ML071970463
ML071970463 | |
Person / Time | |
---|---|
Site: | Millstone |
Issue date: | 07/13/2007 |
From: | Gerald Bichof Dominion, Dominion Nuclear Connecticut |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
07-0440 | |
Download: ML071970463 (73) | |
Text
Dominion Nuclear Connecticut, Inc.
i O O O Donmuon Boulevard, Glen Allcn, V ~ r g ~ n2 uW G O July 13, 2007 U. S. Nuclear Regulatory Commission Serial No. 07-0440 Attention: Document Control Desk MPSNVDB Rev. 1 One White Flint North Docket Nos. 50-336 1 1555 Rockville Pike 50-423 Rockville, MD 20852-2738 License Nos. DPR-65 NPF-49 DOMINION NUCLEAR CONNECTICUT. INC.
MILLSTONE POWER STATION UNITS 2 AND 3 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY (CLIIP)
LBDCR 07-MP2-013 and 07-MP3-033 In accordance with the provisions of 10 CFR 50.90 Dominion Nuclear Connecticut, Inc.
(DNC) is submitting a request for an amendment to the Technical Specifications (TS) for Millstone Power Station Units 2 and 3 (MPS2 and MPS3).
The proposed amendment would revise the TS requirements related to control room envelope habitability. The change is consistent with the intent of NRC-approved Revision 3 to Technical Specification Task Force (TSTF) Standard Technical Specification Change Traveler, TSTF-448, "Control Room Habitability." The availability of this TS improvement was announced in the Federal Register on January 17, 2007 (72 FR 2022) as part of the consolidated line item improvement process (CLIIP). The proposed amendment would align MPS2 and MPS3 TS with NUREG 1432, Rev. 3, "Standard Technical Specifications for Combustion Engineering Plants," and NUREG 1431 , Rev. 3, "Standard Technical Specifications for Westinghouse Plants,"
respectively. Due to the MPS2 and MPS3 TS being custom TS, there are minor differences, primarily specification numbers, between the proposed wording in TSTF-448, Revision 3, and the proposed wording in this request.
Attachment 1 contains the description and justification for MPS2 and MPS3.
Attachments 2 and 3 contain the associated marked up TS pages. The associated marked up Bases changes are provided in Attachment 4 for information only and will be implemented in accordance with the Technical Specification Bases Control Program.
The proposed amendment does not involve a Significant Hazards Consideration pursuant to the provisions of 10 CFR 50.92. The Site Operations Review Committee has reviewed and concurred with the determination.
Upon approval, DNC will implement the amendment within 180 days.
Serial No. 07-0440 Docket Nos. 50-3361423 CLIIP: Control Room Habitability Page 2 of 3 In accordance with 10 CFR 50.91 (b), a copy of this license amendment request is being provided to the State of Connecticut.
Should you have any questions in regard to this submittal, please contact Mr. Thomas Shaub at (804) 273-2763.
Sincerely, w
Gerald T. Bischof Vice President - Nuclear Engineering Attachments: (4)
- 1. Evaluation of Proposed License Amendment, MPS2 and MPS3
- 2. Marked Up Pages, MPS2
- 3. Marked Up Pages, MPS3
- 4. Marked Up Bases Pages, MPS2 and MPS3, (for information only)
Commitments made in this letter: None COMMONWEALTH OF VIRGINIA 1
)
COUNTY OF HENRICO )
The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by Gerald T. Bischof, who is Vice President - Nuclear Engineering of Dominion Nuclear Connecticut, Inc. He has affirmed before me that he is duly authorized to execute and file the foregoing document in behalf of that company, and that the statements in the document are true to the best of his knowledge and belief.
Acknowledged before me this /3 ,2007.
My Commission Expires: .*jh Notary Public
Serial No. 07-0440 Docket Nos. 50-3361423 CLIIP: Control Room Habitability Page 3 of 3 cc: U.S. Nuclear Regulatory Commission Region I 475 Allendale Road King of Prussia, PA 19406-1415 Mr. J. D. Hughey NRC Project Manager, Millstone Units 2 and 3 U.S. Nuclear Regulatory Commission, Mail Stop 8B3 One White Flint North 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Millstone Power Station Director Bureau of Air Management Monitoring and Radiation Division Department of Environmental Protection 79 Elm Street Hartford, CT 06106-5127
Serial No. 07-0440 Docket Nos. 50-336150-423 ATTACHMENT 1 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY (CLIIP)
EVALUATION OF PROPOSED LICENSE AMENDMENT DOMINION NUCLEAR CONNECTICUT, INC.
MILLSTONE POWER STATION UNITS 2 AND 3
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 1 of 11 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY (CLIIP)
EVALUATION OF PROPOSED LICENSE AMENDMENT 1.0 Description The proposed amendment modifies the Millstone Power Station Units 2 and 3 (MPS2 and MPS3) Technical Specification (TS) requirements related to control room envelope (CRE) habitability. The changes are consistent with Nuclear Regulatory Commission (NRC) approved Technical Specification Task Force (TSTF) change TSTF-448, Revision 3. The availability of this TS improvement was published in the Federal Register on January 17, 2007 as part of the consolidated line item improvement process (CLIIP) .
Upon approval, DNC will implement the amendment within 180 days.
2.0 Assessment 2.1 Applicability of Published Safety Evaluation DNC has reviewed the safety evaluation dated January 17, 2007 as part of the CLIIP.
This review encompassed both the NRC staff's evaluation, as well as the supporting information provided to support TSTF-448. DNC has concluded that the justifications presented in the TSTF proposal and the safety evaluation prepared by the NRC staff are applicable to MPS2 and 3 and justify this amendment for the incorporation of the changes to the MPS2 and 3 TS.
2.2 Optional Changes and Variations DNC is not proposing any significant variations or deviations from the TS changes described in the TSTF-448, Revision 3, or the applicable parts of the NRC staff's model safety evaluation dated January 17, 2007. The parts of Section 3.0 of the model safety evaluation that are applicable for each unit are stated below. Additionally, a plant specific listing of any differences is provided below. These differences reflect adjustments, as needed, to account for plant-specific design, current licensing basis, or differences due to plant-specific non-STS wording or format.
The following proposed changes to the MPS2 TS are consistent with TSTF-448 and the evaluations from the TSTF-448, Revision 3, Model Safety Evaluation, Sections 3.2, 3.3, and 3.4.
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 2 of 11
- 1. DNC proposes to modify the applicability of TS 3.7.6.1 for consistency with TSTF-448 and Standard TS. The current phrase "irradiated fuel movement within containment or the spent fuel pool" has been changed to "movement of recently irradiated fuel assemblies." The associated TS Basis revision includes the following discussion: "ACTIONS a., b., and c. of this specification are applicable at all times during plant operation in MODES 1, 2, 3, and 4. ACTIONS d. and e. are applicable in MODES 5 and 6, or whenever recently irradiated fuel assemblies are being moved. The control room emergency ventilation system is required to be OPERABLE during fuel handling involving handling recently irradiated fuel (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay. The term "recently" is defined as all irradiated fuel assemblies, until analysis is performed to determine a specific time."
Therefore, revising the phrase indicated above, together with the revision of the TS Bases, does not change the way irradiated fuel assemblies are currently handled at MPS2. Similar modifications are proposed to other references to movement of fuel elsewhere in the TS. (Model Safety Evaluation - Section 3.2)
DNC proposes to establish new action requirements for an inoperable CRE boundary. The existing TS 3.7.6.1 Control Room Emergency Ventilation System (CREVS) actions are more restrictive than would be appropriate in situations for which CRE occupant's implementation of compensatory measures or mitigating actions would temporarily afford adequate CRE occupant protection from postulated airborne hazards. To account for such situations in Operational MODES 1, 2, 3, and 4, DNC proposes to modify TS 3.7.6.1 ACTION c. to apply when one or more Control Room Emergency Ventilation Trains are inoperable due to an inoperable CRE boundary. The revised ACTION c. would allow 90 days to restore the CRE boundary to operable status, provided the mitigating actions are immediately implemented (ACTION c.1) and within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> are verified to ensure, that in the event of a DBA, CRE occupant radiological exposures will not exceed the calculated dose of the licensing basis analyses of DBA consequences, and that CRE occupants are protected from hazardous chemicals and smoke (ACTION c.2).
(Model Safety Evaluation - Section 3.3 Evaluation 2)
- 3. To distinguish the revised TS 3.7.6.1 Action c. from the existing ACTIONS for the CREVS inoperable, DNC is proposing that TS 3.7.6.1 ACTION a, in Operational MODES 1, 2, 3, and 4, be revised to state, "With one Control Room Emergency Ventilation Train inoperable except as specified in ACTION c." (Model Safety Evaluation - Section 3.3 Evaluation 2)
- 4. DNC proposes to modify TS 3.7.6.1 ACTION e. to also apply when one or more Control Room Emergency Ventilation Trains are inoperable due to an inoperable CRE boundary. This modification to TS 3.7.6.1 ACTION e. is needed because the proposed modification to TS 3.7.6.1 ACTION c. requirements will only apply in MODES 1, 2, 3, and 4. The modification of TS 3.7.6.1 ACTION e. will ensure that
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 3 of 11 an ACTION is specified for an inoperable CRE boundary during all MODES of applicability. (Model Safety Evaluation - Section 3.3 Evaluation 4)
DNC proposes to delete TS SR 4.7.6.1.e.3 that requires verification that control room air inleakage is less than 130 SCFM with the CREVS operating in the recirculation/filtration mode. Specifically, DNC proposes to replace the existing control room air inleakage surveillance with an inleakage measurement Surveillance Requirement and CRE Habitability Program (see below), in accordance with the approved version of TSTF-448, Revision 3. (Model Safety Evaluation - Section 3.3 Evaluation 6)
In place of the control room air inleakage testing Surveillance Requirement, DNC proposes to add a new Surveillance Requirement 4.7.6.1.h that will require performance of CRE unfiltered air inleakage testing in accordance with the Control Room Envelope Habitability Program, proposed TS 6.27 (described below). The performance of unfiltered air inleakage testing past the CRE boundary into the CRE will be in accordance with the testing methods and at the frequencies specified in the CRE Habitability Program. (Model Safety Evaluation - Section 3.3 Evaluation 6)
DNC proposes a new administrative controls program TS consistent with the model program TS in TSTF-448, Revision 3. This new program is described in TS 6.27, "Control Room Envelope Habitability Program." In combination with the revised TS SR 4.7.6.1.h, this program is intended to ensure the operability of the CRE boundary, which as part of an operable CREVS will ensure that the CRE habitability is maintained such that CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program will ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under DBA conditions without personnel receiving radiation exposures in excess of 5 rem Total Effective Dose Equivalent (TEDE) for the duration of the accident. The MPS2 CRE Habitability Program contains the required elements identified in TSTF-448, Revision 3. This guidance references ASTM E741 as an acceptable method for ascertaining the unfiltered leakage into the CRE. DNC proposes to follow this method. (Model Safety Evaluation - Section 3.4)
The following proposed changes to the MPS3 TS are consistent with TSTF-448 and the evaluations supporting TSTF-448, Revision 3, Model Safety Evaluation, Sections 3.2, 3.3, and 3.4.
- 1. DNC proposes to modify the applicability of TS 3.7.7 for consistency with TSTF-448 and Standard TS. The current phrase "fuel movement within containment or the spent fuel pool" has been changed to "movement of recently irradiated fuel
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 4 of 11 assemblies." The associated TS Bases revision includes the following discussion:
"The control room emergency ventilation system is required to be OPERABLE during fuel handling involving handling recently irradiated fuel (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis),
due to radioactive decay. The term "recently" is defined as all fuel assemblies, until analysis is performed to determine a specific time." Therefore, revising the phrase indicated above, together with the revision of the TS Bases, does not change the way fuel assemblies are handled at MPS3. Similar modifications are proposed to other references to movement of fuel elsewhere in the TS. (Model Safety Evaluation
- Section 3.2)
- 2. DNC proposes to establish new action requirements for an inoperable CRE boundary. The existing TS 3.7.7 Control Room Emergency Ventilation System (CREVS) actions are more restrictive than would be appropriate in situations for which CRE occupant implementation of compensatory measures or mitigating actions would temporarily afford adequate CRE occupant protection from postulated airborne hazards. To account for such situations in MODES 1, 2, 3, and 4, DNC proposes to modify TS 3.7.7 ACTION c, to apply when one or more Control Room Emergency Air Filtration Systems are inoperable due to an inoperable CRE boundary. The revised ACTION c would allow 90 days to restore the CRE boundary to operable status, provided the mitigating actions are immediately implemented (ACTION c.1) and within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> are verified to ensure, that in the event of a Design Bases Accident (DBA), CRE occupant radiological exposures will not exceed the calculated dose of the licensing basis analyses of DBA consequences, and that CRE occupants are protected from hazardous chemicals and smoke (ACTION c.2).
