IR 05000259/1981023

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-259/81-23,50-260/81-23 & 50-296/81-23 on 810804-07.No Noncompliance Noted.Major Areas Inspected:Fire Protection/Prevention
ML20010F284
Person / Time
Site: Browns Ferry  
Issue date: 08/14/1981
From: Conlon T, Miller W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20010F278 List:
References
50-259-81-23, 50-260-81-23, 50-296-81-23, NUDOCS 8109090562
Download: ML20010F284 (6)


Text

_r

.

.

.

>

,

/

UNITED STATES o

NUCLEAR REGULATORY COMMISSION

'

>

c, t

c REGION il 101 MARIETTA ST., N.W., SUITE 3100 Q

~

.s ATLANTA, GEORGIA 30303

'

  • tkk*

AUS 181981

'

Report No. 50-259/81-23, 50-260/81-23, 50-296/81-23 l

'

Licensee: Tennessee Valley Authority Facility Name:

Browns Ferry Docket No. 50-259, 50-260, 50-296

,

!

License No. DPR-33, DPR-55 and DPR-68 Inspection at Browns Ferry Site near Decatur, Alabama Inspector:

OhNo Ff(

h//9'/f- /

W. pMiller, Jr.

Date' Signed I

Approved by: fhh O AAI.

/I y c //v / G /

o s

T.YE. Conlon, Section Chief Dats Signed Ericjineering Inspection Branch Engineering and Technical Inspection Division SUMMARY

^

Inspection on August 4-7, 1981

!

!

Areas Inspected This routine, unannounced inspection involved 30 inspector-hours onsite in the areas of fire protection / prevention.

Results I

Of the areas inspected, no violations or deviations were identified.

810 909 %J ;

. _ _ -

...

.

a

,'

u

,

-

REPORT DETAILS 1.

Persons Contacted Licensee ::ricyees L

!

  • H. J. Abercrombie, Plant Superintendent J.~ L. Harness, Assistant Plant Superintendent I
  • Joe D. Ferguson,- Assistant Outage Director

- *R. Hunkapillar, Assistant Operations Supervisor

.

  • R. Cole, QA o

l

  • J. R. Norris, QA
  • R. Phifer, Safety Supervisor
  • T. Keckeisen, Fire Protection Engine -
  • R. E. Thompson, Supervisor Fire Pro'tection Engineering / Chattanooga
  • T' L. Chinn, Compliance Staff Supervisor

.

'W. Percle, Outage-Electrical

.T. Marshal, Outage-Electrical T. Childers, Outage l

J. M. Price, Training Officer E. G. Thornton, Training Officer / Operations

!

,

NRC Resident Inspector

  • R. F. Sullivan

'

('

  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on August 7,1981 with l

those persons indicated in paragraph 1 above.

i 3.

Licensee Action on Previous Inspection Findings

.a.

(Closed) Unresolved Item (259/77-23-10,260/77-23-10 and 296/77-23-10)-Completion of general fire prevention training for all employees: _All employees receive a course in general safety and fire prevention prior to receiving a plant security badge.

Employee retraining is conducted quarterly through the general safety = meetings.

'

The inspector reviewed approximately 100 training records and verified

,

,

that the required training was being conducted. This item is closed.

,

.b.

(Closed) Violation Item' (259/81-01-01,260/81-01-01 and 296/81-01-01)-

Sprinkler' system not provided. for the intake pumping station:

An.

automatic preaction sprinkler system has been provided for this cable.

tunnel-area ber.eath the RHR service water pumps. This system does not i

fully ' conform to the provisions ' of _ NFPA-13, Automatic Sprinkler-Systems, in that the ' sprinkler piping system is.not ' supervised as

required by Section 5-3.5.204 NFPA-13.

However, the licensee is not '

,

committed to this code. Therefore, this item is closed.

'

,

L

.

t

. '

-

_

._

_

..

. -

.

.

.

.

c.

