05000416/LER-2018-001, Reactor Manual Shutdown Due to Turbine Pressure Control Valve Position Changes

From kanterella
(Redirected from 05000416/LER-2018-001)
Jump to navigation Jump to search
Reactor Manual Shutdown Due to Turbine Pressure Control Valve Position Changes
ML18088B198
Person / Time
Site: Grand Gulf 
(NPF-029)
Issue date: 03/29/2018
From: Emily Larson
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GNRO-2018/00010 LER 2018-001-00
Download: ML18088B198 (6)


LER-2018-001, Reactor Manual Shutdown Due to Turbine Pressure Control Valve Position Changes
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(B), System Actuation
4162018001R00 - NRC Website

text

  • ~=':r* Entergy GNR0-2018/00010 March 29, 2018 U.S. Nu9lear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 Entergy Operations, Inc.

P. 0. Box756 Port Gibson, MS 39150 Eric A. Larson Site Vice President Grand Gulf Nuclear Station Tel. (601) 437-7500 10CFR50.73

SUBJECT:

Licensee Event Report 2018-001-00, Reactor.Manual Shutdown due to Turbine Pressure Control Valve Position Changes Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. NPF-29

Dear Sir or Madam:

Attached is Licensee Event Report 2018-001-00, Reactor Manual Shutdown due to Turbine Pressure Control Valve Changes. This report is being submitted in accordance with 1 OCFR50. 73(a)(2)(iv)(A) for any event or condition that resulted in a manual or automatic actuation of any of the systems listed in 1 OCFR50.73(a)(2)(iv)(B).

This letter contains no new commitments. If you have any questions or require additional information, please contact Dougla$ Neve at 601-437-2103.

Sincerely, rct_

Eric A. Larson Site Vice President Grand Gulf Nuclear Station

  • EAUdre

Attachment:

Licensee Event Report 2018-001-00 cc: see next page

GNR0-2018/00010 Page 2 of 2 U.S. Nuclear Regulatory Commission A TIN: Mr. Siva Ling am*

Mail Stop OWFN 8 81 Rockville, MD 20852-2738

.NRC Senior Resident Inspector Grand Gulf Nuclear Station Port Gibson, MS 39150 U. S. Nuclear Regulatory Commission ATTN: Mr. Kriss Kennedy, NRR/DORL (w/2)

Mail Stop OWFN 8 81 Washington, DC 20555-0001 r

GNR0-2018/00010 Attachment Licensee Event Report 2018-001-00

NRC FORM 366 U.S; NUCLEAR REGULATORY COMMISSION APPROVED. BY OMB: NO. 3150-0104 EXPIRES: 10/31/2018 (06-2016)

, the NRG may not conduct or sponsor, and a person is not required to respond to, the information collection..

1. FACILITY NAME
2. DOCKET Grand Gulf Nuclear Station, Unit 1 05000 416

E. CORRECTIVE ACTIONS

The following corrective actions are completed or planned.

Completed:

YEAR

3. LEA NUMBER SEQUENTIAL NUMBER 2018-001-00 Control circuit card has been replaced and adjusted to correct tolerances and retested satisfactorily.

REV.

NO.

Planned actions included in the corrective action program which may be changed in accordance with the program:

Revise procedure to set up TCV circuitry to reflect appropriate test report F.

SAFETY SIGNIFICANCE

The safety significance of this event is low because all systems operated as designed and the TCV changes did not challenge any safety parameters. The manual scram was performed as a conservative measure. There were no actual nuclear safety consequences or radiological consequences during the eve~t.

G. PREVIOUS SIMILAR EVENTS

Entergy conducted a three-year review of the relevant licensee event reports and determined that there was one similar known event reported as GGNS Licensee Event Report 2016-05-00 "Automatic Reactor SCRAM." The failure in that event was a failed amplifier card, which is different from this event which is an incorrect potentiometer setting. Therefore, the corrective actions for the previous event would not have prevented this event.