Re Automatic Reactor Trip Due to Generator Lockout Signal
ML063280208
Person / Time
Site: Harris 
(NPF-063)
Issue date: 11/17/2006
From: Mccartney E
Progress Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
HNP-06-125 LER 06-003-00
Download: ML063280208 (6)


LER-2006-003, Re Automatic Reactor Trip Due to Generator Lockout Signal
Event date:
Report date:
4002006003R00 - NRC Website

text

L Progress Energy NOV 1'7 2006 U.S. Nuclear Regulatory Commission Serial: HNP-06-125 ATTN: NRC Document Control Desk 10CFR50.73 Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT UNIT 1 DOCKET NO. 50-400/LICENSE NO. NPF-63 LICENSEE EVENT REPORT 2006-003-00 Ladies and Gentlemen:

The enclosed Licensee Event Report 2006-003-00 is submitted in accordance with 10 CFR 50.73. This report describes an automatic turbine/reactor trip due to a generator lockout signal. Event notification EN 42848 previously reported this event on September 19, 2006 in accordance with 10 CFR 50.72.

Please refer any questions regarding this submittal to Mr. Dave Corlett, Supervisor -

Licensing/Regulatory Programs, at (919) 362-3137.

Sincerely, Eric A. McCartney Plant General Manager Harris Nuclear Plant EAM/sfm Enclosure c:

HNP Senior NRC Resident NRC-NRR Project Manager NRC Regional Administrator, Region II Progress Energy Carolinas, Inc.

Harris Nuclear Plant Pý 0. Box 165 New Hill, NC 27562

Serial: HNP-06-125 Page 2 bc:

Mr. G.E. Attarian Mr. D. Bailey Mr. D.T. Conley Mr. D.C. DiCello Mr. J.W. Donahue Mr. R.J. Duncan II Mr. S.D. Ebneter Mr. D.G. Eisenhut Mr. J.P. Fulford Mr. C.J. Gannon Mr. R.T. Garner Mr. J.M. Given, Jr.

Mr. J.W. Gurganious Mr. C.S. Hinnant Mr. E.D. Hux INPO Mr. M.T. Janus Mr. C.S. Kamilaris Mr. C.W. Komegay Mr. R.D. Martin Mr. E.A. McCartney Mr. H.J. Miller Mr. S.T. O'Connor Mr. E.L. Wills Licensing File(s) (2 copies)

Nuclear Records

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 06/30/2007 (6-2004)

, the NRC may not conduct digits/characters for each block) or sponsor, and a person is not required to respond to, the information digis/carater foreac blck)collection.

3. PAGE Harris Nuclear Plant - Unit I 05000400 1 OF 4
4. TITLE Automatic Reactor Trip Due to Generator Lockout Signal
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE

]

8. OTHER FACILITIES INVOLVED D

Y Y

SEQUENTIAL jREV M

D Y,

FACILITY NAME DOCKET NUMBER MONT DAY YEA YEA SEUENTSLLREV ONT DAY IYEAR 'N/A05 0

MO T D Y YE R lr. K NUMBER iNO.

N /AN~

05000 I

I IFACILITY NAME DOCKET NUMBER 09 19 2006 2006

- 003 -

00 11 17 2006 N/A 05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply) o 20.2201(b)

[I 20.2203(aX3Xi) 0 50.73(aX2Xi)(C)

[I 50.73(aX2)(Xvii)

[1 20.2201(d) 0 20.2203(aX3)(ii) 0 50.73(a)(2XiiXA) 0 50.73(a)(2XviiiXA) r-20.2203(aXl) 0 20.2203(aX4) 0 50.73(a)(2XiixB)

E0 50.73(aX2Xviii)(B)

[I 20.2203(a)(2Xi) 0 50.36(cXIXiXA)

[0 50.73(a)(2Xiii) 0 50.73(aX2XixXA)

10. POWER LEVEL 0 20.2203(aX2Xii) 0 50.36(cXlXiiXA) 0 50.73(aX2XivXA)

[0 50.73(aX2Xx)

[o 20.2203(aX2)(iii) 0 50.36(c)(2)

[0 50.73(a)(2XvXA) 0 73.71(aX4)

[O 20.2203(aX2Xiv) 0 50.46(a)(3Xii)

[0 50.73(aX2XvXB)

[0 73.71(aX5) 100 [1 20.2203(aX2Xv)

[0 50.73(aX2Xi)(A)

[I 50.73(a)(2Xv)(C) 0 OTHER o 20.2203(aX2)(vi)

[0 50.73(a)(2XiXB)

[0 50.73(a)(2XvXD)

Specify in Abstract below I

or in (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of NRC Form 366A)

IV. PREVIOUS SIMILAR EVENTS

There are no previous HNP trips related to a failure the main generator neutral ground protection relay.

V. CORRECTIVE ACTIONS

Completed corrective actions include replacing the failed relay module in the main generator stator ground detection circuit. Additional corrective actions are to establish specific inspection requirements for the generator, main transformer and auxiliary transformer protective relays and to brief appropriate maintenance personnel.

VI. COMMITMENTS

This document contains no new regulatory commitments.