05000445/FIN-2013007-11
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Correct Design Calculations to Incorporate Technical Specification Allowed Frequency Range for the Emergency Diesel Generator in a Timely Manner |
Description | The inspectors identified a Green, non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, states, in part, measures shall be established to assure that conditions adverse to quality are promptly identified and corrected. Specifically, since May 2010, the licensee failed to correct a condition adverse to quality in a timely manner that involved updating design basis calculations for safety-related equipment to include the allowed technical specification frequency range of 2 percent for the emergency diesel generators. The finding was entered into the licensee\'s corrective action program as Condition Report CR-2013-006604. The inspectors determined that the failure to correct a condition adverse to quality in a timely manner that involved updating design basis calculations for safety-related equipment to include the allowed technical specification frequency range of 2 percent for the emergency diesel generators was a performance deficiency. The performance deficiency is more-than-minor because it was associated with the Reactor Safety, Mitigating Systems Cornerstone, Design Control attribute and adversely affected the cornerstone objective to ensure availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the calculations to support safety-related equipment did not include allowed technical specification frequency range for the emergency diesel generators to ensure the equipment would be capable of performing their safety-related functions. Using Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, Exhibit 2, the inspectors determined the finding was of very low (Green) safety significance because the finding was a deficiency affecting the design or qualification that did not result in the safety-related equipment losing operability or functionality. This finding had a crosscutting aspect in the area of problem identification and resolution associated with the corrective action program component because the licensee failed to take appropriate corrective actions to address updating design basis calculations to include technical specification allowed emergency diesel generator frequency range in a timely manner, commensurate with their safety significance. |
Site: | Comanche Peak |
---|---|
Report | IR 05000445/2013007 Section 4OA2 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | T Farnholtz R Smith G Skinner B Correll C Edwards T Buchanan J Braisted |
Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |