/07 I to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shell be liable In any manner for any personal Injury or property damage or a lose of any kind arising from or connected with til.s Inspection.

___Commissions &-,4 75sr,

-" inspectfs Signature National Board, State, Province and Endorsements

@ Date BanA~.,& -'

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07160 V1 Owner Southern Nuclear OperatingCompany Date 04116/08

. 1. Name 40 Inverness Center Parkway, Birmingham,AL Sheet 1 of I Address

2. Plant Voglie Electric Generatina Plant Unit Name Waynesboro, GA 30830 1070956801 Address Repair/Replacement Organization P.O. No., Job No., etc.

.3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A

. Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address 4.. Identification of System 1301/Main Steam System

5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Ca., a (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No' PIPE PULLMAN POWER N/A N/A Vl-1301-104-H003 1987 INSTALLED YES SUPPORT PRODUCTS 7." Description of Work Snubber AD-12501, serial#41 was replaced with a snubberAD-12501, serial #132.
8. Test Conducted: Hydrostatic [] PneumaticE] Nominal Operating Pressure[] ExemptfZ]

Other [] Pressure _ psi Test Temp. 7F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of A hoatio No. N/A Expiration Date /NA-/A Signed

  • 1"".' Team Leader Date ______'______

Owner oi Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission-issued by the National BoArd of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of arf Caon elcut have Inspected the components described in this Owner's Report during the period 07/16/07 V to sQ Mx. and state that to the best of my knowledge and belief, the Owner has performed examinations and talken corrective measures" described in this Owner's Report In accordance with the requirements of the ASME Code, Section :Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ihe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer sh~all be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions &A~.75(

SSgnature *National Board, State, Province and Endorsements 0 Date :5'-A W ,nX

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi TravelerN 07161

1. Owner Southern Nuclear Operating Company Date 04113/08 Name 40 Inverness CenterParkway,Bininigham, AL Sheet 1 of Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1070956001 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtie Expiration Date N/A Address
4. Identification of System 1208/Chemicaland Volume Control System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cas i (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 203 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped!

" Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A Vl-1208-012-HO11 1987 INSTALLED YES -

SUPPORT PRODUCTS _

7. Description of Work SnubberAD- 153L, serial#250 was replaced with a snubberAD- 153L, serial#702.
8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Pressure[] Exempt'X Other ] Pressure _ psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of z N/A Expiration Date N/A Signed Team Leader Date "

  • I'"*

Owner or Own~er'l Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georaia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut:

of Harr. CQonncticut have inspected the components described in this Owner's Report during the period .07/16/07 to 0,. and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section IXI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. I Commissions GC,^. W'&

Inspeffor's Signature National.Board, State, Province and Endorsements Date ze, 4,-tfP -,car'*

CORRECTED_ ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07162

1. Owner Southern Nuclear OperatingCompany Date 06116108 C Name 40 Inverness Center Parkway,Birmingham, AL Address Sheet I of 1
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1070955601 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance DeDartment Type Code Symbol Stamp NAV Name Authorization No. NAV Plant Voglie Expirtion Date N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components r National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed aYes or No)

PIPE PULLMAN POWER N/A N/A Vl-1201-030-H055 1987 INSTALLED YES SUPPORT PRODUCTS 7, Description of Work SnubberAD-151, serial #427was replaced with a snubberAD-151, serial#424. The removed snubberAD-151, Serial#427 failedfunctional testing as documented by CR# 2008103664. The verification of acceptabilitywas not completed until afterthe pipe support was returnedto service as documented by CR# 2008106722.

8. Test Conducted: Hydrostatic [] Pneumatic"] Nominal Operating Pressure[] Exempt[N]

Other Q] Pressure _____ psi Test Temp. __ _ F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of " Georgia and employed by HartfordSteam Boiler Inspection andInsurance Co. of Connecticut of Harrd. have inspected the components described In this Owner's Report during the period 07/16/07 to _.4*34aand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this in on.

Commissions (,, 7*"

ff~spectir4ignature National Board, State, Province and Endorsements C Date  ; ", ,

ORIGINAL A FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07163

1. Owner Southern Nuclear OperatingCompany Date 04/17/08 Name 40 inverness CenterParkway, Birmingham,AL Sheet 1 off Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1070954201 Address Repair/Replacement Organization P.O. No;, Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vootle Expiration Date N/A Address
4. Identification of System 1204 / Safetv Injection System
5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section X.1Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Codie Name of Name of Manufacturer Board Other Year Removed, or Stamped Cmoent Manufacturer Serial No. No. Identification Built Installed (Yes or NIo)

PIPE PULLMAN POWER N/A N/A VI-1204-043-H013 1987 INSTALLED YES I SUPPORT PRODUCTS

7. Description of Work Snubber PSA-3, serial #28741 was replaced with a snubber PSA-3, serial#28740.

0 8. Test Conducted: Hydrostatic []

OtherE]

Pneumatic[]

Pressure _____

Nominal Operating. PressureW psi Test Temp. -_OF ExemptL]

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Autorization No. N/A Expiration Date N/A Signed W' Team Leader Date Owner or Owher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Roiler Insoection and InsuranceCo. of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to aZi.*, and state that to the best of my knowledge and belief, the Owner has performed examinations and tdken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or 'connected with this inspection.

Z:- ý ý .iCommissions

ýft'a C-34. Lo fnspe&6r'sSignature - National Board, State, Province and Endorsements 0 Date A3 k . A

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler# 07164

1. Owner Southern "NuclearOperatihg Company Date 04/10/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet of Address
2. Plant Voptle Electric GeneratingPlant Unit 1' Name Waynesboro, GA 30830 1070954001 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenahceDepartment Type Code Symbol Stamp N/A Name Authorization No. NIA Plant Votfle Expiration Date NIA Address
4. Identification of System 1204 / Safety Inlaction System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, WInter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A VI-1204-025-HO07 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-1, serial #24583 was replaced with a snubberPSA-1, serial#24326.
8. Test Conducted: Hydrostatic f] Pneumatic- Nominal Operating Pressure[ Exemptf]

Other [] Pressure pal Test Temp, OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify. that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auftrization No. NIA Expiration Date NIA Signed, 0 t<." \ or Team Leader Date

-- Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartford.n2 n icut have Inspected the components described In this Owner's Report during the period 07/16/07 to Y and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correct ve measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning; the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

( __L________________--___-__,

, lnspehuffSignaturs

____ Commissions 6p. .

National Board, State, Province end Endorsements Date /5 ,o.L _

cocm ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07165

1. Owner Southern NuclearOperating Company Date 06/16108 Name 40 Inverness CenterParkway, Birmingham, AL Sheet I of I Address 2 Plant Vogtle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1070955501 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1305/ Condensate and FeedwaterSystem
5. (a) Applicable Construction Code ASME Sec. iIl, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1305-064-H005 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA-35, serial#40271 was replaced with a snubber PSA-35, seral#12261. The removed snubber PSA-35r senal #40271 failed functional testingas documented by CR# 2008103698. The verification of acce tability was not completed unhiAaffar iha nina ~,,nnnt w~a rainmari in ~~an4i~a n~ dn,,nmnntaA hu (~a 9f~,A1fl~7OO III afterthe - ail-f was retumed to servke as documented b r- CR#2008106722 8, Test Conducted: Hydrostatic [J Pneumaticfl Nominal Operating Pressurer] Exempt]

Other n Pressure psi Test Temp. _

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Criiaeo A1 _ Expiration Data NIA Signed TeamnLeader Date L./-ki or Ower's Designee, Tite CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georafa and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartord Connticut have Inspected the components described in this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Snscs Sgntut B S P ndtCommissionss insp s ignaureNational Board, State, Province and Endorsements C Date c2 a Zrjm #¶'&O i

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASM E Code Section XI' Traveler# 07166

1. Owner Southern Nuclear OperatingCompany Date 04/10/08 Name 40 Inverness Center Parkway. Birmingham, AL Sheet I of Address
2. Plant Vogtle Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 1070955401 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp NIA Name Authorization No. NIA Plant Vogtle Expiration Date WA Address
4. Identification of System 1305 / Condensate andFeedwaterSystem
5. (a) Applicable Construction- Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built installed (Yes or NoL PIPE PULLMAN POWER N/A N/A V1-1305-060-H003 1987 INSTALLED YES SUPPORT PRODUCTS _

J

7. Description of Work Snubber PSA-100, serial #2219was replacedwith a snubberPSA-100, serial#2188.
  • J
8. Test Conducted: Hydrostatic 5 Pneumaticf] Nominal OperatingPressuref[] Exempt[i]

Other [] Pressure _psi Test Temp. _ _OF 9 Ramarks Sea Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A5t zati n No. N/A Expiration Date N/A Signed

-- oner* o)P (5wrer'Jo esignee, Title" Team Leader Date I L .

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors I and the state or Province of Georqla and employed by HartfordSteam Boiler Inspection andInsurance Co. of Connecticut of 6ardConnecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to /2& nand state that. to the best of my knowledge and belief; the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectionl XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning, the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shell be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions t AnspeciEr Signature~ National Board, State, Province and Endorsements Date AZ. APfA. ZM!B

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By.The, Provisions Of The ASME Code Section XI Traveler# 07167 Owner Southern Nuclear Operatlng Company Date 04/17/08 1

. 1.

Name 40 Inverness CenterParkway, Birmingham.AL Address Sheet 1 of

2. Plant Vogte Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 1070955101 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A.

