Text

OMB Control No.: 3150-0011 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, DC 20555 NRC GENERIC LETTER 2006-XX: POST-FIRE SAFE-SHUTDOWN CIRCUIT ANALYSIS SPURIOUS ACTUATIONS ADDRESSEES All holders of operating licenses for nuclear power reactors, except those who have permanently ceased operations and have certified that fuel has been permanently removed from the reactor vessel.

PURPOSE The U.S. Nuclear Regulatory Commission (NRC) is issuing this generic letter (GL) to:

(1) Request addressees to review their fire protection program to confirm compliance with applicable regulatory requirements regarding their interpretation of multiple spurious actuations caused by hot shorts, in light of the information provided in this GL and, if appropriate, take additional actions to return to compliance. Specifically, although some licensees have performed their post-fire safe-shutdown circuit analyses based on an assumption of only a single spurious actuation per fire event or that spurious actuations will occur with sufficient time between them for operators to take corrective actions, (commonly referred to by the NRC and industry as one-at-a-time) recent industry cable fire test results demonstrated that these assumptions are not valid.

(2) Require addressees to submit a written response to the NRC in accordance with NRC regulations in Title 10 of the Code of Federal Regulations (10 CFR), Section 50.54(f).

The reason for this request is to reaffirm the NRC position that multiple spurious actuations caused by hot shorts must be considered and evaluated per 10 CFR 50.48 and 10 CFR Part 50, Appendix A, General Design Criterion (GDC) 3. This position was confirmed by the results of the Electric Power Research Institute (EPRI)/Nuclear Energy Institute (NEI) cable fire tests, which showed a relatively high probability of multiple spurious actuations occurring simultaneously, or in rapid succession, during or after a fire (see EPRI Report No. 1006961, Spurious Actuation of Electrical Circuits Due to Cable Fires: Results of an Expert Elicitation, dated May 2002 and NUREG/CR-6776, Cable Insulation Resistance Measurements Made During Cable Fire Tests, dated June 2002). Some licensees have ML061280517 ENCLOSURE 1

GL 2006-XX Page 2 of 12 assumed a single spurious actuation per fire event, and others have assumed that multiple spurious actuations can only occur with sufficient time between actuations to allow for mitigation. The EPRI/NEI test data clearly show that the assumption that there is sufficient time between actuations to allow for mitigation between multiple spurious actuations is not appropriate. If licensees have not considered multiple spurious actuations occurring simultaneously or in rapid succession during or after a fire in their post-fire safe-shutdown circuit analysis, they may not be in compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3, which require that structures, systems, and components important to safety shall be designed and located to minimize, consistent with other safety requirements, the probability and effect of fires and explosions. Licensees who conclude that they are no longer in compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3, based on the information provided in this GL, should implement compensatory measures and inform the staff of their planned corrective actions to return to compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3.

BACKGROUND The regulatory requirements for post-fire safe shutdown are given in 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3. Additionally, all nuclear power plants (NPPs) licensed to operate before January 1, 1979, are required to comply with 10 CFR Part 50, Appendix R, Section III.G, Fire Protection of Safe Shutdown Capability. All NPPs licensed to operate after January 1, 1979, were evaluated against Section 9.5.1 of NUREG-0800, the Standard Review Plan. The fire protection plan (FPP) and the associated safety evaluation report (SER) are specifically incorporated into those plants licensing bases. All NPP licensees are responsible for meeting fire protection and license condition commitments made during the establishment of their fire protection program.

The objective of the fire protection requirements and guidance is to ensure that one train of systems necessary to achieve and maintain safe shutdown remains free of fire damage. To do so, licensees must protect circuits whose fire-induced failure could prevent the operation, or cause maloperation, of equipment necessary to achieve and maintain post-fire safe shutdown.

As part of its fire protection program, each licensee performs a circuit analysis to identify these circuits and to provide adequate protection against fire-induced failures.

