ES-401 BWR Examination Outline Form ES-401-1 Facilitv:

Peach Bottom Printed: 12/21/2006 Date Of Exam:

02/05/2007

1.
2.
3.
4.
5.
6.

Ensure that at least two topics from every WA category are sampled within each tier of the RO and SRO-only outlines (i.e., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each WA category shall not be less than two).

The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by k1 from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.

Systems/evolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted and justified; operationally important, site-specific systems that are not included on the outline should be added. Refer to ES-401, Attachment 2, for guidance regarding the elimination of inappropriate WA statements.

Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.

Absent a plant-specific priority, only those WAS having an importance rating (IR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.

Select SRO topics for Tiers 1 and 2 from the shaded systems and WA categories.

7.* The generic (G) WAS in Tiers 1 and 2 shall be selected from Section 2 of the WA Catalog, but the

8.

topics must be relevant to the applicable evolution or system.

On the following pages, enter the WA numbers, a brief description of each topic, the topics' importance ratings (IRs) for the applicable license level, and the point totals (#) for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in other than Category A2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note # I does not apply). Use duplicate pages for RO and SRO-only exams.

9. For Tier 3, select topics from Section 2 of the WA catalog, and enter the WA numbers, descriptions, IRs, and point totals (#) on Form ES-401-3. Limit SRO selections to WAS that are linked to 10 CFR 55.43.

I

BWR RO Examination Outline Facility:

Peach Bottom Printed: 12/2 I 12006 ES - 401 Emergency and Abnormal Plant Evolutions - Tier 1 / Group 1 (RO / SRO)

Form ES-401-1 equire the notification of reference to procedures those actions that require immediate operation of 1

BWR RO Examination Outline Facility:

Peach Bottom Printed: 12/2 I /2006 ES - 401 Emergency and Abnormal Plant Evolutions - Tier 1 / Group 2 (RO / SRO)

Form ES-401-1 1

BWR RO Examination Outline Printed:

12/2 1 /2006 1

2

BWR RO Examination Outline Facility:

Peach Bottom ES - 401 Plant Systems - Tier 2 / Group 2 (RO / SRO)

I I KI

' %s/Evol# / Name I-.. ~01001 CRD Hydraulic 204000 RWCU 214000 RPIS I

I 2 1500 1 Traversing In-Core Probe 216000 Nuclear BoiIer Inst.

L 230000 RHWLPCI: Torus/Pool Spray Mode 233000 Fuel Pool Cooling/Clean-up 24 1 000 ReactodTurbine Pressure Regulator 245000 Main Turbine Generator/Aux 59001 Reactor Feedwater

'~\\/

286000 Fire Protection K/A Category Totals:

1 Printed: 12/2 112006 Form ES-401-1 1

Generic Knowledge and Abilities Outline (Tier 3)

CatePow KA#

ToDic IR Conduct of Operations 2.1.1 Knowledge of conduct of operations requirements.

3.7 1

2.1.20 Ability to execute procedure steps.

4.3 1

Subtotal:

2 Equipment Control 2.2.24 Ability to analyze the affect of maintenance activities on 2.6 1

2.2.28 Knowledge of new and spent fuel movement procedures.

2.6 1

2.2.34 Knowledge of the process for determining the internal and 2.8 1

Subtotal:

3 Radiation Control 2.3.2 Knowledge of facility ALARA program.

2.5 1

2.3.4 Knowledge of radiation exposure limits and 2.5 1

~

LCO status.

external effects on core reactivity.

contamination control, including permissible levels in excess of those authorized.

d 2.3.1 1 Ability to control radiation releases.

2.7 1

Subtotal:

3 BWR RO Examination Outline Printed: 12/21/2006 2.4.2 2.4.45 Facility:

Peach Bottom Date of Exam:

Form ES-401-3 Knowledge of system set points, interlocks and automatic 3.9 1

Ability to prioritize and interpret the significance of each actions associated with EOP entry conditions.

3.3 1

annunciator or alarm.

Emergency Plan I

I Subtotal:

2 1

Tier 3 Point Total:

10 1

ES-401 BWR Examination Outline Form ES-401-1 Facility:

Peach Bottom Printed: 12/21 /2006 Date Of Exam:

02/05/2007 1

2 3

4 1

2 3

4 0

7

3. Generic Knowledge And Abilities Categories 0

0 0

0 2

2 1

2 Note:

1.
2.
3.
4.
5.
6.