Name Authorization No. N/A PlantVoctle Expiration Date NIA Address

4. Identification of System 1301 1 Main Steam System
5. (a) Applicable Construction Code ASME Sec. I11,1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca.,a (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed aes or No)L PIPE PULLMAN POWER N/A N/A Vl-1301-104-H004 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work Snubber PSA-35, serial #12253 was replaced with a snubberPSA-35, serial#12262. 1
a. Test Conducted: Hydrostatic ] Pneumatic[] Nominal Operating Pressure[] Exempt[Z]

Other ] Pressure -psi Test Temp. __IF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Au^rzation No N/A Expiration Date N/A Signed <rA:;w.s Team Leader Date OwneFror nr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of. Georgia and employed by HartfordSteam Boiler Inspectionand Insurance Co. of Connecticut of Lart! Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions &AL Inspelblor's Signature National Board, State, Province and Endorsements aWI Date R,3 AftPR. alexnal

ORIGINAL .

FORM NIS-2 OWNER'S REPORT FOR REPAIRPREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07168

1. Owner Southern Nuclear Operating Company Date 04/17/08 Name 40 Inverness Center Pakway,Birmingham, AL Sheet I of I Address
2. Plant Vogtle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1070954801 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A I

Name Authorization No. N/A Plant Vootla Expiration Date N/A Address

4. Identification of System 1204/Safety Injection System
5. (a) Applicable Construction Code ASME Sec. 111,1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or Nol PIPE PULLMAN POWER N/A N/A V1-1204-127-HO15 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work Snubber PSA-35, serial#12252 was replaced with a snubber PSA-35, serial#11248.
8. Test Conducted: Hydrostatic E] Pneumatic[] Nominal Operating Pressure[] Exempt[OJ Other U Pressure _ psi Test Temp. _ OF_
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached -

CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Au oirizatlon No Nl/A Expiration Date N/A -

Signed Team Leader Date 12..li 2r 16nOwnr or Ower's Designee, Title CERTIFICATE OF INSERVICE INSPECTION -

I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georcia and employed by Hartford Steam Boiler Insoection and InsuranceCo. of Connecticut of Hartfnrd, Connecticut have inspected the components described in this Owner's Report during the period 07/16/07 I to ....d/ *.L*LR*. and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectioni. X.

. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. C

_ _Inspe_-__ _ Signature

_'s National Board, State, Province and Endorsements Date d5 AAA. A~e'

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI

.2 Iraveler# 07169

1. Owner Southern Nuclear OperatingCompany Date 04/21/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I of Address

.2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830. A061951201 and 1070953901 Address Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp W/A Name Authorization No. AN/A
  • Plant Vogtle Expiration Date N/A Address
4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. I1/, 1977 Edition, Winter 1977 Addenda, 1644-5. Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001.Ed. thru 2003Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Manufacturer Board Other Year Removed, or Stamped Name of Name of Component Manufacturer Serial No. No. Identification Built Installed (es or No)

PIPE PULLMAN POWER N/A N/A VW-1204-023-H007 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber PSA.10; serial #15976 was replacedwith a snubber PSA-10, serial#12859. The telescoping cylinder was previously replacedin the Installedsnubber sernal #12859 under Traveler-06094and WO# A061951201.
8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Pressure[] Exempt(']

Other [ Pressure . psi Test Temp. __OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A C f ofAtorlzation No. ' N/A Expiration Date N/A Signed TeamLeader Date Owher or'Oner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by' HartfordSteam Boiler InsPactionand Insurance Co. of Connecticut of _Har.frd, Connecticut have Inspected the components described in this Owner's Report during the period 11/01/06 to e2g=&,

a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

.By signing this certificate neither the. Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

_______________________Commissions CY4. M i nspaor's Signature National Board, State, Province and Endorsements 6 Date : j AA. e'Otr I

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07'170

1. Owner Southern Nuclear OperatingCompany Date )4/10/08 Name of 40 Inverness CenterParkway, Birmingham, AL Sheet I of Address 1
2. Plant Vootle ElectricGenerating Plant Unit Name 1070953701 Waynesboro, GA 30830 1070953701 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment TypeaCode Symbol Stamp N/A Name Authorization No. N/A Plant Vogqle Expiration Date N/A Address
4. Identification of System 1201 / Reactor CoolantSystem
5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed, thru 2003 Add.

(c) Applicable Section Xl Code Case(s) MIA

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A VI-1201-042-HOOI 1987 INSTALLED YES SUPP5ORT PRODUCTS _

7. Description of Work Snubber PSA-1, serial #12207 was replaced with a snubber PSA-1, serial#24315.
8. Test Conducted: Hydrostatic'[ PneumatlcE Nominal Operating Pressure[ Exempt[IX Other F] P Pressure _ psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp. NIA Certificate of AutjbdIzatoon No,. N/A Expiration Date N/A Signed X' Team Leader Date . -

Owner or Ownet's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and InsuranceCo. of Connecticut of rf Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 i to W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any persohal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 6h 7-M n nspec.i"ris Signature " National Board, State, Province and Endorsements

[Date /tK, ,QdaA* ,Q0*

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07171 i

1. Owner Southem Nuclear OperatingCompany Date 04/17/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1070953401 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp Nl/A Name Authorization No. N/A Plant Voole Expiration Data N/A Address
4. Identification of System 1208/ Chemical and Volume Control System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca!

(b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components SNational Corrected, ASME Coae Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1208-024-H005 1987 INSTALLED YES SUPPORT PRODUCTS _

7. Description of Work Snubber PSA-1/4, serial #34217 was replacedwith a snubber PSA-1/4, sedal #34205.
8. Test Conducted: Hydrostatic [] PneumaticE1 Nominal Operating Pressure[] Exempt(X]

Other [] Pressure psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Au r n N/A Expiration Date N/A Signed Team Leader Date

.- - rc)ýner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticul of HV Cnn uecticut have inspected the components described In this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, SectionI XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningithe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising' from or connected with this Ins ecton.

__CCommissions 11.

'nspecto,6 Signature National Board, State, Province and Endorsements Date AHit.,oA'240

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section X1 Traveler# 07172

1. Owner Southern Nuclear Operatinq Company Date 07/02/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1___ _ Of 1 Address
2. Plant Vogfle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1060178404 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp W/A Name Authorization No. WA/

Plant Vogtle Expiration Date WAb Address

4. Identification of System 1204 / Safety Injection System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No) 1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-014-01 1987 INSTALLED YES SYSTEM PRODUCTS
7. Description of Work A I" drainline connection was welded to line 1204-014-4.per DCP 1060178404.
8. Test Conducted: Hydrostatic F1 Pneumatic[] Nominal Operating PressureX] Exemptrl Other [] Pressure _ psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Aj ýtion N/A Expiration Date N/A

4) Signed Ow.e*or O 'a.JTl Team Leader Date Owner oOwersesignee, Title"--,

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georlai and employed by Hartford Steam Boiler Inspection and InsuranceCo. of Connecticut of rtford cnneciut have Inspected the components described In this Owner's Report during the period 08/06/07 to -- i. f-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 15IA 74, r Inspqldr's Signature National Board, State, Province and Endorsements Date 4 ;3"-11-y W "

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07180 1, Owner Southern Nuclear OperatingCompany Date 06/18/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet of 1 Address

2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1071004001 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. NIA Plant Vootle Expiration Date WAV Address
4. Identification of System 1208/ Chemical and Volume ControlSystem
5. (a) Applicable Construction Code ASME Sec. ill, 1971 Edition, Winter 1972 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thu 2003 Add, (c) Applicable Section Xl Code Case(s) N/A
6. Identification Of Components
7. Description of Work installed replacementrelief valve. Relief valve SNN N56900-00-0074 has been previously installedandis utilized as a rotating spare; originallypurchased underPO# 7029205 and received underMIR# 970901.

B. Test Conducted- Hydrostatic (] PneumatlicF- Nominal Operating PressureE] Exempt[]

Other I[] Pressure _ psi Test Temp. ?F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of (thrizatiorlo. N/A Expiration Date N/A Signed V X ý,ý Team Leader Date

-Ow-neor'Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of 194d Clne tcut have inspected the components described In this Owner's Report during the period 08&23W7 to a$446 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XIL By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectionl.

Commissions 6* ;7 Inspects Signature National Board, State, Province and Endorsements Date ,=. .*Jt.,= "

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# O07181 Owner Southern Nuclear OperatingCompany Date 07/07/08 O 1. Name 40 Inverness CenterParkway. Birmingham, AL Sheet , Of 7;1 oo Address

2. Plant Vogtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1071003901 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp fl/A Name Authorization No. /AV N/A I Plant Vogfe Explratlon Date Address .
4. Identification of System 1205 / Residual Heat Removal System
5. (a) Applicable Construction Code ASME Sec, II1,1971 Edition, Winter 1972 Addenda, 1567 Code Caso I

(b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thQi 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped' Component Manufacturer Serial No. No, Identification Built Installed asesor No*)

RELIEF VALVE CROSBY VALVE S N56904-00-0065 N/A 1PSV8708B 1991 REMOVED YES GAGE CO. _

RELIEF VALVE CROSBY VALVE & N56904-00-0037 N/A 1PSV87088 1977 INSTALLED YES I GAGE CO.