(Model Safety Evaluation - Section 3.3 Evaluation 2)
- 3. To distinguish the revised TS 3.7.7 ACTION c from the existing ACTIONS for a Control Room Emergency Air Filtration System inoperable, DNC is proposing that TS 3.7.7 ACTION a, in MODES 1, 2, 3, and 4, be revised to state, "With one Control Room Emergency Air Filtration System inoperable, except as specified in ACTION c." (Model Safety Evaluation - Section 3.3 Evaluation 2)
- 4. DNC proposes to modify TS 3.7.7 ACTION e. to also apply when one or more Control Room Emergency Air Filtration Systems are inoperable due to an inoperable CRE boundary. This modification to TS 3.7.7 ACTION e is needed because the proposed modification to TS 3.7.7 ACTION c requirements will only apply in MODES 1, 2, 3, and 4. The modification of TS 3.7.7 ACTION e will ensure that an ACTION is specified for an inoperable CRE boundary during all MODES of applicability. (Model Safety Evaluation - Section 3.3 Evaluation 4)
- 5. DNC proposes to delete the MPS3 CRE pressurization Surveillance Requirement (SR) 4.7.7.e.2 that requires verification that the system can maintain a positive pressure of at least 118 inches water gauge relative to the adjacent areas during the filtered pressurization mode of operation at a pressurization flow rate of I 230 cfm.
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 5 of 11 The deletion of this SR is proposed because measurements of unfiltered air inleakage into the CRE at numerous reactor facilities has demonstrated that a basic assumption of this SR, an essentially leak-tight CRE boundary, was incorrect for most facilities. Therefore, meeting this SR by achieving the required CRE pressure is not necessarily a conclusive indication of CRE boundary leak tightness (i.e., CRE boundary operability). DNC proposes to replace the existing TS control room pressurization surveillance, TS SR 4.7.7.e.2, with an inleakage measurement SR and CRE Habitability Program in TS (described below), in accordance with the approved version of TSTF-448, Revision 3. (Model Safety Evaluation - Section 3.3 Evaluation 6)
- 6. In place of the pressurization SR, DNC proposes to add a new SR 4.7.7.h that will require performance of CRE unfiltered air inleakage testing in accordance with the Control Room Envelope Habitability Program, proposed TS 6.8.4.h (described below). The performance of unfiltered air inleakage testing past the CRE boundary into the CRE will be in accordance with the testing methods and at the frequencies specified in the CRE Habitability Program. (Model Safety Evaluation - Section 3.3 Evaluation 6)
DNC proposes a new administrative controls program TS consistent with the model program TS in TSTF-448, Revision 3. This new program is described in TS 6.8.4.h, "Control Room Envelope Habitability Program." In combination with the revised TS SR 4.7.7.h, this program is intended to ensure the operability of the CRE boundary, which as part of an operable CREVS will ensure that the CRE habitability is maintained such that CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program will ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under DBA conditions without personnel receiving radiation exposures in excess of 5 rem TEDE for the duration of the accident. The MPS3 CRE Habitability Program contains the required elements identified in TSTF-448, Revision 3. (Model Safety Evaluation - Section 3.4)
For the Control Room Envelope Habitability Program description of the measurement frequency for CRE pressure relative to external areas adjacent to the CRE boundary during the pressurization mode of operation given in new TS 6.8.4.h, the stated frequency will be "48 months on a STAGGERED TEST BASIS" versus the TSTF value of [18] months. This variance is due to the difference between the MPS3 TS definition of STAGGERED TEST BASIS and the definition used by Standard Technical Specifications (STS), as well as the existing MPS3 24-month surveillance interval. The MPS3 definition of STAGGERED TEST BASIS is:
"A STAGGERED TEST BASIS shall consist of a test schedule for (n) systems, subsystems, trains, or other designated components obtained by dividing the specified test interval into (n) equal subintervals. The testing of one system,
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 6 of 11 subsystem, train, or other designated component at the beginning of each subinterval."
The STS definition is:
"A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function."
Therefore, in order to prescribe testing one of the subsystems every 24 months as stated in TSTF-448, the frequency must be stated as "48 months on a STAGGERED TEST BASIS," for MPS3.
Plant Specific Discussion A listing of MPS2 minor differences relative to Section 2.0 of the model safety evaluation is provided below. These differences reflect adjustments, as needed, to account for plant-specific design, current licensing basis, or differences due to plant-specific non-STS wording or format.
- 1. The MPS2 CREVS does not have heaters or demisters. Accordingly, the reference to heaters and demisters in model safety evaluation - Section 2.2 is not applicable to MPS 2.
- 2. Unfiltered air inleakage testing is conducted at MPS2 per ASTM E741-83, rather that ASTM E741-00, as referenced in Model Safety Evaluation - Section 2.3. This version of the standard reflects the current procedure and licensing basis for conducting unfiltered air inleakage testing at MPS2 and is acceptable based on the experience gained through the performance of tracer gas testing of the MPS2 control room using this standard for many years.
MPS2 and MPS3 To account for MPS2 and MPS3 specific control room habitability design, current licensing basis, or differences due to plant specific non-Standard Technical Specification wording or format, the following adjustments have been incorporated into the proposed TS markups:
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 7 of 11
- 1. MPS2 and 3 have not adopted the Standardized Technical Specification Format.
TSTF-448 has been incorporated into existing sections with new sections being added as applicable.
- 2. TSTF-448, Rev. 3, TS 3.7.10 (NUREG 1432 STS) and TS 3.7.11 (NUREG 1431 STS), Required Action 'B.2' in reference to ensuring exposure to smoke hazards will not exceed limits, was reworded in proposed MPS2 and 3 TS ACTION c.2 to state "mitigating actions are taken for exposure to smoke hazards" as the limit is qualitative not quantitative.
TS Bases With the exceptions identified above, TS Bases changes have been prepared to reflect applicable Bases statements from TSTF-448, Revision 3. These changes will be processed in accordance with the requirements of TS 6.23 (MPS2) and TS 6.18 (MPS3), "Technical Specifications (TS) Bases Control Program," which provides assurance that DNC has established and will maintain the adequacy of the Bases.
Exceptions TSTF-448 allows exceptions to the testing methods and frequencies described in Regulatory Guide 1.197, Regulatory Positions C.l and C.2. DNC proposes the following exceptions:
- 1. Appropriate application of ASTM E741 shall include the ability to take minor exceptions to the test methodology. These exceptions shall be documented in the test report.
This exception is necessary because the required testing methodology, ASTM E741, was not originally intended for nuclear power plant control room envelope testing.
Some minor exceptions from the standard are necessary and are usually determined by the test vendor. NEI 99-03, Revision 1, Appendix EE discusses exceptions typically taken by ASTM E741 test vendors. While not an all-inclusive list, the exceptions listed in Appendix EE provide examples of the type of exceptions that will be allowed by the proposed Control Room Envelope Habitability Program. Any exceptions to the test methodology will be documented in the individual test report to ensure that the testing performed is in accordance with the Control Room Envelope Habitability Program requirements of proposed Technical Specifications 6.27 (MPS2) and TS 6.8.4.h (MPS3).
- 2. Vulnerability assessments for radiological, hazardous chemical and smoke, and emergency ventilation system testing were completed as documented in the UFSAR and other licensing basis documents. The exceptions to the Regulatory Guides (RG) referenced in RG 1.I96 (i.e., RG 1.52, RG 1.78, and RG 1.183), which were
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 8 of 11 considered in completing the vulnerability assessments, are documented in the UFSARIcurrent licensing basis. Compliance with these RGs is consistent with the current licensing basis as described in the UFSAR and other licensing basis documents.
This general exception does not affect the periodic testing and evaluation of the CRE boundary. Periodic testing and evaluation of the CRE boundary will be performed consistent with the regulatory positions described in Sections C . l and C.2 of RG 1.197. This exception identifies how the MPS2 and 3 control room habitability licensing bases were developed, which are consistent with the intent of RG 1.I96 and the regulatory guides referenced therein, but are not in verbatim compliance with the regulatory positions established in each RG. The MPS2 and 3 commitment to the following regulatory guides is described in following licensing basis documents:
RG 1.52, Rev. 2, 1978-TS 4.6.5.1 RG 1.78, Rev. 0, 1974 - Technical Evaluation MG-EV-04-001, Rev. 0 RG 1.95, Rev. 1, 1977 - Technical Evaluation MG-EV-04-001, Rev. 0 RG 1.183, July 2000 - UFSAR Section 14 RG 1.52, Rev. 2, 1978 - UFSAR 1.8 and 6.5.1.2 RG 1.78, Rev. 0, 1974 - UFSAR 1.8 and 6.4.4.2 RG 1.95, Rev. 1, 1977 - UFSAR 1.8 and 6.4.4.2 RG 1.183, July 2000 - UFSAR 1.8 and 15 2.3 License Condition Regarding Initial Performance of New Surveillance and Assessment Requirements DNC proposes the following as a license condition to support implementation of the proposed TS changes. These license conditions are in accordance with TSTF-448, Revision 3, with no deviations.
Upon implementation of Amendment No. xxx adopting TSTF-448, Revision 3, the determination of control room envelope (CRE) unfiltered air inleakage as required by SR 4.7.6.1 .h, in accordance with TS 6.27.c.(i), the assessment of CRE habitability as required by TS 6.27.c.(ii), and the measurement of CRE pressure as required by TS 6.27.d, shall be considered met. Following implementation:
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 9 of 11 (a) The first performance of SR 4.7.6.1 .h, in accordance with TS 6.27.c.(i), shall be within the specified Frequency of 6 years, plus the 18-month allowance of SR 4.0.2, as measured from November 2, 2006, the date of the most recent successful tracer gas test, or within the next 18 months if the time period since the most recent successful tracer gas test is greater than 6 years.
(b) The first performance of the periodic assessment of CRE habitability, TS 6.27.c.(ii),
shall be within 3 years, plus the 9-month allowance of SR 4.0.2, as measured from November 2, 2006, the date of the most recent successful tracer gas test, or within the next 9 months if the time period since the most recent successful tracer gas test is greater than 3 years.
(c) Not applicable due to neutral pressure CRE.
Upon implementation of Amendment No. xxx adopting TSTF-448, Revision 3, the determination of control room envelope (CRE) unfiltered air inleakage as required by SR 4.7.7.h, in accordance with TS 6.8.4.h.c.(i), the assessment of CRE habitability as required by TS 6.8.4.h.c.(ii), and the measurement of CRE pressure as required by TS 6.8.4.h.d, shall be considered met. Following implementation:
(a) The first performance of SR 4.7.7.h, in accordance with TS 6.8.4.h.c.(i), shall be within the specified Frequency of 6 years, plus the 18-month allowance of SR 4.0.2, as measured from June 16, 2004, the date of the most recent successful tracer gas test, as identified in the report referenced in the August 31, 2004 letter response to Generic Letter 2003-01 , or within the next 18 months if the time period since the most recent successful tracer gas test is greater than 6 years.
(b) The first performance of the periodic assessment of CRE habitability, TS 6.8.4.h.c.(ii), shall be within 3 years, plus the 9-month allowance of SR 4.0.2, as measured from June 16, 2004, the date of the most recent successful tracer gas test, as identified in the report referenced in the August 31, 2004 letter response to Generic Letter 2003-01, or within the next 9 months if the time period since the most recent successful tracer gas test is greater than 3 years.
(c) The first performance of the periodic measurement of CRE pressure, TS 6.8.4.h.d, shall be within 24 months, plus the 180 days allowed by SR 4.0.2, as measured from March 23, 2007, the date of the most recent successful pressure measurement test, or within 180 days if not performed previously.
3.0 Requlatorv Analysis 3.1 No Significant Hazards Consideration
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 10 of 11 DNC has reviewed the proposed no significant hazards consideration determination (NSHCD) published in the Federal Register as part of the CLIIP. DNC has concluded that the proposed NSHCD presented in the Federal Register notice is applicable to MPS2 and MPS3 and is hereby incorporated by reference to satisfy the requirements of 10 CFR 50.91(a).