Ensure that at least two topics from every WA category are sampled within each tier of the RO and SRO-only outlines (Le., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each WA category shall not be less than two).

The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by +I from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.

Systemslevolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted and justified; operationally important, site-specific systems that are not included on the outline should be added. Refer to ES-401, Attachment 2, for guidance regarding the elimination of inappropriate WA statements.

Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.

Absent a plant-specific priority, only those WAS having an importance rating (IR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.

Select SRO topics for Tiers 1 and 2 from the shaded systems and WA categories.

7.* The generic (G) WAS in Tiers 1 and 2 shall be selected from Section 2 of the WA Catalog, but the

8.

topics must be relevant to the applicable evolution or system.

On the following pages, enter the WA numbers, a brief description of each topic, the topics' importance ratings (IRs) for the applicable license level, and the point totals (#) for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in other than CategoryA2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note # I does not apply). Use duplicate pages for RO and SRO-only exams.

9. For Tier 3, select topics from Section 2 of the WA catalog, and enter the WA numbers, descriptions, IRs, and point totals (#) on Form ES-401-3. Limit SRO selections to WAS that are linked to 10 CFR 55.43.

1

BWR SRO Examination Outline Facility:

Peach Bottom Printed: 1212 1 /2006 ES - 401 Emergency and Abnormal Plant Evolutions - Tier 1 / Group 1 (RO / SRO)

Form ES-401-1 parameters which are entry-level conditions for emergency and abnormal t

It Total:

7 -

1

BWR SRO Examination Outline Facility:

Peach Bottom Printed: 12/21/2006 ES - 401 Emergency and Abnormal Plant Evolutions - Tier 1 / Group 2 (RO / SRO)

Form ES-401-1 I

Printed:

12/2 I /ZOO6 BWR SRO Examination Outline Facility:

Peach Bottom

'L' I

BWR SRO Examination Outline Facility:

Peach Bottom Plant Systems - Tier 2 / Group 2 (RO / SRO)

Printed:

12/2 1/2006 Form ES-401-1 1

Generic Knowledge and Abilities Outline (Tier 3) 2.1.4 Knowledge of shift staffing requirements.

3.4 2.1.6 Ability to supervise and assume a management role 4.3 during plant transients and upset conditions.

BWR SRO Examination Outline Printed: 12/2 1/2006 1

1 Facility:

Peach Bottom Date of Exam:

Form ES-401-3 Knowledge of the process for managing maintenance Knowledge of SRO fuel handling responsibilities.

3.6 activities during shutdown operations.

3.8

'd CatePory Conduct of Operations 1

1 I

2.3.1 Equipment Control Knowledge of 10 CFR 20 and related facility radiation 3.O 1

control requirements.

Knowledge of the bases for prioritizing safety functions Knowledge of the process used track inoperable alarms.

during abnormaVemergency operations.

2.2.18 4.0 1

2.8 1

~~

2.2.29

~~

Subtotal:

Radiation Control Emergency Plan 2.4.22 I 2.4.33 I Subtotal:

2 1

Tier 3 Point Total:

7 1

~ ES-401 Record of Rejected WAS Form ES-401-4 E

Reason for Rejection Peach Bottom uses static inverters for uninterruptable power supplies, not Randomly Selected WA 262002 A I.02 290003 A3.02 295024 A2.05 295008 G2.4.49 259002 G2.1.14 G2.3.2 motor-generators.

At Peach Bottom, there is no direct association between the Control Room HVAC System and the Fire Protection System.

Peach Bottom has no direct indication or procedural guidance for determining suppression chamber air space temperature.

Unable to construct an SRO question for this KA that meets the requirements of NUREG-I 023.

Unable to construct an SRO question for this KA that meets the requirements of NUREG-1023.

This KA was already sampled on the RO portion of the exam. Unable to construct an additional question at the SRO level.

