IR 05000334/2007007

From kanterella
(Redirected from IR 05000412/2007007)
Jump to navigation Jump to search
IR 05000334-07-007, 05000412-07-007 on 01/22 - 02/08/ 2007, Beaver Valley Power Station, Units 1 and 2; Triennial Fire Protection Team Inspection, Fire Protection
ML070590225
Person / Time
Site: Beaver Valley
(DPR-066, NPF-073)
Issue date: 02/27/2007
From: Rogge J
NRC Region 1
To: Lash J
FirstEnergy Nuclear Operating Co
References
IR-07-007
Download: ML070590225 (11)


Text

February 27, 2007

SUBJECT:

BEAVER VALLEY POWER STATION - NRC TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000334/2007007, 05000412/2007007

Dear Mr. Lash:

On February 8, 2007, the U.S. Nuclear Regulatory Commission (NRC) completed a triennial fire protection team inspection at your Beaver Valley Power Station Units 1 and 2. The enclosed report documents the inspection results which were discussed on February 8, 2007, with Mr. M. Manoleras, Director of Site Engineering, and other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

Based on the results of this inspection, no findings of significance were identified.

The scope of the inspection was reduced for both Units 1 and 2, in accordance with Inspection Procedure 71111.05TTP, issued on May 9, 2006, as a result of your ongoing project to convert the fire protection program of both Units to the performance-based methodology as described in National Fire Protection Association Standard 805.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/ADAMS.html (the Public Electronic Reading Room).

Sincerely,

/RA/

John F. Rogge, Chief Engineering Branch 3 Division of Reactor Safety

Docket Nos. 50-334, 50-412 License Nos. DPR-66, NPF-73

Enclosure:

NRC Inspection Report 05000334/2007007, 05000412/2007007

REGION I==

Docket Nos.

50-334, 50-412 License Nos.

DPR-66, NPF-73 Report No.

05000334/2007007 and 05000412/2007007 Licensee:

FirstEnergy Nuclear Operating Company (FENOC)

Facility:

Beaver Valley Power Station, Units 1 and 2 Location:

Post Office Box 4 Shippingport, PA 15077 Dates:

January 22 - February 8, 2007 Inspectors:

L. Cheung, Senior Reactor Inspector, DRS K. Young, Senior reactor Inspector, DRS P. Finney, Reactor Inspector, DRS S. Lewis, Reactor Inspector, DRS M. Patel, Reactor Inspector, DRS Approved by:

John F. Rogge, Chief Engineering Branch 3 Division of Reactor Safety

ii

SUMMARY OF FINDINGS

IR 05000334/2007007, 05000412/2007007 on 01/22 - 02/08/ 2007, Beaver Valley Power

Station, Units 1 and 2; Triennial Fire Protection Team Inspection, Fire Protection.

This report covered a two-week triennial fire protection team inspection by five Region I specialist inspectors. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process, Revision 3, dated July 2000.

NRC-Identified and Self-Revealing Findings

No findings of significance were identified.

Licensee-Identified Violations

None

REPORT DETAILS

Background This report presents the results of a triennial fire protection inspection conducted in accordance with NRC Inspection Procedure (IP) 71111.05TTP, Fire Protection - NFPA 805 Transition Period (Triennial). The objective of the inspection was to assess whether FirstEnergy Nuclear Operating Company (FENOC) has implemented an adequate fire protection program and that post-fire safe-shutdown capabilities have been established and are being properly maintained at the Beaver Valley Power Station, Units 1 and 2. The following fire areas (FAs) were selected for detailed review based on risk insights from the Individual Plant Examination (IPE)/Individual Plant Examination of External Events (IPEEE):

Beaver Valley Power Station Unit 1 Beaver Valley Power Station Unit 2 Fire Area CS-1, Fire Area CB-2, Fire Area ES-1, Fire Area SB-2, Fire Area CV-1, Fire Area CV-1.

Section 71111.05-05 of IP 71111.05TTP specifies a minimum sample size of three fire areas.

Inspection of these three areas in each Unit fulfills the procedure completion criteria. The inspection team evaluated the licensees fire protection program (FPP) against applicable requirements which include plant Technical Specifications, Operating License Condition 2.C.5 (Unit 1) and 2.F (Unit 2), NRC Safety Evaluations, 10 CFR 50.48 and 10 CFR 50 Appendix R.

The team also reviewed related documents that include the Updated Final Safety Analysis Report (UFSAR), the Fire Hazards Analysis (FHA) and the Post-Fire Safe Shutdown Analysis for both Units 1 and 2.

Specific documents reviewed by the team are listed in the attachment.

REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems

==1R05 Fire Protection

==

.01 Post-Fire Safe Shutdown From Outside Main Control Room (Alternative Shutdown) and

Normal Shutdown

a. Inspection Scope

Methodology The team reviewed the safe shutdown analysis, operating procedures, piping and instrumentation drawings (P&IDs), electrical drawings, the UFSAR and other supporting documents to verify that hot and cold shutdown could be achieved and maintained from outside the control room for fires that rely on shutdown from outside the control room.

