IR 05000315/2002006
| ML023030330 | |
| Person / Time | |
|---|---|
| Site: | Cook (DPR-058, DPR-074) |
| Issue date: | 10/28/2002 |
| From: | Anton Vegel Division Reactor Projects III |
| To: | Bakken A American Electric Power Co |
| References | |
| IR-02-006 | |
| Download: ML023030330 (65) | |
Text
October 28, 2002
SUBJECT:
D. C. COOK NUCLEAR POWER PLANT, UNITS 1 AND 2 NRC INSPECTION REPORT 50-315/02-06(DRP); 50-316/02-06(DRP)
Dear Mr. Bakken:
On September 30, 2002, the NRC completed an inspection at your D. C. Cook Nuclear Power Plant, Units 1 and 2. The enclosed report documents the inspection findings which were discussed on October 2, 2002, with Mr. J. Pollock and other members of your staff.
This inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.
The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.
Based on the results of this inspection, one finding whose significance is to be determined was identified (Section 4OA3.2). This issue was determined to be a violation of NRC requirements and is considered to be an unresolved item pending a final safety significance determination.
The NRC has increased security requirements at the D. C. Cook Nuclear Power Plant in response to terrorist acts on September 11, 2001. Although the NRC is not aware of any specific threat against nuclear facilities, the NRC issued an Order and several threat advisories to commercial power reactors to strengthen licensees capabilities and readiness to respond to a potential attack. The NRC continues to monitor overall security controls and will issue temporary instructions in the near future to verify by inspection the licensees compliance with the Order and current security regulations.
In accordance with 10 CFR 2.790 of the NRCs "Rules of Practice," a copy of this letter and its enclosures will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
A. We will gladly discuss any questions you have concerning this inspection.
Sincerely,
/RA/
Anton Vegel, Chief Branch 6 Division of Reactor Projects Docket Nos. 50-315; 50-316 License Nos. DPR-58; DPR-74
Enclosure:
Inspection Report 50-315/02-06(DRP);
50-316/02-06(DRP)
REGION III==
Docket Nos:
50-315; 50-316 License Nos:
50-315/02-06(DRP); 50-316/02-06(DRP)
Licensee:
Indiana and Michigan Electric Company Facility:
D. C. Cook Nuclear Power Plant, Units 1 and 2 Location:
1 Cook Place Bridgman, MI 49106 Dates:
July 1, 2002 through September 30, 2002 Inspectors:
B. Kemker, Senior Resident Inspector D. Passehl, Senior Project Engineer S. Orth, Senior Project Engineer R. Lerch, Senior Project Engineer P. Pelke, Project Engineer A. Dunlop, Reactor Engineer I. Netzel, Reactor Engineer G. ODwyer, Reactor Engineer R. Winter, Reactor Engineer W. Slawinski, Senior Radiation Specialist Approved by:
A. Vegel, Chief Branch 6 Division of Reactor Projects
Table of Contents
SUMMARY OF FINDINGS
.................................................... 3
Summary of Plant Status:..................................................... 4 1.
REACTOR SAFETY...................................................4 1R04 Equipment Alignment............................................. 4 1R05 Fire Protection.................................................. 5 1R06 Flood Protection Measures........................................ 6 1R11 Licensed Operator Requalification................................... 7 1R12 Maintenance Effectiveness........................................ 7 1R13 Maintenance Risk Assessments and Emergent Work Evaluation........... 8 1R15 Operability Evaluations
........................................... 9 1R16 Operator Workaround........................................... 10 1R17 Permanent Plant Modifications..................................... 10 1R19 Post Maintenance Testing........................................ 11 1R20 Refueling and Outage Activities.................................... 12 1R22 Surveillance Testing............................................. 12 1R23 Temporary Plant Modificaitons..................................... 13 1EP6 Drill Evaluation................................................. 14 2.
RADIATION SAFETY................................................. 14 2OS1 Access Controls to Radiologically Significant Areas..................... 14 2OS3 Radiation Monitoring Instrumentation and Protective Equipment........... 16 2PS1 Radioactive Gaseous and Liquid Effluent Treatment and Monitoring Systems
3.
SAFEGUARDS...................................................... 22 3PP3 Response to Contingency Events.................................. 22 4.
OTHER ACTIVITIES.................................................. 23 4OA1 Performance Indicator Verification.................................. 23 4OA3 Event Follow-up................................................ 25 4OA6 Management Meetings........................................... 31 KEY POINTS OF CONTACT................................................. 32 LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED............................ 33 LIST OF ACRONYMS USED................................................. 34 LIST OF DOCUMENTS REVIEWED
........................................... 35
SUMMARY OF FINDINGS IR 05000315-02-06(DRP), IR 05000316-02-06(DRP), on 07/01/2002-09/30/2002, Indiana and Michigan Electric Company, D. C. Cook Nuclear Power Plant, Units 1 and 2. Event Follow-up.
This report covers a 12-week period of inspection by resident and region based inspectors.
The radioactive gaseous and liquid effluent treatment and monitoring program inspection was conducted by a regional senior radiation specialist. The inspectors identified one finding, which is an apparent violation whose significance is to be determined. The significance of most findings is indicated by their color (Green, White, Yellow, Red) using Inspection Manual Chapter 0609, "Significance Determination Process," (SDP). The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG 1649, "Reactor Oversight Process," Revision 3, dated July 2000.
A.
Inspector Identified Findings
Cornerstone: Initiating Events
TBD. An Apparent Violation of 10 CFR 50, Appendix B, Criterion V,
"Instructions, Procedures, and Drawings," was self-revealed. The licensee failed to provide an appropriate procedure for testing the Unit 1 pressurizer power operated relief valves (PORVs), causing an uncontrolled release of reactor coolant system inventory to the pressurizer relief tank. This issue was self-revealed on June 5, 2002, when pressurizer PORV 1-NRV-153 inadvertently opened while testing actuation logic circuitry for pressurizer PORV 1-NRV-151.
The surveillance test procedure failed to provide adequate control of 1-NRV-151 and 1-NRV-153, which have a common automatic opening signal. The release rate exceeded the 25 gallons-per-minute limit established for declaring an Unusual Event in accordance with the licensees Emergency Plan.
The inspectors assessed this finding using the Significance Determination Process. The inspectors concluded that this issue could be reasonably viewed as a precursor to a significant event and was therefore more than a minor concern. The inspectors also concluded that this finding was associated with the initiating events cornerstone and adversely affected the cornerstone objective.
Specifically, the uncontrolled release of reactor coolant system inventory upset plant stability and challenged the inventory control safety function. The inspectors determined that the unit was in a configuration where a single active failure or personnel error could have resulted in a rapid loss of reactor coolant system inventory and therefore required a Phase 2 SDP analysis for shutdown risk. The safety significance of this finding is "To Be Determined" (TBD) pending the completion of additional staff review. (Section 4OA3.2)
Licensee Identified Violations
None
REPORT DETAILS
Summary of Plant Status:
Unit 1 operated at or near full power during this inspection period.
Unit 2 operated at or near full power during this inspection period with the following exceptions:
On July 22, 2002, Unit 2 experienced an automatic reactor trip when the main turbine tripped due to a low condenser vacuum while cycling circulating water isolation valves on the main condenser for waterbox debris flushing. The main steam isolation valves were shut after the trip to arrest an excessive reactor coolant system cooldown due to auxiliary steam loads. The licensee performed a reactor startup and synchronized the unit to the grid on July 23, 2002.
On July 27, 2002, the licensee performed a reactor shutdown to replace a circulating water pump discharge valve that had failed closed. Following the replacement of the valve and some additional forced outage maintenance activities, the licensee performed a reactor startup and synchronized the unit to the grid on August 3,
REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity
1R04 Equipment Alignment
.1 Partial System Walkdowns
a. Inspection Scope
The inspectors performed partial system walkdowns of the following risk-significant systems:
Initiating Events Cornerstone
Unit 2 West Component Cooling Water System Train
Unit 2 CD Emergency Diesel Generator Mitigating Systems Cornerstone
Unit 2 West Charging and Safety Injection System Train
Unit 1 West Residual Heat Removal System Train The inspectors selected these systems based on their risk significance relative to the reactor safety cornerstones. The inspectors reviewed operating procedures, Technical Specification (TS) requirements, Administrative Technical Requirements, system diagrams, and the impact of ongoing work activities on redundant trains of equipment in order to identify conditions that could have rendered the systems incapable of performing their intended functions. The inspectors also walked down accessible portions of the systems to verify system components were aligned correctly.
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for equipment alignment related issues documented in selected condition reports (CRs).
b. Findings
No findings of significance were identified.
.2 Complete System Walkdown
a. Inspection Scope
The inspectors performed a complete system walkdown of the following risk-significant system:
Mitigating Systems Cornerstone
Unit 1 and 2 Essential Service Water (ESW) System The inspectors reviewed ongoing system maintenance, open job orders, and design issues for potential effects on the ability of the ESW system to perform its design functions. The inspectors ensured that the configuration of the system was in accordance with applicable operating procedure checklists. The inspectors verified acceptable material condition of system components, availability of electrical power to system components, and that ancillary equipment or debris did not interfere with system performance.
b. Findings
No findings of significance were identified.
1R05 Fire Protection
.1 Routine Resident Inspector Tours
a. Inspection Scope
The inspectors performed fire protection walkdowns of the following risk-significant plant areas:
Initiating Events Cornerstone
Unit 1 Engineered Safety Features (ESF) Motor Control Center Room (Zone 41)
Unit 2 ESF Motor Control Center Room (Zone 45)
Mitigating Systems Cornerstone
Unit 1 "N" Train Battery Room (Zone 106)
Unit 2 "N" Train Battery Room (Zone 107)
Unit 1 Turbine Driven Auxiliary Feedwater Pump Room (Zone 17E)
Unit 2 Turbine Driven Auxiliary Feedwater Pump Room (Zone 17F)
Unit 2 Auxiliary Feedwater Corridor (Zone 17C)
Unit 1 East Main Steam Valve Enclosure (Zone 33)
Unit 2 West Main Steam Valve Enclosure (Zone 34)
Unit 1 AB Emergency Diesel Generator Room (Zone 16)
Unit 2 AB Emergency Diesel Generator Room (Zone 19)
The inspectors verified that fire zone conditions were consistent with assumptions in the licensees Fire Hazard
Analysis.
The inspectors walked down fire detection and suppression equipment, assessed the material condition of fire control equipment, and evaluated the control of transient combustible materials.
b. Findings
No findings of significance were identified.
1R06 Flood Protection Measures
a. Inspection Scope
The inspectors reviewed and assessed flood protection measures for internal flooding events. The inspectors evaluated whether the licensee took appropriate precautions to mitigate the risk from internal flooding events. Specifically, the inspectors performed the following:
reviewed the Updated Final Safety Analysis Report (UFSAR) and other selected design basis documents to identify those areas susceptible to internal flooding;
reviewed the licensees probabilistic risk analysis and associated flood protection reports to identify risk significant flood areas and protective features;
reviewed abnormal and alarm response procedures associated with the diagnosis and mitigation of flooding events;
performed a walkdown of the Turbine Building sub-basement, the auxiliary feedwater pump area, the emergency diesel generator rooms, the refueling water storage tank pipe tunnels, the Auxiliary Building sub-basement, and the ESW system pipe tunnel to evaluate whether appropriate flood protection controls were being maintained;
reviewed selected station operating procedures used to identify and mitigate internal flooding events; and
interviewed selected operating and engineering staff regarding internal flooding protection controls.
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for flood protection related issues documented in selected CRs.
b. Findings
No findings of significance were identified.
1R11 Licensed Operator Requalification
.1 Resident Inspector Quarterly Review
a. Inspection Scope
The inspectors assessed licensed operator performance and the training evaluators critique during licensed operator annual requalification evaluations in the D.C. Cook Plant operations training simulator on August 13, 2002 and September 24, 2002. The inspectors focused on alarm response, command and control of crew activities, communication practices, procedural adherence, and implementation of emergency plan requirements.
b. Findings
No findings of significance were identified.
1R12 Maintenance Effectiveness
a. Inspection Scope
The inspectors evaluated the licensees handling of selected degraded performance issues involving the following risk-significant structures, systems, and components (SSCs):
Mitigating Systems Cornerstone
Auxiliary Feedwater System
600 Volt Alternating Current Safety-Related Power
Emergency Diesel Generators The inspectors assessed performance issues with respect to the reliability, availability, and condition monitoring of the SSCs. Specifically, the inspectors independently verified the licensees handling of SSC performance or condition problems in terms of:
appropriate work practices,
identifying and addressing common cause failures,
scoping of SSCs in accordance with 10 CFR 50.65(b),
characterizing SSC reliability issues,
tracking SSC unavailability,
trending key parameters (condition monitoring),
10 CFR 50.65(a)(1) or (a)(2) classification and reclassification, and
appropriateness of performance criteria for SSCs/functions classified (a)(2)and/or appropriateness and adequacy of goals and corrective actions for SSCs/functions classified (a)(1).
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for maintenance effectiveness related issues that were documented in selected CRs.
b. Findings
No findings of significance were identified.
1R13 Maintenance Risk Assessments and Emergent Work Evaluation
a. Inspection Scope
The inspectors reviewed the licensees evaluation and management of plant risk for maintenance activities on the following equipment:
Initiating Events Cornerstone
Unit 2 Reserve Feed Transformer
Unit 2 East Component Cooling Water System Train Barrier Integrity Cornerstone
Unit 1 East Containment Spray System Train Mitigating Systems Cornerstone
Unit 2 Pressurizer Power Operated Relief Valves (PORVs)
Unit 2 East Charging System Train
Unit 2 West Component Cooling Water System Train
Unit 2 West Essential Service Water Pump These activities were selected based on their potential risk significance relative to the reactor safety cornerstones. As applicable for each of the above activities, the inspectors reviewed the scope of maintenance work, discussed the results of the assessment with the licensees probabilistic risk analyst and/or shift technical advisor, and verified that plant conditions were consistent with the risk assessment. The inspectors also reviewed TS requirements and walked down portions of redundant safety systems, when applicable, to verify that risk analysis assumptions were valid and applicable requirements were met.
b. Findings
No findings of significance were identified.
1R15 Operability Evaluations
a. Inspection Scope
The inspectors reviewed the following CRs to ensure that either:
- (1) the condition did not render the involved equipment inoperable or result in an unrecognized increase in plant risk, or
- (2) the licensee appropriately applied TS limitations and appropriately returned the affected equipment to an operable status.
Barrier Integrity Cornerstone
CR 02113065 2-OHP-4030-STP-007E, East Containment Spray System Operability Test, Does Not Have a Maximum of 60 Gallons Per Minute Water Flow Rate from the Spray Additive Tank Line with Spray Pump on Recirculation as Stated in TS Bases Section 3/4.6.2.2
CR 02264018 Unit 1 Control Room Door (1-DR-AUX412B) Was Propped Open Without Specific Procedure Guidance to Allow it to Be Open Mitigating Systems Cornerstone
CR 02122057 1-IMO-911 Could Not Be Set Within the Prescribed Thrust Limitations Provided in VDS-1-IMO-911
CR 02116032 1-HV-AES-2 Exhaust Fan Was Found in Standby With its Backdraft Damper Stuck Partially Open and the Fan Rotating Backwards
CR 02125016 Potentially High Boron Concentration (Above 2600 Parts Per Million) in Unit 1 Reactor Coolant System in Mode 4 Shortly Before Entering Mode 5 In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for issues potentially affecting the operability of safety related SSCs that were documented in selected CRs.
b. Findings
No findings of significance were identified.