(Closed) Violation Item (259/81-01-02, 260/81-01-02 and 296/81-01-02)-

Fire suppression systems for cable spreading rooms do not conform to license conditions: ' The licensee reques'ted by letter from L. M. Mills, TVA to H. R. Denton, NRR dated March 4, 1981, that the facility operating licenses be revised to make the automatic water spray system for the cable spreading rooms the primary extinguishing system and the manual carbon dioxide synem the secondary system. A reply to this request has not been received. Furthermore, this item was reduced from a violation to an unresolved item by NRC's letter from V.

Stello, NRC/IE to W. F. Willis, TVA dated June 3,1981. This item is to remain open pending revisions to the operating license d.

(0 pen) Unresolved Item (259/81-01-03, 260/81-01-03 and 296/81-01-03)-Combustible ceiling in control rooms: A design charge request (DCR No. 2454) has been issued to replace this ceiling with a noncombustible type ceiling.

Most of the ceiling material will be replaced upon receipt of the new ceiling material.

The ceiling directly over the control panels is to be replaced when the units are l

shut down. The completion schedule of this modification as listed in a letter from L. M. Mills, TVA to R. L. Tedesco, NRR of May 22, 1981 as

'

follows: Unit 1 May 1983, Unit 2 July 1982 and Unit 3 January 1982.

e.

(Closed) Violation Item (259/81-01-04, 260/81-01-04 and 296/81-01-04)-

Substandard fire barrier enclosures for battery rooms: The fire doors

!

into the battery rooms contain louvered openings which are provided l

with fire dampers.

All duct penetrations into each battery unit complex have been equipped with fire dampers. This item is closed.

f.

(0 pen) Deviation Item (259/81-01-05, 260/81-01-05 and 296/81-01-05)-Use of unapproved automatically activated deluge valves in the HVAC fire protection sprinkler system: The licensee has issued a design change request (DCR No. P 2424) to replace these valves with standard fire protection valves; however, the schedule date of completion has not been established.

l g.

(0 pen)

Violation Item (259/81-01-06, 260/81-01-06 and l

296/81-01-06)-Failure to follow the fire protection procedures: This violation contained two examples, the status of which are as follows:

(1) Fire Brigade Drills:

Between February 6, through March 2, 1981 all fire brigade members participated in at least one fire brigade drill. The inspector reviewed the drill and verified that the make up drill and the normal scheduled first and second quarter drills were conducted. This item is closed.

(2) Uncoated Cables:

The licensee has committed to coat all uncoated cables prior to the end of the Unit I refueling outage which is scheduled for September 6,1981. This item remains open.

h.

(Closed) Violation Item (259/81-01-07, 260/81-01-07 and

e L

.

,.

296/81-01-07)-Nonfunctional fire doors:

The licensee has issued procedures MMI-116, Semi-annual Maintenar.ce of Fire Doors, and SIL 23, Daily Fire Door Inspection which requires semi-annual ' maintenance inspection for all fire doors and requires all fire doors to be visually inspected daily by the safety group. These procedures shoc9 help assure that all fire doors will be functional.

This itam is closed.

1.

(Closed)

Deviation Item (259/81-01-08, 260/81-01-08 and 296/81-01-08)-Failure to complete fire door modifications: All of the required fire doors have been installed. This item is closed.

j.

(0 pen)

Unresolved Item (259/81-01-09, 260/81-01-09 and 296/81-01-09)-Corrective action to be taken on Trienniai Fire Protection Audit. Most of the maintenance and procedure change items in the audit have been corrected. Items which require design changes or plant modifications have been forwarded to ENDES for review. This item remains open and will be reviewed during a subsequent NRC inspection.

k.

(Closed)

Violation Item (259/81-01-10, 260/81-01-10 and i

296/81-01-10)-Failure to determine operability of fire pump A during October 1980. The

.ensee has revised the surveillance inspection schedule to require the electric driven fire pumps to be tesi ed on

.

Wednesday during the day shifts and the diesel engine to be tested on l

Tuesday during the evening shift. The schedule should assure that each pump will be tested at the required frequency. The test and inspection records from January through July 1981 were reviewed by the inspector

,

and it was verified that the pumps were being tested at the specified frequency. This item is closed.

