05000266/FIN-2013002-04
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Survey for Neutron Dose from Source Storage |
| Description | A finding of very low safety significance and an associated non-citied of violation of 10 CFR 20.1501 was self-revealed when the licensee failed to evaluate dose to personnel from neutron radiation. Specifically, on September 5, 2012, it was self-revealed to the licensee that unevaluated neutron dose was present in an office area located outside the Radiologically Controlled Area (RCA) due to a source storage room housing a neutron source. This issue was entered into the licensees CAP as AR01809560. Corrective actions included moving the neutron source into the RCA, performing a condition evaluation, and performing dose estimates to various plant personnel. The finding was determined to be more than minor in accordance with IMC 0612, Appendix B, because the finding was associated with the Occupational and Public Radiation Safety Cornerstones and adversely affected the cornerstones objective. The inspectors evaluated the finding using IMC 0609, Appendix D, for the Public Radiation Safety Cornerstone, and determined the finding to be of very low safety significance. The finding had a cross-cutting aspect in the area of human performance, work practices, because the licensee failed to ensure supervisory and management oversight of work activities such that nuclear safety is supported (H.4(c)). Specifically, the licensee did not provide supervisory oversight to ensure that the survey program was sufficient to ensure compliance with 10 CFR Part 20 requirements. |
| Site: | Point Beach |
|---|---|
| Report | IR 05000266/2013002 Section 2RS4 |
| Date counted | Mar 31, 2013 (2013Q1) |
| Type: | NCV: Green |
| cornerstone | Pr Safety |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71124.04 |
| Inspectors (proximate) | J Cameron M Jones M Thorpe Kavanaugh N Feliz Adorno P Smagacz R Winter S Burton V Myers |
| Violation of: | 10 CFR 20.1501, Surveys and Monitoring 10 CFR 20, Standards for Protection Against Radiation |
| INPO aspect | |
| ' | |
Finding - Point Beach - IR 05000266/2013002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Point Beach) @ 2013Q1
Self-Identified List (Point Beach)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||