L-PI-08-029, Supplement to License Amendment Request (LAR) to Add a Power Factor to the Emergency Diesel Generators' (EDG) 24-Hour Load Test (Surveillance Requirement 3.8.1.9)
ML081150606 | |
Person / Time | |
---|---|
Site: | Prairie Island |
Issue date: | 04/24/2008 |
From: | Wadley M Nuclear Management Co |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
L-PI-08-029, TAC MD7217, TAC MD7218 | |
Download: ML081150606 (94) | |
Text
Prairie Island Nuclear Generating Plant Cornrn~ttedto Nuclear Excelience Operated by Nuclear Management Company, LLC L-PI-08-029 10 CFR 50.90 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Prairie Island Nuclear Generating Plant Units 1 and 2 Dockets 50-282 and 50-306 License Nos. DPR-42 and DPR-60 Supplement to License Amendment Request (LAR) to Add a Power Factor to the Emergencv Diesel Generators' (EDG) 24-hour Load Test (Surveillance Requirement 3.8.1.9) (TAC Nos. MD7217 and MD7218)
Reference:
- 1. License Amendment Request (LAR) to Add a Power Factor to the Emergency Diesel Generators' (EDG) 24-hour Load Test (Surveillance Requirement 3.8.1.9), dated October 29, 2007, Accession Number ML073020289.
In Reference 1, Nuclear Management Company, LLC (NMC) submitted an LAR for the Prairie Island Nuclear Generating Plant (PINGP) Units 1 and 2 to revise Surveillance Requirement (SR) 3.8.1.9 to require that the EDG load test is performed at or below a power factor of 0.85. To support the review of Reference 1, the NRC Staff has requested additional information which is provided in Enclosure 1 to this letter. NMC submits this supplement in accordance with the provisions of 10 CFR 50.90.
The supplemental information provided in this letter does not impact the conclusions of the Determination of No Significant Hazards Consideration and Environmental Assessment presented in the October 29, 2007 submittal.
In accordance with 10 CFR 50.91, NMC is notifying the State of Minnesota of this LAR by transmitting a copy of this letter and enclosure to the designated State Official.
Please address any comments or questions regarding this LAR supplement to Mr. Dale Vincent, P.E., at 651-388-1 121.
1717 Wakonade Drive East Welch, Minnesota 55089-9642 Telephone: 651.388.1 121
Document Control Desk Page 2 Summary of Commitments This letter contains no new commitments and no revisions to existing commitments.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on APR 2 4 2008 Michael D. Wadley Site Vice President, Prairie lslan Generating Plant Units 1 and 2 Nuclear Management Company, LLC Enclosures (1) cc: Administrator, Region Ill, USNRC Project Manager, Prairie Island, USNRC Resident Inspector, Prairie Island, USNRC State of Minnesota
Enclosure The Nuclear Regulatory Commission (NRC) Staff has requested the following additional information to support review and approval of Reference 1.
Question 1:
Describe how the proposed power factor limit was calculated to be the worst-case power factor during the most limiting operation of the EDGs [emergency diesel generators]. Provide the calculation (or the portion thereof) that shows the worst-case load profile (in both kW & kVAR) for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and the calculated worst-case power factor.
Nuclear Management Company, LLC (NMC) response:
The proposed power factor was conservatively calculated in NMC Engineering Calculation ENG-EE-021. Portions of this calculation are provided in Attachment 1 to this Enclosure which provides the information requested in this question.
Question 2:
Describe how the procedures direct operators to verify grid and Engineered Safeguards Bus voltages which limit the power factor testing (that's as close as practicable to 0.85) each time the EDG is tested per TS SR 3.8.1.9.
NMC response:
The current Technical Specifications (TS) do not have a test power factor test requirement and therefore the current procedures do not direct the operators to achieve a specific power factor or achieve a power factor as close as practicable to 0.85.
Additional guidance will be provided to the operators as part of implementation of this license amendment following approval. However, as discussed below, there may not be much flexibility for improvement over the current practices.
As discussed in the Enclosure to Reference 1, on page 7 of 13, the current Unit 1 EDG testing procedures direct the operators to adjust the VARs as close to 1000 kVARs as possible while maintaining the associated safeguards bus voltage under 4400 V.
Similarly, the Unit 2 EDG testing procedures direct the operators to keep the associated safeguards bus voltage under 4400 V while setting the VAR load to approximately 1250 kVARs.
Typically, performance of EDG testing within these limits provides a power factor which is as close as practicable to 0.85 when instrument uncertainty is considered. The 4400 V limit protects the equipment on the safeguards buses, but it also limits the reactive load that can be placed on the EDGs. The VAR limits provide a reasonable Page 1 of 3
Enclosure load on the EDGs within the voltage limit. Test data from the last twelve months for EDG D l (Unit 1) monthly tests for which the data is available and the last six months for EDG D5 (Unit 2) are presented in Tables 1 and 2, respectively, below.
Table 1 D l Test Data Date Bus Voltage kVAR 1/28/2008 4254 1000 12/25/2007 4348 1000 11/26/2007 4364 1000 10/282007 4353 1000 9/24/2007 4324 1000 8/27/2007 4340 990 7/23/2007 4343 1000 6/25/2007 4358 1000 5/29/2007 4338 1000 4/23/2007 4320 900 3/26/2007 4290 950 2/26/2007 4318 1000 Table 2 D5 Test Data Date Bus Voltage kVAR 11211208 4355 1250 1211712007 4362 1250 11/ I 812007 4355 1250 10/23/2007 4355 1250 911712007 4380 1250 8/20/2007 4353 1250 Due to voltage instrument error, the kVAR would not be increased for most of these tests and thus the resultant power factor was as close as practicable to 0.85.
Page 2 of 3
Enclosure Due to its position relative to the grid, the 345 kV grid voltages at the Prairie Island Nuclear Generating Plant (PINGP) are usually maintained above the nominal voltage which also causes the plant 4160 V safeguards bus voltages to be above their nominal voltage. Examples of typical 345 kV grid voltages and 4160 V safeguards bus voltages were provided on page 7 of 13 in the Enclosure to Reference 1. Additional VARs could be loaded on the EDGs, which would lower the power factor toward the proposed TS 0.85 limit, if the 345 kV grid voltage and resultant 4160 V safeguards bus voltages are lower than typical. During implementation of this license amendment, the EDG test procedures will be revised to include additional guidance for operators to increase the VAR load if the voltage limits permit. This guidance may be in the form of nomographs which provide the operators a means of approximating the power factor achieved, instrument uncertainty information, and guidance for when and how much to increase the kVAR loading.
During performance of the 24-hour EDG load test (Surveillance Requirement 3.8.1.9),
the EDGs are considered inoperable and verification of operable paths between the offsite transmission grid and the onsite 4160 V safeguards distribution system is required within one hour and every eight hours thereafter in accordance with TS 3.8.1 Condition 8.1. This verification includes checking grid voltages (161 kV and 345 kV systems) are above the Security Analysis System voltage setpoint which assures that plant voltages will be adequate following a two unit trip; verifying the resultant 4160 V safeguards bus voltages are within the acceptance range (4000 V to 4400 V), and verifying the 480 V safeguards bus voltages are within the acceptance range (420 V to 505 V).
References:
- 1. License Amendment Request (LAR) to Add a Power Factor to the Emergency Diesel Generators' (EDG) 24-hour Load Test (Surveillance Requirement 3.8.1.9),
dated October 29,2007, Accession Number ML073020289.
Page 3 of 3 to Enclosure 88 pages follow
QF-0549 {FP-E-CAL-01 ), Rev. 2 Page 1 of 106 Calculation Signature Sheet Document Information I NMC Calculation /Doc) No: ENG-EE-021 I Revision: 3 I I
Title:
Diesel Generator Steady State Loading for an SI Event Concurrent with Loss of Offsite Power (LOOP) for Dl.. D2,. D5.. D6 I IFacility: MT PB [XI PI PL HUIFT I unit: @ 1 IXI 2 I Safety Class: [XI SR Aug Q Non SR Special Codes: Safeguards Proprietary Type: Calc Sub-Type: I
] NOTE: I Print and sign name in signature blocks, as required. J Description of Revision: Revised to incorporate the new Variable Frequency Drives (VFD1s)and new larger Charging Pump motors, incorporated changes from Addendurns 1-4, changed assumption about MV's, included loading for 21 Interruptible Bus Aux Transformer which had not been included before and Prepared by:
Jon South
@,A,/.'
reformatted entire calculation to aid ease of reading I I 1 Date:
I/-/&- 0 7 Reviewed by:" Date:
Ray Parazin /lal\-dV Type of Review: Design Verification Tech Review Vendor Acceptance I
Method Used ( F O ~DV only): view Alternate Calc Test Appmved by: \Date: t I Minor Revisions (continued on next page)
Record Retention: Retain this form with the associated calculation for the life of the plant.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 7 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D.5, D6 COMP. BY: JS 1.0 Purpose and Summary Result The purpose of this calculation is to provide a documented list of plant loads to support an SI event coincident with a LOOP (Design Basis Accident, DBA), to determine diesel generator state loading by event time periods after the seven step load sequence, and to determine the necessary power factor the diesel generators will be required to support by time period.
The results of this calculation demonstrate that the loading on the Emergency Diesel Generators remain below the continuous duty rating of the Emergency Diesel Generators for all four analyzed time periods. It also demonstrates that the power factor required by the Emergency Diesel Generator loads is within the capability of the Emergency Diesel Generators. For specific values see section 7.0 Conclusions.
2.0 Methodology 2.1 The MCC's shared by both units (1T1, 1T2, 1MAl, 1MA2, IAB 1, and 1AB2) are to be switched to the unit being analyzed. The transferable MCC's could be aligned to either unit at the start of the event and therefore to maximize analyzed loading, the transferable MCC's are included as loading for each possible supply.
2.2 Passport Report WM-0414, Engineering Motor Data Report was sorted by loads identified as operating in each time period and then sorted by MCC. The following methodology was used to determine the loading periods identified in the report.
2.2.1 When three or more similar loads (charging pumps) are distributed between the two trains and normal demand is for at least two operating loads, all will be assumed to be running unless prohibited by operating procedures. In that case, the operating procedure restriction may be applied after taking account of an Auto Start.
2.2.2 Restart of loads will be performed per Operating Procedures (i.e. charging pumps).
2.2.3 All loads started by an SI signal are assumed to run indefinitely unless stopped as a result of the change from Injection to Recirculation phase, or as a result of a manual stop as called for in an operating procedure.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 8 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 2.2.4 To account for single train operation or worst case combination, redundant loads assigned to separate trains will be assumed to run as follows for diesel generator loading purposes: Two redundant 100% capability loads assigned to different trains will each run.
2.2.5 Auxiliary loads that support major equipment such as those for diesel generators, cooling water pumps, etc. will be assumed to be running unless they are specifically load shed by their control circuitry from the major equipment or another source. They may be subsequently classified as stopped if specifically called for in an operating procedure.
2.2.6 Loads assumed to be in Standby mode and therefore not operating are justified based on operating procedure restrictions or good operating practice. Otherwise they are assumed to be running.
2.2.7 All 480V operating loads prior to a LOOP which do not maintain a start signal are assumed to stop running. The following loads with seal in contacts and no other start signal will be lost:
Dome Recirculation Fans (Beyond 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)
Sample Room Exhaust & Booster Fans (Between 5 - 30 minutes)
Gap Cooling Supply Fans (Beyond 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)
Reactor Vessel Support Cooling Fans (Beyond 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)
Charging Pumps & Charging Pump Cooling Fans (Between 0 - 5 minutes)
Per operating procedures, these loads will be restored to operating at the time interval listed next to each.
2.2.8 This calculation is divided into four time intervals. These four time intervals were previously established for the design basis accident (DBA):
0 - 5 minutes, 5 - 30 minutes, 30 minutes - 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and beyond 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
2.3 This resulted in four load listings which contain the applicable kilowatt (Actual kW) and kilovar (Actual KVA) loading on the MCC for the time period specified.
The kilowatt and kilovar loading is totaled per MCC. Loads which were identified as intermittent then had their kilowatt loading reduced to 50% per assumption 4.2.f.
2.4 The kilowatt, kilovar and kilowatt loading adjusted for intermittent loads is then summed per MCC for the associated time interval.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 9 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY. JS 2.5 After the loading for each MCC for each time interval was determined, the loading on each EDG for each time interval was calculated. Transferable MCC's were included as loading on each applicable EDG. The loading is identified per EDG per time period by MCC and then summed to arrive at total kilowatt loading per EDG for each time interval.
2.6 The power factor for each EDG for each time period was then determined by summing the total kilowatt loading on each EDG and the total kilovolt ampere loading. No reductions for intermittent operation were taken for power factor determination since the power factor is the total kilowatt loading divided by the total kilovolt ampere loading. Reducing this fiaction by taking credit for intermittent operation would arrive at a possibly non-conservative power factor.
3.0 Acceptance Criteria 3.1 For the four time intervals in the Design Basis Accident, the total KW values for each steady state load period, including allowances for cable and transformer losses, are calculated and compared to the D I D 2 steady state KW rating 2750 KW. In addition, the initial loading (in the first 5-10 minutes) can be evaluated for possible use of the D I D 2 cumulative rating of 30 minutes in excess of 3000 KW not to exceed 3250 KW. [Ref. 9.31 3.2 For the four time intervals in the Design Basis Accident, the total KW values for each steady state load period, including allowances for cable and transformer losses, are calculated and compared to the D51D6 continuous rating of 5400 KW, and not to exceed the 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> rating of 5940 KW. [Ref. 9.31 3.3 The total Power Factor values for each steady state load period are calculated.
The calculated Power Factors are then compared the rated EDG Power Factor rating. All four EDG's have a rating of 0.8 for Power Factor. [Ref. 9.31 NOTE: At the time of the writing of this revision, an LAR was being prepared to specify that a Technical Specification Surveillance requirement for testing the EDG's at a Power Factor of 0.85. Should a &re revision of this Design Calculation arrive at a Power Factor of less than 0.85, the Technical Specification Surveillance requirement should be revisited.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 10 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS 4.0 Assumptions 4.1 Unvalidated Assumptions None 4.2 Validated Assumptions
- a. It is assumed that Transformer losses conservatively bounded at 2% of the 480V loading for 41601480V transformers in the motor list.
Basis: Conservative assumption for ease in calculation. Previous experience performing load flow calculations with ETAP has shown that total losses from both cable and transformer losses are usually less than 1%.
- b. It is assumed that Cable losses are conservatively bounded at 3% of the total running load.
Basis: Conservative assumption for ease in calculation. Previous experience performing load flow calculations with ETAP has shown that total losses from both cable and transformer losses are usually less than 1%.
- c. It is assumed that all distribution panels will be assumed loaded to the lesser of either the nameplate value of their associated distribution transformer (with a 0.9 power factor), or as defined by a referenced design basis load calculation. Lighting loads will assume connected load and receptacle loads will assume transformer load.
Basis: Conservative assumption to maximize loading on the EDG.
- d. It is assumed that Motor Operated Valves are not assumed to significantly affect the steady state loading of the EDG's.
Basis: The typical loading of an MOV is less than 1 kW and the typical stroke time is less than 30 seconds.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 11 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS
- e. It is assumed that Motor Operated Valves are not assumed to significantly affect the steady state power factor of the EDG's.
Basis: The typical loading of an MOV is less than 1 kW and the typical stroke time is less than 30 seconds. Operation of a generator with a power factor other than 1.0 results in heating of various parts of the generator. This is a long term concern of maintaining cooling to the generator therefore a short transient is not of concern.
Also since the MOV loading is usually less than 1 kW and the total generator loading is greater than 1 100 kW, the overall change in the power factor is extremely small.
- f. It is assumed that loads identified as intermittent loads operate at full load for 50% of the loading interval.
Basis: Loads such as diesel oil he1 transfer pumps and boric acid tank heaters operate irregularly but less than 50% of the time. Accounting for these loads operating at 50% of capacity is a conservative assumption to allow for a reasonable estimate of loading impact on the emergency diesel generators.
- g. It is assumed that the loading on the battery chargers is reduced to steady state I&C loads within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and remains at this loading for the 1 Hour to 14 Day time period.
