Definitions 1.1 1.0 USE AND APPLICATION 1.1 Definitions


N O T E ------------------------------------------------

The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.

Term Definition ACTIONS ACTUATION LOGIC TEST AXIAL FLUX DIFFERENCE (AFD)

CHANNEL CALIBRATION ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.

An ACTUATION LOGIC TEST shall be the application of various simulated or actual input combinations in conjunction with each possible interlock logic state required for OPERABILITY of a logic circuit and the verification of the required logic output.

AFD shall be the difference in normalized flux signals between the top and bottom halves of a two section excore neutron detector.

A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel output such that it responds within the necessary range and accuracy to known values of the parameter that the channel monitors. The CHANNEL CALIBRATION shall encompass all devices in the channel required for channel OPERABILITY. Calibration of instrument channels with resistance temperature detector (RTD) or thermocouple sensors may consist of an inplace qualitative assessment of sensor behavior and normal calibration of the remaining adjustable devices in the channel. The CHANNEL CALIBRATION may be performed by means of any series of sequential, overlapping, or total channel steps.

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 1.1-1

Definitions 1.1 1.1 Definitions (continued)

CHANNEL CHECK CHANNEL OPERATIONAL TEST(COT)

CORE ALTERATION CORE OPERATING LIMITS REPORT (COLR)

DOSE EQUIVALENT 1-131 A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation. This determination shall include, wXhere possible, comparison of the channel indication and status to other indications or status derived from independent instrument channels measuring the same parameter.

A COT shall be the injection of a simulated or actual signal into the channel as close to the sensor output as practicable to verify OPERABILITY of all devices in the channel required for channel OPERABILITY. The COT shall include adjustments, as necessary, of the required alarm, interlock, and trip setpoints required for channel OPERABILITY such that the setpoints are within the necessary range and accuracy. The COT may be performed by means of any series of sequential, overlapping, or total channel steps.

CORE ALTERATION shall be the movement of any fuel, sources, or reactivity control components, within the reactor vessel with the vessel head removed and fuel in the vessel. Suspension of CORE ALTERATIONS shall not preclude completion of movement of a component to a safe position.

The COLR is the unit specific document that provides cycle specific parameter limits for the current reload cycle. These cycle specific parameter limits shall be determined for each reload cycle in accordance with Specification 5.6.5. Plant operation within these limits is addressed in individual Specifications.

DOSE EQUIVALENT 1-131 shall be that concentration of 1-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of l-131, 1-132, 1-133, 1-134, and 1-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table III of TID-14844, AEC, 1962, "Calculation of Distance Factors for Power and Test Reactor Sites".

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 1.1-2

Definitions 1.1

1..1 Definitions (continued)

E -AVERAGE DISINTEGRATION ENERGY LEAKAGE E shall be the average (weighted in proportion to the concentration of each radionuclide in the reactor coolant at the time of sampling) of the sum of the average beta and gamma energies per disintegration (in MeV) for isotopes, other than iodines, with half lives > 15 minutes, making up at least 95% of the total noniodine activity in the coolant.

LEAKAGE from the Reactor Coolant System (RCS) shall be:

a.

Identified LEAKAGE

1.

LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal water injection or leakoff), that is captured and conducted to collection systems or a sump or collecting tank;

2.

LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or

3.

RCS LEAKAGE through a steam generator (SG) to the Secondary System;

b.

Unidentified LEAKAGE All LEAKAGE (except RCP seal water injection or leakoff) that is not identified LEAKAGE;

c.

Pressure Boundary LEAKAGE LEAKAGE (except SG LEAKAGE) through a nonisolable fault in an RCS component body, pipe wall, or vessel wall.

Prairie Island Units 1 and 2 1.1-3 Unit I -Amendment No. 158 Unit 2 - Amendment No. 149

Definitions 1.1 1.1 Definitions (continued)

MASTER RELAY TEST MODE OPERABLE OPERABILITY PHYSICS TESTS A MASTER RELAY TEST shall consist of energizing all master relays in the channel required for channel OPERABILITY and verifying the OPERABILITY of each required master relay.

The MASTER RELAY TEST shall include a continuity check of each associated required slave relay. The MASTER RELAY TEST may be performed by means of any series of sequential, overlapping, or total steps.

A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor coolant temperature, and reactor vessel head closure bolt tensioning specified in Table 1.1-1 with fuel in the reactor vessel.

A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, normal or emergency electrical power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).

PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation. These tests are:

a.

Described in Appendix J of the USAR, Pre-Operational and Startup Tests;

b.

Authorized under the provisions of 10 CFR 50.59; or

c.

Otherwise approved by the Nuclear Regulatory Commission.

Prairie Island Units I and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 1.1-4

Definitions 1.1 1.1 Definitions (continued)

PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)

QUADRANT POWER TILT RATIO (QPTR)

RATED THERMAL POWER (RTP)

REACTOR TRIP SYSTEM (RTS)

RESPONSE

TIME The PTLR is the unit specific document that provides the reactor vessel pressure and temperature limits, including heatup and cooldo\\kn rates, and the OPPS arming temperature for the current reactor vessel fluence period. These pressure and temperature limits shall be determined for each fluence period in accordance with Specification 5.6.6. Plant operation within these operating limits is addressed in LCO 3.4.3, "RCS Pressure and Temperature (P/T)

Limits," LCO 3.4.12, "Low Temperature Overpressure Protection (LTOP) -Reactor Coolant System Cold Leg Temperature (RCSCLT)

> Safety Injection (SI) Pump Disable Temperature," and LCO 3.4.13, "Low Temperature Overpressure Protection (LTOP)

- Reactor Coolant System Cold Leg Temperature (RCSCLT)

Safety Injection (SI) Pump Disable Temperature."

QPTR shall be the ratio of the maximum upper excore detector calibrated output to the average of the upper excore detector calibrated outputs, or the ratio of the maximum lower excore detector calibrated output to the average of the lower excore detector calibrated outputs, whichever is greater.

RTP shall be a total reactor core heat transfer rate to the reactor coolant of 1650 MWt.

The RTS RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its RTS trip setpoint at the channel sensor output until opening of a reactor trip breaker. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured.

Prairie Island Units 1 and 2 Unit I -Amendment No. 158 Unit 2 - Amendment No. 149 1.1-5

Definitions 1.1 1.1 Definitions (continued)

SHUTDOWN MARGIN (SDM)

SLAVE RELAY TEST STAGGERED TEST BASIS SDM shall be the instantaneous amount of reactivity by which:

a.

The reactor is subcritical; or

b.

The reactor would be subcritical from its present condition assuming all rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity worth, which is assumed to be fully withdrawn. With any RCCA not capable of being fully inserted, the reactivity worth of the RCCA must be accounted for in the determination of SDM. In MODES 1 and 2, the fuel and moderator temperatures are changed to the nominal zero power design temperature.

A SLAVE RELAY TEST shall consist of energizing all slave relays in the channel required for channel OPERABILITY and verifying the OPERABILITY of each required slave relay. The SLAVE shall include a continuity check of associated required testable actuation devices. The SLAVE RELAY TEST may be performed by means of any series of sequential, overlappping, or total steps.

A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.

Prairie Island Units 1 and 2 1.1-6 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Definitions 1.1 1.1 Definitions (continued)

THERMAL POWER TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT)

THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

A TADOT shall consist of operating the trip actuating device and verifying the OPERABILITY of all devices in the channel required for trip actuating device OPERABILITY. The TADOT shall include adjustment, as necessary, of the trip actuating device so that it actuates at the required setpoint within the necessary accuracy. The TADOT may be performed by means of any series of sequential, overlapping, or total channel steps.

Prairie Island Units 1 and 2 1.1-7 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Definitions 1.1 Table 1.1-1 (page 1 of 1)

M CD F S MODE TITLE REACTIVITY 00 RATED AVERAGE CONDITION THERMAL REACTOR (kff)

POWER a, COOLANT TEMPERATURE (0F)

I Power Operation

> 0.99

> 5 NA 2

Startup

> 0.99

<5 NA 3

Hot Standby

< 0.99 NA

> 350 4

Hot Shutdown(b)

< 0.99 NA 350 > Tas > 200 5

Cold Shutdown~h)

< 0.99 NA

< 200 6

Refueling(c)

NA NA NA (a)

Excludirn decay heat.

(b)

All reactor vessel head closure bolts fully tensioned.

(c)

One or more reactor vessel head closure bolts less than fully tensioned.

Prairie Island Units I and 2 1.1-8 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

Logical Connectors 1.2 1.0 USE AND APPLICATION 1.2 Logical Connectors PURPOSE The purpose of this section is to explain the meaning of logical connectors.

Logical connectors are used in Technical Specifications (TS) to discriminate between, and yet connect, discrete Conditions, Required Actions, Completion Times, Surveillances, and Frequencies. The only logical connectors that appear in TS are AND and OR. The physical arrangement of these connectors constitutes logical conventions with specific meanings.

BACKGROUND Several levels of logic may be used to state Required Actions. These levels are identified by the placement (or nesting) of the logical connectors and by the number assigned to each Required Action.

The first level of logic is identified by the first digit of the number assigned to a Required Action and the placement of the logical connector in the first level of nesting (i.e., left justified with the number of the Required Action). The successive levels of logic are identified by additional digits of the Required Action number and by successive indentations of the logical connectors.

When logical connectors are used to state a Condition, Completion Time, Surveillance, or Frequency, only the first level of logic is used, and the logical connector is left justified with the statement of the Condition, Completion Time, Surveillance, or Frequency.

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 1.2-1

Logical Connectors 1.2 1.2 Logical Connectors (continued)

EXAMPLES The following examples illustrate the use of logical connectors.

EXAMPLE 1.2-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. LCOnotmet.

A.1 Verify...

AND A.2 Restore...

In this example the logical connector AND is used to indicate that when in Condition A, both Required Actions A. 1 and A.2 must be completed.

Prairie Island Units 1 and 2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149 1.2-2

Logical Connectors 1.2 1.2 Logical Connectors EXAMPLES (continued)

EXAMPLE 1.2-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

LCO not A. 1 Trip...

met.

OR A.2.1 Verify...

AND A.2.2.1 Reduce...

OR A.2.2.2 Perform...

OR A.3 Align...

This example represents a more complicated use of logical connectors. Required Actions A. 1, A.2, and A.3 are alternative choices, only one of which must be performed as indicated by the use of the logical connector OR and the left justified placement.

Any one of these three Actions may be chosen. If A.2 is chosen, then both A.2.1 and A.2.2 must be performed as indicated by the logical connector AND. Required Action A.2.2 is met by performing A.2.2.1 or A.2.2.2. The indented position of the logical connector OR indicates that A.2.2.1 and A.2.2.2 are alternative choices, only one of which must be performed.

Prairie Island Units I and 2 1.2-3 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.0 USE AND APPLICATION 1.3 Completion Times PURPOSE BACKGROUND DESCRIPTION The purpose of this section is to establish the Completion Time convention and to provide guidance for its use.

Limiting Conditions for Operation (LCOs) specify minimum requirements for ensuring safe operation of the unit. The ACTIONS associated with an LCO state Conditions that typically describe the ways in which the requirements of the LCO can fail to be met.

Specified with each stated Condition are Required Action(s) and Completion Time(s).

The Completion Time is the amount of time allowed for completing a Required Action. It is referenced to the time of discovery of a situation (e.g., inoperable equipment or variable not within limits) that requires entering an ACTIONS Condition unless otherwise specified, providing the unit is in a MODE or specified condition stated in the Applicability of the LCO. Required Actions must be completed prior to the expiration of the specified Completion Time.

An ACTIONS Condition remains in effect and the Required Actions apply until the Condition no longer exists or the unit is not within the LCO Applicability.

If situations are discovered that require entry into more than one Condition at a time within a single LCO (multiple Conditions), the Required Actions for each Condition must be performed within the associated Completion Time. When in multiple Conditions, separate Completion Times are tracked for each Condition starting from the time of discovery of the situation that required entry into the Condition.

Once a Condition has been entered, subsequent trains, subsystems, components, or variables expressed in the Condition, discovered to be inoperable or not within limits, will not result in separate entry Prairie Island Units I and 2 1.3-1 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times DESCRIPTION into the Condition, unless specifically stated. The Required Actions (continued) of the Condition continue to apply to each additional failure, with Completion Times based on initial entry into the Condition.

However, when a subsequent train, subsystem, component, or variable expressed in the Condition is discovered to be inoperable or not within limits, the Completion Time(s) may be extended. The Completion Time extension cannot be used to extend the stated Completion Time for the first inoperable train, subsystem, component, or variable. To apply this Completion Time extension, two criteria must first be met. The subsequent inoperability:

a.

Must exist concurrent with the first inoperability; and

b.

Must remain inoperable or not within limits after the first inoperability is resolved.

The total Completion Time allowed for completing a Required Action to address the subsequent inoperability shall be limited to the more restrictive of either:

a.

The stated Completion Time, as measured from the initial entry into the Condition, plus an additional 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; or

b.

The stated Completion Time as measured from discovery of the subsequent inoperability.

The above Completion Time extensions do not apply to those Specifications that have exceptions that allow completely separate re-entry into the Condition (for each train, subsystem, component, or variable expressed in the Condition) and separate tracking of Completion Times based on this re-entry. These exceptions are stated in individual Specifications.

Prainre Island Unit 1 - Amendment No. 158 Units l and 2 1.3-2 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times DESCRIPTION (continued)

The above Completion Time extension does not apply to a Completion Time with a modified "time zero." This modified "time zero" may be expressed as a repetitive time (i.e., "once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />,"

where the Completion Time is referenced from a previous completion of the Required Action versus the time of Condition entry) or as a time modified by the phrase "from discovery...

Example 1.3-3 illustrates one use of this type of Completion Time.

The 10 day Completion Time specified for Conditions A and B in Example 1.3-3 may not be extended. An example of a modified "time zero" with the Completion Time expressed as "once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />" is illustrated in Example 1.3-6, Condition A. In this example, the Completion Time may not be extended.

Prairie Island Units 1 and 2 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149 1.3-3

Completion Times 1.3 1.3 Completion Times (continued)

EXAMPLES The following examples illustrate the use of Completion Times with different types of Conditions and changing Conditions.

EXAMPLE 1.3-1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Required B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated AND Completion Time not met.

B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> Condition B has two Required Actions. Each Required Action has its own separate Cmpletion Time. Each Completion Time is referenced to the time that Condition B is entered.

The Required Actions of Condition B are to be in MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND in MODE 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. A total of 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> is allowed for reaching MODE 3 and a total of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> (not 42 hours4.861111e-4 days <br />0.0117 hours <br />6.944444e-5 weeks <br />1.5981e-5 months <br />) is allowed for reaching MODE 5 from the time that Condition B was entered. If MODE 3 is reached within 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />, the time allowed for reaching MODE 5 is the next 33 hours3.819444e-4 days <br />0.00917 hours <br />5.456349e-5 weeks <br />1.25565e-5 months <br /> because the total time allowed for reaching MODE 5 is 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

If Condition B is entered while in MODE 3, the time allowed for reaching MODE 5 is the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Prairie Island Units 1 and 2 1.3-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXAMPLE 1.3-2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One train A.l Restore train to 7 days inoperable.

OPERABLE status.

B. Required B.l Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated AND Completion Time not met.

B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> When a train is declared inoperable, Condition A is entered. If the train is not restored to OPERABLE status within 7 days, Condition B is also entered and the Completion Time clocks for Required Actions B. 1 and B.2 start. If the inoperable train is restored to OPERABLE status after Condition B is entered, Condition A and B are exited, and therefore, the Required Actions of Condition B may be terminated.

When a second train is declared inoperable while the first train is still inoperable, Condition A is not re-entered for the second train.

LCO 3.0.3 is entered, since the ACTIONS do not include a Condition for more than one inoperable train. The Completion Time clock for Condition A does not stop after LCO 3.0.3 is entered, but continues to be tracked from the time Condition A was initially entered.