Beginning in 1997, the NRC staff noticed that a series of licensee event reports (LERs) identified plant-specific problems related to potential fire-induced electrical circuit failures that could prevent operation, or cause maloperation, of equipment necessary to achieve and maintain safe shutdown. The staff documented these problems in Information Notice (IN) 99-17, Problems Associated With Post-Fire Safe-Shutdown Circuit Analyses. Based on the number of similar LERs, the NRC treated the issue generically. In 1998, the NRC staff started to interact with interested stakeholders in an attempt to understand the problem and develop an effective risk-informed solution to the circuit analysis issue. NRC also issued Enforcement Guidance Memorandum 98-002, Revision 2 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML003710123), to provide a process for treating inspection findings while the issues were being clarified. Because different stakeholders interpreted the regulations differently, the NRC decided to temporarily suspend the associated circuit part of fire protection inspections. This decision is documented in an NRC memorandum

GL 2006-XX Page 3 of 12 from John Hannon (Chief, Plant Systems Branch, Office of Nuclear Reactor Regulation (NRR))

to Gary Holahan (Director, Division of Safety Systems, NRR) dated November 29, 2000 (ADAMS Accession No. ML003773142).

In 2001, EPRI and NEI performed a series of cable functionality fire tests to further the nuclear industrys understanding of fire-induced circuit failures, particularly spurious equipment actuations initiated by hot shorts. EPRI coordinated this effort and issued the final report (EPRI Report No. 1006961). Additional analysis of the EPRI/NEI test results can be found in NUREG/CR-6776. Based on the test results, the NRC staff and NEI concluded that the probability of fire-induced circuit failures can be relatively high and that there can be a relatively high probability of multiple spurious actuations occurring simultaneously or in rapid succession.

DISCUSSION Although both the NRC and the industry have used the phrase one-at-a-time in connection with post-fire spurious actuations caused by hot shorts, it is not defined in 10 CFR Part 50 regulations or fire protection guidance documents. The phrase has been used in at least two different senses. Some licensees have used one-at-a-time to mean that only one spurious actuation need be postulated for any single fire event. Other licensees have used the phrase to mean that multiple spurious actuations do not occur simultaneously and that there is sufficient time between spurious actuations for operators to take corrective actions. NRC has issued SERs that accepted both interpretations for specific situations in specific plants (e.g.,

NUREG-0876, Supplement No. 6, Safety Evaluation Report Related to the Operation of Byron Station, Units 1 and 2, ADAMS Legacy Accession No. 8411200507). However, the NRC staff has interpreted the regulations to mean that these interpretations are only allowed with respect to the design of alternate shutdown capability. The EPRI/NEI cable fire testing conducted in 2001 demonstrated that neither interpretation conforms with the likely effects of a fire in an area containing safe-shutdown cables. Therefore, these interpretations do not ensure safe shutdown.

In the S. J. Collins (NRC) letter to R. E. Beedle (NEI) dated March 11, 1997 (ADAMS Accession No. ML003716454), the NRC reiterated its position that multiple spurious actuations caused by hot shorts must be considered and evaluated. Subsequent to the Collins letter, the 2001 EPRI/NEI fire testing demonstrated that multiple spurious actuations can occur with a relatively high probability and that they can occur simultaneously or in rapid succession without sufficient time for mitigation between actuations.

One of the key observations of the EPRI test report (EPRI Report No. 1006961) was that, given that a hot short occurs in a multi-conductor cable, it is highly probable (over 80 percent) that multiple target conductors will be affected (i.e., multiple simultaneous dependent hot shorts). The testing covered most of the types of cable insulation and jacketing materials and the types of raceways commonly used in nuclear power plants. During the testing, numerous variables were introduced to investigate the impact of various factors on cable performance and failure characteristics.

GL 2006-XX Page 4 of 12 While the staff has maintained that post-fire multiple spurious actuations should be considered, the number of actuations that must be considered has not been defined. Since the deterministic approach to post-fire safe-shutdown analyses assumes that all cables in a fire area are damaged by the fire except where protection described in 10 CFR 50, Appendix R, paragraph III.G.2 is provided (separation of cables with a 3-hour fire barrier, physical separation of cables of redundant trains by 20 feet, or separation of cables with a 1-hour fire barrier and fire suppression and detection), it follows that all possible spurious actuations, as well as the cumulative effect of the actuations, should be considered.

