| | | Reporting criterion |
|---|
| 05000416/LER-1982-001-01, /01T-0:on 820618,loss of Dc Power to Div II Diesel Generator Control Circuit Detected.Caused by Failure of Main Fuses to Dc Control Panel Due to Fault in Circuitry of Semiconductor Annunciator module,SAM-2.Module Bypassed | /01T-0:on 820618,loss of Dc Power to Div II Diesel Generator Control Circuit Detected.Caused by Failure of Main Fuses to Dc Control Panel Due to Fault in Circuitry of Semiconductor Annunciator module,SAM-2.Module Bypassed | |
| 05000416/LER-1982-001, Forwards LER 82-001/01T-0 | Forwards LER 82-001/01T-0 | |
| 05000416/LER-1982-002-01, /01T-0:on 820701,two Scrams Initiated by High Flux Spikes on Fuel Loading Chambers Connected to Source Range Monitor Noncoincident Reactor Protection Sys Logic.Probably Caused by Close Proximity of Fuel Bundles to Fuel Chamb | /01T-0:on 820701,two Scrams Initiated by High Flux Spikes on Fuel Loading Chambers Connected to Source Range Monitor Noncoincident Reactor Protection Sys Logic.Probably Caused by Close Proximity of Fuel Bundles to Fuel Chamber | |
| 05000416/LER-1982-002, Forwards LER 82-002/01T-0 | Forwards LER 82-002/01T-0 | |
| 05000416/LER-1982-003-03, /03L-0:on 820616,during Surveillance Testing, Output Amplifiers for free-field Forced Balanced Accelerometer Found Inoperable.Probably Caused by Lightning Damage.Amplifiers Replaced & Surveillance Test Completed | /03L-0:on 820616,during Surveillance Testing, Output Amplifiers for free-field Forced Balanced Accelerometer Found Inoperable.Probably Caused by Lightning Damage.Amplifiers Replaced & Surveillance Test Completed | |
| 05000416/LER-1982-003, Forwards LER 82-003/03L-0 | Forwards LER 82-003/03L-0 | |
| 05000416/LER-1982-004-03, /03L-0:on 820616,prior to Initial Fuel Load,Area Radiation Monitoring Sys Failure Alarm Initiated.Probably Caused by Transient Which Allowed Meter to Fall in Downscale Range of Monitor.Sys Tested & Declared Operable | /03L-0:on 820616,prior to Initial Fuel Load,Area Radiation Monitoring Sys Failure Alarm Initiated.Probably Caused by Transient Which Allowed Meter to Fall in Downscale Range of Monitor.Sys Tested & Declared Operable | |
| 05000416/LER-1982-004, Forwards LER 82-004/03L-0 | Forwards LER 82-004/03L-0 | |
| 05000416/LER-1982-005-01, /01T-0:on 820709,while Performing Refueling Interlock Check,Automatic Interlocks Failed to Stop Refueling Platform Approach to Core.Caused by Malfunction of Interlock Relay.Relay Replaced | /01T-0:on 820709,while Performing Refueling Interlock Check,Automatic Interlocks Failed to Stop Refueling Platform Approach to Core.Caused by Malfunction of Interlock Relay.Relay Replaced | |
| 05000416/LER-1982-005, Forwards LER 82-005/01T-0 | Forwards LER 82-005/01T-0 | |
| 05000416/LER-1982-006-01, /01T-0:on 820709,violation of Tech Spec 4.7.8 Identified Re Temp Monitoring of Specific safety-related Areas Every 12-h.Caused by Procedural Inadequacy & Personnel Error Re Operating Log Requiring Recording Once Every 24-h | /01T-0:on 820709,violation of Tech Spec 4.7.8 Identified Re Temp Monitoring of Specific safety-related Areas Every 12-h.Caused by Procedural Inadequacy & Personnel Error Re Operating Log Requiring Recording Once Every 24-h | |
| 05000416/LER-1982-006, Forwards LER 82-006/01T-0 | Forwards LER 82-006/01T-0 | |