Prairie Island Units 1 and 2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149 1.3-5

Completion Times 1.3 1.3 Completion Times EXAMPLES EXAMPLE 1.3-2 (continued)

\\Vhile in LCO 3.0.3, if either of the inoperable trains is restored to OPERABLE status and the Completion Time for Condition A has not expired, LCO 3.0.3 may be exited and operation continued in accordance with Condition A.

While in LCO 3.0.3, if either of the inoperable trains is restored to OPERABLE status and the Completion Time for Condition A has expired, LCO 3.0.3 may be exited and operation continued in accordance with Condition B. The Completion Time for Condition B is tracked from the time the Condition A Completion Time expired.

Upon restoring either of the trains to OPERABLE status, the Condition A Completion Time is not reset, but continues from the time the first train was declared inoperable. This Completion Time may be extended if the train restored to OPERABLE status was the first inoperable train. A 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> extension to the stated 7 days is alloýx ed, provided this does not result in the second train being inoperable for > 7 days.

Prairie Island Units I and 2 1.3-6 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXA\\

I H-E 1.3-3 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One A.1 Restore Function X 7 days Function X train to train OPERABLE status.

AND inoperable.

10 days from discovery of failure to meet the LCO B. One B.1 Restore Function Y 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Function Y train to train OPERABLE status.

AND inoperable.

10 days from discovery of failure to meet the LCO Prairie Island Units I and 2 1.3-7 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXA MPI,S EXAMPLE 1.3-3 (continued)

ACTIONS C. One Function X train inoperable.

AND One Function Y train inoperable.

C.1 Restore Function X train to OPERABLE status.

OR C.2 Restore Function Y train to OPERABLE status.

When one Function X train and one Function Y train are inoperable, Condition A and Condition B are concurrently applicable. The Completion Times for Condition A and Condition B are tracked separately for each train starting from the time each train was declared inoperable and the Condition was entered. A separate Completion Time is established for Condition C and tracked from the time the second train was declared inoperable (i.e., the time the situation described in Condition C was discovered).

If Required Action C.2 is completed within the specified Completion Time, Conditions B and C are exited. If the Completion Time for Required Action A. 1 has not expired, operation may continue in accordance with Condition A. The remaining Completion Time in Condition A is measured from the time the affected train was declared inoperable (i.e., initial entry into Condition A).

Prairie Island Units I and 2 1.3-8 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> 72 hours

Completion Times 1.3 1.3 Completion Times EXAMPLES EXA.IPLFI 1.3-3 (continued)

The Completion Times of Conditions A and B are modified by a logical connector wvith a separate 10 day Completion Time measured from the time it \\was discovered the LCO was not met. In this example, without the separate Completion Time, it would be possible to alternate between Conditions A, B, and C in such a manner that operation could continue indefinitely without ever restoring systems to meet the LCO. The separate Completion Time modified by the phrase "from discovery of failure to meet the LCO" is designed to prevent indefinite continued operation while not meeting the LCO.

This Completion Time allows for an exception to the normal "time zero" for beginning the Completion Time "clock". In this instance, the Completion Time "time zero" is specified as commencing at the time the LCO was initially not met, instead of at the time the associated Condition was entered.

Prairie Island Units I and 2 Unit I Unit 2 1.3-9 Amendment No. 158 Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXAMPLE 1.3-4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more A. I Restore valve(s) to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> valves OPERABLE inoperable, status.

B.

Required B.I Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated AND Completion Time not B.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> met.

A single Completion Time is used for any number of valves inoperable at the same time. The Completion Time associated with Condition A is based on the initial entry into Condition A and is not tracked on a per valve basis. Declaring subsequent valves inoperable, while Condition A is still in effect, does not trigger the tracking of separate Completion Times.

Once one of the valves has been restored to OPERABLE status, the Condition A Completion Time is not reset, but continues from the time the first valve was declared inoperable. The Completion Time may be extended if the valve restored to OPERABLE status was the first inoperable valve. The Condition A Completion Time may be extended for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> provided this does not result in any subsequent valve being inoperable for > 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

Prairie Island Units I and 2 1.3-10 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXAMPLE 1.3-5 If the Completion Time of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> (plus the extension) expires while one or more valves are still inoperable, Condition B is entered.

ACTIONS


N OTE ------------------------------------

Separate Condition entry is allowed for each inoperable valve.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more A. 1 Restore valve to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> valves OPERABLE inoperable, status.

B.

Required B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated AND Completion Time not B.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> met.

The Note above the ACTIONS Table is a method of modifying how the Completion Time is tracked. If this method of modifying how the Completion Time is tracked was applicable only to a specific Condition, the Note would appear in that Condition rather than at the top of the ACTIONS Table.

Prairie Island Units I and 2 1.3-11 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Completion Times 1.3 1.3 Compl-etion Times EXAMPLES EXAMPLE 1.3-5 (continued)

The Note allows Condition A to be entered separately for each inoperable valve, and Completion Times tracked on a per valve basis. When a valve is declared inoperable, Condition A is entered and its Completion Time starts. If subsequent valves are declared inoperable, Condition A is entered for each valve and separate Completion Times start and are tracked for each valve.

If the Completion Time associated \\vith a valve in Condition A expires, Condition B is entered for that valve. If the Completion Times associated wvith subsequent valves in Condition A expire, Condition B is entered separately for each valve and separate Completion Times start and are tracked for each valve. If a valve that caused entry into Condition B is restored to OPERABLE status, Condition B is exited for that val e.

Since the Note in this example allows multiple Condition entry and tracking of separate Completion Times, Completion Time extensions do not apply.

Prairie Island Units 1 and 2 1.3-12 Unit I Unit 2 Amendment No. 158 Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXAMPLE 1.3-6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIMNVIE A. One channel A. 1 Perform Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> inoperable.

SR 3.x.x.x.

OR A.2 Reduce 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> THERMAL POWER to

< 50% RTP.

B. Required B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated Completion Time not met.

Entry into Condition A offers a choice between Required Action A. 1 or A.2. Required Action A. 1 has a "once per" Completion Time, which qualifies for the 25% extension, per SR 3.0.2, to each performance after the initial performance. The initial 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval of Required Action A. I begins when Condition A is entered and the initial performance of Required Action A. 1 must be complete within the first 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval. If Required Action A. 1 is followed, and the Required Action is not met within the Completion Time (plus the extension allowed by SR 3.0.2), Condition B is entered. If Required Prairie Island Units 1 and 2 1.3-13 Unit I Unit 2 Amendment No. 158 Amendment No. 149

(ompletion Times 1.3 1.3 Completion Times EXAMPLES EXAMPLE 1.3-6 (continued)

Action A.2 is followed and the Completion Time of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> is not met, Condition B is entered.

If after entry into Condition B, Required Action A. 1 or A.2 is met, Condition B is exited and operation may then continue in Condition A.

Prairie Island Units 1 and 2 1.3-14 Unit 1 Unit 2 Amendment No. 158 Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES (continued)

EXAMPLE 1.3-7 ACTIONS CONDI ITION REQUIRED ACTION CIOMPLETION TIME A.

One A. 1 Verify affected 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> subsystem subsystem isolated.

inoperable.

AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND A.2 Restore subsystem 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to OPERABLE status.

B.

Required B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action and associated AND Completion Time not B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> met.

Required Action A.1 has two Completion Times. The 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Completion Time begins at the time the Condition is entered and each "Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter" interval begins upon performance of Required Action A. 1.

Prairie Island Units 1 and 2 1.3-15 Unit 1 -Amendment No. 158 Unit 2 Amendment No. 149

Completion Times 1.3 1.3 Completion Times EXAMPLES EXAMIPLE 1.3-7 (continued)

If after Condition A is entered, Required Action A. I is not met

\\within either the initial 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or any subsequent 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> interval from the previous performance (plus the extension allowed by SR 3.0.2),

Condition B is entered. The Completion Time clock for Condition A does not stop after Condition B is entered, but continues from the time Condition A was initially entered. If Required Action A. I is met after Condition B is entered, Condition B is exited and operation may continue in accordance with Condition A, provided the Completion Time for Required Action A.2 has not expired.

IMMEDIATE COMPLETION TIME When -'Immediately" is used as a Completion Time. the Required Action should be pursued without delay and in a controlled manner.

Prairie Island Units 1 and 2 1.3-16 Unit I -Amendment No. 158 Unit 2 - Amendment No. 149

Frequency 1.4 1.0 USE AND APPLICATION 1.4 FreCIuencv PURPOSE DESCRIPTION The purpose of this section is to define the proper use and application of Frequency requirements.

Each Surveillance Requirement (SR) has a specified Frequency in which the Surveillance must be met in order to meet the associated LCO. An understanding of the correct application of the specified Frequency is necessary for compliance with the SR.

The "specified Frequency" is referred to throughout this section and each of the Specifications of Section 3.0, Surveillance Requirement (SR) Applicability. The "specified Frequency" consists of the requirements of the Frequency column of each SR as well as certain Notes in the Surveillance column that modify performance requirements.

Sometimes special situations dictate when the requirements of a Surveillance are to be met. They are "otherwise stated" conditions allowed by SR 3.0.1. They may be stated as clarifying Notes in the Surveillance, as part of the Surveillance, or both.

Situations where a Surveillance could be required (i.e., its Frequency could expire), but where it is not possible or not desired that it be performed until sometime after the associated LCO is within its Applicability, represent potential SR 3.0.4 conflicts. To avoid these conflicts, the SR (i.e., the Surveillance or the Frequency) is stated such that it is only "required" when it can be and should be performed. With an SR satisfied, SR 3.0.4 imposes no restriction.

The use of "met" or "performed" in these instances conveys specific meanings. A Surveillance is "met" only when the acceptance criteria are satisfied. Known failure of the requirements of a Surveillance, Prairie Island Units I and 2 1.4-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 1.4

Frequency 1.4 1.4 Frequency DESCRIPTION (continued)

EXAMPLES even wvithout a Surveillance specifically being "performed,"

constitutes a Surveillance not "met." "Performance" refers only to the requirement to specifically determine the ability to meet the acceptance criteria.

Some Surveillances contain notes that modify the Frequency of performance or the conditions during which the acceptance criteria must be satisfied. For these Surveillances, the MODE-entry restrictions of SR 3.0.4 may not apply. Such a Surveillance is not required to be performed prior to entering a MODE or other specified condition in the Applicability of the associated LCO if any of the following three conditions are satisfied:

a.

The Surveillance is not required to be met in the MODE or other specified condition to be entered; or

b.

The Surveillance is required to be met in the MODE or other specified condition to be entered, but has been performed within the specified Frequency (i.e., it is current) and is known not to be failed; or

c.

The Surveillance is required to be met, but not performed, in the MODE or other specified condition to be entered, and is known not to be failed.

Examples 1.4-3, 1.4-4, 1.4-5, and 1.4-6 discuss these special situations.

The following examples illustrate the various ways that Frequencies are specified. In these examples, the Applicability of the LCO (LCO not shown) is MODES 1, 2, and 3.

Prairie Island Units I and 2 1.4-2 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

Frequency 1.4 1.4 Frequency EXAMPLES EXAMPLE 1.4-1 (continued)

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Example 1.4-1 contains the type of SR most often encountered in the Technical Specifications (TS). The Frequency specifies an interval (12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />) during which the associated Surveillance must be performed at least one time. Performance of the Surveillance initiates the subsequent interval. Although the Frequency is stated as 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, an extension of the time interval to 1.25 times the stated Frequency is allowed by SR 3.0.2 for operational flexibility. The measurement of this interval continues at all times, even when the SR is not required to be met per SR 3.0.1 (such as when the equipment is inoperable, a variable is outside specified limits, or the unit is outside the Applicability of the LCO). If the interval specified by SR 3.0.2 is exceeded while the unit is in a MODE or other specified condition in the Applicability of the LCO, and the performance of the Surveillance is not otherwise modified (refer to Example 1.4-3), then SR 3.0.3 becomes applicable.

If the interval as specified by SR 3.0.2 is exceeded while the unit is not in a MODE or other specified condition in the Applicability of the LCO for which performance of the SR is required, the Surveillance must be performed within the Frequency requirements of SR 3.0.2 prior to entry into the MODE or other specified condition. Failure to do so would result in a violation of SR 3.0.4.

Prairie Island Unit 1 - Amendment No. 158 Units 1 and 2 1.4-3 Unit 2 - Amendment No. 149

Frequency 1.4 1.4 Frequency EXAMPLES (continued)

EXAMPLE 1.4-2 SURVEILLANCE REQUIREMENTS SURVEILLANCE Verify flow is within limits.

F FREQUENCY Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after

_> 25% RTP AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter I ______________________________

Example 1.4-2 has two Frequencies. The first is a one time performance Frequency, and the second is of the type shown in Example 1.4-1. The logical connector "AND" indicates that both Frequency requirements must be met. Each time reactor power is increased from a power level < 25% RTP to > 25% RTP, the Surveillance must be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

The use of "once" indicates a single performance will satisfy the specified Frequency (assuming no other Frequencies are connected by "'AND"). This type of Frequency does not qualify for the 25%

extension allowed by SR 3.0.2. "Thereafter" indicates future performances must be established per SR 3.0.2, but only after a specified condition is first met (i.e., the "once" performance in this example). If reactor power decreases to < 25% RTP, the measurement of both intervals stops. New intervals start upon reactor power reaching 25% RTP.

Prairie Island Units 1 and 2 1.4-4 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149 11 i

Frequtenc y 1.4 1.4 Frequency EXANIPLES (continued)

EXANIPLE 1.4-3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY NOTE Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after _> 25% RTP.

Perform channel adjustment.

7 days The interval continues, whether or not the unit operation is

< 250o RTP between performances.

As the Note modifies the required performance of the Surveillance, it is construed to be part of the "specified Frequency." Should the 7 day interval be exceeded while operation is < 25% RTP, this Note allows 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after power reaches _> 25% RTP to perform the Surveillance. The Surveillance is still considered to be performed within the "specified Frequency." Therefore, if the Surveillance were not performed within the 7 day (plus the extension allowed by SR 3.0.2) interval, but operation was < 25% RTP, it would not constitute a failure of the SR or failure to meet the LCO. Also, no violation of SR 3.0.4 occurs when changing MODES, even with the 7 day Frequency not met, provided operation does not exceed 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> with power > 25% RTP.

Once the unit reaches 25% RTP, 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> would be allowed for completing the Surveillance. If the Surveillance were not performed within this 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> interval, there would then be a failure to perform a Surveillance within the specified Frequency, and the provisions of SR 3.0.3 would apply.

Prairie Island Units 1 and 2 Unit 1 Unit 2 1.4-5 Amendment No. 158 Amendment No. 149

Frequency 1.4 1.4 Freqluency EXAMPLES (continued)

EXAMPLE 1.4-4 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY NOTE Only required to be met in MODE 1.

Verify leakage rates are within limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Example 1.4-4 specifies that the requirements of this Surveillance do not have to be met until the unit is in MODE 1. The interval measurement for the Frequency of this Surveillance continues at all times, as described in Example 1.4-1. However, the Note constitutes an "'otherwise stated" exception to the Applicability of this Surveillance. Therefore, if the Surveillance were not performed within the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> interval (plus the extension allowed by SR 3.0.2),

but the unit was not in MODE 1, there would be no failure of the SR nor failure to meet the LCO. Therefore, no violation of SR 3.0.4 occurs wxhen changing MODES, even with the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Frequency exceeded, provided the MODE change was not made into MODE 1.

Prior to entering MODE I (assuming again that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Frequency were not met), SR 3.0.4 would require satisfying the SR.

Prairie Island Units I and 2 Unit 1 Unit 2 1.4-6 Amendment No. 158 Amendment No. 149

Frequency 1.4 1.4 Frequency EXAMPLES EXAMPLE 1.4-5 (continued)

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY NOTE--------------

Only required to be performed in MODE 1.

Perform complete cycle of the valve.

