CATEGORY1REGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)ACCESSIONNBR:9801140201DOC.DATE:98/01/02NOTARIZED:YESFACIL:50-335St.LuciePlant,Unit1,FloridaPowerEcLightCo.~~~~~~~-50-389St.LuciePlant,Unit2,FloridaPower&LightCo.AUTH.NAMEAUTHORAFFILIATIONPLUNKETT,T.F.FloridaPowertLightCo.RECZP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)

SUBJECT: Respondstoviolationsnotedininsprept50-335/97-15&50-389/97-15.Correctiveactions:completedtemporarysysalterationthatreversedtwoofthreepowerleadstolowspeedwindingoffanmotoratmotorcontrolcenter.DISTRIBUTIONCODE:IE01DCOPIESRECEIVED:LTRENCLSIZE:TITLE:General(50Dkt)-InspRept/NoticeofViolationResponseNOTES:DOCKET0500033505000389ERECIPIENTZDCODE/NAMEPD2-3PDNRR/DRPM/PECBNUDOCS-ABSTRACTOGC/HDS3XTERNAL:LITCOBRYCE,Q'NRCPDRCOPIESLTTRENCL112211111111111111RECIPIENTIDCODE/NAMEWIENS,L.AEOD/SPD/RABDEDRONRR/DRCH/HHFBNRR/DRPM/PERBOEDIRRGN2FILE01NOACNUDOCSFULLTEXTCOPIESLTTRENCL111111111111111111D0UNOTETOALL"RIDS"RECIPIENTS:PLEASEHELPUSTOREDUCEWASTE.TOHAVEYOURNAMEORORGANIZATIONREMOVEDFROMDISTRIBUTIONLISTSORREDUCETHENUMBEROFCOPIESRECEIVEDBYYOUORYOURORGANIZATION,CONTACTTHEDOCUMENTCONTROLDESK(DCD)ONEXTENSION415-2083TOTALNUMBEROFCOPIESREQUIRED:LTTR19ENCL19 FloridaPower5LightCompany.6351S.OceanDrive,JensenBeach,FL34957January2,1998L-97-32210CFR$2.201U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555Re:St.LucieUnits1and2DocketNos.50-335and50-389ReplytoaNoticeofViolationNRecialInsectionReort97-15FloridaPowerandLightCompany(FPL)hasreviewedthesubjectNoticeofViolationand,pursuantto10CFR$2.201,theresponsestotheviolationsareattached.FPLacknowledgesthatthecitedviolationsrelatedtotheinoperablecontainmentfancoolersareofsignificantregulatoryconcern.Asdescribedintheviolationresponse,FPLhastakencomprehensivecorrectiveactionstoresolvetheidentifiedcondition,andhasreviewedtheeventforgenericimplications.Inthiscontext,FPLappreciatesNRC'srecognitionofthequestioningattitudeexhibitedbySt.Luciepersonnelintheidentificationoftheinoperablecontainmentfancoolerandthetimelyandcomprehensivecorrectiveactionstaken.FPLisoptimisticthatthebehaviordemonstratedbythepersonnelthatidentifiedthefancoolertestingdeficiencyisindicativeoftheculturalchangesencouragedbySt.Luciemanagement.Pleasecontactuswithquestionsontheenclosedviolationresponses.Verytrulyyours,ThomasF.PlunkettPresidentNuclearDivisionTFP/JAS/EJWAttachmentcc:RegionalAdministrator,USNRC,RegionIISeniorResidentInspector,USNRC,St.LuciePlant980%140201980102PDRADOCKOS00033SPDRIIIIIIIIIIIII/IIIIIIIIIIIIIIII/IIIIIIIanFPLGroupcompany St.LucieUnits1and2~~~DocketNos.50-335and50-389L-97-322Page2STATEOFFLORIDA))COUNTYOFPALMBEACH)ss.ThomasF.Plunkettbeingfirstdulysworn,deposesandsays:ThatheisPresident,NuclearDivision,ofFloridaPower&LightCompany,theLicenseeherein;Thathehasexecutedtheforegoingdocument;thatthestatementsmadeinthisdocumentaretrueandcorrecttothebestofhisknowledge,informationandbelief,andthatheisauthorizedtoexecutethedocumentonbehalfofsaidLicensee.ThomasF.PlunkettSTATEOFFLORIDACOUNTYOFSworntoandsubscribedbeforemethis'dayof/~~M,1997byThomasF.Plunk6tt,whoisrsonallyknowntome.Name+go~~oridapIIYPOi&F'CiALtiOTARYSEALOi~COc":nNICnMGALINIS0OOuueaONRuuOSR)l~i)(IXICOidMSSIONEXPIRESOi:RPSFPT10,2001Print,typeorstampCommissionedNameofNotaryPublic)