This review included verification that shutdown from outside the control room could be performed both with and without the availability of offsite power. Plant walkdowns were also performed to verify that the plant configuration was consistent with that described in the safe shutdown and fire hazards analyses. These inspection activities focused on ensuring the adequacy of systems selected for reactivity control, reactor coolant makeup, reactor decay heat removal, process monitoring instrumentation and support systems functions. The team verified that the systems and components credited for use during this shutdown method would remain free from fire damage.

Similarly, for fire areas that utilize shutdown from the control room, the team verified that the shutdown methodology properly identified the components and systems necessary to achieve and maintain safe shutdown conditions.

Operational Implementation The team verified that the training program for licensed and non-licensed operators included alternative shutdown capability. The team also verified that personnel required for safe shutdown using the normal or alternative shutdown systems and procedures are trained and available onsite at all times, exclusive of those assigned as fire brigade members.

The team reviewed the adequacy of procedures utilized for post-fire shutdown and performed an independent walk through of procedure steps to ensure the implementation and human factors adequacy of the procedures. The team also verified that the operators could be reasonably expected to perform specific actions within the time required to maintain plant parameters within specified limits. Time critical actions which were verified included restoration of alternating current (AC) electrical power, establishing the remote shutdown panel, and establishing decay heat removal.

Specific procedures reviewed for alternative shutdown, including shutdown from outside the control room, included the following:

Unit 1 C

10M-56C.4.B, Unit 1 Shift Manager Procedure, Revision 33 C

10M-56C.4.C, Unit 1 NCO Procedure, Revision 29 C

10M-56C.4.D, Unit 1 Nuclear Operator #1 Procedure, Revision 29 C

10M-56C.4.E, Unit 1 Shift Technical Advisors Procedure, Revision 17 C

10M-56C.4.F-1, Unit 1 BIP (Back-up Indication Panel) Activation, Revision 20 Unit 2 C

2OM-56.C.4.B, Unit Supervisor Procedure, Revision 26 C

2OM-56.C.4.C, NCO Procedure, Revision 16 C

2OM-56.C.4.D, Nuclear Operator #1 Procedure, Revision 19 C

2OM-56.C.4.E, Nuclear Operator #2 Procedure, Revision 18 C

2OM-56.C.4.F-1, ASP Activation, Revision 11 The team reviewed manual actions to ensure that they could be implemented in accordance with plant procedures in the time necessary to support the safe shutdown method for each fire area. The team verified that the licensee had identified operator manual actions for post-fire safe-shutdown and had plans in place to assess them as part of the plant wide risk evaluation for transition to NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition. The team also reviewed the periodic testing of the alternative shutdown transfer capability and instrumentation and control functions to ensure the tests are adequate to ensure the functionality of the alternative shutdown capability.

b. Findings

No findings of significance were identified.

.02 Protection of Safe Shutdown Capabilities

a. Inspection Scope

The team reviewed the fire hazards analysis, safe shutdown analyses and supporting drawings and documentation to verify that safe shutdown capabilities were properly protected. The team ensured that separation requirements of Section III.G of 10 CFR 50, Appendix R were maintained for the credited safe shutdown equipment and their supporting power, control and instrumentation cables. This review included an assessment of the adequacy of the selected systems for reactivity control, reactor coolant makeup, reactor heat removal, process monitoring, and associated support system functions.

The team reviewed FENOCs procedures and programs for the control of ignition sources and transient combustibles to assess their effectiveness in preventing fires and in controlling combustible loading within limits established in the Fire Hazard Analysis (FHA). A sample of hot work and transient combustible control permits were also reviewed. The team performed plant walkdowns to verify that protective features were being properly maintained and administrative controls were being implemented.

The team also reviewed FENOCs design control procedures to ensure that the process included appropriate reviews and controls to assess plant changes for any potential adverse impact on the fire protection program and/or post-fire safe shutdown analysis and procedures.

b. Findings

No findings of significance were identified.

.03 Passive Fire Protection

a. Inspection Scope

The team walked down accessible portions of the selected fire areas to observe material condition and the adequacy of design of fire area boundaries (including walls, fire doors and fire dampers) to ensure they were appropriate for the fire hazards in the area.

The team reviewed installation/repair and qualification records for a sample of penetration seals to ensure the fill material was of the appropriate fire rating and that the installation met the engineering design. The team also reviewed similar records for fire protection wraps to ensure the material was of an appropriate fire rating and that the installation met the engineering design.

b. Findings

No findings of significance were identified.

.04 Active Fire Protection

a. Inspection Scope

The team reviewed the design, maintenance, testing and operation of the fire detection and suppression systems in the selected plant fire areas. This included verification that the manual and automatic detection and suppression systems were installed, tested and maintained in accordance with the National Fire Protection Association (NFPA) code of record, or as NRC approved deviations, and that they would control and/or extinguish fires associated with the hazards in the selected areas. A review of the design capability of suppression agent delivery systems was verified to meet the code requirements for the fire hazards involved. The team also performed a walkdown of accessible portions of the detection and suppressions systems in the selected areas as well as a walkdown of major system support equipment in other areas (e.g., fire protection pumps, Carbon Dioxide (CO2) storage tanks and supply system) and assess the material condition of the systems and components.