7 days The interval continues, whether or not the unit operation is in MODE 1.2, or 3 (the assumed Applicability of the associated LCO) between performances.

As the Note modifies the required performance of the Surveillance, the Note is construed to be part of the "specified Frequency."

Should the 7 day interval be exceeded while operation is not in MODE 1, this Note allows entry into and operation in MODES 2 and 3 to perform the Surveillance. The Surveillance is still considered to be performed within the "specified Frequency" if completed prior to entering MODE 1. Therefore, if the Surveillance were not performed within the 7 day (plus the extension allowed by SR 3.0.2) interval, but operation was not in MODE 1, it would not constitute a failure of the SR or failure to meet the LCO. Also, no violation of SR 3.0.4 occurs when changing MODES, even with the 7 day Frequency not met, provided operation does not result in entry into MODE 1.

Once the unit reaches MODE 1, the requirement for the Surveillance to be performed within its specified Frequency applies and would require that the Surveillance had been performed. If the Surveillance were not performed prior to entering MODE 1, there would then be a Prairie Island Unit 1 - Amendment No. 158 Units I and 2 1.4-7 Unit 2 - Amendment No. 149

Frequency 1.4 1.4 Frequency EXAMPLES EXAMPLE 1.4-5 (continued) failure to perform a Surveillance within the specified Frequency, and the provisions of SR 3.0.3 would apply.

EXAMPLE 1.4-6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY NOTE Not required to be met in MODE 3.

Verify parameter is within limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Example 1.4-6 specifies that the requirements of this Surveillance do not have to be met while the unit is in MODE 3 (the assumed Applicability of the associated LCO is MODES 1,2, and 3). The interval measurement for the Frequency of this Surveillance continues at all times, as described in Example 1.4-1. However, the Note constitutes an "otherwvIse stated" exception to the Applicability of this Surveillance. Therefore, if the Surveillance were not performed within the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> interval (plus the extension allowed by SR 3.0.2), and the unit was in MODE 3, there would be no failure of the SR nor failure to meet the LCO. Therefore, no violation of SR 3.0.4 occurs when changing MODES to enter MODE 3, even with the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Frequency exceeded, provided the MODE change does not result in entry into MODE 2. Prior to entering MODE 2 (assuming again that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Frequency were not met), SR 3.0.4 would require satisfying the SR.

Prairie Island Units 1 and 2 Unit 1 Unit 2 1.4-8 Amendment No. 158 Amendment No. 149

SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs In MODES 1 and 2, the combination of THERMAL POWER, Reactor Coolant System (RCS) highest loop average temperature, and pressurizer pressure shall not exceed the SLs specified in Figure 2.1.1-1.

2.1.2 RCS Pressure SL In MODES 1,2, 3, 4, and 5, the RCS pressure shall be maintained

  • 5 2735 psig.

2.2 SL Violations 2.2.1 If SL 2.1.1 is violated, restore compliance and be in MODE 3 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

2.2.2 If SL 2.1.2 is violated:

2.2.2.1 In MODE I or 2, restore compliance and be in MODE 3 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

2.2.2.2 In MODE 3, 4, or 5, restore compliance within 5 minutes.

Prairie Island Units 1 and 2 2.0-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

0 10 20 30 40 50 60 70 80 delta-T (Th-T,) OF Figure 2.1.1-1 (page 1 of 1)

Reactor Core Safety Limits Prairie Island Units 1 and 2 2.0-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 SLs 2.0 660 650 640 630 620 610 600 590 580 To CU L..

E

,H 570 560 550 540

LCO Applicability 3.0 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY LCO 3.0.1 LCO 3.0.2 LCO 3.0.3 LCOs shall be met during the MODES or other specified conditions in the Applicability, except as provided in LCO 3.0.2 and 3.0.7.

Upon discovery of a failure to meet an LCO, the Required Actions of the associated Conditions shall be met, except as provided in LCO 3.0.5, LCO 3.0.6 and LCO 3.0.8.

If the LCO is met or is no longer applicable prior to expiration of the specified Completion Time(s), completion of the Required Action(s) is not required unless otherwise stated.

When an LCO is not met and the associated ACTIONS are not met, an associated ACTION is not provided, or if directed by the associated ACTIONS, the unit shall be placed in a MODE or other specified condition in which the LCO is not applicable. Action shall be initiated within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to place the unit, as applicable, in:

a.

MODE 3 within 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />;

b.

MODE 4 within 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />; and

c.

MODE 5 within 37 hours4.282407e-4 days <br />0.0103 hours <br />6.117725e-5 weeks <br />1.40785e-5 months <br />.

Exceptions to this Specification are stated in the individual Specifications.

Where corrective measures are completed that permit operation in accordance with the LCO or ACTIONS, completion of the actions required by LCO 3.0.3 is not required.

LCO 3.0.3 is only applicable in MODES 1, 2, 3, and 4.

Prairie Island Units 1 and 2 3.0-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

LCO Applicability 3.0 3.0 LCO APPLICABILITY (continued)

LCO 3.0.4 LCO 3.0.5 LCO 3.0.6 When an LCO is not met, entry into a MODE or other specified condition in the Applicability shall not be made except when the associated ACTIONS to be entered permit continued operation in the MODE or other specified condition in the Applicability for an unlimited period of time. This Specification shall not prevent changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.

Exceptions to this Specification are stated in the individual Specifications.

LCO 3.0.4 is only applicable for entry into a MODE or other specified condition in the Applicability in MODES 1, 2, 3, and 4.

Equipment removed from service or declared inoperable to comply with ACTIONS may be returned to service under administrative control solely to perform testing required to demonstrate its OPERABILITY or the OPERABILITY of other equipment. This is an exception to LCO 3.0.2 for the system returned to service under administrative control to perform the testing required to demonstrate OPERABILITY.

When a supported system LCO is not met solely due to a support system LCO not being met, the Conditions and Required Actions associated with this supported system are not required to be entered.

Only the support system LCO ACTIONS are required to be entered.

This is an exception to LCO 3.0.2 for the supported system. In this event, an evaluation shall be performed in accordance with Specification 5.5.13, "Safety Function Determination Program (SFDP)." If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

Prairie Island Units I and 2 3.0-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

LCO Applicability 3.0 3.0 LCO APPLICABILITY LCO 3.0.6 (continued)

LCO 3.0.7 LCO 3.0.8 When a support system's Required Action directs a supported system to be declared inoperable or directs entry into Conditions and Required Actions for a supported system, the applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.

Test Exception LCOs 3.1.8 and 3.4.18 allow specified Technical Specification (TS) requirements to be changed to permit performance of special tests and operations. Unless otherwise specified, all other TS requirements remain unchanged. Compliance with Test Exception LCOs is optional. When a Test Exception LCO is desired to be met but is not met, the ACTIONS of the Test Exception LCO shall be met. When a Test Exception LCO is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.

When a Technical Specification supported system LCO is not met solely due to the inoperability of a non-Technical Specification support system listed below, the Technical Specification supported system LCO is considered to be met unless the associated delay time of the non-Technical Specification support system has expired. This is an exception to LCO 3.0.2 for the Technical Specification. Upon expiration of the non-Technical Specification support system delay time, the Technical Specification supported system shall be declared inoperable and the applicable Conditions and Required Actions for the Technical Specification supported system shall be entered in accordance with LCO 3.0.2.

Non-Technical Specification Support System Delay Time Snubbers 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Prairie Island Units I and 2 3.0-3 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

LCO Applicability 3.0 3.0 LCO APPLICABILITY (continued)

LCO 3.0.9 Unless specifically noted, all the information provided in the LCO including the associated ACTION requirements shall apply to each unit individually. Whenever certain portions of a specification refer to systems, components, operating parameters, setpoints, etc., which are different for each unit, this will be identified in parentheses or notes or in the Applicability section as appropriate.

Prairie Island Units I and 2 3.0-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

LCO Applicability 3.0 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY SR 3.0.1 SRs shall be met during the MODES or other specified conditions in the Applicability for individual LCOs, unless otherwise stated in the SR. Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the LCO.

Failure to perform a Surveillance within the specified Frequency shall be failure to meet the LCO except as provided in SR 3.0.3.

Surveillances do not have to be performed on inoperable equipment or variables outside specified limits.

SR 3.0.2 The specified Frequency for each SR is met, except for SRs with a specified Frequency of 24 months, if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.

The specified Frequency is met for each SR with a specified Frequency of 24 months if the Surveillance is performed within 24 months, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.

For Frequencies specified as "once," the above interval extension (1.25 times the interval specified) does not apply.

If a Completion Time requires periodic performance on a "once per..." basis, the interval extension (1.25 times the interval specified) applies to each performance after the initial performance.

Exceptions to this Specification are stated in the individual Specifications.

Prairie Island Unit 1 - Amendment No. 158 Units 1 and 2 3.0-5 Unit 2 - Amendment No. 149

LCO Applicability 3.0 3.0 SR APPLICABILITY (continued)

SR 3.0.3 If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is greater. This delay period is permitted to allow performance of the Surveillance. A risk evaluation shall be performed for any Surveillance delayed greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and the risk impact shall be managed.

If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.

When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.

SR 3.0.4 Entry into a MODE or other specified condition in the Applicability of an LCO shall not be made unless the LCO's Surveillances have been met within their specified Frequency. This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.

SR 3.0.4 is only applicable for entry into a MODE or other specified condition in the Applicability in MODES 1, 2, 3 and 4.

Prairie Island Unit 1 - Amendment No. 158 Units 1 and 2 3.0-6 Unit 2 - Amendment No. 149

SDM 3.1.1 3.1 REACTIVITY CONTROL SYSTEMS 3.1.1 SHUTDOWN MARGIN (SDM)

LCO 3.1.1 APPLICABILITY:

SDM shall be within the limits provided in the COLR MODE 2 with keff < 1.0, MODES 3, 4, and 5.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.

A.1 Initiate boration to restore 15 minutes SDM to within limit.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.1.1 Verify SDM is within limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.1.1-1

Core Reactivitv 3.1 REACTIVITY CONTROL SYSTIFIS 3.1.2 Core Reactivity LCO 3.1.2 The measured core reactivity hiall be within + 1% Ak/k of predicted valuies.

APPLICABILITY:

MODE 1 and 2.

ACTIONS CONDITION A.

Measured core reactivity not within limit.

REQUIRED ACTION

+

A.1 Re-evaluate core design and safety rmalysis, and determine that the reactor core is acceptable for continued operation.

AND A.2 Establish appropriate operating restrictions and SRs.

COMPLETION TIME 7 days 7 days B.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

Prairie Island Units 1 and 2 3.1.2-1 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149 I

Core Reactivity 3.1.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.2.1 Verify measured core reactivity is within + 1% Ak/k Prior to entering of predicted values.

MODE I after each refueling SR 3.1.2.2 NOTES -------------------------

1. Only required to be performed after 60 effective full power days (EFPD).
2.

The predicted reactivity values may be adjusted (normalized) to correspond to the measured core reactivity prior to exceeding a fuel burnup of 60 EFPD after each fuel loading.

Verify measured core reactivity is within +/- 1% Ak/k 31 EFPD of predicted values.

Prairie Island Units 1 and 2 3.1.2-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ITC 3.1.3 3.1 REACTIVITY CONTROL SYSTEMS 3.1.3 Isothermal Temperature Coefficient (ITC)

LCO 3.1.3 The ITC shall be maintained within the limits specified in the COLR.

The maximum COLR upper limit shall be:

a.

< 5 pcmI°F for power levels !< 70% RTP; and

b.

< 0 pcm/°F for power levels > 70% RTP.

APPLICABILITY:

MODE 1 and MODE 2 with keff > 1.0 for the upper ITC limit, MODES 1, 2, and 3 for the lower ITC limit.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. ITC not within upper A.1 Establish administrative 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

limit, withdrawal limits for control banks to maintain ITC within limit.

B. Required Action and B1.1 Be in MODE 2 with 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion lff < 1.0.

Time of Condition A not met.

Prairie Island Units 1 and 2 3.1.3-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ITC 3.1.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. ------- NOTE NOTE Required Action C. I LCO 3.0.4 is not applicable.

must be completed whenever Condition C is entered.

C.1 Re-evaluate core design and Once prior to safety analysis, and reaching the determine that the reactor equivalent of an Projected end of cycle core is acceptable for equilibrium RTP (EOC) ITC not within continued operation.

all rods out boron lower limit, concentration of 300 ppm D. Required Action and D.I Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time of Condition C not met.

Prairie Island Units 1 and 2 3.1.3-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ITC 3.1.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.3.1 Verify ITC is within upper limit.

Once prior to entering MODE 1 after each refueling SR 3.1.3.2 Verify ITC will be within limits specified in the Once after each COLR at 70% RTP.

refueling prior to THERMAL POWER exceeding 70%

RTP SR 3.1.3.3 Verify that ITC will be within limits at EOC.

Once after each refueling prior to THERMAL POWER exceeding 70%

RTP Prairie Island Units I and 2 3.1.3-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Group Alignment Limits 3.1.4 3.1 REACTIVITY CONTROL SYSTEMS 3.1.4 Rod Group Alignment Limits.

LCO 3.1.4 All shutdown and control rods shall be OPERABLE.

AND Individual actual rod positions shall be within 24 steps of their group step counter demand position when the demand position is between 30 and 215 steps, or within 36 steps of their group step counter demand position when the demand position *< 30 steps, or >_ 215 steps.

APPLICABILITY:

MODES I and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more rod(s)

A.1.1 Verify SDM is within the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable, limits provided in the COLR.

OR A. 1.2 Initiate boration to restore 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> SDM to within limit.

AND A.2 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Prairie Island Units 1 and 2 3.1.4-1 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Group Alignment Limits 3.1.4 ArTTC')NS (continued

CONDITION REQUIRED ACTION COMPLETION TIME B. One rod not within alignment limits.

B.1.1 Verify SDM is within the limits provided in the COLR.

OR B. 1.2 Initiate boration to restore SDM to within limit.

AND B.2.1.1 Perform SR 3.2.1.1 and SR 3.2.1.2.

AND B.2.1.2 Perform SR 3.2.2.1.

OR B.2.2 Reduce High Neutron Flux Trip Setpoint to

_ 85% RTP.

AND B.3 Verify SDM is within the limits provided in the COLR.

AND 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 1 hour 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 8 hours 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units 1 and 2 3.1.4-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Group Alignment Limits 3.1.4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)

B.4 Re-evaluate safety 30 days analyses and determine the THERMAL POWER for which the results remain valid for duration of operation under these conditions.

C. Required Action and C. 1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition B not met.

D. More than one rod not D.1.1 Verify SDM is within the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> within alignment limit, limits provided in the COLR.

OK D. 1.2 Initiate boration to restore 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> required SDM to within limit.

AND D.2 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Prairie Island Units 1 and 2 3.1.4-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Group Alignment Limits 3.1.4 gl nRvFtI T.ANCE PEOIJ1REMENTS SURVEILLANCE SR 3.1.4.1 NOTE -------------------------

If RPI differs by > 12 steps from the group step counter demand position, enter LCO 3.1.7 to determine RPI OPERABILITY.

Verify individual rod positions within alignment limit.

FREQUENCY 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.1.4.2 Verify rod freedom of movement (trippability) by 92 days moving each rod, not fully inserted in the core,

> 10 steps in either direction.

SR 3.1.4.3 Verify rod drop time of each rod, from the fully Prior to reactor withdrawn position, is :< 1.8 seconds from the criticality after beginning of decay of stationary gripper coil voltage each removal of to dashpot entry, with:

the reactor head

-1. Tvg >- 500'F; and

b. Both reactor coolant pumps operating.

Prairie Island Units 1 and 2 3.1.4-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 VZ1 T VFJLLANCE REQUIREMENTS

____r_

Shutdown Bank Insertion Limits 3.1.5 3.1 REACTIVITY CONTROL SYSTEMS 3.1.5 Shutdown Bank Insertion Limits LCO 3.1.5 APPLICABILITY:

Each shutdown bank shall be within insertion limits specified in the COLR.