7. Description of Work Relief valve was replaced with a rotatingspare which has been previously In service.
8. Test Conducted: Hydrostatic ] PneumatlcE] Nominal Operating Pressure[X Exempt[]

Other [] Pressure _ psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate offA . . N/A Expiration Date WA Signed kw ý TeamLeader Date Ownbrer Owndr's Designeer Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by HartfordSteam Boiler Inspection and insurance Co. of ConnecticUt of Haror nectict have inspected the components described In this Owner's Report during the period 08/28/07 I to 'a nd state that to the best of my knowledge and belief, the Owner has performed examinations end taken corrective measures described' In this Owner's Report In accordance with the requirements of the ASME Code, Sectlo!n XI.

By signing this certificate neither the Inspector nor hia employer makes any warranty, expressed or Implied, concernin'g the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employerfshall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions -A 7',r,,

spect ignature National Board, State, Province and Endorsements -

pLDate t.- .2uhI

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRI/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07183

1. Owner Southern Nuclear OperatingCompany Date 06/19/G0 Name 40 Inverness CenterParkway, Birmingham,AL Sheet of 1 Address
2. Plant Voctle Electric GeneratlnePlant Unit 1 Name Waynesboro, GA 30830 1070494301 and PO)# 7078886 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse ElectricCo. Type Code Symbol Stamp N/A Name Authorizatlon No. N/IA 44 Inverness CenterPwv.. Suite 148. Blrminaham. AL 35242 Expiration Date IWA Address
4. Identification of System 1201 / Reactor Conlant 9ystem 1201 / Reactor C lant Svstern
5. (a) Applicable Construction Code ASME Sec. It1, 1971 Edition, Winter 1972 Addenda, NV/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity -2001 Ed. thnJ 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PUMP WESTINGHOUSE 6-9744D35G01 38 1-1201-P6-002 1984 INSTALLED YES ELECTRIC CORP.

7. Description of Work A replacement No. 2 seal housing was installed. The replacement No. 2 seat housinq,serial number 1607, is a rotating sparethat has been previously In service.
a. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[E] Exempt[]

Other [] Pressure _psi Test Temp.

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A rl n No. N/A Expiration Date N/A Signed Team Leader Date Owner or Oreer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoi ' and employed by HartfordSteam Boiler Inspection and insurance Co. of Connecticut of Hartford, Connecticut- have inspected the components described in this Owner's Report during the period 0829/07 to I.1 =*, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions t 7-.

Sffispecto-O'Signature National Board, State, Province and Endorsements Date Js ". A "

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 07187

1. Owner Southern Nuclear OperatingCo.mpany Date 06/23/08 Name 40 Inverness CenterParkway,Birmingham, AL Sheet of 1 Address
2. Plant Vogtle Electnc Generating Plant Unit 1 Name Waynesboro, GA 30830 1070494401and PO# 7078886 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness Center Pwy., Suite 148, Birmingham, AL 35242 Expiration Date W/A Address
4. Identification of System 1201 /Reactor Coolant System
5. (a) Applicable Construction Code ASME Sec. iii, 1971 Edition, Winter 1972 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) NVA

6. Identification Of Components National Corrected, " ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PUMP WESTINGHOUSE 10-9744D35G02 N/A 1-1201-P6-004 1995 INSTALLED YES ELECTRIC CORP.

7. Description of Work A replacementNo. 2 seal housing was installed. The replacemenl No. 2 seal housing, serial number 1813, is a rotatingspare that has been previously in service.
8. Test Conducted: Hydrostatic f] Pneumatic[] Nominal Operating PresSure[z] Exempt(]

Other [] Pressure . psi Test Temp. __ _ F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of tohion N/A V Expiration Date NIA 9 Signed w Ti Team Leader Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georala and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of Hartfo .on~etiat have inspected the components described In this Owner's Report during the period 08/29 /7 to f and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correctve measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this ecton.

Commissions &s.

Inspectlc s Signature - National Board, State, Province and Endorsements Date ,as/*.1 , ,-_ r,

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07195

1. Owner Southern Nuclear OperatingCompany Date 04110108 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I of 1 Address
2. Plant Vogtle Electric Generating Plant Unit Name Waynesboro, GA 30830 1053337801 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name AuthoriIzation No. N/A Plant Vogtle Expirat ion Date N/A Address
4. Identification of System 1204 I Safety Injection Systemr S. (a) Applicable Construction Code ASME Sec. Iii, 1977 Edition , Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Act ivity -2001 Ed. thru 2003 Add..

(c) Applicable Section Xl Code Case(s) NWA

6. 'Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built installed (Yes or No)

PIPE PULLMAN POWER N/A N/A Vl-1204-003-H006 1987 INSTALLED YES I SUPPORT PRODUCTS _

'I

7. Description of Work Snubber PSA-1/4, serial#33467 was replaced with a LUsega Type 30 snubber,serial#30500420/092.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Exempt[M Other [] Pressure _ psi Test Temp. __OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A r

Certificate of Aut orIon No. N/A Expiration Date N/A -

Signed -W  ?

Owner or Own~r's Designee, Title Team Leader Date Ic(cS t

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georola and employed by HartfordSteam Boiler Inspectionand insuranceCo. of Connecticut of Harfd, Connecticut have Inspected the components described in this Owner's Report during the period 09/17/07 i to . AIA.I.* , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective. measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectioni Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningl the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with 'this inspection.

  • j i
.r AarZ*/**- Commissions 64. "

onspar's Signature National Board, State, Province and Endorsements Date /, aP. PA

11 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY . '

As F*equired By The Provisions Of The ASME Code Section Xl Traveler# 07197 0 1. Owner Southern NuclearOperatingCompany Name ,

40 Inverness Center Parkway, Birmingham,AL Address Date Sheet 04/18/08 of 1

2. Plant VoWtie Electric GeneratinqPlant Unit 1 Name Waynesboro, GA 30830: 1053338101 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Malntenaince Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1206 / ContainmentSpray System
5. (a) Applicable Construction Code. ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

() Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A VI-1206-002-H027 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber AD- 153, serdal '405 was replacedwith a Lisega Type 30 snubber,serial#30500642/86.

A We. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Exempt~jJ OtherE] Pressure . psi Test Temp. OF

9. Remarks See Item 7.
  • Applicable Manufacturer's Data Reports to be attached
  • .. CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate ofthorizatlon No. N/A Expiration Date N/A SSigned: Team Leader Date Owner r Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors-and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection andInsurance Co. of Connecticut of Harifood Connecticut have inspected the components described in this Owner's Report during the, period 09/17/07 to -/_-,1 >.-f--, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected,.wlth this Inspection.

Commissions GA.

V Insl tor's Signature National Board, State, Province and Endorsements Date: 40A. - A,*.

I ORIGINAL -

,I FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 4'

Traveler# 07203

1. Owner Southern Nuclear Operating Company Date 04/10/OR Name 04110108 40 Inverness CenterParkway, Birmingham, AL Sheet 1 of I Address
2. Plant Vootle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1053339101 Address RepalirReplacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voqtle Expiration Dale N/A Address
4. Identification of System 1301/Main Steam Svstem
5. (a) Applicable Construction Code ASME Sec. I11,1977 Edition, Winter 1977 Addenda, N-249.1 Code Cat a (b) Applicable Edition of Section XI Used for Repalr/Replacement Activity 2001 Ed. thru 2003Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Cole Manufacturei Board Other Year Removed, or Stamped Name of Name of Component Manufacturer Serial No. No. Identification Built Installed YesYES or NoL PIPE PULLMAN POWER N/A N/A V I-1301. t 6.HO002 1987 INSTALLED SUPPORT PRODUCTS

__ _I __!i

7. Description of Work Snubber AD-5503, serial #224 was replaced with a Usega Type 30 snubber,serial#30500211/089. I
8. Test Conducted: Hydrostatic [] Pneumatic] Nominal Operating Pressurel] Exempto' Other r Pressure psi Test Temp. °F
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xh.

Type Code Symbol Stamp N/A Certificate of Nthorizati N N/A Expiration Date N/A Signed Owner o O'n-'s Team Leader Date !dft 04<ýM rOvrier or Ovner's Designee, Title Er;.. 11IC I E-3.OFUP IN:*P..VlIC INPECT"UIOINI I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticu of Htord, Connecticut have Inspected the components described In this Owner's Report during the period 09/17/07 I to la,jaoor,, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Sectioni Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningithe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions 6 Y I lnspeeffir's Signature National Board, State, Province and Endorsements 0 Date /,a M APR.

AD o '

  • ORIGINAL 4 FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY
  • As Required By The Provisions Of The ASME Code Section XI Traveler# 07205
1. Owner Southern NuclearOperatingCompany Date 04/14/08 P Name 40 Inverness CenterParkway, Birmingham, AL Sheet I of Address
2. Plant Vogle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1053341401 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voatle Expiration Date N/A Address 4., Identification of System 1301/Main Steam System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thrn 2003 Add, (c) Applicable Section XI Code Case(s) N/A
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No0)

PIPE PULLMAN POWER AN/A N/A V1.1301-109.H004 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Snubber AD-151L, serial #251 was replaced with a Lisega Type 30 snubber,serial#30500263/14.
8. Test Conducted: Hydrostatic [] Pneumaticn] Nominal Operating Pressure[] Exempt[o]

, ]Other Pressure - psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME.

Code,Section XI.

Type Code Symbol Stamp . N/A.

Certificate of t o*I N/A Expiration Date N/A Signed; Team Leader Date

  • Owner or'Oner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION a I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boller Inspectionand Insurance Co. of Connecticut of Hartford. Connecticut have Inspected the components described In this Owner's Report .during the period 09/17/07 to . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section. XI.

. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

__________________________Commissions 11.4 7s-.

Finspec-dlis Signature . National Board, State, Province and Endorsements SDate S P.A!eT

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT AcTIvITY As Required By The Provisions Of The ASME Code Section X1 y

Traveler# 07206

1. Owner Southern Nuclear OperatingCompany Date 04/21/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet I of I Address
2. Plant Votile Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1053341501 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Coda Symbol Stamp N/A Name Authorization No. N/A Plant Voptle Expiration Date N/A Address
4. Identification of System 13011 Main Steam System
5. (a) Applicable Construction Code ASME Sec. i//, 1977 Edition, Winter 1977 Addenda, N-249-'1 Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1301-126-H037 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work SnubberAD-73, serial#187 was replaced with a LIsega Type 30 snubber,serial#30500235/019.
8. Test Conducted: Hydrostatic [] Pneumatic[ Nominal Operating Pressure[] ExemptZJ Other ] Pressure _psi ' Test Temp. _ OF_
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auhjrizaeon No. N/A Expiration Date N/A Signed. OeJ e n"1t Owner-or Own6r's Des~ignee, Title Team Leader Date d/

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Co tcu have inspected the components described in this Owner's Report during the period 09/17/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

_ _ _ _ _ _ Commissions 6, 75(P i

  • Inspeor's Signature . National Board, State, Province and Endorsements 6 Date W Atx. oalt

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY F

  • As Required By The Provisions Of The ASME Code Section XI Traveler # 07209
1. Owner Southern Nuclear Operating Company Date 04/09/08 Name 40 Inverness Center Parkway, Birmingham,AL Sheet 1 of Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 1053343501 Address RepalrlReplacement Organization P.O. No., Job No,, etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vog1le- Expiration Date WN/A Address
4. Identification of System 1305/Condensate and FeedwaterSystem S. (a) Applicable Construction Code ASME Sec. III. 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(q) Applicable SctionXi Code Case(s) N/A

8. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1305.064-HO06 1987 INSTALLED YES SUPPORT PRODUCTS _

7. Description of Work Snubber PSA-100, serial #2504 was replacedwith a Lisega Type 30 snubber,serial #30500569/02.
8. Test Conducted: Hydrostatic [ PneumatfcE Nominal Operating Pressure[] Exempt'l Other [ Pressure _ psi Test Temp. _F
9. Remarks See Ite/n 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE

'I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Iz on No N/A Expiration Date N/A Signed *' /(" o'~r Team Leader Date I/*-.L*.*  ;

-"gnwne&-Owhor's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the stats or Province of Geordta and employed by Hartford Steam Boiler Inspectionand Insurance Co. of Connecticul of Hartford. Connecticut have Inspected the components described in this Owners Report during the period 09/17/07 to .7.1_./,2_ X, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning

!the examinatlons and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer sIhall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this

___________________________Commissions , 74.

inspe@6r' Signature 'Nationlal Board, State, Province and Endorsements Date lr APA ,2=i*

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07221

1. Owner Southern Nuclear ODeratinaCompany Date 07/08/08 Name 40 Inverness CenterParkway, Birmingham. AL Sheet I of 5 Address
2. Plant Voatle Electric GeneratinaPlant Unit 1 Name Waynesboro, GA 30830 Address RepairlReplacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. NAV Plant Vootla Expiration Oato NAV Address
4. Identification of System 1208 / Chemicaland Volume Control System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No VALVE ATWOOD & 1-18269-07 N/A IHV41320A 1983 CORRECTED YES MORRILL CO., INC.
7. Description of Work Installeda replacementplug and cover screws on valve. Copies of Form N-2 for the replacementplug and cover screws are attached.

S. Test Conducted: Hydrostatic F] Pneumatlc[E Nominal Operating PressureE[_] Exempt[]

Other ] Pressure _psi Test Temp. __ _ F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A ri n WA Expiration Date N/A E Signed e, V Team Leader Date 7 c?

`:-"wne OrOwrler% Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georcia and employed by Hartford Steam Boiler Inspection andInsuranceCo. of Connecticut of Hartfod.CannicgLt have Inspected the components described In this Owner's Report during the period 12/06107 to Z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In ction.

_ _ _ _low Commissions 4 7s"L,

" fnspectcs ignature National Board, State, Province and Endorsements Date / Z/f-iryc j .

-TrL/eIer- -07 22 (

Skeet 2<45 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production pg. 1 ofil2

1. Manufactured and certified by Fisher Controls International. Inc.. N. Stnningnn  : CT (name aindaddmess of NPT Cartificate Holder(

Power Company, PO Box 1295, Birmingham, AL

2. Manufactured for Georgia (name and address of Purchast er)

Vogtle Electric Generating Plant, Waynesboro, CA

3. Location of installation (name and addreisl
4. Type: 16B1649 Rev.A SA564 Gr. 630 145 ksi min. n/a 1996 (drawing no.) i. spec. no. ) (tensile strength) ICRtN Wart built)
5. ASME Code.Section III,Division 1: 4.-9*Ji97-191 -) Winter 77 2 n/a

,& Y-zj _ tedlatonl (addenda date) (class) Code Case no.)

6. Fabricated in accordance with Const. Spec. (Div. 2 only) n/a Revision n/a Date nj/,

(no.)

7. Remarks: Plug for Atwood & Morrill 3" Class 300 Figure 1366 BW
8. Nom. thickness (in.) n/a Min. design thickness (in.) n/a Die. ID (ft &in.) n/a Length overall (ft & in.) .n/a....
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

Part or Appurtenance National Part or Appurtenance National Serial Number Board No. Serial Number Board No.

in Numerical Order in Numerical Order (1)

A0369 n/a (26) i - +

(2) (27)

(3) (28) +

(4) (29)

(5) 130) "I.

(6) 131)

(7) 132)

(8) (33)

(9) (34)

(10) (35) 111) (36)

(12) (37)

(13) (38)

(141 (39)

(15) .4 (40)

(16) (41)

(17) (42)

(18) I (43)

(19) (44)

(20) (45) 121) (46) 122) (47)

(23) (48)

(24) (49)

(25) i (50)

10. Design pressure 375 psi. Temp, 225 - F. Hydro. test pressure n/a at temp. OF (when applicable)

Supplemental information in the form of lists, sketches, or drawings may he used provided (11 size is 8 % x t1 (2) information in items 2 and 3 on this Date Report is included on each sheet. (3) each sheet is numbered end the number of sheets is recorded at the top of this form.

(12/88) This form (E000401 may be obtained from the Order Dept., ASME, 22 Law Drive. Box 2300, Fairfield, NJ 07007-2300.

FORM N-2 (Back - Pg. 2 of .2_2 8 e L 3o45 Certificate Holder's Serial Nos. A0369 through n/a CERTIFICATION OF DESIGN Design specifications certified by S.W. Ashworth P.E. State GA Reg. no. 017030 (when applcabl.1 Design report* certified by n/a P.E. State n/a Reg. o. n/a 1when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this~llbli=li P conforms to the rules of construction of the ASME Code, Section II1.Division 1.

NPT Certificate of Authorization No. N-1847 Expires Sept. 2, 1998 (NPT Cartificate Holder) faluthorized representativrej, CERTIFICATE OF INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by Commercial Union Ins. Co.

of Boston, M have inspected these items described in this Data Report on March 18, 1996 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code,Section III,Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore. neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

Date 3'-Z3 A Sign . .

(Atoie napector)

- Commissions c7,3*/-Ž INatI'. as.iifle). endorsements) and stateor prov. and no.)

T-rmvv er - 0722.2(

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL Skeet 4Vf5 NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production pg. 1 of2

1. Manufactured and certified by Fisher Controls International. Inn.- N. rtnni* rofnn tT (name and addressa Of NPT Certiicate Holder)

Georgia Power Company, PO Box 1295, Birmingham, AL

2. Manufactured for (name and address of Purchaser)
3. Location of installation Vogtle Electric Generating Plant, Waynesboro, GA fname and addreu)
4. Type: 16B1594 Rev.A SA193 B8 96.4 ksi n/a 1996 (drawing no.) Imt. laie. no.1 (tensile strength) . ICRNI (year built)
5. ASME Code,Section III, Division 1: 9 19'17 Winter 77 2 n/a s,., +&Z-ledhion) iaddenda dejatela)s) iCode Ca no.s Fabricated in accordance with Const. Spec. (Div. 2 only) n/a Revision n/a Date n/a (no.)
7. Remarks: 7/16"-14 x 11/2" hex head cap screws for Atwood & Morril 3" Clas-n Ion Figure 1366 BW. manufactured by Texas Bolt Co. Heat No. 36231 Quantity 4 bolts all identified with the number "5".
8. Nom. thickness (in.) n/a Min. design thickness (in.) n/a Dia. ID (ft & in.) 7/16" Length overall (ft & in.) 1  !/?"
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

Part or Appurtenance National Part or Appurtenance National Serial Number Board No. Serial Number Board No.

in Numerical Order in Numerical Order 01 5 n/a (26)

(2) (27)

(3) (28)

(4) 129)

(5) (30)

(61 (31)

(7) (32)

(8) (33)

(9) (34)

(10) (35)

¶11)

(35)

(12) (37)

(13) (38)

(14) (39)

(15) (40)

(16) (41)

(17) (42)

(18) (43)

(19) (44)

(20) (45)

(21) (46)

(22) (47)

(23) (48)-

(24) (49)

(25) (50)

10. Design pressure 375 psi. Temp. 225 OF. Hydro. test pressure n/a at temp. OF (when applicablel Supplemental information In the form of lists, sketches, or drawings may be used provided ll) size is 8 % X 11, (2) information in Items 2 and 3 on this Data Report is Included on each sheet, (3) each sheet is numbered and the number of sheets Is recorded at the top of this form.

