NUCLEAR REGULATORY COMMISSION UNITED STATES (
<
o REGION ll
\\/C I
101 MARIETTA ST., N.W., SUITE 3100
- $
%,*****#g ATLANTA, GEORGIA 30303 MAR 2 01981 c
Report No. 50-364/81-08
Licensee: Alabama Power Company
,
i 600 North 18th Street Birmingham,.AL 35202 Facility Name:
Farley 2 Docket No. 50-364 License No. NPF-8 Inspection at Farley site near Ashford, AL f
_
_
88!8/
Inspector:
W. H. Miller, Jr.
QT Date Signed
'
V
[
Approved by: /
T. E. Conlon,QectMn Chiptf~,-Engineering Dafe Signed
Inspection Branch v
Engineering and Technical Inspection Division SUMMARY t
Inspected on February 24-27, 1981
Areas Inspected This special announced inspection involved 26 inspector-hours onsite in tne area of fire protection / prevention.
Results
Of the areas inspected, no violations or deviations were identified.
d m
o I
l 8105050 MF
-
-a
-
.
.
.
REPORT DETAILS 1.
Persons Contacted Licensee Employees
- W. G. Hairston, III, Plant Manager J. D. Woodard, Assistant Plant Manager
-
- J. A Mooney, Project Manager /Constructio
- R. E. Hollands, QA Supervisor / Construction
- J. C. Bozeman, Project Engineer / Construction
- J. G. Hegi, Project QC Engineer / Construction
- D. E'Mansfield, Startup Superintendent
.
- E. L. Stephenson, Startup Supervisor
- K. W. McCrackin, Technical Superintendent / Production
- F. G. Watford, Fire Marshal
- J. W. Kale, Safety Audit and Engineering Review N. Hatton, Startup Engineer R. George, Licensing Supervisor
- E. Worden, Project Engineer Other 0rganizations R. L. Rowley, Bechtel - Systems Performance S. J. Ellis, Daniels - Project Manager E. R. Merrill, Daniels - Civil Mariager
>
D. L.. Garrison, Daniels - Quality Manager S. N. Pace, Daniels - QC Engineer Project Civil NRC Resident Inspector
- W. H. Bradford
- Attended exit interview 2.
Exit Interview The inspection scope and findings were summarized on February 27, 1981 with
,
those persons indicated in paragraph L above.
t 3.
Licensee Action on Previous Inspection Findings 39'
a.
(Closed) Unresolved Item (364/80-25-02):
Fire hose not provided for containment host stations. NRR memorandum of November 14, 1980, from l
!
V. Benaraya to S. E. Bryan, IE:HQ stated that the storage of fire hose outside the containment in lieu of providing fire hose at each connec-tion was approved during NRR's fire protection review. Therefore, this item is not a violation or deviation and is closed.
j
i l
'
l
.
'
.-.
_
.
.
.
_.
_
.
-
..
.
.
1
'
!
,
.
(0 pen) Unresolved Item (364/80-02-05): Substandard automatic sprinkler
!
b.
system. The licensee stated that a report was being prepared which
will identify areas in which the sprinkler systems deviate from the
!
code-provisions of National Fire-Protection Association Standard No.
_;
,
13, Automatic-Sprinkler Systems.
This report. will be sent by the
licensee t'o NRR for evaluation. ' This item will remain-open pending the l
results of NRR'.s review.
!
c.
(Closed) Deviation Item (364/80-42-01): Inadequate Fire Protection QA
'
Program.
The licensee basi conducted supplemental inspections with
!
appropriate documentation to verify that the -fire protection systems have been installed. in accordance with the design and construction documents. This item is closy.
!.
d.
.(Closed) Unresolved Item (364/80-42-02):
Installation and tests of fire protection systems are not complete. The operations startup and test program for all fire protectiorr systems is practically complete.
The licensee's QC/QA program appears adequate to assure that the fire protection features will be installed, inspected and tested prior to
'
fuel load. This item is not a violation or deviation and is closed.
!.
e.
(Closed) Unresolved Item (364/80-42-03):, Spray only type fire nozzles not provided for fire hose stations in cable tunnels. The licensee has
evaluated the use of the combination straight stream spray type nozzles
!
installed on the cable-tunnel fire hose system and advised that these i
nozzles are adequate for the type of potential' fires that could occur within the tunnels.
The fire brigade will be trained in the proper use of these type
nozzles. This action appears satisfactory.
This item is not con-sidered a violation or deviation and is closed.
'
i j
f.