1.-

(Closed)

Unresolved Item (259/81-01-11, 260/81-01-11 and 296/81-01-11)-Fire brigade training records not availaole on site: The licensee has consolided all of the fire brigade training records into files maintained by the operations training group.

The inspectori reviewed the fire brigade training records for 6 fire brigade members

,

'

and 5 fire brigade team leaders (assistant shift engineers) and verified that the training records were on file. This item is closed.

m.

(Closed)

Violation Item (259/81-01-12, 260/81-01-12 and 296/81-01-12)-Failure to provide adequate fire watch while CO2 system

.

was out of service. The licensee has revised procedure BF14.16, Fire Watch, to require that the fire watch assigned to various areas of the plant, be assigned the required keys or card keys for access into the areas to be patrolled. Form BF.31, Removal of Fire Protection Systems from Service, has been revised to require that the areas to be covered by the fire watch to be listed.

These changes should assure that adequate fire watches are provided in the future. This item is closed.

n.

(Closed) Deviation Item (259/81-01-M and 260/81-01-13)-Improper

<

hardware on a fire door between the electrical equipment rooms in the

,

k

-

.

,

W,f

-

W

-

Units-I and 2 diesel generator -building. Approved type hardware has

~

been provided _for this door. 'This item is closed.

-,

.4.

Unresolved Items '

Unresolved-items'were not identified during this inspecticn.

.

. 5 '.

' Inspector Followup Items

a.

Diesel' Fire Pump The control valve between the air release valve for the diesel fire pump;and the pump discharge piping is maintained in the open. position.

,

Procedure SI 4.11.,, _ Fire Protection System. Inspection, has been revised to indicate that this valve is to be maintained in the open position, b.

Outside _ Fire Protection Equipment Houses

'

Procedure MMI63, Fire Hose, Cabinets, Reals and Cart Inspection, has been revised to require a monthly inspection of the equipment within e

the equipment houses.

The licensee has evaluated the equipment

' required for these houses and determined that, in addition to the hose cart and wheeled fire extinguisher, only minimum equipment is required to be maintained since a standard well equipped fire department pumper is maintained on site for response to fires as needed.

c.

Administrative Fire Protection Procedures Procedure BF14.47, Fire Training, has been revised to require each fire brigade member to pass an annual physical for performance of strenous fire fighting activities, and brigade members to participate in quarterly classes training and fire drills.

d.

Fire Pumps Procedure SI4.11. A.1.6.3., High Pressure Fire Protection System Fire Pump Operability Check has been revised to require the electric pump to be test run for at least 15 minutes. Procedure SI4.11.A.1.b.(a), High Pressure Fire Protection Diesel Driven Fire Pump Operability Check, has been revised to require the diesel pump to be test operated for at least 30 minutes and indicates acceptance and rejection criteria.

6.

Fire' Protection / Prevention Program Implementation a.

Facility Tour and Observation of Work Activities The' inspector made.a tour of the plant to review the corrective action'

taken on ; previous identified enforcement items, _. unresolved items and

>

.'

.

inspector followup items as identified in Paragraphs 3 and 5.

During

-

k?

')

,>

a.

. +

i

,

.

s

....

-.

i i'

.

this tour the inspector verified that the licensee was adhering to'the procedures for the control of combustible materials, flammable and combustible liquids and gases, welding and cutting operations and housekeeping operations. All of fire alarm and suppression systems covered by the Technical Specifications were inspected and verified to be in service.

b.

Fire Brigade Equipment The fire brigade is assigned a total of 11 self contained breathing-.

apparatus and 20 spare cylinders. A total of 21 units (7 per control room) and 21 spare cylinders are located in the control room complex.

Additional units and spare cylinders are available from the health physics group, if needed. A total of 75 units and 190 cylinders are provided at the site. The cylinder can be refilled by means of a compressor or from two cascade systems. The number of self contained breathing apparatus and spare cylinders exceeds the requirements of the Technical Specifications.

A total of 15 sets of fire fighting gear (coats, pants, boots - and helmets) is provided for the brigade members. This equipment appeared to be maintained in a satisfactory manner.

Within the areas examined no violations or deviatio7s were detected.

L