The SERs incorporated into the licensing bases of Byron Station, Units 1 and 2 and Braidwood Station, Units 1 and 2, specifically allow a design assumption of a single spurious actuation per fire event in the post-fire safe-shutdown circuit analysis. However, most plants postulated in their licensing basis that multiple spurious actuations occur with sufficient time between spurious actuations for operators to take corrective actions. All licensees should review their circuits analysis to verify that it assumes the possibility of simultaneous multiple spurious actuations during a fire. Depending on the results of this review, licensees may conclude that they are no longer in compliance with the fire protection regulations. Licensees who so determine should implement compensatory measures and inform the staff of their plan of corrective actions to return to compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3. One acceptable corrective action is to make plant modifications to protect against possible multiple spurious actuations. Another is to justify an exemption (or license amendment, as applicable) as described in the Methods of Compliance section of this GL.

The NEI letter of May 30, 1997, presents the industrys position on the phrase one-at-a-time.

The industrys position is that possible functional failure states from a single hot short in the components control circuitry should be analyzed one-at-a-time (not sequentially nor with cumulative consequences) for a fire in a certain fire area. As one basis for this position, the letter references the response to Question 5.3.10 in GL 86-10, Implementation of Fire Protection Requirements. Although this response states that the safe shutdown capability should not be adversely affected by any one spurious actuation or signal resulting from a fire in any plant area, per Question 5.3.10, the response applies only to Appendix R,Section III.L, Alternative and Dedicated Shutdown Capability. The NRC emphasized this position in an April 30, 1982, letter from Dennis M. Crutchfield (Chief, Operating Reactors Branch #5, Division of Licensing) to P. B. Fiedler (Vice President & Director, Oyster Creek) (ADAMS Accession No. ML011150521) by stating that it is essential to remember that these alternative requirements (i.e., III.G.3 and III.L) are not deemed to be equivalent to protection required by 10 CFR Part 50, Appendix R, paragraph III.G.2.

As noted in the attachment to a February 6, 1997, memorandum from L. B. Marsh (Chief, Plant Systems Branch, NRR) to J. F. Stolz (Director, Project Directorate I-2) regarding the NRC interpretation of the GL 86-10 guidance on spurious valve actuation, the reference to any one spurious actuation in the response to Question 5.3.10 is intended to provide a design basis for determining the capacity and capability of the alternative or dedicated shutdown train (e.g., the size of the pump and the support systems needed to maintain reactor coolant inventory, the scope of onsite electrical power distribution and power needs, and an operational baseline and set of plant conditions to define the scope of initial manual actions to restore systems

GL 2006-XX Page 5 of 12 necessary to accomplish the required reactor performance goals). Again, these alternative requirements do not provide the same level of protection as required by 10 CFR Part 50, Appendix R, paragraph III.G.2.

NEI also stated in the May 30, 1997, letter that any other interpretation leads to complex and costly analysis which is not justified for the very small safety benefit. The NEI letter offered no assessment of the safety significance of multiple sequential and cumulative failures. It is important to note that the NEI letter of May 30, 1997, preceded the 2001 EPRI/NEI fire testing.

As noted above, the cable functionality fire testing demonstrated that multiple spurious actuations can occur and that they can occur in rapid succession without sufficient time for mitigation. Therefore, if a licensee does not account for multiple spurious actuations in its circuits analysis, the licensee may not be in compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3, which require that a licensee provide and maintain free of fire damage one train of systems necessary to achieve and maintain safe shutdown.

A bounding analysis on the potential fire risk in terms of core damage frequency (ADAMS Accession No. ML060830212) indicates that, despite some likely conservative assumptions, multiple spurious actuations caused by hot shorts can be risk significant.

