Finding | |
|---|---|
| Title | Failure to Analyze Effect of System Harmonics on Degraded Voltage Relays |
| Description | The inspectors identified a Green, non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, that states, in part, measures provide for verifying or checking the adequacy of design, such as by the performance of design reviews, by the use of alternate or simplified calculational methods, or by the performance of a suitable testing program. Specifically, prior to May 20, 2013, the licensee failed to assess the adverse effects of 6.9kV and 480V system harmonics on the degraded voltage relays. The finding was entered into the licensees corrective action program as Condition Report CR-2013-006230. The inspectors determined that the failure to analyze the effect of electrical system harmonics on the degraded voltage relays was a performance deficiency. The performance deficiency is more-than-minor because it was associated with the Reactor Safety, Mitigating Systems Cornerstone, Design Control attribute and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, failure to analyze the effect of electrical system harmonics on the degraded voltage relays could cause the relays to fail to actuate at the setpoint specified in Technical Specifications. Using Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, Exhibit 2, the inspectors determined the finding was of very low (Green) safety significance because the finding was a deficiency affecting the design or qualification that did not result in the safetyrelated equipment losing operability or functionality. This finding did not have a crosscutting aspect because the most significant contributor to the performance deficiency did not reflect current licensee performance. |
| Site: | Comanche Peak |
|---|---|
| Report | IR 05000445/2013007 Section 1R21 |
| Date counted | Jun 30, 2013 (2013Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | T Farnholtz R Smith G Skinner B Correll C Edwards T Buchanan J Braisted |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control Technical Specification |
| INPO aspect | |
| ' | |