L-PI-10-013, Inservice Inspection Summary Report, Interval 4, Period 2, Outage 1, Refueling Outage Dates: 09-12-2009 to 11-23-2009, Unit 1, Fuel Cycle 25: 03-23-2008 to 11-23-2009
ML100550912 | |
Person / Time | |
---|---|
Site: | Prairie Island |
Issue date: | 02/22/2010 |
From: | Schimmel M Northern States Power Co, Xcel Energy |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
FOIA/PA-2010-0209, L-PI-10-013 | |
Download: ML100550912 (133) | |
Text
@ Xcel Energya I
FEB 2 2 2010 L-PI-10-013 10 CFR 50.55a U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Prairie Island Nuclear Generating Plant Unit 1 Docket 50-282 License No. DPR-42 Inservice lns~ectionSummaw Re~ort,Interval 4, Period 2, Outaae 1, Refueling Outage Dates: 09-12-2009 to 11-23-2009 Unit 1, Fuel Cvcle 25: 03-23-2008 to 11-23-2009 During the 2009 Prairie Island Nuclear Generating Plant (PINGP) Unit 1 refueling outage, an inservice inspection (ISI) examination for the second period of the fourth interval was conducted. Enclosure 1 is a copy of the IS1 examination summary report for this period.
The summary report is being submitted in accordance with the PINGP American Society of Mechanical Engineers (ASME) Code Section XI IS1 Program and is intended to satisfy the inspection reporting requirements contained in IWA-6230 of the ASME Boiler and Pressure Vessel Code.
The report identifies components examined, the examination methods used, the examination number, and summarizes the results. All anomalies were either corrected or an engineering evaluation was performed to accept "as-is" conditions. A description of repairtreplacement activities and the corresponding work order numbers are provided in Section 8 of the enclosure.
Summarv of Commitments This letter contains no new commitments and no revisions to existing commitments.
Mark A. Schimmel Site Vice President Prairie Island Nuclear Generating Plant Northern States Power Company - Minnesota 1717 Wakonade Drive East Welch, Minnesota 55089-9642 Telephone: 651.388.1 121
Document Control Desk Page 2 Enclosure cc: Administrator, Region Ill, USNRC Project Manager, Prairie Island, USNRC Resident Inspector, Prairie Island, USNRC Chief Boiler Inspector, State of Minnesota
ENCLOSURE 1 Inservice Inspection Summary Report, Interval 4, Period 2, Outage 1, Refueling Outage Dates: 09-12-2009 to 11-23-2009 Unit 1, Fuel Cycle 25: 03-23-2008 to 11-23-2009
XCEL ENERGY PRAIRIE ISLAND NUCLEAR GENERATING PLANT 1717 WAKONADE DRIVE EAST WELCH, MINNESOTA 55089 OPERATED BY:
NORTHERN STATES POWER COMPANY - MINNESOTA 414 NICOLLET MALL, MINNEAPOLIS, MN 55401 INSERVICE INSPECTION
SUMMARY
REPORT INTERVAL 4, PERIOD 2, OUTAGE 1 REFUELING OUTAGE DATES: 09-12-2009 TO 11-23-2009 UNIT 1, FUEL CYCLE 25: 03-23-2008 TO 11-23-2009 COMMERCIAL SERVICE DATE: DECEMBER 16,1973 Prepared by: Date: a/[s/-0 Reviewed by: Date: .
Reviewed by: Date: <//g 1 0 Ron Clow Reviewed by: L C G?d--
Reviewed by: , -
Program bnglneertng Supl(yv~sor,Xcel Em Date: 3. / g./ 0 Approved by: &A Dean ch tzen Program kngmeenng M Steve Skoyen I \
Date: Z-\?-Z+\~$
t I
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT 1 Table of Contents Number of Pages Section 1. Discussion Section 2. Form NIS-1, Owner's Report for Inservice Inspection 2 Section 3. IS1 Examinations 12 Section 4. IWE Examinations 1 Section 5. Pressure Tests 3 Section 6. Snubber Inservice Testing and Preservice Examinations 3 Section 7. Steam Generator Eddy Current Examination Results 1 Section 8. RepairIReplacement Activities for Fuel Cycle 25 102
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 1. Discussion
1.0 INTRODUCTION
This summary report identifies the colnponents examined, examination methods used, examination number and summarizes the results of examinations performed during the 2nd period of the 4th interval, unit 1 fuel cycle 25. The 4th inspection interval is based on the examination requirements of the ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition with 2000 Addenda.
2.0 PERSONNEL Visual and nondestructive examinations were performed by Xcel Energy/Northern States Power Company - Minnesota and Lambert Macgill & Thomas (LMT). The Hartford Steam Boiler Inspection and Insurance Company of Connecticut provided the Authorized Inspection services. Examination personnel certifications are maintained on file by Northern States Power Company - Minnesota.
3.0 INSPECTION
SUMMARY
Examination results indicate that plant system integrity has been maintained.
Section 3 contains the Class 1 and 2 components examined, examination number and summary of the examination results performed during unit 1 cycle 25. The number and percentage of examinations or tests completed are also included in this section as required by IWA-6220(f). There were no Class 1 or 2 examinations with service induced indications requiring scope expansion or repairlreplacement. There was one in scope Limited Examination of the 12 RHR Heat Exchanger report number 2009U039 entered into the site corrective action program AR 012 19016.
Section 4 contains the IWE Class MC components examined, the examination number and sumnlary of the examination results performed during unit 1 cycle 25. The second IWE interval (September 10,2008 to September 9,2018) is based on the examination requirements of ASME Section XI, Subsection IWA and IWE, 2001 Edition through the 2003 Addenda.
Section 5 contains the pressure test results. All indications of leakage were evaluated and corrective measures performed as required by IWB-3 142, IWC-3 132 and IWA-5250.
Pressure tests that have not yet been completed, but will be completed prior to the end of the period, will be documented in the 4thinterval, 2ndperiod, 2ndoutage 90 day summary report.
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 6 contains the Snubber inspection results. There were no visual snubber failures.
All snubbers that under went functional testing had satisfactory results.
Section 7 addresses the Eddy Current examination results of the 11 and 12 Steam Generators tubes.
Section 8 contains 50 RepairIReplacement activities completed under the 4th Interval during the unit 1 cycle 25.
4.0 EXAMINATON REPORTS, EQUIPMENT AND MATERIALS The insewice inspection reports in Sections 3 and 4 contain references to procedures, equipment, and materials used to complete the specific examinations. Copies of the examination reports, examination procedures, and equipment records are available from Northern States Power Company Minnesota.
Sections 3 and 4 contain several abbreviations which are identified below:
CAP = Corrective Action Process CE = Condition Evaluation GEO = Geometry, evaluation of indication OPR = Operability Recommendation IN = Information Notice IND = Indication requires further evaluation NAD = No Apparent Defects SE = Safety Evaluation WO = Work Order
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 2. NIS-1 (2 pages)
NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS (As required by the Provisions of the ASME Code Rules)
I. Owner: Northern States Power Company - Minnesota, 414 Nicollet Mall, Minneawolis, MN 55401 (Name and Address of Owner)
- 2. Plant: Prairie Island Nuclear Generating Plant, 1717 Wakonade Drive E, Welch, Minnesota 55089 (Name and Address of Plant)
- 3. Plant Unit 1
- 4. Owner Certificate of Authorization (if required) N/A
- 5. Commercial Service Date 1211611973
- 6. National Board Number for Unit NIA
- 7. Components Inspected Component or Manufacturer or Manufacturer of State or National Board Appurtenance Installer Installer Serial No. Province No. No.
Reactor Vessel Head Mitsubishi Heavy Inds. 6-VH-NI 1 5855 Reactor Vessel Creuot-Loire 686 MINN-200-51 ---
Pressurizer Westinghouse 1111 --- 68-20 11 Steam Generator Framatome ANP GVlP1291 --- 161 12 Steam Generator Framatome ANP GVlP1292 --- 162 11 Reactor Coolant Pump Westinghouse W515 --- ---
12 Reactor Coolant Pump Westinghouse W516 --- ---
I 1 RHR Heat Exchanger Joseph Oats & Sons 1817-1A --- 340 12 RHR Heat Exchanger Joseph Oats & Sons 1817-1B --- 34 1 11 RHR Pump Byron Jackson --- --- ---
12 RHR Pump Byron Jackson --- --- ---
11 Safety Injection Pump Bingham , --- --- ---
12 Safety Injection Pump Bingham --- --- -
11 Accumulator Tank Delta Southern 41038-70-1 --- 2554 A t
12 Accumulator Tank ~elta'southern 41038-70-2 --- 2555 11 Boric Acid Tank NAVCO --- --- ---
- 8. Examination Dates: 911212009 to 1 1I2312009
- 9. l nspection Period Identification: (2nd Period) 2/7/2008 to 1212012011
- 10. Inspection Interval Identification: (4th Interval) 1212112004 to 12/20/2014 U
1I.Applicable Edition of Section XI 1998 Edition with 2000 Addenda
- 12. DateIRevisionof lnspection Plan: 04/24/09, Revision 5
- 13. Abstract of Examination and Tests. Include a list of examinations and tests and statement concerning status of work required for the lnspection Plan See Sections 3 through 7
- 14. Abstract of Results of Examinations and Tests See Sections 3 through 7
- 15. Abstract of Corrective Measures See Sections 3 through 6 We certify that a) that the statements made in this report are correct, b) the examinations and tests meet the lnspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code.Section XI.