METHODS OF COMPLIANCE Based on the information provided in this GL, if a licensee concludes that it is no longer in compliance with the fire protection regulations, there are several acceptable methods to reestablish full regulatory compliance. One way is to reperform the post-fire safe-shutdown circuit analysis based on guidance provided in this GL and make the necessary modifications.

Another way to address this issue is to perform either a risk-informed evaluation that considers defense-in-depth and safety margins or a deterministic evaluation.

If a licensee proposes to use a risk-informed approach to justify an exemption or license amendment in accordance with 10 CFR 50.12, the licensee should follow the guidance of Regulatory Guide 1.174, An Approach for Using Probabilistic Risk Assessment in Risk-Informed Decisions on Plant-Specific Changes to the Licensing Basis.

Licensees who have adopted the standard fire protection license condition in GL 86-10 can make changes to the approved fire protection program without prior staff approval if the changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire. GL 86-10, Implementation of Fire Protection Requirements, provides guidance on performing and documenting these changes. Plants licensed after January 1, 1979, that use a risk-informed approach must submit a license amendment in accordance with 10 CFR 50.90.

The exception to 10 CFR 50.90, provided in the standard license condition and in 10 CFR 50.48(f)(3), does not apply because the risk assessment approaches used by these plants deviate from the approved deterministic approaches used in their licensing basis. Furthermore, the licensees risk assessment tools have not been reviewed or inspected against quality standards found acceptable to the NRC staff. Consequently, the staff believes that the use of risk informed approaches should receive prior NRC approval.

GL 2006-XX Page 6 of 12 An additional method to achieve compliance is the adoption of a performance-based fire protection program in accordance with 10 CFR 50.48(c), National Fire Protection Association Standard NFPA 805. Regulatory Guide 1.205, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants, dated September 2004 (ADAMS Accession No. ML042740308), and NEI 04-02, Guidance for Implementing a Risk-Informed, Performance-Based Fire Protection Program Under 10 CFR 50.48(c), Revision 0, dated March 2006 (ADAMS Accession No. ML060600183), provide additional guidance to licensees who plan to use this option.

APPLICABLE REGULATORY REQUIREMENTS NRC regulations in 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3, require each operating NPP (licensed before or after issuance of GDC 3) to have an FPP providing post-fire safe-shutdown capability. That is, a means must be provided of ensuring that one of the redundant trains of safe-shutdown structures, systems, and components is protected so that it remains free of fire damage, allowing safe shutdown of the plant. The regulation in 10 CFR 50.90 requires a licensee who desires to amend its license, to submit an amendment request to the NRC. An NPP licensed to operate before January 1, 1979, may submit an exemption request in accordance with 10 CFR 50.12.

All NPPs licensed to operate before January 1, 1979 (pre-1979 plants), are required to comply with 10 CFR Part 50, Appendix R, paragraph III.G, Fire Protection of Safe Shutdown Capability. Paragraph III.G states, in part, that one train of systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergency control station(s) is free of fire damage. Paragraph III.G.2 states, in part, that where cables or equipment, including associated non-safety circuits that could prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to ground, of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located within the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided. All NPPs licensed to operate after January 1, 1979, are required to comply with 10 CFR 50.48(a), which requires that each operating NPP have an FPP that satisfies GDC 3. The FPP is incorporated into the operating license for post-1979 plants as a license condition. This license condition specifically cites the staff SER in the licensees FPP to demonstrate that the license condition has been met (although licensees may modify their FPP as long as there is no adverse effect on safe shutdown).

Based on the regulations that state that cables or equipment that could prevent operation or cause maloperation of a safe shutdown train of equipment due to hot shorts, open circuits, or shorts to ground must be protected, and the new information provided by the EPRI/NEI cable fire tests, approved fire protection programs that do not include protection against possible simultaneous occurrence of multiple spurious actuations (including programs for plants with SERs that specifically approve the assumption of a single spurious actuation per fire event) may not comply with these regulatory requirements.

