Finding | |
---|---|
Title | Adverse Impact of Flood Drain Strainer Design Modification on Flooding Analysis |
Description | The inspectors identified an NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, having very low safety significance for the licensees failure to fully verify the adequacy of a design modification important to safety. Specifically, the licensee failed to recognize that bag-type strainers back fitted into floor drains in the Auxiliary Building for the purpose of preventing debris from blocking the floor drain piping were designed in such a way that they actually increased the potential for blockage, thus negatively impacting the analysis of record for internal flooding. The licensee subsequently entered the issue into their corrective action program, performed preliminary evaluation of the affected areas and demonstrated operability. Additional action was initiated to revise the internal flooding calculation and safe shutdown analysis to address the impact of the floor drain strainers. The finding was more than minor because it was associated with the Mitigation Systems Cornerstone attribute of protection against external events such as flooding and affected the cornerstone objective of ensuring the availability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the floor drain strainer bags were inadequately designed such that they would have increased the possibility of drain plugging. The finding is of very low safety significance (Green) because the licensee was able to demonstrate that, in the event the drains became plugged in any room, a flood in the affected room would have not affected the alternate shutdown equipment. The inspectors determined there was no cross-cutting aspect associated with this finding because these bag-type strainers were installed in 1996; therefore, the finding was not reflective of current performance. |
Site: | Braidwood ![]() |
---|---|
Report | IR 05000456/2010007 Section 1R21 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Garmoe B Palagi D Reeser E Duncan G O'Dwyer J Benjamin M Perry R Nga Dahburc Brown C Edwards E Sanchez G Morris J Gilliam L Jones P Lougheed S Edmonds |
INPO aspect | |
' | |
Finding - Braidwood - IR 05000456/2010007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2010Q2
Self-Identified List (Braidwood)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||