05000456/FIN-2010007-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | DDAFW Pump Battery Racks were not restored to their Design Basis Seismic Category I |
| Description | The inspectors identified an NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, having very low safety significance for the licensees failure to restore the Diesel Driven Auxiliary Feedwater (DDAFW) battery racks to their design basis qualification, Seismic Category I. Specifically, although the licensee identified the existence of gaps between the wooden spacer blocks, batteries and end of racks in 2004 the licensee failed to provide adequate justification to demonstrate that the existing condition still met the Seismic Category I Design Basis requirements as specified in their design documents. The gaps between the wooden spacer blocks could affect the reliability of the DDAFW DC safety-related batteries being that this component was outside its design basis for over a period of six years. The licensee subsequently entered the issue into their corrective action program and restored the batteries racks to their design requirements. The finding was more than minor because it was associated with the Mitigating Systems cornerstone attribute of equipment performance, and affected the cornerstone objective of ensuring the availability of DDAFW batteries to perform their safety function in external events to prevent undesirable consequences. Specifically, the licensee did not assure that the wooden spacer blocks including the gap would provide adequate support to ensure that the seismically qualified battery rack will perform its safety function. This finding is of very low safety significance (Green) because the qualification deficiency was confirmed not to result in loss of operability or functionality. The inspectors determined that there was no cross-cutting aspect associated with this finding because the gaps between the wooden spacers and the DDAFW batteries were initially identified in 2004; therefore, the finding was not indicative of the plants current performance. |
| Site: | Braidwood |
|---|---|
| Report | IR 05000456/2010007 Section 1R21 |
| Date counted | Jun 30, 2010 (2010Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | A Garmoe B Bartlett D Szwarc E Duncan J Benjamin J Robbins M Perry R Langstaff R Ng T Go V Meghania Dahburc Brown C Edwards E Sanchez G Morris J Gilliam L Jones P Lougheed S Edmonds |
| INPO aspect | |
| ' | |
Finding - Braidwood - IR 05000456/2010007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2010Q2
Self-Identified List (Braidwood)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||