GL 2006-XX Page 7 of 12 APPLICABLE REGULATORY GUIDANCE Fire-induced hot shorts that cause spurious actuations can prevent a train of safe shutdown equipment from performing its post-fire safe-shutdown function. NRC regulations do not limit the number of spurious actuations that must be considered. In addition, NRC regulations do not state whether multiple spurious actuations should be assumed to occur simultaneously or sequentially. Licensees should adequately justify any limits or assumptions used in performing the post-fire safe-shutdown circuit analysis.

In order to demonstrate compliance with the regulatory requirement that one safe-shutdown train remain free of fire damage, licensees should analyze the potential for multiple, concurrent or in rapid succession spurious actuations and provide adequate protection where required.

Fire modeling techniques and risk analysis techniques which the staff has found acceptable are provided in Section 4.0 of Regulatory Guide 1.205, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants, dated March 2006 (ADAMS Accession No. ML060600183) and may be used in the evaluations.

The deterministic methodology in NEI 00-01, Rev. 1 (January 2005), Guidance for Post-Fire Safe Shutdown Circuit Analysis, Chapter 3 (including the associated appendices), for analysis of post-fire safe-shutdown circuits, in conjunction with the guidance provided in this GL, is one acceptable approach to achieving regulatory compliance with post-fire safe-shutdown circuit protection requirements for multiple spurious actuations. Licensees should assume that the fire may affect all unprotected cables and equipment within the fire area simultaneously and address all cable and equipment impacts affecting the required safe-shutdown path in the fire area. All potential impacts within the fire area should be addressed.

The risk significance analysis methodology provided in Chapter 4 of NEI 00-01 should not be applied as a basis for regulatory compliance except where a National Fire Protection Association (NFPA) 805 licensing basis has been adopted in accordance with 10 CFR 50.48(c) or it is used to support exemption and license amendment requests for plants that have not adopted an NFPA licensing basis. Furthermore, regardless of the plant licensing basis, the NRC agrees with the NEI 00-01 guidance that all failures deemed to be risk significant, whether they are clearly compliance issues or not, should be placed in the Corrective Action Program with an appropriate priority for action. The remaining sections of NEI 00-01 provide acceptable circuit analysis guidance on both the deterministic approach and the risk-informed, performance-based approach.

REQUESTED ACTIONS All addressees are requested to take the following actions:

(1) Within 90 days of the date of this letter, all addressees are requested to evaluate their licensing basis regarding multiple spurious post-fire safe-shutdown circuit analyses.

Specifically, they are requested to compare the plant licensing basis to the regulatory requirement for protecting redundant safe-shutdown trains from multiple simultaneous spurious actuations and maintaining one train free of fire damage.

GL 2006-XX Page 8 of 12 (2) Based on the plant licensing basis and the information provided in this GL, addressees should reach a conclusion, within 90 days of the date of this GL, on whether the NPP is in compliance with regulatory requirements.

(3) If addressees conclude that their plants are not in compliance with regulatory requirements, they should, in accordance with their FPP, implement compensatory actions and prepare corrective action plans. These addressees should make plans within 6 months of the date of this letter for plant modifications, license amendments, exemption requests, or other means to meet regulatory requirements and the plants licensing basis.

REQUESTED INFORMATION All addressees are requested to provide the following information:

(1) Within 90 days of the date of this GL submit a description of their licensing basis regarding multiple spurious post-fire safe-shutdown circuit analyses. Specifically, they should compare the plant licensing basis to the regulatory requirement for protecting redundant safe-shutdown trains from multiple simultaneous spurious actuations and maintaining one train free of fire damage.

(2) Within 90 days of the date of this GL submit a conclusion based on the plant licensing basis and the information provided in this GL as to whether the NPP is in compliance with regulatory requirements.

a. If addressees conclude their plants are not in compliance with regulatory requirements, they should submit an assessment of the functionality of affected structures, systems, and components that addresses the ability to achieve and maintain safe shutdown in light of multiple spurious hot shorts as a result of a fire. An assessment consistent with an evaluation performed for Regulatory Information Summary (RIS) 2005-20 will be acceptable.
b. Addressees that conclude they are not in compliance with regulatory requirements should also submit a description of the compensatory measures in place to maintain the safe-shutdown function of affected areas of the plant in accordance with the approved fire protection program.

