05000259/FIN-2013011-14
From kanterella
Revision as of 07:59, 25 September 2017 by StriderTol (talk | contribs) (Created page by program invented by Mark Hawes)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Failure to Implement an Adequate Test Program for RHRSWS and EECS |
Description | The team identified a non-cited violation of 10CFR50, Appendix B, Criterion XI, Test Control, because the licensee did not establish a test program for Residual Heat Removal Service Water (RHRSW) and Emergency Equipment Cooling Water (EECW) pumps such that the test adequately demonstrated the pumps would perform satisfactorily in service. Specifically, BFN did not perform RHRSW/EECW pump performance testing such that it adequately accounted for river water temperature impact on the pump lift, which affected pump flow and vibration performance. The test program did not account for changes to pump lift caused by river water temperature changes; as a result the test program did not adequately monitor pump and system performance and degradation. The licensee completed a prompt operability determination verifying that the pumps remained operable and documented the issue in PERs 730497 and 741036. The Finding was more than minor because at affected the Mitigating System Cornerstone and if left uncorrected, could become a more significant safety concern. The team determined the Finding was of very low safety significance because it was not a design or qualification deficiency, and it did not result in an actual loss of one or more trains of the RHRSW or EECW systems and/or their function. The Finding had a crosscutting aspect in the area of Problem Identification and Resolution, Corrective Action Program, because the licensee did not to thoroughly evaluate the changes in RHRSW and EECW pump performance such that the resolution addressed the causes and extent-of-condition. |
Site: | Browns Ferry |
---|---|
Report | IR 05000259/2013011 Section 4OA4 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 95003 |
Inspectors (proximate) | C Even C Moore E Guthrie J Eargle J Heinly R Skokowski |
Violation of: | 10 CFR 50 Appendix B Criterion XI |
CCA | P.2, Evaluation |
INPO aspect | PI.2 |
' | |