Certificate of Authorization No. (if applicable) N/A ExpirationDate Date 2 - 19 - a01ts Signed Owner c9-zL4 BY Tom Downing CERTIFICATE OF INSERVICE INSPECTION I, undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or provinces of 1I and employed by -Hartford Steam Boiler lnspection and Insurance Company- of f
-Minnesota
-Connecticut have inspected the components described in this Owner's Report during the period I I R
i:
03/23/2008 to 11/23/2009 , and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the inspection plan and as required by the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes and any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.
Commissions md as24 1 National Board, State, Province, and Endorsements I Date: Iqef@
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 3. IS1 Examinations (1 2 pages)
Page 1 of 8 Inservice Inspection Report Interval 4, Period 2, PllRF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No Comp ID Comp Desc Item Procedure MethodlReporVResults System DwgllSO Exam Date Scope Class 1 Cat 117/2009 IS1 Class 1 Category B-B 301 038 W-2 VERTICAL SHELL WELD 82.12 FP-PE-NDE- UT / 2009U038 1 NAD RC 406 301041 W-5 TOP HEAD ISHELL 82.11 FP-PE-NDE- UT 12009U037 INAD RC 406 301 077 W- 1 Tubesheet to Head 82.60 FP-PE-NDE- VT /2009V062 1 NAD VC 520 301078 W-2 Tubesheet to Head 82.60 FP-PE-NDE- VT 12009V064 1 NAD VC 520 301079 W-3 Tubesheet to Head 82.60 FP-PE-NDE- VT 12009V066 1 NAD VC 520 Class 1 Category B-D 303030 N-1 IR -
NOZZLE HX 83.160 FP-PE-NDE- VT 12009V067 1 NAD VC 520 303031 N-21R HX - NOZZLE 83.160 FP-PE-NDE- VT 12009V068 1 NAD VC 520 303032 N-31R NOZZLE - HX 83.160 FP-PE-NDE- VT 12009V069 INAD VC 520 303033 N-41R HX - NOZZLE 83.160 FP-PE-NDE- VT 12009V070 1 NAD VC 520 303035 N-51R NOZZLE - HX 83.160 FP-PE-NDE- VT 12009V071 1 NAD VC 520 303037 N-61R HX - NOZZLE 83.160 FP-PE-NDE- VT 12009V072 1 NAD VC 520 Class 1 Category B-G-1 321031 R.V NUTS NUTS (17-32) 86.10 FP-PE-NDE- VT 12009V048 1 NAD RV 510 321032 R.V. STUDS STUDS (17 - 32) 86.30 FP-PE-NO- UT / 2009U023 1 NAD RV 408
-"m**msv~,,M Page 2 of 8 lnservice lnspection Report Interval 4, Period 2, PllRF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. ltem Procedure Method/ReporVResults System DwgllSO Exam Date Scope 321033 R.V. WSHRS WASHERS (17 - 32) B6.50 FP-PE-NDE- VT 12009V047 1 NAD RV 510 Class 1 Category 6-G-2 300305 B-1 BOLTS FLANGE 87.50 FP-PE-NDE- VT 12009V024 INAD RC 510 300479 B-1 FLANGE BOLTS B7.50 FP-PE-NDE- VT 12009V026 1 NAD VC 510 300651 B-1 VALVE BOLTING 87.70 FP-PE-NDE- VT 12009V003 1 NAD RC 151-24 911 112009 PSI 510 FP-PE-NDE- VT 12009V049 1 NAD RC ISI-24 9/24/2009 IS1 510 300808 B-2 BOLTS B7.50 FP-PE-NDE- VT 12009V029 1 NAD VC 510 ISI-29B 9/17/2009 IS1 151-298 9/19/2009 PSI 30091 8 8-2 VALVE BOLTING 67.70 FP-PE-NDE- VT 12009V002 1 NAD SI 151-308 911112009 PSI 510 301 043 B-1 MANWAY STUDS 87.20 FP-PE-NDE- VT 12009V039 1 NAD RC 510 305702 B-2 Valve Bolting (Installed RC-10-1 as of 87.70 FP-PE-NDE- VT 12009V032 1 NAD RC 11115/04) 510 Class 1 Category 6-M-2 302621 V- I VALVE INT SURFACES FP-PE-NDE- VT 12009V004 1 NAD RC 9/10/2009 PSI 530 FP-PE-NDE- VT 12009V046 INAD RC 9/25/2009 IS1 530 Class 1 Category B-P 370026 SP 1392 Unit 1 RCS Bolting Inspection 815.00 FP-PE-NDE- VT 12009V074 1 NAD RC, SI. VC, RH 520 11/12/2009 IS1 206901 and 1206902
Page 3 of 8 Inservice Inspection Report Interval 4, Period 2, PI1RF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12116173
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item Procedure Method/Report/Results System DwgllSO Exam Date Scope Class 1 Category F A 300001 H-2 SNUBBER Fl.10~ FP-PE-NDE- VT 12009V019 1 NAD RC 530 300023 H-4 LATERAL RESTRAINT Fl.lOb FP-PE-NDE- VT 12009V028 1 NAD RC 530 300167 H-8 ROD Fl.lOa FP-PE-NDE- VT 12009V036 1 NAD RH 530 Fl.10~ FP-PE-NDE- VT 12009V030 1 NAD RC 9/19/2009 PSI 530 300613 H-9 RIGID RESTRAINT LUGS Fl.lOa FP-PE-NDE- VT 1 2009V037 1 NAD RH 530 300659 H-1 RUP'T RESTRAINT Fl.lOb FP-PE-NDE- VT 12009V038 1 NAD RC 530 300786 H-3 SPRING HANGERICLAMP Fl.10~ FP-PE-NDE- VT 12009V017 1NAD RC 530 300787 H-1 HYDRSNUBBER Fl.10~ FP-PE-NDE- VT 12009V020 1 NAD RC 530 300839 H-2 ANCHOR Fl.lOb FP-PE-NDE- VT 12009V025 INAD VC 530 I
300939 H-2 RUPTURE RESTRAINT Fl.lOb FP-PE-NDE- VT 12009V021 1 NAD RC 530 303039 H-1A FLOORSTAND F1.40 FP-PE-NDE- VT 12009V057 1 NAD VC 530 12009V058 / IND VC 10/27/2009 IS1 2009V0611 NAD VC 1012912009 PSI 320212 H-1 B Snubber BIClamp Fl.10~ FP-PE-NDE- VT 12009V031 1 NAD RC 9/19/2009 PSI 530 Class 1 Category R-A 300012-RI W-9 -
ELBOW PIPE R1.ll-2 FP-PE-NDE- UT 12009U013 1 NAD RC 402
Page 4 of 8 Inservice Inspection Report Interval 4, Period 2, PI1RF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item Procedure MethodlReport/Results System DwgllSO Exam Date Scope 300013-RI W-8 -
PIPE ELBOW R1.ll-2 FP-PE-NDE- UT 12009U012 1 NAD RC 402 300014-RI W-7 -
45" ELBOW PIPE R1.ll-2 FP-PE-NDE- UT 12009U011 1 NAD RC 402 300015-RI W-6 -
PIPE 45" ELBOW Rl.11-2 FP-PE-NDE- UT 12009U010 1 NAD RC 402 L~mfted SI ISi-2 9/13/2009 OWN qufred by ASME and are not commltrnenh No relief request or other actton is required to 300217-Rl W-13 -
PIPE 45" ELBOW R1.20-4 FP-PE-NDE- UT 12009U006 / NAD RC 402 300218-Rl W-14 45" ELBOW - PIPE R1.20-4 FP-PE-NDE- UT 12009U007 1 NAD RC 402 300248-Rl W-4 PIPE - ELBOW R1.20-4 FP-PE-NDE- UT 12009U008 1 NAD RC 402 300249-Rl W-5 ELBOW - PIPE R1.204 FP-PE-NDE- UT 12009U009 1 NAD RC 402 30031 1-RI W-6 PIPE - ELBOW R1.204 FP-PE-NDE- UT 12009U032 1 NAD RC 402 300368-Rl W-20 PIPE - ELBOW R1.204 FP-PE-NDE- UT 12009U033 1 NAD RC 402 300369-Rl W-2 1 ELBOW - PIPE R1.20-4 FP-PE-NDE- UT 12009U034 1 NAD RC 402 300370-Rl W-22 PIPE - ELBOW R1.20-4 FP-PE-NDE- UT 12009U035 1 NAD RC 402 300403-Rl W-5 PIPE - ELBOW Rl.11-2 FP-PE-NDE- UT 12009U017 1 NAD RC 402 300418-Rl W-2 ELBOW - PIPE R1.20-4 FP-PE-NDE- UT 12009U020 1 NAD VC 402 I
1 300435-Rl W- I PIPE - ELBOW R1.20-4 FP-PE-NDE-402 UT 12009U016 1 NAD VC
"#m--~-xL~s--*w*
Page 5 of 8 Inservice Inspection Report Interval 4, Period 2, PllRF02009 I.Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item Procedure MethodlReport/Results System DwgllSO Exam Date Scope 300438-Rl W-12 ELBOW - PIPE R1.20-4 FP-PE-NDE- UT 12009U022 1 NAD VC 402 300439-Rl W-1 1 PIPE - ELBOW FP-PE-NDE- UT 12009U021 1 NAD 151 402 300573-Rl W-2 ELBOW - PIPE FP-PE-NDE- UT 12009U027 1 NAD IS!
402 300640-Rl W-3 PIPE - ELBOW FP-PE-NDE- UT 12009U026 I NAD 151 402 300766-Rl W-4 ELBOW - PIPE FP-PE-NDE- UT 12009U029 1 NAD IS!