1R16 Operator Workarounds
.1 Semiannual Review of the Cumulative Effect of Operator Workarounds
a. Inspection Scope
The inspectors reviewed the cumulative effect of operator workarounds, control room deficiencies, and degraded conditions on equipment availability, initiating event frequency, and the ability of the operators to implement abnormal or emergency operating procedures. During this review the inspectors considered the cumulative effects of operator workarounds on the following:
the reliability, availability and potential for mis-operation of a system;
the ability of operators to respond to plant transients or accidents in a correct and timely manner; and
the potential to increase an initiating event frequency or affect multiple mitigating systems.
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for issues potentially affecting the functionality of mitigating systems or on the operators response to initiating events that were documented in selected CRs.
b. Findings
No findings of significance were identified.
1R17 Permanent Plant Modifications
a. Inspection Scope
The inspectors reviewed the engineering analyses, modification documents and design change information associated with the following permanent plant modification:
Barrier Integrity Cornerstone
Design Change 1-DCP-5173, "Unit 1 Provide Essential Service Water Minimum Flow Path Via Containment Spray System Heat Exchanger," Revision 0
Design Change 2-DCP-5174, "Unit 2 Provide Essential Service Water Minimum Flow Path Via Containment Spray System Heat Exchanger," Revision 0 The modification provided a minimum flow path for the ESW pumps through the containment spray system heat exchangers to eliminate a potential common mode failure concern for the emergency diesel generators. During this inspection, the inspectors evaluated the implementation of the design to verify that:
the compatibility, functional properties, environmental qualifications, seismic qualification, and classification of materials and replacement components were acceptable;
the affected operating procedures and training were identified and necessary changes were completed;
the pressure boundary integrity was not compromised;
the implementation of the modifications did not impair key safety functions;
no unintended system interactions occurred;
the system performance characteristics affected by the modification continued to meet the design basis; and
the modification design assumptions were appropriate.
Completed activities associated with the implementation of the modification were also inspected and the inspectors discussed the modification with the responsible engineers and operations staff. In addition, the inspectors reviewed the applicable sections of the TS, UFSAR, and 10 CFR 50.59 safety evaluation associated with the design change packages.
b. Findings
No findings of significance were identified.
1R19 Post Maintenance Testing
a. Inspection Scope
The inspectors reviewed the post maintenance testing requirements associated with the following scheduled maintenance activities:
Barrier Integrity Cornerstone
Unit 1 East Containment Spray System Train Maintenance Mitigating Systems Cornerstone
Unit 2 AB Emergency Diesel Generator Maintenance
Unit 2 North Safety Injection Pump Maintenance
Unit 2 East Auxiliary Feedwater Pump Maintenance
Unit 2 East Centrifugal Charging System Train Maintenance
Unit 2 East Component Cooling Water System Train Maintenance
Unit 2 West Component Cooling Water System Train Maintenance
Unit 2 West Essential Service Water Pump Replacement The inspectors selected these post maintenance testing activities because the systems were identified as risk significant in the licensees risk analysis. The inspectors reviewed the scope of the work performed and evaluated the adequacy of the specified post maintenance testing. The inspectors verified that the post maintenance testing was performed in accordance with approved procedures, that the procedures clearly stated acceptance criteria, and that the acceptance criteria were met. During this inspection, the inspectors interviewed operations, maintenance and engineering department personnel and reviewed the completed post maintenance testing documentation.
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for post maintenance testing related issues documented in selected CRs.
b. Findings
No findings of significance were identified.
1R20 Refueling and Outage Activities
.1 Unit 2 Forced Outage
a. Inspection Scope
On July 27, 2002, the licensee performed a reactor shutdown to replace a circulating water pump discharge valve that had failed closed. Shear pins that connect the number 23 circulating water pump discharge valves (2-WMO-23) disk to the stem severed, causing the valve to fail closed. The unit was ramped down at approximately 20 percent per hour and the reactor was tripped at 11:50 p.m. from 15 percent power. The licensee entered Mode 4 (Hot Shutdown) to perform additional maintenance work. The licensee performed a reactor startup and synchronized the unit to the grid on August 3, 2002.
The inspectors evaluated the licensees conduct of forced outage activities to assess the licensees control of plant configuration and risk management actions. The inspectors reviewed the cause for the valve failure as well as the extent of condition of other circulating water pump discharge valves. The inspectors observed portions of the restart activities to verify that requirements of the TS and administrative procedure requirements were met prior to changing operational modes or plant configurations.
b. Findings
No findings of significance were identified.
1R22 Surveillance Testing
a. Inspection Scope
For the surveillance test procedures listed below, the inspectors observed selected portions of the surveillance test and/or reviewed the test results to determine whether risk significant systems and equipment were capable of performing their intended safety functions and to verify that testing was conducted in accordance with applicable procedural and TS requirements:
01-IHP-4030-SMP-103, "Reactor Coolant Flow Protection Set III Functional Test and Calibration," Revision 4
01-IHP-4030-SMP-104, "Delta T/Tavg Protection Set I Functional Test and Calibration," Revision 4
02-OHP-4030-STP-30, "Daily and Shiftly Surveillance Checks," Revision 39
02-IHP-4030-STP-511, "Train B Reactor Protection System and Engineered Safety Features Reactor Trip Breaker and Solid State Protection System Automatic Trip/Actuation Logic Functional Test," Revision 4
12-EHP-6040-PER-323, "Flux Mapping System Operation and Supportive Data Collection," Revision 4a The inspectors reviewed the test methodology and test results in order to verify that equipment performance was consistent with safety analysis and design basis assumptions.
In addition, the inspectors reviewed the issues that the licensee entered into its corrective action program to verify that identified problems were being entered into the program with the appropriate characterization and significance. The inspectors also reviewed the licensees corrective actions for surveillance testing related issues documented in selected CRs.
b. Findings
No findings of significance were identified.
1R23 Temporary Plant Modifications
a. Inspection Scope
The inspectors reviewed the temporary modification listed below to verify that the installation was consistent with design modification documents and that the modification did not adversely impact system operability or availability:
2-TM-00-57, "On-line Leak Repair of 2-FW-118-4," Revision 1 The temporary modification installed a temporary leak seal on the south bearing cover for the number 4 steam generator feedwater header containment isolation check valve (2-FW-118-4). A steam leak developed at the flange where the cover is fastened to the valve body that could not be corrected by normal maintenance practices with the unit on line. The inspectors verified that configuration control of the modification was correct by reviewing design modification documents and confirmed that appropriate post-installation testing was accomplished. The inspectors interviewed engineering and maintenance department personnel and reviewed the design modification documents and the 10 CFR 50.59 evaluation against the applicable portions of the UFSAR.
b. Findings
No findings of significance were identified.
1EP6 Drill Evaluation
a. Inspection Scope
The inspectors observed the conduct of the licensees third quarter announced emergency planning drill that was conducted in the licensees control room simulator and emergency response facilities on August 22, 2002. The inspection effort was focused on evaluation of the licensees classifications, notifications, and protective action recommendations for the simulated event. The inspectors also evaluated the licensees conduct of the training evolution, including the licensees critique of performance to identify weaknesses and deficiencies.
b. Findings
No findings of significance were identified.
RADIATION SAFETY
Cornerstone: Occupational Radiation Safety
2OS1 Access Control to Radiologically Significant Areas (71121.01)
.1 Plant Walkdowns and Radiological Boundary Verification
a. Inspection Scope
The inspector conducted walkdowns of selected radiologically controlled areas to verify the adequacy of radiological area boundaries and postings. Specifically, the inspector walked down all locked high radiation area (LHRA) boundaries (excluding LHRAs located within other LHRAs) in the Auxiliary Building to determine if these areas and selected high radiation areas were properly posted and controlled in accordance with 10 CFR 20 and the licensees TS. The inspector also observed the radiological conditions of work areas within those high and locked high radiation areas walked down to assess the radiological housekeeping and contamination controls.
b. Findings
No findings of significance were identified.
.2 High Risk Significant, High Radiation Area, and Very High Radiation Area Access
Controls
a. Inspection Scope
The inspector reviewed the licensees procedures and practices for the control of access to radiologically significant areas (high, locked high, and very high radiation areas) and assessed compliance with those procedures, the licensees TS and the requirements of 10 CFR 20.1601 and 20.1602. Implementation of a recently developed procedure and technical/administrative guidelines for the verification and control of radiologically significant areas were also reviewed for adequacy and conformity with regulatory requirements. In particular, the inspector reviewed the licensees practices for the control of keys to LHRAs and very high radiation areas including the review of key issuance and tracking logs and key inventory surveillance records for 2002 thru July, the use of access control guards to control entry into such areas, and the licensees methods for independently verifying proper closure and latching of LHRA doors. The inspector also reviewed evolving communication plans and interface practices between radiation protection (RP) and plant operations staff to assess the licensees communication protocols relevant to changing plant conditions that could alter radiological area status. Additionally, the inspector attended a pre-job briefing for the transfer of a reactor cavity filter from one LHRA to another, to determine if radiological information was adequately exchanged and if plans for area access control were sound and met regulatory requirements.
b. Findings
No findings of significance were identified.
.3 Radiation Work Permit Reviews
a. Inspection Scope
The inspector reviewed several radiation work permits (RWPs) for work that was recently completed in radiologically significant areas. Electronic dosimeter alarm setpoints for both dose rate and integrated dose were evaluated to verify conformity with work area radiological conditions given the work activity. The inspector also reviewed work instructions specified in the RWPs and in pre-job briefing information in order to evaluate access control restrictions for compliance with TS and the licensees access control procedures.
b. Findings
No findings of significance were identified.
.4 Control of Non-Fuel Materials Stored in the Spent Fuel Pool
a. Inspection Scope
The inspector reviewed the licensees radiological controls and practices for the storage of highly activated or contaminated materials (non-fuel) in the spent fuel pool. A foreign material exclusion (FME) maintenance procedure which contained provisions for temporary storage of material in the spent fuel pool was reviewed along with the most recent pool inventory record, and a walkdown of the spent fuel pool area was conducted. The inspector discussed with RP staff the administrative and physical controls that would be considered should temporary storage of highly activated/contaminated material in the spent fuel pool be necessary to ensure consistency with the licensees FME procedure and with Regulatory Guide 8.38, Information Notice 90-33, and applicable Health Physics Positions in NUREG/CR-5569.
Plans to develop a RP procedure or expand the existing FME procedure to fully address the regulatory guidance and standardize the licensees practices were discussed with RP management.
b. Findings
No findings of significance were identified.
.5 Identification and Resolution of Problems
a. Inspection Scope
The inspector reviewed the licensees CR database and several individual CRs related to access, posting and key controls for radiologically significant areas that were generated in 2002 through July 22, 2002. The review was performed to determine the scope and extent of problems identified by the licensee. The inspector evaluated the effectiveness of the licensees corrective action process to identify and characterize individual problems and potential trends and to develop corrective actions to prevent recurrence. The inspector also reviewed the licensees planned actions to address deficiencies with its access control program that were identified during a recent industry assist inspection.
b. Findings
No findings of significance were identified.
2OS3 Radiation Monitoring Instrumentation and Protective Equipment (71121.03)
.1 Walkdowns of Radiation Monitoring Instrumentation
a. Inspection Scope
The inspector conducted walkdowns of selected area radiation monitors (ARMs) to verify they were located as described in the UFSAR, to determine if they were optimally positioned relative to the potential source(s) of radiation they were intended to monitor, and to assess their material condition. The inspector also reviewed the status of repair or troubleshooting activities associated with those ARMs that the inspector observed had work request tags, to verify that instrument problems were being addressed in an appropriate and timely manner.
b. Findings
No findings of significance were identified.
.2 Tests and Calibrations of Radiation Monitoring Instrumentation
a. Inspection Scope
The inspector selectively reviewed radiological instrumentation associated with monitoring transient high and/or very high radiation areas and instruments used for remote emergency assessment to verify that the instruments had been calibrated consistent with industry standards and in accordance with station procedures. The inspector reviewed alarm setpoints for selected ARMs to verify that they were established consistent with the UFSAR and TS. Specifically, the inspector reviewed calibration procedures and the most recent calibration records and/or source characterization/verification documents for the following radiation monitoring instrumentation and instrument calibration equipment:
Unit 1 North Seal Water Injection Filter Cubicle ARM
Unit 2 South Seal Water Injection Filter Cubicle ARM
Unit 1 West Centrifugal Charging Pump Room ARM
Unit 1 and Unit 2 High Range Containment Radiation Monitors
Radcal Corporation Model 20X5-180 Ion Chamber and Model 2025 Electrometer (Instrument Calibrator Output Measurement Equipment)
J. L. Shepherd Model M89 Instrument Calibrators The inspector evaluated RP technician performance while selected instruments used for surveys of personnel and equipment prior to unconditional release from the radiologically controlled area were source checked, to determine if those checks were completed adequately and in conformance with station procedures. Alarm setpoints for these instruments were also reviewed to determine if they were established at levels consistent with industry standards and regulatory guidance provided in Health Physics Positions Number 72 and Number 250 of NUREG/CR-5569. An inspector identified deficiency with the methodology of source checking the portal radiation monitors used at station egress locations was assessed to verify that it did not impact instrument operability or compromise detector alarm function verification. Additionally, the inspector reviewed the most recent calibration record and procedure for one of the licensees portal monitors used at the north guard post to monitor staff as they leave the plant restricted area. The review was performed to ensure the monitor was calibrated adequately and as required by procedure and that the instruments alarm setpoint was established consistent with industry guidance.
b. Findings
No findings of significance were identified.
.3 Respiratory Protection Program
a. Inspection Scope
The inspector reviewed aspects of the licensees respiratory protection program for compliance with the requirements of Subpart H of 10 CFR 20, and to ensure that self-contained breathing apparatus (SCBA) were properly maintained and ready for emergency use. Specifically, the inspector reviewed SCBA equipment inspection, functional test and maintenance procedures and records for selected periods in 2002 through July, for all SCBA units staged for emergency use and located in various areas of the plant. The review was performed to determine if the equipment was properly maintained consistent with industry standards and station procedures.
The inspector walked-down the SCBA air bottle filling station in the Operations Support Center and SCBA equipment storage locations in the Unit 1 and Unit 2 Control Rooms, the Operations Support Center, the RP Access Control Building, and at the 633 foot elevation of the Turbine Building. The inspector examined several SCBA units that were stored in these areas to assess their material condition, and to verify that air bottle hydrostatic tests were current and that bottles were pressurized to meet procedural requirements. The inspector discussed SCBA equipment inspection and functional testing with a RP technician that performed these activities to verify that surveillances were completed adequately and that the equipment was properly maintained. The inspector also reviewed training certificates and training matrices for selected RP staff to determine if those licensee personnel performing SCBA equipment maintenance and inspection were qualified consistent with industry standards.