Basis: The battery chargers are automatically re-energized at step I or when the EDG's output breakers have closed. Conservatively assuming the battery chargers do not provide output current for 20 more seconds, the batteries only supply current without the charger for 30 seconds. This current is limited to 800 amperes by a fused disconnect between the battery and the DC distribution cabinet {Ref. NF-40301-1and Passport Equipment Database for 1 1 BATTIDISC; NF-40301-2and Passport Equipment Database for 12 BATTIDISC; NF-40547-1and Passport Equipment Database for 21 BATT/DISC; NF-40547-2and Passport Equipment Database for 22 BATT/DISC). 800 amperes for 30 seconds is 6.67 amp-hrs. The battery chargers are capable of supplying 300 amperes {Ref. USAR 8.5.3). Normal steady state I&C loads range from 16 amps on battery 22 to 39 amps on battery 11 as shown in attachment 10.1. Conservatively assuming all battery steady state I&C loading is 50 amps means that the battery chargers can supply 250 amps in excess of loading for 59.5 minutes which will easily fully recharge the batteries and result in a loading on the battery chargers of 50 amps at the maximum float voltage of 130.5VDC or 6.525 kW. For the time period 1 Hour to 14 Days the affected plant is in the long-term decay cooling mode with no major DC loads such as 4160 VAC breaker spring charging motors, EDG field flashing, inverters (inverter loading is carried on the EDG's), etc., being anticipated therefore loading on the battery chargers should be limited to battery float current and normal I&C loading.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 12 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 5.0 Inputs 5.1 The actual KW, actual KVA, and load interval characterization for each load fed fiom emergency diesel generator backed busses were taken fiom existing data in the plant equipment database (Passport). The data was extracted from Passport Report WM-0414, Engineering Motor Data Report, run on 09/06/07. The following changes were made to that data to account for plant changes that have not been incorporated into the plant Equipment database:
5.1.1 MTR 11 IF 11 BATT Charger - Load of 39.15 KW actual and 44.24 KVA actual included in each loading interval (see ENG-EE-02 1, Revision 2, Addendum 1). Assumption g changes the 1 Hour to 14 Day loading to 6.53 kW.
5.1.2 MTR 11IF 11 Interruptible Bus Aux XFMR - Load of 67.50 KW actual and 75 KVA actual included in each loading interval (see Assumption 4.2.c and ENG-EE-021, Revision 2, Addendum 1).
5.1.3 MTR 112G Train A Event Monitoring Room East Unit Cooler -
Load of 1.86KW actual and 3.73KVA actual included in each loading interval (see ENG-EE-021, Revision 2, Addendum 1).
5.1.4 MTR 112G 121 Spent Fuel Pool Pump - Load of 55.95 KW actual and 7 1.90 KVA actual included in each loading interval (see ENG-EE-021, Revision 2, Addendum 1).
5.1.5 MTR121F-33-12BATTCharga-Loadof39.15KWactualand44.24 KVA actual included in each loading interval (see ENG-EE-02 1, Revision 2, Addendum I). Assumption g changes the 1 Hour to 14 Day loading to 6.53 kW.
5.1.6 MTR 1226 122 Spent Fuel Pool Pump - Load of 55.95 KW actual and 7 1.90 KVA actual included in each loading interval (see ENG-EE-021, Revision 2, Addendum 1).
5.1.7 MTR 21 IF 21 BATT charger - Load of 39.1 5 KW actual and 44.24 KVA actual included in each loading interval (see ENG-EE-02 1, Revision 2, Addendum 1). Assumption g changes the 1 Hour to 14 Day loading to 6.53 kW.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 13 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP)for Dl, D2, D5, D6 COMP. BY: JS 5.1.8 MTR 2 11F 21 Interruptible Bus Aux XFMR - Load of 67.50 KW actual and 75 KVA actual included in each loading interval (see Assumption 4.2.c and 5.4).
5.1.9 MTR 21 1K 23 D5 DSL Gen Bldg Sply Fan - Load of 38.20 KW actual and 47.75 KVA actual included in each loading interval (see 5.5).
5.1.10 MTR211K-16-23 D5 DSLGenBldgRetumFan-Loadof38.20KW actual and 47.75 KVA actual included in each loading interval (see 5.5).
5.1.1 1 MTR 22 1F 22 BATT Charger - Load of 39.15 KW actual and 44.24 KVA actual included in each loading interval (see ENG-EE-02 1, Revision 2, Addendum 1). Assumption g changes the 1 Hour to 14 Day loading to 6.53 kW.
5.1.12 MTR221K-15 -24 D6 DSLGenBldg Sply Fan-Loadof38.20KW actual and 47.75 KVA actual included in each loading interval (see 5.5).
5.1.13 MTR221K-16-24D6DSLGenBldgReturnFan-Loadof38.20KW actual and 47.75 KVA actual included in each loading interval (see 5.5).
5.1.14 MTR 222E 22 RX VSL Support Clg Fan - Load of 21.67 KW actual and 27.09 KVA actual is included in each loading interval (see ENG-EE-021, Revision 2, Addendum 1).
5.2 USAR Section 8 - Plant Electrical Systems, Revision 28. The bounding case for diesel steady state loading is defined to be a LBLOCA in conjunction with a LOOP.
(Section 8.4.3 of the FSAR, "Performance Analysis - Loss of Coolant Accident and Loss of Off- Site Power", provides the basis for this information.)
5.3 The replacement Variable Frequency Drives and Motors for the Charging Pumps will require 105 kW at a 0.95 Power Factor. The basis is EC 945 1 - Charging Pump Drive Replacement motor sizing calculation: Proto-Power calculation 07-033 -
Charging Pump Motor Sizing.
5.4 ENG-EE-02 1, Revision 2, Addendum 1 added MTR 11IF-35,ll INTERRUPTABLE BUS AUX XFMR however it did not add MTR 21 1F-35,21 INTERRUPTABLE BUS AUX XFMR which is the same load on the opposite train. This revision will add the loading due to MTR 21 IF-35.
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 15 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads 111 MTR 11lC-10 121 CLG WTR SFGD TRVLG SCRN 0.61 0.94 I 0.3 1 21 1 MTR 11lC-14 12 CLG WTR PMP RIGHT JACKET WTR HTR 6.00 6.00 Y 6.00 21 1 MTR 111C-15 12 CLG WTR PMP LEFT JACKET WTR HTR 6.00 6.00 Y 6.00 111 MTR 11lC-21 11 CLG WTR STRNR 0.48 0.88 I 0.24 111 MTR 111C-22 21 CLG WTR STRNR 0.48 0.88 I 0.24 21 1 MTR 111C-25 11 SFGDS SCRNHSE ROOF EXHT FAN 8.60 10.76 Y 8.60 21 1 MTR 11lC-26 12 CLG WTR PMP U O PMP 1.20 1.99 Y 1.20 21 1 MTR 11lC-27 12 CLG WTR PMP STARTING AIR COMPR 12.75 15.93 I 6.38 21 1 MTR 111C-51 121 DD CLG WTR PMP OIL STG TNK PMP ' 0.68 1.24 I 0.34 21 1 MTR 1 1lC-52 121 SCREEN DIFF CONT PNL 70385 0.86 0.96 Y 0.86 MCC lABl Transferable 37.66 45.58 30.16 111 MTR 111E-13 11 BATT RM SPCL EXHT FAN 111 MTR 11l E-2 11 TD AFW PMP AUX U O PMP 111 MTR 11lE-43 123 AIR COMPR UNIT CLR 111 MTR 11l E-44 121 AIR COMPR UNIT CLR 111 MTR 111E-45 11/21 TD AFW PMPS UNIT CLR 111 MTR 111E-46 111 SWGR RM UNIT CLR 111 MTR 11lE-47 15 SWGR RM UNIT CLR 111 MTR 11l E-6 121 STA AIR COMPR MCC 1Al
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 16 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent 111 MTR lllF-31 11 INVERTER (INSTR BUS 11-WHI) 6.26 6.95 Y 6.26 111 MTR 11IF-32 13 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 111 MTR 11lF-33 11 BATTERY CHARGER 39.15 44.24 Y 39.15 111 MTR 11IF-35 11 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 111 MTR 11lF-36 17 INVERTER 6.26 6.95 Y 6.26 MCC lACl 125.43 140.09 125.43 111 MTR 111J-1 12 CHG PMP 105.00 111 MTR 1115-12 11/21 RHR CUBICLE AIR MNTR RE-26 (29026) 0.93 111 MTR 111J-52 11 CC PMP MTR UNIT CLR 1.04 111 MTR 111J-53 12 CHG PMP MTR UNIT CLR 0.76 111 MTR 1115-57 112 SWGR RM UNIT CLR 0.86 111 MTR 111J-59 12 CHG PUMP RM EXHT FAN 0.42 111 MTR lllJ-70 11 SI PMP MTR UNIT CLR 0.45 111 MTR 111J-71 11 SI PMP MTR UNIT CLR 0.45 111 MTR 1115-72 11 SI PMP MTR UNIT CLR 0.45 111 MTR 111J-73 11 SI PMP MTR UNIT CLR 0.45 111 MTR 1115-74 11 SI PMP MTR UNIT CLR 0.45 111 MTR I l l J-80 11 CS PMP MTR UNlT CLR 0.45 111 MTR lllJ-81 11 CS PMP MTR UNIT CLR 0.45 111 MTR lllJ-82 11 CS PMP MTR UNIT CLR 0.45 111 MTR I 1 1J-90 11 RHR PMP UNIT CLR 0.45 111 MTR 111J-91 11 RHR PMP UNIT CLR 0.45 MCC 1K1 113.51
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 17 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EO -
EOUIPMENT NAME KW KVA DBAPOST With 50%
COMP~NENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads MTR 11lK-32 121 Dl DSL GEN RM SPLY FAN MTR 11lK-33 121 D 1 DSL GEN RM EXHT FAN MTR 11lK-34 D 1 DSL GEN START-UP AIR COMPR MTR 11lK-56 121 DSL GEN FOST XFER PMP MTR 111K-60 D 1 DSL GEN CLEAN FUEL RTRN PMP MCC lTAl 42.79 54.26 42.79 112 MTR 112C-1 PRZR HTRS 1-3;l-25 & 1-54 38.40 38.40 I 19.20 112 MTR 112C-2 PRZR HTRS 1-8;l-308~1-58 38.40 38.40 I 19.20 112 MTR 112C-3 PRZR HTRS 1-12;l-35&1-64 38.40 38.40 I 19.20 112 MTR 112C-4 PRZR HTRS 1-16;l-40&1-70 38.40 38.40 I 19.20 112 MTR 112C-5 PRZR HTRS 1-45&1-77 38.40 38.40 I 19.20 MCC IS1 192.00 192.00 96.00 112 MTR 112D-51 121 ABSV EXHT FLTR HTR 20.00 20.00 Y 20.00 112 MTR 112D-54 121 ABSV EXHT FAN 19.12 23.90 Y 19.12 MCC lMAl Transferable 39.12 43.90 39.12
PINGP CALCULATION NUMBER. ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 18 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of OffsitePower (LOOP) for Dl, D2, D5, D6 COMP. RY: JS
- 6. I :0 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN YfN for intermittent MTR 112E-14 11 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 112E- 11 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 112E-15 121 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 112E-18 11 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-19 13 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-56 11 RX VSL SUPPORT CLG FAN 19.12 23.9 Y 19.12 MTR 112E-57 11 RX VSL GAP CLG SPLY FAN MTR 112E-62 123 WASTE GAS COMPRESSOR MTR 112E-8 11 BORIC ACID TANK HEATER A 112 MTR 112E-9 121 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 1L1 121.52 151.88 85.89
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 19 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads MTR 112G-1 SHLD BLDG VENT GAS RAD MON IRE-22 (29032)
MTR 112G-11 121 CONT RM CHLR MTR 112G-12 121 CONT RM CHLD WTR PMP MTR 112G-13 121 CONT RM CLEAN-UP FAN MTR 112G-14 RECEPTACLE PNL lRPA8 MTR 112G-15 121N RELAY RM UNIT CLR MTR 112G-16 TRN A EVENT MON RM EAST UNIT CLR MTR 112G-17 121S RELAY RM UNIT CLR MTR 112G-18 BA HEAT TRACE SWITCHRACK I (PNL ETN- 1,B,C)
MTR 112G-19 BA HEAT TRACE SWITCHRACK I11 (PNL ETN-N)
MTR 112G-3 121 CONT RM CHLR OIL PMP 112 MTR 112G-4 121 SFP PMP 55.95 71.90 112 MTR 112G-5 121 CONT RM AIR HNDLR & FAN 12.30 15.38 Y 112 MTR 112G-8 AUX BLDG VENT GAS RAD MON IRE-37 (29049) 1.01 1.55 Y 212 MTR 212G-1 2 1 CNTMTfSBV AIR RAD MON 2RE-11/12 1.40 2.15 Y (29030/2903 1) 212 MTR 2126-8 AUX BLDG VENT GAS RAD MON 2RE-37 (29050) 1.01 1.55 Y MCC IT1 Transferable 373.38 425.43 112 MTR 112J-2S 11 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 112 MTR 112J-3s 13 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x1 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 20 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads MTR 112K-35 11 SBV RECIRC FAN MTR 112K-36 11 SBV EXHT FAN MTR 112K-55 11 SBV EXHT FLTR HTR MCC lMl 32.66 37.04 32.66 22 1 MTR 121C-14 22 CLG WTR PMP RIGHT JACKET WTR HTR 6.00 6.00 Y 6.00 22 1 MTR 121C-15 22 CLG WTR PMP LEFT JACKET WTR HTR 6.00 6.00 Y 6.00 121 MTR 121C-21 12 CLG WTR STRNR 0.48 0.88 I 0.24 121 MTR 121C-22 22 CLG WTR STRNR 0.48 0.88 I 0.24 22 1 MTR 121C-25 2 1 SFGDS SCRNHSE ROOF EXHT FAN 8.73 10.92 Y 8.73 22 1 MTR 121C-26 22 CLG WTR PMP U O PMP 1.20 1.99 Y 1.20 22 1 MTR 121C-27 22 CLG WTR PMP STARTING AIR COMPR 12.75 15.93 I 6.38 22 1 MTR 121C-51 122 DD CLG WTR PMP OIL STG TNK PMP 0.68 1.24 I 0.34 22 1 MTR 12lC-52 122 SCREEN DIFF CONT PNL 70386 0.86 0.96 Y 0.86 121 MTR 121C-9 122 CLG WTR SFGD TRVLG SCRN 0.6 1 0.94 I 0.3 1 MCC 1AB2 Transferable 37.79 45.74 30.29 MTR 121E-19 12 MD AFW PMP AUX U O PMP MTR 121E-43 122 AIR COMPR UNIT CLR MTR 121E-44 12/22 MD AFW PMPS UNlT CLR MTR 121E-45 121 SWGRRM UNITCLR MTR 121E-46 16 SWGR RM UNIT CLR MTR 121E-6 122 STA AIR COMPR MCC 1.42 85.13 104.86 44.75
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 21 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, DS, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent 121 MTR 121F-31 12 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 121 MTR 121F-33 12 BATTERY CHARGER 39.15 44.24 Y 39.15 121 MTR 121F-34 14 INVERTER (INSTR BUS IV-YEL) 6.26 6.95 Y 6.26 121 MTR 12IF-35 12 BATT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 121 MTR 121F-36 18 INVERTER 6.26 6.95 Y 6.26 MCC 1AC2 58.45 65.89 58.45
