L-2011-223, Response to NRC Request for Additional Information (RAI) Regarding Extended Power Uprate (EPU) License Amendment Request (LAR) No. 205 and Electrical Engineering Branch Issues

From kanterella
(Redirected from L-2011-223)
Jump to navigation Jump to search

Response to NRC Request for Additional Information (RAI) Regarding Extended Power Uprate (EPU) License Amendment Request (LAR) No. 205 and Electrical Engineering Branch Issues
ML11192A204
Person / Time
Site: Turkey Point  
Issue date: 07/07/2011
From: Kiley M
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2011-223, TAC ME4907, TAC ME4908
Download: ML11192A204 (28)


Text

Florida Power & Light, 9760 S.W. 344 St. Homestead, FL 33035 0

JUL 0 7 2011 FPL.

L-2011-223 10 CFR 50.90 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555-0001 Re:

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Response to NRC Request for Additional Information (RAI) Regarding Extended Power Uprate (EPU) License Amendment Request (LAR) No. 205 and Electrical Engineering Branch Issues

References:

(1) M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2010-113), "License Amendment Request for Extended Power Uprate (LAR 205)," (TAC Nos. ME4907 and ME4908), Accession No. ML103560169, October 21, 2010.

(2) Email from J. Paige (NRC) to T. Abbatiello (FPL), "Turkey Point EPU - Electrical Engineering (EEEB) Request for Additional Information - Round 1," Accession No. ML110610719, March 2, 2011.

(3) M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2011-081), "Response to NRC Request for Additional Information (RAI) Regarding Extended Power Uprate (EPU)

License Amendment Request (LAR) No. 205 and Electrical Engineering Branch Issues,"

Accession No. ML110940179, March 31, 2011.

(4) Email from J. Paige (NRC) to S. Hale (FPL) "Turkey Point EPU - Electrical Engineering (EEEB) Request for Additional Information - Round 2," Accession No. ML11160A156, June 9, 2011.

By letter L-2010-113 dated October 21, 2010 [Reference 1], Florida Power and Light (FPL)

Company requested to amend Facility Operating Licenses DPR-31 and DPR-41 and revise the Turkey Point Units 3 and 4 Technical Specifications (TS). The proposed amendment will increase each unit's licensed core power level from 2300 megawatts thermal (MWt) to 2644 MWt and revise the Renewed Facility Operating Licenses and TS to support operation at this increased core thermal power level. This represents an approximate increase of 15% and is therefore considered an extended power uprate (EPU).

On March 2, 2011, FPL received an RAI via email from the U.S. Nuclear Regulatory Commission (NRC) Project Manager (PM) [Reference 2] regarding electrical engineering issues associated with the EPU Licensing Report. FPL provided responses to the RAI questions via FPL letter L-2011-081, dated March 31, 2011 [Reference 3].

By email from the NRC PM dated June 9, 2011 [Reference 4], additional information was requested by the NRC staff to support further review of the EPU LAR. The RAI consisted of two (2) questions pertaining to the RAI responses provided in Reference 3. These RAI questions and the FPL responses are documented in the Attachment to this letter.

Turkey Point Units 3 and 4 L-2011-223 Docket Nos. 50-250 and 50-251 Page 2 of 2 In accordance with 10 CFR 50.91(b)(1), a copy of this letter is being forwarded to the State Designee of Florida.

This submittal does not alter the significant hazards consideration or environmental assessment previously submitted by FPL letter L-2010-113 [Reference 1].

This submittal contains no new commitments and no revisions to existing commitments.

Should you have any questions regarding this submittal, please contact Mr. Robert J. Tomonto, Licensing Manager, at (305) 246-7327.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on July __,

2011.

Very truly yours, Michael Kiley Site Vice President Turkey Point Nuclear Plant Attachment cc:

USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Resident Inspector, Turkey Point Nuclear Plant Mr. W. A. Passetti, Florida Department of Health

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 1 of 26 Turkey Point Units 3 and 4 RESPONSE TO NRC RAI REGARDING EPU LAR NO. 205 AND EEEB ELECTRICAL ENGINEERING BRANCH ISSUES ATTACHMENT

Turkey Point Units 3 and 4 L-2011-223 Docket Nos. 50-250 and 50-251 Attachment Page 2 of 26 Response to Request for Additional Information The following information is provided by Florida Power & Light Company (FPL) in response to the U. S. Nuclear Regulatory Commission's (NRC) Request for Additional Information (RAI). This information was requested to support the review of License Amendment Request (LAR) No. 205, Extended Power Uprate (EPU), for Turkey Point Nuclear Plant (PTN) Units 3 and 4 that was submitted to the NRC by FPL letter L-2010-113 on October 21, 2010 [Reference 1].

On March 2, 2011, FPL received an RAI via email from the NRC Project Manager (PM) regarding electrical engineering issues associated with FPL's request to implement the EPU [Reference 2].

FPL provided responses to the RAI questions via FPL letter L-2011-081, dated March 31, 2011

[Reference 3].

In an email dated June 9, 2011 [Reference 4], the NRC staff requested additional information regarding FPL's request to implement the EPU. The RAI consisted of two questions from the NRC Electrical Engineering Branch (EEEB). These RAI questions and the applicable FPL responses are documented below.

EEEB-2.1 Provide the normal and accident radiation dose levels for all areas in which environmentally qualified equipment is installed in tabular form showing the Pre-EPU, EPU conditions, and qualified doses. In the table(s), identify any equipment qualified based on replacement or further evaluation (such as cables discussed in the licensee's response letter dated March 11, 2011).