4.0 Environmental Consideration DNC has reviewed the environmental evaluation included in the model safety evaluation dated January 17, 2007 as part of the CLIIP. DNC has concluded that the staff's findings presented in that evaluation are applicable to MPS2 and MPS3 and the evaluation is hereby incorporated by reference for this application.
5.0 References
- 1. NRC Generic Letter 2003-01, "Control Room Habitability," dated June 12, 2003.
- 2. Letter from Anthony R. Pietrangelo, NEI, to Dr. William Beckner, NRC, dated December 30, 2002, "Forwarding of TSTF."
3 . Letter from Dr. William Beckner, NRC, to Anthony R. Pietrangelo, NEI, dated July 1, 2003.
- 4. Letter from the Technical Specifications Task Force to Dr. William Beckner, NRC, dated August 19, 2003, "TSTF-448, Revision 1," (TSTF-03-03).
- 5. Letter from Thomas Boyce, NRC, to the Technical Specifications Task Force dated December 16, 2003.
- 6. Letter from the Technical Specifications Task Force to Dr. William Beckner, NRC, dated March 8, 2004, "Response to NRC Request for Additional Information Regarding TSTF-448, Revision 1, 'Control Room Habitability'," (TSTF-04-02).
- 7. Regulatory Guide 1.196, "Control Room Habitability at Light-Water Nuclear Power Reactors," dated May 2003.
- 8. Letter from Patrick Hiland, NRC, to the Technical Specifications Task Force, dated January 24, 2005.
- 9. Letter from C. Craig Harbuck, NRC, to Alex Marion, NEI, dated June 23, 2005, "Summary of Meeting Held May 26, 2005 Between NRC Staff and Industry on TSTF-448, Control Room Habitability, Revision 1."
Serial No. 07-0440 Docket Nos. 50-336150-423 CLIIP: Control Room Habitability Attachment 1 Page 11 of 11
- 10. Letter from Technical Specifications Task Force to U.S. NRC, "TSTF-448, Revision 2, 'Control Room Habitability'," dated August 18, 2005.
- 11. Letter from Thomas H. Boyce (NRC) to Technical Specifications Task Force dated December 28,2005.
- 12. Letter from Thomas H. Boyce (NRC) to Technical Specifications Task Force dated March 10, 2006.
- 13. Letter from Timothy J. Kobetz (NRC) to Technical Specifications Task Force dated May 12, 2006.
- 14. NEI 99-03, Revision 0, "Control Room Habitability Assessment Guidance," dated June 2001.
- 15. Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003.
Serial No. 07-0440 Docket No. 50-336 ATTACHMENT 2 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY (CLIIP)
MARKED UP MPS2 TECHNICAL SPECIFICATION PAGES DOMINION NUCLEAR CONNECTICUT, INC.
MILLSTONE POWER STATION UNIT 2
DNC shall take all necessary steps to ensure that the decommissioning trust is maintained in accordance with the application for approval of the transfer of the MPS Unit No. 2 license and the requirements of the Order approving the transfer, and consistent with the safety evaluation supporting the Order.
The Final Safety Analysis Report (FSAR) supplement, as revised, submitted pursuant to 10 CFR 54.21(d), shall be included in the next scheduled update to the FSAR required by 10 CFR 50.71(e)(4) following the issuance of this renewed operating license. Until that update is complete, DNC may make changes to the programs and activities described in the supplement without prior Commission approval, provided that DNC evaluates such changes pursuant to the criteria set forth in 10 CFR 50.59 and otherwise complies with the requirements in that section.
The FSAR supplement, as revised, describes certain future activities to be completed prior to the period of extended operation. DNC shall complete these activities no later than July 31, 2015, and shall notify the NRC in writing when implementation of these activities is complete and can be verified by NRC inspection.
All capsules in the reacitor vessel that are removed and tested must meet the test procedures and reporting requirements of American Society for Testing and Materials (ASTM) E 185-82 to the extent practicable for the configuration of the specimens in the capsule. Any changes to the capsule withdrawal schedule, including spare capsules, must be approved by the NRC prior to implementation. All capsules placed in storage must be maintained for future insertion. Any changes to storage C1 Insert A D.
requirements must be approved by the NRC, as required by 10 CFR Part 50, Appendix H.
This renewed operating license is effective as of its date of issuance and shall expire at midnight July 31, 2035.
FOR THE NUCLEAR REGULATORY COMMISSION J. E. Dyer, Director Office of Nuclear Reactor Regulation
Attachment:
- 1. Appendix A - Technical Specifications Date of Issuance: November 28,2005 Renewed License No. DPR-65
Millstone Power Station Unit 2 Operating License Page 6 Insert A (13) Upon implementation of Amendment No. xxx adopting TSTF-448, Revision 3, the determination of control room envelope (CRE) unfiltered air inleakage as required by SR 4.7.6.1 .h, in accordance with TS 6.27.c.(i),
the assessment of CRE habitability as required by TS 6.27.c.(ii), and the measurement of CRE pressure as required by TS 6.27.d, shall be considered met. Following implementation:
(a) The first performance of SR 4.7.6.1.h, in accordance with TS 6.27.c.(i), shall be within the specified Frequency of 6 years, plus the 18-month allowance of SR 4.0.2, as measured from November 2, 2006, the date of the most recent successful tracer gas test, or within the next A8 months if the time period since the most recent successful tracer gas test is greater than 6 years.
(b) The first performance of the periodic assessment of CRE habitability, TS 6.27.c.(ii), shall be within 3 years, plus the 9-month allowance of SR 4.0.2, as measured from November 2, 2006, the date of the most recent successful tracer gas test, or within the next 9 months if the time period since the most recent successful tracer gas test is greater than 3 years.
(c) Not applicable due to neutral pressure CRE.
INDEX ADMINISTRATIVE CONTROLS SECTION PAGE a
6.22 REACTOR COOLANT PUMP FLYWHEEL INSPECTION PROGRAM .................... 6-28 6.23 TECHNICAL SPECIFICATION (TS)BASES CONTROL PROGRAM ....................... 6-28 6.24 DIESEL FUEL OIL TEST PROGRAM .............................. ,.,......................................... 6-29 6.25 PE-STRESSED CONCRETE CONTAINMENT TENDON SUWEILLANCE PROGRAM ....................:...,............................. .. .. . .. ......... .. 8 - 2 9 6.26 STEAM GENERATOR PROGRAM...i............................ ............... . ................6-30 1
'6 MILLSTONE - UNIT 2 Amendment No.278, #
PLANT SYSTEMS 3/4.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.6.1 Two independent Control Room Emergency Ventilation Trains shall be OPERABLE."
S 1,2,3,4,5 and 6.
diated fue ACTION:
MODES 1,2,3, and 4: except as specified in ACTION c.,
- a. 4 With one Control Room Emergency Ventilation Train inoperable, estore the inoperable train to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- b. With both Control Room Emergency Ventilation Trains inoperable, except as specified in mmediatelv sumend the movement of urad~atedfuel assemblies within th&
store at least one inoperable train to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, and COLD SHUTDOWN within the COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- The Control ~ o o ~ b o u n dmay a r ~be opened intermittently under administrative control.
I MILLSTONE - UNIT 2 3/4 7-16 Amendment No. ?2,M , %,
4-49, t 238,245, =y?lp'
Millstone Power Station Unit 2 Technical Specification 3.7.6 Control Room Emergency Ventilation System Page 314 7-16 Insert B CRE boundary perform the following:
I Immediately initiate action to implement mitigating actions, and
- 2. Verify, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, mitigating actions ensure CRE occupant exposures to radiological and chemical hazards will not exceed limits, and mitigating actions are taken for exposure to smoke hazards, and
Otherwise,
PLANT SYSTEMS 314.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION
- d. With one Control Room Emergency Ventil le train to OPERABLE status within 7 days. After 7 days, either initiate and maintain operation of the remaining OPERABLE Control Room Emergency Ventilation Train in the recirculation mode of operation, or immediately suspend the movement ofkadiated k e l assemblies.
- e. -=!i?oom Emergency With both Control - - Ventilation Trains inoperable, or with the OPERABLE Control Room Emergency Ventilation Train required to be in the recirculation mode by ACTION d. not capable of being powered by an OPERABLE normal and emergency power some, ediately suspen-8ws;.and the movement of irradiated fuelassem%
I one or more Control Room Emergency Ventilatio Trains inoperable due to an inoperable CRE boundary,
- h MODES 5 and 6, when a Control Room Emergency Ventilation Train is determined to be inoperable solely because its emergency power source is inoperable, or solely because its normal power source is inoperable, it may be considered OPERABLE for the purpose of satisEying the requirements of 3.7.6.1 Limiting Condition for Operation, provided: (1) its corresponding normal or emergency power source is OPERABLE;and (2) all of its redundant system (s), subsystem (s), train (s), component (s) and device(s) are OPERABLE, or likewise satisfl the requirements of the specification. Unless both conditions (1) and (2) are satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, then ACTION 3.7.6.1.d or 3.7.6.1.e shall be invoked as applicable.
314 7- 16a Amendment No. &l5,248,WI 284,##
PLANT SYSTEMS SURVmL.LANCEREQUIREMENTS (Continued)
Verifying that control room air in-leakage is less than 200 SCFM with Control Room Emergency Ventilation System operating in the recirculation/fdtrtttionmode.
- f. After each complete or partial replacement of a mPA filter bank by verifying that the I%PA filter banks remove greater than or equal to 99%of the DOP when they are tested in-place in accordance with ANSI N5 10-1975 while operating the train at a flow rate of Z O O cfin 10%.
- g. After each complete or partial replacement of a charcoal adsorber bank by verifying that the charcoal adsorbers remove greater than or equal to 99%of a halogenated hydrocarbonrefrigeranttest gas when they are tested in-pIace in '
accordance with ANSI N510-1975while operating the train at a flow rate of Z O O c f h z t 10%.
- h. By performance of CRE unfiltered air iuleakage testing in accordance with the CRE Habitability Program at a frequency in accordance with the CRE Habitability Program.
Amendment No. 72,MQ,W, 228, #$
ELECTRTCAL POWER SYSTEMS A.C. DISTIUBUTION SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.2.2 As a minimum, the following A.C. electrical busses shall be OPERABLE and energized fiom sources of power other than a diesel generator but aligned to an OPERABLE diesel generator:
1 - 4160 volt Emergency Bus 1 - 480 volt Emergency Load Center 2 - 120 volt A.C. Vital Busses APPLICABILITY MODES 5 and 6.
ACTION:
With less than the above complement of A.C. busses OPERABLE and energized, suspend all operations involving CORE ALTERATIONS and positive reactivity additions that could result in loss of required SDM or boron concentration, and fuel assemblies.
SURVEILLANCE REQUrnMENTS 4.8.2.2 The specified A.C. busses shall be determined OPERABLE and energized fiom normal A.C. sources at least once per 7 days by verifying correct breaker alignment and indicated power availability.
MILLSTONE UNIT 2 Amendment No. -I%,#$
ELECTRICAL POWER SYSTEMS D.C. DISTRIBUTION - SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.2.4 One 125 - volt D.C.bus train electrical power subsystem shall be OPERABLE:
APPLICABILITY: MODES 5 and 6.
ACTION:
With no 125-volt D.C.bus trains OPERABLE, suspend all operations involving CORE ALTERATIONS and positive reactivity additions that could result in loss of required SDM or boron concentration, and fuel assemblies.
SURVEILLANCE REQUIREMENTS 4.8.2.4.1 The above required 125-volt D.C. bus train shall be determined OPERABLE at least .
once per 7 days by verifymg correct breaker alignment and indicated power availability.
4.8.2.4.2 The above required 125-volt D.C. bus train battery bank and charger shall be demonstrated OPERABLE per SurveiIlance Requirement 4.8.2.3.2.
- t. -
MILLSTONE UNIT 2 314 8-10 Amendment No. W,.M, 2?9,,#$~
ADMINISTRATIVE CONTROLS 6.26 STEAM GENERATOR lSG) PROGRAM (Continued)
- c. Provisions for SG tube repair criteria: Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
- d. Provisions for SG tube inspections: Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weId at the tube outlet, and that may satis9 the applicable tube repair criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.l., d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SO tube integrity is maintained until the next SG inspection. An assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what Iocations.
