MONTHYEARNL-05-0706, March 2005 Monthly Operating Report for Joseph M. Farley Nuclear Plant2005-04-13013 April 2005 March 2005 Monthly Operating Report for Joseph M. Farley Nuclear Plant NL-05-0455, February 2005 Monthly Operating Report for Joseph M. Farley Nuclear Plant2005-03-14014 March 2005 February 2005 Monthly Operating Report for Joseph M. Farley Nuclear Plant NL-05-0253, January 2005 Monthly Operating Reports for Joseph M Farley Nuclear Plant Units 1 and 22005-02-14014 February 2005 January 2005 Monthly Operating Reports for Joseph M Farley Nuclear Plant Units 1 and 2 NL-05-0039, December 2004 Monthly Operating Report Joseph M Farley Nuclear Plant2005-01-12012 January 2005 December 2004 Monthly Operating Report Joseph M Farley Nuclear Plant NL-04-2436, November 2004 Monthly Operating Reports for Joseph M. Farley Nuclear Plant2004-12-13013 December 2004 November 2004 Monthly Operating Reports for Joseph M. Farley Nuclear Plant NL-04-2198, October 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant2004-11-11011 November 2004 October 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant NL-04-1971, September 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant2004-10-11011 October 2004 September 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant NL-04-1782, August 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant2004-09-14014 September 2004 August 2004 Monthly Operating Reports for Joseph M Farley Nuclear Plant NL-04-1445, July 2004 Monthly Operating Report for Joseph M. Farley Nuclear Plant, Units 1 & 22004-08-11011 August 2004 July 2004 Monthly Operating Report for Joseph M. Farley Nuclear Plant, Units 1 & 2 NL-04-1268, June 2004 Monthly Operating Report for Joseph M. Farley Nuclear Plant, Units 1 & 22004-07-13013 July 2004 June 2004 Monthly Operating Report for Joseph M. Farley Nuclear Plant, Units 1 & 2 NL-04-0996, May 2004 Monthly Operating Report for Joseph M Farley Units 1 and 22004-06-10010 June 2004 May 2004 Monthly Operating Report for Joseph M Farley Units 1 and 2 NL-04-0801, April 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 22004-05-11011 May 2004 April 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 2 NL-04-0571, March 2004 Monthly Operating Report for Joseph M. Farley2004-04-13013 April 2004 March 2004 Monthly Operating Report for Joseph M. Farley NL-04-0329, February 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 22004-03-11011 March 2004 February 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 2 NL-04-0186, January 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 22004-02-12012 February 2004 January 2004 Monthly Operating Report for Joseph M. Farley, Units 1 and 2 NL-04-0028, December 2003 Monthly Operating Report for Joseph M. Farley, Units 1 and 22004-01-13013 January 2004 December 2003 Monthly Operating Report for Joseph M. Farley, Units 1 and 2 NL-03-2481, November 2003 Monthly Operating Report for Joseph M Farley Units 1 and 22003-12-15015 December 2003 November 2003 Monthly Operating Report for Joseph M Farley Units 1 and 2 NL-03-2314, October 2003 Monthly Operating Report for Farley, Units 1& 22003-11-11011 November 2003 October 2003 Monthly Operating Report for Farley, Units 1& 2 NL-03-2094, September 2003 Monthly Operating Report for Joseph M. Farley, Units 1 and 22003-10-0808 October 2003 September 2003 Monthly Operating Report for Joseph M. Farley, Units 1 and 2 NL-03-1907, August 2003 Monthly Operating Report for Joseph M Farley2003-09-10010 September 2003 August 2003 Monthly Operating Report for Joseph M Farley NL-03-1659, July 2003 Monthly Operating Report for Joseph M. Farley2003-08-13013 August 2003 July 2003 Monthly Operating Report for Joseph M. Farley NL-03-1491, June 2003 Monthly Operating Report for J. M. Farley Nuclear Plant2003-07-0808 July 2003 June 2003 Monthly Operating Report for J. M. Farley Nuclear Plant NL-03-1295, May 2003 Monthly Operating Report for Joseph M Farley2003-06-11011 June 2003 May 2003 Monthly Operating Report for Joseph M Farley NL-03-1064, April 2003 Monthly Operating Report for Joseph M. Farley2003-05-13013 May 2003 April 2003 Monthly Operating Report for Joseph M. Farley NL-03-0761, March 2003 Monthly Operating Report for Farley Nuclear Plant2003-04-14014 April 2003 March 2003 Monthly Operating Report for Farley Nuclear Plant NL-03-0554, February 2003 Monthly Operating Report for Joseph M. Farley2003-03-10010 March 2003 February 2003 Monthly Operating Report for Joseph M. Farley NL-03-0344, January 2003 Monthly Operating Report for Joseph M. Farley Nuclear Plant2003-02-11011 February 2003 January 2003 Monthly Operating Report for Joseph M. Farley Nuclear Plant NL-03-0117, December 2002 Monthly Operating Report for Joseph M. Farley Nuclear Plant2003-01-0909 January 2003 December 2002 Monthly Operating Report for Joseph M. Farley Nuclear Plant L-02-016, July 2002 Monthly Operating Report for Joseph M. Farley Nuclear Plant2002-08-12012 August 2002 July 2002 Monthly Operating Report for Joseph M. Farley Nuclear Plant L-02-005, February 2002 Monthly Operating Report for Joseph M. Farley, Units 1 & 22002-03-11011 March 2002 February 2002 Monthly Operating Report for Joseph M. Farley, Units 1 & 2 2005-04-13
[Table view] |
Text
Dave Morey Southern Nuclear Vice President Operating Company, Inc.