The team reviewed electric and diesel fire pump flow and pressure tests to ensure that the pumps were meeting their design requirements. The team also reviewed the fire main loop flow tests to ensure that the flow distribution circuits were able to meet the design requirements.

The team also assessed the fire brigade capabilities by reviewing training and qualification records, and drill critique records. The team also reviewed pre-fire plans and smoke removal plans for the selected fire areas to determine if appropriate information was provided to fire brigade members and plant operators to identify safe shutdown equipment and instrumentation, and to facilitate suppression of a fire that could impact post-fire safe shutdown. In addition, the team inspected the fire brigades protective ensembles, self-contained breathing apparatus (SCBA), and various fire brigade equipment (including smoke removal equipment) to determine operational readiness for fire fighting.

b. Findings

No findings of significance were identified.

.05 Protection From Damage From Fire Suppression Activities

a. Inspection Scope

The team performed document reviews and plant walkdowns to verify that redundant trains of systems required for hot shutdown are not subject to damage from fire suppression activities or from the rupture or inadvertent operation of fire suppression systems. Specifically, the team verified that:

C A fire in one of the selected fire areas would not directly, through production of smoke, heat or hot gases, cause activation of suppression systems that could potentially damage all redundant trains; C

A fire in one of the selected fire areas (or the inadvertent actuation or rupture of a fire suppression system) would not directly cause damage to all redundant trains (e.g., sprinkler caused flooding of other than the locally affected train);

C Adequate drainage is provided in areas protected by water suppression systems.

b. Findings

No findings of significance were identified.

.06 Alternative Shutdown Capability

a. Inspection Scope

Alternative shutdown capability for the areas selected for inspection utilizes shutdown from outside the control room and is discussed in Section 1R05.01 of this report.

.07 Circuit Analyses

This topic was not inspected for plants in NFPA 805 transition.

.08 Communications

a. Inspection Scope

The team reviewed safe shutdown procedures, the safe shutdown analysis and associated documents to verify an adequate method of communications would be available to plant operators following a fire. During this review the team considered the effects of ambient noise levels, clarity of reception, reliability and coverage patterns.

The team also inspected the designated emergency storage lockers to verify the availability of portable radios for the fire brigade and for plant operators. The team also verified that communications equipment such as repeaters, transmitters, etc. would not be affected by a fire.

b. Findings

No findings of significance were identified.

.09 Emergency Lighting

a. Inspection Scope

The team observed the placement and coverage area of eight-hour emergency lights, and in specified locations permanent essential lighting, throughout the selected fire areas to evaluate their adequacy for illuminating access and egress pathways and any equipment requiring local operation and/or instrumentation monitoring for post-fire safe shutdown. The team also verified that the battery power supplies were rated for at least an eight-hour capacity. Preventive maintenance procedures and various documents, including the completed surveillance tests were reviewed to ensure adequate surveillance testing and periodic battery replacements were in place to ensure reliable operation of the eight-hour emergency lights and that the emergency lighting units were being maintained consistent with the manufacturers recommendations and accepted industry practices.

b. Findings

No findings of significance were identified.

.10 Cold Shutdown Repairs

a. Inspection Scope

The team verified that the licensee had dedicated repair procedures, equipment, and materials to accomplish repairs of components required for cold shutdown which might be damaged by the fire to ensure cold shutdown could be achieved within the time frames specified in their design and licensing bases. The inspectors verified that the repair equipment, components, tools and materials (e.g. pre-cut cables with prepared attachment lugs) were available and accessible on site.

b. Findings

No findings of significance were identified.

.11 Compensatory Measures

a. Inspection Scope

The team verified that compensatory measures were in place for out-of-service, degraded or inoperable fire protection and post-fire safe shutdown equipment, systems, or features (e.g., detection and suppression systems and equipment, passive fire barriers, pumps, valves or electrical devices providing safe shutdown functions or capabilities). The team also verified that the short term compensatory measures compensated for the degraded function or feature until appropriate corrective action could be taken and that FENOC was effective in returning the equipment to service in a reasonable period of time.

b. Findings

No findings of significance were identified.

OTHER ACTIVITIES

4OA2 Identification and Resolution of Problems

.01 Corrective Actions for Fire Protection Deficiencies

a. Inspection Scope

The team verified that the licensee was identifying fire protection and post-fire safe shutdown issues at an appropriate threshold and entering them into the corrective action program. The team also reviewed a sample of selected issues to verify that the licensee had taken or planned appropriate corrective actions.

b. Findings

No findings of significance were identified.

4OA6 Meetings, Including Exit

Exit Meeting Summary

The team presented their preliminary inspection results to Mr. M. Manoleras, Director of Site Engineering, and other members of the site staff at an exit meeting on February 8, 2007. No proprietary information was included in this inspection report.

ATTACHMENT

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee Personnel

J. Belfiore

Engineer

A. Boros

FP System Engineer

P. Boulden

Appendix R Resolution

P. Boulden, Jr.

Appendix R Resolution

T. Brown

Training

T. Cotter

Operations Supt.