I II ES-401, Page 27 of 33

ES-301 Administrative ToDics Outline Form ES-301 -I Facility: Peach Bottom Examination Level: RO SRO (7 Administrative Topic (See Note)

Conduct of Operations Conduct of Operations Equipment Control Radiation Control Emergency Plan TY Pe Code*

Date of Examination: 2/5/2007 Operating Test Number: 2007 NRC Describe activity to be performed G2.1.7 - Calculate Drywell Bulk Average Temperature

[2005 NRC]

G2.1.25 - Perform Reactor Coolant Leakage Surveillance

[NEW1 G2.2.11 - Prepare A Partial Procedure [PLOR-205C]

G2.4.43 - Perform Personnel Notifications During A Security Threat [PLOR-2? 7C]

NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics, when 5 are required.

  • Type Codes & Criteria:

(C)ontrol room, (S)imulator, or Class(R)oom (D)irect from bank (2 3 for ROs; 5 4 for SROs & RO retakes)

(N)ew or (M)odified from bank (5 1)

(P)revious 2 exams (5 1; randomly selected)

~

~~

~

~~

~

ES 301, Page 22 of 27

-4

~..

1---

ES-301 Administrative ToDics Outline Form ES-301-1 Facility: Peach Bottom Examination Level: RO 0 SRO Administrative Topic (See Note)

Conduct of Operations Conduct of Operations Equipment Control Radiation Control Emergency Plan TY Pe Code*

Date of Examination: 2/5/2007 Operating Test Number: 2007 NRC Describe activity to be performed G2.1.4 - Evaluate Shift Staffing [ZOO2 NRC]

G2.1.7 - Evaluate A P1 Edit And Take Corrective Action For A Thermal Limit Violation [PLOR-218C]

G2.2.11 - Prepare A Partial Procedure [PLOR-205C]

G2.3.9 - Review And Approve Primary Containment PurgeNent Isolation Valve Cummulative Hour Log [NEW]

G2.4.38 - Review And Authorize Issuance Of Thyroid Blocking Agent (KI) [PLOR-215C]

NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics, when 5 are required.

  • Type Codes & Criteria:

(C)ontrol room, (S)imulator, or Class(R)oom (D)irect from bank (5 3 for ROs; 5 4 for SROs & RO retakes)

(N)ew or (M)odified from bank (2 1)

(P)revious 2 exams (5 1; randomly selected)

ES 301, Page 22 of 27

ES-301 Control Roomlln-Plant Systems Outline Form ES-301-2

i. 201001 A2.09 - Low CRD Scram Air Header Pressure - Unit 3 (Alternate Path - Place Standby Regulator In Service) [PLOR-316PA / 2002 NRC]
j. 295031 EA1.05 - Defeat RClC Low Pressure Isolation - Unit 3

[ PLOR-086PI Facility: Peach Bottom Exam Level: RO SRO-I 0 SRO-U 0 A, D, E, 1

D, E, R 2

p, R Date of Examination: 2/5/2007 Operating Test Number: 2007 NRC

k. 264000 A2.10 - Diesel Generator Air Start Solenoid Override

[PLOR-O49P]

Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U, including 1 ESF)

D, E 6

System / JPM Title

a. 295037 EA1.04 - Inject Boron Into RPV (Alternate Path - RWCU Fails To Isolate) IPLOR-301 CAI - SET I
  • Type Codes
b. 295031 EA1.02 - Manually Initiate HPCl (Alternate Path - Manual Initiation Pushbutton Fails To Operate) [PLOR300CA] - SET 2
c. 218000 A4.03 - ADS Reset Following Blowdown [PLOR-O23C / 2005
d. 209001 A4.04 - Perform Core Spray B Pump Capacity Test For IST (Alternate Path - Minimum Flow Valve Fails To Open) [NEW] - SET 4
e. 219000 A4.13 - HPSW Injection Into The Torus [PLOR-O81C] - SET 1
f. 262001 A4.04 - Synchronize Turbine Generator Output With Grid At Minimum Load IPLOR-Ol7Cl-SET 4 NRC] - SET 3 Criteria for RO / SRO-I / SRO-U
g. 400000 G2.1.23 - Restore TBCCW Following Loss Of Both Pumps
h. 261000 A2.10 - PRO Scram Actions (Alternate Path - SBGT Fails To

[PLOR-O68C] - SET 3 Automatically Initiate) [NEW] - SET 2 Type Code*

A, L, N, S Safety Function 1

2 3

4 5

6 8

9

n I

n (A)lternate path (C)ontrol room (D)irect from bank (E)mergency or abnormal in-plant (L)ow-Power I Shutdown (N)ew or (M)odified from bank including 1(A)