The inspector performed a review to determine if a sufficient cadre of the licensees emergency response organization that could be called upon to perform vital emergency response activities that required use of respiratory protection equipment were trained and qualified in SCBA use. Specifically, the inspector reviewed respiratory protection training and SCBA qualification records for current operations on-shift staff, the stations fire brigade and members of the licensees RP and maintenance staffs to ensure personnel qualifications were maintained consistent with the licensee's emergency plan and procedures.
b. Findings
No findings of significance were identified.
.4 Identification and Resolution of Problems
a. Inspection Scope
The inspector reviewed the results of a self-assessment that focused on SCBA qualifications and that was completed by the licensee's emergency preparedness staff in January 2001, and the licensees CR database and several individual CRs related to radiation monitoring instrumentation and SCBA equipment generated in 2002 through July 22, 2002. The review was performed to evaluate the effectiveness of the licensees self-assessment and corrective action program to identify problems, to characterize and prioritize problems, and to develop appropriate corrective actions. Plans to address inspector identified deficiencies with SCBA training relative to air bottle change-out and to ensure that all appropriate emergency response staff consistently maintain SCBA qualifications were discussed with station and RP management.
b. Findings
No findings of significance were identified.
Cornerstone: Public Radiation Safety
2PS1 Radioactive Gaseous and Liquid Effluent Treatment and Monitoring Systems (71122.01)
.1 Walkdowns of Liquid and Gaseous Effluent Monitoring and Control Systems
a. Inspection Scope
The inspectors performed walkdowns of the major components of the liquid and gaseous effluent monitoring and release systems, including point of discharge effluent radiation monitors, liquid radioactive waste (radwaste) processing tanks, gas decay tanks and steam generator blowdown flash tanks, to verify that the current system configuration was as described in the Updated Final Safety Analysis Report (UFSAR)and was consistent with the Offsite Dose Calculation Manual (ODCM), and to assess equipment material condition.
The inspectors also walked down the radwaste system control panel, reviewed the status of work requests for selected effluent related systems and discussed processing equipment reliability, use and operating practices with environmental staff.
b. Findings
No findings of significance were identified.
.2 Radioactive Effluent Release Data, Dose Calculations, and ODCM Changes
a. Inspection Scope
The inspectors reviewed the 1999, 2000, and 2001 Annual Radioactive Effluent Release Reports and selected radioactive effluent release data for 2002 through September 2002 to verify that the radioactive effluent control program was implemented as described in the ODCM and to ensure that any anomalies in the release data were adequately understood by the licensee and were properly assessed and reported. The inspectors evaluated the licensees methodology for the calculation of offsite dose and selectively reviewed results of both liquid and gaseous effluent sample analyses for 2002, to verify that the licensee properly calculated dose from effluents consistent with the ODCM. The inspectors also reviewed revisions made to the ODCM in calendar years 2000 and 2001 and the justifications for other than editorial changes, to verify they were completed and reported in accordance with Technical Specifications and the ODCM.
b. Findings
No findings of significance were identified.
.3 Liquid and Gaseous Effluent Releases
a. Inspection Scope
As there were no liquid batch releases performed during the inspection, the inspectors reviewed the release packages for two liquid effluent batch release completed in 2001 and for one completed in 2002. The review was conducted to verify that the licensees release procedures and practices, including dose projections to members of the public and use of station specific scaling factors, were technically sound and conformed to ODCM methodology and Technical Specification requirements. The inspectors also reviewed selected batch (containment pressure reliefs and containment purge/vent) and continuous gaseous effluent release data including results of chemistry sample analyses, to independently verify that the data was properly used to complete calculations of offsite dose consistent with ODCM methodology and the licensees procedures. For those release packages reviewed, the inspectors also examined the discharge monitor alarm set points and the set point calculation methodology to verify they were established in accordance with the ODCM and the licensees procedure. The inspectors accompanied a chemistry technician during a weekly change-out and analysis of the particulate and iodine unit vent effluent samples, to verify that practices and analytical techniques were technically sound and consistent with procedure.
Additionally, the inspectors reviewed chemistry data for selected periods in 2002 to verify that compensatory samples were taken and analyzed as required by the ODCM during periods when effluent monitors were out of service.
b. Findings
No findings of significance were identified.
.4 Liquid and Gaseous Effluent Monitor Calibration
a. Inspection Scope
The inspectors reviewed records of instrument calibrations performed since the last inspection for selected point of discharge effluent radiation monitors and flow meters, to determine if they had been calibrated consistent with industry standards and in accordance with station procedures and the ODCM. Specifically, the inspectors reviewed the calibration records for the following effluent radiation detectors and flow monitors:
- Unit 2 Condenser Air Ejector Exhaust
- Unit 1 and Unit 2 Vent Exhaust
- Unit 1 and Unit 2 Steam Generator Blowdown
- Unit 1 and Unit 2 Essential Service Water (East Heat Exchanger)
- Unit 1 and Unit 2 Essential Service Water (West Heat Exchanger)
- Common Unit Liquid Radwaste Discharge Line
- Unit 1 Gland Seal Exhaust Flow Monitor
- Unit 1 Vent Flow Monitor
- Unit 2 Gland Seal Exhaust Flow Monitor
- Unit 2 Vent Flow Monitor The inspectors also reviewed supporting health physics calculations that established calibration constants, reference source responses and alarm set point values for these monitors, to verify the technical viability of the calibration program and for compliance with ODCM criteria. Additionally, the inspectors examined effluent monitor performance and overall radiation monitoring system health information for 2001-2002 and discussed monitor troubleshooting efforts and associated remedial actions with the assigned system engineer, to assess the adequacy of the licensees efforts to identify problems and improve the overall reliability of the effluent radiation monitoring and control system.
b. Findings
No findings of significance were identified.
.5 Air Cleaning System Surveillance Tests
a. Inspection Scope
The inspectors reviewed the most recent results for both trains of the Unit 1 and Unit 2 Engineered Safety Features (ESF) ventilation system exhaust air filter testing to verify that test methodology, frequency and test results met Technical Specification requirements. Specifically, the inspectors evaluated the test methodology and reviewed the test results of in-place high efficiency particulate air (HEPA) and charcoal absorber penetration tests, laboratory tests of charcoal absorber methyl iodide penetration, in-place combined HEPA filter and charcoal absorber train pressure drop tests and tests to demonstrate automatic start of the standby fans.
b. Findings
No findings of significance were identified.
.6 Analytical Instrumentation Quality Control and Inter-laboratory Comparison Program
a. Inspection Scope
The inspectors reviewed the chemistry departments quality control data for selected periods in 2002 through September for those instrumentation systems used to quantify effluent releases. The review was performed to assess equipment performance and to verify that testing was completed consistent with station procedures. This included a review of the chemistry counting laboratory gamma spectroscopy systems and liquid scintillation counters. The inspectors also reviewed the most recent energy calibration records, efficiency checks and lower limit of detection (LLD) determinations for all spectroscopy systems used to analyze effluent samples. The review was performed to determine if calibration and efficiency check acceptance criteria and ODCM specified LLDs were met and if the calibrations were conducted in accordance with procedure.
The inspectors reviewed the results of the first and second quarter 2002 radiochemistry inter-laboratory cross checks to determine if the cross check program was adequately implemented consistent with industry standards and to verify the quality of the radioactive effluent analyses performed by the licensee.
b. Findings
No findings of significance were identified.
.7 Identification and Resolution of Problems
a. Inspection Scope
The inspectors reviewed a 2001 radiation protection department self-assessment of effluent sampling/analysis and ODCM implementation, performance assurance department field observations reports and audits completed in 2001 through September 2002, and condition reports (CRs) generated during approximately the 12-month period preceding the inspection that related to ODCM implementation and the liquid and gaseous effluent monitoring and control program. The documents were reviewed to evaluate the licensees ability to assess the effluent control program, to identify repetitive problems or trends, contributing causes and extent of condition, and to implement corrective actions to achieve lasting results.
b. Findings
No findings of significance were identified.
SAFEGUARDS
Cornerstone: Physical Protection
3PP3 Response to Contingency Events (71130.03)
The Office of Homeland Security (OHS) developed a Homeland Security Advisory System (HSAS) to disseminate information regarding the risk of terrorist attacks. The HSAS implements five color-coded threat conditions with a description of corresponding actions at each level. NRC Regulatory Information Summary (RIS) 2002-12a, dated August 19, 2002, "NRC Threat Advisory and Protective Measures System," discusses the HSAS and provides additional information on protective measures to licensees.
a. Inspection Scope
On September 10, 2002, the NRC issued a Safeguards Advisory to reactor licensees to implement the protective measures described in RIS 2002-12a in response to the Federal Governments declaration of threat level "Orange." Subsequently, on September 24, 2002, the OHS downgraded the national security threat condition to "Yellow" and a corresponding reduction in the risk of a terrorist threat.
The inspectors interviewed licensee personnel and security staff, observed the conduct of security operations, and assessed licensee implementation of the threat level "Orange" protective measures. Inspection results were communicated to the region and headquarters security staff for further evaluation.
b. Findings
No findings of significance were identified.
OTHER ACTIVITIES
4OA1 Performance Indicator Verification
.1 Unplanned Scrams per 7000 Critical Hours and Scrams with Loss of Normal Heat
Removal
a. Inspection Scope
Initiating Events Cornerstone The inspectors verified the Unplanned Scrams per 7000 Critical Hours and the Scrams with Loss of Normal Heat Removal performance indicators for both units. The inspectors reviewed each licensee event report (LER) from October 2001 to June 2002, determined the number of scrams that occurred, evaluated each of the scrams against the performance indicator definitions, and verified the licensees calculation of critical hours for both units.
b. Findings
No findings of significance were identified.
.2 Unplanned Power Changes per 7000 Critical Hours
a. Inspection Scope
Initiating Events Cornerstone The inspectors verified the Unplanned Power Changes per 7000 Critical Hours performance indicator for both units. The inspectors reviewed power history data for both operating units from October 2001 to June 2002, determined the number of power changes greater than 20 percent full power that occurred, evaluated each of those power changes against the performance indicator definition, and verified the licensees calculation of critical hours for both units.
b. Findings
No findings of significance were identified.
a. Inspection Scope
Mitigating Systems Cornerstone The inspectors verified the following performance indicators for both units:
Safety System Unavailability - Emergency AC [Alternating Current] Power,
Safety System Unavailability - Auxiliary Feedwater,
Safety System Unavailability - High Pressure Safety Injection, and
Safety System Unavailability - Residual Heat Removal.
The inspectors reviewed operating logs, maintenance history and surveillance test history for unavailability information for these systems from October 2001 to June 2002.
The inspectors also verified the licensees calculation of required hours for both units and evaluated applicable safety system equipment unavailability against the performance indicator definition. The inspectors interviewed engineering and operations staff to determine whether the performance indicator data was being collected and reported consistent with the guidance contained in NEI [Nuclear Energy Institute] 99-02, "Regulatory Assessment Performance Indicator Guideline," Revision 2.
b. Findings
No findings of significance were identified.
.4 Occupational Exposure Control Effectiveness
a. Inspection Scope
Occupational Radiation Safety Cornerstone The inspector evaluated the RP departments performance indicator data analysis methods and associated records to determine if the licensee had accurately assessed and reported the performance indicator for the Occupational Radiation Safety Cornerstone in accordance with the criteria specified in NEI 99-02, "Regulatory Assessment Performance Indicator Guideline," Revisions 1 and 2. Specifically, the inspector reviewed the licensees CR database and selected CRs generated between December 2001 and July 2002, and selected radiologically controlled area egress transaction dose information and electronic dosimetry alarm reports generated in 2002 through July. The review was performed to identify any access control or unintended dose performance indicator occurrences that were not recognized by the licensee and to verify the licensees performance indicator results for the Occupational Radiation Safety Cornerstone. The inspector also reviewed performance indicator verification records completed by the RP staff for the first two quarters of 2002, and discussed performance indicator data collection and analysis processes with the RP departments performance indicator data steward to determine if the program was implemented consistent with the licensees performance indicator procedure and the NEI guideline.
b. Findings
No findings of significance were identified.
.5 Radiological Effluent Technical Specification (RETS)/ODCM Radiological Effluent
Occurrence PI
a. Inspection Scope
The inspectors reviewed the licensees assessment of its public radiation safety performance indicator for RETS/ODCM radiological effluent occurrences to determine if the indicator was adequately assessed and reported. Specifically, the inspectors reviewed CRs generated during the 12-months preceding the inspection to identify any potential occurrences such as unmonitored, uncontrolled or improperly calculated effluent releases that may have impacted offsite dose. Also, the inspectors evaluated the licensees methods for determining offsite dose and selectively verified that gaseous and liquid effluent release data and associated offsite dose calculations performed since this indicator was last reviewed in November 2001 were accurate. The inspectors discussed the RETS/ODCM PI data collection and analysis process with the data steward for this indicator to verify that the indicator was assessed consistent with industry guidelines as provided by the applicable revision of Nuclear Energy Institute Document 99-02, Regulatory Assessment Performance Indicator Guideline.
b. Findings
No findings of significance were identified.
4OA3 Event Follow-up
.1 Unit 2 Reactor Trip and Restart Following Loss of Main Condenser Vacuum
a. Inspection Scope
On July 22, 2002, Unit 2 experienced an automatic reactor trip in response to a main turbine trip on low condenser vacuum. Immediately prior to the main turbine trip, operators were flushing the main condenser waterboxes of debris by cycling the circulating water inlet isolation valves. The licensee did not expect to have condenser vacuum lower to below the turbine trip setpoint and determined that the apparent cause for the loss of vacuum condition was degraded condenser performance. The licensee restarted Unit 2 on July 23, 2002, after cleaning and inspecting the main condenser water boxes. The inspectors assessed control room operator performance immediately following the reactor trip, reviewed the post trip report, and observed portions of the reactor restart activities. The inspectors also reviewed the LER for this event.
b. Findings
(Closed) LER 50-316-2002-006-00: "Unit 2 Reactor Trip Due to Low Condenser Vacuum." The inspectors concurred with the licensees conclusion that the safety significance of this event was minimal. The licensee entered this event into its corrective action program as CR 02203001. This event did not constitute a violation of NRC requirements. This LER is closed.
.2 Pressurizer Power Operated Relief Valve Inadvertently Opened During Testing
Resulting in a Loss of Reactor Coolant System Inventory and an Unusual Event
a. Inspection Scope
On June 5, 2002, with Unit 1 in Mode 4 (Hot Shutdown), pressurizer PORV 1-NRV-153 inadvertently opened while testing actuation logic circuitry for pressurizer PORV 1-NRV-151. Approximately 100 gallons of reactor coolant was released to the pressurizer relief tank. The release rate exceeded the 25 gallons-per-minute limit established for declaring an Unusual Event in accordance with the licensees Emergency Plan. The inspectors reviewed the circumstances associated with this event, including the root cause determination, operator response during the event, and corrective actions.
b. Findings
An Apparent Violation of 10 CFR 50, Appendix B, Criterion V, "Instructions, Procedures, and Drawings," was self-revealed. The licensee failed to provide an appropriate procedure for testing the Unit 1 pressurizer PORVs, causing an uncontrolled release of reactor coolant system inventory to the pressurizer relief tank. Pending additional evaluation, the safety significance of this issue is "To Be Determined" (TBD).