| 05000416/LER-1982-008-99, /99X-1:on 820626,during Testing of Carbon Dioxide (CO2) Fire Protection Sys,Ventilation Dampers for Div 1 & 2 Switchgear Rooms Failed to Close Upon CO2 Actuation Signal. Caused by Insufficient Power Supply to Melt Thermal Li | /99X-1:on 820626,during Testing of Carbon Dioxide (CO2) Fire Protection Sys,Ventilation Dampers for Div 1 & 2 Switchgear Rooms Failed to Close Upon CO2 Actuation Signal. Caused by Insufficient Power Supply to Melt Thermal Links | |
| 05000416/LER-1982-008, Forwards LER 82-008/99X-1 | Forwards LER 82-008/99X-1 | |
| 05000416/LER-1982-009-03, /03L-0:on 820708,observed That Accumulated Hours of Operation for Standby Gas Treatment Sys & Control Room Emergency Filtration Sys Not Recorded.Operators Reinstructed | /03L-0:on 820708,observed That Accumulated Hours of Operation for Standby Gas Treatment Sys & Control Room Emergency Filtration Sys Not Recorded.Operators Reinstructed | |
| 05000416/LER-1982-009, Forwards LER 82-009/03L-0.Detailed Event Analysis Submitted | Forwards LER 82-009/03L-0.Detailed Event Analysis Submitted | |
| 05000416/LER-1982-010-03, /03L-0:on 820709,Div 2 Control Room Emergency Filtration Automatic Initiation Capability Declared Inoperable.Caused by Sys Isolation Under Brown Tags Due to Freon Leak in Air Conditioning Compressor | /03L-0:on 820709,Div 2 Control Room Emergency Filtration Automatic Initiation Capability Declared Inoperable.Caused by Sys Isolation Under Brown Tags Due to Freon Leak in Air Conditioning Compressor | |
| 05000416/LER-1982-010, Forwards LER 82-010/03L-0 | Forwards LER 82-010/03L-0 | |
| 05000416/LER-1982-011-01, /01T-0:on 820722,diesel Generator 12 Tripped Due to High Water Jacket Temp.Cooling Water Found Isolated at Outlet Valve.Caused by Faulty Indicator Arrow on Pratt MDT-5 Operator.Indicator Realigned & Design Modified | /01T-0:on 820722,diesel Generator 12 Tripped Due to High Water Jacket Temp.Cooling Water Found Isolated at Outlet Valve.Caused by Faulty Indicator Arrow on Pratt MDT-5 Operator.Indicator Realigned & Design Modified | |
| 05000416/LER-1982-011-99, /99X-0:on 830103-24,certain Fire Rated Barriers in Control Bldg & Auxiliary Bldg Opened to Perform Planned Maint.Caused by Cable Routing.Barriers to Be Restored by Apr 1983 | /99X-0:on 830103-24,certain Fire Rated Barriers in Control Bldg & Auxiliary Bldg Opened to Perform Planned Maint.Caused by Cable Routing.Barriers to Be Restored by Apr 1983 | |
| 05000416/LER-1982-012-01, /01T-0:on 820722,radioactive Gaseous Effluent Sampler Flow Rates Were Not Being Recorded Daily Per Tech Spec 4.3.7.12-1.Operating Log Did Not Include Sampler Flow Rates.Temporary Change Notice Initiated | /01T-0:on 820722,radioactive Gaseous Effluent Sampler Flow Rates Were Not Being Recorded Daily Per Tech Spec 4.3.7.12-1.Operating Log Did Not Include Sampler Flow Rates.Temporary Change Notice Initiated | |
| 05000416/LER-1982-012, Forwards LER 82-012/01T-0 | Forwards LER 82-012/01T-0 | |
| 05000416/LER-1982-013, Forwards LER 82-013/03L-0 | Forwards LER 82-013/03L-0 | |
| 05000416/LER-1982-013-03, /03L-0:on 820702,one 4.16-kV Bus Undervoltage Trip Channel Setpoint Found to Be Out of Tech Spec Value. Caused by Incorrect Calibr Procedure.Procedure Revised | /03L-0:on 820702,one 4.16-kV Bus Undervoltage Trip Channel Setpoint Found to Be Out of Tech Spec Value. Caused by Incorrect Calibr Procedure.Procedure Revised | |
| 05000416/LER-1982-014, Forwards LER 82-014/03L-0 | Forwards LER 82-014/03L-0 | |