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 22 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl.. D2., D5,. D6 COMP. BY: IS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent MTR 121J-1 11 CHG PMP 105.00 110.53 Y 105.00 MTR 121J-2 13 CHG PMP 105.00 110.53 Y 105.00 MTR 121J-3 12121 RHR CUBICLE AIR MNTR RE-27 (29041) 1-01 1.55 Y 1.01 MTR 121J-52 12 CC PMP MTR UNIT CLR 1.04 2.07 Y 1.04 MTR 121J-53 13 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 MTR 1215-54 11 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 MTR 1215-58 TRN A EVENT MON R M WEST UNIT CLR 0.86 1.73 Y 0.86 MTR 121J-62 11 CHG PUMP RM EXHT FAN 0.24 0.44 Y 0.24 MTR 121J-63 13 CHG PUMP RM EXHT FAN 0.24 0.44 Y 0.24 MTR 121J-70 12 SI PMP MTR UNIT CLR MTR 121J-71 12 SI PMP MTR UNIT CLR MTR 121J-72 12 SI PMP MTR UNIT CLR MTR 121J-73 12 SI PMP MTR UNIT CLR MTR 121J-74 12 SI PMF' MTR UNIT CLR MTR 121J-80 12 CS PMP MTR UNIT CLR MTR 121J-81 12 CS PMP MTR UNIT CLR MTR 121J-82 12 CS PMP MTR UNIT CLR MTR 121J-90 12 RHR PMP UNIT CLR 121 MTR 121J-91 12 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 1K2 219.61 239.64 219.61
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 23 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIh' Y/N for intermittent 121 MTR 121K-38 122 D2 DSL GEN RM SPLY FAN 16.74 20.93 Y 16.74 121 MTR 121K-39 122 D2 DSL GEN RM EXHT FAN 16.74 20.93 Y 16.74 121 MTR 121K-40 D2 DSL GEN START-UP AIR COMPR 7.47 9.96 Y 7.47 121 MTR 121K-57 123 DSL GEN FOST XFER PMP 0.68 1.24 Y 0.68 121 MTR 121K-60 D2 DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC 1TA2 42.29 54.26 42.29 122 MTR 122-1 122 SWGR RM UNIT CLR 0.86 1.73 Y 0.86 BUS 122 0.86 1.73 0.86 122 MTR 122D-51 122 ABSV EXHT FLTR HTR 20.00 20.00 Y 20.00 122 MTR 122D-54 122 ABSV EXHT FAN 19.12 23.90 Y 19.12 MCC 1MA2 Transferable 39.12 43.90 39.12
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 24 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y m for intermittent MTR 122E-14 12 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 122E- 12 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 122E-15 122 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 122E-18 12 CNTMT DOME RECIRC FAN MTR 122E-32 14 CNTMT DOME RECIRC FAN MTR 122E-56 12 RX VSL GAP CLG SPLY FAN 122 MTR I22E-57 12 RX VSL SUPPORT CLG FAN 19.12 23.9 Y 19.12 122 MTR 122E-8 11 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 122 MTR 122E-9 121 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 1L2 101.57 126.94 75.91
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 25 of 106 TITLE:Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of OffsitePower (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads MTR 1226-1 11 CNTMT/SBV AIR RAD MON IRE-11/12(29028/29029)
MTR 1226-11 122 CONT RM CHLR MTR 1226-12 122 CONT RM CHLD WTR PMP MTR 1226-13 122 CONT RM CLEAN-UP FAN MTR 1226-14 RECEPTACLE PANEL lRPB8 MTR 1226-3 122 CONT RM CHLR OIL PMP MTR 1226-4 122 SFP PMP MTR 1226-5 122 CONT RM AIR HNDLR & FAN MTR 1220-8 AUX BLDG VENT GAS RAD MON IRE-30 (29004)
MTR 222G-1 SHLD BLDG VENT GAS RAD MON 2RE-22 (29033)
MTR 2226- 15 122N RELAY RM UNIT CLR MTR 2226- 16 TRN B EVENT MON RM UNIT CLR MTR 2226- 17 122s RELAY RM UNIT CLR MTR 2226-8 AUX BLDG VENT GAS RAD MON 2RE-30 (29005)
MCC 1T2 Transferable 252.08 303.28 252.08 122 MTR 1225-2s 12 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 122 MTR 122J-3s 14 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x2 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 26 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl., D2., DS., D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent 122 MTR 122K-35 12 SBV RECIRC FAN 15.93 19.92 Y 15.93 122 MTR 122K-36 12 SBV EXHT FAN 0.73 1.12 Y 0.73 122 MTR 122K-40 AC DIST PANEL 145 FEEDER 4.50 5.00 Y 4.50 122 MTR 122K-47 122 SMPL RM EXHT FAN 6.69 8.37 Y 6.69 122 MTR 122K-55 12 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC lM2 43.85 50.41 43.85 15 MTR 15-1 I1 SI PUMP 63 1.20 692.80 Y 63 1.20 15 MTR 15-4 11 RHRPUMP 162.10 180.10 Y 162.10 15 MTR 15-5 11 CC PMP 199.00 222.80 Y 199.00 15 MTR 15-9 11 CS PMP 199.10 227.00 Y 199.10 BUS 15 1191.40 1322.70 1191.40 16 MTR 16-1 12 CS PMP 199.10 227.00 Y 199.10 16 MTR 16-3 12 MD AFW PMP 233.90 266.70 Y 233.90 16 MTR 16-5 12 CC PMP 199.00 222.80 Y 199.00 16 MTR 16-6 I2 RHR PUMP 162.10 180.10 Y 162.10 16 MTR 16-7 12 SI PUMP 631.20 692.80 Y 63 1.20 BUS 16 1425.30 1589.40 142530
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 27 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, D6 COMP. BY: JS BUS EO -
EOUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads 180 MTR 181-1 PRZR HTRS 1-2;l-23&1-50 38.40 38.40 I 19.20 180 MTR 181-2 PRZR HTRS 1-6;l-288~1-56 38.40 38.40 I 19.20 180 MTR 181-3 PRZR HTRS 1-11;l-33&1-59 3 8.40 38.40 I 19.20 180 MTR 181-4 PRZR HTRS 1-15;l-388~1-67 38.40 38.40 I 19.20 180 MTR 181-5 PRZR HTRS 1-43;l-738~1-74 38.40 38.40 I 19.20 MCC 1R1 192.00 192.00 96.00 21 1 MTR 211D 2 1 D5 DSL RM COOLING FAN 97.87 113.80 Y 97.87 BUS 211 97.87 113.80 97.87 21 1 MTR 21 1E-5 123 STA AIR COMPR 79.17 94.8 1 I 39.59 21 1 MTR 21 1E-6 21 MD AFW PMP AUX U0 PMP 1.61 2.47 Y 1.61 21 1 h4TR 211E-8 2 1 BATT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 MCC 2A1 8130 98.08 41.72 211 MTR 21 IF-31 2 1 INVERTER (INSTR BUS 11-WHI) 6.26 6.95 Y 6.26 21 1 MTR 21 IF-32 23 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 211 MTR 21 IF-33 2 1 BATTERY CHARGER 29.78 33.09 Y 29.78 21 1 MTR 21 IF-35 2 1 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 21 1 MTR 21 1F-36 27 INVERTER 6.26 6.95 Y 6.26 MCC 2AC1 116.06 128.94 116.06
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 28 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EO -
EOUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN YIN for intermittent loads MTR 21 1J-1 22 CHG PMP MTR 2 11J-5 1 2 1 CC PMP MTR UNIT CLR MTR 2 11J-52 22 CHG PMP MTR UNIT CLR MTR 2 11J-57 22 CHG PUMP R M EXHT FAN MTR 2 11J-60 21 SI PMP MTR UNIT CLR MTR 21 1J-61 21 SI PMP MTR UNIT CLR MTR 2 11J-62 2 1 SI PMP MTR UNIT CLR MTR 2 11J-63 21 SI PMP MTR UNIT CLR MTR 2 11J-64 2 1 SI PMP MTR UNIT CLR MTR 211J-70 2 1 CS PMP MTR UNIT CLR MTR 211J-71 2 1 CS Ph4P MTR UNIT CLR MTR 2 11J-72 2 1 CS PMP MTR UNIT CLR MTR 211J-80 21 RHR PMP UNIT CLR 21 1 MTR211J-81 21 RHRPMF' UNIT CLR 0.45 0.89 Y 0.45 MCC 2K1 111.99 123.62 111.99
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 29 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads 21 1 MTR 21 1K-1 2 1 D5 FO STG TNK XFER PMP 4.17 5.57 I 2.09 MTR 211K-10 D5 ENG 2 HTILT RADIATOR FAN 2 38.20 47.74 Y 38.20 MTR 211K-12 2 1 D5 DSL GEN BLDG SPLY F A N 38.20 47.75 Y 38.20 MTR 211K-13 21 D5 DSL GEN BLDG RETURN FAN 38.20 47.75 Y 38.20 MTR 211K-15 23 D5 DSL GEN BLDG SPLY F A N 38.20 47.75 38.20 MTR 21 1K-16 23 D5 DSL GEN BLDG RETURN FAN 38.20 47.75 38.20 MTR 21 1K-19 AC DISTRUBUTION PANEL 247 1.91 2.25 I 0.96 MTR 2 11K-2 D5 ENG 1 FO B-U PMP 1.14 1.75 Y 1.14 MTR211K-3 D5 ENG 1 HTILT RADIATOR FAN 1 38.20 47.75 Y 38.20 MTR 2 11K-5 23 D5 FO STG TK XFER PUMP 4.18 5.57 I 2.09 21 1 MTR 21 1K-6 D5 ENG 2 FO B-U PMP 1.14 1.75 Y 1.14 21 1 MTR 21 1K-7 D5 ENG 1 HTILT RADIATOR F A N 2 38.20 47.75 Y 38.20 21 1 MTR 2 11K-9 D5 ENG 2 HTLT RPLDIATOR F A N 1 38.20 47.75 Y 38.20 MCC 2TA1 318.14 398.88 313.01 212 MTR 212C-1 PRZR HTRS 2-13;2-3682-65 38.40 38.40 I 19.20 212 MTR 2 12C-2 PRZR HTRS 2-9;2-3 1&2-59 38.40 38.40 I 19.20 212 MTR 2 12C-3 PRZR HTRS 2-4;2-26&2-54 38.40 38.40 I 19.20 212 MTR 2 12C-4 PRZR HTRS 2-2 1;2-47&2-48 38.40 38.40 I 19.20 212 MTR 2 12C-5 PRZR HTRS 2-1 8;2-42;&2-72 38.40 38.40 I 19.20 MCC 2S1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 30 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading EBUS EQ EQUIPMENT NAME KW COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent loads MTR212E-14 21 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 2 12E- 21 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 212E-18 2 1 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 212E-19 23 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 2 12E-44 21 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 MTR 212E-45 21 RX VSL SUPPORT CLG FAN 21.67 27.09 Y 21.67 MTR 2 12E-8 2 1 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 2L1 75.16 95.83 62.81 212 MTR 212J-2s 2 1 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 212 MTR 212J-3S 23 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2 x 1 40.52 106.64 40.52 212 MTR 212K-35 2 1 SBV RECIRC FAN 15.93 19.92 Y 15.93 212 MTR 212K-36 2 1 SBV EXHT FAN 0.62 0.96 Y 0.62 212 MTR 2 12K-42 21 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC 2M1 32.55 36.88 32.55
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 3 1 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN YIN for intermittent loads 22 1 MTR 221B-51 22 CC PMP MTR UNIT CLR 0.60 1.20 Y 0.60 22 1 MTR 22 1B-52 23 CHG PMP MTR UNIT CLR 0.50 1.OO Y 0.50 22 1 MTR 221B-53 2 1 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 22 1 MTR 221B-57 2 1 CHG PUMP RM EXHT FAN 0.42 0.76 Y 0.42 22 1 MTR 221B-58 23 CHG PUMP RM EXHT FAN 0.33 0.60 Y 0.33 22 1 MTR 22 1B-60 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-61 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-62 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 1B-63 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 1B-64 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-70 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 18-71 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-72 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-80 22 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 3 8-81 22 RHR PMP UNJT CLR 0.45 0.89 Y 0.45 MCC 2KA2 7.21 14.19 7.2 1 22 1 MTR 221D 22 D6 DSL RM COOLING FAN 97.87 113.80 Y 97.87 BUS 221 97.87 113.80 97.87 22 1 MTR 22 1E-7 22 TD AFW PMP AUX UO PMP 1.61 2.47 Y 1.61 MCC 2A2 1.61 2.47 1.61
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 32 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP)for D l , D2, D5, D6 COMP. BY: JS 6.1 0 - 5 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent 22 1 MTR 22 1F-3 1 22 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 22 1 MTR 22 1F-33 22 BATTERY CHARGER 39.15 44.24 Y 39.15 22 1 MTR 22 IF-34 24 INVERTER (INSTR BUS IN-YEL) 6.26 6.95 Y 6.26 22 1 MTR 22 1F-35 22 BATT RM SPCL EXHT FAN 0.40 0.61 Y 0.40 22 1 MTR 221F-36 28 INVERTER 6.26 6.95 Y 6.26 MCC 2AC2 58.33 65.70 5833 22 1 MTR 221J-1 2 1 CHG PMP 105.00 110.53 Y 105.00 22 1 MTR 22 1J-2 23 CHG PMP 105.00 110.53 Y 105.00 MCC 2K2 210.00 221.05 210.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 33 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT
- NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN YJN for intermittent loads 22 1 MTR 221K-1 22 D6 FO STG TNK XFER PMP 4.18 5.57 I 22 1 MTR 221K-10 D6 ENG 2 HTLT RADIATOR FAN 2 38.20 47.75 Y 22 1 MTR 221K-12 22 D6 DSL GEN BLDG SPLY FAN 38.20 47.75 Y 22 1 MTR 221K-13 22 D6 DSL GEN BLDG RETURN FAN 38.20 47.75 Y 22 1 MTR 221K-15 24 D6 DSL GEN BLDG SPLY FAN 38.20 47.75 22 1 MTR 221K-16 24 D6 DSL GEN BLDG RETURN FAN 38.20 47.75 22 1 MTR 221K-19 AC DISTRUBUTION PANEL 248 1.90 2.25 I 22 1 MTR 221K-2 D6 ENG 1 FO B-U PMP 1.14 1.75 Y 22 1 MTR 221K-3 D6 ENG 1 HTJLT RADIATOR FAN 1 38.20 47.75 Y 22 1 MTR 221K-5 24 D6 FO STG TNK XFER PMP 4.18 5.57 I 22 1 MTR 22 1K-6 D6 ENG 2 FO B-U PMP 1.14 1.75 Y 22 1 MTR 221K-7 D6 ENG 1 HTLT RADIATOR FAN 2 38.20 47.75 Y 22 1 MTR 22 1K-9 D6 ENG 2 HTLT RADIATOR FAN 1 38.20 47.75 Y MCC 2TA2 318.14 398.89 MTR 222E-18 22 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 222E-32 24 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 222E-43 22 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 MTR 222E-44 22 RX VSL SUPPORT CLG FAN 21.67 27.09 2 1.67 MTR 222E-5 22 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 222E-5s 22 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 MTR 222E-8 2 1 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 2L2 75.16 95.83 62.81