402 300767-Rl W-5 PIPE - ELBOW FP-PE-NDE- UT 12009U036 1 NAD 151 402 300890-Rl W-6 BENT PIPE - REDUCER FP-PE-NDE- UT 12009U019 1 NAD 151 402 300909-Rl W-6 ELBOW - PIPE FP-PE-NDE- UT 12009U014 1 NAD IS!
402 30091 1-RI W-7 PIPE - ELBOW FP-PE-NDE- UT 12009U015 1 NAD 151 402 300955-Rl W-6 ELBOW - PIPE FP-PE-NDE- UT 12009U025 1 NAD 151 402 302912-Rl W-7 PIPE 1 PIPE FP-PE-NDE- UT 12009U024 1 NAD 151 402 Class 1 Category T.S.
301030 28-78P678 RCP Flywheel SWI NDE-MT-1 MT 12009M0011 NAD AUG Class 2 Category C-C 321288 H-1IIA Int. Attach[SEISMIC RESTRAINT] C3.20 SWI NDE-MT-1 MT 12009M002 1 NAD FW
-*L ---a- -&*a Page 6 of 8 Inservice Inspection Report interval 4, Period 2, PllRF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12116173
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item Procedure MethodlReport/Results System DwgllSO Exam Date Scope 321391 H-1lIA Int. Attach[Anchor Strut] C3.20 SWI NDE-PT-1 PT 12009P001 1 NAD RH ISI-53C 9/29/2009 IS1 Class 2 Category C-H 370002 SP 1168.4A Component Cooling System Pressure Test C7.00 FP-PE-NDE- VT 12009V060 1 NAD CC Class 2 520 370010 SP 1168 10 RHR System Pressure Test C7 00 FP-PE-NDE- VT 12009V059 1 IND RH 520 Comments Dry bor~ca c ~ d~nd~catlonD~sposd~oned acceptable as 8s on AR1184495 370012 SP 1168.12 SI Accumulator System Pressure Test C7.00 FP-PE-NDE- VT 12009V065 1 NAD SI 520 370015 SP 1168 15 Post LOCA Hydrogen Control System C7 00 FP-PE-NDE- VT 12009V055 INAD HC Pressure Test 520 I 370018 SP 1168.19 Unit 1 Sampling System Pressure Test C7.00 FP-PE-NDE-520 VT 12009V063 1 NAD 370021 SP 1168.23 Reactor Coolant Gas Vent System C7.00 FP-PE-NDE- VT 12009V073 1 NAD RV Pressure Test 520 370024 SP 1168.25 Auxiliary Building Trench Pressure Test C7.00 FP-PE-NDE- VT 12009V013 1 NAD SI. RH, CS, CA 520 370088 SP 1168.88 Cooling Water System to Unit 1 FCUs C7.00 FP-PE-NDE- ~r I2 0 0 9 ~ 0 1 2INAD CL Pressure Test 520 Class 2 Category F A 301288 H-1 SEISMIC RESTRAINT F1.20a FP-PE-NDE- VT 12009V016 1 NAD 530 VT 12009V050 IIND ned on W0390709 302242 H-6 HYDRSNUBBER F1.20~ FP-PE-NDE- VT 12009V040 INAD RH 9/22/2009 PSI 530 302987 H-4 SNUBBER 4 F1.40 FP-PE-NDE- VT 12009V052 1 NAD SG 913012009 PSI 530 303007 H-4 SNUBBER 4 F1.40 FP-PE-NDE- VT 12009V053 1 NAD SG 913012009 PSI 530
Page 7 of 8 Inservice Inspection Report Interval 4, Period 2, PllRF02009 I.Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item procedure Method/Report/Results System DwgllSO Exam Date Scope 305104 H-3 RODICLAMP F1.20a FP-PE-NDE- VT 12009V008 INAD SI ISI-99A 9/13/2009 IS1 530 305287 H-1 BOX SUPPORT F1.20a FP-PE-NDE- VT 12009V018 INAD SI 530 305308 H-3 SNUBBER F1.20~ FP-PE-NDE- VT 1 2009V054 INAD SI ISI-98C 9/26/2009 PSI 530 305641 H-12 Seismic Restraint FP-PE-NDE- VT 12009V027 1 NAD ISI-52A 530 305643 H-2 Single Spring FP-PE-NDE- VT 12009V015 1 NAD ISI-69A 530 315936 H-1 Single Spring Base Support FP-PE-NDE- VT 12009V044 1 NAD ISI-55C 530 Class 2 Category R A 301431-Rl W-ZLSU -
PIPE ELBOW FP-PE-NDE- UT 12009U028 1 NAD ISI-89A 402 301692-Rl W-23 Pipe - Sweepolet FP-PE-NDE- UT 12009U031 1 NAD ISI-69 401 302264-Rl W-13 PIPE - ELBOW FP-PE-NDE- UT 12009U001 1 NAD 151-918 402 303043-Rl W-3 REDUCER PIPE- FP-PE-NDE- UT 1200911002 1 NAD ISI-96 402 305092-Rl W-2 1 PIPE - ELBOW FP-PE-NDE- UT 12009U005 1 NAD ISI-100A 402 305094-Rl W-23 PIPE - ELBOW FP-PE-NDE- UT 12009U004 1 NAD 151-1OOA 402 305095-Rl W-24 ELBOW - PIPE FP-PE-NDE- UT I200911003 1 NAD ISI-lOOA 402 305267-Rl W-10 PIPE - ELBOW FP-PE-NDE- UT I200911030 1 NAD ISI-98A 402 Class 3 Category D-A 322413 CWH- Int. Attach[Floor Restraint] D1.10 FP-PE-NDE- VT 12009V023 1 NAD CW 525NIA 510
--La)*"
Page 8 of 8 Inservice Inspection Report Interval 4, Period 2, PllRF02009
- 1. Owner: Northern States Power Company Minnesota 4. Owner Certificate of Authorization (If Req.):
414 Nicollet Mall, Minneapolis, MN 55401 5. Commercial Service Date: 12/16/73
- 2. Plant: Prairie Island Nucleat Generating Plan 6. National Board Number for Unit: NIA 1717 Wakonade Drive East, Welch, MN 55089
- 3. Plant Unit: 1 Summary No. Comp. ID Comp. Desc. Item Procedure Method/ReporVResults System DwgllSO Exam Date Scope 322712 CCH-36lIA Int. Attach[Seismic Anchor] D l .20 FP-PE-NDE- VT 12009V009 1 NAD CC ND-1-3-218 9/13/2009 IS1 510 322743 CCH-374lIA Int. Attach[Strut] 01.20 FP-PE-NDE- VT / 2009V007 1 NAD CC 510 Class 3 Category 0-B 370078 SP 1168.86 Cooling Water System to Unit 1 FCUs D2.10 FP-PE-NDE- VT / 2009V0411 NAD CL Pressure Test 520 Class 3 Category F A 312413 CWH-525A Floor Restraint F1.40 FP-PE-NDE- VT 12009V022 1 NAD CW ND-1-3-15 9/17/2009 IS1 530 312425 CWH-405 Snubber /Clamp F1.30~ FP-PE-NDE- VT / 2009V051 1 NAD ND-1-3-17 9/26/2009 PSI 530 312436 CWH-436 Snubber F1.30~ FP-PE-NDE- VT 12009V014 1 NAD ND-1-3-18 9/16/2009 PSI 530 ND-1-3-91 9/12/2009 IS1 312691 SVH-54 Double Strut /Clamp F1.30a FP-PE-NDE- VT 12009VOll 1 NAD 530 312712 CCH-36 Seismic Anchor F1.30b FP-PE-NDE- VT 12009V010 1 NAD 530 312743 CCH-374 Strut F1.30a FP-PE-NDE- VT 12009V006 1 NAD 530 312748 CCH-399 Spring Base F1.30~ FP-PE-NDE- VT /2009V045 1 NAD 530 312772 CCH-380 Snubber /Clamp F1.30~ FP-PE-NDE- VT 12009V056 1 NAD 530 Class NC Category HVY LDS 305421 RV lnternals RV lnternals Lifling Rig NUREG612 SWI NDE-MT-1 MT 12009M003 1 NAD ISI-HVY-LDS-2 911912009 AUG Lifting Rig
Prairie Island Nuclear Plant Completion Code Compliance Summary - 4th Interval IS1 - Code Edition - 1998 Edition, 2000 Addenda Number Percent Total# Total Number Comp. Percent Total Total Required for Required Sched for Comp. 1st 2nd Req'd for Comp. To % Comp.
Cat. Item No. Code Case Population Interval for Interval Interval Period Period 1st Period Date To Date Notes B-A B-A Total:
B1.ll B1.30 RR-4-1 N-623 3
1 4
100%
100%
3 1
4 3
4 1
0 0
0 0
0 0
0%
0%
0%
0 0
0 I I 0%
O*
0%
Deferral to end of interval allowed per IWB-2500-1 Deferral to end of interval allowed per N-623 B-B 82.1 1 2 100% 2 0 1 1 2 100%
B-B 82.12 2 100% 2 0 1 1 2 100%
B-B 82.40 4 50% 2 2 0 0 0 0%
B-B 82.60 RR-4-2 3 0 50% VT-2 each outage per R R 4 2 . Not included in count.
Total: 11 6 2 2 2 16-50% 4 67% Total Percentage completed excludes 82.60 B-D 83.100 N-648-1 6 100% 6 6 0 0 0 Deferral to end of interval allowed per IWB-2500-1 B-D 83.120 5 100% 5 5 0 0 0 B-D 83.140 4 100% 4 0 4 0 0 4 B-D B-D Total:
83.160 83.90 RR-4-2 6 6
27 100% 6 15 6
17 0
4 0
0 16-50%
0 0
4 II W - 2 each outage per R R 4 2 . Not included in count.
Total Percentage completed for 83.120 and 83.140. Other items NA.