- 2. Inspect 100% of the tubes at sequential periods of 144, 108,72, and, thereafter, 60 effective full power months. The first sequential period shall be considered to begin after the first inservice inspection of the SGs. En addition, inspect 50% of the tubes by the refueling outage nearest the midpoint of the period and the remaining 50% by the refueling outage nearest the end of the period. No SG shall operate for more than 72 effective fidl power months or three refbeling outages (whichever is less) without being inspected.
- 3. If crack indications are found in any SG tube, then the next inspection for each SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever is less). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
- e. Provisions for monitoring operational primary to secondaty LEAKAGE.
MILLSTONE UNIT 2 Amendment No.
Pb
Millstone Power Station Unit 2 Technical Specification Section 6 Administrative Controls Page 6-31 Insert C 6.27 Control Room Envelope Habitability Proqram A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of 5 rem total effective dose equivalent (TEDE) for the duration of the accident. The program shall include the following elements:
- b. Requirements for maintaining the CRE boundary in its design condition including configuration control and preventive maintenance.
- c. Requirements for (i) determining the unfiltered air inleakage past the CRE boundary into the CRE in accordance with the testing methods and at the Frequencies specified in Sections C. Iand C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.l and C.2 of Regulatory Guide 1.197, Revision 0.
The following are exceptions to Sections C.l and C.2 of Regulatory Guide 1.197, Revision 0:
- 1. Appropriate application of ASTM E741 shall include the ability to take minor exceptions to the test methodology. These exceptions shall be documented in the test report, and
- 2. Vulnerability assessments for radiological, hazardous chemical and smoke, and emergency ventilation system testing were completed as documented in the UFSAR and other licensing
basis documents. The exceptions to the Regulatory Guides (RG) referenced in RG A.d96 (i.e., RG 1.52, RG 1.78, and RG 1.783),which were considered in completing the vulnerability assessments, are documented in the UFSARfcurrent licensing basis. Compliance with these RGs is consistent with the current licensing basis as described in the UFSAR and other licensing basis documents.
- d. Not applicable due to neutral pressure CRE.
- e. The quantitative limits on unfiltered air inleakage into the CRE. These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c.
The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences. Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.
- f. The provisions of Surveillance Requirement 4.0.2 are applicable to the frequencies for assessing CRE habitability and determining CRE unfiltered inleakage as required by paragraph c.
Serial No. 07-0440 Docket No. 50-423 ATTACHMENT 3 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY MARKED UP NIPS3 TECHNICAL SPECIFICATION PAGES DOMINION NUCLEAR CONNECTICUT, INC.
MILLSTONE POWER STATION UNIT 3
(e) The appropriate section of the decommissioning trust agreement shall state that the trustee, investment advisor, or anyone else directing the investments made in the trusts shall adhere to a "prudent investor" standard, as specified in 18 CFR 35,32(a)(3) of the Federal Energy Regulatory Commission's regulations.
DNC shall take all necessary steps to ensure that the decommissioning trust is maintained in accordance with the application for approvat of the transfer of the MPS Unit No. 3 license and the requirements of the Order approving the transfer, and consistent with the safety evaluation supporting the Order.
The Final Safety Analysis Report (FSAR) supplement, as revised, submitted pursuant to 10 CFR 54.21(d), shall be included in the next scheduled update to the FSAR required by 10 CFR 50.71(e)(4) following the issuance of this renewed operating license. Until that update is complete, DNC may make changes to the programs and activities described in the supplement without prior Commission approval, provided that DNC evaluates such changes pursuant to the criteria set forth in 10 CFR 50.59 and otherwise complies with the requirements in that section.
The FSAR supplement, as revised, describes certain future activities to be completed prior to the period of extended operation. DNC shall complete these activities no later than November 25, 2025, and shall notify the NRC in writing when implementation of these activities is complete and can be verified by NRC inspection.
All capsules in the reactor vessel that are removed and tested must meet the test procedures and reporting requirements of American Society for Testing and Materials (ASTM) E 185-82 to the extent practicable for the
=
configuration of the specimens in the capsule. Any changes to the capsule withdrawal schedule, including spare capsules, must be approved by the NRC prior to implementation. All capsules placed in storage must be maintained for future insertion. Any changes to storage requirements must Insert D be approved by the NRC, as required by 10 CFR Part 50, Appendix H.
D. Exemptions from certain requirements of Appendix J to 10 CFR Part 50 (Section 6.2.6, SSER 4) and from a portion of the requirements of General Design Criterion 4 (Section 3.9.3.1, SSER 4) of Appendix A to 10 CFR Part 50 have previously been granted. See Safety Evaluation Report Supplement 4, November 1985. With these exemptions the facility will operate, to the extent authorized herein, in conformity with the application, as amended, the provisions of the Act, and the rules and regulations of the Commission.
E. The licensee shall fully implement and maintain in effect all provisions of the Commission-approved physical security, training, and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements Renewed License No. NPF-49
Millstone Power Station Unit 3 Operating License Page 5 Insert D (10) Upon implementation of Amendment No. xxx adopting TSTF-448, Revision 3, the determination of control room envelope (CRE) unfiltered air inleakage as required by SR 4.7.7.h, in accordance with TS 6.8.4.h.c.(i), the assessment of CRE habitability as required by TS 6.8.4. h.c.(ii), and the measurement of CRE pressure as required by TS 6.8.4.h.d, shall be considered met. Following implementation:
(a) The first performance of SR 4.7.7.h, in accordance with TS 6.8.4.h.c.(i), shall be within the specified Frequency of 6 years, plus the 18-month allowance of SR 4.0.2, as measured from June 16, 2004, the date of the most recent successful tracer gas test, as identified in the report referenced in the August 31, 2004 letter response to Generic Letter 2003-01, or within the next 18 months if the time period since the most recent successful tracer gas test is greater than 6 years.
(b) The first performance of the periodic assessment of CRE habitability, TS 6.8.4.h.c.(ii), shall be within 3 years, plus the 9-month allowance of SR 4.0.2, as measured from June 16, 2004, the date of the most recent successful tracer gas test, as identified in the report referenced in the August 31, 2004 letter response to Generic Letter 2003-01, or within the next 9 months if the time period since the most recent successful tracer gas test is greater than 3 years.
(c) The first performance of the periodic measurement of CRE pressure, TS 6.8.4.h.d, shall be within 24 months, plus the 180 days allowed by SR 4.0.2, as measured from March 23, 2007, the date of the most recent successful pressure measurement test, or within 180 days if not performed previously.
@ a m ' '
TABLE 3.3-3 (Continued1 TABLE NOTATIONS I
- The Steamline Isolation Logic and Safety Injection Logic for this trip function may be blocked in this MODE below the P-1 1 (Pressurizer Pressure Interlock) Setpoint.
- MODES 1,2,3,4,5 and 6 .
cked below P- 1I when Safety Injection on low steam fine pressure is not blocked.
ACTION STATEMENTS ACTION 14 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; however, one channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing per Specification 4.3.2.1, provided the other channel is OPERABLE.
F ACTION 15 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; however, one channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing per Specification 4.3.2.1, provided the other channel is OPERABLE.
d'.
ACTION 16 - With the number of OPERABLE channels one less than the Total Number of Channels, operation may proceed until performance of the next required ANALOG CKANNEL OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within I hour.
ACTION 17 - With the number of OPERABLE channels one less than the Total Number of Channels, operation may proceed provided the inoperable channel is placed in the bypassed condition and the Minimum Channels OPERABLE requirement is met. One additional channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for suveilIance testing per Specification ACTION 18 - With the number of OPERABLE Channels, restore the inoperable After 7 days, or if no channels mewme&, if applicable, and and in COLD SWTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
ACTION 19 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
I MILLSTONE - UNIT 3 3/4 3-24 Amendment No. 57,742,89,429, ?03,
=@
TABLE 4.3-2 Kontinuedl TABLE NOTATION I. Each train shall be tested at teast every 62 days on a STAGGERED TEST BASIS.
- 2. This surveillance may be performed continuously by the emergency generator load sequencer auto test system as long as the EGLS auto test system is demonstrated OPERABLE by the performance of an ACTUATMlN LOGIC TEST at least once per 92 days.
6
- 3. On a monthly basis, a loss of voltage condition will be initiated at each undervoltage monitoring relay to verify individual relay operation. Setpoint verification and actuation of the associated logic and alarm relays will be performed as part of the CHANNEL CALIBXWTION required once per 18 months.
- 4. For Engineered Safety Features Actuation System fhctional units with only Potter &
Brulnfield MDR series relays used in a clean, environmentally confrolled cabinet, as discussed in Westinghouse Owners Group Report WCAP- 13900, the surveiIlance interval for slave relay testing is R.
- MODES 1,2,3,4,5 and 6 .
MILLSTONE - UNIT 3 3/4 3-41 Amendment No. 45, ?4, ?-9,.1-88, -129, w,a, =,pp -- -
TABLE 3.3-6 Kontinuedj TABLE NOTATIONS 8
With fuel in the he1 storage pool areas.
ACTION STATEMENTS ACTION 28 - With less than the Minimum Channels may continue for up to 30 days provided an appropriate portable continuous monitor with the same Alarm Setpoint is provided in the fuel storage pool area.
Restore the inoperable monitors to OPERABLE status within 30 days or suspend
" k 3 ACTION 29 - With the number of OPERABLE ChanneIs less than the Minimum Channels OPERABLE requirement, comply with the ACTION requirements of Specification 3.4.6.1.
MILLSTONE - UNIT 3 Amendment No. 48,-IB@%f
PLANT SYSTEMS 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.7 Two independent Control Room Emergency Air Filtration Systems shall be OPERABLE.#
APPLICABILI'IY MODES 1,2,3,4,5 and 4.
ACTION:
MODES l , 2 , 3 and 4: xcept as specified in ACTION c.,I )
- a. I, With one Control Room Emergency Air Filtration System inoperable, estore the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- b. With both Control Room Emergency Air Filtration Systems inoperable, except as soecified in ACTION c..&ediatelv susoend the movement of he1 within t h e 9 hL w
G e n t fuel pool.esrore% least one ;nop&ble syskn to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
gllPIIIIIIIC2
@===+4
- c. Wtthbe& - - Control Room Emergency Air FiItration Systems inoperable due to an 9 inoperable&ontrol Roomboundary, immediately suspend the movement of fuel within the spent fuel pool and restore the Control Room boundary to OPERABL s within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> ofie in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and
- d. With one Control Room Emergency Air Filtration System inoperable, restore the inoperable system to OPERABLE status within 7 days. After 7 days, either initiate and maintain operation of the remaining OPERABLE Control Room Emergency Air Filtration System in the on, or immediately s'
- e. Emergency Air Filtration Systems inoperable, or with the OPERABLE Control Room ~GergencyAir ~iltrationSystem r d r e d to be in the mckad&a mode by ACTION d. not capable of being powered by an OPERABLE emergency pow be opened intermittently under administrative control.
MILLSTONE - UMT 3 3/4 7-15 Amendment No. 2, GikI-,£03, #f
Millstone Power Station Unit 3 Technical Specification 3.7.7 Control Room Emergency Ventilation System Page 314 7-15 Insert E CRE boundary, perform the following:
- 1. Immediately initiate action to implement mitigating actions, and
- 2. Verify, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, mitigating actions ensure CRE occupant exposures to radiological and chemical hazards will not exceed limits, and mitigating actions are taken for exposure to smoke hazards, and
Otherwise,
~ i w g -
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) fying that the system maintains the control room at a positive of geater than or equal to 1/8 inch Water Gauge at less than or equal to a pressurization flow of 230 cfm relative to adjacent areas and outside atmosphere during the filtered pressurization made of operation; and ) ($-
(3) Verifying that the heaters dissipate 9.4 f1 k W when tested in accordance with ANSI N510-1980.
f AAer each complete or partial replacement of a HEPA filter bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 0.05% in accordance with ANSI N510-1980 for a DOP test aerosol while operating the system at a flow rate of 1120 cfin *20%; and
- g. After each complete or partial replacement of a charcoal adsorber bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 0.05% in accordance with ANSI N510- 1980 for a halogenated hydrocarbon refrigerant test gas while operating the system at a flow rate of 1120 cfm k20%.
- ANSI N5 10-1980 shall be used in place of ANSI N510-1975 referenced in Regulatory Guide 15 2 , Revision 2, March 1978.