Discussion On June 5, 2002, while performing testing to verify the automatic opening of pressurizer PORV 1-NRV-151, pressurizer PORV 1-NRV-153 also opened unexpectedly. With the associated PORV block valve for 1-NRV-153 open, approximately 100 gallons of reactor coolant was released to the pressurizer relief tank. The reactor coolant inventory transfer was immediately apparent to control room operators via alarms and indications, resulting in a 15 second response time for operators to close the block valve and terminate the reactor coolant discharge.
Three pressurizer PORVs are provided on each unit. The PORVs are designed to operate manually and automatically through a complex series of control and actuation circuits. The control circuits include interlocks and common actuation signals for the PORVs and pressurizer heaters that are needed to control pressurizer pressure. A common signal operates both 1-NRV-151 and 1-NRV-153. Another common signal operates the third PORV (1-NRV-152) and energizes/de-energizes pressurizer heaters.
The TS require periodic testing of the circuitry to verify proper operation from the pressure sensing instruments through operation of the valves and heaters. One of the required tests performed during refueling outages verifies that each valve will open upon receipt of a signal from the actuation circuitry.
The licensee recently changed the surveillance test procedure to allow testing each PORV individually rather than together, as the testing was previously conducted. The licensees root cause evaluation concluded that the procedure change did not contain adequate instructions to establish initial test conditions to prevent unintended opening of both interlocked valves 1-NRV-151 and 1-NRV-153 while one valve was being tested.
The licensee subsequently revised the procedure and performed the testing satisfactorily on June 6, 2002.
Analysis The inspectors assessed this finding using the Significance Determination Process (SDP). The inspectors concluded that this issue could be reasonably viewed as a precursor to a significant event and was therefore more than a minor concern. The inspectors also concluded that this finding was associated with the initiating events cornerstone and adversely affected the cornerstone objective. Specifically, the uncontrolled release of reactor coolant system inventory upset plant stability and challenged the inventory control safety function. Because Unit 1 was in a shutdown mode during this period, the inspectors performed a Phase 1 SDP review of this issue using the guidance provided in NRC Inspection Manual Chapter 0609, Appendix G, "Shutdown Operations Significance Determination Process." Based on the above information, the inspectors concluded that the most appropriate Appendix G checklist to use for this issue was the checklist for "Pressurized Water Reactor Hot Shutdown Operation - Time to core boiling less than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />." Because, operator intervention was required to manually close the affected PORV block valve, the inspectors concluded that the unit was in a configuration where a single active failure or personnel error could have resulted in a rapid loss of reactor coolant system inventory as described in Section II.B.(2) of the checklist. Consequently, the inspectors concluded that this issue increased the likelihood of a loss of reactor coolant system inventory and therefore required a Phase 2 SDP analysis. The inspectors discussed the safety significance of this issue with the Regional Senior Reactor Analyst; and, pending the completion of a Phase 2 analysis, the safety significance of this issue is to be determined.
Enforcement 10 CFR 50, Appendix B, Criterion V, "Instructions, Procedures, and Drawings," requires, in part, that activities affecting quality shall be prescribed by documented instructions, procedures, or drawings, of a type appropriate to the circumstances and shall be accomplished in accordance with these instructions, procedures, or drawings. Contrary to the above, the licensee failed to provide a procedure of a type appropriate to the circumstances for testing the Unit 1 pressurizer PORVs, which is an activity affecting quality. Specifically, the instructions contained in 1-IHP-4030-102-017, "Pressurizer Power Operated Relief Valve (PORV) Actuation Channel Calibration with Valve Operation (for Modes 1, 2, and 3)," Revision 1, failed to provide adequate control of pressurizer PORVs 1-NRV-151 and 1-NRV-153, which have a common automatic opening signal. This issue was self-revealed on June 5, 2002, when pressurizer PORV 1-NRV-153 inadvertently opened while testing actuation logic circuitry for 1-NRV-151, causing an uncontrolled release of reactor coolant system inventory to the pressurizer relief tank. This issue is considered to be an Unresolved Item pending a final safety significance determination (URI 50-315-02-06-01(DRP)). The licensee entered this violation into its corrective action program as CR 02157039.
.3 (Closed) LER 50-315-2002-003-00:
"Main Steam Safety Valves Exceed Allowable Lift Setpoints." During surveillance testing of the Unit 1 main steam safety valves (MSSVs)on May 2 and 3, 2002, the licensee identified that 7 of 20 MSSVs failed to meet the TS acceptance criteria for the lift setpoint. As a result of each MSSV test failure, the licensee entered the appropriate TS Limiting Condition for Operation and restored each valve to an operable condition within the TS allowed outage time. The valve lift test failures were due to metallic bonding between the stainless steel valve disk and nozzle resulting in an increase in each of the valves lift setpoint. The licensee performed an evaluation of the impact of the MSSV surveillance testing results on the transient and accident analysis described in the UFSAR and concluded that the out of tolerance conditions were bounded by the 110 percent secondary system design pressure assumed in the analysis. The inspectors reviewed and concurred with the licensees evaluation. The licensee entered this event into its corrective action program as CR 02122063, CR 02123003, CR 02123037, CR 02123039, CR 02123049, CR 02123050, and CR 02123053. This event did not constitute a violation of NRC requirements. This LER is closed.
.4 (Closed) LER 50-315-2002-005-00:
"Unit 1 Manual Trip Due to Trip of East Main Feedwater Pump." On June 14, 2002, operators manually tripped Unit 1 in response to a main feedwater pump trip. The feedwater pump condenser became clogged with zebra mussel shells and lost vacuum when a circulating water pump was started, transporting debris to the feedwater pump condenser. The inspectors concurred with the licensees conclusion that the safety significance of this event was minimal. The licensee entered this event into its corrective action program as CR 02165064. This event did not constitute a violation of NRC requirements. This LER is closed.
.5 (Closed) LER 50-315-2002-006-00:
"Switchyard Fire Results in Violation of Technical Specification 3.0.5." On June 12, 2002, an explosion of a current transformer in a 345 kilo-volt breaker and fire in the switchyard resulted in the loss of the preferred offsite power source to the Unit 1 and Unit 2 ESW pumps. Since the Unit 2 East ESW pump was out-of-service for planned maintenance and the Unit 1 West ESW pump was considered inoperable in accordance with TS 3.7.4.1 because the cross-tie valves between the units were open to maintain the Unit 2 East ESW header pressurized, the licensee entered TS 3.0.5 for both units. The licensee requested and received enforcement discretion for an additional 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> to accomplish restoration of the Unit 2 East ESW pump to preclude a required dual unit Mode 3 (Hot Standby) entry. The inspectors reviewed the event and the licensees request for enforcement discretion in NRC Inspection Report 50-315/316-02-07(DRP). The inspectors concluded that the enforcement discretion was necessitated by the coincidental performance of pre-planned maintenance on the Unit 2 East ESW pump during the event; therefore, entry into TS 3.0.5 was not due to a failure to comply with regulatory requirements. The inspectors determined that the information provided in LER 50-315-2002-006-00 did not raise any new issues or change the conclusions of the initial reviews documented in NRC Inspection Report 50-315/316-02-07(DRP). The NRC staff concluded that there was no net increase in risk associated with extending the allowed outage time for TS 3.0.5 from 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> to a total of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. The licensee entered this event into its corrective action program as CR 02163045. This violation of TS 3.0.5 is a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRCs Enforcement Policy. This LER is closed.
.6 (Closed) LER 50-315-2002-007-00:
"Technical Specification 3.3.3.1 Required Special Report for Inoperable Radiation Monitors." The action statement for TS 3.3.3.1 associated with radiation monitors 1-VRA-1310 (upper containment high range radiation monitor) and 1-MRA-1702 (steam generator number 3 PORV outlet monitor) requires that the radiation monitors be returned to operable status within 7 days of the event or that a special report be written and issued to the NRC within 14 days of the event. On June 23, 2002, the licensee identified that radiation monitor 1-VRA-1310 had been inoperable for 12 days as a result of maintenance performed on another radiation monitor. At the time of the maintenance activity, the licensee was unaware of the interactions between the two monitors. During its review of that event, the licensee identified that a human performance error during a calibration on April 12, 2002 had rendered another radiation monitor 1-MRA-1702 inoperable for a period of 79 days. At the time of discovery, the licensee corrected the problem and entered the issues into its corrective action program as CR 02174004 and CR 02199084. In both cases, the time of discovery resulted in the licensee exceeding the requirement for a 14-day special report. The failure to issue a special report to the NRC within 14 days of the event is a violation of TS 3.3.3.1. This finding constitutes a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRCs Enforcement Policy. This LER is closed.
.7 (Closed) LER 50-315-2000-008-00:
"Failure to Test Essential Service Water Valves in Accordance with Technical Specifications." This issue was previously discussed in Section E2.2 of NRC Inspection Report 50-315/316-00-01(DRP). The inspectors identified that the ESW outlet valves for the component cooling water heat exchangers were tested in one direction only; however, testing the valves to both open and close was necessary to meet TS surveillance requirement 4.7.4.1.b. The licensees failure to adequately test these valves is a violation of TS 4.7.4.1.b. The inspectors reviewed the revised test procedures that included the required test provisions. Because these valves subsequently passed surveillance testing, this issue is considered to be of minor safety significance. The licensee entered this event into its corrective action program as CR P-00-04744 and CR 00314038. This finding constitutes a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRCs Enforcement Policy. This LER is closed.
.8 (Closed) LER 50-315-2000-008-01:
"Failure to Test Essential Service Water Valves in Accordance with Technical Specifications," Supplement 1. The licensee submitted Supplement 1 to LER 50-315-2000-008-00 to provide additional information concerning the analysis of the event, the cause, and corrective actions. The inspectors determined that the information provided in Supplement 1 to LER 50-315-2000-008-00 did not raise any new issues or change the conclusion of the initial review, which was documented above in Section 4OA3.7. This LER is closed.
.9 (Closed) LER 50-315-2000-009-00:
"Failure to Perform Technical Specification Valve Position Surveillance on Leak-off Valves." The licensee identified that prior to 1997, the TS containment integrity surveillance test requirement of verifying valve position every 31 days was not met for two containment isolation valves in Unit 1. This constituted a violation of Technical Specification 4.6.1.1.a.1. The surveillance procedure was revised to verify the correct position of the affected valves. Because these leak-off valves were located in a sealed enclosure with limited access, this issue is considered to be of minor safety significance. The licensee entered this event into its corrective action program as CR 00341030. This finding constitutes a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRCs Enforcement Policy. This LER is closed.
.10 (Closed) LER 50-316-2000-013-00:
"Safety Injection Valve Closure at High Power Levels Could Result in Exceeding Peak Centerline Temperature Limits." The licensee was performing Unit 2 valve testing at full power which put the unit in an improper alignment for brief periods. This constituted a violation of 10 CFR 50, Appendix B, Criteria III, "Design Control." The procedures were revised to perform this testing when the plant was shutdown. Unit 1 procedures were also revised although the requirement did not apply to Unit 1 power levels. Because the testing was performed for very short durations and on an 18 month interval, this issue is considered to be of minor safety significance. The licensee entered this event into its corrective action program as CR P-00-11217. This finding constitutes a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRCs Enforcement Policy. This LER is closed.
.11 (Closed) LER 50-315-1999-012-01:
"Auxiliary Building ESF Ventilation System May Not Be Capable of Maintaining ESF Room Temperatures Post-Accident, Supplement 1.
On April 20, 1999, the licensee discovered several issues that, when taken in aggregate, resulted in insufficient assurance that the ESF ventilation system was capable of performing its safety and accident mitigation functions. The inspectors reviewed the original LER in NRC Inspection Report 50-315/316-99-29(DRS) and concluded that this was a minor issue. The licensee submitted Supplement 1 to LER 50-315-1999-012-00 to provide new information concerning the analysis of the event and corrective actions. The cause for this event was the licensee's failure to adequately control design basis calculations and supporting documentation. This constituted a violation of 10 CFR 50, Appendix B, Criteria III, "Design Control." The licensee entered this event into its corrective action program as CR P-99-08841. The inspectors determined that the licensees corrective actions were adequate to prevent recurrence.
This finding constitutes a violation of minor significance that is not subject to enforcement action in accordance with Section VI of the NRC's Enforcement Policy.
This LER is closed.
.12 (Closed) LER 50-315-1999-001-01:
"General Electric HFA Relays Installed in Emergency Diesel Generators May Not Meet Seismic Qualifications," Supplement 1.
On January 6, 1999, it was determined that General Electric HFA safety related relays installed in plant system circuits may not be properly configured in accordance with vendor instructions for relay contact adjustment and servicing, and therefore, may not meet seismic qualification. The inspectors reviewed the original LER and determined that this was a minor issue. The licensee submitted Supplement 1 to LER 50-315-1999-001-00 to provide new information concerning the analysis of the event and corrective actions. The extent of condition was identified and all affected relays were reconfigured and calibrated to restore operability. The inspectors determined that the information provided in Supplement 1 to LER 50-315-1999-001-00 did not raise any new issues or change the conclusion of the initial review, which was documented in NRC Inspection Report 50-315/316-99-29(DRS). The licensee entered this event into its corrective action program as CR P-99-00270. This LER is closed.
4OA6 Meetings
.1 Interim Exits
The results of the Occupational Radiation Safety - Radiation Monitoring Instrumentation and Access Control to Radiologically Significant Areas Inspection were presented to Mr. J. Pollock and other members of licensee management at the conclusion of the inspection on July 26, 2002. The licensee acknowledged the findings presented. The inspector asked the licensee whether any materials examined during the inspection should be considered proprietary. No proprietary information was identified. The inspector subsequently discussed changes to the original characterization of the findings with Mr. D. Wood on August 16, 2002.
.2 Resident Inspectors Exit
The inspectors presented the inspection results to Mr. J. Pollock and other members of licensee management at the conclusion of the inspection on October 2, 2002. The licensee acknowledged the findings presented. The inspectors asked the licensee whether any materials examined during the inspection should be considered proprietary.
Proprietary information was examined during this inspection but is not specifically discussed in this report. The inspectors subsequently discussed changes to the original characterization of the findings with Mr. J. Pollock on October 18, 2002.