L-97-322AttachmentP~g1~ViolaioATechnicalSpecification3.6.2.1statesthattwocontainmentspraytrainsandtwocontainmentcoolingtrainsshallbeOPERABLE.Contrarytotheabove,betweenMay16,1997andOctober8,1997,whileoperatinginModes1,2,and3,oneUnit2containmentcoolingtrainwasinoperable.R~g~ny1.FPLconcurswiththeviolation.2.REASONFORVIOLATIONThisviolationwascausedbyboth:a)personnelerrorduringpostmaintenancetestingactivitiesassociatedwithcontainmentcoolingfan2-HVS-1D;and,b)aninadequate31dayTechnicalSpecificationsurveillanceprocedure.Thesedeficienciescontributedtoreturningcontainmentcoolingfanunit2-HVS-1Dtoservicewhenitwasunabletoperformitsemergencymodeofoperationduetoreverseslowspeedoperation.CausesandcorrectiveactionsassociatedwiththeabovearediscussedinFPL'sresponsestoviolationsBandC,respectively.Thelowflowalarmfor2-HVS-1Dwasnotdocumentedduringtheperiodic18monthtestoftheengineeredsafetyfeaturesbecausethecontainmentfancoolerunitwasoutofserviceduringthetest.Althoughtheproceduralrequirementsfordocumentingactionstobetakentoresolveannunciatorsreceivedduringtheperformanceofsafeguardstestingwereweak,thistestwasnotamissedopportunityfordiscoveringthat2-HVS-1Dwasinoperableduringtheemergencymodeofoperation.3.CORRECTIVESTEPSTAKENANDTHERESULTSACHIEVEDFPLenteredtheapplicableTechnicalSpecificationACTIONstatementswhenthelowflowalarmswerereceivedduringinitialandsubsequentcontainmentfancoolerslowspeedtestingonOctober6andOctober7,1997.Thereverseslowspeedoperationwascorrectedbyimplementingatemporarysystemalterationthatreversedtwoofthethreepowerleadstothelowspeedwindingofthefanmotoratthemotorcontrolcenter.Thisactionwascompletedwithintheallowedoutagetimeforinoperablecontainmentfancooler(s).Containmentfancoolerunit2-HVS-1DwasreturnedtoserviceonOctober9,1997,afterproperoperationoftheunitwasverifie L-97-322AttachmentP~ae24.CORRECTIVESTEPSTOAVOIDFURTHERVIOLATIONSFPLrevisedsurveillanceoperatingprocedure1-0400050,"PeriodicTestoftheEngineeredSafetyFeatures,"toenhancethedispositionofannunciatorsthatarereceivedduringtheperformanceoftheIntegratedSafeguardsTest.Thisrevisionincludesanewappendixusedtotrackanddispositionannunciatorsthatoccurduringthetest.ThisrevisiontotheUnit1procedurewascompletedonNovember18,1997.B.TheUnit2Safeguardsprocedure,2-0400050,willberevisedtoincludethenewannunciatorresponseappendixpriortoperformingsafeguardstestingduringtheUnit21998refuelingoutage(SL2-11).FullcompliancewasachievedonOctober9,1997,whencontainmentfancoolerunit2-HVS-IDwasreturnedtoservic L-97-322AttachmentP~ae3VIolation810CFR50,AppendixB,CriterionV,Instructions,ProceduresandDrawings,requires,inpart,thatactivitiesaffectingqualityshallbeprescribedbydocumentedproceduresofatypeappropriatetothecircumstancesandshallbeaccomplishedinaccordancewiththoseprocedures.MaintenanceProcedure(MP)2-0950173,Revision9,"TheOverhaulofContainmentFanCoolersMotors2HVS-lA,1B,1C,1D(EQMotors),"Section9.9,implementsthepostmaintenancechecksofthecontainmentfancoolermotorsaftermaintenance.MP2-0950173requiresthefantobestartedinslowandfastspeedtoverifyproperbladerotationineachspeed.Contrarytotheabove,onMay16,1997,thelicenseefailedtoperformSection9.9ofMaintenanceProcedure2-0950173properlyinthatcontainmentfancooler2-HVS-1Dwasnotstartedinslowspeedandproperbladerotationwasnotverified.