Farley Project Post Office Box 1295 Birmingham, Alabama 35201 Tel 205 992.5131 August 12, 2002 SOUTHERN COMPANY Docket Nos.: 50-348 Energy to Serve Your World 50-364 NEL-02-0165 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Joseph M. Farley Nuclear Plant Monthly Operating Report Ladies and Gentlemen:
Enclosed are the July 2002 Monthly Operating Reports for Joseph M. Farley Nuclear Plant Units 1 and 2, as required by Section 5.6.4 of the Technical Specifications.
If you have any questions, please advise.
Respectfully submitted, Dave Morey RWC:mor
Enclosures:
- 1. July Monthly Operating Report for Plant Farley Unit 1
- 2. July Monthly Operating Report for Plant Farley Unit 2
Page 2 U. S. Nuclear Regulatory Commission cc: Southern Nuclear Operating Company Mr. D. E. Grissette, General Manager U. S. Nuclear Regulatory Commission, Washington, D. C.
Mr. F. Rinaldi, Licensing Project Manager - Farley U. S. Nuclear Regulatory Commission, Region II Mr. L. A. Reyes, Regional Administrator Mr. T. P. Johnson, Senior Resident Inspector - Farley
OPERATING DATA REPORT DOCKET NO.: 50-348 UNIT NAME: J. M. Farley - Unit I DATE: August 8, 2002 COMPLETED BY: W. L. Marlar TELEPHONE: (334) 814-4554 OPERATING STATUS
- 1. Reporting Period: JULY 2002
- 2. Design Electrical Rating (Net MWe): 854
- 3. Maximum Dependable Capacity (Net MWe): 833 This Month Year to Date Cumulative
- 4. Number Of Hours Reactor Was Critical: 744.0 5,056.1 177,302.0
- 5. Hours Generator On-line: 744.0 5,040.0 175,008.2
- 6. Unit Reserve Shutdown Hours: 0.0 0.0 0.0
- 7. Net Electrical Energy Generated (MWH): 614,347.0 4,220,294.0 138,573,240.0 CHALLENGES TO PRESSURIZER PORV OR PRESSURIZER SAFETY VALVES Date Tag No. Event Description There were no challenges to Pressurizer PORV or Pressurizer Safety Valves.
El-i
UNIT SHUTDOWNS DOCKET NO.: 50-348 UNIT NAME: J. M. Farley - Unit 1 DATE: August 8, 2002 CON4PLETED BY: W. L. Marlar REPORTING PERIOD: JULY 2002 TELEPHONE: (334) 814-4554 Type Method of F: Forced Duration Reason Shutting Down Cause/Corrective Actions No. Date S: Scheduled (Hours) (1) (2) Comments There were no unit shutdowns during the month.
(1) REASON: (2) METHOD:
A - Equipment Failure (Explain) I - Manual B - Maintenance or Test 2 - Manual Trip/Scram C - Refueling 3 - Automatic Trip/Scram D - Regulatory Restriction 4 - Continuation E - Operator Training/License Examination 5 - Other (Explain)
F - Administrative G - Operational Error (Explain)
H - Other (Explain)
CAUSE/CORRECTIVE ACTION/COMMENTS NARRATIVE REPORT There were no significant power reductions this period.
El-2
OPERATING DATA REPORT DOCKET NO.: 50-364 UNIT NAME: J. M. Farley - Unit 2 DATE: August 8, 2002 COMPLETED BY: W.L. Marlar TELEPHONE: (334) 814-4554 OPERATING STATUS
- 1. Reporting Period: JULY 2002
- 2. Design Electrical Rating (Net MWe): 855
- 3. Maximum Dependable Capacity (Net MWe): 842 This Month Year to Date Cumulative
- 4. Number Of Hours Reactor Was Critical: 744.0 5,087.0 160,572.6
- 5. Hours Generator On-line: 744.0 5,087.0 158,632.8
- 6. Unit Reserve Shutdown Hours: 0.0 0.0 0.0
- 7. Net Electrical Energy Generated (MWH): 620,323.0 4,312,552.0 126,894,631.0 CHALLENGES TO PRESSURIZER PORV OR PRESSURIZER SAFETY VALVES Date Tag No. Event Description There were no challenges to Pressurizer PORV or Pressurizer Safety Valves.
E2-1
UNIT SHUTDOWNS DOCKET NO.: 50-364 UNIT NAME: J. M. Farley - Unit 2 DATE: August 8, 2002 COMPLETED BY: W. L. Marlar REPORTING PERIOD: JULY 2002 TELEPHONE: (334) 814-4554 Type Method of F: Forced Duration Reason Shutting Down Cause/Corrective Actions No. Date S: Scheduled (Hours) (1) (2) Comments There were no unit shutdowns during the month.
(1) REASON: (2) METHOD:
A - Equipment Failure (Explain) I - Manual B - Maintenance or Test 2 - Manual Trip/Scram C - Refueling 3 - Automatic Trip/Scram D - Regulatory Restriction 4 - Continuation E - Operator Training/license Examination 5 - Other (Explain)
F - Administrative G - Operational Error (Explain)
CAUSE/CORRECTIVE ACTION/COMMENTS NARRATIVE REPORT At 0000 on 020720, a ramp down to approximately 92% power was commenced to perform governor valve testing. The testing was completed and the unit was returned to 100% power at 0700 on 020720.