Table 2.1-1 below provides the pre-EPU and EPU radiation values for the EQ Documentation Packages (EQ Doc Pacs) that comprise the EQ Program at Turkey Point Units 3 & 4 Nuclear Power plant.

The following doses are identified in the table:

1. Normal operating plant dose (NOP) - 60 year normal operating dose
2. Gamma accident dose - LOCA (unless indicated)
3. Total integrated dose (TID) - NOP plus accident dose
4. Equipment Qualification dose - from the EQ Doc Pacs Note: A beta dose of 1.36E7 Rads (adjusted for cable insulation thickness) are included for cables inside containment.

The equipment that required further evaluation is listed on Table 2.1-2. These equipment outliers outside containment were evaluated as discussed in EEEB branch RAI response 1.3 b as contained in letter L-2011-081 dated March 31, 2011 [Reference 3]. The outliers inside containment were evaluated based on location specific evaluations as further described in EEEB branch RAI response 1.3 b as contained in Reference 3.

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 3 of 26 Table 2.1 EPU and Pre-EPU EQ Dose Comparison PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CABLE CODE LT1 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE LP1 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE LP4 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE LP7 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C22 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C32 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C52 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C72 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C92 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B75 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E--07 LT-3-6308A (2 THRU 5) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-3-6308A-1 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-3-6308B (2 THRU 5) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-3-6308B-1 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-3-6309A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.16E+08 LT-3-6309B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.16E+08 LT-4-6308A (2 THRU 5) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-4-6308A-1 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-4;6308B (2 THRU 5) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-4-6308B-1 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 1.57E+06 3.85E+07 1.16E+08 LT-4-6309A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.16E+08 LT-4-6309B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.16E+08 RAD-3-6311 A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 RAD-4-631 1A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 RAD-4-631 IB 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 RAD-3-6311 B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE N6 1.3 1E+03 2.46E+06 2.46E+06 1.3 1E+03 2.93E+06 2.93E+06 3.OOE+06 Location Specific Dose CABLE CODE 60 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE 61 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 JPR WIRE - GE 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 4 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments I

Normal Accident Integrated Normal Accident Integrated Qualification SDose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

TB-EB-25 5.26E+04 7.45E+06 7.50E+06 1.31E+03 1.1OE+07 1.1OE+07 2.04E+08 TB-EB-5 5.26E+04 7.45E+06 7.50E+06 1.31E+03 1.1OE+07 1.1OE+07 2.04E+08 3N1403-B MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 1.00E+06 3N1405-A MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 1.00E+06 4N1403-B MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 1.00E+06 4N 1405-A MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 1.00E+06 CABLE CODE MA6R 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE MB6R/M]B7R 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 MAIR 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 3V30A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 3.OOE+08 3V30B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 3.OOE+08 3V30C 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 3.OOE+08 4V30A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 3.OOE+08 4V30B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1E+07 3.OOE+08 4V30C 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 3.OOE+08 MOV-3-535 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-536 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-750 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-751 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-866A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-866B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-3-6386 5.25E+05 2.63E+06 3.15E+06 3.69E+07 4.39E+06 4.13E+07 2.04E+08 MOV-4-535 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-536 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-750 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-751 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-866A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-866B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 MOV-4-6386 5.25E+05 2.63E+06 3.15E+06 3.69E+07 4.39E+06 4.13E+07 2.04E+08 MOV-3-744A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.15E+07 4.22E+07 2.OOE+08 MOV-3-744B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.15E+07 4.22E+07 2.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 5 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

MOV-4-744A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.15E+07 4.22E+07 2.OOE+08 MOV-4-744B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.15E+07 4.22E+07 2.OOE+08

'MOV-3-350 5.26E+04 5.47E+05 6.OOE+05 5.26E+04 7.64E+04 1.29E+05 2.OOE+07 MOV-3-843A 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.1OE+06 3.1OE+06 2.OOE+07 MOV-3-843B 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.1OE+06 3.1OE+06 2.OOE+07 MOV-3-860A 1.3 1E+03 6.1OE+05 6.1OE+05 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+07 MOV-3-860B 1.IE+03 6.1OE+05 6.1OE+05 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+07 MOV-3-863A 1.)IE+03 2.OOE+06 2.OOE+06 1.31E+03 1.1OE+07 1.l10OE+07 2.OOE+07 MOV-3-863B 1.31E+03 2.OOE+06 2.OOE+06 1.31E+03 1.1OE+07 1.10OE+07 2.OOE+07 MOV-3-869 5.26E+04 7.45E+06 7.50E+05 5.26E+04 4.80E+06 4.85E+06 2.00E+07

!MOV-3-872 5.26E+04 7.45E+06 7.50E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+07 MOV-3-880A 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.1OE+06 3.1OE+06 2.OOE+07 MOV-3-880B 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.1OE+06 3.1OE+06 2.OOE+07 MOV-3-1404 MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 2.OOE+07 MOV-4-350 5.26E+04 7.50E+04 1.28E+05 5.26E+04 1.07E+05 1.60E+05 2.OOE+07 MOV-4-843A 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.60E+06 3.60E+06 2.OOE+07 MOV-4-843B 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.60E+06 3.60E+06 2.OOE+07 MOV-4-860A 1.31E+03 6.1OE+05 6.1OE+05 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+07 MOV-4-860B 1.31E+03 6.1OE+05 6.1OE+05 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+07 MOV-4-863A 1.31E+03 2.00E+06 2.OOE+06 1.31E+03 1.1OE+07 I. 1OE+07 2.OOE+07 MOV-4-863B 1.31E+03 2.OOE+06 2.OOE+06 1.31E+03