(P)revious 2 exams (WCA (S)imulator 4-6 I 4-6 I 2-3 ES-301, Page 23 of 27

ES-301 Control Roomlln-Plant Systems Outline Form ES-301-2

a. 295037 EA1.04 - Inject Boron Into RPV (Alternate Path - RWCU Fails To
b. 295031 EA1.02 - Manually Initiate HPCl (Alternate Path - Manual
c. 218000 A4.03 - ADS Reset Following Blowdown [PLOR-O23C I2005
d. 209001 A4.04 - Perform Core Spray B Pump Capacity Test For IST
e. 219000 A4.13 - HPSW Injection Into The Torus [PLOR-O81C] - SET 1 Isolate) [PLOR-301CA] - SET 1 Initiation Pushbutton Fails To Operate) [PLOR-300CA] - SET 2 NRC] - SET 3 (Alternate Path - Minimum Flow Valve Fails To Open) [NEW] - SET 4 Facility: Peach Bottom Exam Level: RO SRO-I [x1 SRO-U 0 A, D, S 1

A, D, L, S 2

D, L, p, s 3

A, N, s 4

D, s 5

Date of Examination: 2/5/2007 Operating Test Number: 2007 NRC

g. 400000 G2.1.23 - Restore TBCCW Following Loss Of Both Pumps

[PLOR-O68C] - SET 3

h. 261 000 A2.10 - PRO Scram Actions (Alternate Path - SBGT Fails To Automatically Initiate) [NEW] - SET 2

~~~~~

~

Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U, including 1 ESF)

D, s 8

A, L, N, S 9

System I JPM Title

i. 201001 142.09 - Low CRD Scram Air Header Pressure - Unit 3 (Alternate Path - Place Standby Regulator In Service) [PLOR-316PA 12002 NRC]
j. 295031 EA1.05 - Defeat RClC Low Pressure Isolation - Unit 3

[ PLOR-086Pl Safety 1

I Function A, D, E, 1

D, E, R 2

p, R

k. 264000 A2.10 - Diesel Generator Air Start Solenoid Override

[ PLOR-049Pl

f.

D, E 6

  • Type Codes (A)lternate path Criteria for RO I SRO-I I SRO-U 4-6 I 4-6 I 2-3 (E)mergency or abnormal in-plant (L)ow-Power I Shutdown (N)ew or (M)odified from bank including 1 (A)

W C A (P)revious 2 exams (S) i m ulator (C)ontrol room (D)irect from bank

> I / 2 1 1 2 1

> I / 2 1 1 2 1

> 2 / 1 2 1 3 1

- >I/

2 1 1 3 1

< 3 15 3 I 5 2 (randomly selected)

< 9 / 5 8 1 5 4

i. 201001 A2.09 - Low CRD Scram Air Header Pressure - Unit 3 (Alternate Path - Place Standby Regulator In Service) [PLOR316PA 12002 NRC]

'hi A, D, E, 1

P, R ES-301 Control Room/ln-Plant Svstems Outline Form ES-301-2

k. 264000 A2.10 - Diesel Generator Air Start Solenoid Override

[PLOR-O49P]

Facility: Peach Bottom Exam Level: RO SRO-I 0 SRO-U D, E 6

Date of Examination: 21512007 Operating Test Number: 2007 NRC Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U, including 1 ESF)

System I JPM Title

a.
b. 295031 EA1.02 - Manually Initiate HPCl (Alternate Path - Manual Initiation Pushbutton Fails To Operate) [PLOR-300CA] - SET 2
c. 218000 A4.03 - ADS Reset Following Blowdown [PLOR-O23C 12005 NRCl-SET 3
d. 209001 A4.04 - Perform Core Spray B Pump Capacity Test For IST (Alternate Path - Minimum Flow Valve Fails To Open) [NEW] - SET 4
e.
f.
g.
h.

In-Plant Systems@ (3 for RO); (3 for SRO-I); (3 or 2 for SRO-U)

Type Code*

A, N, s ESF Safety Function 2

3 4

I.

I I

  • Type Codes I

Criteria for RO I SRO-I I SRO-U (A)lternate path (C)ontrol room (D)irect from bank (E)mergency or abnormal in-plant (L)ow-Power I Shutdown (N)ew or (M)odified from bank including 1 (A)

(P)revious 2 exams

R)CA
S)imulator 4-6 I 4-6 I 2-3 ES-301, Page 23 of 27

Scenario Outline ES-D-I Event No.

1 2

Simulation Facility Peach Bottom Scenario No.

Op Test No.

2007 NRC Malfunction Event Event No.

Type*

Description R

URO Power ascension with control rods CRS C

ALL Control rod drifts out TS Examiners Operators CRS (SRO)

URO (ATC)

PRO (BOP) 3 4

Scenario Summary The scenario begins with the reactor at approximately 5% power during a reactor startup. Following shift turnover, the crew should continue with the reactor startup, pulling control rods in accordance with the approved startup sequence. A control rod will drift out, requiring the crew to execute ON-I21 Drifting Control Rod and declare the affected control rod inoperable.

I I

