-_.

.

-

-

-

.-

-..

.-.

-

-

-.

-

.

<

,

.

i U. S. NUCLEAR REGULATORY C0ft11SSION OFFICE OF INSPECTION AND ENFORCEMENT

'

REGION V

RIport No. 50-312/81-30 l

Docket No. 50-312 License No.-

DPR-54 Safeguards Group Licensee: Sacramento Municinal Utility District P. O. Box 15830

.__

Sacramento. California 95813

'

,

,

Facility Name: Rancho Reco Inspection at: Herald. California (Rancho Seco site)

.

Inspection conducted: Sectomher 29 - October 1. 1981

,

Inspectors: fl hpi Laib'//

JNf/58f Qf/Hernandez, React'od Inspector Date Signed Date Signed Approved by:

[d

)O io/zt/st

,

T. W.. Bishop, Chief, Reactor Projects Section 1

'Jate Signed i

L Reactor Construction Projects Branch I

Sumary:

Irispection on September _ 29 - October 1,1981 (Report No. 50-312/81-30)

"

'

Areas Inspected: Routine unannounced inspection by a regional inspector of licensee activities related to plant modifications including:

licensee

!-

action on previous inspection findings; review of construction and implementing i

procedures; and observation of concrete placement activities for the Nuclear

Service Electrical Building basemat.

The.1spection involvod 22 inspector-hours onsite by one in:pector.

].

Results:

No items of noncompliance or deviations were identified.

!-

8111050607 811022 PDR ADOCK 05000312

,

o PDR

,

"f.

_

RV Fonn 219 (2)

d%

% _.,.

,

.~

,

.-

-

-

" w : ;r -

. _. -.: -.+.~.

a. w

....

..

.

.-......._~.-._=.....:.._.

(.

~,-

'

i

,

DETAILS ~

1.

P_ersons Contacted

.

a.

Sacramento Municipal Utility District (SMUD)_

  • R. J. Rodriguez, Manager Nuclear Operations
  • R. Columbo, Technical Assistant
  • L. G. Schwieger, Manager Quality Assurance
  • V. C. Lewis, Onsite Generation Engineering Supervisor W. J. Jurkovich, Generation Engineering Engineer

'

  • T. E. Perry, Onsite Quality Assurance Supervisor Q. L. Coleman, Gaelity Assurance Engineer D.

Dearman,

Civil Field Engineer T. L. Singer, Mechanical Field Engineer b.

Bechtel Power Corporation C. Letellier, Quality Control Coordinator H. Davis, Civil Inspector E. Conley, Mechanical / Welding Inspector c.

U. S. Testing Company H. L. Stevens, Site Supervisor

'

d.

SMF Corporation T. Twomey, Job Superintendent H. Keltner, Construction Field Engineer

  • Denotes those attending the exit interview on October 1, 1981.

2.

Site To_ur The inspector toured the facility modifications upon arrival onsite, to observe in-process and completed work activities and to ascertain general compliance with regulatory requirements, codes, standards, and procedures. Activities examined included excavation, conduit and reinforcing steel installation, soil compaction and concrete pre-placement, and formwork activities for the Nuclear Service Electrical Building.

No items of noncompliance or deviations were identified.

t

._

.. _.. _

. _.. _ _ _

_ _ _ _

_

. -.

,,, -

,

..

-2-3.

Licensee Action on Previously Identified Inspection Items a.

(Closed) Noncompliance (50-312/81-24/01): Failure to have quality

_ assurance and quality control procedures reviewed and approved in accordance with contract requirements.

The licensee's response to the item of noncompliance was examined and the actions described in the response were verified.

On August 3, 1981 the licensee's quality assurance organization formally approved U. S. Testing's Quality Assurance Manual and Quality Control Procedures; and on August 11, 1981 the Engineering Ins)ection Instructions (EII's) were approved to be used in conjunction wit 1 and as a supplement to the Construction Inspection Data Reports (CIDR's).

This item is closed, b.

(Closed) Followup Item (50-312/81-24/02): An individual identified by SMF Corporation as a Quality Assurance Engineer was in fact not performing a quality assurance function.

The licensee str.ted that per SMUD memorandum dated December 11,

,

1980, SMUD relieved SMF of all quality assurance responsibility during the construction of the Nuclear Service Electrical Building.

Accordingly, the individual in question has had his title modified to reflect his actual duties.

This item 4 closed.

4.

Structural Concrete Observation of Work and Work Activities

.

Licensee activities related to the pre-placement and placement of the Nuclear. Service Electrical Building basemat were observed. The observations' included examination of embedments, form work, reinforcing steel, cleaaliness, concrete cover, concrete free fall, concrete horizontal

-

free flow, consolidation, and quality control inspection. The activities were observed for compliance to the pertinent contract drawing (No.

C-508, Sheet 17, Revision 5.0), the construction inspection procedures, and the contract specification.

L

_.,.

-

..

-3-Field testing of concrete for the placement was performed by U. S.

Testing Company personnel. The testing was observed by the inspector for compliance to the requirements of the applicable ACI, ASTM, and contract requirements. The testing observed included slump, air entrainment, and tenperature measurements.

All activities observed were found to be in accordance with the requirements.

No items of noncompliance or deviations were identified.

5.

Management Interview.

On October 1,1981, the1 inspector met.with licensee and engineering management personnel denoted in paragraph 1.

The scope of the inspection, the observations, and the finding of the inspection were discussed.

,

,

-

-

-

,