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 34 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MINYJN for intermittent loads 222 MTR 222J-2s 22 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 222 MTR 2225-3s 24 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2x2 40.52 106.64 40.52 222 MTR 222K-35 22 SBV RECIRC FAN 15.93 19.92 Y 15.93 222 MTR 222K-36 22 SBV EXHT FAN 0.62 0.96 Y 0.62 222 MTR 222K-40 AC DIST PANEL 245 FEEDER 4.50 5.00 Y 4.50 222 MTR 222K-42 22 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC 2M2 37.05 41.88 37.05 25 MTR 25-10 21 MD AFWPMP 233.90 266.70 Y 233.90 25 MTR 25-13 21 CC PMP 199.00 222.80 Y 199.00 25 MTR 25-7 2 1 RHR PMP 160.50 180.10 Y 160.50 25 MTR 25-8 21 SIPMP 63 1.20 692.80 Y 63 1.20 25 MTR 25-9 21 CS PMP 199.10 227.00 Y 199.10 BUS 25 1423.70 1589.40 1423.70 26 MTR 26- 10 22 SI PMP 631.20 692.80 Y 63 1.20 26 MTR 26-1 1 22 RHR PMP 160.50 180.10 Y 160.50 26 MTR 26-5 22 CC PMP 199.00 222.80 Y 199.00 26 MTR 26-9 22 CS PMP 199.10 227.00 Y 199.10 BUS 26 1189.80 1322.70 1189.80
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 35 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl. D2. D5. D6
- d h ,
BUS EO EQUIPMENT
- NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 0-5 reduction TAG MIN Y/N for intermittent 27 MTR 27- 1 121 MD CLG WTR PMP 783.09 879.88 Y 783.09 BUS 27 783.09 879.88 783.09 270 MTR 271-1 PRZR HTRS 2-15;2-38&2-67 38.40 38.40 I 19.20 270 MTR 271-2 PRZR HTRS 2-33 ;2-6 1&2-62 38.40 38.40 I 19.20 270 MTR 27 1-3 PRZR HTRS 2-6;2-28&2-56 38.40 38.40 I 19.20 270 MTR 27 1-4 PRZR HTRS 2-2;2-238~2-50 38.40 38.40 I 19.20 270 MTR 271-5 PRZR HTRS 2-44;2-75&2-76 38.40 38.40 I 19.20 MCC 2R1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 36 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN YRV for intermittent 111 MTR lllC-10 121 CLG WTR SFGD TRVLG SCRN 21 1 MTR 1llC-14 12 CLG WTR PMP RIGHT JACKET WTR HTR 21 1 MTR 111C-15 12 CLG WTR PMP LEFT JACKET WTR HTR 111 MTR lllC-21 11 CLG WTR STRNR 111 MTR 111C-22 2 1 CLG WTR STRNR 21 1 MTR 111C-25 11 SFGDS SCRNHSE ROOF EXHT FAN 21 1 MTR 111C-27 12 CLG WTR PMP STARTING AIR COMPR 21 1 MTR 11lC-52 121 SCREEN DIFF CONT PNL 70385 MCC lABl Transferable 111 MTR lllE-13 11 BATT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 111 MTR lllE-43 123 AIR COMPR UNIT CLR 1.04 2.07 I 0.52 111 MTR 11lE-44 121 AIR COMPR UNIT CLR 1.04 2.07 Y 1.04 111 MTR 11lE-45 11/21 TD AFW PMPS UNIT CLR 1.04 2.07 Y 1.04 111 MTR 1llE-46 111 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 111 MTR 1llE-47 15 SWGR RM UNIT CLR 0.62 1.23 Y 0.62 111 MTR 11lE-6 121 STA AIR COMPR 79.17 94.81 Y 79.17 MCC 1Al 84.29 104.77 83.77
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 37 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads MTR 11lF-31 11 INVERTER (INSTR BUS 11-WHI)
MTR 11lF-32 13 INVERTER (INSTR BUS 111-BLU)
MTR 11lF-33 11 BATTERY CHARGER MTR 11lF-35 11 INTERRUPTABLE BUS AUX XFMR MTR 11lF-36 17 INVERTER MCC lACl 125.43 140.09 125.43 111 MTR lllJ-1 12 CHG PMP 105.00 110.53 Y 105.00 111 MTR lllJ-12 11/21 RHR CUBICLE AIR MNTR RE-26 (29026) 0.93 1.55 Y 0.93 111 MTR 111J-52 11 CC PMP MTR UNIT CLR 1.04 2.07 Y 1.04 111 MTR 111J-53 12 CHG PMP MTR UNIT CLR 0.76 1.52 Y 0.76 111 MTR 1115-57 112 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 111 MTR 1115-59 12 CHG PUMP RM EXHT FAN 0.42 0.76 Y 0.42 111 MTR 111J-70 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 1115-71 11 SIPMPMTRUNITCLR 0.45 0.89 Y 0.45 111 MTR 111J-72 11 SIPMPMTRUNITCLR 0.45 0.89 Y 0.45 111 MTR 111J-73 11 SIPMPMTRUNITCLR 0.45 0.89 Y 0.45 111 MTR 111J-74 11 SIPMPMTRUNITCLR 0.45 0.89 Y 0.45 111 MTR 111J-80 11 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR lllJ-81 11 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 111J-82 11 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 111J-90 11 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 111 MTR lllJ-91 11 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 1K1 113.51 127.05 113.51
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 38 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent 111 MTR 11lK-32 121 Dl DSL GEN RM SPLY FAN 16.74 20.93 Y 16.74 111 MTR 111K-33 121 Dl DSL GEN RM EXHT FAN 16.74 20.93 Y 16.74 111 MTR 11lK-34 D 1 DSL GEN START-W AIR COMPR 7.97 9.96 Y 7.97 111 MTR 11lK-56 121 DSL GEN FOST XFER PMP 0.68 1.24 Y 0.68 111 MTR 11lK-60 D 1 DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC lTAl 42.79 54.26 42.79 112 MTR 112C-1 PRZRHTRS 1-3;l-25 & 1-54 38.40 38.40 I 19.20 112 MTR 112C-2 PRZRHTRS 1-8;l-30&1-58 38.40 38.40 I 19.20 112 MTR 112C-3 PRZRHTRS 1-12;l-35&1-64 38.40 38.40 I 19.20 112 MTR 112C-4 PRZR HTRS 1- 16; 1-408~1-70 38.40 38.40 I 19.20 112 MTR 112C-5 PRZR HTRS 1-458~1-77 38.40 38.40 I 19.20 MCC IS1 192.00 192.00 96.00 112 MTR 112D-51 121 ABSV EXHT FLTR HTR 20.00 20.00 Y 20.00 112 MTR 112D-54 121 ABSV EXHT FAN 19.12 23.90 Y 19.12 MCC lMAl Transferable 39.12 43.90 39.12
PINGP CALCULATION NUMBER. ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 39 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent MTR 112E-14 11 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 112E- 11 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 112E-15 121 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 112E-18 11 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-19 13 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-56 11 RX VSL SUPPORT CLG FAN 19.12 23.9 Y 19.12 112 MTR 112E-57 11 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 112 MTR 112E-62 123 WASTE GAS COMPRESSOR 19.95 24.94 I 9.98 112 MTR 112E-8 11 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 112 MTR 112E-9 121 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 1L1 121.52 151.88 85.89
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 40 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads MTR 112G-1 SHLD BLDG VENT GAS RAD MON IRE-22 (29032) 1.01 1.55 Y 1.01 MTR 112G-11 121 CONTRM CHLR 140.47 159.63 Y 140.47 MTR 112G-12 121 CONT RM CHLD WTR PMP 20.40 25.50 Y 20.40 MTR 112G-13 121 CONT R M CLEAN-UP FAN MTR 112G-14 RECEPTACLE PNL 1RPA8 MTR 112G-15 121N RELAY RM UNIT CLR 112 MTR 112G-16 TRN A EVENT MON RM EAST UNIT CLR 1.86 1.83 1.86 112 MTR 112G-17 121s RELAY RM UNIT CLR 0.86 1.72 Y 0.86 112 MTR 112G-18 BA HEAT TRACE SWITCHRACK I (PNL ETN-l,B,C) 90.00 90.00 I 45.00 112 MTR 112G-19 BA HEAT TRACE SWITCHRACK I11 (PNLETN-N) 30.00 30.00 I 15.00 112 MTR 112G-3 121 CONT RM CHLR OIL PMP 0.24 0.44 Y 0.24 112 MTR 112G-4 121 SFP PMP 55.95 71.90 55.95 112 MTR 112G-5 121 CONT RM AIR HNDLR & FAN 12.30 15.38 Y 12.30 112 MTR 112G-8 AUX BLDG VENT GAS RAD MON IRE-37 (29049) 1.01 1.55 Y 1.01 212 MTR 212G-1 2 1 CNTMTISBV AIR RAD MON 2RE- 11112 1.40 2.15 Y 1.40 (29030129031) 212 MTR 2126-8 AUX BLDG VENT GAS RAD MON 2RE-37 (29050) 1.01 1.55 Y 1.01 MCC IT1 Transferable 373.38 423.53 313.38 112 MTR 112J-2S 11 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 112 MTR 112J-3s 13 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x1 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 41 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP.
- - .-- . BY:
- - . JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Ym for intermittent 112 MTR 112K-35 11 SBV RECIRC FAN 15.93 19.92 Y 15.93 112 MTR 112K-36 11 SBV EXHT FAN 0.73 1.12 Y 0.73 112 MTR 112K-47 121 SMPL RM EXHT FAN 6.69 8.37 Y 6.69 112 MTR 112K-48 121 SMPL RM BSTR FAN 0.68 1.35 Y 0.68 112 MTR 112K-55 11 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC l M l 40.03 46.76 40.03 22 1 MTR 121C-14 22 CLG WTR PMP RIGHT JACKET WTR HTR 22 1 MTR 121C-15 22 CLG WTR PMP LEFT JACKET WTR HTR 121 MTR 121C-21 12 CLG WTR STRNR 121 MTR 121(2-22 22 CLG WTR STRNR 221 MTR 121C-25 2 1 SFGDS SCRNHSE ROOF EXHT FAN 221 MTR 121C-27 22 CLG WTR PMP STARTING AIR COMPR 22 1 MTR 121C-52 122 SCREEN DIFF CONT PNL 70386 121 MTR 121C-9 122 CLG WTR SFGD TRVLG SCRN MCC 1AB2 Transferable 121 MTR 121E-44 12/22 MD AFW PMPS UNIT CLR 1.04 2.07 Y 1.04 121 MTR 121E-45 121 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 121 MTR 121E-46 16 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 MCC 1A2 2.76 5.51 2.76
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 42 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP)for Dl, D2, D5,D6 6.2 5 - 30 Minute Loading BUS EO EQUIPMENT
- NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent 121 MTR 121F-31 12 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 121 MTR 121F-33 12 BATTERY CHARGER 39.15 44.24 Y 39.15 121 MTR 121F-34 14 INVERTER (INSTR BUS IV-YEL) 6.26 6.95 Y 6.26 121 MTR 121F-35 12 BAIT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 121 MTR 121F-36 18 INVERTER 6.26 6.95 Y 6.26 MCC 1AC2 58.45 65.89 58.45
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 43 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, D5, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads MTR 121J-1 11 CHG PMP MTR 1215-2 13 CHG PMP 121 MTR 1215-3 12121 RHR CUBICLE AIR MNTR RE-27 (2904 1) 121 MTR 1215-52 12 CC PMP MTR UNIT CLR 121 MTR 121J-53 13 CHG PMP MTR UNIT CLR 121 MTR 1215-54 11 CHG PMP MTR UNIT CLR 121 MTR 121J-58 TRN A EVENT MON W WEST UNIT CLR 121 MTR 12 1J-62 11 CHG PUMP RM EXHT FAN 121 MTR 12 15-63 13 CHG PUMP RM EXHT FAN 121 MTR 1215-70 12 SI PMP MTR UNIT CLR 121 MTR 121J-71 12 SI PMP MTR UNIT CLR 121 MTR 1213-72 12 SI PMP MTR UNIT CLR 121 MTR 1213-73 12 SI PMP MTR UNIT CLR 121 MTR 121J-74 12 SI PMP MTR UNIT CLR 121 MTR 121J-80 12 CS PMP MTR UNIT CLR 121 MTR 1215-81 12 CS PMP MTR UNIT CLR 121 MTR 121J-82 12 CS PMP MTR UNIT CLR 121 MTR 1215-90 12 RHR PMP UNIT CLR 121 MTR 1215-91 12 RHR PMP UNIT CLR MCC 1K2
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 44 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, D6 COMP. RY: JS BUS EO EOUIPMENT
- NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads MTR 121K-38 122 D2 DSL GEN RM SPLY FAN MTR 121K-39 122 D2 DSL GEN RM EXHT FAN MTR 121K-40 D2 DSL GEN START-UP AIR COMPR MTR 121K-57 123 DSL GEN FOST XFER PMP 121 MTR 121K-60 D2 DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC 1TA2 42.29 54.26 42.29 122 MTR 122-1 122 SWGR RM UNIT CLR 0.86 1.73 Y 0.86 BUS 122 0.86 1.73 0.86 122 MTR 1221)-51 122 ABSV EXHT FLTR HTR 20.00 20.00 Y 20.00 122 MTR 122D-54 122 ABSV EXHT FAN 19.12 23.90 Y 19.12 MCC 1MA2 Transferable 39.12 43.90 39.12
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 45 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. RV1 TS BUS EQUIPMENT NAME KW KVA DBAPOST WithSO%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads MTR 122E-14 12 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 122E- 12 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 122E-15 122 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 122E-18 12 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 122E-32 14 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 122E-56 12 RX VSL GAP CLG SPLY FAN MTR 122E-57 12 RX VSL SUPPORT CLG FAN MTR 122E-8 11 BORIC ACID TANK HEATER B 122 MTR 122E-9 121 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 1L2 101.57 126.94 75.91
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 46 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: IS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads 122 MTR 122G-1 11 CNTMTISBV AIR RAD MON 1RE-11/12(29028/29029) 122 MTR 122G-11 122 CONT RM CHLR MTR 1226-12 122 CONT RM CHLD WTR PMP MTR 1226-13 122 CONT RM CLEAN-UP FAN MTR 1220-14 RECEPTACLE PANEL 1RPB8 120 MTR 1226-3 122 CONT R M CHLR OIL PMP 122 MTR 1226-4 122 SFP PMP 122 MTR 1226-5 122 CONT RM AIR HNDLR & FAN 122 MTR 1226-8 AUX BLDG VENT GAS RAD MON IRE-30 (29004) 1.01 1.55 Y 222 MTR 2226- 1 SHLD BLDG VENT GAS RAD MON 2RE-22 (29033) 1.01 1.55 Y 222 MTR 2226- 15 122N RELAY RM UNIT CLR 0.86 1.73 Y 222 MTR 2226-16 TRN B EVENT MON RM UNIT CLR 0.86 1.73 Y 222 MTR 2226-17 122s RELAY RM UNIT CLR 0.86 1.73 Y 222 MTR 2226-8 AUX BLDG VENT GAS RAD MON 2R.E-30 (29005) 1.01 1.55 Y MCC IT2 Transferable 252.08 303.28 122 MTR 122J-2s 12 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 122 MTR 122J-3S 14 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x2 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 47 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads 122 MTR 122K-35 12 SBV RECIRC FAN 15.93 19.92 Y 15.93 122 MTR 122K-36 12 SBV EXHT FAN 0.73 1.12 Y 0.73 122 MTR 122K-40 AC DIST PANEL 145 FEEDER 4.50 5.00 Y 4.50 122 MTR 122K-47 122 SMPL RM EXHT FAN 6.69 8.37 Y 6.69 122 MTR 122K-55 12 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC lM2 43.85 50.41 43.85 15 MTR 15-1 11 SIPUMP 63 1.20 692.80 Y 63 1.20 15 MTR 15-4 11RHRPUMP 162.10 180.10 Y 162.10 15 MTR 15-5 11 CCPMP 199.00 222.80 Y 199.00 15 MTR 15-9 11 CS PMP 199.10 227.00 Y 199.10 BUS 15 1191.40 1322.70 1191.40 16 MTR 16-1 12 CS PMP 199.10 227.00 Y 199.10 16 MTR 16-3 12 MD AFW PMP 233.90 266.70 Y 233.90 16 MTR 16-5 12 CC PMP 199.00 222.80 Y 199.00 16 MTR 16-6 12 RHR PUMP 162.10 ' 180.10 Y 162.10 16 MTR 16-7 12 SI PUMP 63 1.20 692.80 Y 63 1.20 BUS 16 142530 1589.40 1425.30
