ML052430152
| ML052430152 | |
| Person / Time | |
|---|---|
| Site: | Pilgrim |
| Issue date: | 08/29/2005 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| References | |
| Download: ML052430152 (7) | |
Text
REACTOR PROl MINIMUM FUNCTIONAL TE Mode Switch in Shutdown Manual Scram RPS Channel Test Switch (5)
IRM High Flux Inoperative APRM High Flux Inoperative Flow Bias High Flux (15%)
High Reactor Pressure High Drywell Pressure Reactor Low Water Level High Water Level in Scram Discharge Tanks Main Steam Line Isolation Valve Closure Turbine Control Valve Fast Closure Turbine First Stage Pressure Permissive Turbine Stop Valve Closure Reactor Pressure Permissive PNPS TABLE 4.1.1 7ECTION SYSTEM (SCRAM) INSTRUMENTATION FUNCTIONAL TESTS
- ST FREQUENCIES FOR SAFETY INSTRUMENTATION AND CONTROL CIRCUITS Functional Test Minimum Frequencv (3)
Place Mode Switch in Shutdown Each Refueling Outage Trip Channel and Alarm Every 3 Months Trip Channel and Alarm Once per week Trip Channel and Alarm (4)
Trip Channel and Alarm Trip Output Relays 4 Trip Output Relays 4 Trip Output Relays 4 Trip Output Relays 4 Trip Channel and Alarm (4)
Trip Channel and Alarm (4)
Trip Channel and Alarm (4)
Trip Channel and Alarm (4)
Trip Channel and Alarm Trip Channel and Alarm Trip Channel and Alarm (4)
Trip Channel and Alarm Trip Channel and Alarm (4)
Once Per Week During Refueling and Before Eac Startup Once Per Week During Refueling and Before Each Startup Every 3 Months Every 3 Months Every 3 Months Once Per Week During Refueling and Before Each Startup Every 3 Months Every 3 Months Every 3 Monlths Every 3 Months Every 3 Months Every 3 Months Every 3 Months Every 3 Months Every 3 Months I
I Amendment No.73-999, 117, 117,162, 151, 217 3/4.1-5
NOTES FOR TABLE 4.1.1
- 1.
Deleted
- 2.
Deleted
- 3.
Functional tests are not required when the systems are not required to be operable or are tripped.
If tests are missed, they shall be performed prior to returning the systems to an operable status.
- 4.
This instrumentation is exempted from the instrument channel test definition. This instrument channel functional test will consist of injecting a simulated electrical signal into the measurement channels.
- 5.
Test RPS channel after maintenance.
Amendment No. 6, 79, 117, 217 3/4.1-6
PNPS TABLE 4.1.2 REACTOR PROTECTION SYSTEM (SCRAM) INSTRUMENT CALIBRATION MINIMUM CALIBRATION FREQUENCIES FOR REACTOR PROTECTION INSTRUMENT CHANNELS Instrument Channel IRM High Flux Calibration Test (5)
Comparison to APRM on Controlled Shutdowns Full Calibration APRM High Flux Output Signal Flow Bias Signal Heat Balance (8)
Calibrate Flow Comparator and Flow Bias Network Calibrate Flow Bias Signal (1)
TIP System Traverse LPRM Signal High Reactor Pressure High Drywell Pressure Reactor Low Water Level High Water Level in Scram Discharge Tanks Main Steam Line Isolation Valve Closure Turbine First Stage Pressure Permissive Turbine Control Valve Fast Closure Turbine Stop Valve Closure Reactor Pressure Permissive Note (7)
Note (7)
Note (7)
Note (7)
Note (6)
Note (7)
Standard Pressure Source Note (6)
Note (7)
Minimum Frequency (2)
Note (4)
Once per Operating Cycle Once every 3 Days At least once every 18 Months Every 3 Months Every 1000 Effective Full Power Hours Note (7)
Note (7)
Note (7)
Note (7)
Note (6)
Note (7)
Every 3 Months Note (6)
Note (7)
I Amendment No. 4O,-9, 9X, 117,4151, 164,1514, 217 3/4.1-7
NOTES FOR TABLE 4.1.2
- 1.
Adjust the flow bias trip reference, as necessary, to conform to a calibrated flow signal.
- 2.
Calibration tests are not required when the systems are not required to be operable or are tripped.
- 3.
Deleted.
- 4.
Maximum frequency required is once per week.
5..
Response time is not a part of the routine instrument channel test, but will be checked once per operating cycle.
- 6.
Physical inspection and actuation of these position switches will be performed during the refueling outages.
- 7.
Calibration of these devices will be performed during refueling outages.
To verify transmitter output, a daily instrument check will be performed. Calibration of the associated analog trip units will be performed concurrent with functional testing as specified in Table 4.1.1.
- 8.
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after thermal power is > 25% rated thermal power.
A m n m n N. 7.
.9 1 1 7 1.
2 1 3 /4.1 -8..............
Amendment No. 79, 99, 147,4164, 217 3/4.1-8
PNPS TABLE 4.2.D MINIMUM TEST AND CALIBRATION FREQUENCY FOR RADIATION MONITORING SYSTEMS Instrument Channels Instrument Functional Test
- 1)
Refuel Area Exhaust Monitors - Upscale (1)
- 2)
Refuel Area Eihaust Monitors - Downscale (1)
Calibration Instrument Check I
Once/3 months Once/3 months Once/day Once/day Logic System Functional Test (4) (6)
- 1)
Reactor Building Isolation
- 2)
Standby Gas Treatment System Actuation Frequency Once/Operating Cycle Once/Operating Cycle Amendment No. 89A-301-161, 217 I./4 9-.q I
PNPS TABLE 4.2.G MINIMUM TEST AND CALIBRATION FREQUENCY FOR ATWS RPT/ARI INSTRUMENTATION Instrument Channel Instrument Functional Test Instrument Check Calibration I
- 1. Reactor High Pressure
- 2. Reactor Low-Low Water Level (1) (7)
(1) (7)
(7)
Once/day (7)
Once/day I
Amendment No. 42, 68, 83, 121, 217 314.2-39
NOTES FOR TABLES 4.2.A THROUGH 4.2.G
- 1.
Initially once per month until exposure hours (M as defined on Figure 4.2-1) is 2.0 x 105; thereafter, according to Figure 4.2-1 with an interval not less than one month nor more than three months.
- 2.
Calibrations of IRMs and SRMs shall be performed during each startup or during controlled shutdowns with a required frequency not to exceed once per week.
- 3.
Deleted.
- 4.
Simulated automatic actuation shall be performed once each operating cycle. Where possible, all logic system functional tests will be performed using the test jacks.
- 5.
Reactor low water level and high drywell pressure are not included on Table 4.2.A since they are tested on Tables 4.1.1 and 4.1.2.
- 6.
The logic system functional tests shall include a calibration of time delay relays and timers necessary for proper functioning of the trip systems.
- 7.
Calibration of analog trip units will be performed concurrent with functional testing.
The functional test will consist of injecting a simulated electrical signal into the measurement channel. Calibration of associated analog transmitters will be performed each refueling outage.
Amendment No.2, 99, 10, 1.7,151,16, 18, 217 3/4.2-41 3/4.2-41