1. 1 OE+07 1.1OE+07 2.OOE+07 MOV-4-869 5.26E+04 7.45E+06 7.50E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+07 MOV-4-872 5.26E+04 7.45E+06 7.50E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+07 MOV-4-880A 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.60E+06 3.60E+06 2.OOE+07 MOV-4-880B 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.60E+06 3.60E+06 2.OOE+07 MOV-4-1404 MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 2.OOE+07 MOV-878A 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.90E+06 3.90E+06 2.OOE+07 MOV-878B 1.31E+03 7.49E+05 7.50E+05 1.31E+03 3.50E+06 3.50E+06 2.OOE+07 MOV-3-1403 MILD MILD MILD 1.31E+/-03
3. 1 OE+04 3.24E+04 1.OOE+07 MOV-3-1405 MILD MILD MILD 1.31E+03
3. 1 OE+04 3.24E+04 L.OOE+07 MOV-4-1403 MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 L.OOE+07

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 6 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

MOV-4-1405 MILD MILD MILD 1.31E+03 3.1OE+04 3.24E+04 1.OOE+07 PCV-3-455C*LS 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 PCV-3-456*LS 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 PCV-4-455C*LS 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 PCV-4-456*LS 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.04E+08 CV-3-310A*LS 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.04E+08 CV-3-310B*LS 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.04E+08 CV-4-310A*LS 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.04E+08 CV-4-310B*LS 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.04E+08 C;V-3-200A*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-3-200B*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-3-200C*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-4-200A*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-4-200B*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-4-200C*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 POV-3-2601*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 POV-3-2603*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 POV-4-2601 *LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-4-2819*LS 5.25E+05 3.95E+07 4.00E+07 6.92E+05 5.64E+07 5.71E+07 2.04E+08 POV-4-2603*LS 5.25E+05 8.05E+05 1.33E+06 6.92E+05 1.57E+06 2.27E+06 2.04E+08 CV-3-2819*LS 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.04E+08 CV-3-4658A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-4658B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-4659A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-4659B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-4668A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-4668B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-4658A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-4658B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV 4659A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-4659B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08

, I

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 7 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CV-4-4668A*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-4668B*LS 5.26E+04 3.82E+05 4.35E+05 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2810*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2812*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2814*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2810*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2812*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2814*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2903*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2904*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2905*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2906*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2907*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-3-2908*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2903*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2904*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2905*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2906*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2907*LS 5.26E+04 7.51E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 CV-4-2908*LS 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 4.80E+06 4.85E+06 2.04E+08 POV-3-2604*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 POV-3-2605*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 POV-3-2606*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 POV-4-2604*LS MILD MILD MILD MILD

<l.OOE+05 MILD 2.04E+08 POV-4-2605*LS MILD MILD MILD MILD

<l.OOE+05 MILD 2.04E+08 POV-4-2606*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 CV-3-6275A*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 CV-3-6275B*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 CV-3-6275C*LS MILD MILD MILD MILD

<l.OOE+05 MILD 2.04E+08 CV-4 6275A*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08 CV-4-6275B*LS MILD MILD MILD MILD

<1.OOE+05 MILD 2.04E+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 8 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CV-4-6275C*LS MILD MILD MILD MILD

<1.00E+05 MILD 2.04E+08 CABLE CODE N47 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE N50 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE N52 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE 53 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE 54 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE 55 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE 56 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.00E+08 CABLE CODE N7 5.26E+04 4.1OE+05 4.70E+05 1.3 1E+03 3.60E+06 3.60E+06 5.OOE+06 Location Specific Dose CABLE CODE 63 6.OOE+04 7.54E+06 7.60E+06 1.3 1E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE N20 6.OOE+04 2.16E+06 2.22E+06 5.26E+04 4.80E+06 4.85E+06 5.OOE+06 Location Specific Dose CABLE CODE 21 6.OOE+04 7.54E+06 7.60E+06 1.31E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE 22 6.OOE+04 7.54E+06 7.60E+06 1.31E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE 23 6.OOE+04 7.54E+06 7.60E+06 1.31E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE 24 6.OOE+04 7.54E+06 7.60E+06 1.31 E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE 25 6.OOE+04 7.54E+06 7.60E+06 1.31 E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE N 13 6.00E+04 6.90E+05 7.50E+05 5.26E+04 7.17E+05 7.70E+05 5.OOE+06 Location Specific Dose CABLE CODE 064 6.OOE+04 6.90E+05 7.50E+05 1.31 E+03 7.OOE+06 7.OOE+06 1.00E+07 Location Specific Dose CABLE CODE 063 6.OOE+04 7.50E+06 7.56E+06 1.3 1E+03 1.1OE+07 I.IOE+07 7.50E+07 SPL SLEEVE - WN BUTT 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 SPL SLEEVE - WN BOLT 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.15E+08 SPL SLEEVE - WN SHIM 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.15E+08 SPL SLEEVE - RNF 100 6.OOE+04 7.54E+06 7.55E+06 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+08 SPL SLEEVE-NHIVT 6.OOE+04 7.54E+06 7.55E+06 1.31E+03 1.09E+07 1.1OE+07 2.OOE+08 SPL SLEEVE-NMCK-8(L) 6.OOE+04 7.54E+06 7.55E+06 1.3 1E+03 1.09E+07 1.1OE+07 5.OOE+07 NEW RAYCHEM 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.15E+08 SPL SLEEVE NMCK 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.90E+08 SPL SLEEVE NESK 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 SPL SLEEVE NCBK 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 SPL SLEEVE NPK 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 SPL SLEEVE NPKV 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.15E+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 9 of 26 I