| 05000416/LER-1982-014-03, /03L-0:on 820713,carbon Dioxide Fire Protection Sys Initiated in Electrical Penetration Room in Auxiliary Bldg W/O Fire.Caused by Faulty Supervisory Relay.Relay Replaced | /03L-0:on 820713,carbon Dioxide Fire Protection Sys Initiated in Electrical Penetration Room in Auxiliary Bldg W/O Fire.Caused by Faulty Supervisory Relay.Relay Replaced | |
| 05000416/LER-1982-015, Forwards LER 82-015/03L-0 | Forwards LER 82-015/03L-0 | |
| 05000416/LER-1982-015-03, /03L-0:on 820714,limiting Condition of Operation Entered Due to Gaseous Effluent Sampler Being Removed from Svc for Maint.Caused by Inverted Indicator Floats in Meter Tubes Due to Preoperational Testing.Floats Reinstalled | /03L-0:on 820714,limiting Condition of Operation Entered Due to Gaseous Effluent Sampler Being Removed from Svc for Maint.Caused by Inverted Indicator Floats in Meter Tubes Due to Preoperational Testing.Floats Reinstalled | |
| 05000416/LER-1982-016-03, /03L-0:on 820702,during Review of Completed Surveillance,One Channel Found Out of Spec.Caused by Delayed Notification to Shift Supervisor of Failure Until 820707 When Test Results Identified as Unacceptable | /03L-0:on 820702,during Review of Completed Surveillance,One Channel Found Out of Spec.Caused by Delayed Notification to Shift Supervisor of Failure Until 820707 When Test Results Identified as Unacceptable | |
| 05000416/LER-1982-016, Forwards LER 82-016/03L-0 | Forwards LER 82-016/03L-0 | |
| 05000416/LER-1982-017, Forwards LER 82-017/03L-0 | Forwards LER 82-017/03L-0 | |
| 05000416/LER-1982-017-03, /03L-0:on 820714,during Fire Door Alarms Check Surveillance Test,Several Doors Failed to Alarm in Secure Position.Caused by Electronic Malfunction & Equipment Out of Adjustment.Equipment Restored to Operable Status | /03L-0:on 820714,during Fire Door Alarms Check Surveillance Test,Several Doors Failed to Alarm in Secure Position.Caused by Electronic Malfunction & Equipment Out of Adjustment.Equipment Restored to Operable Status | |
| 05000416/LER-1982-019, Forwards LER 82-019/01T-0 | Forwards LER 82-019/01T-0 | |
| 05000416/LER-1982-019-01, /01T-0:on 820801,sampling Required on 820729,30 & 31 Was Not Performed.Caused by Removal of Sampler Pumps for Replacement,Due to Inoperability of Fuel Handling Area Ventilation Effluent Monitoring Sys | /01T-0:on 820801,sampling Required on 820729,30 & 31 Was Not Performed.Caused by Removal of Sampler Pumps for Replacement,Due to Inoperability of Fuel Handling Area Ventilation Effluent Monitoring Sys | |
| 05000416/LER-1982-021-99, /99X-1:on 820720,limiting Condition for Operation Entered Due to Quarterly Test of Radioactive Liquid Effluent Monitoring Sys Not Being Performed by 820720.Caused by Inadequate Sys Design.Design Change Implemented | /99X-1:on 820720,limiting Condition for Operation Entered Due to Quarterly Test of Radioactive Liquid Effluent Monitoring Sys Not Being Performed by 820720.Caused by Inadequate Sys Design.Design Change Implemented | |
| 05000416/LER-1982-022, Forwards LER 82-022/03L-0 | Forwards LER 82-022/03L-0 | |
| 05000416/LER-1982-022-03, /03L-0:on 820721,fuel Handling Area Gaseous Effluent Monitor Inoperable.Caused by Fuse Failure.Fuse Replaced & Monitor re-energized.Samples Taken During Period of Inoperability Found Acceptable | /03L-0:on 820721,fuel Handling Area Gaseous Effluent Monitor Inoperable.Caused by Fuse Failure.Fuse Replaced & Monitor re-energized.Samples Taken During Period of Inoperability Found Acceptable | |
| 05000416/LER-1982-023, Forwards LER 82-023/03L-0 | Forwards LER 82-023/03L-0 | |