TS CRS Inadvertent RClC initiation Following the control rod drift, the crew should secure drywell purge in preparation for inerting the drywell. Once drywell purge is secured, an inadvertent RClC initiation will occur, requiring the crew to perform a RClC shutdown and declare it inoperable. This event will be followed by a failure of the in-service CRD flow control valve, which will require the crew to enter ON-I 07 Loss of CRD Regulating Function and shift to the alternate flow control valve.

5 6

Next, a Recirc system leak will develop in the drywell requiring entry into OT-101 High Drywell Pressure. The crew should take actions for the rising drywell pressure and should manually scram the reactor and enter T-100 Scram. During the scram, seven rods will fail to insert resulting in an ATWS. When drywell pressure reaches 2 psig, the crew should enter T-101 RPV Control and T-102 Primary Containment Control. Multiple failures of drywell spray valves will prevent spraying the drywell, requiring the crew to perform T-I 12 Emergency Blowdown when drywell temperature cannot be restored and maintained below 281 degrees F. With several rods stuck out, the crew should terminate and prevent injection in accordance with T-240 prior to the emergency depressurization.

M ALL Recirculation system leak in the drywell C

URO I

CRS PRO Secure drywell purge I

CRS I CRD flow control valve failure 7

8 C

URO Seven rods stick full out during the scram CRS C

PRO Drywell spray valve failures - prevents drywell spray CRS

Scenario Outline ES-D-1 Simulation Facility Peach Bottom Scenario No.

  1. 2 Op Test No.

2007 NRC Event No.

I 2

Examiners Operators CRS (SRO)

Malfunction Event Event No.

Type*

Description R

URO Lower reactor power with reactor recirculation flow CRS N

PRO Secure a condensate pump C RS URO (ATC)

PRO (BOP) 3 4

Scenario Summary The scenario begins with the reactor at 41% power and a plant shutdown in progress. The crew will lower reactor power using reactor recirculation flow and at approximately 35% power the crew will secure a condensate pump. Following the condensate pump shutdown, MCC E-324-D-A will de-energize, resulting in loss of power to the E-3 diesel generator auxiliaries and an inoperable diesel generator.

TS C

URO Recirc RPT breaker trip TS CRS CRS Loss of MCC E324-D-A / E-3 diesel generator auxiliaries This will be followed by a trip of the B recirc pump due to a failed RPT breaker. The crew should carry out the actions of OT-I 12 UnexplainedlUnexpected Change in Core Flow, which includes consulting Technical Specifications. A loss of offsite power will occur next, requiring entry into SE-11 Loss of Off-Site Power. The crew should stabilize plant parameters using T-IO0 Scram and should recognize and respond to a failure of the HPCl flow controller to operate in automatic. The E-2 diesel generator output breaker will fail to automatically close, the E-4 diesel generator will fail to automatically start, and the E-3 diesel generator will not start at all. The crew should manually close the E-2 diesel generator output breaker and manually start the E-4 diesel generator using the quick-start pushbutton.

5 6

Following this event, a steam leak will develop in the drywell, requiring the crew to execute T-101 RPV Control and T-I 02 Primary Containment Control.

M ALL Loss of off-site power C

PRO E-2 diesel generator breaker fails to auto close CRS E-3 diesel generator fails to start (auto and manual)

E-4 diesel generator fails to auto start 8

M ALL Steam leak in the drywell 7

1 URO HPCl flow controller fails in automatic I I CRS I

Scenario Outline ES-D-1 Event No.

1 Simulation Facility Peach Bottom Scenario No.

  1. 3 Op Test No.

2007 NRC Examiners Operators CRS (SRO)

URO (ATC)

Ma Ifu n ction Event Event No.

Type*

Description N

TS breaker)

ALL Transfer RPS bus to alternate supply (failed trip coil on B RPS feeder PRO (BOP) 3 4