K. Grada

Outage Manager

K. Halliday

NFPA Project

R. Hansen

Manager, Oversight

S. Hubley

Maintenance Manager

H. Kahl

Electrical Design Engineer

C. Manuso

Design Engineering Manager

M. Manoleras

Director, Site Engineering

J. Maracek

Fleet Licensing

J. Mauck

Compliance

J. Miller

Fire Marshal

L. Miller

Fire Protection Engineer

M. Mousv

Operations

R. Mueller

Operations

R. Plummey

Procedure Writer

R. Oates

Appendix R Resolution

F. Oberlitner

Design Engineering

D. Price

Supervisor, Structural Engineering

R. Rubert

Supervisor, Design Engineering

B. Sepelak

Compliance Supervisor

S. Solhdoost

Appendix R Resolution

J. Stranger

Appendix R Resolution

J. Witter

Unit 2 Operations Supt.

NRC

J. Rogge, Chief, Engineering Branch 3, Division of Reactor Safety
P. Cataldo, Senior Resident Inspector, Beaver Valley Power Station
D. Werkhieser, Resident Inspector, Beaver Valley Power Station

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened

None

Open and Closed

None

Closed

None

Discussed

None

Fire Protection Licensing Documents

Beaver Valley Power Station Unit 1, Updated Final Safety Analysis Report

Beaver Valley Power Station Unit 1, Updated Fire Protection Appendix R Review, Rev. 27

SER Dated 1/5/83, SER For Appendix R to 10CFR Part 50 Items II

I.G and III.L - BVNS, Unit 1

Exemption Request Dated 3/14/83,BVPS, Unit 1, Request for Exemption from the

Requirements of Appendix R to 10CFR, Part 50 & Notice From Appendix R to 10CFR50 Fire

Protection Requirements

Letter From NRC Dated 7/27/87, BVPS Unit No. 1 - Transmittal of Appendix R Technical

Exemption Regarding Emergency Lighting

Fire Protection Safe Shutdown Report, Beaver Valley Power Station Unit 2, Addendum 29

BV1 Exemption Approval from NRC dated 03/14/83

Duqesne Light letter to the NRC, dtd 10/27/1976

Calculations/Engineering Evaluation Reports

8700-DMC-1352,

Emergency Diesel Generator Operating Time With Loss of RW, Rev. 0

8700-DMC-1644,

Pressurizer Level Response Following a Fire, Rev. 0

8700-DMC-3232,

Minimum Time Required to Overfill Steam Generator Using Only Auxiliary

Feedwater Following a Plant Trip, Rev. 0

8700-DMC-3463,

VCT Pressure Limits to Prevent Gas Intrusion to the Charging Pump

Suction, Rev. 2

8700-DMC-3509,

HHSI Pump Oil Temperature Following Loss of RW, Rev. 0

8700-B-084

BVPS Unit 1 Fire Hazard Analysis, Rev. 9

10080-DEC-0240

Unit 2 Fire Protection Safe Shutdown Breaker Coordination Analysis

dated 11/6/2002

TER 13543

Results of Fire Protection Reviews for CA991340-05 and CA991340-06,

Rev. 0

TER 13728

Repairs to Achieve Safe Shutdown - BV1 UFPARR, Rev. 0

TER 13719

Unit 1 Breaker Circuit Coordination Analysis, Rev. 0

10080-DMC-0820

Beaver Valley Power Station Unit 2 Loss of Offsite Power and Stuck

Open Pressurizer PORV Analysis, Rev. 0

DCP-1794

Retiring of Heat Actuated Detector TD-FE-2A-3, 10/23/92

FPPCE 06-038

Fire Protection Program Change Evaluation, Rev.0

EM 63302

CO2 System 2 Concentration Testing

EM 63077

CO2 Discharge Zone Time Settings

SOV-2.33A.01

Main Plant Carbon Dioxide System Test (Fire Protection)