2 MILLSTONE - UNTT 3 Amendment No. 2,423,WY ?Sy,&$d
psg-ELECTNCAL POWER SYSTEMS t D. C , SOURCES SHUTDOWN LIMTING CONDITION FOR OPERATION 3.8.2.2 As a minimum, one train (A or B) of batteries and their associated full capacity chargers shall be OPERABLE:
- a. Train - "A" consisting of:
- 1) Battery Bank 30lA-1 and a full capacity battery charger, and
- 2) Battery Bank 30 1A-2 and a full capacity battery charger.
- b. Train - "B" consisting of:
- 1) Battery Bank 301B-1 and a full capacity battery charger, and
- 2) Battery Bank 301B-2 and a full capacity battery charger.
APPLICABILITT MODES 5 and 6.
ACTIOK :
With the required uspend ali operations involving CORE ALTERATIONS, t could result in loss of required SDM or boron concentration, operation with loads over the he1 storage pool, or operation with a potential for draining the reactor vessel; initiate corrective action to restore the required train to OPERABLE status as soon as possible.
SURVEILLANCE REQUIREMENTS 4.8.2.2 The above required train shall be demonstrated OPERABLE in accordance with Specification 4.8.2.1.
MILLSTONE - UNIT 3 3/4 8-15 Amendment No. I% 64, % , ,%,%$y
ELECTRICAL P O m R SYSTEMS ONSITE POWER DISTRIBUTION SHUTDOWN LIMITING CONDITION FOR OPERATION (Continued) tr
- 4) Two 125 volt DC Busses consisting of:
a) Bus #3Ol B- 1 energized from Battery Bank #3OlB- 1, and b) Bus #301B-2 energized fiom Battery Bank #301B-2.
APPLICABILITY: MODES 5 and 6'.
Ired electrical busses not energized in the required manner, rations involving CORE ALTERATIONS, positive reactivity loss of required SDM or boron concentration, movement of n with loads over the kel storage pool, or operations with potential for draining the reactor vessel, initiate corrective action to energize the required electricat busses in the specified manner as soon as possible.
SURVEILLANCE REQULRETVLEbiTS 4.8.3.2 The specified busses shall be determined energized in the required manner at least once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.
MILLSTONE - UNIT 3 8P Amendment No.. 4 4 ,
ADMINISTUTIVE CONTROLS PROCEDURES AND PROGRAMS (Continued) evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack..
- e. Provisions for monitoring operational primary to secondary LEAKAGE.
6.8.5 Written procedures shall be established, implemented and maintained covering Section I.E, Radiological Environmental Monitoring, of the REMODCM.
6.8.6 All procedures and procedure changes required for the Radiological Environmental Monitoring Program (REMP)of Specification 6.8.5 above shall be reviewed by an individual (other than the author) from the organization responsible for the REMP and approved by appropriate supervision.
Temporary changes may be made provided the intent of the original procedure is not altered and the change is documented and reviewed by an individual (other than the author) from the organization responsible for the REMP, within 14 days of implementation.
6.9 REPORTING REOUIREMENTS ROUTINE REPORTS 6.9.1 In addition to the applicable reporting requirements of Title 10, Code of Federal Regulations, the following reports shall be submitted to the U.S. Nuclear Regulatory Commission, Document Control Desk, Washington, D.C.20555, one copy to the Regional Administrator, Region I, and one copy to the NRC Resident Inspector, unless otherwise noted.
STARTUP REPORT 6.9.1.1 A summary report of plant startup and power escalation testing shall be submitted following: (1) receipt of an Operating License, (2) amendment to the license involving a planned increase in power level, (3) installation of fuel that has a different design or has been manufactured by a different he1 supplier, and (4) modifications that may have significantIy altered the nuclear, thermal, or hydraulic performance of the unit.
The Startup Report shall address each of the tests identified in the Final Safety Analysis Report and shall include a description of the measured values of the operating conditions or characteristics obtained during the test program and a comparison of these values with design predictions and specifications. Any corrective actions that were required to obtain satisfactory operation shall also be described. Any additional specific details required in license conditions based on other commitments shall be included in this report.
MILLSTONE UNIT 3 Amendment No. 69,4436, Xi, 238
Millstone Power Station Unit 3 Technical Specification Section 6 Administrative controls Page 6-17c Insert F 6.8.4. h Control Room Envelope Habitabilitv Program A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of 5 rem total effective dose equivalent (TEDE) for the duration of the accident. The program shall include the following elements:
- b. Requirements for maintaining the CRE boundary in its design condition including configuration control and preventive maintenance.
- c. Requirements for (i) determining the unfiltered air inleakage past the CRE boundary into the CRE in accordance with the testing methods and at the Frequencies specified in Sections C. 1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.l and C.2 of Regulatory Guide 1.I97, Revision 0.
The following are exceptions to Sections C.1 and C.2 of Regulatory Guide 1.t 97, Revision 0:
- 1. Appropriate application of ASTM E741 shall include the ability to take minor exceptions to the test methodology. These exceptions shall be documented in the test report, and
- 2. Vulnerability assessments for radiological, hazardous chemical and smoke, and emergency ventilation system testing were completed as documented in the UFSAR and other licensing basis documents.
The exceptions to the Regulatory Guides (RG) referenced in RG
1.196 (i.e., RG 1.52, RG 1.78, and RG 1.183), which were considered in completing the vulnerability assessments, are documented in the UFSARkurrent licensing basis. Compliance with these RGs is consistent with the current licensing basis as described in the UFSAR and other licensing basis documents.
Measurement, at designated locations, of the CRE pressure relative to all external areas adjacent to the CRE boundary during the pressurization mode of operation by one train of the CREVS, operating at the flow rate required by the Surveillance Requirements, at a Frequency of 48 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the 24 month assessment of the CRE boundary.
The quantitative limits on unfiltered air inleakage into the CRE. These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c.
The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences. Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.
The provisions of Surveillance Requirement 4.0.2 are applicable to the Frequencies for assessing CRE habitability, determining CRE unfiltered inleakage, and measuring CRE pressure and assessing the CRE boundary as required by paragraphs c. and d., respectively.
Serial No. 07-0440 Docket No. 50-336 50-423 ATTACHMENT 4 APPLICATION FOR TECHNICAL SPECIFICATION IMPROVEMENT REGARDING CONTROL ROOM HABITABILITY MARKED UP BASES PAGES (INFORMATION ONLY)
DOMINION NUCLEAR CONNECTICUT, INC.
MILLSTONE POWER STATION UNITS 2 AND 3
BDCR 05-MP2-002 PLANT SYSTEMS BASES 314.7.4 SERVICE WATER SYSTEM (Continued) determined to be inoperable should be the loop that results in the most adverse pIant configuration with respect to the availability of accident mitigation equipment. Restoration of loop independence within the time constraints of the allowed outage time is required, or a plant shutdown is necessary.
It is acceptable to operate with the SW header supply valves to sodium hypochlorite (2-SW-84A and 2-SW-84B) and the SW header supply valves to the north and south filters(2-SW-298 and 2-SW-299) open.The flow restricting orifices in these lines ensure that safety related loads continue to receive minimum required flow during a LOCA (in which the lines remain intact) or during a seismic event (when the lines break). Therefore, operation with these valves open does not affect OPERABILITY of the SW loops.
Surveillance Requirement 4.7.4.1 .a verifies the correct alignment for manual, power operated, and automatic valves in the Service Water (SW) System flow paths to provide assurance that the proper flow paths exist for SW operation. This surveillance does not apply to valves that are locked, sealed, or otherwise secured in position, since these valves were verified to be in the correct position prior to locking, sealing, or securing. A valve that receives an actuation signal is allowed to be in a nonaccident position provided the valve automatically repositions within the proper stroke time. This surveillance does not require any testing or vaIve manipulation. Rather, it involves verification that those valves capable of being mispositioned are in the correct position.
The 3 1 day frequency is appropriate because the valves are operated under procedural control and an improper valve position would only affect a single train. This frequency has been shown to be acceptable through operating experience.
Surveillance Requirements 4.7.4.1 .b and 4.7.4.1 .c demonstrate that each automatic SW valve actuates to the required position on an actual or simulated actuation signal and that each SW pump starts on receipt of an actual or simulated actuation signal. This surveillance is not required for valves that are locked, sealed, or otherwise secured in the required position under administrative controls. The 18 month frequency is based on the need to perform these surveillances under the conditions that apply during a plant outage and the potential for unplanned transients if the surveillances were performed with the reactor at power. The 18 month frequency is also acceptable based on consideration of the design reliability (and confirming operating experience) of the equipment. The actuation logic is tested as part of the Engineered Safety Feature Actuation System (ESFAS) testing, and equipment performance is monitored as part of the Insewice Testing Program.
314.7.5 DELETED 314.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM The OPERABILITY of the Control Room Emergency Ventilation System ensures that
- 1) the ambient air temperature does not exceed the allowable temperature for continuous du rating for the equipment and instrumentation cooled by this system and 2) the control room d remain habitable for operations personnel during and following all credible accident conditions.
MILLSTONE - UNIT 2 B 314 7-4 Amendment No. 2£3,2%,272,273,
PLANT SYSTEMS BASES 314.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
The OPERABILITY of this system in conjunction with control room design provisions is based on limiting the radiation exposure to personnel occupying the control room. For all postulated design basis accidents, the radiation exposure to personnel occupying the control room shall be 5 rem TEDE or less consistent with the requirements of 10 CFR 50.67 intermittently under administrative controIs. For entry and exit through doors the administrative control of the opening is performed by the person(s) entering or exiting the area. For other openings, these controls consist of stationing a dedicated individual at the opening who is in constant communication with the control room. This individual will have a method to rapidly The control room radiological dose calculations use the conservative minimum acceptable flow of 2250 cfm based on the flowrate surveillance requirement of 2500 cfin 10%.*
MILLSTONE UNIT 2 £3 314 7-4a Amendment No. 22-8, %,272,233, 284,
Millstone Power Station Unit 2 Technical Specification Bases 3.7.6 Control Room Emergency Ventilation System Page B314 7-4a Insert G The Control Room Envelope (CRE) is the area within the confines of the CRE boundary that contains the spaces that control room occupants inhabit to control the unit during normal and accident conditions. This area encompasses the control room, and other non-critical areas including adjacent support offices, and utility rooms. The CRE is protected during normal operation, natural events, and accident conditions. The CRE boundary is the combination of walls, floor, ceiling, ducting, valves, doors, penetrations and equipment that physically form the CRE. The OPERABILITY of the CRE boundary must be maintained to ensure that the inleakage of unfiltered air into the CRE will not exceed the inleakage assumed in the licensing basis analysis of design basis accident (DBA) consequences to CRE occupants. The CRE and its boundary are defined in the Control Room Envelope Habitability Program.
In order for the control room emergency ventilation systems to be considered OPERABLE, the CRE boundary must be maintained such that the CRE occupant dose from a large radioactive release does not exceed the calculated dose in the licensing basis consequence analyses for DBAs, and that CRE occupants are protected from hazardous chemicals and smoke.
TS LC0 3.7.6.1is modified by a footnote allowing the CRE boundary to be opened intermittently under administrative controls. This footnote only applies to openings in the CRE boundary that can be rapidly restored to the design condition, such as doors, hatches, floor plugs, and access panels. For entry and exit through doors, the administrative control of the opening is performed by the person(s) entering or exiting the area. For other openings, these controls should be proceduralized and consist of stationing a dedicated individual at the opening who is in continuous communication with the operators in the CRE. This individual will have a method to rapidly close the opening and to restore the CRE boundary to a condition equivalent to the design condition when a need for CRE isolation is indicated.
Millstone Power Station Unit 2 Technical Specification Bases 3.7.6 Control Room Emergency Ventilation System Page B3/4 7-4a Insert H ACTIONS a., b., and c. of this specification are applicable at all times during plant operation in MODES 1, 2, 3, and 4. ACTIONS d. and e. are applicable in MODES 5 and 6, or when recently irradiated fuel assemblies are being moved. The control room emergency ventilation system is required to be OPERABLE during fuel handling involving handling recently irradiated fuel (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay. The term "recently" is defined as all irradiated fuel assemblies, until analysis is performed to determine a specific time.
PLANT SYSTEMS BASES 3/4.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
Currently there are some situations where the CREV System may not automatically start on an accident signal, without operator action. Under most situations, the emergency filtration fans will start and the CREV System will be in t fan (F21A or B) or an exhaust fan (F3 1A or B),
train lineup. Also, if a single emergency bus doe the opposite train filter fan will automatically not automatically start. Therefore, operator actio This action is specified in the Emergency Operat calculations do not take credit for CREV Sy allow for operator action.
