Finding | |
|---|---|
| Title | Flooding Impact of Loose Items Found on Roof Tops |
| Description | During the inspectors external flooding sample, the inspectors identified an Unresolved Item (URI) associated with a potential flooding event caused by loose items found by inspectors on roof tops. As part of this evaluation, the inspectors checked for obstructions that could impact the ability of various installed drain systems to function as designed. 8 Enclosure During the inspectors walkdown and inspection of building roofs, the inspectors found loose items on the turbine building and facade roofs. Specifically, the inspectors identified several large mats, pieces of metal equipment, loose scaffolding, piping, ladders, and other miscellaneous items. The inspectors were concerned that the loose items could clog various drains in the event of heavy precipitation and cause a flooding concern. The licensee initiated condition report (CR) AR01855615 in response to the inspectors concerns. At the completion of the first quarter inspection period, the licensees review in response to the inspectors concerns regarding the obvious loose items was under evaluation. The inspectors determined that this was an issue of concern in which more information was needed to determine whether a performance deficiency exists. Specifically, the review of the licensees evaluation of the condition was needed to determine whether barriers required to mitigate flooding were in place and functional as a result of the loose items identified. The issue is unresolved pending review of the licensees evaluation. |
| Site: | Point Beach |
|---|---|
| Report | IR 05000266/2013002 Section 1R01 |
| Date counted | Mar 31, 2013 (2013Q1) |
| Type: | URI: |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.01 |
| Inspectors (proximate) | B Bartlett J Cameron K Barclay R Elliott T Bilik V Myersj Cameronm Jones M Thorpe Kavanaugh N Feliz Adorno P Smagacz R Winter S Burton V Myers |
| INPO aspect | |
| ' | |
Finding - Point Beach - IR 05000266/2013002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Point Beach) @ 2013Q1
Self-Identified List (Point Beach)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||