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 48 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent 180 MTR 181-1 PRZR HTRS 1-2; 1-23&1-50 38.40 38.40 I 19.20 180 MTR 181-2 PRZR HTRS 1-6;l-28&1-56 38.40 38.40 I 19.20 180 MTR 181-3 PRZR HTRS 1-11;l-33&1-59 38.40 38.40 I 19.20 180 MTR 1814 PRZR HTRS 1-15;l-38&1-67 38.40 38.40 I 19.20 180 MTR 181-5 PRZR HTRS 1-43;l-73&1-74 38.40 38.40 I 19.20 MCC 1R1 192.00 192.00 96.00 21 1 MTR 211D 2 1 D5 DSL RM COOLING FAN 97.87 113.80 Y 97.87 BUS 211 97.87 f 13.80 97.87 21 1 MTR 211E-5 123 STA AIR COMPR 79.17 94.81 I 39.59 21 1 MTR 211E-8 21 BATT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 MCC 2A1 79.69 95.61 40.11 211 MTR 211F-31 2 1 INVERTER (INSTR BUS 11-WI) 6.26 6.95 Y 6.26 21 1 MTR 21 IF-32 23 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 211 MTR 211F-33 2 1 BATTERY CHARGER 39.15 44.24 Y 39.15 21 1 MTR 21 IF-35 2 1 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 21 1 MTR 21 IF-36 27 INVERTER 6.26 6.95 Y 6.26 MCC 2AC1 125.43 140.09 125.43
PINGP CALCULATION NUMBER. ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 49 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Ym for intermittent loads MTR211J-1 22 CHG PMP MTR211J-51 21 CC PMP MTR UNIT CLR MTR 21 1J-52 22 CHG PMP MTR UNIT CLR MTR 2 11J-57 22 CHG PUMP RM EXHT FAN MTR211J-60 21 SI PMP MTR UNIT CLR MTR211J-61 2 1 SI PMP MTR UNIT CLR MTR 2 11J-62 21 SI PMP MTR UNIT CLR MTR 2115-63 2 1 SI PMP MTR UNIT CLR MTR 2 115-64 21 SI PMP MTR UNIT CLR MTR 2 11J-70 21 CS PMP MTR UNIT CLR MTR 2115-71 2 1 CS PMP MTR UNIT CLR MTR 2 115-72 21 CS PMP MTR UNIT CLR MTR 21 15-80 21 RHR PMP UNIT CLR MTR 2115-81 2 1 RHR PMP UNIT CLR MCC 2Kl 111.99 123.62 111.99
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 50 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl,. D2,. D5,
. D6 COMP. RY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent MTR 21 1K-1 2 1 D5 FO STG TNK XFER PMP MTR 211K-10 D5 ENG 2 HTLT RADIATOR FAN 2 MTR 211K-12 2 1 D5 DSL GEN BLDG SPLY FAN MTR 211K-13 2 1 D5 DSL GEN BLDG RETURN FAN MTR 211K-15 23 D5 DSL GEN BLDG SPLY FAN MTR 211K-16 23 D5 DSL GEN BLDG RETURN FAN MTR211K-19 AC DISTRUBUTION PANEL 247 MTR 21 1K-2 D5 ENG 1 FO B-U PMP MTR 21 1K-3 D5 ENG 1 HTLT RADIATOR FAN 1 MTR 21 1K-5 23 D5 FO STG TK XFER PUMP 21 1 MTR 2 11K-6 D5 ENG 2 FO B-U PMP 1.14 1.75 Y 1.14 21 1 MTR 21 1K-7 D5 ENG 1 HTILT RADIATOR FAN 2 38.20 47.75 Y 38.20 21 1 MTR 211K-9 D5 ENG 2 HTLT RADIATOR FAN 1 38.20 47.75 Y 38.20 MCC 2TAl 318.14 398.88 313.01 212 MTR 212C-1 PRZR HTRS 2-13;2-368~2-65 38.40 38.40 I 19.20 2 12 MTR 2 I2C-2 PRZR HTRS 2-9;2-3 1&2-59 38.40 38.40 I 19.20 212 MTR 2 12C-3 PRZR HTRS 2-4;2-268~2-54 38.40 38.40 I 19.20 212 MTR 212C-4 PRZR HTRS 2-2 1;2-478~2-48 38.40 38.40 I 19.20 212 MTR 2 12C-5 PRZR HTRS 2-18;2-42;&2-72 38.40 38.40 I 19.20 MCC 2S1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 5 1 of I06 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads 212 MTR 212E-14 2 1 BORIC ACID TRANSFER PUMP 212 MTR 2 12E- 2 1 BORIC ACID TRANSFER PUMP (SLOW SPEED) 14s 212 MTR 212E-18 2 1 CNTMT DOME RECIRC FAN 212 MTR 212E-19 23 CNTMT DOME RECIRC FAN 2 12 MTR 2 12E-44 2 1 RX VSL GAP CLG SPLY FAN 2 12 MTR 2 12E-45 21 RX VSL SUPPORT CLG FAN 212 MTR 2 12E-8 2 1 BORIC ACID TANK HEATER A MCC 2L1 212 MTR 212J-2s 2 1 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 212 MTR 212J-3s 23 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2x1 40.52 106.64 40.52 212 MTR 2 12K-35 2 1 SBV RECIRC FAN 15.93 19.92 Y 15.93 212 MTR 212K-36 2 1 SBV EXHT FAN 0.62 0.96 Y 0.62 212 MTR 2 12K-42 2 1 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC 2M1 32.55 36.88 32.55
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 52 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBA POST With 50°/0 COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent 22 1 MTR 221B-51 22 CC PMP MTR UNIT CLR 0.60 1.20 Y 0.60 22 1 MTR 221B-52 23 CHG PMP MTR UNIT CLR 0.50 1.OO Y 0.50 22 1 MTR 221B-53 2 1 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 22 1 MTR 221B-57 2 1 CHG PUMP R M EXHT FAN 0.42 0.76 Y 0.42 22 1 MTR 22 1B-58 23 CHG PUMP RM EXHT FAN 0.33 0.60 Y 0.33 22 1 MTR 221B-60 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-61 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-62 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 221 MTR 221B-63 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-64 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-70 22 CS PMF' MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-71 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 1B-72 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-80 22 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-8 1 22 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 2KA2 7.21 14.19 7.21 22 1 MTR 221D 22 D6 DSL R M COOLING FAN 97.87 113.80 Y 97.87 BUS 221 97.87 113.80 97.87
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 53 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN YIN for intermittent MTR 221F-31 22 INVERTER (INSTR BUS I-RED)
MTR 221F-33 22 BATTERY CHARGER 22 1 MTR 22 1F-34 24 INVERTER (INSTR BUS IV-YEL) 22 1 MTR 221F-35 22 BATT RM SPCL EXHT FAN 22 1 MTR 221F-36 28 INVERTER MCC 2AC2 5833 65.70 58.33 22 1 MTR 2215-1 21 CHG PMP 105.00 110.53 Y 105.00 22 1 MTR 2215-2 23 CHG PMP 105.00 110.53 Y 105.00 MCC 2K2 210.00 22 1.06 210.00
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 54 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EQ EQUIPMENT NAME KW KVA DBA POST With 5O0/0 COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads 22 1 MTR 221K-1 22 D6 FO STG TNK XFER PMP 4.18 5.57 I 2.09 MTR 221K-10 D6 ENG 2 HTLT RADIATOR FAN 2 MTR 221K-12 22 D6 DSL GEN BLDG SPLY FAN MTR 221K-13 22 D6 DSL GEN BLDG RETURN FAN MTR 221K-15 24 D6 DSL GEN BLDG SPLY FAN MTR 221K-16 24 D6 DSL GEN BLDG RETURN FAN MTR 221K-19 AC DISTRUBUTION PANEL 248 22 1 MTR 221K-2 D6 ENG 1 FO B-U PMP 22 1 MTR 22 13-3 D6 ENG 1 HTLT RADIATOR FAN 1 22 1 MTR 22 1K-5 24 D6 FO STG TNK XFER PMP 22 1 MTR 22 1K-6 D6 ENG 2 FO B-U PMP 1.14 1.75 Y 1.14 22 1 MTR 22 1K-7 D6 ENG 1 HTLT RADIATOR FAN 2 38.20 47.75 Y 38.20 22 1 MTR 221K-9 D6 ENG 2 HTLT RADIATOR FAN 1 38.20 47.75 Y 38.20 MCC 2TA2 318.14 398.89 313.01 MTR 222E-18 22 CNTMT DOME RECIRC FAN 11.2 14.0 1 Y 11.20 MTR 222E-32 24 CNTMT DOME RECIRC FAN 11.2 14.0 1 Y 11.20 MTR 222E-43 22 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 MTR 222E44 22 RX VSL SUPPORT CLG FAN 21.67 27.09 21.67 MTR 222E-5 22 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 222E-5s 22 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 MTR 222E-8 2 1 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 2L2 75.16 95.83 62.81
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 55 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.2 5 - 30 Minute Loading BUS EO -
EOUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent loads 222 MTR 2225-23 22 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 222 MTR 222J-3s 24 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2x2 40.52 106.64 40.52 222 MTR 222K-35 22 SBV RECIRC FAN 15.93 19.92 Y 15.93 222 MTR 222K-36 22 SBV EXHT FAN 0.62 0.96 Y 0.62 222 MTR 222K-40 AC DIST PANEL 245 FEEDER 4.50 5.00 Y 4.50 222 MTR 222K-42 22 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC 2M2 37.05 41.88 37.05 25 MTR 25-10 21 MD AFW PMP 233.90 266.70 Y 233.90 25 MTR 25-13 21 CC PMP 199.00 222.80 Y 199.00 25 MTR 25-7 2 1 RHR PMP 160.50 180.10 Y 160.50 25 MTR 25-8 21 SI PMP 63 1.20 692.80 Y 63 1.20 25 MTR 25-9 21 CS PMP 199.10 227.00 Y 199.10 BUS 25 1423.70 1589.40 1423.70 26 MTR 26-10 22 SI PMP 63 1.20 692.80 Y 63 1.20 26 MTR 26-11 22 RHR PMP 160.50 180.10 Y 160.50 26 MTR 26-5 22 CC PMP 199.00 222.80 Y 199.00 26 MTR 26-9 22 CS PMP 199.10 227.00 Y 199.10 BUS 26 1189.80 1322.70 1189.80
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 56 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, D6 COMP. BY: JS BUS EO -
EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL. ACTUAL SEQ 5-30 reduction TAG MIN Y/N for intermittent 27 MTR 27-1 121 MD CLG WTR PMP 783.09 879.88 Y 783.09 BUS 27 783.09 879.88 783.09 270 MTR 271-1 PRZR HTRS 2-15;2-388~2-67 38.40 38.40 I 19.20 270 MTR 271-2 PRZR HTRS 2-33 ;2-6 1&2-62 38.40 38.40 I 19.20 270 MTR 27 1-3 PRZR HTRS 2-6;2-288~2-56 38.40 38.40 I 19.20 270 MTR 271-4 PRZR HTRS 2-2;2-23&2-50 38.40 38.40 I 19.20 270 MTR 271-5 PRZR HTRS 2-44;2-75&2-76 38.40 38.40 I 19.20 MCC 2R1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 57 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads 111 MTR lllC-10 121 CLG WTR SFGD TRVLG SCRN 0.61 0.94 I 0.3 1 21 1 MTR 111C-25 11 SFGDS SCRNHSE ROOF EXHT FAN 8.60 10.76 Y 8.60 211 MTR 111C-27 12 CLG WTR PMP STARTING AIR COMPR 12.75 15.93 I 6.38 21 1 MTR 11l C-52 121 SCREEN DIFF CONT PNL 70385 0.86 0.96 Y 0.86 MCC lABl Transferable 22.82 28.59 16.14 MTR 111E-13 11 B A l T RM SPCL EXHT FAN MTR 111E-43 123 AIR COMPR UNIT CLR MTR 111E-44 121 AIR COMPR UNIT CLR MTR 111E-45 11/21 TD AFW PMPS UNIT CLR MTR 11lE-46 111 SWGR RM UNIT CLR MTR 111E-47 15 SWGR RM UNIT CLR 111 MTR 11lE-6 121 STA AIR COMPR 79.17 94.8 1 Y 79.17 MCC 1Al 84.29 104.77 83.77 111 MTR 111F-31 11 INVERTER (INSTR BUS 11-WHI) 6.26 6.95 Y 6.26 111 MTR 11lF-32 13 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 111 MTR 1l lF-33 11 BATTERY CHARGER 39.15 44.24 Y 39.15 111 MTR 11lF-35 11 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 111 MTR lllF-36 17 INVERTER 6.26 6.95 Y 6.26 MCC lACl 125.43 140.09 125.43
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 58 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads MTR 111J-1 12 CHG PMP 105.00 110.53 Y 105.00 MTR lllJ-12 11/21 RHR CUBICLE AIR MNTR RE-26 (29026) 0.93 1.55 Y 0.93 MTR 1115-14 11 RHR PIT SUMP PMP 2.42 3.03 Y 2.42 MTR 111J-52 11 CC PMP MTR UNIT CLR 1.04 2.07 Y 1.04 MTR 111J-53 12 CHG PMP MTR UNIT CLR MTR 1115-57 112 SWGR RM UNIT CLR MTR 111J-59 12 CHG PUMP RM EXHT FAN 111 MTR 111J-70 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR lllJ-71 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 111J-72 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 1115-73 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 111J-74 11 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 1115-80 11 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 111J-8 1 11 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 111 MTR 1115-82 11 CSPMP h4TRUNITCLR 0.45 0.89 Y 0.45 111 MTR 111J-90 11 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 111 MTR 1115-91 11 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 1K1 115.93 130.08 115.93 111 MTR 111K-32 121 D l DSL GEN RM SPLY FAN 16.74 20.93 Y 16.74 111 MTR 111K-33 121 D l DSL GEN RM EXHT FAN 16.74 20.93 Y 16.74 111 MTR 111K-56 121 DSL GEN FOST XFER PMP 0.68 1.24 Y 0.68 111 MTR 111K-60 D l DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC lTAl 34.82 44.30 34.82
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 59 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUKPMENT NAME KW KVA DBA POST With 50O/0 COMPONENT ACTUAL ACTUAL SEQ lL2 reduction TAG TO 1HR for YlTV intermittent 112 MTR 112C-1 PRZR HTRS 1-3;l-25 & 1-54 38.40 38.40 I 19.20 MTR 112C-2 PRZR HTRS 1-8;l-30&1-58 MTR 112C-3 PRZRHTRS 1-12;l-35&1-64 MTR 112C-4 PRZR HTRS 1- 16;1-40&1-70 112 MTR 112C-5 PRZR HTRS 1-45&1-77 38.40 38.40 I 19.20 MCC IS1 192.00 192.00 96.00 112 MTR 112D-51 121 ABSV EXHT FLTR HTR 20.00 20.00 Y 20.00 112 MTR 112D-54 121 ABSV EXHT FAN 19.12 23.90 Y 19.12 MCC lMAl Transferable 39.12 43.90 39.12 MTR 112E-14 11 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 112E- 11 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 112E-15 121 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 112E-18 11 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-19 13 CNTMT DOME RECIRC FAN MTR 112E-56 11 RX VSL SUPPORT CLG FAN MTR 112E-57 1 1 RX VSL GAP CLG SPLY FAN 112 MTR 1128-62 123 WASTE GAS COMPRESSOR 19.95 24.94 I 9.98 112 MTR 112E-8 11 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 112 MTR 112E-9 121 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 1L1 121.52 151.88 85.89