| 05000416/LER-1982-023-03, /03L-0:on 820723,Div 3 Switchgear Room CO2 Fire Protection Sys Declared Inoperable Due to Failure of Latching Mechanism to Secure Door.Caused by Failure of Striker Plate.Striker Plate Adjusted | /03L-0:on 820723,Div 3 Switchgear Room CO2 Fire Protection Sys Declared Inoperable Due to Failure of Latching Mechanism to Secure Door.Caused by Failure of Striker Plate.Striker Plate Adjusted | |
| 05000416/LER-1982-024, Forwards LER 82-024/03L-0 | Forwards LER 82-024/03L-0 | |
| 05000416/LER-1982-024-03, /03L-0:on 820723,limiting Condition for Operation Was Entered Due to Inoperability of Zone 1006 Flame Detector in HPCS Diesel Generator East Corridor.Cause Not Stated. Detector Cleaned & Tested.Fire Watch Initiated | /03L-0:on 820723,limiting Condition for Operation Was Entered Due to Inoperability of Zone 1006 Flame Detector in HPCS Diesel Generator East Corridor.Cause Not Stated. Detector Cleaned & Tested.Fire Watch Initiated | |
| 05000416/LER-1982-025, Forwards LER 82-025/03L-0 | Forwards LER 82-025/03L-0 | |
| 05000416/LER-1982-025-03, /03L-0:on 820724,fire Doors 1A309,1A109,1A202 & 1A312 Found Alarming in Closed Position.Cause Not Stated. Fire Watch Established,Magnetic Switch Components Adjusted & Operation Verified | /03L-0:on 820724,fire Doors 1A309,1A109,1A202 & 1A312 Found Alarming in Closed Position.Cause Not Stated. Fire Watch Established,Magnetic Switch Components Adjusted & Operation Verified | |
| 05000416/LER-1982-026-03, /03L-0:on 820725,smoke Detector Above Steam Tunnel Area Zone 2-08 Alarmed W/O Fire & Would Not Reset.Caused by Initiated Manual Pull Station.Sys Restored & Hourly Fire Watch Discontinued | /03L-0:on 820725,smoke Detector Above Steam Tunnel Area Zone 2-08 Alarmed W/O Fire & Would Not Reset.Caused by Initiated Manual Pull Station.Sys Restored & Hourly Fire Watch Discontinued | |
| 05000416/LER-1982-026, Forwards LER 82-026/03L-0 | Forwards LER 82-026/03L-0 | |
| 05000416/LER-1982-027-99, During Special Insp,Seal AV-8D Not Installed in Spare HVAC Penetration to Containment Exhaust Filter Train Room.Caused by Current Drawings Not Requiring Sealing.Design Change Issued | During Special Insp,Seal AV-8D Not Installed in Spare HVAC Penetration to Containment Exhaust Filter Train Room.Caused by Current Drawings Not Requiring Sealing.Design Change Issued | |
| 05000416/LER-1982-027-03, /03L-0:on 820727,discovered That Seal AV-8D Not Installed in Spare HVAC Penetration to Containment Exhaust Filter Train Room.Also Found That Current Drawings Do Not Reflect Open Penetration in Secondary Containment | /03L-0:on 820727,discovered That Seal AV-8D Not Installed in Spare HVAC Penetration to Containment Exhaust Filter Train Room.Also Found That Current Drawings Do Not Reflect Open Penetration in Secondary Containment | |
| 05000416/LER-1982-028, Forwards LER 82-028/01T-0 | Forwards LER 82-028/01T-0 | |
| 05000416/LER-1982-028-01, /01T-0:on 820814,Halon Sys Surveillance Test Revealed That Acceptance Criteria for Change Pressure of Halon Bottles Not Met.Caused by Surveillance Test Performed Prior to Issuance of Ol.Halon Bottles Replaced | /01T-0:on 820814,Halon Sys Surveillance Test Revealed That Acceptance Criteria for Change Pressure of Halon Bottles Not Met.Caused by Surveillance Test Performed Prior to Issuance of Ol.Halon Bottles Replaced | |
| 05000416/LER-1982-029, Forwards LER 82-029/03L-0 | Forwards LER 82-029/03L-0 | |