05000259/FIN-2010002-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | New Fuel Receipt Inspection and Refueling Operations Supervised By Non-qualified Senior Reactor Operators |
Description | The inspectors identified a noncited violation of Technical Specifications 5.4.1.a for the failure to comply with operating procedures for Unit 3 new fuel receipt inspection and refueling operations that required the Fuel Handling Supervisor (FHS) to be trained and certified. During Unit 3 new fuel receipt inspections and refueling operations unqualified senior reactor operators (SRO) were allowed to supervise fuel handling activities. The unqualified SROs were subsequently re-qualified or not allowed to supervise fuel handling activities until qualified. This issue was entered into the licensees corrective action program as problem evaluation reports 220410 and 220791. This finding was determined to be of greater than minor significance because it was associated with the Barrier Integrity Cornerstone attribute of Human Performance, and adversely affected the cornerstone objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. Specifically, the use of unqualified FHS(s) to supervise new fuel receipt inspection and core refueling operations would reduce the level of assurance that fuel handling activities were accomplished safely and error free to prevent inadvertent fuel damage. The finding was evaluated and determined to be of very low safety significance using Inspection Manual Chapter 0609, Appendix G, Shutdown Operations Significance Determination Process, Attachment 1, Phase 1 Operational Checklists, Checklist 7, because it did not involve any human performance errors that resulted in fuel assembly damage, inappropriate core alteration, loss of reactor coolant and/or spent fuel pool inventory, or reduction of any safe shutdown mitigation capability. The cause of this finding was directly related to the cross-cutting aspect of Procedural Compliance in the Work Practices component of the Human Performance area because neither the night shift FHS or relief FHS(s) complied with the operating procedure requirements that all personnel supervising new fuel receipt inspections and/or refueling operations must be qualified [(H.4(b) |
Site: | Browns Ferry ![]() |
---|---|
Report | IR 05000259/2010002 Section 1R20 |
Date counted | Mar 31, 2010 (2010Q1) |
Type: | NCV: Green |
cornerstone | Barrier Integrity |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.2 |
Inspectors (proximate) | C Stancil T Ross H Gepford E Guthrie R Baldwin K Korth M Coursey |
CCA | H.8, Procedure Adherence |
INPO aspect | WP.4 |
' | |
Finding - Browns Ferry - IR 05000259/2010002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Browns Ferry) @ 2010Q1