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 60 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with LOSS DATE: 11/12/2007 of Offsite Power (LOOP) for Dl., D2., D5., D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO lHR for Y/N intermittent MTR 112G-1 SHLD BLDG VENT GAS RAD MON IRE-22 (29032)
MTR 112G-11 12 1 CONT RM CHLR MTR 112G-12 121 CONT RM CHLD WTR PMP MTR 112G-13 121 CONT RM CLEAN-UP FAN MTR 112G-14 RECEPTACLE PNL 1RPA8 MTR 112G-15 12 1N RELAY RM UNIT CLR MTR 112G-16 TRN A EVENT MON RM EAST UNIT CLR MTR 112G-17 121S RELAY RM UNIT CLR MTR 112G-18 BA HEAT TRACE SWITCHRACK I (PNL Em-1,B,C) 90.00 90.00 I 45.00 MTR 112G-19 BA HEAT TRACE SWITCHRACK I11 (PNL ETN-N) 30.00 30.00 I 15.00 MTR 112G-4 121 SFP PMP 55.95 71.90 55.95 112 MTR 112G-5 121 CONT RM AIR HNDLR & FAN 12.30 15.38 Y 12.30 112 MTR 112G-8 AUX BLDG VENT GAS RAD MON IRE-37 (29049) 1.01 1.55 Y 1.01 212 MTR 212G-1 21 CNTMTISBV AIR RAD MON 2RE-11/12 1.40 2.15 Y 1.40 (29030129031) 212 MTR 212G-8 AUX BLDG VENT GAS RAD MON 2RE-37 (29050) 1.01 1.55 Y 1.01 MCC IT1 373.14 424.99 313.14 Transferable 112 MTR 112J-2s 11 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 112 MTR 112J-3s 13 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x1 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 61 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl.. D2,. D5,. D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG T O 1HR for YfN intermittent MTR 112K-35 11 SBV RECIRC FAN MTR 112K-36 11 SBV EXHT FAN MTR 112K-47 121 SMPL RM EXHT FAN MTR 112K-48 121 SMPL RM BSTR FAN MTR 112K-55 11 SBV EXHT FLTR HTR MCC l M l 40.03 46.76 40.03 22 1 MTR 121C-25 21 SFGDS SCRNHSE ROOF EXHT FAN 8.73 10.92 Y 8.73 22 1 MTR 121C-27 22 CLG WTR PMP STARTING AIR COMPR 12.75 15.93 I 6.38 22 1 MTR 121C-52 122 SCREEN DIFF CONT PNL 70386 0.86 0.96 Y 0.86 121 MTR 121C-9 122 CLG WTR SFGD TRVLG SCRN 0.61 0.94 I 0.3 1 MCC 1AB2 Transferable 22.95 28.75 16.27 121 MTR 121E-44 12/22 MD AFW PMPS UNIT CLR 1.04 2.07 Y 1.04 121 MTR 121E-45 121 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 121 MTR 121E-46 16 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 MCC 1A2 2.76 5.51 2.76 121 MTR 121F-31 12 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 121 MTR 121F-33 12 BATTERY CHARGER 39.15 44.24 Y 39.15 121 MTR 121F-34 14 INVERTER (INSTR BUS IV-YEL) 6.26 6.95 Y 6.26 121 MTR 121F-35 12 BA'lT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 121 MTR 121F-36 18 R\NERTER 6.26 6.95 Y 6.26 MCC 1AC2 58.45 65.89 58.45
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 62 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for YN intermittent MTR 1215-1 11 CHG PMP MTR 121J-10 12 RHR PIT SUMP PMP MTR 121J-2 13 CHG PMP MTR 1215-3 12121 RHR CUBICLE AIR MNTR RE-27(29041)
MTR 1215-52 12 CC PMP MTR UNIT CLR MTR 1215-53 13 CHG PMP MTR UNIT CLR MTR 121J-54 11 CHG PMP MTR UNIT CLR MTR 121J-58 TRN A EVENT MON RM WEST UNIT CLR MTR 1215-62 11 CHG PUMP RM EXHT FAN MTR 121J-63 13 CHG PUMP RM EXI-IT FAN 121 MTR 121J-70 12 SI PMF MTR UNIT CLR 121 MTR 1215-71 12 SI PMP MTR UNIT CLR 121 MTR 1215-72 12 SI PMP MTR UNIT CLR MTR 1215-73 12 SI PMP MTR UNIT CLR MTR 121J-74 12 SI PMP MTR UNIT CLR MTR 121J-80 12 CS PMP MTR UNIT CLR 121 MTR 1215-81 12 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 121 MTR 121J-82 12 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 121 MTR 12 15-90 12 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 121 MTR 1215-91 12 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 1K2 222.03 242.68 222.03
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 63 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIF'MENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads MTR 121K-38 122 D2 DSL GEN RM SPLY FAN MTR 121K-39 122 D2 DSL GEN RM EXHT FAN MTR 121K-57 123 DSL GEN FOST XFER PMP MTR 121K-60 D2 DSL GEN CLEAN FUEL RTRN PMP MCC 1TA2 34.82 44.30 34.82 122 MTR 122-1 122 SWGR RM UNIT CLR 0.86 1.73 Y 0.86 BUS 122 0.86 1.73 0.86 122 MTR 122D-51 122 ABSV EXHT FLTR HTR 122 MTR 122D-54 122 ABSV EXHT FAN MCC 1MA2 Transferable 39.12 43.90 39.12 122 MTR 122E-14 12 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 122E- 12 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 122E-15 122 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 122E-18 12 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 122 MTR 122E-32 14 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 122 MTR 122E-56 12 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 122 MTR 122E-57 12 RX VSL SUPPORT CLG FAN 19.12 23.9 Y 19.12 122 MTR 122E-8 11 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 122 MTR 122E-9 121 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 1L2 101.57 126.94 75.91
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 64 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, DS, D6 COMP. RY: JS BUS EO -
EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Yrn intermittent MTR 1226- 1 11 CNTMTISBV AIR RAD MON IRE-11/12(29028/29029)
MTR 1226-11 122 CONT RM CHLR MTR 1226-12 122 CONT RM CHLD WTR PMP 122 MTR 1226-13 122 CONT RM CLEAN-UP FAN 122 MTR 1226-14 RECEPTACLE PANEL lRPB8 122 MTR 1226-4 122 SFP PMP 122 MTR 1226-5 122 CONT RM AIR HNDLR & FAN 12.30 15.38 Y 12.30 122 MTR 1226-8 AUX BLDG VENT GAS RAD MON IRE-30 (29004) 1.01 1.55 Y 1.01 222 MTR 2226-1 SHLD BLDG VENT GAS RAD MON 2RE-22 (29033) 1.01 1.55 Y 1.01 222 MTR 2226- 15 122N RELAY RM UNIT CLR 222 MTR 2226-16 TRN B EVENT MON RM UNIT CLR 222 MTR 2226- 17 122s RELAY RM UNIT CLR 222 MTR 2226-8 AUX BLDG VENT GAS RAD MON 2RE-30 (29005) 1.01 1.55 Y 1.01 MCC IT2 251.84 302.84 251.84 Transferable 122 MTR 122J-2S 12 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 122 MTR 122J-3s 14 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x2 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 65 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with LOSS DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 1/2 reduction TAG TO lHR for Y/N intermittent 122 MTR 122K-35 12 SBV RECIRC FAN 15.93 19.92 Y 15.93 122 MTR 122K-36 12 SBV EXHT FAN 0.73 1.12 Y 0.73 122 MTR 122K-40 AC DIST PANEL 145 FEEDER 4.50 5.00 Y 4.50 122 MTR 122K-47 122 SMPL RM EXHT FAN 6.69 8.37 Y 6.69 122 MTR 122K-55 12 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC lM2 43.85 50.41 43.85 15 MTR 15-1 11 SI PUMP 63 1.20 692.80 Y 63 1.20 15 MTR 15-4 11 RHR PUMP 162.10 180.10 Y 162.10 15 MTR 15-5 11 CCPMP 199.00 222.80 Y 199.00 15 MTR 15-9 11 CS PMP 199.10 227.00 Y 199.10 BUS 15 1191.40 1322.70 1191.40 MTR 16-1 12 CS PMP MTR 16-3 12 MD AFW PMP MTR 16-5 12 CC PMP MTR 16-6 12 RHR PUMP MTR 16-7 12 SI PUMP BUS 16 1425.30 1589.40 1425.30
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 66 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads MTR 181-1 PRZRHTRS 1-2;l-23&1-50 MTR 181-2 PRZR HTRS 1-6;l-288~1-56 MTR 181-3 PRZRHTRS 1-11;l-338~1-59 MTR 181-4 PRZR HTRS 1-15;l-38&1-67 MTR 181-5 PRZR HTRS 1-43;l-73&1-74 MCC 1R1 192.00 192.00 96.00 211 MTR 21 1D 2 1 D5 DSL R M COOLING FAN 97.87 113.80 Y 97.87 BUS 211 97.87 113.80 97.87 MTR 21 1E-5 123 STA AIR COMPR MTR 211E-8 2 1 BATT RM SPCL EXHT FAN MCC 2Al 79.69 95.61 40.11 21 1 MTR 211F-31 2 1 INVERTER (INSTR BUS 11-WHI) 6.26 6.95 Y 6.26 21 1 MTR 21 IF-32 23 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 211 MTR 211F-33 2 1 BATTERY CHARGER 39.15 44.24 Y 39.15 21 1 MTR 211F-35 2 1 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 21 1 MTR 2 1IF-36 27 INVERTER 6.26 6.95 Y 6.26 MCC 2ACl 125.43 140.09 125.43
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 67 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent MTR 2115-1 22 CHG PMP MTR 2115-14 2 1 RHR PIT SUMP PMP MTR 2115-51 2 1 CC PMP MTR UNIT CLR MTR 2 115-52 22 CHG PMP MTR UNIT CLR MTR 2 115-57 22 CHG PUMP RM EXHT FAN MTR 2 115-60 2 1 SI PMP MTR UNIT CLR MTR 2115-61 2 1 SI PMP MTR UNIT CLR MTR 2 115-62 2 1 SI PMP MTR UNIT CLR MTR 2 115-63 2 1 SI PMP MTR UNIT CLR MTR 2115-64 2 1 SI PMP MTR UNIT CLR MTR 2 115-70 2 1 CS PMP MTR UNIT CLR MTR 21 15-71 2 1 CS PMP MTR UNIT CLR MTR 2115-72 2 1 CS PMP MTR UNIT CLR MTR2115-80 2 1 RHR PMP UNIT CLR 21 1 MTR 2115-81 2 1 RHR PMP UNIT CLR 0.45 0.89 MCC 2K1 114.59 126.65
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 68 of 106 TITLE: Diesel Generator Steady State Loadmg for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads MTR 211K-1 2 1 D5 FO STG TNK XFER PMP MTR 211K-10 D5 ENG 2 HT/LT RADIATOR FAN 2 MTR 211K-12 21 D5 DSL GEN BLDG SPLY FAN MTR 211K-13 21 D5 DSL GEN BLDG RETURN FAN MTR 21 1K-15 23 D5 DSL GEN BLDG SPLY FAN MTR 211K-16 23 D5 DSL GEN BLDG RETURN FAN MTR 211K-19 AC DISTRUBUTION PANEL 247 MTR 21 1K-2 D5 ENG 1 FO B-U PMF' MTR 21 1K-3 D5 ENG 1 HTLT RADIATOR FAN 1 MTR 211K-5 23 D5 FO STG TK XFER PUMP MTR 2 11K-6 D5 ENG 2 FO B-U PMF' MTR 2 11K-7 D5 ENG 1 HTLT RADIATOR FAN 2 21 1 MTR 211K-9 D5 ENG 2 HT/LT RADIATOR FAN 1 38.20 47.75 Y 38.20 MCC 2TA1 318.14 398.88 313.01 MTR 212C-1 PRZR HTRS 2-13;2-36&2-65 MTR 212C-2 PRZR HTRS 2-9;2-3 1&2-59 MTR 212C-3 PRZR HTRS 2-4;2-26&2-54 MTR 212C-4 PRZR HTRS 2-21;2-47&2-48 MTR 212C-5 PRZR HTRS 2-18;2-42;&2-72 MCC 2S1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 69 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQUIPMENT NAME KW KVA DBA POST With 50°h COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent 212 MTR 2 12E-14 2 1 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 212 MTR 2 12E- 2 1 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s 212 MTR 212E-18 2 1 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 212 MTR 212E-19 23 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 212 MTR 2 12E-44 2 1 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 212 MTR 2 12E-45 2 1 RX VSL SUPPORT CLG FAN 2 1.67 27.09 Y 21.67 212 MTR 212E-8 2 1 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 2L1 75.16 95.83 62.81 212 MTR 2 12J-2s 2 1 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 212 MTR 2125-3s 23 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2x1 40.52 106.64 40.52 212 MTR 2 12K-35 21 SBV RECIRC FAN 15.93 19.92 Y 15.93 212 MTR 2 12K-36 2 1 SBV EMIT FAN 0.62 0.96 Y 0.62 212 MTR 2 12K-42 2 1 SBV EXHT FLTR HTR 16.00 16.00 Y 16.00 MCC 2M1 32.55 36.88 32.55
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 70 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads 22 1 MTR221B-51 22 CC PMP MTR UNIT CLR 0.60 1.20 Y 0.60 22 1 MTR 221B-52 23 CHG PMP MTR UNIT CLR 0.50 1.OO Y 0.50 22 1 MTR 221B-53 2 1 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 221 MTR 221B-57 2 1 CHG PUMP RM EXHT FAN 0.42 0.76 Y 0.42 22 1 MTR 221B-58 23 CHG PUMP RM EXHT FAN 0.33 0.60 Y 0.33 22 1 MTR 221B-60 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-61 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-62 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-63 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-64 22 SI PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-70 22 CS PMP MTR UNIT CLR 0.45 0.89 Y , 0.45 22 1 MTR 221B-71 22 CS PMP MTR UNIT CLR ' 0.45 0.89 Y 0.45 22 1 MTR 221B-72 22 CS PMP MTR UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 22 1B-80 22 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 22 1 MTR 221B-81 22 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 2KA2 7.21 14.19 7.21 22 1 MTR 221D 22 D6 DSL RM COOLING FAN 97.87 113.80 - Y 97.87 BUS 221 97.87 113.80 97.87