N O T E -------------------------------------

This LCO is not applicable while performing SR 3.1.4.2.

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more shutdown A.I.1 Verify SDM is within the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> banks not within limits, limits provided in the COLR.

OR A. 1.2 Initiate boration to restore 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> SDM to within limit.

AND A.2 Restore shutdown banks to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> within limits.

Prairie Island Units 1 and 2 3.1.5-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Shutdown Bank Insertion Limits 3.1.5 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and B.I Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.5.1 Verify each shutdown bank is within the limits 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> specified in the COLR.

Prairie Island Units I and 2 3.1.5-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Control Bank Insertion Limits 3.1.6 3.1 REACTIVITY CONTROL SYSTEMS 3.1.6 Control Bank Insertion Limits LCO 3.1.6 APPLICABILITY:

Control banks shall be within the insertion, sequence, and overlap limits specified in the COLR.

-- NOTE This LCO is not applicable while performing SR 3.1.4.2.

MODE 1, MODE 2 with keff >- 1.0.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Control bank insertion A.1.1 Verify SDM is within the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> limits not met.

limits provided in the COLR.

OR A. 1.2 Initiate boration to restore 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> SDM to within limit.

AND A.2 Restore control bank(s) to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> within limits.

Prairie Island Units 1 and 2 3.1.6-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Control Bank Insertion Limits 3.1.6 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Control bank sequence or B.I.1 Verify SDM is within the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> overlap limits not met.

limits provided in the COLR.

OR B. 1.2 Initiate boration to restore 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> SDM to within limit.

AND B.2 Restore control bank 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> sequence and overlap to within limits.

C. Required Action and C.1 Be in MODE 2 with keff 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion

< 1.0.

Time not met.

Prairie Island Units I and 2 3.1.6-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Control Bank Insertion Limits 3.1.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.6.1 Verify estimated critical control bank position is Prior to within the limits specified in the COLR.

achieving criticality SR 3.1.6.2 Verify each control bank insertion is within the limits 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> specified in the COLR.

SR 3.1.6.3 Verify sequence and overlap limits specified in the 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> COLR are met for control banks not fully withdrawn from the core.

Prairie Island Units 1 and 2 3.1.6-3 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Position Indication 3.1.7 3.1 REACTIVITY CONTROL SYSTEMS 3.1.7 Rod Position Indication LCO 3.1.7 The Rod Position Indication (RPI) System and demand position indication shall be OPERABLE.

APPLICABILITY:

MODES 1 and 2.

ACTIONS NOTE Separate Condition entry is allowed for each inoperable rod position indicator and each demand position indicator.

CONDITION REQUIRED ACTION COMPLETION TIME A. One RPI per group A. 1 Verify the position of the Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> inoperable for one or rod(s) with inoperable more groups.

position indicators by using movable incore detectors.

OR A.2 Reduce THERMAL 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> POWER to _ 50% RTP.

Prairie Island Units 1 and 2 3.1.7-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Position Indication 3.1.7 ArTIr)N.z (rnntiniied

CONDITION REQUIRED ACTION COMPLETION TIME B. More than one RPI per group inoperable for one or more groups.

B. I Monitor and record demand position indication for rods with inoperable RPI.

AND B.2 Monitor and record reactor coolant system average temperature.

AND B.3 Verify, using movable incore detectors, position of rods with inoperable RPIs which have been moved in excess of 24 steps in one direction since last determination of their position.

AND B.4 Restore inoperable RPIs to OPERABLE status such that a maximum of one RPI per group is inoperable.

J ____________________________

I Once per hour Once per hour Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> 24 hours Prairie Island Units 1 and 2 3.1.7-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Position Indication 3.1.7 ACTIONS (continued)

CONDITION REQUIkED ACTION COMPLETION TIME C. Indication for one C.1.1 Verify by administrative Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> demand position per bank means all RPIs for the inoperable for one or affected bank(s) are more banks.

OPERABLE.

AND C.1.2 Verify the rod position Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> indication of the most withdrawn rod and the least withdrawn rod of the affected bank(s) are

_* 12 steps apart.

OR C.2 Reduce THERMAL 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> POWER to _ 50% RTP.

D. Required Action and D.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

Prairie Island Units 1 and 2 3.1.7-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Rod Position Indication 3.1.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.7.1 Verify each RPI agrees within 12 steps of the group Once prior to demand position between 30 and 215 steps, or within criticality after 24 steps of the group demand position when the each removal of demand position is ý> 215 steps or !< 30 steps.

the reactor head Prairie Island Units 1 and 2 3.1.7-4 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

PHYSICS TESTS Exceptions - MODE 2 3.1.8 3.1 REACTIVITY CONTROL SYSTEMS 3.1.8 PHYSICS TESTS Exceptions - MODE 2 LCO 3.1.8 APPLICABILITY:

During the performance of PHYSICS TESTS, the requirements of LCO 3.1.3, "Isothermal Temperature Coefficient (ITC)";

LCO 3.1.4, "Rod Group Alignment Limits";

LCO 3.1.5, "Shutdown Bank Insertion Limits";

LCO 3.1.6, "Control Bank Insertion Limits"; and LCO 3.4.2, "RCS Minimum Temperature for Criticality" may be suspended and the number of required channels for LCO 3.3.1, "RTS Instrumentation," Functions 2, 3, 6, 7, and 16.e may be reduced to "3" required channels, provided:

a. RCS lowest loop average temperature is > 535°F;
b. SDM is within the limits provided in the COLR; and
c. THERMAL POWER is < 5% RTP.

During PHYSICS TESTS initiated in MODE 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.

A. I Initiate boration to restore 15 minutes SDM to within limit.

AND A.2 Suspend PHYSICS TESTS 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> exceptions.

Prairie Island Units I and 2 3.1.8-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

PHYSICS TESTS Exceptions - MODE 2 3.1.8 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. THERMAL POWER not B. I Open reactor trip breakers.

Immediately within limit.

C. RCS lowest loop average C.1 Restore RCS lowest loop 15 minutes temperature not within average temperature to

limit, within limit.

D. Required Action and D.1 Be in MODE 3.

15 minutes associated Completion Time of Condition C not met.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.8.1 Perform a CHANNEL OPERATIONAL TEST on Prior to initiation power range and intermediate range channels per of PHYSICS SR 3.3.1.7, SR 3.3.1.8, and Table 3.3.1-1.

TESTS SR 3.1.8.2 Verify the RCS lowest loop average temperature is 30 minutes

> 535°F.

Prairie Island Units 1 and 2 3.1.8-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

PHYSICS TESTS Exceptions - MODE 2 3.1.8 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.1.8.3 Verify THERMAL POWER is _< 5% RTP.

30 minutes SR 3.1.8.4 Verify SDM is within the limits provided in the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> COLR.

Prairie Island Units I and 2 3.1.8-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

F (Z) 3.2.1 3.2 POWER DISTRIBUTION LIMITS 3.2.1 Heat Flux Hot Channel Factor (F Q (Z))

LCO 3.2.1 APPLICABILITY:

FQ(Z), as approximated by F'(Z) and F ' (Z), shall be within the limits specified in the COLR.

MODE 1.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. -------- NOTE---------

A.1 Reduce THERMAL 15 minutes after Required Action A.4 POWER >_ 1% RTP for each each F ' (Z) shall be completed 1% F c (Z) exceeds limit, determination whenever this Condition is entered.

AND A.2 Reduce Power Range 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after FQ(Z) not within limit.

Neutron Flux-High trip each F c (Z) setpoints > 1% for each determination 1% Fc(Z) exceeds limit.

AND A.3 Reduce Overpower AT trip 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after setpoints > 1% for each 1%

each F c (Z)

F, c(Z) exceeds limit, determination AND Prairie Island Units 1 and 2 Unit 1 Unit 2 -

3.2.1-1 Amendment No. 158 Amendment No. 149

F (Z) 3.2.1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.4 Perform SR 3.2.1.1 and Prior to increasing SR 3.2.1.2.

THERMAL POWER above the limit of Required Action A. 1 B. -------- NOTE-----

Required Action B.4 shall be completed whenever this Condition is entered.

F " (Z) not within limits.

B.1 Reduce THERMAL POWER> 1% RTP for each 1% F '(Z) exceeds limit.

AND B.2 Reduce Power Range Neutron Flux-High trip setpoints _> 1% for each 1%

F w (Z) exceeds limit.

AND B.3 Reduce Overpower AT trip setpoints > 1% for each 1%

Fw (Z) exceeds limit.

AND B.4 Perform SR 3.2.1.1 and SR 3.2.1.2.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after each F (Z) determination 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after each F w (Z) determination 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after each F ' (Z) determination Prior to increasing THERMAL POWER above the limit of Required Action B.1 Prairie Island Units 1 and 2 3.2.1-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Fo(Z) 3.2.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and C.1 Be in MODE 2.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

Prairie Island Units I and 2 3.2.1-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

F0(Z) 3.2.1 SURVEILLANCE REQUIREMENTS


N O T E -------------------------------------------------

During power escalation at the beginning of each cycle, THERMAL POWER may be increased until an equilibrium power level has been achieved, at which a power distribution map is obtained.

SURVEILLANCE a-SR 3.2.1.1 Verify F'(Z) is within limit.

FREQUENCY Once after each refueling prior to THERMAL POWER exceeding 75% RTP AND Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after achieving equilibrium conditions after exceeding, by

Ž> 10% RTP, the THERMAL POWER at which F ' (Z) was last verified AND 31 effective full power days (EFPD) thereafter Prairie Island Units I and 2 3.2.1-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

F o (Z) 3.2.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE I~

SR 3.2.1.2 NOTE--

If measurements indicate that the maximum over z K-Z[0]

has increased since the previous evaluation of F (Z):

a. Increase F ' (Z) by an appropriate factor specified in the COLR and reverify F ' (Z) is within limits; or
b. Repeat SR 3.2.1.2 once per 7 EFPD until either a.

above is met or two successive flux maps indicate that the maximum over z K(z) has not increased.

Verify F w' (Z) is within limit.

FREQUENCY Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after achieving equilibrium conditions after each refueling after THERMAL POWER exceeds 75% RTP AND Prairie Island Units 1 and 2 3.2.1-5 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

F Q(Z) 3.2.1 SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.2.1.2 (continued)

FREQUENCY Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after achieving equilibrium conditions after exceeding, by

_> 10% RTP, the THERMAL POWER at which F w (Z) was last verified AND 31 EFPD thereafter L _________________________________________________________

Prairie Island Units 1 and 2 3.2.1-6 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 i

F N All1 3.2.2 3.2 POWER DISTRIBUTION LIMITS 3.2.2 Nuclear Enthalpy Rise Hot Channel Factor (Frý

)

LCO 3.2.2 FA shall be within the limits specified in the COLR.

APPLICABILITY:

MODE 1.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. --------- NOTE ---------

A.1 Reduce THERMAL 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Required Actions A.2 POWER to < 50% RTP.

and A.4 must be completed whenever AND Condition A is entered.

A.2 Perform SR 3.2.2.1.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> not within limit.

AND A.3 Reduce Power Range 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Neutron Flux-High trip setpoints to !< 55% RTP.

AND Prairie Island Units I and 2 3.2.2-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

F N 3.2.2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.4 ---------

NOTE-------

THERMAL POWER does not have to be reduced to comply with this Required Action.

Perform SR 3.2.2.1.

Prior to THERMAL POWER exceeding 50% RTP AND Prior to THERMAL POWER exceeding 75% RTP AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER reaching 2!95% RTP B. Required Action and B.1 Be in MODE 2.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

Prairie Island Units 1 and 2 3.2.2-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

3. 2 3.2.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.2.2.1 Verify F,1 is within limits specified in the COLR.

Prairie Island Units 1 and 2 3.2.2-3 FREQUENCY Once after each refueling prior to THERMAL POWER exceeding 75% RTP AND 31 EFPD thereafter Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 i

AFD 3.2.3 3.2 POWER DISTRIBUTION LIMITS 3.2.3 AXIAL FLUX DIFFERENCE (AFD)

LCO 3.2.3 The AFD:

a.

Shall be maintained within the target band about the target flux difference. The target band is specified in the COLR.

b.

May deviate outside the target band with THERMAL POWER

< 90% RTP but > 50% RTP, provided AFD is within the acceptable operation limits and cumulative penalty deviation time is _< 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> during the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The acceptable operation limits are specified in the COLR.

c.

May deviate outside the target band with THERMAL POWER

< 50% RTP.

NOTES -----------------------------------

I.

The AFD shall be considered outside the target band when two or more OPERABLE excore channels indicate AFD to be outside the target band.

2.

With THERMAL POWER > 50% RTP, penalty deviation time shall be accumulated on the basis of a 1 minute penalty deviation for each 1 minute of power operation with AFD outside the target band.

3.

With THERMAL POWER < 50% RTP and >15% RTP, penalty deviation time shall be accumulated on the basis of a 0.5 minute penalty deviation for each 1 minute of power operation with AFD outside the target band.

4.

A total of 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> of operation may be accumulated with AFD outside the target band without penalty deviation time during surveillance of power range channels in accordance with SR 3.3.1.6, provided AFD is maintained within acceptable operation limits.

Prairie Island Unit 1 - Amendment No. 158 Units 1 and 2 3.2.3-1 Unit 2 - Amendment No. 149

APPLICABILITY:

MODE 1 with THERMAL POWER > 15% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

THERMAL POWER A.I Restore AFD to within 15 minutes

> 90% RTP.

target band.

AND AFD not within the taiget band.

B.

Required Action and B.1 Reduce THERMAL 15 minutes associated Completion POWER to < 90% RTP.

Time of Condition A not met.

Prairie Island Units I and 2 3.2.3-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 AFD 3.2.3

AFD 3.2.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. --------- NOTE ---------

C.1 Reduce THERMAL 30 minutes Required Action C.1 POWER to < 50% RTP.

must be completed whenever Condition C is entered.

THERMAL POWER

< 90% and > 50% RTP with cumulative penalty deviation time > 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> during the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

OR THERMAL POWER

< 90% and >_ 50% RTP with AFD not within the acceptable operation limits.

D.

Required Action and D.1 Reduce THERMAL 9 hours1.041667e-4 days <br />0.0025 hours <br />1.488095e-5 weeks <br />3.4245e-6 months <br /> associated Completion POWER to < 15% RTP.

Time for Condition C not met.

Prairie Island Units 1 and 2 3.2.3-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

AFD 3.2.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.2.3.1 Verify AFD is within limits for each OPERABLE 7 days excore channel.

SR 3.2.3.2 NOTE The initial target flux difference after each refueling may be determined from design predictions.

Determine, by measurement, and update target flux Once within 31 difference.

EFPD after each refueling AND 31 EFPD thereafter Prairie Island Units I and 2 3.2.3-4 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

QPTR 3.2.4 3.2 POWER DISTRIBUTION LIMITS 3.2.4 QUADRANT POWER TILT RATIO (QPTR)

LCO 3.2.4 The QPTR shall be < 1.02.

APPLICABILITY:

MODE 1 with THERMAL POWER > 50% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. QPTR not within limit.

A. 1 Reduce THERMAL 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> after each POWER > 3% from RTP QPTR for each 1% of QPTR determination

> 1.00.

AND A.2 Perform SR 3.2.4.1.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.2.4-1

QPTR 3.2.4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

I A.3 Perform SR 3.2.1.1, SR 3.2.1.2 and SR 3.2.2.1.

AND A.4 Re-evaluate safety analyses and confirm results remain valid for duration of operation under this condition.

AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after achieving equilibrium conditions from a THERMAL POWER reduction per Required Action A.1 AND Once per 7 days thereafter.

Prior to increasing THERMAL POWER above the limit of Required Action A. I Prairie Island Units I and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.2.4-2

QPTR 3.2.4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.5 ---------

NOTES------

1. Perform Required Action A.5 only after Required Action A.4 is completed.
2. Required Action A.6 shall be completed when Required Action A.5 is performed.