Procedures

10M-56C.4.G

Unit 1 Nuclear Operator #2 Procedure, Revision 0

10M-56B.4.I

Unit 1 Safe Shutdown Following a Serious Fire in The Service Building,

Revision 8

1/2OM-48.1.B

Operations Shift Complement and Functions, Rev. 4

2OM-56B.4.B

Operating Procedure - Safe Shutdown Following a Fire in the Cable Vault

Building, Rev. 14

2OM-56B.4.1

Safe Shutdown Following a Serious Fire in the Service Building, Rev. 9 1/2

ADM-0407

Installation and Inspection of Permanent and Temporary Penetration

Seals, Rev. 2

1/2-ADM-1900

Fire Protection Program, Rev. 14

1/2-ADM-1901

Fire Protection Pre-Fire Plan Administrative Control, Rev. 2

1/2-ADM-1902

Fire Brigade, Rev. 4

1/2-ADM-1903

Fire Protection Program Chang Process, Rev. 1

1/2-ADM-1904

Control of Ignition Sources (Hot Work) and Fire Watches, Rev. 0

1/2-ADM-1905

Fire Protection/Fire Barrier Impairments, Rev.0

1/2-ADM-2021

Control of Penetrations (Including HELB Doors), Rev.4

1BVT-1.33.5

Fire-Rated Assemblies Visual Inspection, Issue 4, Rev.6

1/2PMP-75VS-VNT-4 M Ventilation System Fire Damper Maintenance and Trip Check,

Issue 4, Rev. 10

1PMP-38VB-EL-1E

Emergency Lighting Maintenance, Testing and Inspection, Issue 4,

Rev. 20

1/2-PIP-M16

Penetration Seals, Rev. 6

IP-S-07P

Grouting, Rev. 4

1OM-33.4.Y

Jumpering Smoke Detectors, Rev. 0

1OM-33.4.AAO

West Cable Vault Fire, Rev. 2

1OM-33.4.ABE

West Cable Vault Fire Prot System Trouble, Rev. 0

1OM-33.4.AAW

West Cable Vault CO2 Discharge, Rev. 0

1OM-33.4.AEA

Cable Vault Hose Reels Gate Valve Flow, Rev. 0

1OM-33.4.AAV

Cable Tray Mezzanine CO2 Discharge, Rev. 0

1OM-33.4.AAN

Cable Tray Mezzanine Fire, Rev. 2

1OM-33.4.ABD

Cable Tray Mezz Fire Prot System, Rev. 0

1OM-33.4.ADF

A/C Equip or Cable Sprdg Rm Fire, Rev. 2

1OM-33.4.ADV

A/C Equip or Cable Sprdg Rm Trouble, Rev. 0

1OM-33.4.ADN

A/C Equip or Cable Sprdg Rm Flow, Rev. 0

1OST-33.1B

Fire Protection System Water Flow and Drain Test, Rev. 8

1OST-33.5

Fire Protection System Inspection Test, Rev. 8

1OST-33.10A

Miscellaneous Deluge Valve Tests, Rev. 16

1OST-33.12

Fire Protection System Valve Stroke Test, Rev. 4

1OST-33.13C

Ten Ton CO2 Fire Protection System Test, Rev. 9

1OST-33.16

Smoke Detector Instrumentation Test, Rev.13

1OST-33.9

CO2 Fire Protection System Inspection Test, Rev. 6

1/2OST-33.12

Fire Protection System Loop Flow Test, Rev.11

1/2-ADM-1900

Fire Protection Program, Rev. 14

1/2-ADM-1904

Control of Ignition Sources (Hot Work) and Fire Watches, Rev. 0

1/2-ADM-1905

Fire Protection/Fire Barrier Impairments, Rev. 0

1/2PMP-33FP

Fire Doors-1M, Periodic Inspection of Fire Doors, Rev. 3

2PMP-38-EMERLGT-4E Appendix R and Non Appendix R Emergency Lighting Operability

Test, Inspection, and Repair, Rev. 11

1MSP-6.02-1

Unit 1 P-403, Reactor Coolant System Wide Range Pressure Calibration,

Revision 11

1MSP-6.42-1

Unit 1 L-IRC-460, Pressurizer Level Channel II Calibration, Revision 2

1MSP-6.90-1

Calibration of Various In-containment Protection Transmitters During

Shutdown, Revision 2

1LCP-56-BIP

Calibration of the Back-up Indicating Panel Instrumentation, Revision 2

L-1FW475

Unit 1 Loop 1 Narrow Range Steam Generator Level Channel 2

Calibration, Revision 10

2LCP-24-L477F

Unit 2 2FWS-L477F, Steam Generator (2RCS-SG21A) Wide Range

Level Calibration, Revision 1

2LCP-6-L459AF