B-G-I B6.10 3 100% 3 1 1 1 0-34% 2 I I67%
Deferral to end of interval allowed per IWB-2500-1. Each component is a set of 16.
Deferral to end of interval allowed per IWB-2500-1. Each component is a set of 24 RCP bolts. Only required when B-G-I B6.180 0% required by B-L-2.
B-G-I B6.190 2 25% 1 0 0 0 0 0 I 0% 10nly required when disassembled Deferral to end of interval allowed per IWB-2500-1. Each B-G-I 86.30 67% component is a set of 16.
Deferral to end of interval allowed per IWB-2500-1. Each B-G-I B6.40 OOh component is a set of 48.
B-G-1 Total:
86.50 3 14 100% 3 12 1
4 1
3 1
3 2
6 67%
I Deferral to end of interval allowed per IWB-2500-1. Each component is a set of 16.
211 91201 0 Scheduleworks V. 8.1 Page 1 - 4
irie Island Nuclear Plant de Compliance Summary - 4th In IS1 - Code Edition - 1998 Edition, 2000 Addenda Number Percent Total# Total Number Comp. Percent Total Total Required for Required Sched for C o m ~ 1st
. 2nd Rea'd for Comb. To % Comb.
Cat. Item No. Code Case Population Interval for interval Interval ~eiod Period 1st Period ate To ~ a i e Notes B-G-2 B7.50 11 0% 0 4 3 4 100% 7 1 0% ]only required when required by B-L-2 4
19 0%
25%
0 5
0 7
1 5
0 1
1 100%
1 6 I 112%
Only required when required by 6-M-2 Total Percentage completed for 87.20 and 87.30. Other Total: 39 7 14 10 6 16-50% 16 100% lems NA.
B-K 810.10 6 66.6% 2 2 1 0 1 25% Only one attachment of one of multiple vessels 8-K 810.20 46 10% 5 3 2 0 16-50% 2 40%
B-K B10.30 3 10% 1 1 0 0 0% 0 0%
Total: 55 8 6 3 0 16-50% 3 30%
Total: 1 1 1 0 0 0 Limited to one pump in each group of similar pumps. Only B-L-2 B12.20 0% requiredwhen disassembled.
Total: 0%
Total: 19 0 2 1 0 1
1 I I I
0%
0%
I Examination only required when valve disassembled and limled to one from each group.
Accessible areas of RV interior VT-3 inspected once each B-N-I 813.10 1 100% 1 0 1 0 0% 1 100% period.
Total: 1 1 0 1 0 0% 1 100%
Total: 2 2 2 0 0 0-100%
0 0
0 I I 0%
O%
Deferral to end of interval allowed per IWB-2500-1 Deferral to end of interval allowed per IWB-2500-1 Total: 1 1 1 0 0 0 I O % I 211912010 Scheduleworks V. 8.1 Page 2 - 4
Number Percent Total# Total Number Comp. Percent Total Total Required for Required Sched for Comp. 1st 2nd Req'd for Comp. To % Comp.
Cat. Item No. Code Case Population Interval for Interval Interval Period Period 1st Period Date To Date Notes B-0 814.10 60 10% 6 0 0 0 0 I 0%
IDeferral to end of interval allowed per IWB-2500-1 Total: 60 6 0 0 0 0 0%
B-P B15.00 Multiple 2 50% Class 1 pressure tests performed each outage.
Total: 2 50%
C-A C1.10 0 0% Welds at gross structural discontinuity only.
C-A C1.20 2 100%
C-A C1.30 1 100%
I I ~ omultiple r vessels such as SG required Total: 8 4 1 2 1 3 75% exams may be limited to one vessel.
C-B C2.21 2 20% 1 1 0 0 0 0%
C-B C2.22 2 20% 1 1 0 0 0 0%
C-B C2.31 4 50% 2 1 1 0 1 50%
For multiple vessels of similar design exams Total: 8 4 3 1 0 1 25% may be limited to one vessel C-C C3.10 12 2 1 1 0 1 C-C C3.20 115 10% 12 7 3 2 5 C-C C3.30 16 10% 2 2 0 0 0 C-C C3.40 2 0% 1 1 0 0 0 Total: 145 17 11 4 2 16-50% 6 C-H C7.00 N-533-1 14 1 50% I ~ l a s 2s pressure tests scheduled once each period.
D-A 01.10 8 50% 4 2 1 1 2 D-A 01.20 82 10% 9 5 2 2 4 D-A D1.30 6 10% 1 1 0 0 0 Total: 97 14 8 4 3 7 211912010 Scheduleworks V. 8.1 Page 3 - 4
Prairie Island Nuclear Plant ompletion Code Compliance Summary - 4th Interval IS1 - Code Edition - 1998 Edition, 2000 Addenda Number Percent Total# Total Number Comp. Percent Total Total Required for Required Sched for Comp. 1st 2nd Req'd for Comp. To % Comp.
Cat. Item No. Code Case Population Interval for Interval Interval Period Period 1st Period Date To Date Notes I I D-B D2.10 Multiple 7 50% Class 3 pressure tests scheduled once each period.
Total: 7 50%
F-A F-A F-A F-A F-A F-A F-A F-A F-A F-A Total:
R-A R1.ll-2 1-RR-45 83 25% 21 6 9 6 15 R-A R1 . I 1-5 1-RR-45 46 10% 6 1 4 1 5 R-A R1.16-2 1-RR-45 2 25% 1 0 1 0 R-A R1.16-5 1-RR-45 4 10% 1 0 0 0 R-A R1.18-6 1-RR-45 8 0% 0 0 0 0 0 R-A R1.19-5 1-RR-45 4 10% 1 1 0 0 0 R-A R1.20-4 1-RR-45 774 10% 78 31 22 26 R-A R1.20-6 1-RR-45 672 0% 0 0 0 0 R-A R1.20-7 1-RR-45 28 0% 0 0 0 0 0 Total: 1621 108 39 36 33 69 Page 4 - 4
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 4. IWE Examinations (1 page)
The IWE program has entered the second ten-year inspection interval (9/10/2008 through 9/9/2018). Inspections will be performed in accordance with the requirements of ASME Section XI, Subsection IWA and IWE, 2003 Addenda as required and modified by the Code of Federal Regulations, Title 10, Part 50.55a.
All unit 1 IWE inspections have been deferred to the second outage of the first period and will be reported in the cycle 26 (1R27) summary report.
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 5. Pressure Tests (3 pages)
The following class 1 and class 2 scheduled pressure tests were conducted during Unit I cycle 25. All indications were evaluated and corrective measures performed as required by IWB-3 142 and IWA-5250.
Code Class 1 & 2 Pressure Tests Unit 1 Cycle 25 System CategoIrv 1 Procedure a I Class ,I GYO# Completion I
Dnqntnr I SP 1070 Reactor I I\ G Q b L V I pa-I--&
bUUldl I1 I B-P 1 Coolant System 1 1 1 316697 1 1111212009 /
Integrity yest Dnentnw-I\cabrul SP 1421 Bare Metal
\I..---I V ebbel I B-P 1 Visual Exam of I 1 1 378208 1 1012112009 1 Bottom RV Head DP C I \IP u,
SP 1392 Unit 1 I \ W , -1, nn,cia, ar
,v, ,1 B-P, C-H 1 Insulated Bolted 1 112 1 316709 1 11/17/2009 1 Connection Inspection P-,-.I;-~ SP 1168.8B Cooling uuulll 1 y
,,,-A_-
vvawr 1 C-H, D-B / Water to Unit 1 FCU'S 1 213 1 333258 1 9/28/2009 1 Pressure Test Safety SP 1168.13 Safety Inin~tinn C-H Injection System 2 372198 In Progress*
Component Component Cooling C-H 371660 911312009 Cooling System Class 2 Pressure Test Main & Aux SP 1168.17 C-H Feedwater System 2 372200 In Progress*
Feed Pressure Test Residual Heat SP 1168.10 RHR C-H 2 372194 1012812009 Removal System Pressure Test SP 1168.11 Main Main Steam C-H Steam System 2 372196 In Progress*
Pressure Test Safety SP 1168.12 SI Injection C-H Accumulator System 2 372197 11/3/2009 Accumulator Pressure Test SP 1168.15 Post Hydrogen LOCA Hydrogen C-H 2 372199 1011212009 Control Control System Pressure Test
Chemical SP 1168.16 Chemical Volume C-H and Volume Control 2 381209 In Progress*
Control System Pressure Test System Main and SP 1168.17 Aux Feed C-H Feedwater System 2 372200 In Progress*
Pressure Test Sampling C-H SP 1168.19 2 373578 11/5/2009 System Reactor SP 1168.23 RCGVS Coolant Gas C-H 372201 11/4/2009 Vent System System Pressure Test Aux Building SP 1168.25 Auxiliary C-H Building Trench 2 380787 911512009 Trench Pressure Test
- The class 2 portions of these pressure tests are in progress
. - and will be completed before the end of the period.
Boric Acid Leakage Identified at Bolted Connections Eighteen code class components were identified as having boric acid indications at bolted connections in cycle 25. Per the H2 Boric Acid program document, boric acid indications found as a result of a boric acid inspection are evaluated as if found during a pressure test. In each instance corrective actions were initiated and the component was evaluated and found suitable for continued service or corrected prior to continued service.