Normalize excore detectors Prior to to restore QPTR to within increasing limits.

THERMAL POWER above the limit of Required Action A. I AND Prairie Island Units 1 and 2 3.2.4-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

QPTR 3.2.4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.6 ---------

NOTE-------

Perform Required Action A.6 only after Required Action A.5 is completed.

Perform SR 3.2.1.1, SR Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> 3.2.1.2 and SR 3.2.2.1.

after achieving equilibrium conditions at RTP not to exceed 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after increasing THERMAL POWER above the limit of Required Action A.1 B. Required Action and B.1 Reduce THERMAL 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> associated Completion POWER to

Time not met.

Prairie Island Units 1 and 2 3.2.4-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

QPTR 3.2.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.2.4.1 NOTES

1.

With input from one Power Range Neutron Flux channel inoperable and THERMAL POWER

_< 85% RTP, the remaining three power range channels can be used for calculating QPTR.

2.

SR 3.2.4.2 may be performed in lieu of this Surveillance.

Verify QPTR is within limit by calculation.

SR 3.2.4.2 NOTE Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after input from one or more Power Range Neutron Flux channels are inoperable with THERMAL POWER

> 85% RTP.

Verify QPTR is within limit using the movable incore detectors or thermocouples.

FREQUENCY 7 days 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units I and 2 3.2.4-5 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 3.3 INSTRUMENTATION 3.3.1 Reactor Trip System (RTS) Instrumentation LCO 3.3.1 The RTS instrumentation for each Function in Table 3.3.1-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.1-1.

ACTIONS NOTE-------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more Functions A. I Enter the Condition Immediately with one or more referenced in Table 3.3.1 -1 required channels or for the channel(s) or train(s).

trains inoperable.

B.

One Manual Reactor B. 1 Restore channel to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> Trip channel OPERABLE status.

inoperable.

OR B.2 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> Prairie Island Units I and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.3.1-1

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C.

One channel or train C. 1 Restore channel or train to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> inoperable.

OPERABLE status.

OR C.2.1 Initiate action to fully insert 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> all rods.

AND C.2.2 Place the Rod Control 49 hours5.671296e-4 days <br />0.0136 hours <br />8.101852e-5 weeks <br />1.86445e-5 months <br /> System in a condition incapable of rod withdrawal.

D.

One Power Range -

NOTE--------

Neutron Flux channel The inoperable channel may be inoperable, bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing and setpoint adjustment of other channels.

D.1.1 Place channel in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND Prairie Island Units 1 and 2 3.3.1-2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME D. (continued)

D. 1.2 --------

NOTE------

Only required to be performed when THERMAL POWER is

> 85% RTP and the Power Range Neutron Flux input to QPTR is inoperable.

Perform SR 3.2.4.2.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OR D.2 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> E. One channel inoperable.

NOTE--------

The inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

E. I Place channel in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR E.2 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units 1 and 2 3.3.1-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME F.

One Intermediate Range F.I Reduce THERMAL 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Neutron Flux channel POWER to < P-6.

inoperable.

OR F.2 Increase THERMAL 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> POWER to > P-10.

G.

Two Intermediate Range G.1 ---------

NOTE------

Neutron Flux channels Limited plant cooldown or inoperable, boron dilution is allowed provided the change is accounted for in the calculated SDM.

Suspend operations Immediately involving positive reactivity additions.

AND G.2 Reduce THERMAL 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> POWER to < P-6.

Prairie Island Units I and 2 3.3.1-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME H.

One Source Range H. ---------

NOTE------

Neutron Flux channel Limited plant cooldown or inoperable, boron dilution is allowed provided the change is accounted for in the calculated SDM.

Suspend operations Immediately involving positive reactivity additions.

1.

Two Source Range 1.1 Open Reactor Trip Breakers Immediately Neutron Flux channels (RTBs).

inoperable.

J.

One Source Range J. 1 Restore channel to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> Neutron Flux channel OPERABLE status.

inoperable.

OR J.2.1 Initiate action to fully insert 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> all rods.

AND J.2.2 Place the Rod Control 49 hours5.671296e-4 days <br />0.0136 hours <br />8.101852e-5 weeks <br />1.86445e-5 months <br /> System in a condition incapable of rod withdrawal.

Prairie Island Units I and 2 3.3.1-5 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME K.

One channel inoperable.

NOTE---------

The inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

K.1 Place channel in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR K.2 Reduce THERMAL 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> POWER to < P-7 and P-8.

L.

One or both channel(s)

NOTE---------

inoperable on one bus.

One inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

L.1 Place channel(s) in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR L.2 Reduce THERMAL 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> POWER to < P-7 and P-8.

Prairie Island Units 1 and 2 3.3.1-6 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME M.

One Reactor Coolant M. 1 Restore channel to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> Pump Breaker Open OPERABLE status.

channel inoperable.

OR M.2 Reduce THERMAL 54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> POWER to < P-7 and P-8.

N.

One Turbine Trip NOTE---------

channel inoperable The inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channel(s).

N. 1 Place channel in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR N.2 Reduce THERMAL 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> POWER to < P-9.

Prairie Island Units 1 and 2 3.3.1-7 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME

0.

One train inoperable.

NOTE--

One train may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

0.1 Restore train to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OPERABLE status.

OR 0.2 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> P.

One RTB train

.NOTES-------

inoperable.

1.

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing, provided the other train is OPERABLE.

2.

One RTB may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for maintenance on undervoltage or shunt trip mechanisms, provided the other train is OPERABLE.

P.1 Restore train to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OPERABLE status.

OR P.2 Be in MODE 3.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> Prairie Island Units 1 and 2 3.3.1-8 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME Q.

One or more channels Q.1 Verify interlock is in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable, required state for existing unit conditions.

OR Q.2 Be in MODE 3.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> R.

One oi more Thannels R.1 Verify interlock is in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable, required state for existing unit conditions.

OR R.2 Be in MODE 2.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> S.

One trip mechanism S.1 Restore inoperable trip 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> inoperable for one RTB.

mechanism to OPERABLE status.

OR S.2 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> Prairie Island Units 1 and 2 3.3.1-9 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS


NOTE -------------------------------------------------

Refer to Table 3.3.1-1 to determine which SRs apply for each RTS Function.

SURVEILLANCE FREQUENCY SR 3.3.1.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.1.2 NOTES

1.

Adjust NIS channel if absolute difference is

> 2%.

2.

Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after THERMAL POWER is >_ 15% RTP.

Compare results of calorimetric heat balance 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> calculation to Nuclear Instrumentation System (NIS) channel output.

Prairie Island Units 1 and 2 3.3.1-10 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.3.1.3 NOTES --------------------------

1.

Adjust NIS channel if absolute difference is

> 2%.

2.

Not required to be performed until 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after THERMAL POWER is > 15% RTP.

Compare results of the incore detector measurements to NIS AFD.

i SR 3.3.1.4 NOTE --------------------------

This Surveillance must be performed on the reactor trip bypass breaker prior to placing the bypass breaker in service.

Perform TADOT.

FREQUENCY 31 effective full power days (EFPD) 31 days on a STAGGERED TEST BASIS SR 3.3.1.5 Perform ACTUATION LOGIC TEST.

31 days on a STAGGERED TEST BASIS Prairie Island Units 1 and 2 3.3.1-11 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.6 NOTE Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER is > 75% RTP.

Calibrate excore channels to agree with incore 92 EFPD detector measurements.

SR 3.3.1.7 NOTE Not required to be performed for source range instrumentation prior to entering MODE 3 from MODE 2 until 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after entry into MODE 3.

Perform COT.

92 days Prairie Island Units 1 and 2 3.3.1-12 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.3.1.8 NOTES -------------------------

1. This Surveillance shall include verification that interlocks P-6 and P-10 are in their required state for existing unit conditions.
2. Not required to be performed for intermediate and source range instrumentation prior to reactor startup following shutdown *< 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

Perform COT.

FREQUENCY NOTE Only required when not performed within previous 92 days Prior to reactor startup AND Twelve hours after reducing power below P-10 for power and intermediate range instrumentation AND Four hours after reducing power below P-6 for source range instrumentation AND Every 92 days thereafter Prairie Island Units 1 and 2 3.3.1-13 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 I

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.9 NOTE Verification of setpoint is not required.

Perform TADOT.

92 days SR 3.3.1.10 NOTE This Surveillance shall include verification that the time constants are adjusted to the prescribed values.

Perform CHANNEL CALIBRATION.

24 months SR 3.3.1.11 NOTE Neutron detectors are excluded from CHANNEL CALIBRATION.

Perform CHANNEL CALIBRATION.

24 months Prairie Island Units I and 2 3.3.1-14 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.12 NOTE ---------------------------

This Surveillance shall include verification of Reactor Coolant System resistance temperature detector bypass loop flow rate.

Perform CHANNEL CALIBRATION.

24 months SR 3.3.1.13 Perform COT.

24 months SR 3.3.1.14 NOTE ---------------------------

Verification of setpoint is not required.

Perform TADOT.

24 months SR 3.3.1.15 NOTE Verification of setpoint is not required.

Perform TADOT.

Prior to exceeding the P-9 interlock whenever the unit has been in MODE 3, if not performed within the previous 31 days Prairie Island Units 1 and 2 3.3.1-15 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.3.1.16 NOTE Neutron detectors are excluded from response time testing.

Verify RTS RESPONSE TIME is within limits.

Prairie Island Units 1 and 2 3.3.1-16 FREQUENCY 24 months Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 Table 3.3. 1-1 (page I of 8)

Reactor Trip Sv tern I-,trumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE I

Manual Reactor Trip

2.

Power Range Neutron Flux

a.

High

b.

Low 3(a), 4 (a) 5(a) 1,2 (b)

B C

SR 3.3.1.14 SR 3.3.1.14 D

SR 3.3.1.1 SR 3.3.1.2 SR 3.3.1.7 SR 3.3.1.11 SR 3.3.1.16 D

SR 3.3.1.1 SR 3.3.1.8 SR 3.3. 1.11 SR 3.3.1.16 NA I 10% RTP 40% RTP 4

4

3.

Power Range Neutron Flux Rate

a. High Positive Rate
b. High Negative Rate
4.

Intermediate Range Neutron Flux 1,2 1,2 (b)

(c)

I

, 2 4

4 2

D SR 3.3.1.7 SR 3.3.1.11 SR 3.3.1.16 D

SR 3.3.1.7 SR 3.3.1.11 SR 3.3.1.16 F, G SR 3.3.1.1 SR 3.3.1.8 SR 3.3.1.11

< 6% RTP with time constant 2 2 sec S8% RTP with time constant

Ž 2 sec

< 40% RTP With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.

Below the P-10 (Power Range Neutron Flux) interlocks.

Above the P-6 (Intermediate Range Neutron Flux) interlocks.

Prairie Island Units 1 and 2 3.3.1-17 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 (a)

(b)

(c)

RTS Instrumentation 3.3.1 Table 33.1-1 (page 2 of S)

Reactor Trip Systcmn Instrumentation APPLICA13LE MODES OR OTH ER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

5.

Source Range Neutron Flux

6. Overtemperature AT
7. Overpower AT

-(d) 1,2 4

4 St 1

R 3.3. 1.1 SR 3.3. 1. 8 SR 3.3.1.11 SR 3.3.1.16 I, J SR 3.3. 1.1 SR 3.3.1.7 SR 3.3. 1.11 SR 3.3.1-16 E

SR 3.3. 1.1 SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 SR 3.3.1.12 SR 3.3.1.16 E

SR 3.3.1.1 SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 SR 3.3.1.12 SR 3.3.1.16 O1E6 cps I.OE6 cps Refer to Note I (Page 3.3.1-23)

Refer to Note 2 (Page 3.3.1-24)

8. Pressurizer Pressure 4

3 K

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 E

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10

> 1760 psig

!< 2400 psig With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.

Below the P-6 (Intermediate Range Neutron Flux) interlocks.

Above the P-7 (Low Power Reactor Trips Block) interlock.

Prairie Island Units 1 and 2 3.3.1-18 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

a.

Low

b.

High l(e) 1,2 (a)

(d)

(e) 3(a), 4(a), 5(a)

RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 3 ofS)

Reactor Trip Systcm !nstrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

9.

Pressurizer Water Level - High

10. Reactor Coolant Flow-Low
11.

Loss of Reactor Coolant Pump (RCP)

a.

RCP Breaker Open

b. Under frequency 4 kV Buses II and 12 (21 and 22)
12. Undervoltage on 4 kV Buses II and 12(21 and
22)
13. Steam Generator (SG)

Water Level Low Low 1(e) 1(0 1(,

1(0 1,2 3 per loop I per RCP 2 per bus 2 per bus 3 per SG K

SR 3.31.1 SR 3.3.1.7 SR 3.3.1. 10 KSR 3.3.1.1 SR 3.3.1.7 SR 3.3.1. 10 M

SR 3.3.1.14 L

SR 3.3.1.9 SR 3.3.1 10 L

SR 3.3.1.9 SR 3.3. 1.10 E

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.I.10 Above the P-7 (Low Power Reactor Trips Block) interlock.

Above the P-8 (Power Range Neutron Flux) or P-7 (Low Power Reactor Trips Block) interlocks.

Prairie Island Units I and 2 3.3.1-19 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 9V'.

9 0%

NA 58.2 Hz S7 6 % rated bus voltage

> 11.3%

(e)

(f)

RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 4 of 8)

Reactor Tr-p System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

14. Turbine Trip
a.

Low Autostop Oil 1 (g) 3 N

SR 3.3 1.10

Ž 45 psig Pressure SR 3.3.1.15

b.

Turbine Stop l(g) 2 N

SR 3.3. 1.10 Closed Valve Closure SR 3.3.1.15

15. Safety Injection (SI) 1,2 2 trains 0

SR 3.3.1.14 NA Input from Engineered Safety Feature Actuation System (ESFAS)

(g)

Above the P-9 (Power Range Neutron Flux) interlock.

Prairie Island Units 1 and 2 3.3.1-20 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 Table 3.3. 1-I (page 5 of 8)

Reactor Trip Syvtem Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

16. Reactor Trip System Interlocks
a. Intermediate Range Neutron Flux, P-6
b. Low Power Reactor Trips Block, P-7
1. Power Range Neutron Flux
2. Turbine Impulse Pressure
c.

Power Range Neutron Flux, P-8

d. Power Range Neutron Flux, P-9
e. Power Range Neutron Flux, P-10
17. Reactor Trip Breakers(h) (RTBs) 2(d) 1,2 1,2 3(a), 4(a), 5(a)

Q SR 3.3.1.11 SR 3.3.1.13 4

2 4

4 4

2 trains 2 trains R

SR 33..111 SR 3.3.1.13 R

SR 3.3.1.7 SR 3.3. 1. 10 R

SR 33.31.11 SR 3.3.1.13 R

SR 3.3. 1.11 SR 3.3.1.13 Q

SR 3.3.1.11 SR 3.3 1.13 P

SR 3.3.1.4 C

SR 3.3.1.4 With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.

Below the P-6 (Intermediate Range Neutron Flux) interlocks.

Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB.

Prairie Island Units 1 and 2 3.3.1-21 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 I.OE-10 amp

< 12% RTP

< 12% Full Load

< I1% RTP

< 12% RTP z 9% RTP NA NA (a)

(d)

(h)

RTS Instrumentation 3.3.1 Table 3.3. 1-1 (page 6 of 8)

Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

18. Reactor Trip Breaker 1,2 1 each per S

SR 3.3.1.4 NA Undervoltage and Shunt RTB Trip Mechanisms 3(a), 4(a), 5(a) l each per C

SR 3.3.1.4 NA RTB

19. Automatic Trip Logic 1,2 2 trains 0

SR 3.3.1.5 NA 3 (a) 4 (a), 5 (a) 2 trains C

SR 3.3.1.5 NA (a)

With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.