(3) Within 6 months of the date of this GL, submit the plan to return each of the affected structures, systems, and components to compliance with regulatory requirements.

REQUIRED RESPONSE In accordance with 10 CFR 50.54(f), an addressee is required to respond as described below so that the NRC can determine whether a facility license should be modified, suspended, or revoked, or whether other action should be taken.

GL 2006-XX Page 9 of 12 Within 30 days of the date of this GL, an addressee is required to submit a written response if the addressee cannot provide the information or cannot meet the requested completion date.

The addressee must address in its response any alternative course of action that it proposes to take, including the basis for the acceptability of the proposed alternative course of action.

The required written responses should be addressed to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, 11555 Rockville Pike, Rockville, Maryland 20852, under oath or affirmation under the provisions of Section 182a of the Atomic Energy Act of 1954, as amended, and 10 CFR 50.54(f). In addition, a copy of the response should be submitted to the appropriate regional administrator.

REASON FOR INFORMATION REQUEST As discussed above, the NRC position has been that all multiple spurious actuations caused by hot shorts have to be considered in a post-fire safe-shutdown circuits analysis. The EPRI/NEI-performed cable fire testing in 2001 demonstrated that multiple spurious actuations can occur with relatively high likelihood and that they can occur simultaneously or in rapid succession without sufficient time for mitigation between actuations. Many licensees circuits analysis and/or safe-shutdown analysis did not consider this relatively high probability.

The NRC staff will review the responses to this GL and will notify affected addressees if concerns are identified regarding compliance with NRC regulations. The staff may also conduct inspections to determine addressees effectiveness in addressing the GL.

RELATED GENERIC COMMUNICATIONS GL 86-10, Implementation of Fire Protection Requirements, April 24, 1986.

GL 91-18, Rev. 1, Information to Licensees Regarding NRC Inspection Manual Section on Resolution of Degraded and Nonconforming Conditions, October 8, 1997.

IN 92-18, Potential for Loss of Remote Shutdown Capability During a Control Room Fire, February 28, 1992.

IN 99-17, Problems Associated With Post-Fire Safe-Shutdown Circuit Analyses, June 3, 1999.

RIS 2004-03, Risk-Informed Approach for Post-Fire Safe-Shutdown Associated Circuit Inspections, March 2, 2004.

RIS 2004-03, Rev. 1, Risk-Informed Approach for Post-Fire Safe Shutdown Circuit Inspections, December 29, 2004.

RIS 2005-030, Clarification of Post-Fire Safe-Shutdown Circuit Regulatory Requirements, December 20, 2005.

GL 2006-XX Page 10 of 12 BACKFIT DISCUSSION Under the provisions of Section 182a of the Atomic Energy Act of 1954, as amended, 10 CFR 50.109(a)(4)(i), and 10 CFR 50.54(f), this GL requests addressees to evaluate their facilities to confirm compliance with the existing applicable regulatory requirements as discussed in this GL. The NRC position has been that all multiple spurious actuations caused by hot shorts have to be considered in a post-fire safe-shutdown circuits analysis. Also, the 2001 EPRI/NEI fire test program demonstrated that the previous assumptions regarding spurious actuations do not adequately address the potential risk to safe shutdown. The EPRI/NEI cable fire tests clearly showed, during and after a fire, a relatively high probability that multiple spurious actuations will occur simultaneously or in rapid succession. Fire-induced hot shorts that cause spurious actuations can prevent a train from performing its post-fire safe-shutdown function. The regulations require that spurious actuations must be considered.