~Reaone1.FPLconcurswiththeviolation.REASONFORVIOLATIONThecausefortheviolationwaspersonnelerrorthatoccurredduringtheexecutionofpostmaintenancetestingperformedduringthelastUnit2refuelingoutage.Thiserrorresultedinreverserotationofcontainmentfancooler2-HVS-1D.TherootcauseevaluationconcludedthattheimpropertestexecutiononMay16,1997,wascausedbyfaultycommunicationsbetweenthemaintenancepersonnelassessingfanrotationinsidecontainmentandthecontrolroomoperatorwhostartedthefan.FPLreviewedthecompleteddocumentationfortheMay16,1997,postmaintenancetestandcompareditagainsttheMay16,1997,Unit2controlroomsequenceofeventsrecorder(SER).TheSERshowedthat2-HVS-1Dwasstartedtwiceduringthepostmaintenancetesting;however,boththeslowandfastspeedrotationalcheckswereperformedwiththemotoroperatinginfastspeed.Thefactthattwomotorstartsweredoneimpliesthatmaintenancepersonnelwerecorrectlyfollowingthetestproceduresteps.Theproperuseofthreewaycommunications,asrequiredbyboththeConductofMaintenanceandConductofOperationspolicies,wouldhavepreventedthefaultycommunicationwhichledtotheunsatisfactoryexecutionofthepostmaintenancetes L-97-322AttachmentP~ae43.CORRECTIVESTEPSTAKENANDTHERESULTSACHIEVEDA.ProcedureMP-2-0950173,"TheOverhaulofContainmentFanCoolerMotors2-HVS-lA,1B,1C,1D(EQMotors),"wasrevisedtorequirethefollowing:1)verificationsignaturesforbothfastandslowspeedmotorrotationtesting;2)acautionstatementtoensurethatbothwindingsareenergizedtoverifypropermotorrotationsubsequenttoelectricallyreconnectingthemotor;3)anaddendumsheetthatwillbeusedbythecontrolroomoperatorstofollowtheperformanceofthemotorrotationchecks;and,4)arequirementtoperformafunctionaltestofthecontainmentfancoolerinbothfastandslowspeedpriortoreturningtheunittoservice(i.e.,nolowflowalarmspresentduringrotationchecks).TheprocedurerevisionswerecompletedonNovember28,1997.AdditionaleditorialclarificationsweresubsequentlyaddedandapprovedonDecember17,1997.4.CORRECTIVESTEPSTOAVOIDFURTHERVIOLATIONSA.Thisspecificevent,includingtheimportanceofaccuratecommunicationsandtheuseofthreewaycommunications,wasincludedinaMaintenancetrainingbulletinthatwasissuedonNovember22,1997.B.ProcedureADM-78.01,"PostMaintenanceTesting,"willberevisedtoaddacautionnoteabouttestingmultiplespeedormultiplewindingmotorsbyJanuary31,1998.5.FullcompliancewasachievedonNovember28,1997,whentheprocedurerevisionstoMP-2-0950173,"TheOverhaulofContainmentFanCoolerMotors2-HVS-1A,1B,1C,1D(EQMotors),"werecomplete