Prairie Island Units I and 2 3.3.1-22 Unit I -Amendment No. 158 Unit 2 - Amendment No. 149

RTS Instrumentation Table 3.3.1-1 (page 7 of 8)

Reactor Trip System Instrumentation Note 1: Overtemperature AT The Overtemperature AT Function Allowable Value is defined by the following Trip Setpoint.

AT<ýATo{KI-K 2(T-T')K tj+r )+K 3 (P -P') -f(Al)}

Where: AT is measured Reactor Coolant System (RCS) AT, 'F.

AT0 is the indicated AT at RTP, °F.

s is the Laplace transform operator, sec-l T is the measured RCS average temperature, 'F.

T' is the nominal Ta,g at RTP, = 567.3 (F.

P is the measured pressurizer pressure, psig P' is the nominal RCS operating pressure, = 2235 psig K,-* 1.11 K2 = 0.009/°F K3

- 0.000566/psig

"- 1 30 sec

"-C 2 - 4 sec f(AI) =- 0.0150{12 + (q,- qb)} when qt-qb < - 12% RTP 0% of RTP when -12% RTP < qt-qb <9% RTP 0.0250{(qt - qb) - 9}

when q, - qb > 9% RTP Where q, and qb are percent RTP in the upper and lower halves of the core, respectively, and q, + qb is the total THERMAL POWER in percent RTP.

Prairie Island Unit 1 - Amendment No. 158 Units l and 2 3.3.1-23 Unit 2 - Amendment No. 149

RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 8 of 8)

Reactor Trip System Instrumentation Note 2: Ovemower AT The Overpower AT Function Allowable Value is defined by the following Trip Setpoint.

AT_<AT0K4-K5+t3sT K 6 (T-T')-f(AI)}

AT<A

~1{K 4

[1+

Where:

AT is measured RCS AT, 'F.

AT 0 is the indicated AT at RTP, 'F.

s is the Laplace transform operator, sec 1.

T is the measured RCS average temperature, 'F.

T' is the nominal Tax.g at RTP, = 567.3'F.

K4 < 1.10 K5

- 0.0275/°F for increasing Tavg

= 0/'F for decreasing Taxg K 6 0 0.002/°F when T > T'

= 0/°F when T < T' Tr3 10 sec f(AI) = As defined in Note I Prairie Island Units 1 and 2 3.3.1-24 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 3.3 INSTRUMENTATION 3.3.2 Engineered Safety Feature Actuation System (ESFAS) Instrumentation LCO 3.3.2 APPLICABILITY:

The ESFAS instrumentation for each Function in Table 3.3.2-1 shall be OPERABLE.

According to Table 3.3.2-1.

ACTIONS


NOTE -------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions A. I Enter the Condition Immediately with one or more referenced in Table 3.3.2-1 required channels or for the channel(s) or trains inoperable, train(s).

B. One channel or train B. 1 Restore channel or train to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> inoperable.

OPERABLE status.

OR B.2.1 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> AND B.2.2 Be in MODE 5.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.3.2-1

ESFAS Instrumentation 3.3.2 A rTTnMQ

(-v-ntrnipd

A rI.

T~/ nX 0,

r-r~fli 1tk..- A).

r CONDITION REQUIRED ACTION f

r C. One train inoperable.

NOTE ---------------

One train may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

C. 1 Restore train to OPERABLE status.

OR C.2.1 Be in MODE 3.

AND C.2.2 Be in MODE 5.

4-1 D. One channel inoperable.

NOTE ---------------

The inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

D. 1 Place channel in trip.

OR D.2.1 Be in MODE 3.

AND D.2.2 Be in MODE 4.

COMPLETION TIME 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 12 hours 42 hours4.861111e-4 days <br />0.0117 hours <br />6.944444e-5 weeks <br />1.5981e-5 months <br /> 6 hours 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 18 hours Prairie Island Units 1 and 2 3.3.2-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One or more NOTE---------

Containment Pressure One channel may be bypassed for channel(s) inoperable, up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing.

E.1.1 Place inoperable 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> channel(s) in trip.

AND E. 1.2 Verify one channel per 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> pair OPERABLE.

OR E.2.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND E.2.2 Be in MODE 4.

18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> Prairie Island Units 1 and 2 3.3.2-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 ACTIONS (continued)

CONDITION F.

One channel or train inoperable.

G. One train inoperable.

REQUIRED ACTION F. 1 Restore channel or train to OPERABLE status.

OR F.2.1 Be in MODE 3.

AND F.2.2 Be in MODE 4.

NOTE---------

One train may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

G. 1 Restore train to OPERABLE status.

OR G.2.1 Be in MODE 3.

AND G.2.2 Be in MODE 4.

COMPLETION TIME 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> 54 hours 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> 6 hours 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 18 hours Prairie Island Units 1 and 2 3.3.2-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME H.

One channel

-NOTE---------

inoperable.

The inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

H. I Place channel in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR H.2 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

1.

One or both channel(s) -

NOTE---------

inoperable on one bus.

One inoperable channel may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing of other channels.

1.1 Place channel(s) in trip.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> OR 1.2 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units I and 2 3.3.2-5 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME J.

One train inoperable. --

NOTE---------

One train may be bypassed for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

J. 1 Enter applicable Immediately Condition(s) and Required Action(s) for Auxiliary Feedwater (AFW) train made inoperable by ESFAS instrumentation.

K. One channel inoperable.

K. I Enter applicable Immediately Condition(s) and Required Action(s) for Auxiliary Feedwater (AFW) pump made inoperable by ESFAS instrumentation.

Prairie Island Units 1 and 2 3.3.2-6 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 SURVEILLANCE REQUIREMENTS NOTE Refer to Table 3.3.2-1 to determine which SRs apply for each ESFAS Function.

S............................................................................................................

SURVEILLANCE FREQUENCY SR 3.3.2.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.2.2 Perform ACTUATION LOGIC TEST.

31 days on a STAGGERED TEST BASIS SR 3.3.2.3 Perform COT.

92 days SR 3.3.2.4 NOTE Verification of setpoint not required.

Perform TADOT.

24 months Prairie Island Units I and 2 3.3.2-7 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.2.5


NOTE Verification of setpoint not required.

Perform TADOT.

24 months on a STAGGERED TEST BASIS SR 3.3.2.6 NOTE This Surveillance shall include verification that the time constants are adjusted to the prescribed values.

Perform CHANNEL CALIBRATION.

24 months SR 3.3.2.7 Perform MASTER RELAY TEST.

24 months SR 3.3.2.8 Perform SLAVE RELAY TEST.

24 months Prairie Island Units 1 and 2 3.3.2-8 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 1 of 4)

Engineered Safety Feature \\ctuation System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE Safety Injection

a. Manual Initiation
b. Automatic Actuation Relay Logic
c.

High Containment Pressure

d. Pressurizer Low Pressure
e. Steam Line Low Pressure
2.

Containment Spray

a. Manual Initiation
b. Automatic Actuation Relay Logic 1,2,3,4 1,2,3,4 1,2,3 1,2, 3(a) 1,2, 3(a) 1,2,3,4 1,2,3,4 2

2 trains 3

3 3 per steam line 2

2 trains B

C D

D D

B C

NA NA SR 3.3.2.5 SR 3.3.2.2 SR 3.3.2.8 SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 SR 3.3.2. I SR 3.3.2.3 SR 3.3.2.6 SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 SR 3.3.2.4 SR 3.3.2.2 SR 3.3.2.8 4.0 psig S1760 psig S5 0 0 (b) psig NA NA (a)

Pressurizer Pressure Ž 2000 psig.

(b) Time constants used in the lead/lag controller are t, Ž 12 seconds and t 2 -< 2 seconds.

Prairie Island Units I and 2 3.3.2-9 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 2 of 4)

Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

2.

Containment Spray (continued)

c.

High-High Containment Pressure

3.

Containment Isolation

a.

Manual Initiation

b.

Automatic Actuation Relay Logic

c.

Safety Injection 1,2,3 I, 2,3.4 1,2,3,4 3 sets of 2 2

2 trains E

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 B

SR 3.3.2.4 C

SR 3.3.2.2 SR 3.3.2.8 Refer to Function I (Safety Injection) for all initiation functions and requirements.

4.

Steam Line Isolation

a.

Manual Initiation

b.

Automatic Actuation Relay Logic

c.

High-High Containment Pressure 1,2 (c), 3(c) 1,2(c), 3(c) 1, 2(c), 3(c)

I/loop 2 trains 3

F SR 3.3.2.4 G

SR 3.3.2.2 SR 3.3.2.7 D

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 (c)

Except when both Main Steam Isolation Valves (MSIVs) are closed.

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 5 23 psig NA NA NA NA

!< 17 psig 3.3.2-10

ESFAS Instrumentation 3.3.2 Table 3.32-1 (page 3 of 4)

Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

4.

Steam Line Isolation (continued)

d. High Steam Flow 1, 2(c), 3 (c)(d) 2 per steam line D

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6

< 9.18E5 lb/hr at 1005 psig Refer to Function I (Safety Injection) for all initiation functions and requirements.

Coincident with Low-Low Tag High High Steam Flow 1, 2(c), 3 (c)(d) 4 1, 2(c), 3 (c) 2 per steam line D

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 D

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6

> 536°F

< 4.5E6 lb/hr at 735 psig Coincident with Safety Injection Refer to Function I (Safety Injection) for all initiation functions and requirements.

5.

Feedwater Isolation

a. Automatic Actuation Relay Logic
b. High-High Steam Generator (SG)

Water Level 1,2(e), 3(e) 1,2(e) 2 trains 3 per SG G

SR 3.3.2.2 SR 3.3.2.7 H

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 Except when both MSIVs are closed.

Reactor Coolant System (RCS) Ta,,g 520'F Except when all Main Feedwater Regulation Valves (MFRVs) and MFRV bypass valves are closed and de-activated or isolated by a closed manual valve.

Prairie Island Units 1 and 2 3.3.2-11 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 Coincident with Safety Injection and (c)

(d)

(e)

NA

< 90%

ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 4 of 4)

Engineered Safety Feature \\cVt',.,tion System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE

5.

Fecdwater Isolation (continued)

c. Safety Injection Refer to Function I (Safety Injection) for all initiation functions and requirements.
6. AuKiliarv Feedwater
a.

Automatic Actuation Relay Logic

b. Low-Low SG Water Level
c.

Safety Injection

d. Undervoltage on 4 kV Buses II and 12(21 and 22)(f
e. Trip of both Main Feedwater Pumps 1, 2,3 1, 2,3 2 trains 3 per SG J

SR 3.3.2.2 D

SR 3.3.2.1 SR 3.3.2.3 SR 3.3.2.6 NA S11.3%

Refer to Function I (Safety Injection) for all initiation functions and requirements.

1,2 2 per bus 2 per pump I

SR 3.3.2.4 SR 3.3.2.6 S76% rated bus voltage K

SR 3.3.2.4 NA Start of Turbine Driven Pump only.

This Function may be bypassed during alignment and operation of the AFW System for SG level control.

Prairie Island Units 1 and 2 3.3.2-12 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 (f0 (g)

EM Instrumentation 3.3.3 3.3 INSTRUMENTATION 3.3.3 Event Monitoring (EM) Instrumentation LCO 3.3.3 The EM instrumentation for each Function in Table 3.3.3-1 shall be OPERABLE.

APPLICABILITY:

MODES 1 and 2.

ACTIONS


N O T E S ------------------------------------------------

1.

LCO 3.0.4 is not applicable.

2.

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. --------- NOTE---------

A. 1 Restore required channel 30 days Not applicable to core to OPERABLE status.

exit temperature Function.

One or more Functions with one required channel inoperable.

Prairie Island Units 1 and 2 3.3.3-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

EM Instrumentation 3.3.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. One or more required B. I Restore required CET 30 days Core Exit Thermocouple channel(s) to OPERABLE (CET) channel(s) status.

inoperable.

AND At least 4 CET channels OPERABLE in the center region of the core.

AND At least one CET channel OPERABLE in each quadrant of the outside core region.

C. Required Action and C. 1 Initiate action in accordance Immediately associated Completion with Specification 5.6.8.

Time of Condition A or B not met.

D. -------- NOTE ---------

D. 1 Restore one channel to 7 days Not applicable to OPERABLE status.

hydrogen monitor or CET channels.

One or more Functions with two required channels inoperable.

Prairie Island Units 1 and 2 3.3.3-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

EM Instrumentation 3.3.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E.

Two hydrogen monitor E. I Restore one hydrogen 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> channels inoperable, monitor channel to OPERABLE status.

F.

Three or more required F. I Restore required channels 7 days CET channels inoperable to OPERABLE status.

in one or more quadrants.

AND Less than four CETs OPERABLE in the center region of the core.

G.

Three or more required G.1 Restore required channels 7 days CET channels inoperable to OPERABLE status.

in one or more quadrants.

AND Less than one CET OPERABLE in each quadrant of the outside core region.

H.

Required Action and H. 1 Enter the Condition Immediately associated Completion referenced in Table 3.3.3-1 Time of Condition D, E, for the channel.

F or G not met.

Prairie Island Units I and 2 3.3.3-3 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

EM Instrumentation 3.3.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME I.

As required by Required 1.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action H.1 and referenced in Table 3.3.3-1.

J.

As required by Required J. 1 Initiate action in Immediately Action H.1 and accordance with referenced in Specification 5.6.8.

Table 3.3.3-1.

Prairie Island Units 1 and 2 3.3.3-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

EM Instrumentation 3.3.3 SURVEILLANCE REQUIREMENTS


NOTE -------------------------------------------------

SR 3.3.3.1 and SR 3.3.3.3 apply to each EM instrumentation Function in Table 3.3.3-1 except Function 11. SR 3.3.3.1 and SR 3.3.3.2 apply to Function 11.

SURVEILLANCE FREQUENCY SR 3.3.3.1 Perform CHANNEL CHECK for each required 31 days instrumentation channel that is normally energized.

SR 3.3.3.2 Perform CHANNEL CALIBRATION.

92 days SR 3.3.3.3 NOTE Neutron detectors are excluded from CHANNEL CALIBRATION.

Perform CHANNEL CALIBRATION.

24 months Prairie Island Units 1 and 2 3.3.3-5 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

EM Instrumentation 3.3.3 Table 3.3.3-1 (page I of 1)

Event Monitoring Instrumentation REQUIRED CHANNELS 2

CONDITION REFERENCED FROM REQUIRED ACTION H. I I

I1.

Power Range Neutron Flux (Logarithmic Scale)

Source Range Neutron Flux (Logarithmic Scale)

Reactor Coolant System (RCS) Hot Leg Temperature RCS Cold Leg Temperature RCS Pressure (Wide Range)

Reactor Vessel Water Level Containment Sump Water Level (Wide Range)

Containment Pressure (Wide Range)

Penetration Flow Path Automatic Containment Isolation Valve Position Containment Area Radiation (High Range)

Hydrogen Monitors

12.

Pressurizer Level Steam Generator Water Level (Wide Range)

Condensate Storage Tank Level 2

2 2

2 2

2 2

2 per penetration flow path(a)(b) 2 2

2 2 per steam generator 2

15.

Core Exit Temperature

16.

Refueling Water Storage Tank Level 4 per quadrant(c) 2 (a)

Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, or check valve with flow through the valve secured.

(b)

Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.

(c)

A channel consists of one core exit thermocouple (CET).

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 FUNCTION

2.
3.
4.
5.
6.
7.
8.
9.
10.

IL.

13.

14.

I I

I I

l 3.3.3-6

4 kV Safeguards Bus Voltage Instrumentation 3.3.4 3.3 INSTRUMENTATION 3.3.4 4 kV Safeguards Bus Voltage Instrumentation LCO 3.3.4 The following 4 kV safeguards bus voltage instrumentation Functions shall be OPERABLE:

a.

Four channels per bus of the undervoltage Function;

b. Four channels per bus of the degraded voltage Function; and
c.

One automatic load sequencer per bus.

APPLICABILITY:

MODES 1, 2, 3, and 4, When associated Diesel Generator (DG) is required to be OPERABLE by LCO 3.8.2, "AC Sources-Shutdown."