In accordance with Code Case N-566-1 "Corrective action for Leakage Identified at Bolted Connections" evaluations considered:
The number and service age of the bolts; Bolt and component material; Corrosiveness of process fluid; Leakage location and system function; Leakage history at the connection or other system components; Visual evidence of corrosion at the assembled connection.
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 6. Snubber Inservice Testing and Preservice Examinations (3 pages)
Appendix A for SP 1225 Summary description of snubber visual inspection and Functional testing for 1R26 During review of the examination summary, typographical errors were identified. These are corrected and initialed in the following pages. The error has been entered into the corrective action program (ARO 1219430).
There were a total of 23 snubbers tested in 1R26, all were functional tests. All testing was SAT. Eighteen of the twenty-three were Basic-PSA hydraulic snubbers, these snubbers had spares rebuilt and tested SAT prior to installation. The Basic-PSA snubbers that were removed were tested in the as found condition and all were also SAT. There was one ITT Grinnel snubber that was tested, rebuilt and then re-installed, which passed functional testing as well. There were two Paul Monroe snubbers that were functionally tested SAT and re-installed. Finally two steam generator valve blocks were replaced with re-built spares, all testing the pre-install of the rebuilt and the as found of the valve blocks removed were tested SAT. There was no scope expansion from failed testing on sample population during 1R26. Most of the testing was performed by a Basic-PSA field representative, with a few tests performed by in-house maintenance after Basic-PSA field rep departure.
The visual inspections SP 1171 and TP 1535 were performed by LMT. There was no scope expansions from the conditions found on these inspections. All cylinders had hydraulic fluid and issues identified during the visual inspections, as evidence of leaking, were inspected by Snubber Engineer and all instances did not depict a failure. All snubbers had acceptable level of fluid. Any leaking identified was attributed to fluid from overfull reservoirs and thermal movement. Those snubbers identified during the inspections with no movement or rotation, were inspected by the snubber engineer and those that were accessible, rotation and movement was restored. The snubbers that were inaccessible were not inspected. No snubbers were found locked up.
Seven snubbers were identified as missing its ID tag. AR 01204801 was initiated to capture and correct this at next opportunity.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT SURVEILLANCE PROCEDURE NUMBER:
SP 1225 SP SNUBBER FUNCTIONAL TESTS REV: 12 Page 8 of 12 Table 2 Snubber Functional Test Summary SNUBBER FUNCTIONAL PI # PI # TEST NO. TEST WO REMOVED REPLACED RESULTS
PRAIRIE ISLAND NUCLEAR GENERATING PLANT SURVEILLANCE PROCEDURE NUMBER:
SP 1225 SNUBBER FUNCTIONAL TESTS REV:
Pane 9 of 12
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 7. Steam Generator Eddy Current Examination Results.
Examination Category B-Q, Steam Generator Tubing, is reported per the requirements of the Plant Technical Specifications.
NSPM INSERVICE INSPECTION PRAIRIE ISLAND UNIT 1 CYCLE 25
SUMMARY
REPORT Section 8. RepairIReplacement Activities for Cycle 25 (1 02 pages) 50 NIS-2 forms are attached which identify Prairie Island Unit 1 Repair1 Replacement Activities during fuel cycle 25,4"' IS1 Interval. The gaps in item number sequence are due to cancelled or unfinished RIR activities.
ilt spares from,.--
,* ,,"", , , -, --,-"--~
stock.,~",-wmm,--,--"-,, ,
pare charging pump packing assem Flanges, Discharge Elbow, and Connector Pipe. 1 reviously rebuilt spare.
",_ - - --" , ----- -- -- -- ---- I --- -
ed flexib/evibr%ion s~oolsand associated ZH 3
ith rebuilt spares -"*---..-----.'..-.-,,"
-."-."-."-","".*"-" from stock. * """"-.*--
1 I'-,.-....--.-".-m-"m-llll~"l.~l__-_--^" ",.."l"-ll" r"l--.,- ,,,".X,III",-"'XX,ll I seal W"*.~ --*-*-,..
gland plate.
~**","..,- --*"<A " ""
R H
-,..*,","",,,T,",.""",-M*--m ", .. i , .""-,*"
2
- ,,",,--.-+
A F 2 d bonnet assembly and body to bonnet 064- fittinss.
1-1 3 T~eplaceddisc.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company, LLC Date 612612008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 332275-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components
' Corrected, 7Component Name Spare Charging Pump Manufacturer Name Goulds Serial #
-I-Other ID Yr Built Removed, or Installed Corrected ASME Code Stamp
- 7. Description of Work Rebuilt spare charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic U Pneumatic r]
Nominal Operating Pressure 1]
Exempt m Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items Ithrough 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of Chis form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-001
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date 6h d /df .
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 153Adcf3 to >JoJur308 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions md 021q2q National Board, Province and Endorsements 50 , %&
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/22/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 352072-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System ZH Code Class 3
- 5. (a) Applicable Construction Code B31. I 1967 EditionlAddenda Addenda nla Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l Bd # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Flexible Spool in Chilled Water Installed LA Pipe
- 7. Description of Work Replaced flexible vibration spools and associated flange fasteners.
- 8. Tests conducted: Hydrostatic Pneumatic 0 Nominal Operating Pressure 0 Exempt Other 0 Pressure psi Test Temp. O F Other: nla NOTE:Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY i
ITEM 1-25-003
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requrrements of the ASME Code,Section XI.
Type Code Symbol Stamp b/&
Certificate of Auth .zat' Expiration Date Signed pi? H "IA !? , ASME Program Engineer Owner or Owner's Designee , Title Date //aa?/O 7 .
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 28 rnw (D8 to &2F@CD4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions rv\Jd . w ~
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company, LLC Date 41212008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 356001-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump pack~ng nla spares Corrected 1- J assemblies
- 7. Description of Work Rebuilt spare charging pump packing assemblies 19, 20, 21.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure 1-1 Exempt Other 0 Pressure psi Test Temp. 0 F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp A/&
Expiration Date
, ASME Program Engineer Date *//!
/ I
&/
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 3/~s/o8 to and state that to the best of my knowledge and belief, the Owner has perforrried examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of Commissions 0~q3-3I /Q.B,d,Z,,dS Inspector's Signature National Board, Province a i d Endorsements Date &.d , do&
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company, LLC Date 6/25/2008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 354651-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System ZH Code Class 3
- 5. (a) Applicable Construction Code B31. I 1967 Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None 6, ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Flexlble Spool in Chilled Water 075-012 Installed L1 Plpe
- 7. Description of Work Replaced flexible vibration spools and associated flange fasteners.
- 8. Tests conducted:
Other Pressure psi Test Temp. 0 F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-005
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp /&
Certificate of Autho Signed Date ~/a<hf.
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of ta and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 23APRo8 to . ;55dod08 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
(T'-'yz-n.Q$ Commissions ~d 0219r'-t spector's signature National Board, Province and Endorsements Date M 25 lL
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company, LLC Date 512212008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 358040-02 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 Chargtng Pump Ajax 6498 145-042 Corrected 1 1
- 7. Description o f Work Replaced charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic LJ Pneumatic L] Nominal Operating Pressure n Exempt
[d Other r]
Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp ,v"k/a Expiration Date w
, ASME Program Engineer Date sL</&p Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of M i m t a and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period s-2-& to S/a?/oB and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
J a i k L 4 Commissions I%/ oSYSj/ ~ , d , d ~ d . 5 '
Inspector's Signature National Board, Province aAd Endorsements Date A+ a t &8
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company, LLC Date 811512008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch M~nnesota55089 359106-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l Bd # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 BATP GOLI~~S 792A190-1 145-611 Corrected 11
- 7. Description of Work Replaced the mechanical seal gland plate.
- 8. Tests conducted: Hydrostatic n Pneumatic Nominal Operating Pressure n Exempt m Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-007
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and t h ~ sconforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiratron Date
, ASME Program Engineer Date gh~/$f Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province o f p and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period osmy ns to > ~ o ~ o %
and state that to the best of my knowledge and belief, the Owner has perfor6ed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions mi 02r92~)
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Nuclear Management Company. LLC Date 6/28/2008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 362263-02 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 13 Charging Pump Ajax 6499 145-043 Corrected LI
- 7. Description of Work Replaced charging pump packing assemblies with rebuilt spares from stock.
- 8. Tests conducted: Hydrostatic r]
Pneumatic C] Nominal Operating Pressure Other n Pressure psi Test Temp. O F Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
EM 1-25-008
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N'/a Expiration Date
, ASME Program Engineer Date d/a~%~ ,
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period OSJuUB to 27 Judo8 ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
p-+i~aO.Oq Commissions rr\A m1q2q National Board, Province and Endorsements Date , 2008
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 1. Owner Nuclear Management Company, LLC Date 6/25/2008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 357581-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 13 Charging Pump Ajax 6499 145-043 Corrected I]
- 7. Description of Work Replaced charging pump packing assemblies with rebuilt spares from stock.
- 8. Tests conducted: Hydrostatic Pneumatic U Nominal Operating Pressure n Exempt [a Other 0 Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-009
- 9. Remarks I
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Date 6/ ~ y A y, Owner or Owner's Designee , T~tle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of ota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 29 MAROB to 3oJu~oB ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage .or a loss of any kind arising from or connected with this inspection.
Dated (C--+aO.O-q oInq I spector's Si dature 30 ,
omm missions 021424 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1011012008 Name
- 2. Plant Prairie Island Nuclear Generatrng Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 361 194-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date N/A
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla Edition Addenda nla Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump packing nla spares Corrected 1I assemblies
- 7. Description of Work Rebuilt spare charging pump packing assemblies 1, 2, 3.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure 0 Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-010
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and thts conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date / d / / d /dy w
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period @ J~JL(PB to [@ourpg and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions I m gS~192J National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 112112009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E , Welch Minnesota 55089 301525-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 12000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp VC piping Support Fluor Pioneer CVCH-1675 Corrected 0
- 7. Description of Work Replaced rod end fastener set.
