Finding | |
|---|---|
| Title | Failure To Provide Continuous Monitoring Of A Fire Door |
| Description | The inspectors identified a NCV of Braidwood Operating License Condition 2.E, Fire Protection Program, for the licensees failure to take adequate compensatory measures following the failure of electronic supervision of a fire door. Specifically, when continuous electronic supervision of a fire door in an area with gaseous fire suppression failed, the licensee did not establish an hourly fire watch as required by Procedure BwAP 1110-1, Fire Protection Program System Requirements. The inspectors determined that the licensee failed to take procedurally required compensatory measures for the loss of electronic fire door monitoring. Upon notification of these requirements by the inspectors, the licensee restored power to the system and entered the issue into the CAP as Issue Report (IR) 945777. The inspectors determined the finding is more than minor because it is associated with the external events (fire) attribute of the Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors determined the finding category was Fire Prevention and Administrative Controls and assigned a low degradation rating. Therefore, the finding screened as of very low safety significance. The cause of the finding is related to the work practices attribute of the cross-cutting element of Human Performance (H.4(b)). Specifically, procedures were in place that directed the appropriate compensatory measures for the loss of electronic monitoring of fire doors; however, the licensee did not implement those procedures. |
| Site: | Braidwood |
|---|---|
| Report | IR 05000456/2009004 Section 1R05 |
| Date counted | Sep 30, 2009 (2009Q3) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | R Ng B Dickson M Mitchell B Palagi R Walton M Perry A Garmoe R Skokowski M Thorpe-Kavanaugh T Hartman J Gall |
| CCA | H.8, Procedure Adherence |
| INPO aspect | WP.4 |
| ' | |
Finding - Braidwood - IR 05000456/2009004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2009Q3
Self-Identified List (Braidwood)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||