(Closed) Inspector Followup Item (364/81-03-04):
Inadequate fire
~
barriers between fire pumps. The batteries and charger for Pump DFO-1 and the start-stop switch for pump EFP have been relocated into the closure for the specific pump unit. The power, control and starting circuits to the equipment which remains in the room enclosure for the other pump units have been installed in a fire rated enclosure.
4.
Unresolved Items
!
Unresolved items are matters 1 bout which more information is required to
-
i determine whether they are acceptable or may involve violations or devia-I tions. New unresolved items identified during this inspection are discussed-in paragraph 5.b.(27)
!
t
.
.
,
.'
5.
Fire Protection / Prevention Commitments and Modifications (Unit 2)
This inspection evaluated the licensee'a action on the fire protection commitments made to the NRC. The NRC Fire Protection Safety Evaluation Report (FPSER) which is Seciton 9.5 of the facility Safety Evaluation Report and the licensee's Farley Nuclear Plant Fire Protection Program Reevaluation (FPPR) dated September 15, 1977 with Amendments 1 through 4 were used in this evaluation. These documents describe the fire protection commitments,.
requirements and. schedule dates of implementation. The commitments and findings are as follows:
a.
Commitments Number Building / Location / Item Status Auxiliary Building 77' & 83" EL - Fire Area 1 (1)
Fire Detection Closed (2) Fire Hose Stations Closed (3)
Fire Door (1 ilour) - Rooms 2110/2115 & Stairs Closed (4)
Fire Door (3 Hour) Rooms 104 & 2104
- Not Inspected (5) CO2_ Hose Reel - Room 2161 Closed (6) Automatic Sprinkler Systems - Room 2223 Open Auxiliary Building 100' EL - Fire Area 4 (7) Fire Detection Closed (8) Automatic Sprinkler Systems - Rooms 2160, 2161, Open 2162, 2163 and 217!i (9) Fire Hose Station Closed (10) Dut t Shaft Enciare - Room 2215 Closed (11) Fire Door (1 Hour) - Room 2160 & Stairs Closed (12) Fire Door (3 Hour) - Between Units 1 & 2
- Not Inspected Auxiliary Building 100' EL - Fire Area 5 l
(13) Fire Detection Closed (14)' Automatic Sprinkler System - Roont 2177 Open Auxiliary Building 100' EL - Fire Area 6 a
.
(15)
Fire Detection (Except Room 2195)
Closed
l (16) Automatic Sprinkler Systems - Rooms 2167, 2185, Open l
2189, 2190, and 2194 l
(17) Heat Detectors; SKV Switch - Room 2185 Closed (18) CO2 System; SKV Switch - Room 2185 Closed (19) Fire Hose Stations Closed
!
--
..
..
,
,
Auxiliary Building 100' EL - Fire Area 6 (Continued)
(20)
Fire Doors (3 Hour) - Between Rooms 2185-2'198 Closed and 2197, 2185, and 2167 (21)
Fire Doors-(1h Hour) - Between Room 2185 &
Closed:
Stair 1 (22)
Fire Dampers - Duct Chase Open (23)- Curb (6-inch) - Between CCW Pumps Closed Auxilairy Building Cable Chase - Fire Area 8 (24)
Sprinkler System - Rooms 2116, 2197 & 2337 Open Closed (25)
Fire Detection
.
2337 - 2335 Closed.
(26)
Fire Door (3 Hour) - Between Rooms (27)
Cable Tray Fire Stops (20')
Open Auxiliary Building Cable Chase - Fire Area 9 (28) Sprinkler-System Rooms 2117, 2198, 2338, 2246, and 2344-Open (29) Fire Detection Closed
,
(30)
Fire Door-(3 Heur)
Closed (31) Cable Tray Fire Stops (20')
Open Auxiliary Building 121' EL-Fire Area 4 (32)
Fire Detection Closed (33)
Fire Hose Stations Closed (34) CO2 Mose Reel - Room 2209 Closed
-
(35)
Fire Doors (3 Hour) - Betweerr Rooms 205-2205 &
Open 207-2207 (36)
Fire-Doors (1h Hour) - Between Room 207 &
Closed l
Stairs, Room 209 & Stairs Auxiliary Buf1 ding 121' EL - Fire Area 12 l
(37) Open Sealed Door Between Room 2254 and Unit 1 Open
'
(38) Relocate-Selector Switches From Area 15 to Closed This Roce
,
l (39)
Fire Door (13 Hour) - Between Rooms 2210 & 2254 Closed a
j (40)
Fire Detection Closed m
I Auxiliary Building 128' EL - Fire Area 13 (41)
Fire Detection Closed (42) Sprinkler Systems - Rooms 2227, 2300, 2456 &
Open 2465
__
,
.