ACTIONS


NOTE -------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. -------- NOTE --------

A. 1 Place channel in bypass.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Only applicable to Functions a and b.

One or more Functions with one channel per bus inoperable.

Prairie Island Units 1 and 2 3.3.4-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

4 kV Safeguards Bus Voltage Instrumentation 3.3.4 ACTIONS (continued)

CONDITION B.

NOTE----

Only applicable to Functions a and b.

One or more Functions with two channels per bus inoperable.

REQUIRED ACTION B.1 Place one channel in bypass and place one channel in trip.

AND B.2 Verify all channels associated with redundant load sequencer are OPERABLE.

COMPLETION TIME 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 6 hours Prairie Island Units 1 and 2 3.3.4-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

4 kV Safeguards Bus Voltage Instrumentation 3.3.4 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. --------- NOTE------

Only applicable in MODE 1, 2, 3, or 4.

Required Action and associated Completion Time of Condition A or B not met.

OR Function a or b or both with three channels per bus inoperable.

OR One required automatic load sequencer inoperable.

Perform SR 3.3.4.2 for OPERABLE automatic load sequencer.

AND C.2 Establish offsite paths block loading capability for associated 4 kV safeguards bus.

AND C.3 Verify offsite paths for associated 4kV safeguards bus OPERABLE.

AND C.4 Declare required feature(s) supported by the affected inoperable DG inoperable when its required redundant feature(s) is inoperable.

AND C.5 Restore automatic load sequencer to OPERABLE status.

1 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 8 hours AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> from discovery of Condition C concurrent with inoperability of redundant required feature(s) 7 days Prairie Island Units 1 and 2 3.3.4-3 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149 C.1

4 kV Safeguards Bus Voltage Instrumentation 3.3.4 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D.

Required Action and D.l Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition C not AND met.

D.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> E.


NOTE --------

E.I Enter applicable Immediately Only applicable in Condition(s) and Required MODES 5 or 6.

Action(s) of LCO 3.8.2, "AC Sources - Shutdown" Required Action and for the DG made inoperable associated Completion from inoperable 4 kV Time of Condition A or safeguards bus voltage B not met.

instrumentation.

OR Function a or b or both with three channels per bus inoperable.

OR One required automatic load sequencer inoperable.

Prairie Island Units I and 2 3.3.4-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

4 kV Safeguards Bus Voltage Instrumentation 3.3.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.4.1 Perform COT on each undervoltage and degraded 31 days voltage channel.

SR 3.3.4.2 Perform ACTUATION LOGIC TEST on each 31 days automatic load sequencer.

SR 3.3.4.3 Perform CHANNEL CALIBRATION on 24 months undervoltage and degraded voltage channels with Allowable Value as follows:

a.

Undervoltage Allowable Value > 3016 V and

_< 3224 V with an undervoltage time delay of 4 +/- 1.5 seconds.

b.

Degraded voltage Allowable Value > 3944 V and

< 4002 V with a degraded voltage time delay of 8 + 0.5 seconds and degraded voltage DG start time delay of 7.5 to 63 seconds.

Prairie Island Units 1 and 2 3.3.4-5 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Containment Ventilation Isolation Instrumentation 3.3.5 3.3 INSTRUMENTATION 3.3.5 Containment Ventilation Isolation Instrumentation LCO 3.3.5 The Containment Ventilation Isolation instrumentation for each Function in Table 3.3.5-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.5-1.

ACTIONS


NOTE-Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One required radiation A. 1 Restore the affected 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> monitoring channel channel to OPERABLE inoperable.

status.

Prairie Island Units 1 and 2 3.3.5-1 Unit 1 - Amendment No. 1 58 Unit 2 - Amendment No. 149

Containment Ventilation Isolation Instrumentation 3.3.5 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. --------- NOTE------

Only applicable in MODE 1, 2, 3, or 4 when the Containment Inservice Purge System is not isolated.

One or more Functions with one or more manual or automatic actuation trains inoperable.

OR Two required radiation monitoring channels inoperable.

OR Required Action and associated Completion Time of Condition A not met.

B.1 Enter applicable Conditions and Required Actions of LCO 3.6.3, "Containment Isolation Valves," for containment inservice (low flow) purge valves made inoperable by isolation instrumentation.

Immediately Prairie Island Units 1 and 2 3.3.5-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Containment Ventilation Isolation Instrumentation 3.3.5 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. ----------- NOTE-------

Only applicable during movement of irradiated fuel assemblies within containment when the Containment Purge or Inservice Purge Systems are not isolated.

One or more Functions with one or more manual or automatic actuation trains inoperable.

OR Two required radiation monitoring channels inoperable.

OR Required Action and associated Completion Time for Condition A not met.

C.1 Place and maintain containment purge (high flow) and inservice (low flow) purge valves in closed position.

OR C.2 Enter applicable Conditions and Required Actions of LCO 3.9.4, "Containment Penetrations," for containment purge (high flow) and inservice (low flow) purge valves made inoperable by isolation instrumentation.

Immediately Immediately Prairie Island Units I and 2 3.3.5-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Containment Ventilation Isolation Instrumentation 3.3.5 SURVEILLANCE REQUIREMENTS


NOTE Refer to Table 3.3.5-1 to determine which SRs apply for each Containment Ventilation Isolation Function.

SURVEILLANCE FREQUENCY SR 3.3.5.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.5.2 Perform ACTUATION LOGIC TEST.

31 days on a STAGGERED TEST BASIS SR 3.3.5.3 Perform COT.

31 days SR 3.3.5.4 Perform SLAVE RELAY TEST.

24 months SR 3.3.5.5 NOTE Verification of setpoint is not required.

Perform TADOT.

24 months SR 3.3.5.6 Perform CHANNEL CALIBRATION.

24 months Prairie Island Units 1 and 2 3.3.5-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Containment Ventilation Isolation Instrumentation 3.3.5 Table 3.3.5-1 (page I of I)

Containment Ventilatior Isol.,tion Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS REQUIREMENTS VALUE Manual Initiation a

(a) 3(a) 4(a) 2 SR 3.3.5.5 NA (b)

2.

Automatic Actuation Relay 1(a), 2(a), 3()

4(a) 2 trains SR 3.3.5.2 NA Logic (b)

SR 3.3.5.4

3.

High Radiation in Exhaust 1(a), 2(a), 3(a), 4(a) 2 SR 3.3.5.1 (c)

Air (b)

(I per train)

SR 3.3.5.3 SR 3.3.5.6

4.

M,-nual Containmer" Refer to LCO 3.3.2, -ESFAS Instrumentation," Function 3.a., for initiation functions Isolation and requirements.

5.

Safety Injection Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 1, for initiation functions and requirements.

6.

Manual Containment Spray Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 2.a., for initiation functions and requirements.

(a)

(b)

When the Containment Inservice Purge System is not isolated.

During movement of irradiated fuel assemblies within containment when the Containment Purge or Inservice Purge System is not isolated.

(c)

< count rate corresponding to 500 mrem/year whole body and 3000 mrem/year skin due to noble gases at the site boundary.

Prairie Island Unit 1 - Amendment No. 158 Units I and 2 Unit 2 - Amendment No. 149 3.3.5-5

CRSVS Actuation Instrumentation 3.3.6 3.3 INSTRUMENTATION 3.3.6 Control Room Special Ventilation System (CRSVS) Actuation Instrumentation LCO 3.3.6 APPLICABILITY:

The CRSVS actuation instrumentation for each Function in Table 3.3.6-1 shall be OPERABLE.

According to Table 3.3.6-1.

ACTIONS NOTE-------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions A.I Place one CRSVS train in 7 days with one channel operation and close the inoperable, opposite train outside air dampers.

Prairie Island Units 1 and 2 3.3.6-1 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

CRSVS Actuation Instrumentation 3.3.6 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. One or more Functions B. I Enter applicable Immediately with two channels Conditions and Required inoperable.

Actions for two CRSVS trains made inoperable by inoperable CRSVS actuation instrumentation.

OR B.2 Place both trains in Immediately operation.

C. Required Action and C.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time for Condition A AND or B not met in MODE 1, 2, 3, or 4.

C.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> D. Required Action and D. I Suspend movement of Immediately associated Completion irradiated fuel assemblies.

Time for Condition A or B not met during movement of irradiated fuel assemblies.

Prairie Island Units I and 2 3.3.6-2 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

CRSVS Actuation Instrumentation 3.3.6 SURVEILLANCE REQUIREMENTS


NOTE -------------------------------------------------

Refer to Table 3.3.6-1 to determine which SRs apply for each CRSVS Actuation Function.

SURVEILLANCE FREQUENCY SR 3.3.6.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.2 Perform COT.

92 days SR 3.3.6.3 NOTE---

Verification of setpoint is not required.

Perform TADOT.

24 months SR 3.3.6.4 Perform CHANNEL CALIBRATION.

24 months Prairie Island Units I and 2 3.3.6-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

CRSVS Actuation Instrumentation 3.3.6 Table 3.3.6-1 (page I of 1)

CRSVS Actuation Instrumentation APPLICABLE MODES OR OTHER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION SPECIFIED CONDITIONS CHANNELS REQUIREMENTS VALUE I.

Manual Initiation 1,2, 3,4 2

SR 3.3.6.3 NA (a)

2.

Control Room 1,2, 3,4 2

SR 3.3.6.1 5 times Radiation -

(a)

SR 3.3.6.2 background Atmosphere SR 3.3.6.4

3.

Safety Injection Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 1, for all initiation functions and requirements.

(a)

During movement of irradiated fuel assemblies.

Prairie Island Units 1 and 2 3.3.6-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

SFPSVS Actuation Instrumentation 3.3.7 3.3 INSTRUMENTATION 3.3.7 Spent Fuel Pool Special Ventilation System (SFPSVS) Actuation Instrumentation LCO 3.3.7 APPLICABILITY:

The SFPSVS actuation instrumentation for each Function in Table 3.3.7-1 shall be OPERABLE.

According to Table 3.3.7-1.

ACTIONS

-NOTE OTE...-

LCO 3.0.3 is not applicable.

S............................................................................................................

CONDITION REQUIRED ACTION COMPLETION TIME A. One channel inoperable.

A.1 Place one SFPSVS train in 7 days operation.

Prairie Island Units I and 2 3.3.7-1 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

SFPSVS Actuation Instrumentation 3.3.7 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Two channels inoperable.

B.I.1 Place one SFPSVS train Immediately in operation.

AND B. 1.2 Enter applicable Immediately Conditions and Required Actions of LCO 3.7.13, "Spent Fuel Pool Special Ventilation System (SFPSVS)," for one train made inoperable by inoperable actuation instrumentation.

OR B.2 Place both trains in Immediately operation.

C. Required Action and C. 1 Suspend movement of Immediately associated Completion irradiated fuel assemblies Time for Condition A in the fuel pool enclosure.

or B not met during movement of irradiated fuel assemblies in the fuel pool enclosure.

Prairie Island Units 1 and 2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 3.3.7-2

SFPSVS Actuation Instrumentation 3.3.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform COT.

92 days SR 3.3.7.3 Perform CHANNEL CALIBRATION.

24 months Prairie Island Units 1 and 2 3.3.7-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

SFPSVS Actuation Instrumentation 3.3.7 Table 3.3.7-1 (page 1 of I)

SFPSVS Actuat:c 1 IT,-'rumentation APPLICABLE MODES OR SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS REQUIREMENTS VALUE

1.

Fuel Pool 1,2,3,4 1 per train SR 3.3.7.1 (b)

Enclosure (a)

SR 3.3.7.2 Radiation SR 3.3.7.3 (a) During movement of irradiated fuel assemblies in the fuel pool enclosure.

(b) This value provided by the ODCM.

Prairie Island Units 1 and 2 3.3.7-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

3.4 3.4.1 RCS Pressure, Temperature, and Flow - DNB Limits 3.4.1 REACTOR COOLANT SYSTEM (RCS)

RCS Pressure, Temperature, and Flow - Departure from Nucleate Boiling (DNB)

Limits LCO 3.4.1 RCS DNB parameters for pressurizer pressure, RCS average temperature, and RCS total flow rate shall be within the limits specified below:

a. Pressurizer pressure > the limit specified in the COLR;
b. RCS average temperature *< the limit specified in the COLR; and
c. RCS total flow rate > the value specified in the COLR.

APPLICABILITY:

MODE 1.

NOTE Pressurizer pressure limit does not apply during:

a. THERMAL POWER ramp > 5% RTP per minute; or
b. THERMAL POWER step > 10% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more RCS DNB A.1 Restore RCS DNB 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> parameters not within parameter(s) to within limit.

limits.

Prairie Island Units 1 and 2 3.4.1-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Pressure, Temperature, and Flow - DNB Limits 3.4.1 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and B.1 Be in MODE 2.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.1.1 Verify pressurizer pressure is greater than or equal 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to the limit specified in the COLR.

SR 3.4.1.2 Verify RCS average temperature is less than or 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> equal to the limit specified in the COLR.

SR 3.4.1.3 NOTE Required to be performed within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after

> 90% RTP.

Verify RCS total flow rate is within the limit 24 months specified in the COLR.

Prairie Island Units 1 and 2 3.4.1-2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Minimum Temperature for Criticality 3.4.2 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.2 RCS Minimum Temperature for Criticality LCO 3.4.2 Each RCS loop average temperature (Tavg) shall be Ž_ 540'F.

APPLICABILITY:

MODE 1, MODE 2 with keff > 1.0.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Ta in one or more RCS A.1 Be in MODE 2 with 30 minutes loops not within limit.

kff < 1.0.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.2.1 Verify RCS Tavg in each loop >_ 540'F.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units 1 and 2 3.4.2-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS P/T Limits 3.4.3 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.3 RCS Pressure and Temperature (P/T) Limits LCO 3.4.3 RCS pressure, RCS temperature, and RCS heatup and cooldown rates shall be maintained within the limits specified in the PTLR.

APPLICABILITY:

At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. -------- NOTE--------

A. 1 Restore parameter(s) to 30 minutes Required Action A.2 within limits.

shall be completed whenever this Condition AND is entered.

A.2 Determine RCS is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> acceptable for continued Requirements of LCO operation.

not met in MODE 1, 2, 3, or4.

B. Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A not AND met.

B.2 Be in MODE 5 with RCS 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> pressure < 500 psig.

Prairie Island Units 1 and 2 3.4.3-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS P/T Limits 3.4.3 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIMF C. -------- NOTE ---------

C.1 Initiate action to restore Immediately Required Action C.2 parameter(s) to within shall be completed limits.

whenever this Condition is entered.

AND C.2 Determine RCS is Prior to entering Requirements of LCO acceptable for continued MODE 4 not met any time in other operation.

than MODE 1, 2, 3, or 4.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.3.1 NOTE Only required to be performed during RCS heatup and cooldown operations and RCS inservice leak and hydrostatic testing.

Verify RCS pressure, RCS temperature, and RCS 30 minutes heatup and cooldown rates are within the limits specified in the PTLR.

Prairie Island Units 1 and 2 3.4.3-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODES I and 2 3.4.4 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.4 RCS Loops - MODES 1 and 2 LCO 3.4.4 APPLICABILITY:

Two RCS loops shall be OPERABLE and in operation.

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Requirements of LCO not A.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> met.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.4.1 Verify each RCS loop is in operation.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units 1 and 2 3.4.4-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 3 3.4.5 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.5 RCS Loops - MODE 3 LCO 3.4.5 Two RCS loops shall be OPERABLE, and either:

a. Two RCS loops shall be in operation when the Rod Control System is capable of rod withdrawal; or
b. One RCS loop shall be in operation when the Rod Control System is not capable of rod withdrawal.

N O TE --------------------------------------

Both reactor coolant pumps may be de-energized for < 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to perform preplanned work activities provided:

a.

No operations are permitted that would cause introduction into the RCS, coolant with boron concentration less than required to meet the SDM of LCO 3.1.1; and

b.