412188) This form IE00040) may be obtained from the Order Dept., ASME, 22 Law Drive. Box 2300, Fairfield, NJ 07007-2300.

-Troorcler-Z-07221 FORM N-2 (Back - Pg. 2 of__22' ) eel= 5 o-5 Certificate Holder's Serial Nos. through CERTIFICATION OF DESIGN Design specifications certified by S.W. Ashworth PE. State GA Reg. no. 017030 (when appicableStn Design report* certified by n/a P.E. State n/a Reg. no. fl/a 1when applic,1Slej)

CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this ithese) Hex Head Cap Screws conforms to the rules of construction of the ASME Code, Section IlII,Division 1.

NPT Certificate of Authorization No. N-1847 Expires Sept. 2, 1998 1 996 Date Ma rch 18, Name Fisher Controls Int'l., Inc. Signed -

INPT Certiicate Holder) (authorized ,eprasentatr.

CERTIFICATE OF INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by Commerc-ial Union Ins. Co.

of Boston, KA have inspected these items described in this Data Report on Harch 18 , 1996 ,and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section Ill, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

Date '/--Z3 Sigii Commissions 63

~~j(Authorho ized inspector lNat'l. Bd. mcin.endorsements) and state or prov, and no.]

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08009

1. Owner Southern NuclearOperating Company Date 06/19/08 Name 40 Inverness Center Parkway,Birmingham,AL Sheet of Address
2. Plant Vogtle Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 WO# 1060607904and PO# 7071336 Address Repair/Replacement Organization P.O, No., Job No., etc.
3. Work Performed by Westinchouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. IVA 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Expiration Data N/A Address
4. Identification of System 1201 / Reactor Coolant System _______ _____

`ASME Sec. /II 1971 Summer 1972 N/A

5. (a) Applicable Construction Code **ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Ys or No)
  • PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1981 CORRECTED YES VESSEL ELECTRIC CORP.

1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS I III_1_ 1

7. Description of Work A full structuralweld overlay (FSWOL) was completed on the 1PSV8OIOA safety valve nozzle (N-*). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 058-W-01. The FSWOL design included the use of alternatives to existing Code guidance and was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternativerepairwas obtained under NRC letterNL.08-0405. The FSWOL was completed in accordance with DCP# 1060607901.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[X] Exempt[]

Other r] Pressure N/A psi Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Pthorization ,. N/A Expiration Date N/A

~'Signed .% 'J-Team Leader Date S""" Ow~ner or ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartfrd Con ectict have inspected the components described In this Owner's Report during the period 02/07/08 to 75.,z_ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations- and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this in ection.

Commissions

'fspectols Signature National Board, State, Province and Endorsements Date 7 a)* .r-y 4 r

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section X1 Traveler# 08010

1. Owner Southern Nuclear Operating Company Date 06/19108 Name 40 Inverness CenterParkway, Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle Electric Generating Plant Unit W Name WO# 1060607903 and PO#7071336 Wavnesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse ElectricCo. Type Code Symbol Stamp N/A Name Authorization No.

44 Inverness CenterParkway,Suite 148, Birmingham, AL 35242 Expiration Date NIA Address

4. Identification of System 1201 /Reactor Coolant System

`ASME Sec. I1 1971 Summer 1972 N/A S. (a) Applicable Construction Code *°ASME Sec. II/ 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Edition,2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)
  • PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1981 CORRECTED YES VESSEL ELECTRIC CORP.

1201 PIPING PULLMAN POWER N/A N/A IX4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS I I I I I _ _

7. Description of Work A full structuralweld overlay (FSWOL) was completed on the 1PSV8010B safety valve nozzle (N-2). This FSWOL was placed over the vessel safe-end weld andincluded the piping attachment weld 057-W-0 1. The FSWOL design Included the use of alternativesto existing Code guidance and was submittedto the NRC as ISI-GEN-AL T-07.01 (NL-07-1320 andNL-0 7-2206. Approval for this alternativerepairwas obtainedunder NRC letter NL-08-0405. The FSWOL was completed in accordancewith DCP# 1060607901.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressureg Exempt[]

Other [] Pressure N/A psi Test Temp. N/A OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate offpthorization Do. N/A Expiration Date N/A Signed e kneTt Owvner or Ownmer's Deal lnee, Title Team Leader Date (E3 L. o CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler inspection and Insurance Co. of Connecticut of HartfodC nn ticut have inspected the components described In this Owner's Report during the period 02/07/08 to , and state that to the best of my knowledge and belief, the Owner hasperformed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions 6,,, 75-6 VelnspectW~Signature National Board, State, Province and Endorsements I Date lo nzý.I- Y _2b

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler # 08011

1. Owner Southern NuclearOperating Company Date 06/19/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of 1 Address
2. Plant Voptle Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 WO# 1060607902 and PO# 7071336 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinahouse Electric Co. Type Code Symbol Stamp NAV Name Authorization No. NA&

44 Inverness Center Parkway,Suite 148, Birmingham, AL 35242 Expiration Date N/A Address

4. Identification of System 1201 / Reactor Coolant System

`ASME Sec. ill 1971 Summer 1972 N/A

5. (a) Applicable Construction Code **ASME Sec. IH/ 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix ViII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda
6. Identification Of Components 7.

I Description of Work A full structuralweld overlay (FSWOL) was completed on the 1PSV8010C safety valve nozzle (N-3). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 056-W-01. The FSWOL design included the use of alternativesto existing Code guidanceand was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternative repairwas obtainedunder NRC letter NL-08-0405. The FSWOL was completed in accordancewith DCP# 1060607901.

8. Test Conducted. Hydrostatic R Pneumatic[Z] Nominal Operating Pressure El Exemptfl Other [] Pressure N/A psi Test Temp. N/A
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorti on N N/A Expiration Date IN/A Signed 92 '/!....- Team Leader Date

  • Z3

- "Owhd o'FOIner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by HartfordSteam Boiler Inspection and Insurance-Co. of Connecticut of HartfordConnectcut have Inspected the components described in this Owner's Report during the period 02/07/08 to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions r%-A.,'5'*

-Dt IV nspec6 s Signature National Board, State, Province and Endorsements IDate et 'r-C-'A564 Abcs

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 08012

1. Owner Southern Nuclear OperatingCompany Date 06/19108 Name 40 Inverness Center Parkway. Birmingham, AL Sheet 1 of I Address
2. Plant Vogtle Electric GeneratingPlant Unit W Name Waynesboro, GA 30830 WO# 1060607907 and PO# 7071336 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness CenterParkway, Suite 148, Birmingham,AL 35242 Expiration Date N/A Address
4. Identification of System 1201 Reactor Coolant System
  • ASMESec. III 1971 Summer 1972 W/A
5. (a) Applicable Construction Code "°ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No
  • PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP.

1201 PIPING PULLMAN POWER N/A N/A 1X40L4D20 1987 CORRECTED YES SYSTEM PRODUCTS II I__I1_

7. Description of Work A full structural weld overlay (FSWOL) was completed on the Pressurizerreliefline nozzle (N-4). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 059-W-01. The FSWOL design includedthe use of alternatives to existing Code guidance and was submitted to the NRC as ISl-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternativerepairwas obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptE]

Other [:] Pressure N/A psi Test Temp. N/A -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 1i1J1L. Team Leader Date j Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georala and employed by HartfordSteam Boiler Inspection and InsuranceCo. of Connecticut of Hartford. ConncticuL have inspected the components described In this Owner's Report during the period 02/06/08 to * .a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this ins ection.

. Commissions 6,-4, 75-Ia nspect* Signature National Board, State, Province and Endorsements Date /0 T.' r aC.

jp-¢ 2

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08013

1. Owner Southern Nuclear Operatinq Company Date 06119/08 Name 40 Inverness Center Parkway. Birnmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 WO# 1060607905 and PO# 7071336 Address RepalrlReplacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinohouse Electric Co. Type Code Symbol Stamp N/A Name Authonitatlon No. N/A 44 Inverness Center Parkway, Suite 148, Blnningqham, AL 35242 Expiration Date Address
4. Identification of System 1201 Reactor Coolant System
  • ASMESec. III 1971 Summer 1972 N/A
5. (a) Applicable Construction Code **ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix VIII (c) Applicable Section Xi Code Case(s) None from the 2001 Edition,No Addenda
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)
  • PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP.

1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS

7. Description of Work A full stnjctural weld oveday (FSWOL) was completed on the Pressurizerspray line nozzle (N-5). This FSWOL was placed over the vessel safe-end weld and includedthe piping attachment weld 030-W- 14. The FSWOL design included the use of alternativesto existing Code -guidanceand was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Apprval for this alternativerepairwas obtained underNRC letter NL-08-0405. The FSWOL was completed in accordancewith DCP# 1060607901.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating PressureZ Exempt[]

Other [] Pressure NiA psi Test Temp. NIA -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A CertificateAofJAZol on No.# N/A Expiration Date N/A Signed or)I5u DPC.eg i.'t. Team Leader Date "Z- ,

.. . -"wne? or Own' Dee~no, Title ...