Auxilia y Building 121' EL - Fire' Area 15 (43) Fire Detection Closed (44) Halon System - Room 2202 Closed (45) Fire Doors (3 Hour) - Between Rooms 2202 & 2210 Closed (46) Relocate Selector Switches From One Train to Closed Fire Area 12
-
Auxiliary Building 121' EL - Fire Area 16 (47) Fire Detection Closed (48) Fire Door - Between Rooms 2212 & 2213 Closed (49) Fire Detection Closed (50) Fire Door (3 Hour) - Between Rooms 2213 & 2214 Closed (51) Fire Detection Closed (52) Fire Doors (3 Hour) - Between Rooms 2224 & 2225 Closed Auxiliary Building 121' EL - Fire Area 19 (53) Fire Detection Closed (54) Fire Doors (3 Hour) - Between Rooms 2225, P.226 &
Closed 2211 Auxiliary Buf1 ding 121 EL - Fire Area 20 (55)
Fire Detection Closed (56) CO2 Hose Reel - Room 2210 Closed (57)
Fire-Hose Station Closed (58)
Fire Doors (1 Hour) - Between Room 2234 &
Closed Stairs (59) Automatic Sprinkler Systems - Rooms 2210, 2211, Open 2213, 2228, 2234, 2244 and 2245 Auxiliary Building 121' EL - Fire Area 21 t
l (60)
Fire Detection Closed (61) Heat Detectors and CO2 System - 4.16 KV Swit >-
Closed gear, 5 KV Disconnect Switch, & Four 600 V Load Centers (62)
Fire Doors (3 Hour) - Between Rooms 2228-2229 &
Open 2228-2233 e
Auxiliary Building 121' EL - Fire Area 23
(63)
Fire Detection Closed (64) Halon System Open (65)
Fire Doors (3 Hour) - Between Rooms 2234-2235 &
Open 2233-2235 (66)
Fire Dampers (Operated by Halon System)
Open L
-- ___-_
'
.
.
.
Auxiliary Building 100'^& 121' EL - Fire Area 1
,
(67) Automatic Sprinkler System - Room 2233 Open (68) Fire Detection Closed (69)
Fire Door (1 Hour) - Between Rooms 2223 &
Closed Stairs Auxiliary Building 120' & 139' EL - Fire Area 30
.
(70) Fire Detection Closed i
'
(71) Automatic Sprinkler System (Cable Shaft)
Open (72) Fire Doors (3 Hour) - 120' & 139' Elevation Closed A wiliary Building 120' & 139' EL - Fire Area 31 i
?
(73)
Fire Detection Closed
,
(74) Automatic Sprinkler Systent - Cable Shaft Open (75) Fire Doors (3 Hour) 120' & 139' EL Closed i
. Auxiliary Building 139' EL - Fire Area 4 (76)
Fire Detection Closed (77)
Fie Hose Stations Closed (78) CO2 Hose Reel - Room 2312'
Closed (79)
Fire Doors (3 Hour) - Between Rooms 309 & 2309,
- Not Inspected
.
'
316 & 2316 (80)
Fire Doors (1 Hour) - Between Rooms 2322 &
Closed
,
.
Stairs, 2309 & Stairs
'
(81)
Fire Doors (3 Hour) - Between Rooms 2322 &'
Closed
,
2334 t
,
Auxiliary Building 139' EL - Fire Area 34 i
(82)
Fire Detection Closed
-
(83)
Fire Doors (3 Hour) - Between Rooms 2317 &
Closed 2322, 2334 & 2322, 2334 & 2333
.
Auxiliary Building 139' EL - Fire Area 35
(84)
Fire Detection Closed Auxiliary Building 155' - Fire Area 39 (85)
Fire Detection Closed (86)
Fire Doors (3 Hour) - Between Rooms 2459 & 2446 Closed i
l
'
l
l l
l i
_
_._ __
_
_.
_
. _ _ _. _. _
_
.i
.
,
.
