ML052430152

From kanterella
Revision as of 15:23, 14 March 2020 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Technical Specification Pages Re Surveillance Frequency Improvements
ML052430152
Person / Time
Site: Pilgrim
Issue date: 08/29/2005
From:
Office of Nuclear Reactor Regulation
To:
References
Download: ML052430152 (7)


Text

PNPS TABLE 4.1.1 REACTOR PROl 7ECTION SYSTEM (SCRAM) INSTRUMENTATION FUNCTIONAL TESTS MINIMUM FUNCTIONAL TE:ST FREQUENCIES FOR SAFETY INSTRUMENTATION AND CONTROL CIRCUITS Functional Test Minimum Frequencv (3)

Mode Switch in Shutdown Place Mode Switch in Shutdown Each Refueling Outage Manual Scram Trip Channel and Alarm Every 3 Months RPS Channel Test Switch (5) Trip Channel and Alarm Once per week IRM High Flux Trip Channel and Alarm (4) Once Per Week During Refueling Inoperative and Before Eac Startup Trip Channel and Alarm Once Per Week During Refueling APRM and Before Each Startup High Flux Trip Output Relays 4 Every 3 Months Inoperative Trip Output Relays 4 Every 3 Months I Flow Bias Trip Output Relays 4 Every 3 Months High Flux (15%) Trip Output Relays 4 Once Per Week During Refueling and Before Each Startup High Reactor Pressure Trip Channel and Alarm (4) Every 3 Months High Drywell Pressure Trip Channel and Alarm (4) Every 3 Months Reactor Low Water Level Trip Channel and Alarm (4) Every 3 Monlths High Water Level in Scram Discharge Tanks Trip Channel and Alarm (4) Every 3 Months Main Steam Line Isolation Valve Closure Trip Channel and Alarm Every 3 Months Turbine Control Valve Fast Closure Trip Channel and Alarm Every 3 Months Turbine First Stage Pressure Permissive Trip Channel and Alarm (4) Every 3 Months Turbine Stop Valve Closure Trip Channel and Alarm Every 3 Months Reactor Pressure Permissive Trip Channel and Alarm (4) Every 3 Months Amendment No.73-999, 117, 117,162, 151, 217 I 3/4.1-5

NOTES FOR TABLE 4.1.1

1. Deleted
2. Deleted
3. Functional tests are not required when the systems are not required to be operable or are tripped.

If tests are missed, they shall be performed prior to returning the systems to an operable status.

4. This instrumentation is exempted from the instrument channel test definition. This instrument channel functional test will consist of injecting a simulated electrical signal into the measurement channels.
5. Test RPS channel after maintenance.

Amendment No. 6, 79, 117, 217 3/4.1-6

PNPS TABLE 4.1.2 REACTOR PROTECTION SYSTEM (SCRAM) INSTRUMENT CALIBRATION MINIMUM CALIBRATION FREQUENCIES FOR REACTOR PROTECTION INSTRUMENT CHANNELS Instrument Channel Calibration Test (5) Minimum Frequency (2)

IRM High Flux Comparison to APRM on Controlled Note (4)

Shutdowns Full Calibration Once per Operating Cycle APRM High Flux Output Signal Heat Balance (8) Once every 3 Days I Flow Bias Signal Calibrate Flow Comparator At least once every and Flow Bias Network 18 Months Calibrate Flow Bias Signal (1) Every 3 Months LPRM Signal TIP System Traverse Every 1000 Effective Full Power Hours High Reactor Pressure Note (7) Note (7)

High Drywell Pressure Note (7) Note (7)

Reactor Low Water Level Note (7) Note (7)

High Water Level in Scram Discharge Tanks Note (7) Note (7)

Main Steam Line Isolation Valve Closure Note (6) Note (6)

Turbine First Stage Pressure Permissive Note (7) Note (7)

Turbine Control Valve Fast Closure Standard Pressure Source Every 3 Months Turbine Stop Valve Closure Note (6) Note (6)

Reactor Pressure Permissive Note (7) Note (7)

Amendment No. 4O,-9, 9X, 117,4151, 164,1514, 217 3/4.1-7

NOTES FOR TABLE 4.1.2

1. Adjust the flow bias trip reference, as necessary, to conform to a calibrated flow signal.
2. Calibration tests are not required when the systems are not required to be operable or are tripped.
3. Deleted.
4. Maximum frequency required is once per week.

5.. Response time is not a part of the routine instrument channel test, but will be checked once per operating cycle.

6. Physical inspection and actuation of these position switches will be performed during the refueling outages.
7. Calibration of these devices will be performed during refueling outages.

To verify transmitter output, a daily instrument check will be performed. Calibration of the associated analog trip units will be performed concurrent with functional testing as specified in Table 4.1.1.

8. Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after thermal power is > 25% rated thermal power.

Amn m n N. 7 . 1 1 7.9 1. 21 , .. 3/4.1

. -8..............

Amendment No. 79, 99, 147,4164, 217 3/4.1-8

PNPS TABLE 4.2.D MINIMUM TEST AND CALIBRATION FREQUENCY FOR RADIATION MONITORING SYSTEMS Instrument Channels Instrument Functional Calibration Instrument Check I Test

1) Refuel Area Exhaust Monitors - Upscale (1) Once/3 months Once/day
2) Refuel Area Eihaust Monitors - Downscale (1) Once/3 months Once/day Logic System Functional Test (4) (6) Frequency
1) Reactor Building Isolation Once/Operating Cycle
2) Standby Gas Treatment System Actuation Once/Operating Cycle Amendment No. 89A-301 -161, 217 9-.q I./4 I

PNPS TABLE 4.2.G MINIMUM TEST AND CALIBRATION FREQUENCY FOR ATWS RPT/ARI INSTRUMENTATION Instrument Instrument Functional Instrument Channel Test Calibration Check I

1. Reactor High Pressure (1) (7) (7) Once/day
2. Reactor Low-Low Water (1) (7) (7) Once/day Level I

Amendment No. 42, 68, 83, 121, 217 314.2-39

NOTES FOR TABLES 4.2.A THROUGH 4.2.G

1. Initially once per month until exposure hours (Mas defined on Figure 4.2-1) is 2.0 x 105; thereafter, according to Figure 4.2-1 with an interval not less than one month nor more than three months.
2. Calibrations of IRMs and SRMs shall be performed during each startup or during controlled shutdowns with a required frequency not to exceed once per week.
3. Deleted.
4. Simulated automatic actuation shall be performed once each operating cycle. Where possible, all logic system functional tests will be performed using the test jacks.
5. Reactor low water level and high drywell pressure are not included on Table 4.2.A since they are tested on Tables 4.1.1 and 4.1.2.
6. The logic system functional tests shall include a calibration of time delay relays and timers necessary for proper functioning of the trip systems.
7. Calibration of analog trip units will be performed concurrent with functional testing.

The functional test will consist of injecting a simulated electrical signal into the measurement channel. Calibration of associated analog transmitters will be performed each refueling outage.

Amendment No.2, 99, 10, 1.7,151,16, 18, 217 3/4.2-41 3/4.2-41