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by HartfordSteam Boiler Inspectdion and Insurance Co. of Connecticut of tiagifrd,Con ut have inspected the components described In this Owner's Report during the period 02/O6/08 to . 9_2C&Iand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this C ntion.

Commissions r-Inspect~hSIgnature National Board, State, Province and Endorsements Date 4Ljr abr it

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASM E Code Section XI Traveler# 08014

1. Owner Southern Nuclear OperatingCompany Date 06/19/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet 1 of 1 Address
2. Plant Vogtle Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 WO# 1060607906 and PC# 7071336 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse ElectricCo. Type Code Symbol Stamp NIA Name Authorization No. N/A 44 Inverness CenterParkway, Suite 148, Birmingham, AL 35242 Expiration Date N/A Address
4. Identification of System 1201 Reactor Coolant System

'ASME Sec. IIl 1971 Summer 1972 N/A

5. (a) Applicable Construction Code **ASME Sec. I// 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed YeoN "PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP.

" 1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM. PRODUCTS III

7. Description of Work A full structuralweld overlay (FSWOL) was completed on the Pressurizersurge line nozzle (N-6). This FSWOL was placed over the vessel sate-end weld and included the deoi~ attachmentweld 053- W-01. The FSWOIL desien included the use cf included the oloino a ment weld 053-W-01. elSWOLdn-sioninclu dthauseof was placed over alternatives to existing Codesafe-end the vessel ouidance andand weld was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Aporoval for this alternativerepairwas obtained underNRC letter NL-08-0405. The FSWOL was completed in accordancewith DCP# 1060607901.
8. Test Conducted: Hydrostatic E] Pneumatic'] Nominal Operating PressurezJ Exempt[]

Other F1 Pressure N/A psi Test Temp. N/A

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Atlorizatian No. N/A Expiration Date N/A Signed Team Leader Date ' ___________

Owner or Ovner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of - Georgia _and employed by HartfordSteam Boiler Inspection and InsuranceGo. of Connecticut of _Hartfod Cnne ticut have inspected the components described in this Owner's Report during the period 01/391/08 to Q a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions g!

17 Inspect Signature National Board, State, Province and Endorsements Date / ,0* , ,2

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 08020

1. Owner Southern Nuclear OperatingCompany Date 07/14/08 Name 40 Inverness Center Parkway,Birmingham,AL Sheet I of I Address
2. Plant VogUe Electric Generating Plant Unit Name Waynesboro, GA 30830 1062027801 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No.

Plant VogUe Expiration Date N/A Address

4. Identification of System 1201 /Reactor Coolant System
5. (a) Applicable Construction Code ASME Sec. I4 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed 1201 PIPING NUCLEAR 4027-001 N/A 1X6AB08-56 1986 CORRECTED YES SYSTEM INSTALLATION lX6ABOB-58

.....SER VICES CO. ,_....._ _

7. Description of Work Installedreplacement 3/4" X 5/16"reducer unions at seal table locations H6, N14, C5, J7 and R6.
8. Test Conducted: Hydrostatic [] Pneumaticfl Nominal operating PressureE] Exempt [g]

Other n Pressure psi Test Temp. -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certifi cate ofA orl ic NIA Expiration Date NAV Signed _v T Team Leader Date t,0ag O)wnecr Own r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford, onnecticut have inspected the components described In this Owner's Report during the period 02/04/08 to 1 and state that to the best of my krowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury o property damage or a loss of any kind arising from or connected with this ino econ.

Commissions .

Inspectof Signature. National Board, State, Province and Endorsements Date /__ 1__0_- " I_

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 08034 Owner Southern NuclearOperating Company Date 04/17/08

@ 1. Name 40 Inverness CenterParkway, Birmingham, AL Sheet of Address

2. Plant Vogtle Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 1070957701 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. MIA Plant Vootle Expiration Date WA Address
4. Identification of System 1208 /Chemical and Volume Control System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cai (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thni 2003 Add, (c) Applicable Section XI Code Case(s) N/A
6. Identification Of Components National Corrected, ASME Coe Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or NoL PIPE PULLMAN POWER N/A N/A V1-1208-055.H046 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work A replacementnut was installed on the pipe clamp bolt.

0 8. Test Conducted: Hydrostatic R Pneumatlce-Other F] Pressure _

Nominal Operating Pressure--

psi Test Temp.

ExemptNJ

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auor tion*.No. N/A Expiration Date N/A-Signed X  ?\ Team Leader Date " _

bwniaror 0wrfer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by* HartfordSteam BoilerInspection and Insurance Co. of Connecticut of art onecticut have inspected the components described in this Owner's Report during the period 03/20/08 1 to & and state that to the best of my knowledge and belief, the Owner has performed examinations and tiken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions (&A 7'",

Flnspec~¶ifs Signature National Board, State, Province and Endorsements 0 Date *R.

A-3 ,A

.b

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08035

1. Owner Southern NuclearOperating Company Date 06116/08 Name 40 Inverness CenterParkway,Birmingham. AL Sheet of I Address
2. Plant Vogtile Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1062001501 Address RepairlReplacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1201 / ReactorCoolant System
5. (a) Applicable Construction Code ASME Sec. i1l, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repalr/Replacement Activity 2001 Ed. thry 2003 Add.

(c) Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Narne of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

PIPE PULLMAN POWER N/A N/A V1-1201-030-H044 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work Installed replacementloadpin on pipe support.
a. Test Conducted: - Hydrostatic [] Pneumatic -] Nominal Operating Pressure[] Exempt[Z Other El Pressure _ psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp WA Certificate of Au rz NIA Expiration DateNI Signed I TeamLeader Date

. . .. (JOwner .idrOv;neres Designee, Title..

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of. Georgia and employed by HartfordSteam Boiler Inspectionand Insurance Co, of Connecticut of C ccut ecritfo have inspected the components described In this Owner's Report during the period 03121/08 to o and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcil6 measures described In this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this AV Commissions 7, ý.r_

ý napeoctor

.gnaturei National Board, State, Province and Endorsements

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 08'036 Tra for #

1. Owner Southern NuclearOperating Company Date 06/16/08 Name 40 Inverness Center Parkway. Birmincham. AL Sheet of. -

it- M ,

ArMPAO*

2. Plant Vogtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1080557701

. Address Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed by MaintenanceDepartment Type Coda Symbol Stamp N/A Name Authorization No. N/A Plant Vog/e Expiration Date N/A Address 4.. Identification of System 1305 / Condensate and FeedwaterSvstem
5. .(a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xi Used for RepalrlReplacement Activity 2001 Ed. thru 2003 Add, (a) App!lcable Section Xl Code Case(s) N/A
6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer. Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification' Built Installed or Noi PIPE PULLMAN POWER N/A N/A V1-1305-064-HO04 1987 INSTALLED YES SUPPORT PRODUCTS _ _I
7. Description of Work Snubber PSA-100, serial #2226 was replacedwith a snubber PSA-100, sedal #2175. The removed snubberPSA-100. serial #2226 failed functionaltesting as documented perCR# 2008104385. The verification of acceptability was not completed until 0 8.

after the pipe supportwas returnedto service as documented by CR# 2008106722.

Test Conducted: Hydrostatic [] Pneumsaticr Nominal Operating Pressure[Q Exempt0']

Other 11 Pressure psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Date Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp .- N/A W

i Certificate of oriosI . N/VA Expiration Date N/A Signed Team Leader Date O9nei or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoql and employed by HartfordSteam Boller Inspectionand InsuranceCo. of Connecticut!

c of HartorConnecticut have Inspected the components described In this Owner's Report during the period to , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken 04/01/08 I.

corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.1 By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning *the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions In.A 7.PS*

~nspectoas Signature .National Board, State, Province and Endorsements Date 70,0v 03~

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY '

As Required By The Provisions Of The ASME Code Section Xl Traveler# 08037

1. Owner Southern NuclearOperating Company Date 04/13108 Name 40 Inverness Center Parkway, Birmingham, AL Sheet of 1 Ad,dress
2. Plant Vogtle Electric Generarin Unit 1 Name Waynesboro, GA 30830 1080553601 Address RepairlReplacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address
4. Identification of System 1208 / Chemical and Volume Control System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add, (c) Applicable Section Xl Code Case(s) N/A
6. Identification Of Components National Corrected, ASME Code4 Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No' PIPE PULLMAN POWER N/A N/A VI-1208-449-H013 1987 INSTALLED YES SUPPORT PRODUCTS
7. Description of Work SnubberAD.41, serial#698 was replaced with a snubberAD-41, serial#673.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptFX1 Other 5 Pressure -_psi Test Temp. OF
9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A;oriza Ion No. N/IA Expiration Date N/A Signed _-i'c7\ Team Leader Date GA-i L(.-, ug Owner or Owndr's Dsignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding-e valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut of Hartord Connecticut have Inspected the components described in this Owner's Report during the period 04/01/08 to / and state that to the-best of my knowledge and belief, the Owner has performed examinations end takn corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning tile examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this

. Commissions C,v 75'n, YlnspectgiWS-gnsture National Board, State, Province and Endorsements "

Date Z6 A te.oAff26

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08038 L/

1. Owner Southern Nuclear Operating Company Date 04/16/08 Name 40 Inverness CenterParkway, Birmingham, AL Sheet of Address
2. Plant Vogtle Electric Generating Plant Unit Name Waynesboro, GA 30830 1080555201 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. NfA Plant Voqtie Expiration Date /WA Address
4. Identification of System 1301 /Main Steam System
5. (a) Applicable Construction Code ASME Sec. i/1, 1977 Edition, Winter 1977 Addenda, N-249-1 Code CasEe (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A"

6. Identification Of Components National Corrected, ASME Coae Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6)

PIPE PULLMAN POWER N/A N/A VI-1301-110-H004 1987 INSTALLED YES I SUPPORT PRODUCTS Aw

7. Description of Work Snubber AD- 151L, serial #486 was replaced with a snubberAD-.151L, serial#700.*
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating PressureD ExemptX-]

Other [] Pressure _psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A -

Certificate ofAutboritlon No. N/A Expiration Date N/A I Signed Team Leader Date

-Owneroro ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georqia and employed by HarffordSteam Boiler Inspection andInsuranceCo. of Connecticut of Hartford. Connecticut have inspected the components described in this Owner's Report during the period 04/01/08 to & and state that to the best of my knowledge and belief, the Owner has performed examinations and t~ken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionf XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning- the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with !this inspection.