PRE EPU POST-EPU Component I 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification I

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

NEW'RAYCHlEM 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.15E+08 3N214A 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.09E+06 3.1OE+06 1.00E+07 3N214B 1.31E+03 7.50E+05 7.51E+05 1.31E E+03 3.09E+06 3.1OE+06 1.00E+07 4N214A 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.60E+06 3.60E+06 1.00E+07 4N214B 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.60E+06 3.60E+06 1.OOE+07 3N215A 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.90E+06 3.90E+06 1.00E+07 3N215B 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.90E+06 3.90E+06 1.00E+07 4N215A 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.50E+06 3.50E+06 1.00E+07 4N215B 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.50E+06 3.50E+06 1.00E+07 3N210A 5.26E+04 6.98E+05 7.51E+05 5.26E+04 4.80E+06 4.85E+06 1.00E+07 4N210A 1.31E+03 7.50E+05 7.51E+05 1.31E+03 3.35E+04 3.48E+04 1.00E+07 CABLE CODE LTI 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 JPR WIRE ROCK-RD 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 JPR WIRE ROCK-CH 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B04A/B14 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B05A 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B06A/B 15 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B023 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B063 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B077 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B083 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B13 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B 17 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B 18 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B28 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B38 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B45 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B57 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE C25 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE C30 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE C50 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07

Turl.;ey Point Units 3 and 4 Docket.Nos. 50-250 and 50-251

.I L-2011-223 Attachment Page 10 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification I

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CABLE CODE C70 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE C120 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE C162 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE LP3 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE LP5 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE LP6 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE LP8 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE B42A 5.25E+05 4.94E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 JPR WIRE SIS 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.84E+08 FT-3-122 1.31E+03 2.79E+05 2.80E+05 5.26E+04 4.80E+06 4.85E+06 2.62E+07 I FT-4-122 1.31E+03 1.99E+05 2.OOE+05 5.26E+04 4.80E+06 4.85E+06 2.62E+07 FT-3-940 1.31E+03 1.49E+05 1.50E+05 1.31E+03 3.90E+06 3.90E+06 2.62E+07 FT-3-943 1.31E+03 1.49E+05 1.50E+05 1.31E+03 3.90E+06 3.90E+06 2.62E+07 FT-4-940 1.31E+03 2.47E+04 2.60E+04 1.31E+03 3.50E+06 3.50E+06 2.62E+07 FT-4-943 1.31E+03 2.47E+04 2.60E+04 1.31E+03 3.50E+06 3.50E+06 2.62E+07 PT-3-464 MILD MILD MILD 1.31 E+03 MILD MILD 2.62E+07 PT-3-466 MILD MILD MILD 1.31 E+03 MILD MILD 2.62E+07 PT-3-468 MILD MILD MILD 1.31E+03 MILD MILD 2.62E+07 PT-4-464 MILD MILD MILD 1.31E+03 MILD MILD 2.62E+07 PT-4-466 MILD MILD MILD 1.31E+03 MILD MILD 2.62E+07 PT-4-468 MILD MILD MILD 1.3 1E+03 MILD MILD 2.62E+07 PT-3-474 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-475 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-476 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-484 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-485 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-486 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-494 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-495 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-496 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-474 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 11 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

PT-4-475 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-476 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-484 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-485 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-486 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-494 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-495 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-4-496 MILD MILD MILD 1.31E+03 3.16E+05 3.17E+05 2.62E+07 PT-3-940 1.31E+03 2.29E+05 2.30E+05 1.31E+03 3.9E+06 3.90E+06 2.62E+07 PT-3-943 1.31E+03 2.29E+05 2.30E+05 1.31E+03 3.9E+06 3.90E+06 2.62E+07 PT-4-940 1.31E+03 2.29E+05 2.30E+05 1.31E+03 3.5E+06 3.50E+06 2.62E+07 PT-4-943 1.31E+03 2.29E+05 2.30E+05 1.31E+03 3.5E+06 3.50E+06 2.62E+07 FT-3-150 5.26E+04 7.50E+05 8.03E+05 5.26E+04 7.64E+04 1.29E+05 2.62E+07 FT-4-150 5.26E+04 7.50E+05 8.03E+05 5.26E+04 1.08E+05 1.61E+05 2.62E+07 FT-3-474 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.00E+06 5.19E+07 FT-3-475 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-3-484 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-3-485 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-3-494 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-3-495 5.25E+05 2.O1E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-474 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-475 5.25E+05 2.01E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-484 5.25E+05 2.O0E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-485 5.25E+05 2.O0E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-494 5.25E+05 2.O0E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-4-495 5.25E+05 2.O0E+05 7.26E+05 6.92E+05 3.12E+05 1.OOE+06 5.19E+07 FT-3-605 1.31E+03 7.25E+05 7.26E+05 1.31E+03

. 10OE+07 1.1OE+07 5.19E+07 FT-4-605 1.31E+03 7.25E+05 7.26E+05 1.31E+03 1.1OE+07 1.1OE+07 5.19E+07 FT-3-932 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose FT-3-933 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose FT-4-932 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 12 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