.3 Exit Meeting
Exit Meeting Senior Official at Debrief:
Joseph Pollock Date:
September 27, 2002 Proprietary Information:
None Subjects:
Public Radiation Safety - Radioactive Gaseous and Liquid Effluent Monitoring and Control Change to Inspection Findings:
None KEY POINTS OF CONTACT Licensee M. Allen, Assistant Maintenance Director C. Bakken, Senior Vice President, Nuclear Generation D. Foster, Environmental Specialist J. Gebbie, Plant Engineering Assistant Director S. Greenlee, Nuclear Technical Services Director J. Grimm, System Engineer G. Harland, Work Control/Maintenance Director R. LaBurn, General Supervisor, Radiation Protection Production E. Larson, Operations Director R. Meister, Regulatory Affairs Specialist J. Molden, Acting Plant Manager D. Moul, Operations Staff Manager D. Noble, Technical Support, Radiation Protection/Environmental T. Noonan, Performance Assurance Director J. Pollock, Site Vice President B. Robinson, Radiation Protection Superintendent M. Scarpello, Regulatory Compliance Supervisor T. Summers, Chemistry Superintendent D. Wood, Radiation Protection/Environmental Manager T. Woods, Licensing Supervisor LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED Opened 50-315-02-06-01 URI Pressurizer power operated relief valve inadvertently opened during testing resulting in a loss of reactor coolant system inventory and an unusual event (Section 4OA3.2)
Closed 50-315-1999-001-01 LER General Electric HFA Relays installed in emergency diesel generators may not meet seismic qualifications (Section 4OA3.12)50-315-1999-012-01 LER Auxiliary Building ESF ventilation system may not be capable of maintaining ESF room temperatures post-accident (Section 4OA3.11)50-315-2000-08-00 LER Failure to test essential service water valves in accordance with Technical Specifications (Section 4OA3.7)50-315-2000-08-01 LER Failure to test essential service water valves in accordance with Technical Specifications (Section 4OA3.8)50-315-2000-09-00 LER Failure to perform Technical Specification valve position surveillance on leak-off valves (Section 4OA3.9)50-315-2002-03-00 LER Main steam safety valves exceed allowable lift setpoints (Section 4OA3.3)50-315-2002-05-00 LER Unit 1 manual trip due to trip of east main feedwater pump (Section 4OA3.4)50-315-2002-06-00 LER Switchyard fire results in violation of Technical Specification 3.0.5 (Section 4OA3.5)50-315-2002-07-00 LER Technical Specification 3.3.3.1 required special report for inoperable radiation monitors (Section 4OA3.6)50-316-2000-13-00 LER Safety injection valve closure at high power levels could result in exceeding PCT limits (Section 4OA3.10)50-316-2002-06-00 LER Unit 2 reactor trip due to low condenser vacuum (Section 4OA3.1)
Discussed None LIST OF ACRONYMS USED AC Alternating Current ADAMS Agency-wide Documents and Management System ANSI American National Standards Institute ARM Area Radiation Monitor ASME American Society of Mechanical Engineers CFR Code of Federal Regulations CR Condition Report DCP Design Change Procedure DRP Division of Reactor Projects DRS Division of Reactor Safety ECCS Emergency Core Cooling System EHP Electrical Maintenance Head Procedure ESF Engineered Safety Features ESW Essential Service Water FME Foreign Material Exclusion HEPA High Efficiency Particulate Air HSAS Homeland Security Advisory System IHP Instrument Maintenance Head Procedure LER Licensee Event Report LHRA Locked High Radiation Area LLD Lower Limit of Detection MHP Maintenance Head Procedure MSSV Main Steam Safety Valves NOED Notice of Enforcement Discretion NRC Nuclear Regulatory Commission OA Other Activities ODCM Offsite Dose Calculation Manual OHS Office of Homeland Security OHP Operations Head Procedure PARS Publically Available Records PI Performance Indicator PMI Plant Managers Instruction PMP Plant Managers Procedure PORV Power Operated Relief Valve Radwaste Radioactive Waste RETS Radiological Effluent Technical Specification RIS Regulatory Information Summary RP Radiation Protection RWP Radiation Work Permit SCBA Self-contained Breathing Apparatus SDP Significance Determination Process SSC Structures, Systems, and Components STP Surveillance Test Procedure TS Technical Specification UFSAR Updated Final Safety Analysis Report URI Unresolved Item LIST OF
DOCUMENTS REVIEWED
The following is a list of licensee documents reviewed during the inspection, including
documents prepared by others for the licensee. Inclusion on this list does not imply the NRC
inspectors reviewed the documents in their entirety, but rather, that selected sections or
portions of the documents were evaluated as part of the overall inspection effort. Inclusion of a
document in this list does not imply NRC acceptance of the document, unless specifically stated
in the inspection report.
1R04
Equipment Alignment
1R04.1 Partial System Walkdowns
Unit 2 West Component Cooling Water System Train
D. C. Cook Nuclear Plant Updated Final
Safety Analysis Report (UFSAR)
2-OHP-4021-016-003
Operation of the Component Cooling
Water System During Startup and Power
Operations
Revision 13
2-OHP-5030-001-001
Operations Plant Tours
Revision 20
OP-2-5135-36
Flow Diagram Component Cooling Water
Pumps and Component Cooling Water
Heat Exchangers Unit Number 2
Revision 36
PMP-4043.SLV.01
Sealed/Locked Valve List
Revision 4
Unit 2 West Charging and Safety Injection System Train
01-OHP-4021-008-002
Placing Emergency Core Cooling System
in Standby Readiness
Revision 15b
OP-2-55129-39
Flow Diagram Chemical and Volume
Control System Reactor Letdown and
Charging Unit Number 2
Revision 39
Condition Report (CR)
248048 (1)
NRC Identified a Discrepancy Between
the Normal Operating Procedure and the
Operations Flow Print for the Residual
Heat Removal Heat Exchanger Outlet
Sample Valve 1-RHR-120E/W
September 5, 2002
CR 02249046 (1)
Drawing OP-1-5143 Shows 1-IRV-300
and 1-IRV-311 as Open. NRC Inspector
Noted That These Are Normally Closed
Valves.
September 6, 2002
Unit 1 West Residual Heat Removal System Train
01-OHP-4021-008-002
Placing Emergency Core Cooling System
in Standby Readiness
Revision 15b
OP-1-5143-59
Flow Control Diagram Emergency Core
Cooling (Residual Heat Removal) Unit 1
Revision 59
Clearance Order
22825
East Residual Heat Removal Pump
September 3, 2002
CR 02248048 (1)
NRC Identified a Discrepancy Between
the Normal Operating Procedure and the
Operations Flow Print for the Residual
Heat Removal Heat Exchanger Outlet
Sample Valve 1-RHR-120E/W
September 5, 2002
Unit 2 CD Emergency Diesel Generator
2-OHP-4021-032-
008CD
Operating Diesel Generator 2CD
Subsystems
Revision 2
OP-2-5151C-47
Flow Diagram Emergency Diesel
Generator "CD" Unit 2
Revision 47
OP-2-5151D-56
Flow Diagram Emergency Diesel
Generator "CD" Unit 2
Revision 56
CR 02263059 (1)
2-LDA-245-V1, 2-LDA-245 High Pressure
Side Root Valve Has a Small Packing
Leak Evidenced by Droplet Formed
Around the Packing. Leakage Is Too
Small to Be Quantified in Drops Per
Minute.
September 20,
2002
CR 02263060 (1)
2-DL-156C, CD Emergency Diesel
Generator Full Flow Lube Oil Filter
QT-112-CD Bypass Valve, Has a Small
Packing Leak Evidenced by Lube Oil
Around the Packing Gland. Leakage Is
Too Small to Quantify in Drops Per
Minute.
September 20,
2002
CR 02263061 (1)
2-LDA-235-V2, 2-LDA-235 CD
Emergency Diesel Generator Full Flow
Lube Oil Filter QT-112-CD High D/P
Alarm Switch Low Pressure Side Root
Valve Has a Small Packing Leak. Leak
Was Too Small to Quantify in Drop Per
Minute.
September 20,
2002
CR 02264012 (1)
2-DW-246C, CD Emergency Diesel
Generator Jacket Water Surge Tank
Instrument Column Drain Valve,
Handwheel is Against Piping that
Prevents it from Cycling in Full Range
from Fully Closed to Fully Open
September 20,
2002
CR 02264017 (1)
2-DL-156C, CD Emergency Diesel Full
Flow Lube Oil Filter Bypass Valve is
Missing a Stem Spacer Between the
Handwheel and the Valve Bonnet,
Making the Valve Handwheel Loose
September 20,
2002
CR 02264019 (1)
There is No Pipe Cap Installed
Downstream of the Following Jacket
Water Sample Valves (One for Each
Diesel Generator), 2-ED-228A, 2-DG-
28C, 1-DG-227A & 1-DG-227C. CR
Generated to Request Clarification if Pipe
Caps Are Required
September 20,
2002
Miscellaneous Condition Reports
CR 02193057
Procedure Step Missed in Performance
of 1-OHP-4021-082-026
July 12, 2002
CR 02198040
While Performing 12-THP-6020-CHM-
2, the Condensate Chemical Feed
Tank Overflowed Approximately 100
Gallons
July 17, 2002
CR 02220039
Upon Stopping Unit 1 East ESW Pump,
the Unit 1 East ESW Pump Restarted
When the Control Switch Was Placed
Back in Auto
August 8, 2002
CR 02227065
2-AUX-432, Main Steam to 125 Pounds
Auxiliary Steam Pressure Reducing Valve
2-SRV-402 Inlet Shutoff Valve Was
Found in the Incorrect Position
August 15, 2002
CR 02227067
2-AUX-431, Main Steam to 125 Pounds
Auxiliary Steam Header Pressure
Reducing Valve 2-SRFV-400 Inlet Valve
Was Found Out of Position
August 15, 2002
CR 02246010
While Securing the Control Air
Compressor, a Mis-communication
Resulted in the Closing of 1-PA-128.
This Resulted in a Momentary Loss of Air
Supply to the Unit One Control Air
Header and a Lowering Pressure.
September 3, 2002
1R04.2 Complete System Walkdown
Unit 1 and 2 Essential Service Water System
D. C. Cook Nuclear Plant UFSAR
Clearance Order
22729
2-PP-7W West ESW Pump
Replacement-ground Clearance
Revision 0
Clearance Order
22726
2-PP-7W West ESW Pump
Replacement-ground Clearance
Revision 0
2-OHP-4021-019-001
Operation of the Essential Service Water
System
Revision 25
OP-1-5113-79
Flow Diagram Essential Service Water
System Unit 1
Revision 79
OP-2-5113-71
Flow Diagram Essential Service Water
System Unit 2
Revision 71
OP-1-5113A-6
Flow Diagram Essential Service Water
System Unit 1
Revision 6
OP-2-5113A-8
Flow Diagram Essential Service Water
System Unit 2
Revision 8
CR 02249018
License Renewal Project Not Able to
Locate Two ESW Valves on a Flow
Diagram
September 9, 2002
CR 02249020
License Renewal Project Identified
Potential Discrepancies in Pipe Class
Flags
September 9, 2002
1R05
Fire Protection
1R05.1
Routine Resident Inspector Tours
Section 9.8.1, "Fire Protection System"
D. C. Cook Nuclear Plant Fire Hazards
Analysis, Units 1 and 2
Revision 8
D. C. Cook Nuclear Plant Units 1 and 2
Probabilistic Risk Assessment, Fire
Analysis Notebook
February 1995
PMP 2270.CCM.001
Control of Combustible Materials
Revision 1
PMP 2270.FIRE.002
Responsibilities for Cook Plant Fire
Protection Program Document Updates
Revision 0
PMP 2270.WBG.001
Welding, Burning and Grinding Activities
Revision 0
PMP 5020.RTM.001
Restraint of Transient Material
Revision 1
Plant Managers
Instruction (PMI) 2270
Fire Protection
Revision 26
2-PPP-2270-066-001
Portable Fire Extinguisher Inspections
Revision 0a
D. C. Cook Fire Pre-Plan 078
Revision 1
D. C. Cook Fire Pre-Plan 094
Revision 1
Drawing 12-5267-10
D. C. Cook Fire Facilities Basement Plan
Revision 10
1R06
Flood Protection Measures
D. C. Cook Nuclear Plant UFSAR
D. C. Cook Nuclear Plant Units 1 and 2
Probabilistic Risk Assessment, Internal
Flooding Analysis Noted
April 1992
Engineering Action Plan 01-626, Address
Rain Intrusion/Surface Runoff
June 2001
01-OHP 4024.118
Annunciator #118 Response: Main and
Feed Pump Turbine
Revision 8
2-OHP-4024.218
Annunciator #218 Response: Main and
Feed Pump Turbine
Revision 8
01-OHP 4024.124
Annunciator #124 Response:
Containment
Revision 4
2-OHP-4024.224
Annunciator #224 Response:
Containment
Revision 3a
01-OHP-4024.105
Annunciator #105 Response:
Revision 8
2-OHP-4024.205
Annunciator #205 Response:
Revision 6
01-OHP-4024.106
Annunciator #106 Response: Residual
Heat Removal
Revision 8
2-OHP-4024.206
Annunciator #206 Response: Residual
Heat Removal
Revision 6
01-OHP-4024.116
Annunciator #116 Response:
Condensate
Revision 10
2-OHP-4024.216
Annunciator #216 Response:
Condensate
Revision 7
1R11
Licensed Operator Requalification Training
1R11.1 Resident Inspector Quarterly Review
Licensed Operator Requalification
Training Simulator Evaluation Scenario
for August 13, 2002
Licensed Operator Requalification
Training Simulator Evaluation Scenario
for September 24, 2002
1R12
Maintenance Effectiveness
PMP-5035-MRP-001
Administration
Revision 4
PMI-5035
Revision 9
Auxiliary Feedwater System
Maintenance Rule (a)(1) Action Plan
Auxiliary Feedwater System
Revision 1
Maintenance Rule Scoping Document
Auxiliary Feedwater System
Revision 1
Two-year Unavailability Report for the
Auxiliary Feedwater System
July 16, 2002
CR 02020014
Unit 2 West Motor Driven Auxiliary
Feedwater Pump Coupling Has Thrown a
Substantial Amount of Coupling Grease
on the Inside of the Coupling Guard and
on the Skid below the Coupling
January 20, 2002
CR 02041027
During 2-PP-3E Pump Start Outboard
Packing Gland Reached 190 Degrees
February 10, 2002
CR 02042004
2-PP-3E Outboard Packing Needs to Be
Re-packed
February 11, 2002
600 Volt Safety Related Power
Maintenance Rule Scoping Document
4kV/600V Electrical Distribution System
Revision 4
CR 02139005
Two Fuses Failed Over-current Test
May 19, 2002
CR 02189031
Indication on 1-MFC-111 is Erratic
July 8, 2002
CR 02095031
Relay Found Stuck During Surveillance
April 5, 2002
CR 02102011
Charger 600 Volt Starter Overload Is
Tripping
April 12, 2002
CR 02125063
Breaker Failed Test During Performance
of Surveillance
May 5, 2002
CR 02132013
During Breaker Over-current Testing, the
Breaker Failed to Trip after the Maximum
Allowable Time
May 12, 2002
Maintenance Rule Scoping Document
Revision 2
JO 01046020
DCP-744, 1-OME-150-CD, Install New
High Pressure Fuel Injector Lines
July 12, 2001
JO 02103011
1-PP-163-6R-CD, Replace Pump/Repair
as Needed
April 14, 2002
1-DCP-744
Upgrade of Emergency Diesel Generator
High Pressure Fuel Injector Lines
May 27, 2002
CR 02103011
The Unit 1 CD Emergency Diesel
Generator #6 Rear Fuel Injector Appears
to Be Mechanically Bound
April 13, 2002
Miscellaneous Condition Reports
CR 02019002
Unit 2 N-31 Source Range Detector
Indicates Approximately 1 Decade Lower
than Other Channels
January 19, 2002
CR 02032010
Unit 2 CD2 Battery Charger Tripped Off
When Alternating Current Source Was
Cross-tied.