- 8. Tests conducted: Hydrostatic Pneumatic U Nominal Operating Pressure 0 Exempt @
Other Pressure psi Test Temp. OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-013
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp /h Certificate of Auth. db Expiration Date Signed , ASME Program Engineer Date //Z//~P Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insw. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 13AW8 to 2iJAIJcpS and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
M K$ Commissions md dl9QS Inspector's dgnature National Board, Province and Endorsements Date
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 PO # 21 572 Address Repair Organization P.O. No., Job NO., etc
- 3. Work Performed by HydroAire Inc. Type Code Symbol Stamp NIA Name 834 West Madtson, Chicago, IL 60607 Authorization NIA Address Expiration Date NIA
- 4. Identification of System CL Code Class 3
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed,or Code Installed Stamp 121 CLG WTR Pump Worthington 045-091 Corrected [I
- 7. Description of Work Weld build up on Suction Bells, Column Pipe Flanges, Discharge Elbow, and Connector Pipe. Replaced the lower column pipe.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure n Exempt PJ Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and thls conforms to the requirements of the ASME Code, Sect~onXI.
Type Code Symbol Stamp //k Signed L2@J/A Certificate of ~utho6;a ' Expiration Date
, ASME Program Engineer Owner or Owner's Designee , Title Date d/y//O CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Inso. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period /4~0(rd8 to 12FE610 ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m 3 dl9QY National Board, Province and Endorsements Date
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 511912009 Name
- 2. Plant Prairie Island Nuclear Generatrng Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 157396-01 Address Repair Organization
- P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA NIA Address Expiration Date
- 4. Identification of System CL Code Class 3
- 5. (a) Applicable Construction Code n/a nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp 121 MD Clg Wtr Pump Worthington VTP30535 045-091 Corrected [A
- 7. Description of Work Replaced pump with previously rebuilt spare. Also replaced discharge piping fasterners.
- 8. Tests conducted: Hydrostatic Pneumatic U Nominal Operating Pressure Exempt Other Pressure psi Test Temp. OF Other: IST will be performed in accordance with SPIIOGC.
NOTE:Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
ITEM 1-25-015
- 9. Remarks CERTIFICATE OF COMPLIANCE rt are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Exp~rationDate
, ASME Program Engineer Owner or Owner's Designee , Title Date 3-4 9/OY .
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of p and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period /75EPU>8 to IS~AV@~
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m J dlY2v National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1211612008 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 nf 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 304394-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization Address Expiration Date
- 4. ldentification of System CL Code Class 3
- 5. (a) Applicable Construction Code B31. I 1967 Edition Addenda nla Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp CL Pipe spool piece 24-CL-12 Corrected 0
- 7. Description of Work Replaced piping spool piece.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure NOP psi Test Temp. NOT O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x IIin., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
k PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-019
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp //$$
~h 3 Signed ,/
C//
2 2 Certificate of Authorizatio". tj . Expiration Date
, ASME Program Engineer Owner or Owner's Designee , Title Date /a///@ .
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 2 8 m A V 00 to 0 2 J ~ h l ~ 5 9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions MJ d l q ~
In pector's ~ i g d are National Board, Province and Endorsements Date :oo&u 09 , Jeh9
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY 2
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 411612009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 363090-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. Identification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump Packing Goulds Spares Corrected El Assemblies
- 7. Description o f Work Rebuilt spare charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure 0 Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-020
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code, Sectton XI.
Type Code Symbol Stamp dh Certificate of Authori ation-spflfi& Expiration Date Signed 3l I
- , ASME Program Engineer Date 4 /& d 9 .
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period @3 W\l@8 to 2tS)nPecb9, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions MA 2 i q t Y National Board, Province and Endorsements Date
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/14/2010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 356175-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date N/A
- 4. ldentification of System MS Code Class 2
- 5. (a) Applicable Construction Code B16.34 n/a EditionIAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None 6, ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 SG PWR OPER RELIEF CV Copes Vulcan 7010-95074-1-1 CV-31084 Corrected 0
- 7. Description o f Work Replaced trim including the main and inner plugs.
- 8. Tests conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure n Exempt Other Pressure psi Test Temp. O F Other: Inservice testing will be performed in accordance with SP-1111B.
NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-021
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date /bdho,&
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 19 J A ~0 9 t o 2Uf41Gb ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions mA a\q'Lq National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1 1/5/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 nf 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 357615-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System SG Code Class 2
- 5. (a) Applicable Construction Code B31.1 7 1967 EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp SG Snubber Block Valve McDowell Welman 72218-000-13 12SlG 04 Removed rl SG Snubber Block Valve McDowell Welman 72218-000-19 12SlG 04 Installed Cl
- 7. Description o f Work Replaced valve block.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-024
- 9. Remarks VT-3 Report 2009V053 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp d/&
Expiration Date
, ASME Program Engineer Date +#,(' d9 w I Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 15Jb4@$ to I~HGG~& ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions f%LiLIL4 2L<
National Board, Province and Endorsements E
Z
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 11/5/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 357614-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification o f System SG Code Class 2
- 5. (a) Applicable Construction Code B31.1 1967 EditionlAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code lnstalled Stamp SG Snubber Block Valve McDowell Welman 72218-000-07 11SIG 04 Removed [A
. ~--- -
u p- -- pp pp SG Snubber Block Valve McDowell Welman 72218-000-11 11S/G 04 Installed
- 7. Description of Work Replaced valve block.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure 0 Exempt @
Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-025
- 9. Remarks VT-3 Report 2009V052 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp dh Expiration Date w
, ASME Program Engineer Owner or Owner's Designee , Title Date 1 / .
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of p and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period \43iraa@q to !.*?&m @q ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions 1w14d l S O L 4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 4/27/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 377737-04 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization NIA Address Expiration Date NIA
- 4. ldentification o f System CL Code Class 3
- 5. (a) Applicable Construction Code ASME Vlll 9 1970 EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp D l Lube Oil Cooler Perfex Corp. 7337902-2 4252 K-1443 1970 Corrected El
- 7. Description o f Work Replace stationary and floating channel heads and tube bundle.
- 8. Tests conducted: Hydrostatic a Pneumatic0 Nominal Operating Pressure 0 Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requ~rernentsof the ASME Code,Section XI.
Type Code Symbol Stamp d/b Expiration Date
. ASME Program Engineer Date '/ /Z 7 09 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 273~4 (b9 to 26APRQq and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions md d192c1 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 3/3/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch M~nnesota55089 349328-01, 349328-02 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Expiration Date NIA Address
- 4. Identification o f System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 BATP GOU~~S 792A190-2 145-612 Corrected Cj
- 7. Description of Work Replaced the mechanical seal gland plate and suction flange fasteners.
- 8. Tests conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure Exempt @
Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-027
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code, Sect~onXI.
Type Code Symbol Stamp A(/+
Expiration Date
. ASME Program Engineer Date 3 1 3 /CI 9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period &~~@cbq to 9 r n ~ a m and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
m . O J 1 Commissions rnd oiqtlq
((J nspector'&nature National Board, Province and Endorsements Date VYC),ch 04 , Q-s
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1111312009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 374070-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Expiration Date NIA Address
- 4. Identification of System SI Code Class 2
- 5. (a) Applicable Construction Code B16.34 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 RHR PMP RWST SPLY Aloyco SI-7-2 Corrected L1 Check
- 7. Description o f Work Replace check valve disc.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-028
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp dh rJIA Expiration Date
, ASME Program Engineer Date // /,3]u7 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period to . 2wOd@9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions " d142q "
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 3/3/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 -+ 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Expiration Date N/A Address
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code n/a n/a EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp r- -
11 BATP Goulds 792A190-1 145-611 Corrected ?-/
- 7. Description of Work Replaced the mechanical seal gland plate.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure U Exempt Other Pressure psi Test Temp. O F Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-030
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp 484 Certificate of Aut ' a I 4 Expiration Date Signed , ASME Program Engineer Date 3/349 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 19F&@ to @3~&69 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions mA d(qaq
\ nsp ctor's ~ d t u r e National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 5/6/2009 Name
- 2. Plant Prairie Island Nuclear Generattng Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 368065-01 Address Repair Organization
- P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code n/a n/a EditionlAddenda Addenda nla Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump Packing Goulds Spares Corrected 0 Assemblies
- 7. Description of Work Rebuilt spare charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure u Exempt @
Other Pressure psi Test Temp. O F Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-032
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp A//A Certificate of Authori Expiration Date Signed -!?& ASME Program Engineer Owner or Owner's Designee , Title Date 3/16 h~
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period ~ ( b m ~ ~ mto Q7 mAY (b9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m d 3149-9 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 6/2/2009 Name
- 2. Plant Pra~rieIsland Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 377855-01, EC-12530 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System ZH Code Class 3
- 5. (a) Applicable Construction Code B31.I 1967 EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Flexible Spool in Cooling Water Installed El Pipe
- 7. Description o f Work Replaced flexible vibration spool and associated flange fasteners.