FT-4-933 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-3-459 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-3-460 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-3-461 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-4-459 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-4-460 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-4-461 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose LT-3-474 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-475 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-476 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-484 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-485 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-486 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-494 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-495 5.25E+05 1.14E+07

1. 19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-3-496 5.25E+05
1. 14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-474 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-475 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-476 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-484 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-485 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-486 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-494 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-495 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 LT-4-496 5.25E+05 1.14E+07 1.19E+07 6.92E+05 1.78E+07 1.84E+07 5.19E+07 PT-3-403 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-3-404 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-3-405 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-3-406 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E1+07 5.19E+07 Location Specific Dose PT-4-403 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-4-404 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose

Turkey Point Units 3 and 4 Docket Nos. 5 0-250 and 50-251 L-2011-223 Attachment Page 13 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

PT-4-405 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-4-406 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 3.06E+07 3.13E+07 5.19E+07 Location Specific Dose PT-3-455 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 PT-3-456 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 PT-3-457 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 PT-4-455 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 PT-4-456 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 PT-4-457 5.25E+05 8.05E+05 1.33E+06 3.69E+07 1.57E+06 3.85E+07 5.24E+07 CABLE CODE LIP 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 SV-3-6318A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-3-6318B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-3-6319A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-3-6319B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-3-6611 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-3-6612 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6318A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6318B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6319A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6319B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6611 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 SV-4-6612 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 1.35E+08 ZS-3-6303A 5.25E+05

1. 15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZS-3-6303B 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZS-3-6303C 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZS-4-6303A 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZS-4-6303B 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZS-4-6303C 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZT-4-6303 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 ZT-3-6303 5.25E+05 1.15E+07 1.20E+07 3.69E+07 1.84E+07 5.53E+07 2.22E+08 SPL TAPE (23) 5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 12.2E+08 SPL TAPE (130 C) 5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 1.00E+08

Turkey. Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 14 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

SPL TAPE (70) 5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 1.OOE+08 SPL TAPE (33+)

5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 5.OOE+07 SPL TAPE (SCOTCHFIL) 5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 6.02E+06 Not integral to splice insulation SPL (130C/33+)

5.26E+04 2.40E+06 2.45E+06 5.26E+04 6.95E+06 7.OOE+06 2.OOE+08 SV-3-310A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.OOE+08 SV-3-310B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.OOE+08 SV-4-310A 5.25E+05 3.95E+07 4.OOE+07 6.92E +05 4.19E+07 4.26E+07 2.OOE+08 SV-4-30 OB 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 4.19E+07 4.26E+07 2.OOE+08 SV-3-200A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-200B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-200C 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-200A 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-200B 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-200C 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-2601 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-2804 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-2603 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-2806 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-2601 5.25E+05 3.95E+07 4.00E+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-2804 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-2603 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-4-2806 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 1.57E+06 2.26E+06 2.OOE+08 SV-3-2819 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 SV-4-2819 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+/-07 2.OOE+08 SV-3-2920 5.26E+04 1.77E+05 2.30E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-2921 5.26E+04 1.77E+05 2.30E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-2922 5.26E+04 1.77E+05 2.30E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2920 5.26E+04 2.67E+05 3.20E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2921 5.26E+04 2.67E+05 3.20E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2922 5.26E+04 2.67E+05 3.20E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-2923 5.26E+04 3.27E+05 3.80E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 15 of 26 PRE EPU POST-EPU Component I 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

SV-3-2924 5.26E+04 3.27E+05 3.80E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-2925 5.26E+04 3.07E+05 3.60E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2923 5.26E+04 4.07E+05 4.60E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2925 5.26E+04 4.57E+05 5.10E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-2924 5.26E+04 3.67E+05 4.20E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-2914 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-2915 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-2916 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-2917 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-2918 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-2919 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2914 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2915 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2916 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2917 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2918 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-4-2919 MILD MILD MILD 2.63E+02 3.16E+05 3.16E+05 2.OOE+08 SV-3-121-2 5.26E+04 1.47E+05 2.90E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-4-121-2 5.26E+04 1.47E+05 2.90E+05 5.26E+04 4.80E+06 4.85E+06 2.OOE+08 SV-3-6275A MILD MILD MILD MILD MILD MILD 2.00E+08 SV-3-6275B MILD MILD MILD MILD MILD MILD 2.OOE+08 SV-3-6275C MILD MILD MILD MILD MILD MILD 2.OOE+08 SV-4-6275A MILD MILD MILD MILD MILD MILD 2.OOE+08 SV-4-6275B MILD MILD MILD MILD MILD MILD 2.OOE+08 SV-4-6275C MILD MILD MILD MILD MILD MILD 2.OOE+08 SV-3-2604A MILD MILD MILD 1.3 1E+03 3.11 E+04 3.24E+04 2.OOE+08 SV-3-2604B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2605A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2605B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2606A MILD MILD MILD 1.3 1E+03 3.11 E+04 3.24E+04 2.OOE+08 SV-3-2606B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 16 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

