ENCLOSURE 3 OFFSITE DOSE CALCULATION MANUAL SEQUOYAH NUCLEAR PLANT REVISIONS 57 AND 58 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL Revision 57 Prepared By: George D. Flaherty Sponsor: Tonev Cross Date: 05/21/2012 PORC Review: Coleen Ware Date: 05/23/2012 Approval--Plant Manager: Paul Simmons Date:05/24/2012 Effective Date: 05/30/2012 SQN ODCM Revision 57 Page 2 of 179 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL REVISION LOG (Page 1 of 2)Revision Effective Description of Revision Number Date 51 11/24/2006 DCN 21837 Turbine Building Sump Radiation Monitor (0-RM-90-212)
Replacement also provides Flow on ICS. ICS Computer Point (0-F-4300A) is being made a compliance point.52 01/04/2007 Replaced thermoluminescent dosimeter with dosimeter.
WARL is switching to Vendor supplied dosimeter.
53 04/30/2008 Deleted 30,000 pCi/L Tritium non drinking water pathway, based on new NEI reporting guidelines for Tritium in groundwater.
Added wording to allow 0-RE-90-122 setpoint to be set at a default setpoint.54 12/05/2008 Added containment radiation monitors as compliance instruments due to Exigent TSC 08-07 request. Added reporting requirements for NEI-07-07 compliance.
55 02/17/2009 Added clarification to action 48 on page 22 for purging containment if containment radiation is not operable.56 09/21/2010 Page 15 added clarification for weir overflowing.Page 45 Added Table 2.3-4 LLD's for HTD nuclides for groundwater.
Pages 104, 106, 107, 108, 109, 110 updated x/Q. Page 109 updated D/Q. Pages 107, 108, 109, 110 and 112 updated dates for x/Q and or D/Q. Page 132 and 133 updated meteorological data for x/Q and D/Q. Page 171 added to checklist to check if revision affects NOUE and ALERT calculation values in SQS20247.57 05/30/2012 PER 361162 corrected date range on Table 7.1 and 7.2 header, pages 139 and 140. PER 361162 corrected schematic page 152. PER 463540 changed radiation monitor testing frequency from quarterly to semi-annually, pages 16 and 22. OPS request to clarify applicability note for page 19, item 2.b. Add C-14 to dose calculations to meet NRC requirement to incorporate C-14 in Site Annual Report.Added statement that C-14 will be estimated using EPRI methodology, EPRI report 1021106. NRC has accepted this method for providing C-14 estimates.
This updates pages 111,115,116,&129-134.
Correction made to Sr-89 and Sr-90 LLD on page 44.
SQN ODCM Revision 57 Page 3 of 179 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL REVISION LOG (Page 1 of 2)Revision Approval Date Revision Approval Date Effective Date Original ODCM 2/29/801 Revision 28 9/22/926 12/1/92 Revision 1 4/15/802 Revision 29 3/30/937_
_Revision 2 10/7/802 Revision 30 9/30/932 Revision 3 11/3/80, 2/10/81, Revision 31 10/13/932 4/8/81, 6/4/812 Revision 4 10/22/81, 11/28/81, Revision 32 11/29/932 1/1/94 4/29/82, 11/22/822 Revision 5 10/21/822 Revision 33 2/25/942 Revision 6 1/20/832 Revision 34 4/29/942 5/15/94 Revision 7 3/23/83" Revision 35 10/20/946 11/15/94 Revision 8 12/16/832 Revision 36 7/20/95" 8/4/95 Revision 9 3/7/842 Revision 37 10/26/95D 11/6/95 Revision 10 4/24/842 Revision 38 2/15/966 2/23/96 Revision 11 8/21/84 Revision 39 11/12/965 1/17/97 Revision 12 2/19/852 Revision 40 4/2/98T 4/23/98 Revision 13 12/02/852 Revision 41 8/7/98 8/11/98 Revision 14 4/14/862 Revision 42 4/29/99 4/30/99 Revision 15 11'/5/863 Revision 43 4/29/99 4/30/99 Revision 16 1/16/872 Revision 44 6/17/99D 6/21/99 Revision 17 10/28/877 Revision 45 2/17/006 3/1/00 Revision 18 1/5/882 Revision 46 10/6/01 10/9/01 Revision 19 3/30/882 Revision 47 1/13/03 1/15/03 Revision 20 7/19/882 Revision 48 8/21/05 8/21/05 Revision 20A 12/14/88' Revision 49 5/17/06 5/23/06 Revision 21 2/15/89' Revision 50 9/29/06 9/29/06 Revision 22 6/1/89' See footnote 7 Revision 23 6/28/89, 9/15/894 Revision 25 11/2/90, 4/24/912 Revision 26 1/17/92 5 Revision 27 4/15/922 Revision 28 9/22/92b 1 Low power license for Sequoyah Unit 1.2 RARC Meeting Date.3 Date approved by RARC Chairman.4 Revision 23 implements the Nuclear Data Effluent Management Software.