- 8. Tests conducted: Hydrostatic Pneumatic n Nominal Operating Pressure 0 Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
ITEM 1-25-033
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp 44
/J)@ Expiration Date
, ASME Program Engineer Date &/a /0 9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 2WAG'(W to ~ u k l ~
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
-.Qq pector's ~igfiature t
Commissions rnJ d142q National Board, Province and Endorsements Date 02 Ll&--.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 6/3/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 377857-01, EC-I2530 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA 4, Identification of System ZH Code Class 3
- 5. (a) Applicable Construction Code B31.1 1967 EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME 1 Name Serial # Removed, or Code Installed Stamp1 Flex~bleSpools In Coollng Water Installed P~pe ill(
\
- 7. Description o f Work Replaced flexible vibration spools and associated flange fasteners. I
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
ITEM 1-25-034
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp rJ/a Certificate of Authorization . dl& Expiration Date Signed '@2 , ASME Program Engineer Owner or Owner's Designee , Title Date 4/3/07 ,
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of p and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period cWIPR(bq to Cb3JuhSaq ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m i4 1 9 ~ ,
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 9/9/2009 Name
- 2. Plant Prairie Island Nuclear Generattng Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 376426-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla n/a EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump Packing Goulds Spares Corrected n Assemblies
- 7. Description o f Work Rebuilt spare charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided ( I ) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-035
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code, Sectton XI.
Type Code Symbol Stamp
- 0. Expiration Date
, ASME Program Engineer Date 9'/9/-9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of esota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period (151m 4 CYR~ to @?S&P@~
and state that to the best of my knowledge and belief, the Owner has performed'examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of cted with this inspection.
Commissions J193q National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 12/3/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch Mtnnesota 55089 374056-01, EC 8126 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System RH Code Class 2
- 5. (a) Applicable Construction Code B31. I 1995 EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 RHR HX RC outlet Continental CV31236 Corrected n
- 7. Description of Work Replaced flange fasteners.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure u Exempt Other 0 Pressure psi Test Temp. OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-036
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date /2/3/d~
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 19MAy@9 to and state that to the best of my knowledge and belief, the Owner has performgd examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions diq2L4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
_i
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 7/2112009 Name
- 2. Plant Prairie Island Nuclear Generat~ngPlant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch M~nnesota55089 380738-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date N/A
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code n/a n/a EditionlAddenda Addenda nla Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 Charging Pump Ajax 145-042 Corrected L1
- 7. Description of Work Replaced charging pump packing assemblies with rebuilt spares from stock.
- 8. Tests conducted: Hydrostatic a Pneumatic Nominal Operating Pressure Other Pressure psi Test Temp. OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided ( I ) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp d/#
Exp~rationDate
, ASME Program Engineer Date ;~/a/h~
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 1qmAVcW to ~ZJUL<W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m 4 3 l q OCI National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 712112009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 385773-02 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Expiration Date NIA Address
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacernent Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 13 Charging Pump Ajax 6499 145-043 Corrected 0
- 7. Description o f Work Replaced charging pump packing assemblies with rebuilt spares from stock.
- 8. Tests cohducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. OF Other: n/a NOTE Supplemental sheets In form of lists, sketches, or draw~ngsmay be used, provided (1) slze is 8 1 12 In x 11 in , (2) rnformatlon In Items 1 through 6 on this report IS ~ncludedon each sheet, and (3) each sheet IS numbered and number of sheets is recorded at the top of this form
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-038
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp d/#
.'/A Expiration Date
, ASME Program Engineer Date 7hIhS Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 6BJC)Q (ac? to 22.JUUb9 ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions ma A(qW National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 9/21/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 385886-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date N/A
- 4. ldentification of System VC Code Class 2
- 5. (a) Applicable Construction Code nla nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Spare Charging Pump Packing Goulds Spares Corrected n Assemblies
- 7. Description of Work Rebuilt spare charging pump packing assemblies.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure U Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-039
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp /J/A Expirat~onDate
, ASME Program Engineer Date 9/3/h Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period lOJUrrlQrq to 2/Lsf'@ ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions atqa~
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1111312009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 +., 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Expiration Date NIA Address
- 4. Identification of System RC Code Class 1
- 5. (a) Applicable Construction Code 816.34 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp Cold Leg Inject Line to Loop B Velan SI-9-1 Corrected rI Cold Leg Check
- 7. Description o f Work Replaced cover, body to cover fasteners and valve internals.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure a Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-042
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code.Section XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date //,?/&?
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 27A U&@ to rBd.loai@q and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m i atqa.1 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 11/5/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 361068-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System RH Code Class 2
- 5. (a) Applicable Construction Code n/a nla EditionlAddenda Addenda n/a Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairlReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 RHR Pump Byron Jackson 681NO272 145-111 Corrected 0
- 7. Description of Work Replaced mechanical seal gland plate.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt @
Other Pressure psi Test Temp. O F Other: SP-1089A will be performed due to other maintenance activities.
NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-043
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made rn the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Expiration Date w
, ASME Program Engineer Date &A7 .
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 2 7 A W to CCLdJO\I@ ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m.( ~ 1 9 3 ~ \
'(pector's~ture National Board, Province and Endorsements Date
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY i L
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1111012009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 ,",
-,+ 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 357450-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date N/A
- 4. Identification of System AF Code Class 2
- 5. (a) Applicable Construction Code B16.34 n/a EditionIAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 AFW TO 11 SG valve Powell MV-32238 Corrected I7
- 7. Description o f Work Replaced valve plug.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other 0 Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-044
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and t h ~ sconforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp d/Q Expiration Date
, ASME Program Engineer Date / / /d/uy w
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period to !WC$\/m and state that to the best of my knowledge and belief, the Owner h ons and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
omm missions alqaq National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 112912010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 355659-01 Address Repair Organization
- P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System AF Code Class 2
- 5. (a) Applicable Construction Code ASME Ill 7 1968 EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components
?
Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 TD AFW PMP MS SPLY Copes Vulcan CV-31998 1968 Corrected L1 Valve
- 7. Description of Work Replaced internal trim including the plug.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure n Exempt Other Pressure psi Test Temp. O F Other: Exercise testing in accordance with the requirements of the IST program.
NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY z
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp pJ/a
~h Expiration Date
, ASME Program Engineer Date / h9// P Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province o f p and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period (d'LzPW to 01 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions WJ41qW National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 9/12/2009 Name
- 2. Plant 'Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E. Welch Minnesota 55089 389260-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code 016.34 nla EditionlAddenda Addenda nla Code Cases nla (b)Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. Identification of Components Component Name Manufacturer Manufacturer Nat'l Bd # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 BA XFER PMP DISCH TO 11 Grinnell VC-11-132 Corrected 0 BA FLTR
- 8. Tests conducted: Hydrostatic Pneumatic 0 Nominal Operating Pressure Exempt & i J Other 0 Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-046
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp dl4 Expiration Date
- , ASME Program Engineer Owner or Owner's Designee , Title Date -?//ah? ,
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period Cbl S @ q to IL)~&'O?
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions d dm23 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/6/2010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 100319-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System SI Code Class 2
- 5. (a) Applicable Construction Code B16.34 n/a EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition o f Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp SUMP B TO 12 RHR PMP TRN B Crane MV-32076 Corrected 0
- 7. Description o f Work Replaced disc.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure 0 Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-047
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI Type Code Symbol Stamp n//a Expiration Date
, ASME Program Engineer Date ) 6 2d/0 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION
, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel nspectors and the State or Province of p and employed
)Y HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected he components described in this Owner's Report during the period 642@&9 to Y23~hPit$
~ n state d that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective neasures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
3y signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied,
- oncerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither he lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of iny kind arising from or connected with this inspection.
Commissions A m d l924 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1111312009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 nf 2 Name 1717 Wakonade Dr. E, Welch M~nnesota55089 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System RC Code Class 1
- 5. (a) Applicable Construction Code B16.34 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp HIILO Head SI to 12 RX Vessel Velan SI-9-5 Corrected U Check Valve
- 7. Description o f Work Replaced body to cover fasteners and perform a stake (tack) weld of the disc nut to stud.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I 2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-048
- 9. Remarks VT-1 PSI report 2009V002 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp dh certificate Signed p & .//* Expiration Date
, ASME Program Engineer Date //h3 A&
Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period e W W to lg7hiQgl@?
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions rnJ dtQaq National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 121112009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 nf 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 38981 7-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. ldentification of System VC Code Class 2
- 5. (a) Applicable Construction Code n/a nla EditionlAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l Bd # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 BATP Goulds 792A190-1 145-611 Corrected El
- 7. Description of Work Replaced the mechanical seal gland plate.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt m Other Pressure psi Test Temp. OF Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-049
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Ah!!
Expiration Date V
, ASME Program Engineer Date )&# 7 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period D11."5~P@%f to . eyilOE-@C ,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected
, with this inspection.
Commissions 3i41Y National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1118/2009 Name
- 2. Plant Prairie Island Nuclear Generat~ngPlant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 316861 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System RC Code Class 1
- 5. (a) Applicable Construction Code B31. I 1967 EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 11 PRZR Relief Crosby 6-RV58LLSB RC-10-2 Corrected El
- 7. Description o f Work Replaced inlet flange stud.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure U Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-052
- 9. Remarks VT-1 recorded on PSI report 2009V043.
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp ,414 Expiration Date ASME Program Engineer Date / /k/ do,@
Owner or owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period rBW8q to iq-W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions 4%.)g%\ 33qaq National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1211112009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 289011-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. ldentification of System MS Code Class 2
- 5. (a) Applicable Construction Code B16.34 9 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 SG MS OUTL Stop Check Shutte and RS-19-2 Corrected 1 Koerting
- 7. Description of Work Replaced shaft bearing housing.
