05000259/FIN-2013007-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Evaluate the Effects of the Failure of Non-Class 1E Load Center Transformer Cooling Fans on the Class 1E 4160-480V Load Center Transformers and 480V Shutdown Boards |
Description | The team identified a non-cited violation of 10 CFR 50, Appendix B, Criterion III, Design Control, involving the failure to evaluate the effects of a postulated failure of the load center transformer non-safety-related, non-Class 1E cooling fans, which includes the fan power wiring and fan control equipment, on the safety-related Class 1E shutdown board load center transformers and 480V shutdown boards. This was a performance deficiency. The licensee tested the fans and performed an operability evaluation as documented in Problem Evaluation Report 682254 to provide reasonable assurance that the safety-related transformers would not be damaged from postulated failures from the non-safety-related fans and be capable of operating when required for the design basis accident conditions. The performance deficiency was determined to be more than minor because the finding affected the Design Control attribute of the Mitigating Systems cornerstone objective of ensuring the availability, reliability, and capability of the load center transformers TS1A and TS1B and the 480V shutdown boards 1A and 1B respectively. Specifically, the licensee had not evaluated the effects of the failure of non-safety-related transformer cooling fans, on both the safetyrelated load center transformer and 480V shutdown board and resulted in a reasonable doubt of operability. The team used Inspection Manual Chapter 0609, Significance Determination Process, Attachment 4, Initial Characterization of Findings, and Appendix A, The Significance Determination Process for Findings At-Power, and determined that the finding was of very low safety significance (Green) because the finding was not a design deficiency resulting in the loss of functionality or operability. A cross-cutting aspect was not identified because this performance deficiency has existed since November 2004; therefore, not indicative of current licensee performance. |
Site: | Browns Ferry |
---|---|
Report | IR 05000259/2013007 Section 1R21 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | C Baron G Ottenberg M Riley R Nease R Patterson S Kobylarz S Walker |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control Technical Specification |
INPO aspect | |
' | |