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 71 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent 22 1 MTR 221F-31 22 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 22 1 MTR 221F-33 22 BATTERY CHARGER 39.15 44.24 Y 39.15 22 1 MTR 221F-34 24 INVERTER (INSTR BUS IV-YEL) 6.26 6.95 Y 6.26 22 1 MTR 221F-35 22 BATT RM SPCL EXHT FAN 0.40 0.61 Y 0.40 22 1 MTR 221F-36 28 INVERTER 6.26 6.95 Y 6.26 MCC 2AC2 58.33 65.70 58.33 22 1 MTR 221J-1 21 CHG PMP 105.00 110.53 Y 105.00 221 MTR 2215-10 22 RHR PIT S U M P PMP 2.60 3.03 Y 2.60 22 1 MTR 22 1J-2 23 CHG PMP 105.00 110.53 Y 105.00 MCC 2K2 212.60 224.09 212.60
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 72 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent MTR 221K-1 22 D6 FO STG TNK XFER PMP MTR 221K-10 D6 ENG 2 HT/LT RADIATOR FAN 2 MTR 221K-12 22 D6 DSL GEN BLDG SPLY FAN MTR 221K-13 22 D6 DSL GEN BLDG RETURN FAN 22 1 MTR 221K-15 24 D6 DSL GEN BLDG SPLY FAN 38.20 47.75 38.20 22 1 MTR 221K-16 24 D6 DSL GEN BLDG RETURN FAN 38.20 47.75 38.20 22 1 MTR 221K-19 AC DISTRUBUTION PANEL 248 1.90 2.25 I 0.95 22 1 MTR 22 1K-2 D6 ENG 1 FO B-U PMP 1.14 1.75 Y 1.14 22 1 MTR 221K-3 D6 ENG 1 HT/LT RADIATOR FAN 1 38.20 47.75 Y 38.20 22 1 MTR 22 1K-5 24 D6 FO STG TNK XFER PMP 4.18 5.57 I 2.09 221 MTR 221K-6 D6 ENG 2 FO B-U PMP 1.14 1.75 Y 1.14 22 1 MTR 221K-7 D6 ENG 1 HTJLT RADIATOR FAN 2 38.20 47.75 Y 38.20 22 1 MTR 221K-9 D6 ENG 2 HT/LT RADIATOR FAN 1 38.20 47.75 Y 38.20 MCC 2TA2 318.14 398.89 313.01 222 MTR 222E- 18 22 CNTMT DOME RECIRC FAN 222 MTR 222E-32 24 CNTMT DOME RECIRC FAN 222 MTR 222E-43 22 RX VSL GAP CLG SPLY FAN 222 MTR 222E-44 22 RX VSL SUPPORT CLG FAN 222 MTR 222E-5 22 BORIC ACID TRANSFER PUMP 222 MTR 222E-5s 22 BORIC ACID TRANSFER PUMP (SLOW SPEED) 222 MTR 222E-8 2 1 BORIC ACID TANK HEATER B MCC 2L2
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 73 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.3 30 Minute - 1 Hour Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent loads MTR 222J-2s 22 FCU (SLOW SPEED)
MTR 2225-3s 24 FCU (SLOW SPEED)
MCC 2x2 40.52 106.64 40.52 MTR 222K-35 22 SBV RECIRC FAN MTR 222K-36 22 SBV EXHT FAN MTR 222K-40 AC DIST PANEL 245 FEEDER MTR 222K-42 22 SBV EXHT FLTR HTR MCC 2M2 37.05 41.88 37.05 25 MTR 25-10 21 MDAFWPMP 233.90 266.70 Y 233.90 25 MTR 25-13 21 CC PMF' 199.00 222.80 Y 199.00 25 MTR 25-7 2 1 RHR PMP 160.50 180.10 Y 160.50 25 MTR 25-8 21 SI PMP 63 1.20 692.80 Y 63 1.20 25 MTR 25-9 2 1 CS PMP 199.10 227.00 Y 199.10 BUS 25 1423.70 1589.40 1423.70 26 MTR 26-10 22 SI PMP 63 1.20 692.80 Y 63 1.20 26 MTR 26-1 1 22 RHR PMP 160.50 180.10 Y 160.50 26 MTR 26-5 22 CC PMP 199.00 222.80 Y 199.00 26 MTR 26-9 22 CS PMP 199.10 227.00 Y 199.10 BUS 26 1189.80 1322.70 1189.80
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 74 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBA POST With 50%
COMPONENT ACTUAL ACTUAL SEQ 112 reduction TAG TO 1HR for Y/N intermittent 27 MTR 27- 1 121 MD CLG WTR PMP 783.09 879.88 Y 783.09 BUS 27 783.09 879.88 783.09 270 MTR 271-1 PRZR HTRS 2-15;2-388~2-67 38.40 38.40 I 19.20 270 MTR 271-2 PRZR HTRS 2-33;2-618~2-62 38.40 38.40 I 19.20 270 MTR 271-3 PRZR HTRS 2-6;2-288~2-56 38.40 38.40 I 19.20 270 MTR 271-4 PRZR HTRS 2-2;2-238~2-50 38.40 38.40 I 19.20 270 MTR 271-5 PRZR HTRS 2-44;2-75&2-76 38.40 38.40 I 19.20 MCC 2R1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 75 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ > IHR reduction TAG Y/N for intermittent loads 111 MTR 11lC-10 121 CLG WTR SFGD TRVLG SCRN 0.61 0.94 I 0.3 1 111 MTR lllC-21 11 CLG WTR STRNR 0.48 0.88 I 0.24 111 MTR 11lC-22 2 1 CLG WTR STRNR 0.48 0.88 I 0.24 21 1 MTR 11lC-25 11 SFGDS SCRNHSE ROOF EXHT FAN 8.60 10.76 Y 8.60 21 1 MTR 111C-51 121 DD CLG WTR PMP OIL STG TNK PMP 0.68 1.24 I 0.34 21 1 MTR 11 lC-52 121 SCREEN DIFF CONT PNL 70385 0.86 0.96 Y 0.86 MCC l A B l Transferable 11.71 15.66 10.59 111 MTR 111E-13 11 BATT RM SPCL EXHT FAN 0.52 0.80 Y 0.52 111 MTR 111E-43 123 AIR COMPR UNIT CLR 1.04 2.07 I 0.52 111 MTR 111E-44 121 AIR COMPR UNIT CLR 1.04 2.07 Y 1.04 111 MTR 111E-46 111 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 111 MTR 111E-47 15 SWGR RM UNIT CLR 0.62 1.23 Y 0.62 111 MTR 11lE-6 121 STA AIR COMPR 79.17 94.8 1 Y 79.17 MCC 1Al 83.25 102.70 82.73 MTR 111F-31 1 1 INVERTER (INSTR BUS II-WHI)
MTR 11IF-32 13 INVERTER (INSTR BUS 111-BLU)
MTR 11lF-33 11 BATTERY CHARGER MTR 11lF-35 11 INTERRUPTABLE BUS AUX XFMR 111 MTR 11IF-36 17 INVERTER 6.26 6.95 Y 6.26 MCC lACl 92.81 101.73 92.81
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 76 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading --
BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ > IHR reduction TAG Y/N for intermittent MTR 111J-1 12 CHG PMP MTR 1115-12 11/21 RHR CUBICLE AIR MNTR RE-26 (29026)
MTR 1115-52 11 CC PMP MTR UNIT CLR MTR 111J-53 12 CHG PMP MTR UNIT CLR MTR 111J-57 112 SWGR RM UNIT CLR MTR 111J-59 12 CHG PUMP RM EXHT FAN MTR 1llJ-90 11 RHR PMP UNIT CLR MTR 1115-91 11 RHR PMP UNIT CLR MCC 1K1 111 MTR 11lK-32 121 D l DSL GEN RM SPLY FAN 16.74 20.93 Y 16.74 111 MTR 11lK-33 121 D l DSL GEN RM EXHT FAN 16.74 20.93 Y 16.74 111 MTR 111K-58 122 DSL GEN FOST XFER PMP 0.68 1.24 Y 0.68 111 MTR 111K-60 D l DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC lTAl 34.82 4430 34.82 112 MTR 112C-1 PRZR HTRS 1-3;l-25 & 1-54 38.40 38.40 I 19.20 112 MTR 112C-2 PRZRHTRS 1-8;l-30&1-58 38.40 38.40 I 19.20 112 MTR 112C-3 PRZR HTRS 1-12;l-35&1-64 38.40 38.40 I 19.20 112 MTR 112C-4 PRZR HTRS 1-16;1-408~1-70 38.40 38.40 I 19.20 112 MTR 112C-5 PRZR HTRS 1-45&1-77 38.40 38.40 I 19.20 MCC IS1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 77 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG ~m for intermittent loads 112 MTR 112E-14 11 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 112E- 11 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 112E-15 121 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 112E-18 11 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 112E-19 13 CNTMT DOME RECIRC FAN MTR 112E-56 11 RX VSL SUPPORT CLG FAN MTR 112E-57 11 RX VSL GAP CLG SPLY FAN 112 MTR 112E-8 11 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 112 MTR 112E-9 121 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 1L1 101.57 126.94 75.91 112 MTR 112G-1 SHLD BLDG VENT GAS RAD MON IRE-22 (29032) 1.01 1.55 Y 1.01 MTR 112G-14 RECEPTACLE PNL lRPA8 10.08 11.20 Y 10.08 MTR 112G-15 121N RELAY RM UNIT CLR 0.86 1.72 Y 0.86 MTR 112G-16 TRN A EVENT MON RM EAST UNIT CLR 1.86 3.73 1.86 MTR 112G-17 121S RELAY RM UNIT CLR 0.86 1.72 Y 0.86 MTR 112G-18 BA HEAT TRACE SWITCHRACK I (PNL ETN-l,B,C) 90.00 90.00 I 45.00 MTR 112G-19 BA HEAT TRACE SWITCHRACK III (PNL ETN-N) 30.00 30.00 I 15.00 112 MTR 112G-4 121 SFP PMP 55.95 71.90 55.95 112 MTR 112G-8 AUX BLDG VENT GAS RAD MON IRE-37 (29049) 1.01 1.55 Y 1.01 212 MTR 212G-1 2 1 CNTMTISBV AIR RAD MON 2RE-11/12 1.40 2.15 Y 1.40 (29030/29031) 212 MTR 2 120-8 AUX BLDG VENT GAS RAD MON 2RE-37 (29050) 1.01 1.55 Y 1.01 MCC IT1 Transferable 194.04 217.07 134.04
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 78 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent loads 112 MTR 112J-2s 11 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 112 MTR 112J-3s 13 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 1x1 40.52 106.64 40.52 112 MTR 112K-47 121 SMPL RM EXI-IT FAN 6.69 8.37 Y 6.69 MCC l M l 6.69 8.3 7 6.69 121 MTR 121C-21 12 CLG WTR STRNR 0.48 0.88 I 0.24 121 MTR 121C-22 22 CLG WTR STRNR 0.48 0.88 I 0.24 22 1 MTR 121C-25 2 1 SFGDS SCRNHSE ROOF EXHT FAN 8.73 10.92 Y 8.73 22 1 MTR 121C-51 122 DD CLG WTR PMP OIL STG TNK PMP 0.68 1.24 I 0.34 22 1 MTR 121C-52 122 SCREEN DIFF CONT PNL 70386 0.86 0.96 Y 0.86 121 MTR 121C-9 122 CLG WTR SFGD TRVLG SCRN 0.61 0.94 I 0.3 1 MCC 1AB2 Transferable 11.84 15.82 10.72 121 MTR 121E-43 122 AIR COMPR UNIT CLR 1.59 2.07 I 0.80 121 MTR 121E-44 12/22 MD AFW PMPS UNIT CLR 1.04 2.07 Y 1.04 121 MTR 121E-45 121 SWGR RM UNIT CLR 0.86 1.72 Y 0.86 121 MTR 121E-46 16 SWGR R M UNIT CLR 0.86 1.72 Y 0.86 121 MTR 121E-6 122 STA AIR COMPR 79.17 94.8 1 I 39.59 MCC 1A2 83.52 102.39 43.14
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 79 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y~N for intermittent loads MTR 121F-31 12 INVERTER (INSTR BUS I-RED)
MTR 121F-33 12 BATTERY CHARGER MTR 121F-34 14 INVERTER (INSTR BUS IV-YEL)
MTR 121F-35 12 BATT RM SPCL EXHT FAN MTR 121F-36 18 INVERTER MCC 1AC2 25.83 27.53 25.83 121 MTR 121J-1 11 CHG PMP 105.00 110.53 Y 105.OO MTR 1215-2 13 CHG PMP 105.00 110.53 Y 105.00 MTR 1215-3 12121 RHR CUBICLE AIR MNTR RE-27 (2904 1) 1.01 1.55 Y 1.O1 MTR 1215-52 12 CC PMP MTR UNIT CLR 1.04 2.07 Y 1.04 MTR 121J-53 I 3 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 MTR 1215-54 11 CHG PMP MTR UNIT CLR 0.86 1.73 Y 0.86 MTR 121J-58 TRN A EVENT MON RM WEST UNIT CLR 0.86 1.73 Y 0.86 MTR 121J-62 I I CHG PUMP Rh4 EXHT FAN 0.24 0.44 Y 0.24 MTR 121J-63 13 CHG PUMP RM EXHT FAN 0.24 0.44 Y 0.24 MTR 121J-90 12 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 121 MTR 1215-91 12 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 MCC 1K2 216.01 232.53 216.01
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 80 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > lHR reduction TAG YIN for intermittent loads 121 MTR 121K-38 122 D2 DSL GEN RM SPLY FAN 16.74 20.93 Y 16.74 121 MTR 121K-39 122 D2 DSL GEN RM EXHT FAN 16.74 20.93 Y 16.74 121 MTR 121K-59 124 DSL GEN FOST XFER PMP 0.68 1.24 Y 0.68 121 MTR 121K-60 D2 DSL GEN CLEAN FUEL RTRN PMP 0.66 1.20 Y 0.66 MCC 1TA2 34.82 44.30 34.82 122 MTR 122-1 122 SWGR RM UNIT CLR 0.86 1.73 Y 0.86 BUS 122 0.86 1.73 0.86 MTR 122E-14 12 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 122E- 12 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 122E-15 122 WASTE GAS COMPRESSOR 19.12 23.90 I 9.56 MTR 122E-18 12 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 122E-32 14 CNTMT DOME RECIRC FAN 12.37 15.46 Y 12.37 MTR 122E-56 12 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 MTR 122E-57 12 RX VSL SUPPORT CLG FAN 19.12 23.9 Y 19.12 122 MTR 122E-8 11 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 122 MTR 1226-9 121 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 1L2 101.57 126.94 75.91
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 81 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, DS, 0 6 COMP. BY: JS 6.4 1 Hour - 14 Da~Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With SO%
COMPONENT ACTUAL ACTUAL SEQ > IHR reduction TAG Y/N for intermittent MTR 122G-1 11 CNTMTISBV AIR RAD MON 1RE- 1.37 2.28 Y 1.37 11/12(29028/29029)
MTR 122G-11 122 CONT RM CHLR 140.47 159.63 Y 140.47 MTR 1226-12 122 CONT RM CHLD WTR PMP 20.40 25.50 Y 20.40 MTR 1226-14 RECEPTACLE PANEL lRPB8 9.81 10.90 Y 9.81 MTR 1226-18 BA HEAT TRACE SWITCHRACK I1 (PNL ETR- 75.00 75.00 I 37.50 D,E,F,G)
MTR 1226-19 BA HEAT TRACE SWITCHRACK IV (PNL ERT-R) 30.00 30.00 I 15.00 MTR 1226-4 122 SFP PMP 55.95 71.90 55.95 122 MTR 122G-5 122 CONT RM AIR HNDLR & FAN 12.30 15.38 122 MTR 1226-8 AUX BLDG VENT GAS RAD MON IRE-30 (29004) 1.01 1.55 222 MTR 2226-1 SHLD B W G VENT GAS RAD MON 2RE-22 (29033) 1.01 1.55 222 MTR 2226-15 122N RELAY RM UNIT CLR 0.86 1.73 222 MTR 2226-1 6 TRN B EVENT MON RM UNIT CLR 0.86 1.73 222 MTR 2226-17 122s RELAY RM UNIT CLR 0.86 1.73 222 MTR 2226-8 AUX BLDG VENT GAS RAD MON 2RE-30 (29005) 1.01 1.55 MCC IT2 Transferable 350.91 400.43 MTR 122J-2s 12 FCU (SLOW SPEED)
--- MTR 122J-3s 14 FCU (SLOW SPEED)
MCC 1x2 40.52 106.64 40.52
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 82 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading BUS EQ EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG YIN for intermittent loads 122 MTR 122K-40 AC DIST PANEL 145 FEEDER 4.50 5.00 Y 4.50 122 MTR 122K-47 122 SMPL RM EXHT FAN 6.69 8.37 Y 6.69 MCC 1M2 11.19 13.37 11.19 MTR 15-4 11 RHR PUMP MTR 15-5 11 CC PMP BUS 15 MTR 16-3 12 MD AFW PMP MTR 16-5 12 CC PMP MTR 16-6 12 RHR PUMP BUS 16 595.00 669.60 595.00 MTR 181-1 PRZR HTRS 1-2;1-23&1-50 MTR 181-2 PRZR HTRS 1-6;1-28&1-56 180 MTR 181-3 PRZR HTRS 1-11;1-338~1-59 38.40 38.40 I 19.20 180 MTR 181-4 PRZR HTRS 1-15;l-38&1-67 38.40 38.40 I 19.20 180 MTR 181-5 PRZR HTRS 1-43; 1-738~1-74 38.40 38.40 I 19.20 MCC 1R1 192.00 192.00 96.00 21 1 MTR 211D 2 1 D5 DSL RM COOLING FAN 97.87 113.80 Y 97.87 BUS 211 97.87 113.80 97.87