_________ _-, ___,__ _________Commissions &9 7,,4

. Insp'c4rtPs Sigte National Board, State, Province and Endorsements 0 Date .PR,. aft,,,ye

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08039 9

0 1. Owner Southern Nuclear OperatingCompany Name 40 Inverness CenterParkway, Birmingham, AL Address Date Sheet 04/17/08 of

2. Plant Vogtle Electric GeneratingPlant Unit 1 Name Wavnesboro GA 30830 1080554301 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voatle Expiration Date I/A Address
4. Identification of System l3O02/Auxilinry Faadwntnr Svqtem - I 1302 lAuxiliarv FeedwaterSvstem
5. (a) Applicable Construction Code ASME Sec. 11, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cas a (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Manufacturer Board Other Year Removed, or Stamped Name of Name of Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)L PIPE PULLMAN POWER N/A N/A VI-1302-108-H019 1987 INSTALLED YES SUPPORT PRODUCTS ]
7. Description of Work Snubber AD-501, serial#369 was replaced with a snubberAD-501, serial#163.
8. Test Conducted: Hydrostatic E1 PneumaticD Nominal Operating Pressure[] Exempt[']

Other ] Pressure _ psi Test Temp. _ ___ F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A Orl

  • I 14119- N/A Expiration Date N/A

~lh Signed Team Leader Date /

wiffr obwier's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of Hartfordi Connecticut have Inspected the components described In this Owner's Report during the period 04/01/08 I to Z and state that to the best of my knowledge and belief, the Owner has performed examinations -and tlken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,* Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of'any kind arising from or connected with 'this inspection.

_ _ _ _ _ _ ._ _ _ Commissions &A. 7s-e.

lnsp-llnaor's Signature National Board, State, Province and Endorsements Date ",a

L ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler # 08040

1. Owner 0

Southern Nuclear Operating Company Date of 04117108 L i

Name 40 Inverness Center Parkway,Birmingham, AL Sheet Address

2. Plant Vogftle Electric GeneratingPlant Unit 1 Name, Waynesboro, GA 30830 1080557201 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. W/A Plant Voqtle Expiration Date N/A Address
4. Identification of System 1204 / Safety Inlection System
5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca, ie (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6)

PIPE PULLMAN POWER N/A N/A VI-1204-125-H017 1987 INSTALLED YES SUPPORT PRODUCTS

7. Description of Work SnubberPSA-35, serial#11253 was replaced with a snubberPSA-35, serial#11503.

S. - Test Conducted: Hydrostatic 11 Pneumatic[] Nominal Operating Pressure[] Exemptrx]

Other El Pressure _'psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Aut rization No. NIA Expiration Date NIA -

Signed Team Leader Date Owner or Ownr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors I

and the state or Province of Georoia and employed by. HartfordSteam Boiler Insnection and InsuranceCo. of ConnecticQt of Hartford Connecticut have Inspected the components described In this Owner's Report during the period 04/01/08 1 to 77 Q2L, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ _ _ _ _ m Commissions 6A "

Inspear's Signature National Board, State, Province and Endorsements Date RZ AP& . AAW

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler # 08041

1. Owner Southern Nuclear Operating Company Date 04/17/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogetl Electric GeneratingPlant Unit Name Waynesboro, GA 30830 1080557301 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by MaintenanceDepartment Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address -
4. Identification of System 1305 / Condensate and Feedwater System 1S05 / Cnndansataand FandwatarSvstam
5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca ie (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xl Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Manufacturer Board Other Year Removed, or Stamped Name of Component Manufacturer Serial No. No. Identification Built Installed es or N6)

PIPE PULLMAN POWER N/A N/A V1-1305-062-H006 1987 INSTALLED YES SUPPORT PRODUCTS.

7. Description of Work Snubber PSA-IO0, serial #2221 was replacedwith a snubberPSA-100, serial #2219.

0 8. Test Conducted: Hydrostatic [] Pneumatic[]

Other [] Pressure _

Nominal Operating Pressure[]

psi Test Temp. _ __ OF Exempt[E]

9. Remarks See Item 7 Applicable Manufacturer!s Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Au orization No. AL/A Expiration Date N/A Signed i Team Leader Date '2,2-i'bf WOw~neror Owher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board-of Boiler and Pressure Vessel Inspectors I and the state or Province of Georgla and employed by HartfordSteam Boiler Inspection and Insurance Co. of Connecticut of 6Afor d, LQncticut have Inspected the components described in this Owner's Report during the period 04/01/08 1 to .C/__L-.- and state that to the best of my knowledge and belief, the Owner has performed examinations and t*ken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning Ihe examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with !this Inspection.

Commissions GA Y Inspjft6r's Signature National Board, State, Province and Endorsements 0 Date *,S i* P19.Qb=

IJ

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08042

1. Owner Southern Nuclear OperatingCompany Date 06/17/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet of 1 Address
2. Plant Voqtle Electric GeneratingPlant Unit 1 Name Waynesboro, GA 30830 WO# 1071016101 and PO# 7080438 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness Center Parkwav, Suite 148, Birmingham,AL 35242 Expiration Date N/A Address
4. Identification of System 1201 / Reactor Coolant System 1528-3 &
5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section Xi Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name o0 Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed STEAM WESTINGHOUSE GAGT 1881 N/A 1-1201-B6-001 1981 INSTALLED YES GENERATOR ELECTRIC CORP.
7. Description of Work Installed mechanicaltube plugs in tube locations R57-C44, R6-Cl 10, R8-C1 12. RIO-Cl 14, R 11-Cl 18 and R13-C96.
8. Test Conducted: Hydrostatic F1 Pneumatic[- Nominal Operating Pressurer Exempt]

Other [] Pressure psi Test Temp. -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A ri tion N.) NIA _ Expiration Date W/A Signed Team Leader Date

-wnerbr wer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by HartfordSteam Boiler Inspectionand Insurance Co. of Connecticut of Hard. Connecticut have Inspected the components described in this Owner's Report during the period 04/02/08 to

  • and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

VInspectcWSIgnature

_, _ _ _ Commissions &,4 )'s1-National Board, State, Province and Endorsements Date / %7& .2.1e>se

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl 6

Traveler# 08043

1. Owner Southern NuclearODeratino Comoanv Date 06/17/08 Name 40 Inverness CenterParkway, Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtie Electric GeneratingPlant Unit I Name Waynesboro, GA 30830 WO# 1071016101 and PO4 7080438 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness CenterParkway, Suite 148, Birmingham, AL 35242 Expiration Date W/A System Address /Reactor Coolant 1201
4. Identification of System 1201 / Reactor Coolant Syýstem 1528-3 &
5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

STEAM WESTINGHOUSE GAGT 1884 N/A 1-1201-B6-004 1981 INSTALLED YES GENERATOR ELECTRIC CORP.

7. DescrIption of Work Installed mechanicaltube plugs In tube location R38-C107, *R1I-C62, *R12-C98,R22-C51. Additional mechanical tube pluqs were installedIn the following locations under Traveler-08050:R9-C62. R10-C62, R6- C59M R6-C60, R7-C59, R7-C60, R7-C61, R8-C59, R8-C60, R8-C61, R8-C62. R8-C63r R8-C64. R9-C60, R9-C61, R9-C63. R9-C64, RIO- C60, R1O-C61, RIO-C63, R1O-C64, R.1-C60, Ril-C61, R11-C63, R1l-C64. R12-C60, R12-C61, R12-C62, R12-C63. R12-C64, R13-C61, R13-C62 and R13-C63.