February 1, 2001
CR 02037084
2-ESW-141, All Internal Parts of the
Valve Except Rubber Inserts Are Missing
February 6, 2002
CR 02054026
2-NRV-151, Pressurizer Train B Pressure
Relief Valve has Seat Leakage
February 23, 2002
CR 02054035
2-NRV-151, 2-NRV-152 and 2-NRV-153
Had to Be Reworked to Stop Leakage
after Maintenance Work to Refurbish the
Actuators During U2C13
February 23, 2002
CR 02055010
2-NRV-151, Pressurizer Train B Pressure
Relief Valve, Leaks-by
February 24, 2002
CR 02056091
2-PP-45-3 "Y" Axis Vibration Probe
Failed and Is Currently Defeated
February 25, 2002
CR 02060013
The 10 Meter Backup Wind Speed
Sensor Appears to Have Failed
March 1, 2002
CR 02060048
2-MRV-220 Repair Required Downpower
to Less Than 5 Percent, Which Was an
Unplanned Power Reduction Greater
Than 20 Percent and Caused a Plant
Level Event for Maintenance Rule
Purposes
March 1, 2002
CR 02081006
Found That There is No Display on the
Face of 2-MU-253 and the Alarm Is in for
this Math Unit
March 22, 2002
CR 02079004
2-SV-78-CD2 CD 2 Air Receiver Safety
Valve Was Discovered Lifting and Would
Not Reseat
March 30, 2002
CR 02092038
Steam Jet Air Ejector Radiation Monitor
Failed its Surveillance
April 2, 2002
CR 02113065
2-OHP-4030-STP-007E, East
Containment Spray System Operability
Test, Does Not Have a Maximum of 60
Gallons Per Minute Water Flow Rate for
from the Spray Addictive Tank Line with
Spray Pump on Recirculation as Stated
in TS Bases Section 3/4.6.2.2
April 23, 2002
CR 02115039
Insulator for Disconnect for K1 Breaker
Damaged During Maintenance
April 25, 2002
CR 02115046
2-ERS-2300 Declared Inoperable.
Sample Pump Will Not Start
April 25, 2002
CR 02128037
1-CCW-135 Is Leaking by During Local
Leak Rate Testing at a Rate Greater than
Allowed
May 8, 2002
CR 02136085
Tracking CR for (a)(1) Presentation for
Maintenance Preventable Functional
Failure
May 16, 2002
1R13
Maintenance Risk Assessments and Emergent Work Evaluation
PMP-2291-OLR-001
On-Line Risk Management
Revision 2
PMP-2291-SCH-001,
Data Sheet 1
Work Control Activity Scheduling Process
Sponsored Work Authorization
August 29, 2002
Industry Guideline for Monitoring the
Effectiveness of Maintenance at Nuclear
Power Plants, Section 11, "Assessment
of Risk Resulting From Performance of
Maintenance Activities"
Revision 2
Unit 2 Pressurizer Power Operated Relief Valves (PORVs) Troubleshooting
Daily Shift Managers Logs
August 20, 2002
through
August 21, 2002
Unit 2 Pressurizer PORV (2-NRV-151,
2, 153) Troubleshooting Team Meeting
Minutes
August 20, 2002
Unit 2 Pressurizer PORV (2-NRV-151,
2, 153) Troubleshooting Team Meeting
Minutes
August 21, 2002
CR 02228055
2-NRV-151 Has Excessive Seat Leakage
August 16, 2002
CR 02230010
2-NRV-153 Is Leaking Past Its Closed
Seat
August 18, 2002
CR 02230011
2-NRV-152 Leaks Past Its Closed Seat
August 18, 2002
Unit 2 West Component Cooling Water System Train Maintenance
PMP-2291-OLR-001
Data Sheet 1
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 3
July 14, 2002
through July 20,
2002
Unit 2 East Component Cooling Water System Train Maintenance
Daily Shift Managers Logs
August 28, 2002
PMP-2291-OLR-001,
Data Sheet 1
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 9
August 27, 2002
through
August 30, 2002
Unit 2 East Charging System Train Maintenance
Daily Shift Managers Logs
August 28, 2002
PMP-2291-OLR-001,
Data Sheet 1
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 9
August 25, 2002
through
August 31, 2002
Unit 1 East Residual Heat Removal System Train Maintenance
PMP-2291-OLR-001,
Data Sheet 1
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 9
August 25, 2002
through
August 31, 2002
Unit 2 West Component Cooling Water System Train Maintenance
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 3
July 14, 2002
through
July 20, 2002
Unit 2 West Essential Service Water Pump Maintenance
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 11
September 8, 2002
through
September 14,
2002
NRC Letter to Mr. A. C. Bakken III
Subject: Donald
Units 1 and 2 - Issuance of Amendments
(TAC NOS. MB5729 and MB5730)
{License Amendments 270 and 251,
Respectively}
September 9, 2002
Safety Evaluation for License
Amendment 270 to Unit One License and
License Amendment 251 to Unit Two
License
September 9, 2002
PMP 2291-OLR.001
Data Sheet 1
Work Schedule Review and Approval
Form Cycle 42, Week 11 and Cycle,
Week
September 8, 2002
through September
14, 2002
Safety Monitor Printout for 140 Hour
Allowed Outage Time License Condition
Case
July 24, 2002
CR 02253016
UFSAR Section 9.8.3.4, Item 5 Issued in
Version 17.3 Did Not Name Both
Probabilistic Risk Assessment Elements
September 11,
2002
Unit 2 Reserve Feed Transformer Maintenance
PMP-4100-SDR-001
Plant Shutdown Safety and Risk
Management
Revision 5a
PMP-5035-MRP-001
Administration
Revision 4
On-Line Risk Management Work
Schedule Review and Approval Form
Cycle 42, Week 5
July 28, 2002
through
August 3, 2002
Unit 1 On-Line Risk Status and
Unit 2 Shutdown Risk Status
July 30, 2002 and
July 31, 2001
American Electric Power Eastern System
Emergency Operating Plan
Version 3.1
June 2001
1R15
Operability Evaluations
D. C. Cook Nuclear Plant Unit 1 and 2
Technical Specifications
D. C. Cook Nuclear Plant UFSAR
Information to Licensees Regarding NRC
Inspection Manual Section on Resolution
of Degraded and Nonconforming
Conditions
Revision 1
PMP-7030-ORP-001
Revision 9
PMP 4030-001-001
Impact of Safety Related Ventilation on
the Operability of Technical Specification
Equipment
Revision 4
Calculation
MD-12-RH-129-N
Maximum Differential Pressure During
Operation of Centrifugal Charging Pump
Suction Valves 1-IMO-910, 1-IMO-911,
2-IMO-910, & 2-IMO-911
Revision 2
CR 01020010
2-HV-AES-2 Fan Was Discovered
Rotating Backwards Due to Backdraft
Damper Being Open
January 20, 2001
CR 02113065
2-OHP-4030-STP-007E, East
Containment Spray System Operability
Test, Does Not Have a Maximum of 60
Gallons Per Minute Water Flow Rate for
from the Spray Addictive Tank Line with
Spray Pump on Recirculation as Stated
in TS Bases Section 3/4.6.2.2
April 23, 2002
CR 02116032
1-HV-AES-2 Exhaust Fan Was Found in
Standby With its Backdraft Damper Stuck
Partially Open and the Fan Rotating
Backwards
April 26, 2002
CR 02122057
1-IMO-911 Could Not Be Set Within the
Prescribed Thrust Limitations Provided in
VDS-1-IMO-911
May 2, 2002
CR 02125016
Potentially High Boron Concentration
(Above 2600 Parts Per Million) in Unit 1
Reactor Coolant System in Mode 4
Shortly Before Entering Mode 5
May 5, 2002
CR 02141011
During the Performance of 1-EHP-4030-
28-229, Section 4.7, Outside Air Control
Room Ventilation Dampers Would Not
Seal
May 21, 2002
CR 0214013
Unit 1 "CD" Engine 4R Cylinder Injector
Return Line has Separated Ferrule
May 21, 2002
CR 02186022
Procedure Noncompliance on Call Made
on CR 02137011 for Inservice Testing
Stroke Time Failure of Steam Generator
PORV 2-MRV-233
July 5, 2002
CR 02238004
Significant Ice Buildup Was Found in
Unit 1 Ice Condenser During Operations
Ice Tour
August 25, 2002
CR 02245008
Thermal Power Calorimetric in Unit Two,
Displayed "Unknown" Quality for Loop 3
and 4 Enthalpy While 2-FPI-230, S/G #3
Feed Pressure Channel was being
Calibrated
September 2, 2002
CR 02264018
Unit 1 Control Room Door Was Propped
Open Without Specific Procedure
Guidance to Allow It to Be Open
September 21,
2002
1R16
Operator Workarounds
PMP-4010-OWA-001
Oversight and Control of Operator
Workarounds
Revision 1
NRC Inspection Manual
Temporary Instruction
2515/138
Evaluation of the Cumulative Effect of
Operator Workarounds
Work Around Review Board Meeting
Agenda
July 24, 2002
Work Around Review Board Meeting
Minutes
July 24, 2002
Work Around Review Board Meeting
Agenda
September 25,
2002
Unit 1 Operator Workarounds
July 16, 2002
Unit 2 Operator Workarounds
July 16, 2002
Unit 1 Operator Workarounds
September 23,
2002
Unit 2 Operator Workarounds
September 23,
2002
Unit 1 Operator Workarounds
Contingency Actions for Reactor
Operators
September 24,
2002
Unit 1 Operator Workarounds
Compensatory Actions for Auxiliary
Equipment Operators
September 24,
2002
Unit 2 Operator Workarounds
Contingency Actions for Reactor
Operators
September 24,
2002
Unit 2 Operator Workarounds
Compensatory Actions for Auxiliary
Equipment Operators
September 24,
2002
CR P-99-03751
Demineralized Water Makeup to Control
Room Air Conditioning Units Appears
Possibly to Have a Design to Be
Operated in the Automatic Mode and We
Operate in the Manual Mode
February 26, 1999
CR 02106030
Generate a Routine Task to Cycle ESW
Valve 1-ESW-115 on a Monthly Basis
April 16, 2002
CR 02106032
Generate a Routine Task to Cycle ESW
Valves 2-ESW-240 and 2-ESW-145 on a
Monthly Basis
April 16, 2002
CR 02140025
1-QFC-411 Did Not Show Any Indication
of Flow with Flow Actually Present
May 20, 2002
CR 02152005
The Control Valve Does Not
Automatically Control the Pressure in the
Chilled Water System for the Control
Room Air Conditioning System
June 1, 2002
CR 02210010 (1)
Operator Workaround Board Aggregate
Impact Attachment and Minute Meetings
Were Not Performed in Accordance with
Procedure
July 29, 2002
CR 02229001
The Makup Pump South Middle Prefilter
Automatic Regeneration Timer Control
Box Does Not Function as Designed
August 17, 2002
CR 02230003
While Operating the Steam Generator
Blowdown System on the Normal Blow
Down Tank with the Effluent Aligned to 2-
DRV-350 Frequent Blow Down Low
Sample Alarms Were Received
August 18, 2002
CR 02231001
1-SV-101 (Nitrogen Supply Header to
Accumulator Tanks Safety Valve) Lifted
During Performance of
01-OHP-4021-008-006 (Adjusting
Pressure in Accumulator)
August 19, 2002
CR 02234103
The Screen Save Time Out Function on
the Radiation Monitoring System Control
Terminal in the Radiation Protection
Office Varies From Less Than One
Minute to Over Seven Minutes
August 22, 2002
CR 02236013
1-CMO-429-PI Control Room Position
Indicator Doesnt Move While Valve is
Operated and Is Indicating Approximately
Percent Open with the Valve Fully
Closed
August 24, 2002
CR 02246018
2-WMO-101 Low Pressure Turbine "A"
Northeast Circulating Water Inlet Valve
Continues to Drift Off the Open Seat and
Not Evaluated for Operator Workaround
or Repetitive Action on Equipment
Condition
September 3, 2002
1R17
Permanent Plant Modifications
Design Change
Procedure (DCP) 5173
Unit 1 Provide Essential Service Water
Minimum Flow Path Via Containment
Spray System Heat Exchanger
Revision 0
DCP 5174
Unit 2 Provide Essential Service Water
Minimum Flow Path Via Containment
Spray System Heat Exchanger
Revision 0
Owners Acceptance
Review of AEP-01-119
Large Break Loss of Coolant Accident
Evaluation for Reduced Containment
Spray Temperature
September 17,
2001
AEP-99-480
Westinghouse Sub-atmospheric
Containment Evaluation Report
December 20,
1999
1R19
Post Maintenance Testing
Unit 2 West Component Cooling Water System Train Maintenance
Job Order (JO)
C0192651
Perform Inservice Stroke Time Test of
2-CMO-414
July 21, 2002
JO R0220063
Perform Operability Test of 2-PP-10W
Supply Breaker
July 21, 2002
JO R0222866
Place in Service (Post Maintenance Test)
2-PP-10W
July 21, 2002
JO R0228055
Support Leak Check and Perform Post
Maintenance Test of 2-PP-10W
July 21, 2002
JO R0229289
West Component Cooling Water Loop
Surveillance
July 21, 2002
JO R0231895
West Component Cooling Water Loop
Flow Path Verification
July 21, 2002
2-OHP-4030-216-020W
West Component Cooling Water Loop
Surveillance Test
Revision 1
Engineering Programs
Technical Data Book
Figure 2-15.1
Safety Related Pump Inservice Test
Hydraulic Reference
Revision 59
Engineering Programs
Technical Data Book
Figure 2-15.2
Safety Related Pump Inservice Test
Vibration Reference
Revision 52
Engineering Programs
Technical Data Book
Figure 2-19.1
Power Operated Valve Stroke Time
Limits
Revision 56
Unit 2 East Auxiliary Feedwater Pump Maintenance
2-OHP-4030-STP-017E
East Motor Drive Auxiliary Feedwater
System Test
Revision 10
Engineering Programs
Technical Data Book
Figure 2-15.1
Safety Related Pump Inservice Test
Hydraulic Reference
Revision 60
Engineering Programs
Technical Data Book
Figure 2-15.2
Safety Related Pump Inservice Test
Vibration Reference
Revision 53
Engineering Programs
Technical Data Book
Figure 2-19.1
Power Operated Valve Stroke Time
Limits
Revision 56
Engineering Control
Package 1-2-F2-01
Feedwater Flow Instrumentation
Revision 19
CR 02219071
Increasing Vibration Levels on 2-PP-3E
Motor
August 7, 2002
CR 02221033
While Performing 02-OHP-4030-STP-
017E, Erratic Flow Oscillations Were
Observed on the Common Emergency
Leak-off/Test Line Test Instrument
August 9, 2002
CR 02221037
Job Order Step Was Not Completed As
Written
August 9, 2002
CR 02226074 (1)
Completeness of Documentation and