L-97-322AttachmentP~s5ViolationC10CFR50,AppendixB,CriterionXI,TestControl,requires,inpart,thatatestprogramshallbeestablishedtoassurethatalltestingrequiredtodemonstratethatcomponentswillperformsatisfactorilyinserviceisidentifiedandperformedinaccordancewithwrittentestprocedurewhichincorporatetherequirementsandacceptancelimitscontainedintheapplicabledesigndocuments.FinalSafetyAnalysisReportSection6.2.2.2.2statesthatthefancoolersoperateatareducedflowof39,600cubicfeetperminuteeach,withlowspeedmotoroperationduringaccidentoperation.NormalOperatingProcedure,NOP-2-2000020,Revision2,"ContainmentCoolingSystemOperation,"whichimplementsmonthlysurveillancetestingofthecontainmentfancoolers,requiresthateachcoolingtrainfanunitbestartedfromthecontrolroomandverifiedthateachunitoperatesforatleast15minutes,atleastonceper31days.Contrarytotheabove,asofOctober6,1997,thelicenseefailedtoassurethatalltestingrequiredtodemonstratethatcomponentswillperformsatisfactorilyinservice,inaccordancewiththerequirementsandacceptancelimitscontainedintheapplicabledesigndocuments,wasidentifiedandperformed.Specifically,NOP-2-2000020,didnotrequirethecontainmentcoolerfanstobetestedinslowspeed,whichisthealignmentrequiredduringemergencyoperation.Thisproceduralinadequacyhadexistedsinceinitialplantoperation.R~esense1.FPLconcurswiththeviolation.2.REASONFORVIOLATIONThecausefortheviolationwasnon-cognitivepersonnelerrorduringthedevelopmentofsurveillanceprocedureNOP2-2000020,"ContainmentCoolingSystemOperation,"thatresultedinthesurveillanceproceduredeficiency.Theprocedure,asitwaswritten,didnotmeettheintentoftheTechnicalSpecificationsurveillancerequirementsbecauseitrequiredtestingofthecontainmentcoolerfansonlyinthefastspeed,anddidnotrequireverificationofthepost-accidentsafetyrelatedfunctionofthefansinslowspee L-97-322AttachmentP~ae63.CORRECTIVESTEPSTAKENANDTHERESULTSACHIEVEDProcedureNOP2-2000020,"ContainmentCoolingSystemOperation,"wasrevisedandissuedonOctober13,1997.Therevisionclearlyrequiresthatallfansmustbestartedandruninslowspeed.Onceallfourfanshavebeenshiftedtoslowspeed,theabsenceofanylowflowalarmsthroughoutthe15minuteruntimeconstitutessatisfactorycompletionofthesurveillancetest.Theprocedurealsorequiressatisfactoryfastspeedoperationofthecontainmentfancoolers.B..FPLinvestigatedthegenericimplicationsofthiseventtodeterminewhatotherequipmenttypesmaybesubjecttoinadequatesurveillances.Thereviewrevealedthat,withtheexceptionofheating,ventilating,andairconditioning(HVAC)equipment,additionalrequirements(e.g.,ISUISTrequirementsandindustrystandards)existwhichenhancethedevelopmentofsurveillanceprocedures.AllHVACproceduresusedtoperformTechnicalSpecificationsurveillanceswerereviewedtoensuretheintentoftheTechnicalSpecificationsurveillanceweremet.ThisreviewwascompletedonNovember24,1997.4.CORRECTIVESTEPSTOAVOIDFURTHERVIOLATIONSFPLQualityInstruction(QI)QI-S-PSL-1,"Preparation,Revision,Review/ApprovalofProcedures,"Section5.5requiresthatsiteproceduresbeperiodicallyreviewed.ThisQIwasrevisedtorequireaqualifiedindependentreviewofproceduresthataFectsurveillancesorteststoensurethattheprocedureadequatelyimplementstheintentofUpdatedFinalSafetyAnalysisReport(UFSAR)surveillancedescriptionsandTechnicalSpecificationsurveillancerequirementswhenprocedureperiodicreviewsareconducted.ThisrevisionwasapprovedonNovember28,1997.5.FullcompliancewasachievedonOctober13,1997,whentherevisiontoprocedureNOP2-2000020,"ContainmentCoolingSystemOperation,"wasapproved.