Auxiliary Building 139'. - Fire A~ ea 40 r
(87) Automatic Sprinkler System - Room 2318 Open (88) Fire Detection Closed (89) Spray / Fireproof Structural Steel Closed (90) CO2 System - Manual Closed (91) Fire Doors (3 Hour) - Between Rooms 2318 & 2319 Closed Auxiliary B' ilding 139' EL - Fire Area 41 u
(92) Fire Detection Closed (93) Load Centers and Switchgear - Heat Detectors &
Closed CO2 Systent (94) Fire Doors (3 Hour) - Between Rooms 2335, &
- Closed 2339, 2343 & 2339, 2346 & 2339, 2335 & 2337-2338, 2343 & 2346, 2346 & 2249-2250 Auxiliary Building 139' EL - Fire Area 42 (95) Fire Detection Closed (96) Automatic Sprinkler System - Rooms 2319, 2339 &
Open 2345 (97) Fire Hose Stations Closed (98) Manual Fire Alarm System - Room 2319 Closed (99) Fire doors (14 Hour) - Between Rooms 2345 &
Closed Stairs Auxiliary Building 155' EL - Fire Area 4
.
(100) Fire Detection Closed (101) Load Centers in Rooms 2410A - Heat Detectors &
Closed
.
CO2 System
(102) Fire Hose Station Closed (103) CO2 Hose Reels - Rooms 2409 & 2415 Closed (104) Fire Doors (3 Hour) - Between Units 1 & 2
- Not Inspected
,
(105) Fire Doors (14 Hour) - Between Rooms 2432 &
Closed
,
Stairs and 2408 & Stairs
!
Auxiliary Building 155' EL - Fire Area 4 (106) Fire Detection Closed
_
'
Auxiliary Building 175' EL - Fire Area 51
'
(107) Fire Detection - Room 2501 Closed l
(108) Fire Hose Station Closed I
(109) Containment Fire Detection Closed
-
CTMT Coolers - 12 for each 4 units r
Steam Generators - 1 each
--
,
.
.,
__
_
, _. _ _ _. -.
-
-....,
.
.
l Auxiliary Building 175' EL - Fire Area 51
(Continued)
Duct Detectors - CTMT Vent Fans /2. each
-
Temperature Detectors in Filters
-
(110) Fire Hose Stations Closed (111) 011 Collection System for RCP Closed Auxiliary Building 100' EL - Fire Area 89
.
(112) 011 Storage Room
- Closed Dike
--
Fire Detectio'n
-
Dry Chemical System
-
Auxiliary Building - General
'
'
Closed (113) Emergency Lighting - 8 Hour Type (114) Portable Smoke Removal Equipment Closed (115) Delete Automatic Closure of Fire Main Closed Motor Operated Valve & Provide an Alarm Water Flow Set Point of 2700 gpm (116) Fire Extinguishers Open (117) Fire Dampers
- Closed (118) Fire Barriers for Cables
- Closed (119) Fire Doors Open Service Water Intake - Fire Area 72 Pump Room - Fire Area 72A
<
(120) Fire Detection Closed (121) Fire Barriers Between Pumps Closed (122) Automatic Water Spray System
- Closed Switchgear Rooms - Fire Areas 72 B & E (123) Fire Detection (Smoke)
Closed (124) Switchgear - CO2 System Closed (125) Fire Door (3 Hour) - Wall Penetrations Closed t
!
4KV Disconnect Switch - Fire Areas 72C & D c
(126) Fire Detection Closed
,
'
(127) Disconnect Switchgear Panel - Fire Detector &
Closed CO2 System l
l
[
,
_
. _ _ _. _, _ _ _ _. _.
_ _ -. _ ~ -... _ _ _ _. _
.
.
Battery Rooms - Fire Areas 73 & 74 (128) Fire Doors (3 Hour) - Wall Penetration Closed (129) Fire Extinguisher-Small Dry Chemical in Closed Adjacent Area Service Water Intake - General (130)
Fire Hydrant & Hose House Closed (131) Portable Smoke Removal Fan Closed Cable Tunnels - Fire Area 75 & 76 (132) Automatic Sprinkler System Closed (133)
Fire Door (3 Hour) - Generator Building Not Inspected
(134)
Fire Coating to Water Tight Door and Closed Bulkhead Into the Auxiliary Building (135)
Fire Hose Staticn - Between Generator Building Closed and Unit 2 Auxiliary Building Fire Pumps (136) Fire Wall Between Pumps Closed NOTES:
"Open" - Item is not satisfactory. Refer to paragrah 5.b for details.
" Closed"~ - Item at. pears to meet the commitments to the NRC based on random review cf documentation data and field inspection by the inspector.
- - Refer to paragraph 5.b for comments.
b.