Review Issues Associated With Recent
Performances of 02-OHP-4030-STP-
017E Identified by NRC Senior Resident
Inspector
August 14, 2002
Unit 1 East Residual Heat Removal System Train Maintenance
JO R0209505
Lubricate and Clean Residual Heat
Removal Pump 1-PP-35E Motor
September 5, 2002
01-OHP-4030-STP-050E
East Residual Heat Removal Train
Operability Test Modes 1-4
Revision 9
Unit 2 North Safety Injection Pump Maintenance
2-OHP-STP-051N
North Safety Injection Pump System Test
Revision 11
OP-2-5142-44
Flow Diagram Emergency Core Cooling
Revision 44
Unit 2 AB Emergency Diesel Generator Maintenance
JO R0097099-03
Post Maintenance Test for Time Delay
Relay 2-62-1-LQBA-DGAB
September 21,
2002
JO R0097141-05
Support Instrument Maintenance Post
Maintenance Test of AB Diesel Time
Delay Relays
September 21,
2002
JO R0216722-02
Rack Out/Rack In 2-T21A11 for Post
Maintenance Test
September 21,
2002
JO R0216737-02
Rack In and Cycle 2-21A5
September 21,
2002
JO R0216751-02
Rack Out/Rack In 2-T21B4
September 21,
2002
JO R0216756-03
2-T-131-5, Verify Operability
September 21,
2002
JO R0216757-03
2-T-131-6, Verify Operability
September 21,
2002
JO R0221576-02
2-QT-111-AB, Run Pump to Verify Proper
Operation
September 21,
2002
JO R0232273-01
Quarterly Inservice Test AB1 Fuel
Transfer Pump
September 21,
2002
JO R0233374-01
Alternate ESW Supply Valve Testing
September 21,
2002
JO R0234524-02
STP 027AB Diesel Generator 2AB Slow
Start
September 21,
2002
2-OHP-4030-STP-
27AB
AB Diesel Generator Operability Test
(Train B)
Revision 18
2-OHP-4021-082-020
Removal and Restoration of Power to
600 Volt Bus 21A and Associated Motor
Control Centers
Revision 3
2-OHP-4021-032-008AB
Operating DG2AB Subsystems
Revision 2
Unit 2 West Essential Service Water Pump Replacement
2-DCP-5260-TP-U2W
Unit 2 West Essential Service Water
Pump Performance and Full Flow Test
September 17,
2002
2-LDCP-5260
Essential Service Water Pump Upgrades
for Reliability
Revision 0
2-OHP-4030-219-022W
West Essential Service Water System
Test
Revision 2
Engineering Programs
Technical Data Book
Figure 2-15.1
Safety Related Pump Inservice Test
Hydraulic Reference
Revision 61
Engineering Programs
Technical Data Book
Figure 2-15.2
Safety Related Pump Inservice Test
Vibration Reference
Revision 54
Engineering Programs
Technical Data Book
Figure 2-19.1
Power Operated Valve Stroke Time
Limits
Revision 56
Unit 2 East Centrifugal Charging System Train Maintenance
JO R022245101
Lube and Clean 2-PP-50E-MTR
August 29, 2002
JO R022245202
Clean Filter/Lube Couplings
August 29, 2002
JO R022777602
Drain and Refill Speed Increaser
August 29, 2002
2-OHP-4030-STP-052E
East Centrifugal Charging Pump
Operability Test
Revision 11
Engineering Programs
Technical Data Book
Figure 2-15.1
Safety Related Pump Inservice Test
Hydraulic Reference
Revision 60
Engineering Programs
Technical Data Book
Figure 2-15.2
Safety Related Pump Inservice Test
Vibration Reference
Revision 53
Unit 2 East Component Cooling Water System Train Maintenance
JO R022779501
Drain and Refill Unit 2 East Component
Cooling Water Pump Oil Reservoir
August 29, 2002
JO R021620801
Calibrate Protective Relays for Breaker
August 29, 2002
2-IHP-6030-RLY-002
General Electric Type PJC Instantaneous
Relay Calibration and Maintenance
Revision 2
2-OHP-4030-216-020E
East Component Cooling Water Loop
Surveillance Test
Revision 1
Engineering Programs
Technical Data Book
Figure 2-15.1
Safety Related Pump Inservice Test
Hydraulic Reference
Revision 60
Engineering Programs
Technical Data Book
Figure 2-15.2
Safety Related Pump Inservice Test
Vibration Reference
Revision 53
Engineering Programs
Technical Data Book
Figure 2-19.1
Power Operated Valve Stroke Time
Limits
Revision 56
Miscellaneous Condition Reports
CR 02194001
Loss of Oil Level in 2-PP-4 (Turbine
Driven Auxiliary Feedwater Pump)
Turbine Oil Sump
July 13, 2002
1R20
Refueling and Outage Activities
1R20.1 Unit 2 Forced Outage
D. C. Cook Nuclear Plant Unit 2
Technical Specifications
D. C. Cook Nuclear Plant UFSAR
01-OHP-4021-001-004
Plant Cooldown From Hot Standby to
Cold Shutdown
Revision 36
OHP 4021-017-002
Placing In Service The Residual Heat
Removal System
Revision 16
01-OHP-4021-001-002
Reactor Startup
Revision 27a
01-OHP-4030-114-030
Daily and Shiftly Surveillance Checks
Revision 0
PMP 4100-SDR-001
Plant Shutdown Safety and Risk
Management
Revision 5, C1
Daily Shift Managers Logs
July 27, 2002
through
August 2, 2002
CR 02208007
2-WMO-23 Appears to Have Failed
Closed
July 27, 2002
1R22
Surveillance Testing
D. C. Cook Nuclear Plant UFSAR
D. C. Cook Nuclear Plant Technical
Specifications
2-OHP-4030-STP-030
Daily and Shiftly Surveillance Checks
performed on July 2, 2002 for Unit 2
Revision 39
EHP 6040-PER-323
Flux Mapping System Operation and
Supportive Data Collection
Revision 4a
2-IHP-4030-STP-511
Train B Reactor Protection System and
Engineered Safety Features Reactor Trip
Breaker and Solid State Protection
System Automatic Trip/Actuation Logic
Functional Test
Revision 4
01-IHP-4030-SMP-103
Reactor Coolant Flow Protection Set III
Functional Test and Calibration
Revision 4
01-IHP-4030-SMP-104
Delta T/Tavg Protection Set I Functional
Test and Calibration
Revision 4
CR 02135079
On May 15, 2002, During the Unit 2
Power Ascension, the N-35 Rod Stop
Bistable Actuated Prior to the Blocking of
P-10. It Was Subsequently Determined
that the N-35 and N-36 Trip and Rod
Stop Setpoints/Resets Need to Be Reset
May 15, 2002
CR 02204023
Inservice Test for the 1W Containment
Spray Pump Was Completed Without
Using the Correct Reference Values
July 23, 2002
1R23
Temporary Plant Modifications
D. C. Cook Nuclear Plant UFSAR
2-TM-00-57-R1
On-line Leak Repair of 2-FW-118-4
March 19, 2002
2-EHP-5040-MOD-001
Revision 9
2-MHP-5021-001-051
Installation of Temporary On-line Leak
Sealing
Revision 7
JO 00267043-01
2-FW-118-4 Temporary Leak Seal
April 12, 2002
CFR 50.59 Safety
Screening 2000-2016-00
2-FW-118-4 Temporary Leak Seal
September 29,
2000
CFR 50.59
Applicability
Determination
2002-0494-00
Temporary Modification 2-TM-00-57-R1
March 15, 2002
NRC Inspection Manual
Part 9900 Technical
Guidance
On-line Leak Sealing Guidelines for
ASME [American Society of Mechanical
Engineers] Code Class 1 and 2
Components
July 15, 1997
Unisolatable Reactor Coolant System
Leak Following Repeated Applications of
Leak Sealant
December 1, 1993
CR 02263047 (1)
Completed Procedure was not Vaulted as
Required
September 20,
2002
CR 02263057 (1)
The Completed Signed Off Version of the
Furmanite package/procedure Could Not
Be Located
September 20,
2002
1EP6
Drill Evaluation
Cook Nuclear Plant Emergency Plan
Training Drill Scenario August 22, 2002
Revision 1
Desktop Guide for Emergency Planning
Performance Indicators
Revision 2
PMP-2080-EPP-107
Notifications
Revision 16
2OS1 Access Controls for Radiologically Significant Areas
2-THP-6010-RPP-006
Radiation Work Permit Processing
Revision 17
PMP-6010-RPP-003
High, Locked High, and Very High
Radiation Area Access
Revision 10
2-THP-6010-RPP-016
Radiation Protection Department Shift
Technician Responsibilities
Revision 4
THG.026
Locked High Radiation Area and Very
High Radiation Area Shiftly Verification
Process
Revision 0
Administrative Guideline
High, Locked High and Very High
Radiation Area Controls
Revision 0
Radiation Protection Department Key
Inventory Log
January 1, 2002
through
July 23, 2002
Radiation Protection Department Key
Issuance/Return Log
January 1, 2002
through
July 23, 2002
PMP-2220-001-001
Revision 2a
Non Fuel Related Spent Fuel Pool
Inventory
July 2002
CR 02055004
Key Log Inventory Not Performed
February 24, 2002
CR 02126004
Locked High Radiation Area Posting
May 5, 2002
CR 02153015
601 Pipe Tunnel Floor Hatch Improperly
Posted
June 2, 2002
CR 0219900
Results of Institute of Nuclear Power
Operations Assist Visit
July 18, 2002
2OS3 Radiation Monitoring Instrumentation and Protective Equipment
2-THP-6010-RPP-500
Radiation Protection Instruments
Revision 1
2-THP-6010-RPI-500
Instrument Issue and Operational Testing
Revision 13
2-THP-6010-RPI-805
Radiation Monitoring System Setpoints
Revision 14
Activity Information for Instrument Check
Sources
Various Dates
Form RP-572-a
Portal Monitor Calibration Data Sheet
(Monitor # POR-454)
April 20, 2002
Form RP-818-b
DA1-8 Area Monitor Calibration Data
Sheet (U-1 North Seal Water Injection
Filter Cubicle)
July 18, 2001
Form RP-818-b
DA1-8 Area Monitor Calibration Data
Sheet (U-2 South Seal Water Injection
Filter Cubicle)
March 5, 2002
Form RP-818-b
DA1-8 Area Monitor Calibration Data
Sheet (U-1 West Centrifugal Charging
Pump Room)
July 18, 2001
2-THP-6010-RPC-818
Eberline Radiation Monitoring System
DA1-8 Area Monitor Calibration
Revision 1
2-THP-06010-RPC-566
Source Characterization and Verification
for the J. L. Shepherd Models M89 and
M142-S
Revision 5b
2-THP-06010-RPC-566,
Data Sheet 1
Shepherd Model 89 Exposure Rate
Verification Data Sheet (Instrument M89-
and M89-2)
January 30, 2002
Global Calibration Laboratory Calibration
Data Sheet (Ion Chamber Model 20X5-
180, Serial # 21822 and Electrometer
Model 2025, Serial # 5878)
May 2002
UFSAR, Table 11.3-1
Radiation Monitoring System Channel
Sensitivities and Detecting Medium
Revision 17
1-IHP-6030-IMP-311
Calibration of High Range Containment
Radiation Monitor VRA-1310
December 20,
2001
1-IHP-6030-IMP-312
Calibration of High Range Containment
Radiation Monitor VRA-1410
December 15,
2001
2-IHP-6030-IMP-411
Calibration of High Range Containment
Radiation Monitor VRA 2310
March 13, 2002
2-IHP-6030-IMP-412
Calibration of High range Containment
Radiation Monitor VRA 2410
September 13,
2001
2-IHP-6030-IMP-679
Seal Water Filter Cubicle Area Radiation
Monitor 2-ERS-8400 Functional Check
and Instrument Calibration
Revision 2
1-IHP-6030-IMP-579
Seal Water Filter Cubicle Area Radiation
Monitor 1-ERS-7400 Functional Check
and Instrument Calibration
Revision 1
2-THP-6010-RPP-201
Maintenance and Repair of Respiratory
Devices
Revision 6
SCBA Inventory and Location Chart
Undated
RP Form 201-02
SCBA Inspections
May 2002 through
July 2002
List of Users Qualified to Perform SCBA
Inspections/Tests
Undated
MSA Training Certificate
Certificate for Specified RP Technician
July 24, 2001
MSA Instruction Manual
Portable Regulator Tester III
Undated
SCBA Regulator Calibration Log
July 24, 2002
PMP-6010-RPP-201
Control and Use of Respiratory
Protection Devices
Revision 10
SCBA Training/Qualification Matrices For
Selected Emergency Response
Organization Members
July 25, 2002
D. C. Cook Emergency
Plan
Planning Standard J - Protective
Response
Revision 17
Self-Assessment
SA-2001-SPS-002
SCBA Qualifications of Maintenance
Personnel Assigned to the Operations
Staging Area
January 29, 2001
CR 02048049
Back-up Compressor Grade-D Air
Sample
February 17, 2002
CR 02050073
Breathing Air Quality Checks
February 19, 2002
CR 02052015
Emergency Response Air Packs Not
Serviced Timely
February 21, 2002
2PS1
Radioactive Gaseous and Liquid Effluent Treatment and Monitoring Systems
Annual Radioactive Effluent Release
Report
January 1, 1999 to
December 31,
1999
Annual Radioactive Effluent Release
Report
January 1, 2000 to
December 2000
Annual Radioactive Effluent Release
Report
January 1, 2001 to
December 31,
2001
PMP-6010-OSD.001
Offsite Dose Calculation Manual
Revision 17
2-THP-6010-RPI-805
Radiation Monitoring System Setpoints
Revision 14
2-THP-6010-RPI-805;
Data Sheet 1
Setpoint Determination for Unit 1
Condenser Exhaust Low Range Noble
Gas
April 17, 2002
2-THP-6010-RPI-805;
Data Sheet 1
Setpoint Determination for Unit 2 Unit
Vent Low Range Noble Gas
March 27, 2002
RP-8053
RMS High Alarm Setpoint/General
Parameter Change; Unit 1 Essential
Service Water Heat Exchanger
August 17, 1996
2-THP-6020-CHM-308
Effluent Batch Releases
Revision 5d
2-THP-6010-RPP-603
Gaseous Waste Releases (Manual
Calculations)
Revision 10b
01-EHP-4030.128.228A
1-HV-AES-1 Engineered Safety Feature
Ventilation Surveillance
November 21,2001
2-EHP-4030.228.228B
2-HV-AES-2 Engineered Safety Feature
Ventilation Surveillance
December 7, 2001
2-EHP-4030.228.228A
2-HV-AES-1 Engineered Safety Feature
Ventilation Surveillance
October 1, 2001
01-EHP-4030.128.228B
1-HV-AES-2 Engineered Safety Feature
Ventilation Surveillance
December 11,
2001
01-EHP-4030.128.228B
1-HV-AES-2 Engineered Safety Feature
Ventilation Surveillance
August 13, 2002
2-THP-6010-RPP.007
RP Calculation for Determination of
Reference Response to Beta Disc
Source Set for Eberline RDA-3A
Detectors
2-THP-6010-RPC-810
Data Sheet 1; Calibration Record for Unit
Condenser Air Ejector Exhaust Monitor
September 5, 2001
2-THP-6010-RPC-810
Data Sheet 1; Calibration Record for Unit
Vent Exhaust Monitor
October 16, 2001
2-THP-6010-RPC-810;
Data Sheet 1