Core outlet temperature is maintained at least 10°F below saturation temperature.

APPLICABILITY:

MODE 3.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One RCS loop A.1 Restore inoperable RCS 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> inoperable, loop to OPERABLE status.

Prairie Island Units 1 and 2 3.4.5-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 3 3.4.5 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B.

Required Action and B.1 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time of Condition A not met.

C.

One RCS loop not in C.1 Restore required RCS 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> operation with loop to operation.

Rod Control System capable of rod OR withdrawal.

C.2 Place the Rod Control 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> System in a condition incapable of rod withdrawal.

Prairie Island Units I and 2 3.4.5-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 3 3.4.5 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D.

Two RCS loops D.1 Place the Rod Control Immediately inoperable.

System in a condition incapable of rod OR withdrawal.

Required RCS loop AND not in operation.

D.2 Suspend operations that Immediately would cause introduction into the RCS, coolant with boron concentration less than required to meet SDM of LCO 3.1.1.

AND D.3 Initiate action to restore Immediately one RCS loop to OPERABLE status and operation.

Prairie Island Units I and 2 3.4.5-3 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 3 3.4.5 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.5.1 Verify required RCS loops are in operation.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.5.2 Verify required steam generator capable of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> removing decay heat.

SR 3.4.5.3 NOTE Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.

Verify correct breaker alignment and indicated 7 days power are available to each required pump.

Prairie Island Units I and 2 3.4.5-4 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 4 3.4.6 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.6 RCS Loops - MODE 4 LCO 3.4.6 APPLICABILITY:

Two loops consisting of any combination of RCS loops and residual heat removal (RHR) loops shall be OPERABLE, and one loop shall be in operation.

N O TES -------------------------------------

1.

All reactor coolant pumps (RCPs) and RHR pumps may be de energized for < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> per 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period provided:

a.

No operations are permitted that would cause introduction into the RCS, coolant with boron concentration less than required to meet the SDM of LCO 3.1.1; and

b.

Core outlet temperature is maintained at least 10F below saturation temperature.

2.

No RCP shall be started with any RCS cold leg temperature

  • the Over Pressure Protection System (OPPS) enable temperature specified in the PTLR unless:
a.

The secondary side water temperature of each steam generator (SG) is

  • 50'F above each of the RCS cold leg temperatures; or
b.

There is a steam or gas bubble in the pressurizer.

MODE 4.

Prairie Island Units 1 and 2 3.4.6-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 4 3.4.6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required loop A.1 Initiate action to restore a Immediately inoperable, second loop to OPERABLE status.

AND A.2 ---------

NOTE------

Only required if RHR loop is OPERABLE.

Be in MODE 5.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> B.

Both loops inoperable.

B. 1 Suspend operations that Immediately would cause introduction OR into the RCS, coolant with boron concentration less Required loop not in than required to meet SDM operation.

of LCO 3.1.1.

AND B.2 Initiate action to restore one Immediately loop to OPERABLE status and operation.

Prairie Island Units 1 and 2 3.4.6-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 4 3.4.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.6.1 Verify required RHR or RCS loop is in 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> operation.

SR 3.4.6.2 Verify required SG capable of removing decay 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> heat.

SR 3.4.6.3 NOTE---

Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.

Verify correct breaker alignment and indicated 7 days power are available to each required pump.

Prairie Island Units 1 and 2 3.4.6-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 5, Loops Filled 3.4.7 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Loops-MODE 5, Loops Filled LCO 3.4.7 One residual heat removal (RHR) loop shall be OPERABLE and in operation, and either:

a. One additional RHR loop shall be OPERABLE; or
b. One steam generator (SG) shall be capable of removing decay heat.

NOTES ------------------------------------

1.

The RHR pump of the loop in operation may be de-energized for *< 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> per 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period provided:

a.

No operations are permitted that would cause introduction into the RCS, coolant with boron concentration less than required to meet the SDM of LCO 3.1.1; and

b.

Core outlet temperature is maintained at least 10°F below saturation temperature.

2.

One required RHR loop may be inoperable for *< 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing provided that the other RHR loop is OPERABLE and in operation.

3.

No reactor coolant pump shall be started with one or more RCS cold leg temperatures !< the Over Pressure Protection System (OPPS) enable temperature specified in the PTLR unless:

a. The secondary side water temperature of each SG is !< 50'F above each of the RCS cold leg temperatures; or
b. There is a steam or gas bubble in the pressurizer.
4.

Both RHR loops may be removed from operation during planned heatup to MODE 4 when at least one RCS loop is in operation.

Prairie Island Unit 1 - Amendment No. 158 Units 1 and 2 3.4.7-1 Unit 2 - Amendment No. 149

RCS Loops-MODE 5, Loops Filled

3.4.7 APPLICABILITY

ACTIONS CONDITION MODE 5 with RCS loops filled.

A.

One required RHR loop inoperable.

AND One RHR loop OPERABLE.

ACTION REQUIRED ACTION 4

T A. 1 Initiate action to restore a second RHR loop to OPERABLE status.

OR A.2 Initiate action to restore required SG capable to remove decay heat.

4-1 B. One or more SGs not capable of decay heat removal.

AND One RHR loop OPERABLE.

i B. 1 Initiate action to restore a second RHR loop to OPERABLE status.

OR B.2 Initiate action to restore a required SG capable to remove decay heat.

COMPLETION TIME Immediately Immediately Immediately Immediately Prairie Island Units I and 2 3.4.7-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops-MODE 5, Loops Filled 3.4.7 ACTIONS (continued)

CONDITION C.

No required RHR loops OPERABLE.

OR Required RHR loop not in operation.

REQUIRED ACTION C.1 Suspend operations that would cause introduction into the RCS, coolant with boron concentration less than required to meet SDM of LCO 3.1.1.

AND C.2 Initiate action to restore one RHR loop to OPERABLE status and operation.

COMPLETION TIME Immediately Immediately Prairie Island Units I and 2 3.4.7-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops-MODE 5, Loops Filled 3.4.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.7.1 Verify required RHR loop is in operation.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.7.2 Verify required SG capable of removing decay 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> heat.

SR 3.4.7.3 NOTE Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.

Verify correct breaker alignment and indicated 7 days power are available to each required RHR pump.

Prairie Island Units 1 and 2 3.4.7-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 5, Loops Not Filled 3.4.8 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.8 RCS Loops - MODE 5, Loops Not Filled LCO 3.4.8 APPLICABILITY:

Two residual heat removal (RHR) loops shall be OPERABLE and one RHR loop shall be in operation.

N O TES --------------------------------------

1. All RHR pumps may be de-energized for *< 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> per 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period provided:
a.

No operations are permitted that would cause introduction into the RCS, coolant with boron concentration less than required to meet the SDM of LCO 3.1. 1;

b.

The core outlet temperature is maintained > 10°F below saturation temperature; and

c.

No draining operations to further reduce the RCS water volume are permitted.

2.

One RHR loop may be inoperable for _ 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing provided that the other RHR loop is OPERABLE and in operation.

MODE 5 with RCS loops not filled.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required R-R loop A.1 Initiate action to restore Immediately inoperable.

RHR loop to OPERABLE status.

Prairie Island Units I and 2 3.4.8-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 5, Loops Not Filled 3.4.8 ACTIONS (continued)

A TIN cniud CONDITION B. No required RHR loop OPERABLE.

OR Required RHR loop not in operation.

REQUIRED ACTION B.l Suspend operations that would cause introduction into the RCS, coolant with boron concentration less than required to meet SDM of LCO 3.1.1.

AND NOTE--------

A Safety Injection pump may be run as required to maintain adequate core cooling and RCS inventory.

B.2 Initiate action to restore one RHR loop to OPERABLE status and operation.

COMPLETION TIME Immediately Immediately L _________________________________________________________

Prairie Island Units I and 2 3.4.8-2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

RCS Loops - MODE 5, Loops Not Filled 3.4.8 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.8.1 Verify required RHR loop is in operation.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.8.2 NOTE Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a required pump is not in operation.

Verify correct breaker alignment and indicated 7 days power are available to each required RHR pump.

Prairie Island Units 1 and 2 3.4.8-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer 3.4.9 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.9 Pressurizer LCO 3.4.9 The pressurizer shall be OPERABLE with:

a. Pressurizer water level < 90%; and
b. Two groups of pressurizer heaters OPERABLE with the capacity of each group > 100 kW and capable of being powered from an emergency power supply.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Pressurizer water level A.I Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> not within limit.

AND A.2 Fully insert all rods.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND A.3 Place Rod Control System 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> in a condition incapable of rod withdrawal.

AND A.4 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Prairie Island Units 1 and 2 Unit I Unit 2 -

3.4.9-1 Amendment No. 158 Amendment No. 149

Pressurizer 3.4.9 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B.

One group of pressurizer B.1 Restore group of pressurizer 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> heaters inoperable, heaters to OPERABLE status.

C.

Required Action and C.I Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition B AND not met.

C.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.9.1 Verify pressurizer water level is _* 90%.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.9.2 Verify capacity of each required group of 24 months pressurizer heaters is > 100 kW.

SR 3.4.9.3 Verify required pressurizer heaters are 24 months capable of being powered from an emergency power supply.

Prairie Island Units 1 and 2 3.4.9-2 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer Safety Valves 3.4.10 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.10 Pressurizer Safety Valves LCO 3.4.10 Two pressurizer safety valves shall be OPERABLE with lift settings

> 2410 psig and _< 2560 psig.

APPLICABILITY:

MODES 1, 2, and 3, MODE 4 with all RCS cold leg temperatures > the Over Pressure Protection System (OPPS) enable temperature specified in the PTLR.

NOTE ------------------------------------

The lift settings are not required to be within the LCO limits during MODES 3 and 4 for the purpose of setting the pressurizer safety valves under ambient (hot) conditions. This exception is allowed for 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> following entry into MODE 3 provided a preliminary cold setting was made prior to heatup.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One pressurizer safety A. I Restore valve to 15 minutes valve inoperable.

OPERABLE status.

Prairie Island Units 1 and 2 3.4.10-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer Safety Valves 3.4.10 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

AND OR B.2 Be in MODE 4 with any 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> RCS cold leg temperature Both pressurizer safety

  • < the OPPS enable valves inoperable, temperature specified in the PTLR.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.10.1 Verify each pressurizer safety valve is In accordance OPERABLE in accordance with the Inservice with the Testing Program. Following testing, lift settings Inservice Testing shall be within +/- 1% (2460 to 2510 psig).

Program Prairie Island Units 1 and 2 3.4.10-2 Unit I - Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer PORVs 3.4.11 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.11 Pressurizer Power Operated Relief Valves (PORVs)

LCO 3.4.11 Each PORV and associated block valve shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS NOTES

1.

Separate Condition entry is allowed for each PORV and each block valve.

2.

LCO 3.0.4 is not applicable.

S............................................................................................................

CONDITION REQUIRED ACTION COMPLETION TIME A.

One or both PORVs A. 1 Close and maintain power 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable and capable to associated block of being manually valve(s).

cycled.

Prairie Island Units 1 and 2 3.4.11-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer PORVs 3.4.11 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B.

One PORV inoperable B.1 Close associated block 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and not capable of being valve.

manually cycled.

AND B.2 Remove power from 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated block valve.

AND B.3 Restore PORV to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OPERABLE status.

C. One block valve NOTE---------

inoperable.

Required Actions C.1 and C.2 do not apply when block valve is inoperable solely as a result of complying with Required Actions B.2 or E.2 C.1 Place associated PORV in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> manual control.

AND C.2 Restore block valve to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OPERABLE status.

Prairie Island Units 1 and 2 3.4.11-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

Pressurizer PORVs 3.4.11 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D. Required Action and D.l Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A, B, AND or C not met.

D.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> E. Both PORVs inoperable E. 1 Close associated block 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and not capable of being valvcs.

manually cycled.

AND E.2 Remove power from 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated block valves.

AND E.3 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND E.4 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> F. Both block valves NOTE---------

inoperable.

Required Action F.1 does not apply when block valve is inoperable solely as a result of complying with Required Actions B.2 or E.2 F. 1 Restore one block valve to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> OPERABLE status.

Prairie Island Units 1 and 2 Unit 1 Unit 2 -

3.4.11-3 Amendment No. 158 Amendment No. 149

Pressurizer PORVs 3.4.11 ACTIONS (continued)

CONDITION 1

REQUIRED ACTION COMPLETION TIME G.

Required Action and G.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition F not AND met.

G.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.11.1 NOTES

1. Not required to be performed with block valve closed in accordance with the Required Actions of this LCO.
2. Only required to be performed in MODES I and 2.

Perform a complete cycle of each block valve.

92 days SR 3.4.11.2 NOTE-Only required to be performed in MODES 1 and 2.

Perform a complete cycle of each PORV.

24 months Prairie Island Units 1 and 2 3.4.11-4 Unit 1 -Amendment No. 158 Unit 2 - Amendment No. 149

LTOP - RCSCLT > SI Pump Disable Temperature 3.4.12 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.12 Low Temperature Overpressure Protection (LTOP) -Reactor Coolant System Cold Leg Temperature (RCSCLT) > Safety Injection (SI) Pump Disable Temperature LCO 3.4.12 LTOP shall be provided with:

a.

A maximum of one SI pump capable of injecting into the RCS;

b.

The emergency core cooling system (ECCS) accumulators isolated;

c.

An OPERABLE Over Pressure Protection System (OPPS) with lift setting within the limits specified in the PTLR; and

d.

Two OPERABLE pressurizer power operated relief valves (PORVs).

NOTES

1. Both SI pumps may be run for _* 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> while conducting SI system testing providing there is a steam or gas bubble in the pressurizer and at least one isolation valve between the SI pump and the RCS is shut.
2.

ECCS accumulator may be unisolated when accumulator pressure is less than the maximum RCS pressure for the existing RCS cold leg temperature allowed by the P/T limit curves provided in the PTLR.

MODE 4 when any RCS cold leg temperature is *< the OPPS enable temperature specified in the PTLR and > the SI pump disable temperature specified in the PTLR.

Prairie Island Units I and 2 3.4.12-1 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149 APPLICABIIlTY:

LTOP - RCSCLT > SI Pump Disable Temperature 3.4.12 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Two SI pumps capable of A.1 Initiate action to assure a Immediately injecting into the RCS.

maximum of one SI pump is capable of injecting into the RCS.

B. An ECCS accumulator B. 1 Isolate affected ECCS 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> not isolated when the accumulator.

ECCS accumulator pressure is greater than or equal to the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.

C. Required Action and C.I Increase RCS cold leg 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion temperature to > the OPPS Time of Condition B not enable temperature met.

specified in the PTLR.

OR C.2 Depressurize affected 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ECCS accumulator to less than the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.

D. One required PORV D.1 Restore required PORV to 7 days inoperable.

OPERABLE status.

Prairie Island Units I and 2 3.4.12-2 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

LTOP - RCSCLT > SI Pump Disable Temperature 3.4.12 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. Two PORVs inoperable.

E.1 Be in MODE 5.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> OR AND Required Action and E.2 Depressurize RCS and 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion establish RCS vent of > 3 Time of Condition A, C, square inches.

or D not met.

OR OPPS inoperable.

Prairie Island Units 1 and 2 3.4.12-3 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149

LTOP - RCSCLT > SI Pump Disable Temperature 3.4.12 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.12.1 Verify a maximum of one SI pump is capable of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> injecting into the RCS.

SR 3.4.12.2 Verify each ECCS accumulator is isolated.

Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter SR 3.4.12.3 Verify PORV block valve is open for each 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> required PORV.

SR 3.4.12.4 NOTE -------------------------

Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after decreasing RCS cold leg temperature to *< the OPPS enable temperature specified in the PTLR.

Perform a COT on OPPS.

31 days SR 3.4.12.5 Perform CHANNEL CALIBRATION for each 24 months OPPS actuation channel.

Prairie Island Units 1 and 2 3.4.12-4 Unit 1 - Amendment No. 158 Unit 2 - Amendment No. 149