05000259/FIN-2013007-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Use Worst Case 4160 VAC Bus Voltage in Design Calculations |
Description | The team identified a non-cited violation of 10 CFR 50, Appendix B, Criterion III, Design Control, for the licensees failure to perform analyses demonstrating that the degraded voltage relay (DVR) set points specified in technical specifications (TS) would ensure adequate voltage to safety-related equipment. This was a performance deficiency. The licensee entered this issue into their corrective action program as PERs 676678 and 696876. As immediate corrective actions, the licensee performed a sensitivity study to verify that the voltage at the DVR set points specified in TS could provide adequate starting voltage to a sample of limiting safety-related equipment. The performance deficiency was determined to be more than minor because it affected the Design Control attribute of the Mitigating Systems cornerstone objective of ensuring the availability, reliability, and capability of the 4160 volts alternating current buses. Specifically, the finding challenged the assurance that safety-related loads had adequate motor starting voltage during required degraded voltage scenarios. The team used Inspection Manual Chapter 0609, Significance Determination Process, Attachment 4, Initial Characterization of Findings, and Appendix A, The Significance Determination Process for Findings At-Power, and determined that the finding was of very low safety significance (Green) because the finding was not a design deficiency resulting in the loss of functionality or operability. A cross-cutting aspect was not identified because this performance deficiency has existed since 1993 and was not indicative of current licensee performance. |
Site: | Browns Ferry |
---|---|
Report | IR 05000259/2013007 Section 1R21 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | C Baron G Ottenberg M Riley R Nease R Patterson S Kobylarz S Walker |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control Technical Specification |
INPO aspect | |
' | |
Finding - Browns Ferry - IR 05000259/2013007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Browns Ferry) @ 2013Q2
Self-Identified List (Browns Ferry)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||