Finding | |
---|---|
Title | Lack of Calculation for the DDAFW Minimum Fuel oil Tank Setpoint Level |
Description | The inspectors identified an NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, having very low safety significance related to the licensees failure to develop a calculation for the DDAFW pump minimum fuel oil tank level setpoint. Specifically, the licensee failed to perform a calculation specific to the DDAFW pump day tank to verify the 74 percent level indication was equivalent to the 420 gallons of usable fuel volume that was required by the Technical Specifications (TS). The licensee subsequently entered the issue into their corrective action program to develop design basis documentations. This finding is more than minor because it was associated with the Mitigating Systems cornerstones attribute of design control and affected the cornerstone objective of ensuring the capability of the safety-related system to respond to initiating events to prevent undesirable consequences. Specifically, the licensee failure to verify that 74 percent tank level exceeded the TS value did not assure the pump was capable of performing its safety function for the entire seven hours mission time. This finding is of very low safety significance (Green) because subsequent calculation/evaluation determined the volume of the tank at 74 percent level was slightly above the minimum required TS limit. The inspectors determined there was no cross-cutting aspect associated with this finding because the deficiency was a legacy design issue and, therefore, was not indicative of the plants current performance. |
Site: | Braidwood ![]() |
---|---|
Report | IR 05000456/2010007 Section 1R21 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Dahbur C Brown C Edwards E Sanchez G Morris J Gilliam L Jones P Lougheed S Edmonds |
INPO aspect | |
' | |
Finding - Braidwood - IR 05000456/2010007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2010Q2
Self-Identified List (Braidwood)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||