SV-3-2607A MILD MILD MILD 1.3]E+03 3.1 IE+04 3.24E+04 2.OOE+08 SV-3-2607B MILD MILD MILD 1.31E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2609A MILD MILD MILD 1.31E+03 3.11 E+04 3.24E+04 2.OOE+08 SV-3-2609B MILD MILD MILD 1.3 1E+03 3.1 1E+04 3.24E+04 2.OOE+08 SV-3-2610A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2610B MILD MILD MILD 1.31E+03 3.11E+04 3.24E+04 2.00E-E+08 SV-3-2611A MILD MILD MILD 1.31E+03 3.11E+04 3.24E+04 2.00E+08 SV-3-2611B MILD MILD MILD 1.31E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2612A MILD MILD MILD 1.311E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2612B MILD MILD MILD 1.3 1E+03 3.11 E+04 3.24E+04 2.OOE+08 SV-3-2614A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2614B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2615A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2615B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2616A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2616B MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2617A MILD MILD MILD 1.3 1E+03 3.11E+04 3.24E+04 2.OOE+08 SV-3-2617B MILD MILD MILD 1.31E+03 3.11 E+04 3.24E+04 2.OOE+08 SV-4-2604A MILD MILD MILD 1.31 E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2604B MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2606A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2606B MILD MILD MILD 1.3 IE+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2607A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2607B MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2609A MILD MILD MILD 1.31 E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2609B MILD MILD MILD 1.31 E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-261 1A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-26 11 B MILD MILD MILD 1.31 E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2612A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2612B MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2614A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08

Turkey Point Units 3 and 4 DocketNos. 50-250 and 50-251 L-2011-223 Attachment Page 17 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

SV-4-2614B MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2616A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2616B MILD MILD MILD 1.3 1E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2617A MILD MILD MILD 1.31E+03 8.06E+03 9.37E+03 2.OOE+08 SV-4-2617B MILD MILD MILD 1.3 1E+03 8.06E+03 9.37E+03 2.OOE+08 3P210A 1.31E+03 2.19E+05 2.20E+05 1.31E+03 6.99E+06 7.OOE+06 5.OOE+07 3P210B 1.3 1E+03 2.19E+05 2.20E+05 1.3 1E+03 6.99E+06 7.OOE+06 5.OOE+07 4P210A 1.31E+03 2.19E+05 2.20E+05 1.31E+03 6.80E+06 6.80E+06 8.OOE+06 4P210B 1.31E+03 2.19E+05 2.20E+05 1.31E+03 6.99E+06 7.OOE+06 8.OOE+06 3P214A 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.1OE+06 3.1OE+06 5.OOE+07 3P214B 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.1OE+06 3.1OE+06 5.OOE+07 4P214A 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.60E+06 3.60E+06 5.OOE+07 4P214B 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.60E+06 3.60E+06 5.OOE+07 3P215A 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.89E+06 3.90E+06 5.OOE+07 3P215B 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.89E+06 3.90E+06 5.OOE+07 4P215A 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.50E+06 3.50E+06 5.OOE+07 4P215B 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.50E+06 3.50E+06 5.OOE+07 Spare SI PP Motor 1.31E+03 8.09E+05 8.1OE+05 1.31E+03 3.89E+06 3.90E+06 5.OOE+07 ICC-ERD 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 ICC-LITTON-A 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 ICC-G&H 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 ICC-LITTON-B 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.1OE+08 ICC-LITTON-EGS 8/10 5.25E+05 4.37E+07 4.42E+07 3.69E+07 3.86E+07 7.55E+07 2.25E+08 ICC-G&H-EGS 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 ICC-R-SCC 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 ICC-EGS-CLAMP 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 2.20E+08 ICC-LIT-EGS-MSSI 5.25E+05 4.37E+07 4.42E+07 3.69E+07 5.64E+07 9.33E+07 1.90E+08 ND-3-6649A 1.70E+10 8.50E+09 2.55E+10 3.69E+07 2.72E+10 2.72E+10 7.OOE+1I Plus Neutron.

3C290A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 3NFMSAB 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 3.20E+09 ND-3-6649B 1.70E+10 8.50E+09 2.55E+10 3.69E+07 2.72E+10 2.72E+10 7.OOE+l1 Plus Neutron.

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 18 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads) 3C290B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 3NFMSBB 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.00E+08 ND-4-6649A 1.70E+10 8.50E+09 2.55E+10 3.69E+07 2.72E+10 2.72E+10 7.OOE+1I Plus Neutron 4C290A 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 4NFMSAB 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 3.20E+09 ND-4-6649B 1.70E+10 8.50E+09 2.55E+10 3.69E+07 2.72E+10 2.72E+10 7.OOE+1 1 Plus Neutron.

4C290B 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 4NFMSBB 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 3.20E+09 CABLE CODE B21 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B31 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B06 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B04 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B02 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B 10 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B20 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B40 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B35 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE B08 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C24 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C34 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C54 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C74 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C94 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C21 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C31 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C51 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C71 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C91 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE C20 5.25E+05 4.95E+07 5.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE A04 5.26E+04 2.37E+05 2.90E+05 1.31E+03 1.1OE+07

1. I OE+07 2.OOE+08 CABLE CODE A05 5.26E+04 2.37E+05 2.90E+05 1.31E+03 1.1OE+07 1.1OE+07 2.OOE+08

Turkey Point Units 3 and 4 DocketNos. 50-250 and 50-251 1

L-2011-223 Attachment Page 19 of 26 PRE EPU POST-EPU Component I 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification I

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CABLE CODE A07 5.26E+04 2.37E+05 2.90E+05 1.31E+03 1.1OE+07