'Mechanicalplugs installedon cold leg side of tube only for location R11-C62andR12-C98

8. Test Conducted: Hydrostatic [] Pneumatic[-] Nominal Operating Pressure[] Exempt[g]

Other F1 Pressure _ psi Test Temp. __OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of A o on . N/A Expiration Date N/A Signed - TeamLeader oae 7/

Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by HaIrtford Steam Boiler Insoection and InsuranceCO. of Connecticut of ord- C nn icut have inspected the components described in this Owner's Report during the period 04/02/08 to ,5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

___ __ --. -___ -___, _ Commissions r "ZS-'e

, inspectofSignature National Board, State, Province and Endorsements Date 2 L7-1 L/," 2.0*V2

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08044

1. Owner -Southern Nuclear OperatingCompany Date 06/17/08 Name 40 Inverness CenterParkway,Birmingham, AL Sheet I of1 Address
2. Plant Vogtile Electric GeneratingPlant Unit Name Wavnesboro, GA 30830 WO# 1080539002 and PO# 7079313 Address RepalrlReplacement Organization P.O. No., Job No., etc,
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness Center Parkway,Suite 148, Birmingham, AL 35242 Expiration Date N/A Address
4. Identification of System 1201 / Reactor Coolant System
5. (a) Applicable Construction Code ASME Sec. lU, 1977 Edition, Winter 1977 Addenda, N-272 Code Case (b) Applicable Edition of Section Xi Used for RepaidReplacement Activity 2001 Ed. thru2003Add (c) Applicable Section XI Code Case(s) N/A
6. Identification Of Components
7. Description of Work Installed replacementreducer unions at seal table locations B08, C07, N02, A09, A 11 and D12.
8. Test Conducted: Hydrostatic [] Pneumatlc[-] Nominal Operating Pressure-' Exempt[o]

Other El Pressure psi Test Temp. -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Autpoization No. N/A Expiration Date N/A Signed Ak 2 Team Leader Date L il/II 7P OWner'§ Designee, Title

._oner'oF CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia and employed by _ Hartford Steam BSoler Inspection and Insurance Co. of Connecticut of Hartf rd Co ecti ut have inspected the components described in this Owner's Report during the period 04/03108 to "and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcte measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this ecton.

I Commissions 6.w4 7s-(,

'- Inspect-is Signature National Board, State, Province and Endorsements Date 0?'/ Z1.SLEAN dah7OiX

ORIGINAL L.

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler# 08045

1. Owner Southern Nuclear OperatingCompany Date 0&/28/08 Name 40 Inverness CenterParkway, Birmingham, AL Sheet 1 of 1 Address
2. Plant Vogtle ElectricGenerating Plant Unit I Name Wavnesboro. GA 30830 1072090901 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness Center Parkway,Suite 148, Birmingham,AL 35242 Expiration Date NWA Address
4. identification of System 1201 / Reactor Coolant System 1484-3
5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1528-3 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.

(c) Applicable Section XI Code Case~s) N/A

6. identification Of Components
7. Description of Work Welded tube plugs were installedIn hot leg tube locations RI 1-C62 and R12-C98. Acceptability of welded tube plug installationwas completedper "SG Tube Repair Data Sheet I" from procedure84015-C revision 2.1.
8. Test Conducted: Hydrostatic E Pneumatic[] Nominal Operating Pressure[] Exempt[Z]

Other [] Pressure _ psi Test Temp. _ -F

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A rltion N N/A Expiration Date N/A 4 Signed -*, Team Leader Date 7/-17 AP

-wrirbr Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geormia ' and employed by HartfordSteam Boiler Inspection and InsuranceCo. of Connecticut of Haf Conecticut have inspected the components described in this Owner's Report during the period 04/03/08 to Z/7jf,3EO 1C, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions 6-i4.

1 *Yi nspetgrs Signature National Board, State, Province and Endorsements Date 7 .. " ,

I

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler # 08046

1. Owner Southern Nuclear OperatingCompany Date 06/17/08 Name 40 Inverness CenterParkway, Birmingham,AL Sheet I of 1 Address
2. Plant Voqtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 WO# 1071016101 and PO# 7080438 Address Repair/Replacement Organization P.O. No., Job No., etc,
3. Work Performed by Westinchouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness Center Parkway, Suite 148, Birmlnaham, AL 35242 Expiration Date Address
4. Identification of System 1201 / Reactor CoolantSystem 1528-3 &
5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

STEAM WESTINGHOUSE GAGT 1882 N/A 1-1201-B6-002 1981 INSTALLED YES GENERATOR ELECTRIC CORP.

7. Description of Work Installedmechanical tube plugs In tube location R34-C104
8. Test Conducted: Hydrostatic Other []

n Pneumatic[]

Pressure _psi Nominal Operating PressureD]

Test Temp. OF Exemptr

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xh.

Type Code Symbol Stamp N/A Certificate of th tio o. N/A Expiration Date N/A

.AtC Signed Team Leader Date T?

S wO*,JxDr'Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georia and employed by HartfordSteam Boiler Insoection and Insurance Co. of Connecticut of atdonwt Qnec"ti have inspected the components described In this Owner's Report during the period 04/04/08 to ..- 7*rj.4 d , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions &Ai 7W'&

Ins ýors Signatureý National Board, State, Province and Endorsements Date /_ L*',:T*

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI (0

Traveler# 08047

1. Owner Southern NuclearOperating Company Date 06(16/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet 1 of I Address
2. Plant Vogtle Electric Generating Plant Unit Name Waynesboro, GA 30830 WO# 1071016101 and PO# 7080438 Address Repalr/Replacement Organization P;O. No., Job No., etc.
3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp N/A Name Authorization No. N/A 44 Inverness CenterParkway, Suite 148, Birmingham, AL 35242 Expiration Date NIA Address
4. Identification of System 1201 / Reactor Coolant System 1528-3 &
5. (a) Applicable Construction Code ASME Sec. IHl,1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section Xl Used for RepairlReplacement Activity 2001 Ed. thnr 2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed 2YsoLo STEAM WESTINGHOUSE GAGT 1883 N/A 1-1201-B6-003 1981 INSTALLED YES GENERATOR ELECTRIC CORP.
7. Deacriptlon of Work Installed mechanicaltube plugs in tube locationsR6-C119, R13-C107 and R42-C52.
8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Exempt[']

Other E] Pressure -psi Test Temp. OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A orifl? N/A Expiration Date N/A SSigned .Team Leader Date 4 Own~r or Owntr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georqia and employed by HartfordSteam Boiler Inspection and Insurance Co, of Connecticut of Harfo Cnnectlcut have Inspected the components described in this Owner's Report during the period 04/04.08 to 2, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

________________Commissions c.A 7 '5C Signature National Board, State, Province and Endorsements Date / .ThC 4OTr*

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required ByThe Provisions Of The ASME Code Section XI Traveler# 08054 yf

1. Owner Southern Nuclear OperatingCompany Date 06/18/108 0 Name 40 Inverness Center Parkway, Birmingham,AL Address Sheet of 1
2. Plant Vogtle ElectricGenerating Plant Unit Name Waynesboro, GA 30830 1080620801 and 1080662501 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorizatlon No. N/A Plant Voctle Expiration Date N/A Address Safety Injection /System 1204
4. Identification of System 1204 /Safety Injection System
5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for RepalrlReplacement Activity 2001 Ed. thru 2003 Add, (c) Applicable Section XI Code Case(s) N/A
6. identification Of Components National Corrected, ASME Coda Name of Name of Manufacture- Board Other Year Removed, or Stamped!

Component Manufacturer SerialiNo. No. Identification Built Installed (Yes or No)

VALVE DRAGON VALVES, RX3023 N/A 1-1204-U4-141 1984 INSTALLED YES INC. .

7. Description of Work Installed replacementbonnet yoke, union nut andstem / disc assembly. The VT-2 system leakage examination was satisfactorilycompleted under WO# 1080662501.
8. Test Conducted: Hydrostatic ] PneumatIcD] Nominal Operating PressureX] Exempt[]

Other [] Pressure psi Test Temp. _ _OF

9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A r f 0 N/A Expiration Date N/A Signed Team Leader Date

,Owner ol Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Bolier and Pressure Vessel Inspectors and the state or Province of Geonlia and employed by HartfordSteam Boiler InseCtlon and Insurance Co.of Connecticut of artfo Connecticut have Inspected the components described In this Owner's Report during the period 04112/08 to a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.

I . By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner'a Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions &Atior TInspeR sSintr National Board, State, Province and Endorsements 0 Date o?-N, atIA.")A0 .200,w

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required BylThe Provisions Of The ASME Code Section XI 9

Traveler # 08055 1; Owner Southern Nuclear OperatingCompany Date 06/18/08 Name 40 Inverness Center Parkway,Birmingham, AL Sheet 1 of 1 Address

2. Plant .Vogle Electric GeneratingPlant Unit Name Waynesboro, GA 30830 1080620601 and 1080662501 Address Repair/Replacement Organization P.O. No., Job No., etc.
3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voqtle Expiration Date N/A Address
4. Identification of System -1204 / Safety Inlection System
5. (a).Applicable Construction Code ASME Sec. I1/, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section'XI Used for'Repair/Replacement Activity 2001 Ed. thru2003 Add.

(c) Applicable Section XI Code Case(s) N/A

6. Identification Of Components -

National Corrected, ASME Cods Name of Name of Manufacturer Board Other Year Removed, or Stamped!

Component Manufacturer Serial No. No. Identification Built Installed eYes or No)

VALVE DRAGON VALVES, RX3024 N/A 1-1204-U4-140 1984 INSTALLED YES INC. I

7. Description of Work Installed replacementbonnet yoke, union nut andstem / disc assembly. The.VT-2 system leakage examination was satisfactorilycompleted under WO# 1080662501.

S. Test Conducted: Hydrostatic r1Pneumatic["] -Nominal operating 'Pressure[] Exempt[]

Other [D Pre.sure _psi Test Temp. OF

9. Remrks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report ere correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of tion

,o * /A Expiration Date WA Signed, Vwr n eraDeiIneeam LeaderT 1ý`w~ra)rie'sDesignee. TitleA CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commilssion Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by HartfordSteam Boiler Inspection andInsurance Co. of Connecticut of Hartford Conncicut have inspected the components described in this Owner's Report during the period 04/12/08 to 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectiont Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and-corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with Ithis Commissions &A- )':=~

Inspe 4Kr's Signature National Board, State, Province and Endorsements Dae9I 'A3;a67