Calibration Record for Unit 1 Vent
Exhaust Monitor
July 13, 2001
Form RP 8021
Calibration Record for Unit 1 Steam
Generator Blowdown Monitor
July 6, 2002
Form RP 8021
Calibration Record for Unit 2 Steam
Generator Blowdown Monitor
July 6, 2002
Form RP-8021
Calibration Record for Unit 1 Essential
Service Water Monitor (East Heat
Exchanger)
August 13, 2002
Form RP-8021
Calibration Record for Unit 1 Essential
Service Water Monitor (West Heat
Exchanger)
January 9, 2002
Form RP-8021
Calibration Record for Unit 2 Essential
Service Water Monitor (East Heat
Exchanger)
January 7, 2002
Form RP-8021
Calibration Record for Unit 2 Essential
Service Water Monitor (West Heat
Exchanger)
March 28, 2002
2-THP-6010-RPC-810;
Data Sheet 1
Calibration Record for Common Unit
Liquid Radwaste Line
November 15,
2001
1IHP-4030-SMP.301
Turbine Gland Seal Exhaust Condenser
Vent Gaseous Effluent Flow Functional
Test and Calibration
November 30,
2001
1IHP-4030-SMP.302
Auxiliary Building Ventilation Gaseous
Effluent Flow Functional Test and
Calibration
November 30,
2001
IHP-4030-SMP.401
Turbine Gland Seal Exhaust Condenser
Vent Gaseous Effluent Flow Functional
Test and Calibration
November 30,
2001
IHP-4030-SMP.402
Auxiliary Building Ventilation Gaseous
Effluent Flow Functional Test and
Calibration
November 30,
2001
THP-6010-RPP.007
RP Calculation for Determination of Low
Range Noble Gas Detector Calibration
Constant
June 18, 1997
2-THI-2291-ADM-012
Work Control Process
Revision 2c
2-THP-6020-CHM-322
Vent Stack Gaseous Sampling
Revision 1
Results of Radiochemistry Cross Check
Program
First and Second
Quarters 2002
Energy Calibration Records for Gamma
Spectroscopy Equipment
July 1, 2002
Efficiency Check Records for Gamma
Spectroscopy Equipment
April and May 2002
LLD Determinations for Gamma
Spectroscopy Equipment
May 2002
CR 02270029
Poor Quality Evaluation of CR 02204001
September 27,
2002
Ten Year Summary Data for Liquid and
Gaseous Effluent Releases
CR 02253014
Chemistry Liquid Scintillation Counter
Beta/Alpha Analysis Methods Found
Outside of Acceptance Criteria
September 10,
2002
CR Data Base Listing for Effluent
Monitoring and Controls
September 2001 -
September 2002
CR 0204001
Late Channel Functional Test
July 23, 2002
Radiation Monitoring System Health
Data, A(1) Action Plans, and Reliability
Improvement Plans for Variety of Effluent
Monitors
2001 - September
2002
RP Self-Assessment
Report
ODCM and Effluents
August 2001
Performance Assurance
Field Observation
Gas Decay Tank Release
January 27, 2002
Performance Assurance
Field Observation
Readiness to Perform Steam Generator
Drains
January 22, 2002
Performance Assurance
Audit (PA-01-06)
Chemistry Program
January 11, 2002
4OA1 Performance Indicator (PI) Verification
Regulatory Assessment Performance
Indicator Guideline
Revision 2
Special Plant Procedure
2060-SFI-101
PI Data Gathering
Revision 0
Regulatory Oversight Program PI
Revision 1
Radiologically Controlled Area Electronic
Dosimetry Exit Transactions Summary
Report
January 1, 2002
through
July 18, 2002
CR Database for All Radiation Protection
Department Initiated or Assigned Issues
January 1, 2002
through
July 18, 2002
Letter from
- J. Pollock, American Electric
Power, to the US NRC, Subject: "Cook
Unit 1 and 2 -- 4Q2001 -- PI Data
Elements (QR and CR)"
January 17, 2002
Letter from
- J. Pollock, American Electric
Power, to the US NRC, Subject: "Cook
Unit 1 and 2 -- 1Q2002 -- PI Data
Elements (QR and CR)"
April 19, 2002
Letter from
- J. Pollock, American Electric
Power, to the US NRC, Subject: "Cook
Unit 1 and 2 -- 2Q2002 -- PI Data
Elements (QR and CR)"
July 18, 2002
Unavailability Report for Emergency
Diesel Generators
October 1, 2001
through
June 30, 2002
Unavailability Report for Auxiliary
Feedwater System
October 1, 2001
through
June 30, 2002
CR 01355058 (1)
Inconsistent Reporting of Unavailable
Hours for the Maintenance Rule and the
Reactor Oversight Process for the Same
Conditions
December 21,
2001
CR 01355071 (1)
Safety System Unavailable Hours
Reported in the Reactor Oversight
Process for the 4Q2000 and 1Q2001
Were Reported for the Wrong Train
December 21,
2001
Chemistry Radiochemical Analysis
Results for Selected Periods in 2002,
Offsite Dose Calculation Data Sheets for
Selected Periods in 2001 and 2002 and
Liquid /Gaseous Effluent Dose Summary
Information for November 2001 -
September 2002
4OA3 Event Follow-up
4OA3.1 Unit 2 Reactor Trip and Restart Following Loss of Main Condenser Vacuum
Unit 2 Automatic Reactor Trip Due to
Loss of Main Condenser Vacuum
July 22, 2002
PMP 4010.TRP.001
Data Sheet 1
Unit Two Reactor Trip Review Report
July 22, 2002
LER 316-2002-006-00
Unit 2 Reactor Trip Due to Low
Condenser Vacuum
September 6, 2002
2-OHP-4021-057-006
Operation of Main and Feed Pump
Condensers
Revision 11
Shift Managers Daily Logs
July 22, 2002
CR 02203001
Unit 2 Reactor Automatically Tripped
From 100 Percent Power While Flushing
Main Turbine Condenser Waterboxes
July 22, 2002
CR 02203007
Excessive Reactor Coolant System
Cooldown After Automatic Unit 2 Reactor
Trip
July 22, 2002
CR 02203019
The Closure Time for Unit 2 Main Turbine
Stop Valve "C" Was Abnormally Slow
After the Turbine Trip
July 22, 2002
CR 02203023
Procedure Enhancement for
OHP-4021-057-006, Attachment 9,
"Flushing of Circulating Water Side of
Condenser Halves"
July 22, 2002
CR 02203026
2-MRV-230, The Steam Generator #2
Main Steam Stop Drifts Closed If the
Control Switch is Not in the Open
Position
July 22, 2002
4OA3.2
Pressurizer Power Operated Relief Valve Inadvertently Opened During
Testing Resulting in a Loss of Reactor Coolant System Inventory and an
Unusual Event
Unit 1 Declared an Unusual Event Due to
Reactor Coolant System Leakage
Greater Than 25 Gallons-Per-Minute
During Surveillance Testing
June 6, 2002
01-OHP-4030-102-017
Pressurizer PORV Actuation Channel
Calibration with Valve Operation (for
Modes 1, 2, and 3)
Revision 0
01-OHP-4030-102-017
Pressurizer PORV Actuation Channel
Calibration with Valve Operation (for
Modes 1, 2, and 3)
Revision 1
Daily Shift Managers Logs
June 5, 2002
through
June 6, 2002
CR 02157039
Pressurizer PORV 1-NRV-153 Opened
During Testing with its Block Valve Open,
Causing an Unexpected Release of
Reactor Coolant System Inventory into
the Pressurizer Relief Tank
June 6, 2002
CR 02157101
Evaluate Timeliness of NRC Notification
for Unusual Event Declared Based on
PORV Opening on June 5, 2002 at 23:00
June 6, 2002
4OA3.3
LER 315-2002-003-00, "Main Steam Safety Valves Exceeded Allowable Lift
Setpoints"
LER 315-2002-003-00
Main Steam Safety Valves Exceeded
Allowable Lift Setpoints
June 28, 2002
American Society of
Mechanical Engineers
(ASME) / American
National Standards
Institute (ANSI)
OMa-1988
Addenda to ASME/ANSI OM-1987,
Operation and Maintenance of Nuclear
Power Plants
February 15, 1989
Guidelines for Inservice Testing at
Nuclear Power Plants
April 1995
CR P-99-09868
High Failure Rate of the Main Steam
Safety Valves "As Found" Lift Pressure
April 29, 1999
CR 02122063
1-SV-2A-2 Failed the As Found Set Point
Test
May 2, 2002
CR 02123003
1-SV-1B-3 Failed the As Found Set Point
Test
May 3, 2002
CR 02123037
1-SV-2B-1 Failed the As Found Set Point
Test
May 3, 2002
CR 02123039
1-SV-1B-1 Failed the As Found Safety
Valve Testing
May 3, 2002
CR 02123049
1-SV-1A-4 Failed the As Found Safety
Valve Testing
May 3, 2002
CR 02123050
1-SV-2B-4 Failed the As Found Set Point
Test
May 3, 2002
CR 02123053
1-SV-1B-4 Failed the As Found Set Point
Test
May 3, 2002
CR 02125027
Main Steam Safety Valves Failed As
Found Test and Were Not Adjusted As
Required by the Code
May 5, 2002
CR 02198006
Incorrect Information Within Reportability
Evaluation for CR 02122063
July 17, 2002
4OA3.4
LER 315-2002-005-00, "Unit 1 Manual Trip Due to Trip of East Main
Feedwater Pump"
LER 315-2002-005-00
Unit 1 Manual Trip Due to Trip of East
Main Feedwater Pump
August 13, 2002
CR 02165064
Manual Reactor Trip Due to a Loss of the
East Main Feedwater Pump Following
Start of the #13 Circulating Water Pump
June 14, 2002
4OA3.5
LER 315-2002-006-00, "Switchyard Fire Results in Violation of Technical Specification 3.0.5"
LER 315-2002-006-00
Switchyard Fire Results in Violation of
August 2, 2002
NOED-02-3-002
NRC Letter to Mr.
Subject: "Notice of Enforcement
Discretion for Indiana Michigan Power
Company Regarding
- D. C. Cook, Units 1
and 2 (NOED-02-3-002)"
June 18, 2002
CR 02163045
1-52-L Has Had a Catastrophic Failure
Resulting in a Loss of Offsite Power
Sources Supplied to Reserve Feed
June 12, 2002
4OA3.6
LER 50-315-2002-007-00, "Technical Specification 3.3.3.1 Required Special
Report for Inoperable Radiation Monitors"
LER 50-315-2002-007-00
Technical Specification 3.3.3.1 Required
Special Report for Inoperable Radiation
Monitors
August 22, 2002
CR 02174004
While Performing 1-OHP-4030-114-030,
Daily Surveillance Found that the Wrong
Parameters Were in the File for 1-VRA-
1310 Containment High Range Area
Monitor
June 23, 2002
CR 02199084
An Opportunity Existed to Avoid a
Licensee Event Report, but was Missed
July 18, 2002
4OA3.7
LER 50-315-2000-008-00, "Failure to Test Essential Service Water Valves in
Accordance with Technical Specifications"
LER 50-315-2000-008-00
Failure to Test Essential Service Water
Valves in Accordance with Technical
Specifications
December 12,
2000
CR P-00-04744
ESW from East/West Heat Exchanger
Outlet Valves Past Operabilty Concern
March 27, 2000
CR 00314038
The Condition Evaluation for Condition
Report 00-04744 Was Inadequate
November 9, 2000
4OA3.8
LER 50-315-2000-008-00, "Failure to Test Essential Service Water Valves in
Accordance with Technical Specifications"
LER 50-315-2000-008-01
Failure to Test Essential Service Water
Valves in Accordance with Technical
Specifications
December 7, 2001
4OA3.9
LER 315-2000-009-00, "Failure to Perform Technical Specification Valve
Position Surveillance on Leak-off Valves"
LER 315-2000-009-00
Failure to Perform Technical
Specification Valve Position Surveillance
on Leak-off Valves
January 8, 2001
01-OHP-4030-STP-010
Containment Isolation
Revision 18
2-OHP-4030-208-053A
ECCS [Emergency Core Cooling System]
Valve Operabilty Test Train A
Revision 0
2-OHP-4030-208-053B
ECCS Valve Operabilty Test Train B
Revision 0
DCC-NEMP-306-QCN
Containment Isolation System
Licensing/Design Bases Requirements
Revision 1
Design Information
Transmittal B-02045-00
Containment Isolation Barrier Review
June 6, 2001
OP-1-5146A-34
Ice Condenser Refrigeration Unit 1
Revision 34
OP-2-5146A-19
Ice Condenser Refrigeration Unit 2
Revision 19
CR 00341030
Inadequate Surveillance of 1-RH 110E/W
for Containment Integrity
December 6, 2000
4OA3.10
LER 50-316/2000-013-00, "Safety Injection Valve Closure at High Power
Levels Could Result in Exceeding Peak Centerline Temperature Limits"
LER 50-316/2000-013-00
Safety Injection Valve Closure at High
Power Levels Could Result in Exceeding
Peak Centerline Temperature Limits
October 13, 2000
CR P-00-11217
Unit 2 Outside Safety Limits During High
Head Safety Injection Discharge Valves
Testing
August 11, 2000
4OA3.11
LER 50-315-1999-012-01, "Auxiliary Building ESF [Engineered Safety
Features] Ventilation System May Not be Capable of Maintaining ESF Room
Temperatures Post-Accident"
LER 50-315-1999-012-01
Auxiliary Building ESF Ventilation System
May Not be Capable of Maintaining ESF
Room Temperatures Post-Accident
March 15, 2002
LER 50-315-1999-012-00
Auxiliary Building ESF Ventilation System
May Not be Capable of Maintaining ESF
Room Temperatures Post-Accident
May 20, 1999
Institute of Nuclear Power
Operations Significant
Event Report 63-83
Joy Fan Blades Failures
November 8, 1983
CR P-99-07026
Component Cooling Water Pump Area
Supply Fans have no Missile Protection
March 29, 1999
CR P-99-08841
Insufficient Assurance that the Auxiliary
Building Ventilation is Capable of Meeting
its Safety and Accident Mitigation
Functions
April 20, 1999
4OA3.12
LER 50-315-1999-001-01, "General Electric HFA Relays Installed in
Emergency Diesel Generators May Not Meet Seismic Qualification"
LER 50-315-1999-01-01
General Electric HFA Relays Installed in
Emergency Diesel Generators May Not
Meet Seismic Qualification
December 8,2000
LER 50-315-1999-01-00
General Electric HFA Relays Installed in
Emergency Diesel Generators May Not
Meet Seismic Qualification
February 10, 1999
General Electric Type HFA Relay Contact
Gap and Wipe Setting Adjustments
May 5, 1993
Movable Contact Finger Binding in HFA
Relays Manufactured by General Electric
September 29,
1988
Daily Shift Managers Logs
April 7, 1999
through
July 5, 1999
CR P-99-00270
HFA Relays Installed in the Plant May
Not Satisfy Seismic Requirements
January 6, 1999
(1) Condition report written as a result of inspection activities.