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 83 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQ EQUIPMENT NAME KW KVA DBAPOST Withso%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent MTR 21 1E-5 123 STA AIR COMPR MTR 21 1E-8 2 1 BATT RM SPCL EXHT FAN MCC 2A1 79.69 95.61 40.11 21 1 MTR 21 IF-31 2 1 INVERTER (INSTR BUS 11-WHI) 6.26 6.95 Y 6.26 21 1 MTR 21 IF-32 23 INVERTER (INSTR BUS 111-BLU) 6.26 6.95 Y 6.26 21 1 MTR 21 IF-33 2 1 BATTERY CHARGER 6.53 5.88 Y 6.53 21 1 MTR 21 IF-35 2 1 INTERRUPTABLE BUS AUX XFMR 67.50 75.00 67.50 21 1 MTR 211F-36 27 INVERTER 6.26 6.95 Y 6.26 MCC 2AC1 92.81 101.73 92.81 21 1 MTR211J-1 22 CHG PMP 105.00 110.53 Y 105.00 21 1 MTR211J-51 2 1 CC PMP MTR UNIT CLR 1.40 2.07 Y 1.40 21 1 MTR 2 115-52 22 CHG PMP MTR UNIT CLR 0.76 1.52 Y 0.76 211 MTR 2115-57 22 CHG PUMP RM EXHT FAN 0.33 0.60 Y 0.33 21 1 MTR 211J-80 21 RHR PMP UNIT CLR 0.45 0.89 Y 0.45 21 1 MTR 2115-81 21 RHRPMPUNITCLR 0.45 0.89 Y 0.45 MCC 2K1 10839 116.50 108.39
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 84 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent 21 1 MTR 211K-1 21 D5 FO STG TM(XFER PMP 4.17 5.57 I 21 1 MTR211K-10 D5 ENG 2 HT/LT RADIATOR FAN 2 38.20 47.74 Y 21 1 MTR 21 1K-12 21 D5 DSL GEN BLDG SPLY FAN 38.20 47.75 Y 21 1 MTR 211K-13 21 D5 DSL GEN BLDG RETURN FAN 38.20 47.75 Y 21 1 MTR211K-15 23 D5 DSL GEN BLDG SPLY FAN 38.20 47.75 21 1 MTR211K-16 23 D5 DSL GEN BLDG RETURN FAN 38.20 47.75 21 1 MTR 211K-19 AC DISTRUBUTION PANEL 247 1.91 2.25 I 21 1 MTR 211K-2 D5 ENG 1 FO B-U PMP 1.14 1.75 Y 21 1 MTR 211K-3 D5 ENG 1 HT/LT RADIATOR FAN 1 38.20 47.75 Y 21 1 MTR 2 11K-5 23 D5 FO STG TK XFER PUMP 4.18 5.57 I 21 1 MTR 21 1K-6 D5 ENG 2 FO B-U PMP 1.14 1.75 Y 21 1 MTR 211K-7 D5 ENG 1 HTILT RADIATOR FAN 2 38.20 47.75 Y 21 1 MTR 21 1K-9 D5 ENG 2 HT/LT RADIATOR FAN 1 38.20 47.75 Y MCC 2TAl 318.14 398.88 212 MTR 212C-1 PRZR HTRS 2-13;2-36&2-65 38.40 38.40 I 19.20 212 MTR 2 12C-2 PRZR HTRS 2-9;2-3 1&2-59 38.40 38.40 I 19.20 212 MTR 2 126-3 PRZR HTRS 2-4;2-26&2-54 38.40 38.40 I 19.20 212 MTR 2 12C-4 PRZR HTRS 2-2 1;2-47&2-48 38.40 38.40 I 19.20 212 MTR 212C-5 PRZR HTRS 2- 18;2-42;&2-72 38.40 38.40 I 19.20 MCC 2S1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 85 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent loads MTR 212E-14 2 1 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 MTR 2 12E- 21 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 14s MTR 212E-18 2 1 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 212E-19 23 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 MTR 2 12E-44 2 1 RX VSL GAP CLG SPLY FAN 6.39 8.53 Y 6.39 MTR 2 12E-45 21 RX VSL SUPPORT CLG FAN 2 1.67 27.09 Y 21.67 MTR 2 12E-8 2 1 BORIC ACID TANK HEATER A 7.50 7.50 I 3.75 MCC 2L1 75.16 95.83 62.81 MTR 2 12J-2s 2 1 FCU (SLOW SPEED)
MTR 212J-3s 23 FCU (SLOW SPEED)
MCC 2x1 40.52 106.64 40.52 MTR 221B-51 22 CC PMP MTR UNIT CLR 0.60 1.20 MTR 221B-52 23 CHG PMP MTR UNIT CLR 0.50 1.OO MTR 221B-53 21 CHG PMP MTR UNIT CLR 0.86 1.73 MTR 221B-57 2 1 CHG PUMP RM EXHT F A N 0.42 0.76 MTR 221B-58 23 CHG PUMP RM EXHT FAN 0.33 0.60 MTR 221B-80 22 RHR PMP UNIT CLR 0.45 0.89 MTR 221B-81 22 RHR PMP UNIT CLR 0.45 0.89 MCC 2KA2 3.61 7.07
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 86 of 106 TITLE: Diesel Generator Steady State.Loadingfor an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.4 1 Hour - 14 Day Loading EBUS EQ E Q W M E N T NAME COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent loads 22 1 MTR 221D 22 D6 DSL RM COOLING FAN 97.87 113.80 Y 97.87 BUS 221 97.87 113.80 97.87 22 1 MTR 221F-31 22 INVERTER (INSTR BUS I-RED) 6.26 6.95 Y 6.26 22 1 MTR 221F-33 22 BATTERY CHARGER 6.53 5.88 Y 6.53 22 1 MTR 221F-34 24 INVERTER (INSTR BUS IV-YEL) 6.26 6.95 Y 6.26 22 1 MTR 221F-35 22 BATT RM SPCL EXHT FAN 0.40 0.61 Y 0.40 22 1 MTR 221F-36 28 INVERTER 6.26 6.95 Y 6.26 MCC 2AC2 25.71 27.34 25.71 MTR221J-1 2 1 CHG PMP MTR 221J-2 23 CHG PMP MCC 2K2 210.00 221.06 210.00
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 87 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5, D6 COMP. BY: JS BUS EO EQUIPMENT
- NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent loads MTR 221K-1 22 D6 FO STG TNK XFER PMP MTR 221K-10 D6 ENG 2 HTILT RADIATOR FAN 2 MTR 221K-12 22 D6 DSL GEN BLDG SPLY FAN MTR 221K-13 22 D6 DSL GEN BLDG RETURN FAN MTR 221K-15 24 D6 DSL GEN BLDG SPLY FAN MTR 221K-16 24 D6 DSL GEN BLDG RETURN FAN MTR 221K-19 AC DISTRUBUTION PANEL 248 MTR 221K-2 D6 ENG 1 FO B-U PMP MTR 221K-3 D6 ENG 1 HTILT RADIATOR FAN 1 MTR 22 1K-5 24 D6 FO STG TNK XFER PMP MTR 22 1K-6 D6 ENG 2 FO B-U PMP 22 1 MTR 22 1K-7 D6 ENG 1 HTLT RADIATOR FAN 2 38.20 47.75 Y 38.20 22 1 MTR 22 1K-9 D6 ENG 2 HTJLT RADIATOR FAN 1 3 8.20 47.75 Y 38.20 MCC 2TA2 318.14 398.89 313.01 MTR 222E-18 22 CNTMT DOME RECIRC FAN 11.2 14.01 Y 11.20 222 MTR 222E-32 24 CNTMT DOME RECIRC FAN 222 MTR 222E-43 22 RX VSL GAP CLG SPLY FAN 222 MTR 222E-44 22 RX VSL SUPPORT CLG FAN 222 MTR 222E-5 22 BORIC ACID TRANSFER PUMP 11.47 14.34 I 5.74 222 MTR 222E-5s 22 BORIC ACID TRANSFER PUMP (SLOW SPEED) 5.73 10.35 I 2.87 222 MTR 222E-8 2 1 BORIC ACID TANK HEATER B 7.50 7.50 I 3.75 MCC 2L2 75.16 95.83 62.81
PINGP CALCULATION NUMBER: ENG-EE-02 I REVISION: 3 ADDENDUM: - SHEET NO: Page 88 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, DS,D6 COMP. BY: JS BUS EQUIPMENT NAME KW KVA DBAPOST With 50%
COMPONENT ACTUAL ACTUAL SEQ > IHR reduction TAG Y/N for intermittent 222 MTR 222J-2s 22 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 222 MTR 2225-3S 24 FCU (SLOW SPEED) 20.26 53.32 Y 20.26 MCC 2x2 40.52 106.64 40.52 222 MTR 222K-40 AC DIST PANEL 245 FEEDER 4.50 5.00 Y 4.50 MCC 2M2 4.50 5.00 4.50 25 MTR 25-1 0 21 MDAFWPMP 233.90 266.70 Y 233.90 25 MTR 25-13 21 CC PMF' 199.00 222.80 Y 199.00 25 MTR 25-7 2 1 RHR PMP 160.50 180.10 Y 160.50 BUS 25 593.40 669.60 593.40 26 MTR 26-1 1 22 RHR PMP 160.50 180.10 Y 160.50 26 MTR 26-5 22 CC PMP 199.00 222.80 Y 199.00 BUS 26 359.50 402.90 359.50 27 MTR 27-1 121 MD CLG WTR PMP 783.09 879.88 Y 783.09 BUS 27 783.09 879.88 783.09
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 89 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, D5, D6 COMP. BY: JS BUS EO EOUIPMENT NAME KW KVA DBAPOST With50%
COMPONENT ACTUAL ACTUAL SEQ > 1HR reduction TAG Y/N for intermittent loads 270 MTR 271-1 PRZR HTRS 2-1 5;2-38&2-67 38.40 38.40 I 19.20 270 MTR 271-2 PRZR HTRS 2-33;2-61&2-62 38.40 38.40 I 19.20 270 MTR 271-3 PRZR HTRS 2-6;2-28&2-56 38.40 38.40 I 19.20 270 MTR 27 1-4 PRZR HTRS 2-2;2-238~2-50 38.40 38.40 I 19.20 270 MTR 271-5 PRZR HTRS 2-44;2-75&2-76 38.40 38.40 I 19.20 MCC 2R1 192.00 192.00 96.00
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 94 of 106 TITLE: Diesel Generator Steady State Loadmg for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D l , D2, D5,D6 6.9 Power Factor Determination for 0 - 5 Minutes Loading EDG15 kW kVA EDG 16 kW kVA 1AB1 37.66 45.58 1AB2 37.79 45.74 1A1 85.90 107.24 1A2 85.13 104.86 1AC1 125.43 140.09 1AC2 58.45 65.89 1K1 113.51 127.05 1K2 219.61 239.64 1TAI 42.79 54.26 1TA2 42.29 54.26 1S1 192.00 192.00 BUS 122 0.86 1.73 IMA1 39.12 43.90 1MA2 39.12 43.90 IL1 121.52 151.88 IL2 101.57 126.94 1T I 373.38 425.43 1T2 252.08 303.28 1X I 40.52 106.64 1X2 40.52 106.64 1MI 32.66 37.04 1M2 43.85 50.41 1R1 192.00 192.00 I BUS l5 1191.40 1322.70 BUS 16 1425.30 1589.40 I
II EDG 2395.89 2753.81 EDG 16 TOTAL 2538.57 2924.69 I
EDG 15 Power Factor EDG 25 0.870 EDG 16 Power Factor EDG 26 0.868 I
2A1 2KA2 BUS 21 1 BUS 221 2AC1 2142 2K1 2AC2 2TA1 2K2 2S1 2TA2 2L1 2L2 2x1 2x2 2M1 2M2 IABl 2R1 1T I 1AB2 1MA1 1T2 1MA2 BUS 25 1423.70 1589.40 BUS 26 BUS 27 783.09 879.88 BUS 27 1 EDG 25 TOTAL 3722.54 4278.86 EDG 26 TOTAL 3339.77 3847.95 (
EDG 25 Power Factor 0.870 EDG 26 Power Factor 0.868
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 95 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2,D5,D6 COMP. BY: JS 6.10 Power Factor Determination for 5 - 30 Minutes Loading EDGI 5 kW kVA EDG 16 1ABI 35.78 42.35 1AB2 1A1 84.29 104.77 1A2 1AC1 125.43 140.09 1AC2 1K1 113.51 127.05 1K2 1TAI 42.79 54.26 1TA2 1S1 192.00 192.00 BUS 122 1MA1 39.12 43.90 1MA2 1L1 121.52 151.88 1L2 1T I 373.38 423.53 1T2 1x1 40.52 106.64 1X2 1M I 40.03 46.76 1M2 1R1 BUS 15 1191.40 1322.70 BUS 16 I EDG 2399.77 2755.93 EDG 16 TOTAL I EDG 15 Power Factor EDG 25 0.871 EDG 16 Power Factor EDG 26 2A1 2KA2 BUS 211 BUS 221 2AC1 2A2 2K1 2AC2 2TA1 2K2 2S1 2TA2 2L1 2L2 2x1 2x2 2M1 2M2 IABl 2R1 IT1 1AB2 1MA1 1T2 1MA2 BUS 25 1423.70 1589.40 BUS 26 BUS 27 783.09 879.88 BUS 27 I[ EDG 25 EDG 25 Power Factor 3728.42 4282.41 0.871 EDG 26 TOTAL EDG 26 Power Factor 0.868 I
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 96 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5, D6 COMP. BY: JS 6.1 1 Power Factor Determination for 30 Minute - 1 Hour Loading EDGI5 kW kVA EDG 16 kW kVA 1ABI 22.82 28.59 1AB2 22.95 28.75 1A1 84.29 104.77 1A2 2.76 5.51 1AC1 125.43 140.09 1AC2 58.45 65.89 1K1 115.93 130.08 1K2 222.03 242.68 I 1TAl 34.82 44.30 1TA2 34.82 44.30 1S1 192.00 192.00 BUS 122 0.86 1.73 I IMAI 39.12 43.90 1MA2 39.12 43.90 1L1 121.52 151.88 1L2 101.57 126.94 1 IT1 373.14 424.99 1T2 251.84 302.84 1X I 40.52 106.64 1X2 40.52 106.64 1M1 40.03 46.76 1M2 43.85 50.41 1R1 192.00 192.00 I
I BUS 15 1191.40 1322.70 BUS 16 1425.30 1589.40 I
EDG 15 TOTAL 2381.02 2736.70 EDG 16 TOTAL 2436.07 2800.99 I EDG 15 Power Factor EDG 25 0.870 EDG 16 Power Factor EDG 26 0.870 I 2A1 2KA2 BUS 21 1 BUS 221 2AC 1 2/42 2K1 2AC2 2TA1 2K2 2S1 2TA2 2L1 2L2 2x1 2x2 2M1 2M2 IA61 2R1 1T I 1AB2 1MA1 1T2 1MA2 BUS 25 1423.70 1589.40 BUS 26 1189.80 1322.70 BUS 27 783.09 879.88 BUS 27 783.09 879.88 II EDG 25 EDG 25 Power Factor 3717.82 4273.14 0.870 EDG 26 TOTAL EDG 26 Power Factor 3325.68 3831.09 0.868 I1
PINGP CALCULATION NUMBER: ENG-EE-021 REVISION: 3 ADDENDUM: - SHEET NO: Page 97 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for Dl, D2, D5,D6 COMP. BY:JS 6.12 Power Factor Determination for 1 Hour - 14 Days Loading EDGIS kW kVA EDG 16 kW kVA 1ABI 11.71 15.66 1A62 11.84 15.82 1A1 83.25 102.70 1A2 83.52 102.39 1AC1 92.81 101.73 1AC2 25.83 27.53 1K1 109.91 I19.93 1K2 216.01 232.53 1TAI 34.82 44.30 1TA2 34.82 44.30 1S1 192.00 192.00 BUS 122 0.86 1.73 1MA1 0.00 0.00 1MA2 0.00 0.00 1L l 101.57 126.94 1L2 101-57 126.94 1T I 194.04 217.07 1T2 350.91 400.43 1X I 40.52 106.64 1X2 40.52 106.64 1M I 6.69 8.37 1M2 11.19 13.37 1R1 192.00 192.00 I BUS 15 361.I 0 402.90 BUS 16 595.00 669.60 1 EDG 15 TOTAL 1228.42 1438.24 EDG I 6 TOTAL 1664.07 1933.28 I EDG 15 Power Factor 0.854 EDG 16 Power Factor 0.861 1 EDG 25 - EDG 26 2A1 2KA2 BUS 21 1 BUS 221 2AC1 2A2 2K1 2AC2 2TA1 2K2 2S1 2TA2 2L1 2L2 2x1 2x2 2M1 2M2 IABI 2R1 1T I 1A62 1MA1 1T2 1MA2 BUS 25 593.40 669.60 BUS 26 BUS 27 783.09 879.88 BUS 27 II EDG 25 EDG 25 Power Factor 2586.82 3003.20 0.861 EDG 26 TOTAL EDG 26 Power Factor 2472.85 2866.66 0.863 II
PINGP CALCULATION NUMBER: ENG-EE-02 1 REVISION: 3 ADDENDUM: - SHEET NO: Page 98 of 106 TITLE: Diesel Generator Steady State Loading for an SI Event Concurrent with Loss DATE: 11/12/2007 of Offsite Power (LOOP) for D 1, D2, D5,D6 COMP. BY: JS 7.0 Conclusions As shown by the following summary table, the kilowatt loading on Dl and D2 remains below the continuous duty rating of 2750 k W for both machines for all time periods. Likewise the kilowatt loading on D5 and D6 remains below the continuous duty rating of 5400 kW for both machines for all time periods.
Similarly the summary table demonstrates that the power factor for all four EDG's is greater than their rating of 0.8 for all time periods. NOTE: At the time of the writing of this revision, an LAR was being prepared to specify that a Technical Specification Surveillance requirement for testing the EDG7sat a Power Factor of 0.85. Should a future revision of this Design Calculation arrive at a Power Factor of less than 0.85, the Technical Specification Surveillance requirement should be revisited.
TABLE 1 EDG kW LOADING AND POWER FACTOR EDG 15 (Dl) EDG 16 0 2 ) EDG 25 @5) EDG 26 0 6 )
kW Power kW Power kW Power Loading Factor Loading Factor Loading Factor 0 - 5 MIN 2282.22 0.870 2458.98 0.868 3632.94 0.870 5 - 30 MIN 2286.65 0.871 2413.27 0.870 3639.47 0.871 3336.96 0.868 30 MIN- 1 HR 2267.47 0.870 2394.61 0.870 3628.84 0.870 1 HR- 14 DAYS 1090.15 0.854 1508.93 0.861 2463.73 0.861 LIMIT 2750.00 0.800 2750.00 0.800 5400.00 0.800