Unit 2 2RCS-L459AF, Pressurizer(2RCS*PRE21) Level calibration,

Revision 1

Completed Tests/Surveillances

/ 2 OST-56B.1

Appendix R Equipment Verification, Rev. 3, Completed 4/18/06

/ 2 OST-56B.2

Appendix R Equipment Inventory Verification, Rev. 2, Completed 1/5/07

/ 2 OST-56C.1

Appendix R PAX Phone Verification, Rev. 6, Completed 8/11/06

1/2OST-58E.1RG

Diesel Generator Test, RG-EG-1, Rev. 27, Completed January 06, 2007

2OST-39.1E

Weekly Station Battery Check, BAT 2-5, Rev. 08, Completed January 19,

2007

2OST-39.1F

Weekly Station Battery Check, BAT 2-6, Rev. 10, Completed January 20,

2007

1OST-33.1B

Fire Protection System Water Flow and Drain Test, 10/29/06

1OST-33.13B

Deluge Valve Fire Protection System, Rev.12, 01/11/05, 06/18/06

1/2OST-56C.01

Appendix R PAX Phone Verification, Rev.6, 08/11/06

1OST-33.7

Motor Driven Fire Pump Operation Test, completed 11/18/06

1OST-33.7

Motor Driven Fire Pump Operation Test, completed 1/12/07

1OST-33.8

Diesel Engine Driven Fire Pump Operation Test, completed 11/25/06

1OST-33.8

Diesel Engine Driven Fire Pump Operation Test, completed 1/16/07

1/2OST-33.12

Fire Protection System Loop Flow Test, completed 9/10/06

1/2OST-33.12

Fire Protection System Loop Flow Test, completed 11/29/06

1/2OST-33.17A

[1FP-P-5A] Operational Test, completed 9/27/06

1/2OST-33.17A

[1FP-P-5A] Operational Test, completed 1/27/07

1/2OST-33.17B

[1FP-P-5B] Operational Test, completed 9/23/06

1/2OST-33.17B

[1FP-P-5B] Operational Test, completed 1/18/07

2OST-33.9

CO2 Fire Protection System Inspection, completed 12/09/06

2OST-33.9

CO2 Fire Protection System Inspection, completed 1/06/07

2OST-33.13c

Main Plant CO2 Zone Puff Tests, completed 9/10/03

2OST-33.13c

Main Plant CO2 Zone Puff Tests, completed 5/12/05

2OST-33.16

Early Warning Smoke Detection Instrumentation Test, Rev. 9

Quality Assurance (QA) Audits and System Health Reports

Unit 1 System Health Report 2005-4

Unit 1 System Health Report 2006-2

Fire Protection Health Report 2006-1-BV

Fire Protection Health Report 2006-2-BV

Fire Protection Health Report 2006-3-BV

BV-2-33-System-Unit 2 Fire Protection Health Report 2005-3

BV-2-33-System-Unit 2 Fire Protection Health Report 2006-2

Second Quarter 2006 Beaver Valley Assessment Report (BV-C-06)

Beaver Valley Power Station, BV1 & BV2 Fire Protection Latent Issues Review Report, 1/8/07

Beaver Valley Power Station Unit 1, 1OM-56B Procedures, Shutdown From the Main Control

Room, Operator Manual Actions Feasibility Review, 1/23/07

Beaver Valley Power Station Unit 2, 2OM-56C Safe Shutdown Procedures Manual Operator

Actions Timeline Study, 1/11/04

Drawings

10080-RE-1AN

25V DC & 120V AC One Line Diagram, Rev. 08

10080-RE-1AT

25V DC One Line Diagram, Rev. 15

10080-RE-10AJ

Wiring Diagram - 125V DC Misc Det Safeguard Area, Rev. 12

10080-RE-25GA

Front View, Alternate Shutdown Panel, Section 1 & 2, Revision 9

10080-E-6RG

Elementary Diagram - 480 V MCC Circuit, CCP System Valves to RHS

System, Revision 11

10080-E-6GM

Elementary Diagram - 480 V MCC Circuit, DG 2-1 Heat Exchanger

Header Valve, Revision 17

10080-E-6J5

Elementary Diagram - 480 V MCC Circuit, Charging Pump Suction

Valves, Revision 24

10080-TLD-006-024-01 & 02 Test Loop Diagram, Reactor Coolant System, Pressurizer

2RCS*PRE21 Level, Revision 4

10080-TLD-24A-053-01 & 02 Test Loop Diagram, Main Feedwater System Steam Generator