- 8. Tests conducted: Hydrostatic 0 Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Signed m
Type Code Symbol Stamp Certificate of A riza L Expiration Date
, ASME Program Engineer Date ,241 9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 22sWm to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of Commissions m A Qlgaq National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1111012009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 357063-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System RC Code Class 1
- 5. (a) Applicable Construction Code B16.34 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None 6, Identification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Loop B to PRZ CV-31224 Bypass Kerotest RC-7-1 Corrected n
- 7. Description o f Work Replaced bonnet assembly.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp No. ~4 Expiration Date
, ASME Program Engineer Date Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period %s~Pfi to 1 DUbQQ4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions n A3~3"4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 10/29/2009 Name
- 2. Plant Prairie Island Nuclear Generat~ngPlant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch M~nnesota55089 316571-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code B16.34 n/a EditionlAddenda Addenda n/a Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 121 BA TNK OUTL TO 11/12 BA Grinnell VC-11-121 Corrected 0 XFER PMP SUCT
- 7. Description of Work Replaced bonnet assembly.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-055
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requ~rementsof the ASME Code,Section XI.
Type Code Symbol Stamp /JIA d/a Expiration Date
, ASME Program Engineer Date ja $9 d 9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 19 sePw to 3cbcc~w and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
m . D J , Commissions ~d 31914 National Board, Province and Endorsements Date
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1013012009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 316571-01, 316571-11 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA 4, Identification of System VC Code Class 2
- 5. (a) Applicable Construction Code B16.34 nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp 11 BA FLTR to BA Blender DRN Grinnell VC-15-182 Corrected fl
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure u Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I 2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
L PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp d/d Expirat~onDate w
, ASME Program Engineer Date /6 /3c)/" 'j Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Insp. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period (bloc?'@ to 3(b0~7a9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions *qaV National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1013012009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 316571-01, 316571-10 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification o f System VC Code Class 2
- 5. (a) Applicable Construction Code B16.34 9 nla EditionIAddenda Addenda nla Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairlReplacement Activity 1998E 1 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp 12 BA XFER Pump DlSCH - DRN Grinnell VC-15-156 El
- 7. Description of Work Replaced body to bonnet fasteners.
- 8. Tests conducted: Hydrostatic C] Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-057
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp d/4 Signed cad'*
Certificate of Autho ' Expiration Date
, ASME Program Engineer Owner or Owner's Designee , Title Date /Q 30 0 9 I
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period (bloCr(W to ~ C M T C P ~
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions ~4 a(Qd'--/
National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 10/14/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E. Welch Minnesota 55089 359793-01 Address Repair Organization
- P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date NIA
- 4. Identification o f System CC Code Class 3
- 5. (a) Applicable Construction Code B16.34 n/a EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 CC PMP DlSCH Mission CC-3-2 Installed El
- 7. Description of Work Replaced valve.
- 8. Tests conducted,: Hydrostatic Pneumatic Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: n/a NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
ITEM 1-25-058
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp /1//A Signed flz.
Certificate of Authori Expiration Date
, ASME Program Engineer Owner or Owner's Designee , Title Dafe 10 I/&//!5 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Mimsota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the peri to WcC.ru-%a and state that to the best of my knowledge and belief, the Owner ons and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions m i Gi939-4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/21/2010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 -6 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 355150-01. EC-13953 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. ldentification of System SB
- 5. (a) Applicable Construction Code 831 .I 1967 EditionlAddenda Addenda n/a Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 SGB ISOL TRN B MV Flowse~e MV-32058 Installed L1
- 7. Description of Work Replaced valve.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure Exempt n Other Pressure NOP psi Test Temp. NOT OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 I2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERA TlNG PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY z L ITEM 1-25-059
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N//A
/A2 Expiration Date
, ASME Program Engineer Date / 121h 0 , d Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Jesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period W J m 9 to %88j&& 1g$i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions mpi $lCr2ac-q National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 11/25/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr E, Welch Minnesota 55089 39071 1-01 Address -
R e ~ a iOraanization r P.O. No.. Job No.. etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System CC Code Class 2
- 5. (a) Applicable Construction Code B31 1 7 1967 EditionIAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, o r Code Installed Stamp CC P~plng 1 112-CC-64 Corrected El CC P~prng 1 112-CC-47 Corrected El
- 7. Description of Work Replaced piping to valve flange fasteners.
- 8. Tests conducted: Hydrostatic Pneumatic0 Nominal Operating Pressure Exempt Other Pressure psi Test Temp. O F Other: nla NOTE:Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-061
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requ~rernentsof the ASME Code.Section XI.
Type Code Syrnbo Stamp /I/h dh Expiration Date
, ASME Program Engineer Date // J,; 09 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the lnspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the lnspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions aiq2q National Board, Province and Endorsements I
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/15/2010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 2 of Name 1717 Wakonade Dr. E, Welch Minnesota 55089 391388-09, EC-15064 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date N/A
- 4. Identification of System RC Codeclass 1
- 5. (a) Applicable Construction Code ASME Ill 7 1998 EditionlAddenda Addenda 2000 Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification o f Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp Reactor Vent Gas Plplng 1-RC-82 Corrected L Z
Reactor Vent Gas Plplng 314-RC-83 Corrected u
- 7. Description o f Work Replaced segment of piping and associated fittings.
- 8. Tests conducted: Hydrostatic 0 Pneumatic Nominal Operating Pressure Exempt Other Pressure NOP psi Test Temp. NOT OF Other: nla NOTE: supplemental sheets in form of lists, sketches, or drawings may be used, provided ( I ) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY ITEM 1-25-062
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp
. n//a Expiration Date
, ASME Program Engineer Date / /d4 /d Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB Ins?. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period l5a~~e4 to 15#.&d I@
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions MA 41c4P4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 12/9/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 AS 2 "S
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 28901 1-13 and 14 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp N/A Name Same Authorization N/A Address Expiration Date N/A
- 4. ldentification of System MS Code Class 2
- 5. (a) Applicable Construction Code B16.34 n/a EditionlAddenda Addenda nla Code Cases n/a (b) Applicable Edition of Section XI Utilized for RepairlReplacement Activity 1998E / 2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 SG MS Outlet Stop Chk Schutte & Koerting RS-19-2 Corrected 0
- 7. Description of Work Replaced disc.
- 8. Tests conducted: Hydrostatic 0 Pneumatic0 Nominal Operating Pressure n Exempt Other [? Pressure psi Test Temp. O F Other: Valve will be tested in accordance with SP 1374 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code, Sectron XI.
Type Code Symbol Stamp Expiration Date
, ASME Program Engineer Date / d /4/d 9 Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period 14-rn to and state that to the best of my knowledge and belief, the Owner has performed examinations measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of Commissions dlQ2J National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 1/4/2010 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2 Name 1717 Wakonade Dr. E, Welch Minnesota 55089 392426-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization NIA Address Expiration Date NIA
- 4. Identification of System CC Code Class 3
- 5. (a) Applicable Construction Code B31. I nla EditionlAddenda Addenda nla Code Cases nla (b) Applicable Edition o f Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 CC PMP CC RTRN CHK Mission CC-5-2 Installed c-1
- 7. Description of Work Replaced valve
- 8. Tests conducted: Hydrostatic Pneumaticu Nominal Operating Pressure n Exempt Other Pressure psi Test Temp. OF Other: nla NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code.Section XI.
Type Code Symbol Stamp d/~
Certificate of A riz ' d/4 Expiration Date Signed V
, ASME Program Engineer Date //yAo Owner or Owner's Designee , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period a 2 tdov cb? to ILJAQICD and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions fndI 3199-4 National Board, Province and Endorsements
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY L
- 1. Owner Xcel Energy, NSP-M Nuclear Department Date 11130/2009 Name
- 2. Plant Prairie Island Nuclear Generating Plant Sheet 1 of 2
Name 1717 Wakonade Dr. E, Welch Minnesota 55089 391758-01 Address Repair Organization P.O. No., Job No., etc
- 3. Work Performed by Owner Type Code Symbol Stamp NIA Name Same Authorization N/A Address Expiration Date N/A
- 4. Identification of System AF Code Class 3
- 5. (a) Applicable Construction Code B16.34 nla EditionIAddenda Addenda nla Code Cases nla (b) Applicable Edition of Section XI Utilized for RepairIReplacement Activity 1998E I2000A (c) Applicable Section XI Code Cases None
- 6. ldentification of Components Component Name Manufacturer Manufacturer Nat'l B d # Other ID Yr Built Corrected, ASME Name Serial # Removed, or Code Installed Stamp 12 MD AFW PMP DlSCH TO II Masoneilan MV-32381 Corrected 0 SG MV
- 7. Description of Work Replaced the valve plug.
- 8. Tests conducted: Hydrostatic Pneumatic Nominal Operating Pressure U Exempt Other Pressure psi Test Temp. O F Other: IST in accordance with SP1101.
NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1 12 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and number of sheets is recorded at the top of this form.
PRAIRIE ISLAND NUCLEAR GENERATING PLANT FORM NIS-2 OWNER'S REPORT FOR REPAIR1 REPLACEMENT ACTIVITY i
- 9. Remarks CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp /$(h Signed flz Certificate of A w -
- 0. d;/a Expiration Date
, ASME Program Engineer Owner or Owner's Designee , Title Date ///~OL? ,
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Minnesota and employed by HSB ins^. and Ins. Co. of Connecticut of Hartford Conn. have inspected the components described in this Owner's Report during the period r&sMca'aS@4 to and state that to the best of my knowledge and belief, the Owner has performed examinations measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in the Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury of property damage or a loss of any kind arising from or connected with this inspection.
Commissions flIh.31~3L-4 National Board, Province and Endorsements