.10OE+07 2.OOE+08 CABLE CODE A 12 5.26E+04 2.37E+05 2.90E+05 1.31E+03

1. 1 0E+07 1.1OE+07 2.00E+08 FY-3-1401A-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 FY-3-1401B-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 FY-3-1457A-6 MILD MILD MILD 2.63E+02 3.11 E+04 3.14E+04 9.23E+06 FY-3-1457B-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 FY-3-1458A-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 FY-3-145'8B-6 MILD MILD MILD 2.63E+02 3.II E+04 3.14E+04 9.23E+06 FY-4-1401A-6 MILD MILD MILD 2.63E+02 3.11 E+04 3.14E+04 9.23E+06 FY-4-1401B-6 MILD MILD MILD 2.63E+02 3.11 E+04 3.14E+04 9.23E+06 FY-4-1457A-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 EY-4-1457B-6 MILD MILD MILD 2.63E+02 3.11 E+04 3.14E+04 9.23E+06 FY-4-1458A-6 MILD MILD MILD 2.63E+02 3.11 E+04 3.14E+04 9.23E+06 FY-4-1458B-6 MILD MILD MILD 2.63E+02 3.11E+04 3.14E+04 9.23E+06 JPR WIRE-TELEDYNE 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.OOE+08 TE-3-411D 1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-411 D2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-411 D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-412B1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-412B2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-412B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-412C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-412D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-421D1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-421D2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-4211D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-422B1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-422B2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-422B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-422C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-422D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 20 of 26 PRE EPU POST-EPU Component fD 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

TE-3-431D1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-431 D2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-431 D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-432B31 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-432B2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-432B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-432C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-432D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-411D I 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-41 ID2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.00E+08 TE-4-41 1D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.00E+08 TE-4-412B31 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-41232 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-412B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-412C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.00E+08 TE-4-412D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-421D 1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-421 D2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-421 D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-422B 1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-42212 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-422B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-422C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-422D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-431D 1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-431 D2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-431 D3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-432B 1 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-432B2 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-432B3 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-4-432C 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 21 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

TE-4-432D 1.05E+08 1.47E+06 1.06E+08 1.56E+08 6.22E+07 2.18E+08 3.OOE+08 TE-3-604A 1.3 1E+03 7.55E+06 7.55E+06 1.31E+03 6.99E+06 7.OOE+06 3.00E+08 TE-3-604B 1.31E+03 7.55E+06 7.55E+06 1.31E+03 6.99E+06 7.00E+06 3.OOE+08 TE-3-606 5.26E+04 7.50E+06 7.55E+06 5.26E+04 4.80E+06 4.85E+06 3.OOE+08 TE-4-604A 1.31E+03 7.55E+06 7.55E+06 1.31E+03 6.79E+06 6.80E+06 3.OOE+08 TE-4-604B 1.31E+03 7.55E+06 7.55E+06 1.31E+03 6.99E+06 7.OOE+06 3.OOE+08 TE-4-606 5.26E+04 7.50E+06 7.55E+06 5.26E+04 4.80E+04 4.85E+06 3.OOE+08 TB-NQB 1.31E+03 7.56E+06 7.56E+06 1.31E+03 1.1OE+07 1.IOE+07 2.OOE+08 CONFORMAL COATING 5.26E+04 7.49E+06 7.54E+06 1.31E+03 1.1OE+07 1.10E+07 2.00E+07 GB-i Instrument 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-I (12-14) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-i (12-14/16-18) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (8-10) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (12-14) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (16-18) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (8-10/12-14) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (8-10/12-18) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-2 (12-14/16-18) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-3 (4-6) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-3 (8-10) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-3 (4-6/8-10) 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-S 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-S-2 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 GB-S-3 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.08E+08 QDC-1.5" COND SEAL 5.25E+07 3.95E+07 9.20E+07 3.69E+07 4.32E+07 8.01E+07 2.00E+08 QDC-0.75" COND SEAL 5.25E+07 3.95E+07 9.20E+07 3.69E+07 4.32E+07 8.0 1E+07 2.OOE+08 QDC-0.5" COND SEAL 5.25E+07 3.95E+07 9.20E+07 3.69E+07 4.32E+07 8.0 1E+07 2.OOE+08 ICC-QDC 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.00E+08 ICC-VEAM 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.00E+08 ICC-ROCK 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 4.32E+07 8.01E+07 2.OOE+08 CABLE CODE L59 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 22 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

CABLE CODE L58 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.00E+08 Beta 1.36E+07 CABLE CODE L59 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE L 15 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.OOE+08 Beta 1.36E+07 CABLE CODE LIP 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE L2P 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE LIT 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 CABLE CODE L40 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 1.84E+08 Beta 1.36E+07 COND SEAL ASSY 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 1.07E+08 2.25E+08 Beta 1.36E+07 T3101 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T3102 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T4101 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T4102 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T3131 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T3142 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 2.OOE+08 T3P62 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.28E+08 T3P63 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.28E+08 T4C 1I 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.28E+08 T4P62 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.28E+08 TE-4-410 A&B 1.06E+08 5.40E+07 1.60E+08 1.42E+08 5.65E+07 1.99E+08 2.27E+08 TE-4-420 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-4-430 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-4-413 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-4-423 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-4-433 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-4-6700 5.25E+05 3.95E+07 4.00E+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 TE-4-6701 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 TE-4-6702 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 TE-3-410 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-3-420 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-3-430 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-3-413 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 23 of 26 PRE EPU POST-EPU Component ID 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