5 Scenario Summary The scenario begins with the reactor at 100% power. The 2B EHC Pump is blocked out of service for filter replacement. Following shift turnover, the crew should transfer RPS bus B to the alternate supply to facilitate repairs for a failed trip coil on the B RPS bus feeder breaker. The failed B RPS feeder breaker will already be inoperable when the crew takes the shift.

Following the RPS bus transfer, the RCIC 250 VDC bus will de-energize, rendering RClC inoperable and requiring a Tech Spec entry. Next, the running RBCCW pump will trip and the standby pump will fail to start, resulting in a complete loss of RBCCW. The crew should reduce RBCCW loads (e.g.

RWCU) and reactor power as directed by ON-I 13 Loss of RBCCW.

C URO Lossof RBCCW CRS R

URO Reduce reactor power CRS M

ALL ATWS (hydraulic)

The crew should perform a GP-4 manual scram due to the inability to restore RBCCW to the recirculation pump motors. An ATWS will occur requiring the crew to execute T-101 RPV Control and T-I 17 LeveVPower Control. Shortly after SLC is initiated the SLC pump will trip, requiring the URO to place the alternate SLC pump in service. A drywell vent valve will fail to isolate on low RPV level and the PRO should manually isolate the valve.

I PRO 1

CRS A failure of the only available EHC pump will cause the turbine to trip and the turbine bypass valves to close, requiring the crew to utilize SRVs for reactor pressure control. The crew should perform T-216 Control Rod Insertion By Manual Scram or Individual Scram Test Switches to bypass ARI and RPS, drain the scram discharge volume and initiate another scram.

Drywell vent valve (AO-2509) fails to isolate 8

2 1

I TS CRS I RClC 250 VDC bus failure C

PRO CRS A EHC pump trips I loss of turbine bypass valves URO Standby liquid control pump trips I

CRS 1

Scenario Outline ES-D-1 Simulation Facility Peach Bottom Scenario No.

84 Op Test No.

2007 NRC Exam i ners Operators CRS (SRO)

Event No.

1 2

URO (ATC)

Malfunction Event Event No.

Type*

Description N

PRO CRS Perform the main turbine master trip solenoid valves routine test TS CRS SBO line failure (TRM)

PRO (BOP) 6 7

8 Scenario Summary The scenario begins with the plant at 76% power and the B RHR pump blocked for motor replacement. Following turnover the crew will perform a main turbine master trip solenoid valves routine test. Following this test, the SBO line will fail, requiring a Tech Spec (TRM) entry. A loss of feedwater heaters will require the crew to respond to a positive reactivity addition and reduce reactor power to ensure thermal limits are not exceeded. The crew will then receive an RPS half scram due to a failed low vacuum pressure transmitter (blown fuse). This will require a Tech Spec entry.

Troubleshooting and repairs will be time-compressed, allowing the crew to reset the half scram.

I URO CRS PRO CRS isolate PRO CRS pressure control / depressurization Reactor mode switch failure (manual scram / ARI work)

C Group I failure to auto isolate I failure of the D MSL to manually C

Unable to restore drywell nitrogen / only ADS SRVs available for After RPS is reset, a steam leak will develop in the Turbine Building. As the steam leak grows in magnitude, the crew should recognize the need to shutdown the plant. During the manual scram, a reactor mode switch failure will require the crew to use the manual pushbuttons or Alternate Rod Insertion (ARI) to terminate the ATWS.

A failure of the Group I isolation will require a manual isolation but the D MSL will fail to isolate. The crew should enter T-I04 Radioactive Release to evaluate and control the release. The inability to restore instrument nitrogen to the SRVs will result in a loss of all non-ADS SRVs.

3 l

URO Loss of extraction steam to feedwater heaters I power reduction 1

CRS I URO Failure of a vacuum transmitter / RPS half scram & reset 1 TS CRS 1 S

I I M ALL I Steam leak in the turbine building