2RCS*SG21A Wide Range Level, Revision 2

241-E-11H

Elementary Diagram Miscellaneous Circuits, Rev. 13

241-E-11FZ

Elementary Diagram Miscellaneous Circuits, Sh. 2 & 3, Revision 10,

241-E-6RG

Elementary Diagram 4160 V Charging Pump 2CHS*21A Sh. 1 & 2,

Revision 10

8700-1.35-0169

West Cable Vault El. 735'-6" Wall and Floor Penetrations, Rev. H

8700-1.35-0170

West Cable Vault El. 735'-6" Wall and Floor Penetrations, Rev. E

8700-1.35-0171

West Cable Vault - Wall and Floor Penetrations El. 735'-6", Rev. F

8700-10.001-0761

Cable Mezzanine Floor & Wall Penetrations and Data Sheet, Rev. H

8700-RE-37BH

Sleeve Details Service Building, Sh. 4, Rev.26

8700-RM-433-3

Valve Oper No Diagram Fire Protection - CO2, Rev. 11

8700-RE-21GX

Elementary Diagram Fire Protection (FP) SH60F8, Rev. 11

8700-RE-18U

CO2 Fire Protection Wiring Diag. Storage Units & Terminal Boxes, Sh. 1,

Rev. 7

8700-RE-18V

CO2 Fire Protection Wiring Diag. Cabinets FE-CDL-2A, Sh. 2, Rev. 7

8700-RE-18W

CO2 Fire Protection Wiring Diag. Cabinets FE-CDL-2B, 3 & 4A, Sh. 3,

Rev. 4

8700-RE-51B

Conduit Plan Fire Protection System, Sh. 2, Rev. 4

8700-RE-64JP

Cable Block Diagram - Fire Detection DGP-1A, DGP-1B, & DGP-7,

Rev. 1

8700-RE-64JR

Cable Block Diagram - Fire Detection DGP-2A, DGP-2B, Rev. 1

8700-RE-64JQ

Cable Block Diagram - Fire Detection DGP-3, DGP-4, & DGP-5, Rev. 1

8700-RE-67C

Lighting Plans - Reactor Containment, Sh. 3, Rev. 16

8700-RE-68A

Lighting Plan Service Building, Sh. 1, Rev. 13

8700-RE-68E

Lighting Plan Service Building, Sh.5, Rev.7

8700-RM-433-1

Valve Oper No Diagram Fire Protection - Water, Rev. 17

8700-RM-433-2

Valve Oper No Diagram Fire Protection - Water, Rev. 18

8700-RM-433-4

Valve Oper No Diagram Fire Protection - Halon and CO2, Rev. 5

8700-RM-433-6

Valve Oper No Diagram New Warehouse Fire Prot System, Rev. 6

8700-RM-433-8

Valve Oper No Diagram Fire Protection Details, Rev.11

8700-RM-432-9

Valve Oper No Diagram Filtered Water System, Rev.13

8700-RM-416-1

Vent & Air Cond Primary Plant, Rev. 13

8700-10.1-956

Typical EC-1, EC-2, EC-3, EC-4, EC-5, EC-6, Rev. B

8700-10.1-929

Typical MC-1 & MC-2 Wall/Floor Mechanical Fire Seals, Rev. A

8700-RM-433-1

Fire Protection - Water, Rev. 17

8700-RE-250B-1

Outline Backup Indicating Panel

8700-RE-22W

Steam Generator System Steam Generator #1 Narrow Range Level

Protection I & II Loop Diagram, LT-FW 474 & 475, Revision 9

8700-RE-22Y

Steam Generator System Steam Generator #1 Narrow Range Level

Protection I & II Loop Diagram, LT-FW 494 & 495, Revision 9

8700-RE-22BJ

Reactor Coolant System Pressurizer Level Protection Channel II Level

Control System, Loop Diagram, LT-RC-460, Revision 8

8700-RE-22BM

Reactor Coolant System Wide and Narrow Rang Pressure Loop

Diagram, PT-RC-402, PT-RC 203 and TRB-RC 401, Revision 14

8700-REBR-11

Reactor Coolant System Loop Isolation Valves Temperature Interlock

Cold Leg Protection II Loop Diagram TRB-RC 410, 420,430, Revision 14

10080-RM-433-2A

CO2 Fire Protection, Rev. 15

Pre-Fire Plans

1-PFP-SRVB-725

Cable Tray Mezzanine, Rev. 0

1-PFP-SRVB-713

AE Switchgear, Rev. 0

1-PFP-SFGB-735

West Cable Vault, Rev. 0

Piping and Instrumentation Diagrams (P&IDs)

8700-RM-406

Valve Oper NO Diagram, Reactor Coolant System, Shts. 1 - 4

8700-RM-407

Valve Oper NO Diagram, Chemical & Volume Control System, Shts. 1 - 5

8700-RM-410

P&ID, RHR System, Rev. 12

8700-RM-421

Valve Oper NO Diagram, Main Steam, Shts. 1 - 5

8700-RM-424

Valve Oper NO Diagram, Feedwater System, Shts. 1 - 5

Fire Brigade Documents

FITS Qualification Matrices

Fire Drill, Shift 1, 02/04/06

Fire Drill, Shift 1, 05/10/06

Fire Drill, Shift 1, 09/13/06

Fire Drill, Shift 1, 12/05/06

Fire Drill, Shift 1, 12/08/06

Fire Drill, Shift 2, 01/11/06

Fire Drill, Shift 2, 05/17/06

Fire Drill, Shift 2, 09/20/06

Fire Drill, Shift 2, 12/03/06

Fire Drill, Shift 5, 06/07/06

Fire Drill, Shift 5, 11/22/06

Fire Brigade Training

1/2-ADM-1301.F06

Fire Watch Training, Rev. 1

Operator Safe Shutdown Training

1SQS-56C.1

Alternate Safe Shutdown From Outside Control Room, Rev. 7

1SQS-56C.2

OM 56C - Alternate Safe Shutdown, In-Plant, Rev. 5

2SQS-56C.1

Alternate Safe Shutdown, Rev. 4

2SQS-56C.2

OM 56C - Alternate Safe Shutdown, In-Plant, Rev. 3

3SQS-56B.1

OM-56B Fire Prevention and Control, Rev. 4

Job Performance Measures (JPMs)

1CR-109

Control Room Evacuation, Rev. 4

1PL-030

Safe Shutdown From the Switchgear Room, Rev. 10

1PL-034

Establish Manual Control of Atmospheric Steam Dumps, Rev. 8

1PL-155

Open FWI Valve per 10M-56C.4.F-10, Rev. 0

2PL-019

Align Station Air Compressor for Operation Per OM-56C, Rev. 7

2PL-037

Alternate Shutdown From Generator Building, Rev. 7

2PL-061

Transferring Power for 2RHS*MOV702A, Rev. 6

2PL-076

Isolate AFW During Alternate Safe Shutdown, Rev. 2

Hot Work and Ignition Source Permits

HWP for W/O 200227436, Pipe Tunnel, 12/17/06

HWP for W/O 200241847, Decon Bldg, 12/16/06

HWP for W/O 200194214, PCA Shop, 12/29/06

HWP for W/O 200194214, PCA Shop Roof, 12/28/06

HWP for W/O 200194214, PCA Shop, 12/28/06

HWP for W/O 200016012

HWP for W/O 200158686

HWP for W/O 200166369

HWP for W/O 200213738

HWP for W/O 200228097

HWP for W/O 200230723

HWP for W/O 200235524

HWP for W/O 200237360

Transient Combustible Evaluations

1/2-ADM-1906, Control of Transient Combustible and Flammable Materials, Rev. 0

Condition Reports (* denotes CRs generated as a result of this inspection)