TE-3-423 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 tE-3-433 A&B 1.06E+08 5.40E+07 1.60E+08 1.56E+08 6.22E+07 2.18E+08 2.27E+08 TE-3-6700 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 TE-3-6701 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 TE-3-6702 5.25E+05 3.95E+07 4.OOE+07 3.69E+07 5.64E+07 9.33E+07 2.32E+09 JPR WIRE 5.26E+04 7.5 1E+06 7.56E+06 5.26E+04 1.09E+07 1.1OE+07 2.OOE+08 T3P41 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P42 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P43 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P51 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1 E+07 1.OOE+08 T3P53 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P41 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P42 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P43 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P51 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P52 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P1 1 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P12 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P22 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P12 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P21 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P22 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3C11 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1 E+07 1.OOE+08 T3C12 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1E+07 1.OOE+08 T3C13 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3C21 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3C22 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3C23 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3P52 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1E+07 1.OOE+08 T4C12 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4C13 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08

Turkey' Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 24 of 26 PRE EPU POST-EPU Component ED 60 yr Post Total 60 yr Post Total Component Comments Normal Accident Integrated Normal Accident Integrated Qualification Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

Dose (Rads)

(Rads)

T4C21 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4C23 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3111 5.25E+05 3.95E+07 4.00E+07 6.92E+05 5.64E+07 5.7 1E+07 L.OOE+08 T4C22 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 L.OOE+08 T3114 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1E+07 1.OOE+08 T3115 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3121 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1E+07 1.OOE+08 T3122 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3123 5.25E+/-05 3.95E07 4.OOE+/-07 6.9')E+05 5.64E+07 5.71 E+/-07 1OOE+08 T3124 5.25E+05 3.95E+/-07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4112 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3112 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4114 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 L.OOE+08 T4115 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4121 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4122 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 L.OOE+08 T4123 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4124 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T3113 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.7 1 E+07 OOE+08 T4C41 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4141 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4142 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08 T4P53 5.25E+05 3.95E+07 4.OOE+07 6.92E+05 5.64E+07 5.71E+07 1.OOE+08

Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 L-2011-223 Attachment Page 25 of 26 Table 2.1 EQ Components Requiring Further Evaluation Item Document Description Item Identification No.

I EQ Doc General Cable: 1/C - 4/0 Power Cable/Butyl Insul/PVC JCKT Cable Code N6 Package 1001-12.0 2

EQ Doc Okonite Cable:

Package NIO: I/C - 4/0 Cable W/Butyl Insul & PVC JCKT Cable Codes: N1O*

1001-19.0 N13: I/C - #6 Cable W/Butyl Insul & PVC JCKT N13 N20: 3/C - #12 Power Cable W/Butyl Rubber Insul N20 21: 2/C - #12 Cable W/PE Insul & PVC JACK 21 22: 3/C - #12 Cable W/PE Insul & PVC JACK 22 23: 5/C - #12 Cable WIPE Insul & PVC JACK 23 24: 7/C - #12 Cable W/PE Insul & PVC JACK 24 25: 9/C - #12 Cable W/PE Insul & PVC JACK 25 64: 4/C - #16 Cable W/PE Insul & PVC JACK 64 3

EQ Doc Rosemount, Inc (In Containment)

LT-3-459, 460, 461 Package PT-3-403, 404, 405 and 406 1001-24.1 LT-4-459, 460, 461 PT-4-403, 404. 405 and 406 FT-3-932, 933 FT-4-932, 933 4

EQ Doc Valcor Solenoids SV-3-6427A&B* and Package SV-4-6427A&B*

1001-30.0 5

EQ Doc Kerite Cable Cable Codes for Units 3 and 4:

Package Control Cable w/FR Insul & Jacket 7/C#12 C71 1001-34.2 Control Cable w/FR Insul & Jacket 9/C#12 C91 Control Cable w/FR Insul & Jacket 2/C#10 C20 Control Cable w/FR Insul & Jacket 2/C#12 C21 Control Cable w/FR Insul & Jacket 3/C# 12 C31 Control Cable w/FR Insul & Jacket 5/C#12 C51 6

EQ Doc Masoneilan/Dresser Ind.

I/P-3-121* & IIP-4-121*

Package 1001-35.0

  • Removed from EQ List

Turkey Point Units 3 and 4 L-2011-223 Docket Nos. 50-250 and 50-251 Attachment Page 26 of 26 EEEB-2.2 Provide the actual design ampere rating of modified Isolated Phase Bus Duct to show that it bounds the required 28,508 A rating, as stated in the license amendment request.

The modified isolated phase bus duct (IPBD) is rated for 28,508 A for EPU. This value bounds the EPU nominal generator operating current of 27,083 A.

28,508 A corresponds to full power operation with a 5% reduction in generator output voltage.

References

1.

M. Kiley (FPL) to U.S. Nuclear Regulatory Conunission (L-2010-113), "License Amendment Request for Extended Power Uprate (LAR 205)," (TAC Nos. ME4907 and ME4908), Accession No. ML103560169, October 21, 2010.

2.

Email from J. Paige (NRC) to T. Abbatiello (FPL), "Turkey Point EPU - Electrical Engineering (EEEB) Request for Additional Information - Round 1," Accession No. ML110610719, March 2, 2011.

3.

M. Kiley (FPL) to U.S. Nuclear Regulatory Commission (L-2011-081), "Response to NRC Request for Additional Information (RAI) Regarding Extended Power Uprate (EPU)

License Amendment Request (LAR) No. 205 and Electrical Engineering Branch Issues,"

Accession No. ML110940179, March 31, 2011.

4.

Email from J. Paige (NRC) to S. Hale (FPL) "Turkey Point EPU - Electrical Engineering (EEEB) Request for Additional Information - Round 2," Accession No. ML11160A156, June 9, 2011.