When the CREV System is checked to shift to the recirculation mode of operation, this will be performed from the normal mode of operation, and from the smoke purge mode of
,I- operation.
Jr With both control room emergency ventilation trains inoperable due to an inoperabl 7 control room boundary, the movement of irradiated fuel assemblies within the spent fuel pool must be immediately suspended. The control room boundary must be restored to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or the unit must be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
If the control room boundary is inoperable in MODES 1,2,3, and 4, the control room emergency ventilation trains cannot perform their intended functions. ACTIONS must be taken to restore an OPERABLE control room boundary within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During the period that the control room boundary is inoperable, appropriate compensatory measures (consistent with the intent of GDC 19) should be utilized to protect control room operators from potential hazards such as radioactive contamination, toxic chemicals, smoke, temperature and relative humidity, and physical security. Preplanned measures should be available to address these concerns for intentional and unintentional entry into this condition. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed outage time is reasonable based on the low probability of a DBA occurring during this time period, and the use of compensatory measures. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed outage time is a typically reasonable time to
@iagn_ose,plan, and possibly repair, and test most ~roblemswith the c o ~ L r a a m b w & ~
Surveillance Requirement 4.7.6.1 frequency, methods and acceptance criteria for the Control Room Emergency trains (cleanup trains). These criteria all originate in the Regulatory Positi egulatory Guide 1.52, Rev. 2, March 1978 as discussed below, Section C.5.a requires a visual inspection of the cleanup system be made before the following tests, in accordance with the provisions of section 5 of ANSI N.5 10-1975 :
in-place air flow distribution test DOP test activated carbon adsorber section leak test MILLSTONE - UNIT 2 B 314 7-4b Amendment No. W,W,245,248,234, 284,
Millstone Power Station Unit 2 Technical Specification Bases 314.7.6.1 Control Room Emergency Ventilation System Page B3/4 7-4b Insert I If the unfiltered inleakage of potentially contaminated air past the CRE boundary and into the CRE can result in CRE occupant radiological dose greater than the calculated dose of the licensing basis analyses of DBA consequences (allowed to be up to 5 rem TEDE), or inadequate protection of CRE occupants from hazardous chemicals or smoke, the CRE boundary is inoperable. Actions must be taken to restore an OPERABLE CRE boundary within 90 days.
During the period that the CRE boundary is considered inoperable, action must be initiated to implement mitigating actions to lessen the effect on CRE occupants from the potential hazards of a radiological or chemical event or a challenge from smoke.
Actions must be taken within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to verify that in the event of a DBA, the mitigating actions will ensure that CRE occupant radiological exposures will not exceed the calculated dose of the licensing basis analyses of DBA consequences, and that CRE occupants are protected from hazardous chemicals and smoke. These mitigating actions (i.e., actions that are taken to offset the consequences of the inoperable CRE boundary) should be preplanned for implementation upon entry into the condition, regardless of whether entry is intentional or unintentional. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed outage time is reasonable based on the low probability of a DBA occurring during this time period, and the use of mitigating actions. The 90 day allowed outage time is reasonable based on the determination that the mitigating actions will ensure protection of CRE occupants within analyzed limits while limiting the probability that CRE occupants will have to implement protective measures that may adversely affect their ability to control the reactor and maintain it in a safe shutdown condition in the event of a DBA. In addition, the 90 day allowed outage time is a reasonable time to diagnose, plan and possibly repair, and test most problems with the CRE boundary.
Immediate action(s), in accordance with the LC0 Action Statements, means that the required action should be pursued without delay and in a controlled manner.
PLANT SYSTEMS BASES 314.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
Section C.5.c requires the in-place Dioctyl phthalate (DOP) test for HEPA filters to conform to section 10 of ANSI N510-1975. The HEPA filters should be tested in place (I) initially, (2) at least once per 18 months thereafter, and (3) following painting, fire, or chemical release in any ventilation zone communicating with the system. The testing is to confirm a penetration of less than 0.05%* at rated flow. A filtration system satisfjring this criteria can be considered to warrant a 99% removal efficiency for particulates.
Section C.5.d requires the charcoal adsorber section to be leak tested with a gaseous halogenated hydrocarbon refrigerant, in accordance with section 12 of ANSI N5 10-f 975 to ensure that bypass leakage through the adsorber section is less than 0.05%.** Adsorber leak testing should be conducted (I) initially, (2) at least once per 18 months thereafter, (3) following removal of an adsorber sample for laboratory testing if the integrity of the adsorber section is affected, and (4) following painting, fire, or chemical release in any ventilation zone communicating with the system.
The ACTION requirements to immediately suspend various activities (CORE ALTERATIONS, irradiated fuel movement, etc.) do not preclude completion of the movement of a component to a safe position.
Technical Specification 3.7.6.1 provides the OPERABILITY requirements for the Control Room Emergency Ventilation Trains. If a Control Room Emergency Ventilation Train emergency power source or normal power source becomes inoperable in MODES 1,2,3, or 4 the requirements of Technical Specification 3.0.5 apply in determining the OPERABILITY of the affected Control Room Emergency Ventilation Train. If a Control Room Emergency Ventilation Train emergency power source or normal power source becomes inoperable in MODES 5 or 6 the guidance provided by Note "**" of this specification applies in determining the OPERABILITY of the affected Control Room Emergency Ventilation Train. If a Control Room Emergency Ventilation Train emergency power source or normal power source becomes inoperable while not in MODES I , 2, 3,4,5, or 6 the requirements of Technical Specification 3.0.5 apply in determining the OPERABILITY of the affected Control Room Emergency Ventilation Train.
- Means that the HEPA filter wiIl allow passage of less than 0.05% of the test concentration injection at the filter inlet from a standard DOP concentration injection.
- Means that the charcoaI adsorber sections will allow passage of less than 0.05% of the injected test concentration around the charcoal adsorber section.
MILLSTONE - UNIT 2 I3 314 7-4c Amendment No. %,236,245,248,
"$9'
Millstone Power Station Unit 2 Technical Specification Bases 314.7.6 Control Room Emergency Ventilation System Page B3/4 7-4c Insert J Surveillance Requirement 4.7.6.1 .e.3 verifies the OPERABILITY of the CRE boundary by testing for unfiltered air inleakage past the CRE boundary and into the CRE. The details of the testing are specified in the Control Room Envelope Habitability Program.
The CRE is considered habitable when the radiological dose to CRE occupants calculated in the licensing basis analyses of DBA consequences is no more than 5 rem TEDE and the CRE occupants are protected from hazardous chemicals and smoke.
This SR verifies that the unfiltered air inleakage into the CRE is no greater than the flow rate assumed in the licensing basis analyses of DBA consequences. When unfiltered air inleakage is greater than the assumed flow rate, ACTION c. must be entered.
ACTION c. allows time to restore the CRE boundary to OPERABLE status provided mitigating actions can ensure that the CRE remains within the licensing basis habitability limits for the occupants following an accident. Compensatory measures are discussed in Regulatory Guide 1.196, which endorses, with exceptions, NEI 99-03.
These compensatory measures may also be used as mitigating actions as required by ACTION c. Temporary analytical methods may also be used as compensatory measures to restore OPERABILITY. Options for restoring the CRE boundary to OPERABLE status include changing the licensing basis DBA consequence analysis, repairing the CRE boundary, or a combination of these actions. Depending upon the nature of the problem and the corrective action, a full scope inleakage test may not be necessary to establish that the CRE boundary has been restored to OPERABLE status.
3/4.8 ELECTRICAL POWER SYSTEMS BASES The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systenls during shutdown and refueling ensures that 1) the facility can be nlaintained in the shutdown or REFUELING condition for extended time periods and 2) sufficient instrumentation and control capability is available for monitoring and maintaining the facility status. If the required power sources or distribution systenls are not OPERABLE in MODES 5 and 6, operations involving CORE ALTERATIONS, positive reactivity additions, or movement of irradiated fuel assemblies are required to be suspended. Suspending positive reactivity that could result in failure to meet the minimum SDM or boron concentration limit is required to assure continued safe operation. Introduction of coolant inventory must be from sources ihat have a boron concentration greater than that what would be required in the RCS for minimunl SDM or refueling boron concentration. This may result in an overall reduction in RCS boron concentration, but provides acceptable margin to maintaining subcritical operation. Introduction of temperature changes including temperature increases when operating with a positive MTC must also be evaluated to ensure they do not result in a loss of required SDM Suspension of these activities does not preclude completion of actions to establish a safe conservative condition. These actions minimize the probability of the occurrence of postulated events, It is further required to immediately initiate action to restore the required AC and DC electrical power source or distribution subsystems and to continue this action until restoration is acconlplished in order to provide the necessary power to the unit safety systems.
Each 125-volt D.C. bus train consists of its associated 125-volt D.C. bus, a 125-volt D.C.
battery bank, and a battery charger with at Ieast 400 ampere charging capacity. To demonstrate OPERABILITY of a 125-volt D.C. bus train, these components must be energized and capable of performing their required safety functions. Additionally, in MODES 1 through 4 at least one tie breaker between the 125-volt D.C. bus trains must be open for a 125-volt D.C. bus train to be considered OPERABLE.
For MODES 5 and 6, each battery is sized to supply the total connected vital loads (one battery connected to both buses) for one hour without charger support. Therefore, in MODES 5 and 6 with at least one 125-volt D.C. bus train OPERABLE and the 125-volt D.C. buses cross-tied, the 125-volt D.C. support system operability requirements for: both buses are satisfied.
Footnote (a) to Technical Specification Tables 4.8-1 and 4.8-2 permits the electrolyte level to be above the specified maximum level for the Category A limits during equalizing charge, provided it is not overflowing. Because of the internal gas generation during the performance of an equalizing charge, specific gravity gradients and artificially elevated electrolyte levels are produced which may exist for several days following compIetion of the equalizing charge. These limits ensure that the plates suffer no physical damage, and that adequate electron transfer capability is maintained in the event of transient conditions. In accordance with the recommendations of IEEE 450-1980, electrolyte level readings should be taken only after the battery has been at float charge for at least 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
I MILLSTONE - UNIT 2 B 3/4 8-17 Amendment No. %,49?, ?34, M ,
w, 27-3>m, =, 6
Millstone Power Station Unit 2 Technical Specification Bases 314.82 Electrical Power Systems Page B3/4 8-17 Insert R The movement of recently irradiated fuel assemblies (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay is also required to be suspended. The term "recently" is defined as all irradiated fuel assemblies, until analysis is performed to determine a specific time.
INSTRUMENTATION BASES 314.3.1 and 314.3.2 REACTOR TRIP SYSTEM INSTRUMENTATION and ENGINEERED.
SAFETY FBATURES ACTUATION SYSTEM INSTRUMENTATION (Continued)
The methodology, as defined in WCAP-10991 to derive the Nominal Trip Setpoints, is based upon combining all of the uncertainties in the channels. Inherent in the determination of the Nominal Trip Setpoints are the magnitudes of these channel uncertainties. Sensors and other instrumentation utilized in these channels should be capable of operating within the allowances of these uncertainty magnitudes. Occasional drift in excess of the allowance may be determined to be acceptable based on the other device performance characteristics. Device drift in excess of the allowance that is more than occasional, may be indicative of more serious problems and would warrant further investigation.
The above Bases does not apply to the Control Building Inlet Ventilation radiation monitors ESF Table (Item 7E). For these radiation monitors the allowable values are essentially nominal values. Due to the ukertainties involved in radiological parameters, the methodologih of WCAP-I 099 1 were not applied. Actual trip setpoints will be reestablished below the allowable value based on calibration accuracies and good pr The OPERABILITY requirements for
' that during a fuel handling accident some of the fie1 that is dropped and some of the fuel impacted upon is damaged. Therefore, the movement of either new or irradiated fuel (assemblies or individual fitel rods) can cause a fuel handling accident, and hnctional units 7.a and 7.e are required to be OPERABLE whenever new or irradiated fuel is moved within the containment or
,the storage pool,/~ablenotation "*" of Table 4.3-2 has the same applicability.
The verification of response time at the specified fiequencies provides assurance that the reactor trip and the engineered safety features actuation associated with each channel is completed within the time limit assumed in the safety analysis. No credit is taken in the analysis for those channels with response times indicated as not applicable (i-e., N.A.).
