05000456/FIN-2010002-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Performance of Troubleshooting Leads to Auxiliary Building Ventilation Fan Fire |
| Description | A finding of very low safety significance and an associated Non-Cited Violation of 10 CFR 50, Appendix B, Criterion V, Procedures, was self-revealed when, on January 9, 2010, auxiliary building ventilation fan 0VA01CC caught fire, resulting in the declaration of an Unusual Event. Specifically, troubleshooting performed on the inboard fan bearing in Spring 2009 changed the bearing oil level without proper limits established, which led to bearing failure due to lack of lubrication. The licensees corrective actions included an evaluation of the oil consumption trends for other auxiliary building ventilation fans, additional training on work package quality, and a revision to other existing work orders that are intended to adjust auxiliary building ventilation fan oil levels. The finding was more than minor because it impacted the Systems, Structures, and Components and Barrier Performance attribute of the Barrier Integrity cornerstone objective to provide reasonable assurance that physical design barriers (fuel cladding, reactor coolant system, and containment) protect the public from radionuclide releases caused by accidents or events. Because the finding only represented degradation, rather than loss, of the radiological barrier function provided for the auxiliary building it screened as an issue of very low safety significance (Green). This finding is associated with the cross-cutting area component of resources in the human performance cross-cutting area. Specifically, the work instructions for troubleshooting did not contain adequate guidance to adjust the oil bubbler without causing an adverse equipment impact (H.2(c)) |
| Site: | Braidwood |
|---|---|
| Report | IR 05000456/2010002 Section 4OA3 |
| Date counted | Mar 31, 2010 (2010Q1) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | N Shah R Langstaff J Robbins B Dickson M Perry A Garmoe R Skokowski C Scott |
| CCA | H.7, Documentation |
| INPO aspect | WP.3 |
| ' | |
Finding - Braidwood - IR 05000456/2010002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2010Q1
Self-Identified List (Braidwood)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||