99-01340

01-03412

2-00916

05-04546

06-02940

06-04134

06-05115

06-09620

06-07305

06-11175

06-11341

06-07447

06-00305

06-00322

06-11613

06-10430

07-12200

07-12784

07-12788

07-12929

07-13053

07-13243

07-13361

07-13379

07-13414

07-13481

07-13485

07-13488

07-13491

07-13576

07-13664

07-13833

07-12969

07-13583

07-13598

07-13801

07-13906

07-12042

07-12981

07-13290

07-13427

07-13453

07-13522

07-13691

07-13252*

07-13269*

07-13296*

07-13321*

07-13327*

07-13345*

07-13357*

07-13369*

03-13379*

07-13387*

07-13416*

07-13419*

07-13436*

07-13485*

07-13492*

07-14040*

07-14067*

07-14058*

07-14100*

07-14129*

07-14137*

07-14142*

07-14157*

07-14159*

Work Orders (WO)

200194214

Install Wall Penetration Sleeves

200196145

Inspect, Lube, Maintain Fire Damper Relay Room Return Fire Damper

(1VS-D-93), 02/06/07

200250361

Reseal Penetration 1WC225N05, 02/01/07

200188561

Inspect Emergency Lights, 01/02/07

200188562

Inspect Emergency Lights, 01/20/07

200250361

Replace Penetration Seal WCM-725-52, 02/01/07

200250931

Replace Penetration Seal WCM-725-133, 02/06/07

200250240

Repair Penetration Seal WCM-725-126, 01/30/07

200160247

Fire Protection System Loop Flow Test, 09/11/06

200157999

Fire Protection System Water Flow, 08/14/06

200133271

Unit 1 Loop Calibration P-430 Reactor Coolant System Wide Range Pressure,

2/01/06

200124905

Unit 1 Calibration of L-1FW-475 Narrow Range Steam Generator Level,

04/04/06

200118807

Unit 1 Calibration of Back-up Indicating Panel Instruments, 10/21/05

200139808

Unit 1 Loop Calibration of L-460, 06/13/06

200125192

Unit 1 Perform 1MSP-6.90-1 Calibration, 03/16/06

200115004

Unit 2 Perform Loop Calibration Section of 2LCP-24-L477F, 09/09/05

200151163

Unit 2 Transmitter Calibration, 9/30/06

200151372

Unit 2 Pressurizer Level Loop Calibration, 10/05/06

200133160

Unit 2 2RCS-LI459AF Loop Pressurizer Level Calibration, 05/02/06

200115004

Unit 2 2FWS-L477F Loop Steam Generator Wide Range Level Calibration,

09/16/05

200189529

Loop Calibration for Pressurizer Pressure, 12/07/06

200151428

Transmitter P455F Calibration

WO 200133021

WO 200154520

WO 200155186

WO 200189423

WO 200190141

WO 200190280

WO 200192545

WO 200193824

WO 200193825

Miscellaneous Documents

2W00-06-SM-001

Reactor Vessel Vent Piping Downstream Isolation Train B, Clearance,

November 09, 2006

07-00432

2BVP-CYC-013-1 2W00-06-SM-001 Clearance in effect > 60 days, 50.59

Screening, January 29, 2007

Report of Premixed Grout Cubes, Report #1304

Degraded Fire Barrier/Penetration Seal Evaluation Checklist for SB-713-1616(7,8), 2/1/07

Degraded Fire Barrier/Penetration Seal Evaluation Checklist for ES-1 Cafcote Fire Proofing,

2/1/07

Degraded Fire Barrier/Penetration Seal Evaluation Checklist for ES-2 Cafcote Fire Proofing,

2/1/07

ANI Acceptance of Testing Certificate for ANI Index #4, CTP-1001A, Cable and Fire

Penetration Fire Stop System, 04/29/86

ANI Acceptance of Testing Certificate for ANI Index #6, CTP-1001A, Cable and Fire

Penetration Fire Stop System, 04/29/86

ANI Acceptance of Testing Certificate for ANI Index #11, CTP-1009, Cable and Fire Penetration

Fire Stop System, 04/29/86

Beaver Valley Power Station Unit 1 Probabilistic Risk Assessment Update Report Issue 3,

06/02/06

Fire Qualification Test on Silicone Foam Floor Penetration Seals, SWRI Project 03-6004-006,

07/25/80

Fire Qualification Test on Penetration Seals, SWRI Project 01-6613-001A, 08/28/81

LIST OF ACRONYMS USED

AC

Alternating Current

CFR

Code of Federal Regulations

CO2

Carbon Dioxide

DRS

Division of Reactor Safety

FA

Fire Area

FENOC

FirstEnergy Nuclear Operating Company

FHA

Fire Hazards Analysis

FPP

Fire Protection Program

IP

Inspection Procedure

IPE

Individual Plant Examination

IPEEE

Individual Plant Examination of External Events

IR

Inspection Report

NFPA

National Fire Protection Association

NRC

Nuclear Regulatory Commission

PARS

Publicly Available Records

P&ID

Piping and Instrumentation Drawing

SCBA

Self Contained Breathing Apparatus

UFSAR

Updated Final Safety Analysis Report