Required ACTION 4. of Table 3.3- 1 is modified by a Note to indicate that normal plant control operations that individually add limited positive reactivity (e.g., temperature or boron fluctuations associated with RCS inventory management or temperature control) are not precluded by this ACTION provided they are accounted for in the calculated SDM. The proposed change permits operations introducing positive reactivity additions but prohibits the temperature change or overali boron concentration from decreasing below that required to maintain the specified SDM or required boron concentration.
MILLSTONE - UNIT 3 B 314 3-2 Amendment No. 3 , G , 439, -,I&?,
2t9#d
Millstone Power Station Unit 3 Technical Specification Bases 3f4.3.2 Emergency Safety Features Actuation System Page 6314 3-2 Insert S The Control Building Isolation Manual Actuation and Control Building Inlet Ventilation Radiation are required to be OPERABLE during movement of recently irradiated fuel assemblies (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay. The term "recently" is defined as all fuel assemblies, including new fuel assemblies, until analysis is performed to determine a specific time.
BASES
\
Y4.3.1 and 314.3.2 REACTOR TRIP SYSTEM INSTRUMENTATION and ENGINBE SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION (Continued)
P-1 I On increasingpressurizer pressure, P-1 1 automatically reinstates Safety Injection actuation on low pressurizer pessure and low steam line pressure. On decreasing pressure, P-1 1 allows the manual block of Safety Injection actuation on low pressurizer pressure and low steam fine pressure.
\
P-12 On increasing reactor coolant loop temperature, P-12 automatically provides an anning signal to the Steam Dump System. On decreasing rezictor coolant Ioop temperature, P-12 automatically removes the arming s i s d from the Steam Dump System.
P-14 On increasing steam generator water level, P-14 automatically trips all feedwater isolation valves, main feed pumps and main turbine, and inhibits feedwater control valve modulation.
314-3.3 MONITORING INSTRUMENTATION 314.3.3.1 RADIATION MONITORING FOR PLANT OPERATIONS The OPEFWBILITY of the radiation monitoring instrumentation for plant operations ensures that: (I) the associated action will be initiated when the radiation level monitored by each c1- or combinationthereof reaches its Setpoint, (2) the specified coincidence logic is maintained, and (3) sufficient redundancy is maintained to permit a channel to be out-of-service for testing or maintenance. The radiation monitors for plant operations senses radiation levels in selected plant systems and locations and determines whether or not predetermined limits are being exceeded. Ifthey are, the signals are combined into logic matrices sensitive to combinations indicative of various-accidents and abnormal conditions. Once the required logic combination is completed, the system sends actuation signals to initiate alarms.
314.3.3.2 DELETED 34.3.3.3 DELETED 314.3.3.4 DELETED MILLSTONE - UNlT 3
Millstone Power Station Unit 3 Technical Specification Bases 314.3.3.1 Radiation Monitoring Page 8314 3-4 Insert T The Fuel Storage Pool Area Monitor is required to be OPERABLE during movement of recently irradiated fuel assemblies (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay. The term "recently" is defined as all fuel assemblies, including new fuel assemblies, until analysis is performed to determine a specific time.
February 24,2005 PLANT SYSTEMS BASES SURVEILLANCE REQUIREMENTS For the surveillar!ce rkpirements, the UHS temperature is measured at the locations described in the LC0 write-up provided in this section.
Surveillance Requirement 4.7.5.a verifies that the UHS is capable of providing a 30-day cooling water supply to safety-related equipment without exceeding its design basis temperature. The 24-hour fieq'uency is based on operating experiencerelated to trending of the parameter variations during the applicable MODES. This surv~llancerequirement verifies that the average water temperature of the UHS is less than or equal to 75OF.
6 Surveillaixe Requirement 4.7.5.b rewres that the UHS temperature be monitored on an increased fiequency whenever the 'tJ)-XStemperature is greater than 70°F during the applicable MODES. The intent of this Surveillance Requirement is to increase the awareness of plant personnel regarding UHS temperature trends above 70°F. The fiequency is based on op&ating 6
experience related to trending of the parameter variations during the applicable MODES.
3/4.7.6 DELETED 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM !
BACKGROUND The mntml room emergemy ventilatiun system provides a'prokcted 9 ,hazardous chemicals, or smoke) operators can control the unit following an uncontroHed release of system provides temperature control for the control room during normal and post-accident operations.
The control room emergency ventilation system is comprised of the control room emergency air consists of a moisture separator, electric heater, prefilter, upstream high efficiency particulate air (HEPA) filter, charcoal adsorber, downstream HEPA filter, and fan. ~dditionall~,'ductwork, es or dampers, and instrumentation form part of the system.
Normal Operation A portion of the control room emergency ventilation system is required to operate during normal operations to ensure the temperature of the control room is maintained at or below 95°F.
r MILLSTONE - UNIT 3 B 314 7-10 Amendment No. W,M,W, 24-4,-
@Amowledged by NRC letter dated 08/25/0>
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B3/4 7-10 Insert K The CRE is the area within the confines of the CRE boundary that contains the spaces that control room occupants inhabit to control the unit during normal and accident conditions. This area encompasses the control room, and other non-critical areas including adjacent support offices, toilet and utility rooms. The CRE is protected during normal operation, natural events, and accident conditions. The CRE boundary is the combination of walls, floor, ceiling, ducting, valves, doors, penetrations and equipment that physically form the CRE. The OPERABILITY of the CRE boundary must be maintained to ensure that the inleakage of unfiltered air into the CRE will not exceed the inleakage assumed in the licensing basis analysis of design basis accident (DBA) consequences to CRE occupants. The CRE and its boundary are defined in the Control Room Envelope Habitability Program and UFSAR Section 6.4.2.1.
No. 0 6 - ~ 3 - 0 2 6 )
October 15,2006 PLANT SYSTEMS BASES 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
BACKGROUND (Continued)
Post Accident Operation The control room emergency ventilation system is required to operate during post-accident operations to ensure the temperature of the e a & s b e m 's maintained and to ensure the rrrntrnl raolli will remain habitable during and following accide$c-w/
The following sequence of events occurs upon reeeipt of a co or a signal indicating high radiation in the air supply duct to the emb&mcm boundary is isol t outside air from entering the to prevent the om being exposed to the radiological may exist outside the F .
The analysis for a loss of coolant accident assumes that the high$&releases occur in the first hour after a loss of coo
- 2. ergency.vqntilation system will be placed in mode (outside air is diverted through the to mciktain a positive pressuk). To run the control room emergency air filtration system in the mode, the air supply line must be manually opened.
APPLICABLE SAFETY ANALYSIS The OPERABILITY of the Control Room Emergency Ventilation System ensures that: (1) the ambient air temperature.doesnot exceed the allowable temperature for continuous-duty rating for and instnunentation cooled by this system, a d (2) the ill remain @
during and following all credible a c z o n s . The OPERABILITY of this system in conjunction with control room design provisions is based on limiting the radiation exposure to design basis accidents, the rad 5 rem TEDE or less, consist consistent with the requi MILLSTONE - WI:3 B 314 7-11 Amendment No. -134, ?#
PLANT SYSTEMS BASES 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
LIMITING CONDITION FOR OPERATION Two independent control room emergency air filtration systems are required to OPERABLE to ensure that at least one is available in the event the other system is disabled A control room emergency air filtration system is OPERABLE when the associated:
- a. Fan is OPERABLE;
-b.
c.
HEPA filters and charcoal adsorbem are not excessively restricting flow and are capable of performing their filtration functions; and moisture separator, heater, ductwork, valves, and dampers are OPERABLE, and air circulation can be maintained.
The integrity of the control room habitability boundary (i-e., walls, floors, ceilings, ductwork, and access doors) must be maintained such that the control building habitability zone can be maintained at its design positive pressure if required to be aligned in the filtration pressurization mode. However, the L C 0 is modified by a footnote allowing the control room boundary to be opened intermittently under administrative controls. For entry and exit through doors the administrative control of the opening is performed by the person@)entering or exiting the area. For other opeiiings, these controls consist of statioriing a diJdicaEI i5XEdual. at the opening who is in constant communication with the control room. This individual will have a y close the opening when a need for control room isolation is indicated.
APPLICABILITY In MODES 1,2,3,4,5, and 6. ,
efore, the movement handling accident, and this specification is applicable whenever new or irradiated he1 is cmoved within the containment or the storage pool.
C' I
MILLSTONE - UNIT 3 B 3/4 7-12 Amendment No. 436,283, W,?
@Amowledged by NRC letter dated 08/25/05)
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B3/4 7-12 Insert L Total system failure, such as from a loss of both ventilation trains or from an inoperable CRE boundary, could result in exceeding a dose of 5 rem TEDE to the CRE occupants in the event of a large radioactive release.
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page 8314 7-12 Insert M In order for the CREVS to be considered OPERABLE, the CRE boundary must be maintained such that the CRE occupant dose from a large radioactive release does not exceed the calculated dose in the licensing basis consequence analyses for DBAs, and that CRE occupants are protected from hazardous chemicals and smoke.
TS LC0 3.7.7is modified by a footnote allowing the CRE boundary to be opened intermittently under administrative controls. This footnote only applies to openings in the CRE boundary that can be rapidly restored to the design condition, such as doors, hatches, floor plugs, and access panels. For entry and exit through doors, the administrative control of the opening is performed by the person(s) entering or exiting the area. For other openings, these controls should be proceduralized and consist of stationing a dedicated individual at the opening who is in continuous communication with the operators in the CRE. This individual will have a method to rapidly close the opening and to restore the CRE boundary to a condition equivalent to the design condition when a need for CRE isolation is indicated.
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B3/4 7-12 Insert N The CREVS is required to be OPERABLE during fuel handling involving handling recently irradiated fuel (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), due to radioactive decay. The term "recently" is defined as all fuel assemblies, including new fuel assemblies, until analysis is performed to determine a specific time.
PLANT SYSTEMS BASES 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
ACTIONS MODES 1.2.3. and 4 d
With one control room emergency air filtration system inoperabl ,a ~ i o must n be taken to liiv restore the inoperable system to an OPERABLE status within 7 days. In this condition, the remaining control room emergency air filtration system is adequate to perform the
%e&mbma protection function. However, the overall reliability is reduced bwause a single failure in the OPERABLE train could result in a loss of the control room emergency
, air filtration system hction. The 7-day completion time is based on the low probability of a DBA occurring during this time period, and the ability of the remaining train to provide the required capability.
If the inoperable train cannot be restored to an OPERABLE status within 7 days, the unit must be placed in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. These completion times are reasonable, based on operating experience, to reach the required unit condition from full power conditions in an drderly manner and without challenging unit systems.
- b. With both control room emergency air filtration systems inoperable, except due to an inoperable- bound# movement of fuel within the spent fuel pool m (be immediately sumendedL3Zt least one control room emereencv air filtration svst& must within the next 6 h o w and in COLD SHUTDOWN within the fobwing 30hours, These completion times are reasonable, based on operating experience, to reaccthe required unit conditions from 111 power conditions in an orderly manner and without challenging unit c.
d:-k With be& control room emergency air filtration system's inoperable due to an inoperable ntrol room boundary, the movement of %el within the spent he1 pool must be immediately suspended. The control room boundary must be restored to OP tatus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. o - s u n i t must be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
(consistent with the intent of GDC 19) should be utilized to protect control room operators from potential hazards such as radioactive contamination, toxic chemicals, smoke, temperature and relative humidity, and physical security. Preplanned measures should be)
MILLSTONE - UNIT 3 B 3/4 7-13 Amendment No. 4-36,W, £49, , ,
@$nowledged by ~ m e t t edated r 08/25/09
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B314 7-'I3 Insert 0 CRE boundary, (1) action must be immediately initiated to implement mitigating actions; (2) action must be taken within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to verify mitigating actions ensure CRE occupant exposures to radiological and chemical hazards will not exceed limits, and mitigating actions are taken for exposure to smoke hazards; and (3) the CRE boundary must be restored to OPERABLE status within 90 days. Otherwise,
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B314 7-13 Insert P If the unfiltered inleakage of potentially contaminated air past the CRE boundary and into the CRE can result in CRE occupant radiological dose greater than the calculated dose of the licensing basis analyses of DBA consequences (allowed to be up to 5 rem TEDE), or inadequate protection of CRE occupants from hazardous chemicals or smoke, the CRE boundary is inoperable. Actions must be taken to restore an OPERABLE CRE boundary within 90 days.
During the period that the CRE boundary is considered inoperable, action must be initiated to implement mitigating actions to lessen the effect on CRE occupants from the potential hazards of a radiological or chemical event or a challenge from smoke.