Findings:
Additional information on the "Open" items and items marked "*" in paragraph 5.a is listed below. The below listed numbers correspond to the items in paragraph 5.a.
(4) The fire doors between Units 1 and 2 are secured in the closed
_
position and can not be inspected until after the perreanent plant
-
security system is operational. These doors are to be inspected by the licensee to assure that they are satisfactory.
l (6) The automatic sprinkler systems contain a number of discrepancies
'
from the provisions of NFPA-13. The licensee has identified these discrepaHes and is preparing a report which f s to be sent to NRC/NRR evaluation. Refer to above paragraph 3.b.
l l
-
y,
.y-
,-.p.m-S
,
e w
-
-+,--
,
.
.
(8) Refer to above item (6). Also, the combustible storage portion of Room 2160 is not provided with sprinkler protection although safety related electrical cables are in ad,Jacent areas.
The licensee is to evaluate this and to determine if sprinklers are actually required. This item is identified as Inspector Followup Item (364/81-08-01), sprinkler protection not provided for com-bustible storage area of Room 2160, and will be reviewed during a subsequent NRC inspection.
(12) Refer to above item (4).
(14) Refer to above item (6).
(16) Refer to above item (6).
(22) There are three unprotected openings into duct chase room 2236 from Room 2235. These have been identified by the licnesee and are to be sealed prior to fuel load or the compensatory measures required by the Technical Specification must be applied.
This
.
item is identified as Inspector Followup Item (364/81-08-02)
unprotected openings into duct chase Room 2236 from Room 2235, and will be reviewed during a subsequent NRC inspection.
(24) Refer to above item (6).
(27) The cable tray fire stops have not been provided.
Based on the licensee's evaluation the fire stops are not required due to fire protection features provided within the cable chase. This item is being forwarded to NRR for review and is identified as Unresolved Item (364/81-08-03), fire stops not provided for cable chase.
This item will be reviewed during a subsequent NRC inspection.
(28) Refer to above item (6).
(31) Refer to above item (27).
(35) Refer to above item (4).
(37) This door will be opened when the security plan for Unit 2 is activated. Refer also to above item (4).
(42) Refer to above item (6).
(59)
Refer to above item (6). Also, automatic sprinkler protection was l
not provided for Rooms 2228 and 2234 as stated in Table 3 of the i
FPSER. The licensee is investigating this item to determine why these systems were not installed.
This item is identified as Unresolved Item (364/81-08-06), Sprinkler Protection not provided for Rooms 2228 and 2234 This item will be reviewed during a subsequent NRC inspection.
l
<
?
.
.
(62) One of the fire doors between rooms 2228 and 2233 and one of the t
fire doors between rooms 2234 and 2235 are not approved or listed
!
.
fire doors but appear to meet the construction features of
!
!
approved fire doors. The licensee is evaluating this problem to (
determine if the existing doors are adequate or need to be
replaced. Refer to item (119) below.
!
'
.
[
-
(64) Refer to. item (66) below.
(65) Refer to below item (119).
{
!
(66) The halon system will not maintain the required design concen-tration within room 2235 due to leakage through fire dampers. The t
fire dampers automatically close upon operation of the halon
-
system but apparently do not close tightly.
The fire damper
!
,
manufacturer has recommended that the existing spring closing device be replaced with a different type spring.
This change.
should correct the problem. The licensee advised that this change t
will be made and system retested prior to fuel load. This item is identified as Inspector Followup Item 364/81-08-05), inadequate
'
,
j closing of fire dampers for Room 2235 halon fire extinguishing l
system, and will be reviewed during a subsequent NRC inspection.
l Also, refer to paragraph 5.d.(4) below.
l (67) Refer to above item (6).
'
(71) Refer to above item (6).
l (74) Refer to above item (6).
(79) Refer to above item (4).
,
.
(87) Refer to above item (6).
!
(94) Two of the fire doors between Rooms 2339 and Rooms 2343 and 2346 are not listed or approved fire doors. The licensee is evaluating these doors to determine if the doors are adequate or need to be changed. Refer to item (119) below.
,
(96) Refer to above item (6).
-
(104) Refer to above item (4).
,
(112) The dry chemical system for the oil storage room is activated by fixed temperature detectors in lieu of a smoke detector system as described in the FPPR. The licensee stated that the FPPR was to be revised to describe this current arrangement.
l i
!
!
i i
!
.,
,
._
. _. - -. _. - -..
.. _ _ _ _ _
.
~ -.. - -
-
.
..
-
..
.