Although both the NRC and the industry have used the phrase one-at-a-time in connection with post-fire spurious actuations caused by hot shorts, it is not defined in 10 CFR Part 50 regulations or fire protection guidance documents. The phrase has been used in at least two different senses. Some licensees have used one-at-a-time to mean that only one spurious actuation need be postulated for any single fire event. Other licensees have used the phrase to mean that multiple spurious actuations do not occur simultaneously and that there is sufficient time between spurious actuations for operators to take corrective actions. NRC has issued SERs that accepted both interpretations for specific situations in specific plants (e.g., NUREG-0876, Supplement No. 6, Safety Evaluation Report Related to the Operation of Byron Station, Units 1 and 2, ADAMS Legacy Accession No. 8411200507). However, the NRC staff has interpreted the regulations to mean that these interpretations are only allowed with respect to the design of alternate shutdown capability. The EPRI/NEI cable fire testing conducted in 2001 demonstrated that neither interpretation conforms with the likely effects of a fire in an area containing safe-shutdown cables. Accordingly, the NRR staff's positions in this GL with respect to current fire protection requirements do not constitute backfitting as defined in 10 CFR 50.109(a)(1).

However, for Byron Station, Units 1 and 2 and Braidwood Station, Units 1 and 2, the staff positions with respect to one spurious actuation per fire represents a change in staff position, and if applied to the licensees of these plants, would constitute backfits under 10 CFR 50.109(a)(4)(i). As discussed in this GL, the imposition of the position with respect to multiple spurious actuations is necessary to comply with the (unchanged) staff interpretation of 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3. Staff approval of the single spurious actuation per fire event for Byron Station, Units 1 and 2 and Braidwood Station, Units 1 and 2 constituted staff inconsistencies with respect to the necessary prerequisites for demonstrating compliance with 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3. If necessary, the inconsistencies would be rectified by any backfitting imposed by the NRC in accordance with 10 CFR 50.109(a)(4)(i) and 10 CFR Part 50, Appendix A, GDC 3.

The NRC staff has determined, in accordance with 10 CFR 50.54(f), that the information sought in this GL is necessary to verify licensee compliance with existing regulatory requirements in 10 CFR 50.48 and 10 CFR Part 50, Appendix A, GDC 3.

GL 2006-XX Page 11 of 12 FEDERAL REGISTER NOTIFICATION A notice of opportunity for public comment on this GL was published in the Federal Register (FR) (70 FR 60859) on October 19, 2005. At the request of the industry, a notice that the public comment period for this GL was reopened was published in the Federal Register (70 FR 76083) on December 22, 2005.

SMALL BUSINESS REGULATORY ENFORCEMENT FAIRNESS ACT The NRC has determined that this action is subject to the Small Business Regulatory Enforcement Fairness Act of 1996. The Office of Management and Budget (OMB) has declared the letter not to be a major rule.

PAPERWORK REDUCTION ACT STATEMENT This GL contains information collections that are subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). These information collections were approved by OMB clearance no. 3150-0011, which expires on February 28, 2007.

The burden to the public for these mandatory information collections is estimated to average 709 hours0.00821 days <br />0.197 hours <br />0.00117 weeks <br />2.697745e-4 months <br /> per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the information collection. This burden does not include the hours that will be required to be expended by licensees to return to compliance with the regulations if they are determined to be not in compliance with the regulations. Send comments on any aspect of these information collections, including suggestions for reducing the burden, to the Records and Freedom of Information Act/Privacy Services Branch (T5-F52), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by Internet electronic mail to INFOCOLLECTS@NRC.GOV; and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202 (3150-0011), Office of Management and Budget, Washington, DC 20503.

Public Protection Notice The NRC may not conduct nor sponsor, and a person is not required to respond to, an information collection unless the requesting document displays a currently valid OMB control number.

GL 2006-XX Page 12 of 12 CONTACT Please direct any questions about this matter to the technical contact or the Lead Project Manager listed below or to the appropriate Office of Nuclear Reactor Regulation NRR project manager.

Christopher I. Grimes, Director Division of Policy and Rulemaking Office of Nuclear Reactor Regulation Technical

Contact:

Robert Wolfgang, NRR 301-415-1624 E-mail: rjw1@nrc.gov Lead Project Manager: Quynh Nguyen, NRR 301-415-8123 E-mail: qtn@nrc.gov Note: NRC generic communications may be found on the NRC public Web site, http://www.nrc.gov, under Electronic Reading Room/Document Collections.