Actions must be taken within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to verify that in the event of a DBA, the mitigating actions will ensure that CRE occupant radiological exposures will not exceed the calculated dose of the licensing basis analyses of DBA consequences, and that CRE occupants are protected from hazardous chemicals and smoke. These mitigating actions (i.e., actions that are taken to offset the consequences of the inoperable CRE boundary) should be preplanned for implementation upon entry into the condition, regardless of whether entry is intentional or unintentional. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Completion Time is reasonable based on the low probability of a DBA occurring during this time period, and the use of mitigating actions. The 90 day Completion Time is reasonable based on the determination that the mitigating actions will ensure protection of CRE occupants within analyzed limits while limiting the probability that CRE occupants will have to implement protective measures that may adversely affect their ability to control the reactor and maintain it in a safe shutdown condition in the event of a DBA. In addition, the 90 day Completion Time is a reasonable time to diagnose, plan and possibly repair, and test most problems with the CRE boundary.
immediate action(s), in accordance with the LC0 ACTION Statements, means that the required action should be pursued without delay and in a controlled manner.
PLANT SYSTEMS BASES 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
ACTIONS (Continued)
-C
{available to address these concerns for intentional and unintentional entry in to this condition. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed outage time is reasonable based on the low probability of a DBA occurring during this time period, and the use of compensatory measures. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> allowed outage time is a typically reasonable time to diagnose, plan, and possibly kepair, and test most problems with the control room boundary.
MODES 5 and 6 . 6 V -
d.
-Gent With one control room emeuzen~yair tiltratam svstem inweram. stion must taken to w
restore the inoperable system to an O P E R A B L ~ wS h~i n 12 of recently irradiated fuel assemblies
~ ~ After 7 days, either
~ 7~days.
initiate and maintain operation of the remaining O P E W L E control room emergency air filtration system in the fbel. Initiating and maintaining op mode ensures:
(i) OPERABILITY of the the automatic actuation logic; and (ii) ac I -o----J
- e. With both control room emergency air filtration s$stems inoperable, or with the train required by ACTION 'd' not capable of being powered by an OPERABLE em'ergency power source, actions must be taken to suspend a11 operations involving the movement o L fuel. This action places the unit in a condition that minimizes risk. This Gii'%ae the movement of fuel to a safe position.
SUR"VEILLmBREOU-TS 4.7.7.a covered by the technical specifications. Typically, temperature aberrations will be readily apparent.
Standby systems should be checked periodically to ensure that they function properly. As the environment and normal operating conditions on this system are not too severe, testing the trains once every 3 1 days on a STAGGERED TEST BASIS pr'ovides an adequate check of this system. This surveillance requirement verifies a system flow rate of 1,120 cfin 20%.
- Additionally, the system is required to operate for at least 10 continuous hours with the heaters energized. These operations are sufficient to reduce the buildup of moisture on the adsorbers and HEPA filters due to the humidity in the ambient air.
MILLSTONE - UNIT 3 B 314 7-13a Amendment No. ~ 2.433,249,-
~
('%N--dated 08/2510$
PLANT SYSTEMS BASES 3J4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
SURVEILLANCE REQUIREMENTS (Continued)
After 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoaI adsorber operation, a representative carbon sample must be obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, March 1978, and a Iaboratory analysis must verify that the representative carbon sample meets the laboratory testing criteria of ASTM D3803-89 and Millstone Unit 3 specific parameters.
The laboratory analysis is required to be performed within 3 1 days after removal of the sample.
ANSI NS 10-1980 is used in lieu of ANSI N5 10-1975 referenced in Revision 2 of Regulatory Guide 1.52.
The maximum surveillance interval is 900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br />, per Surveillance Requirement 4.0.2. The 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of operation requirement originates from Nuclear Regulatory Guide 1.52, Table 2, Note C. This testing ensures that the charcoal adsorbency capacity has not degraded below acceptable limits as well as providing trending data.
This surveillance verifies that the pressure drop across the combined HEPA filters and charcoal adsorbers banks at less than 6.75 inches water gauge when the system is operated at a flow rate of 1,120 cfm 20%. The frequency is at least once per 24 months.
4.7.7.e.2 Insert Q
'>T shi surveillance verifies that the system maintains the control mom at a positive pressure of 1
greater than or equal to 118 inch water gauge at less than or equal to a pressurization flow of 230 c h relative to adjacent areas and outside atmosphere during positive pressure system operation. The frequency is at least once per 24 months.
I The intent of this surveillance is to verify the ability of the control room emergency air I 1 filtration system to maintain a positive pressure while running in the filtered pressurization I I mode.
A CE31 signal will automaticaliy align an operating filtration system into the recirculation mode f operation due to the isolation of the air supply line to the filter.
MILLSTONE - UNIT 3 B 314 7-1 5 Amendment No. W,4-8+, 184,283,236,
Millstone Power Station Unit 3 Technical Specification Bases 314.7.7 Control Room Emergency Ventilation System Page B314 7-15 Insert Q This Surveillance verifies the OPERABILITY of the CRE boundary by testing for unfiltered air inleakage past the CRE boundary and into the CRE. The details of the testing are specified in the Control Room Envelope Habitability Program.
The CRE is considered habitable when the radiological dose to CRE occupants calculated in the licensing basis analyses of DBA consequences is no more than 5 rem TEDE and the CRE occupants are protected from hazardous chemicals and smoke.
This SR verifies that the unfiltered air inleakage into the CRE is no greater than the flow rate assumed in the licensing basis analyses of DBA consequences. When unfiltered air inleakage is greater than the assumed flow rate, ACTION c. must be entered.
ACTION c. allows time to restore the CRE boundary to OPERABLE status provided mitigating actions can ensure that the CRE remains within the licensing basis habitability limits for the occupants following an accident. Compensatory measures are discussed in Regulatory Guide 1.196, which endorses, with exceptions, NEI 99-03.
These compensatory measures may also be used as mitigating actions as required by ACTION c. Temporary analytical methods may also be used as compensatory measures to restore OPERABILITY. Options for restoring the CRE boundary to OPERABLE status include changing the licensing basis DBA consequence analysis, repairing the CRE boundary, or a combination of these actions. Depending upon the nature of the problem and the corrective action, a full scope inleakage test may not be necessary to establish that the CRE boundary has been restored to OPERABLE status.
March 7,2006 PLANT SYSTEMS BASES 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM (Continued)
SURVEILLANCE REOUIREMENTS (Continued) emergency ventilation system will be aligned in the filtered pressurization mode (outside air is diverted through the filters to the control room envelope to maintain a positive pressure).
Alignment to the filtered pressurization mode requires manual operator action to open the air This surveillance verifies that the heaters can dissipate 9.4 rt 1 kW at 480V when tested in accordance with ANSI N5 10-1980. The frequency is at least once per 24 months. The heater kW measured must be corrected to its nameplate rating. Variations in system voltage can lead to measurements of kW which cannot be compared to the nameplate rating because the output kW is proportional to the square of the voltage.
Following the complete or partial replacement of a HEPA filter bank, the OPERABILITY of the cleanup system should be confirmed. This is accomplished by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criterion of less than 0.05% in accordance with ANSI N510-1980 for a DOP test aerosol while operating the system at a flow rate of 1,120 cfin 20%.
- Following the complete or partial replacement of a charcoal adsorber bank, the OPERABILITY of the cleanup system should be confirmed. This is accomplished by verifying that the cleanup system satisfied the in-place penetration and bypass leakage testing acceptance criterion of less than 0.05% in accordance with ANSI N5 T 0-1 980 for a halogenated hydrocarbon refrigerant test gas while operating the system at a flow of 1,120 cfm 20%. *
References:
(1 ) Nuclear Regulatory Guide 1.52, Revision 2 (2) MP3 UFSAR, TabIe 1.8-1, NRC Regulatory Guide 1.52 (3) NRC Generic Letter 9 1-04 (4) Condition Report (CR) #M3-99-027 1 i
MILLSTONE - UNIT 3 B 3/4 7-16 Amendment No. 436, 243,W ,
(-[(5) 3 NEI 99-03, C -.
(6) Letter fiom Eric J. Lee& (NRC) to James W. Davis (NEI) dated January 30,2004, "NEI Draft White paper, Use of Generic Letter 9 1-1 8 Process and Alternative Source Terms in the Context of Control Room Habitability." (ADAMS Accession No. ,
ELECTRICAL POWER SYSTEMS BASES A.C. SOURCES, D.C. SOURCES, and ONSITE POWER DISTRIBUTION (Continued)
The Surveillance Requirement f o r demonstrating t h e OPERABILITY of the s t a t i o n b a t t e r i e s are based on t h e recommendations of Regulatory Guide 1.129,
-"Ma-intenance Testing and Repl acement of Large Lead Storage Batteries f o r Nuclear Power Plants," February 1978, and IEEE Std 450-1975 & 1980, "IEEE Recommended Practice f o r Maintenance, Testing, and Repl acement of Large Lead Storage Batteries f o r Generating Stations and Substations." Sections 5 and 6 o f ZEEE Std 450-1980 replaced Sections 4 and 5 of IEEE Std 450-1975, otherwise the balance of I E E E Std 450-1975 applies.
Veri fyi ng average e l e c t r o l y t e temperature above t h e minimum f o r which t h e battery was sized, t o t a l battery terminal voltage on f l o a t charge, connection resistance values, and t h e performance of battery service and discharge t e s t s ensures the effectiveness o f the charging system, t h e a b i l i t y t o handle high 6
discharge r a t e s , and compares the battery capacity a t t h a t time with t h e rated capacity .
, Table 4.8-2a s p e c i f i e s the normal l i m i t s f o r each designated p i l o t c e l l and each connected c e l l f o r e l e c t r o l y t e level, f l o a t voltage, and s p e c i f i c gravity. The 1imits f o r t h e designated p i l o t c e l l s f l o a t voltage and s p e c i f i c gravity, greater than 2.13 v o l t s and 0.015 below t h e manufacturer's f u l l charge s p e c i f i c gravity o r a battery charger current t h a t had stabilized a t a low value, is c h a r a c t e r i s t i c of a charged c e l l with adequate capacfty. The normal l i m i t s f o r each connected c e l l f o r f l o a t voltage and s p e c i f i c gravity, greater than 2.13 v o l t s and not more than 0.020 below the manufacturer's f u l l charge s p e c i f i c gravity w i t h an average s p e c i f i c gravity of a l l t h e connected c e l l s not more than 0.010 below t h e manufacturer's f u l l charge specific gravity, ensures the OPERABILITY and capability o f t h e battery.
Operation with a battery c e l l ' s parameter outside the normal limit but within the allowable value specified i n Table 4.8-2a is permitted f o r up t o 7 days. During t h i s 7-day period: (1) t h e allowable values f o r e l e c t r o l y t e level ensures no physical damage t o t h e p l a t e s with an adequate electron t r a n s f e r capability; (2) t h e a1 lowable value f o r the average specific gravity of a1 1 the c e l l s , not more than 0.020 below the manufacturer's recommended f u l l charge s p e c i f i c gravity, ensures t h a t the decrease in r a t i n g will be l e s s than the safety margin provided i n sizing; (3) t h e allowable value f o r an individual c e l l 's s p e c i f i c gravity, ensures t h a t an individual cell's specific gravity wi 11 not be more than 0.040 below t h e manufacturer's f u l l charge s p e c i f i c gravity and t h a t the overall capability of the battery will be maintained within an acceptable l i m i t ; and (4) t h e allowable value f o r an individual c e l l 's f l o a t voltage, g r e a t e r than 2.07 v o l t s , ensures t h e battery's capability t o perform i t s design function.
MlLLSTONE - UNlT 3 B 3/4 8- Amendment No.
@evis:d by NRC l e t t i dated April 1. 1 9 9 g
Millstone Power Station Unit 3 Technical Specification Bases 3/43 Electrical Power Systems Page B314 8-2 Insert U If the required power sources or distribution systems are not OPERABLE in MODES 5 and 6, operations involving CORE ALTERATIONS, positive reactivity changes, movement of recently irradiated fuel assemblies (i.e., fuel that has occupied part of a critical reactor core within a time frame established by analysis), crane operation with loads over the fuel storage pool, or operations with a potential for draining the reactor vessel are required to be suspended. The term "recently" is defined as all irradiated fuel assemblies, including new fuel assemblies, until analysis is performed to determine a specific time.