.-
.
'
.
,
!
(116) Most of the portable fire extinguishers. for the plant have not been installed. However, the mounting brackets have been instal--
!
'
led. The licensee advised that the extinguishers are in storage j
at the site and will be installed as each room is turned over to
!
- the plant.
!
(117) An inspection was made of all fire damper installations by the
contractor's QC group.
This inspection was audited by the l
,
licensee's construction QA group.
Inspection records indicate
.
that all fire dampers were installed in accordance with the l
manufacturer's installation criteria.
>
,
(118) Refer to paragraph 5.c.
J l
(119) The licensee is currently re-evaluating 18 doors installed
j throughout Unit 2 to determine if they meet the commitments to the i
NRC and are satisfactory or need to be changed.
These doors
,
include a total gof 13 security and water tight doors and 5 doors
.
provided with a removable transus. The existing doors provide a
!
!
l fire stop in the fire barriers but the exact fire resistance
!
rating of these doors is not known.
This ' item is identified as
!
Inspector Followup Item (364/81-08-04), licensee's evaluation of l
unlisted or approved fire doors, and will be inspected during a
subsequent NRC inspection.
j
.
l (122) The service water pumps are provided with an automatic closed head j
water spray system. This system will probably be of slow response
in the event of a motor or pump fire since the sprinkler heads are j
'
located an excessive distance below the ceiling or roof of the
building and are not provided with heat collectors as required by l
NFPA-13. This problem was identified to the licensee in IE Report i
!
Nos. 50-348/80-03 and 50-364/80-03 and to NRP by NRC/IE interof-fice memorandum.
NRR's memorandum response af August 18, 1980, i
from V. Benarcya to S. E. Bryan, IE:HQ advised that the existing i
'
system was satisfactory and was recommended during NRR's fire j
protection site visit.
Since this item is acceptable to NRR no i
further action will be taken by NRC Region II to correct this
discrepancy.
i (132) Refer to above item (4).
i
!
'
c.
Electrical Cable Separation
- y The inspector reviewed the construction drawings and cable pull cards i
'
for the following electrical circuits.
!
!
2 VAFA-H4R No. A Auxiliary Feed Water Pump - Ventilation Fan
!
2 VBFB-G5P No. B Auxiliary Feed Water Pump - Ventilation Fan
}
.
2 VADF-04P Component Cooling Water Pump A - Power Supply j
l 2 VBDG-04P Component Cooling Water Pump B - Power Supply
'L i
t i
!
!
[
'
!
e t
i
.
,
,.
,
The redundant circuit for these two system's were installed on separate floor elevations or in separate cable shafts, except on the 100 foot elevation where the circuits of redundant train are located within 20 feet of each other, but are provided with a fire rated barrier. This arrangement meets the requirements of FPSER.
d.
Startup and Test Inspection and Data The following inspection and test data prepared by the licensee's startup and test group was reviewed by the inspector:
(1) Procedure 013-3-001, Functional Test for Smoke Detection and Sprinkler Actuation System:
Inspection and tests were approximately 99% complete with full completion scheduled for March 2,1981.
(2) Procedure 013-3-005, Wet Pipe Automatic Sprinkler Systems:
,
Inspection and tests were completed on January 27, 1981, but data had not been reviewed and approved by the-startup supervisor.
(3) Procedure 013-3-006, CO2 System Functionai Tests Tests were completed on January 13, 1981, but data had not been reviewed and approved by the startup supervisor.
'
(4) Procedure 013-3-007, Halon Functional Tests The system for the hot shutdown control room was completed on February 4,1981 but the system for the CRDM switchgear room had not satisfactorily passed the required concentration tests. The system will function properly but the fire dampers into the room will not close tight enough to prevent loss of the halon gas.
A Design Change Notice (CN-2BM-4266), has been issued which will require the fire dampers to be equipped with a difierent type closure spring which should keep the dampers shut when they are supposed to be in the closed position. Refer to above paragraph 5.b.(66).
(5) Procedure 013-3-011, Fire Protection System Flush
The tests were completed on November 18, 1980, but the test data had not been reviewed and appro' fed by the startup supervisor.
(6) Procedure 013-3-012, Functional Test for Wet /Preaction Sprinkler Systems
_ -. _. -
._
.
-
.
.
-..
..
_
-
e
.
.
l l
The tests were completed on January 27, 1981 and approved by the
,
startup supervisor on February 26, 1981.
Within the areas examined, no violations or deviations were identified.
.
J
- * *
-
e
-