This ODCM revision and the software will be implemented concurrently on October 9, 1989. Releases made during the month of October prior to the software implementation will be backfitted to comply with this revision.5 Revision 26 was recommended for approval by the SQN RARC at the October 2, 1991 meeting.The revision date is January 17, 1992. The final implementation date for Revision 26 will be March 17, 1992.6 PORC Meeting Date.7 New revision log started.
SQN ODCM Revision 57 Page 4 of 179 INTRODUCTION
...................................................................................................................................................................
8 1/2 CONTROLS AND SURVEILLANCE REQUIREM ENTS .........................................................................................
11 1/2 .0 A P P L IC A B IL IT Y .........................................................................................................................................................
11 1/2.1 INSTRUM ENTATION ..................................................................................................................................................
13 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUM ENTATION ................................................
13 TABLE 1. 1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION
.........................................
14 TABLE 2.1-1 -RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE RE QUIRE M ENTS ..................................................................................................................................................................
16 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
...........................................
18 TABLE 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
....................................
19 TABLE 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE RE QUIRE M ENTS ..................................................................................................................................................................
22 1/2.2 RADIOACTIVE EFFLUENTS
......................................................................................................................................
24 1/2.2.1 LIQUID EFFLUE NTS ................................................................................................................................................
24 1/2.2. 1.1 CONCENTRA TION ................................................................................................................................................
24 TABLE 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM .......................................
25 1/2 .2 .1.2 D O S E .......................................................................................................................................................................
2 8 1/2.2.1.3 LIQUID RADW ASTE TREATM ENT SYSTEM ..............................................................................................
29 1/2.2.2 GASEOUS EFFLUENTS
............................................................................................................................................
30 1/2 .2 .2 .1 D O S E RA T E ............................................................................................................................................................
30 TABLE 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM ...... 31 1/2.2.2.2 DOSE -NOBLE GASES ..........................................................................................................................................
34 1/2.2.2.3 DOSE 131, 1-133, TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GRE ATER THAN EIGHT DAYS ..........................................................................................................................................
35 1/2.2.2.4 GASEOUS RADW ASTE TREATM ENT ................................................................................................................
36 1/2 .2 .3 T O T A L D O S E .............................................................................................................................................................
3 7 1/2.3 RADIOLOGICAL ENVIRONM ENTAL MONITORING
.......................................................................................
38 1/2.3.1 M ONITORING PROGRA M .......................................................................................................................................
38 TABLE 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ..............
40 TABLE 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES42 TABLE 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)A,B .......................................
43 1/2.3.2 LAND USE CENSUS ..................................................................................................................................................
45 1/2.3.3 INTERLABORATORY COM PARISON PROGRAM ..........................................................................................
47 BASES ....................................................................................................................................................................................
49 IN STRUM ENTATION ...........................................................................................................................................................
49 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION
................................................
49 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
...........................................
49 1/2.2 RA DIOACTIVE EFFLUENTS
......................................................................................................................................
49 1/2.2.1.1 CONCENTRA TION ................................................................................................................................................
49 1/2 .2 .1.2 D O S E .......................................................................................................................................................................
4 9 1/2.2.1.3 LIQUID RADW ASTE TREATM ENT SYSTEM ..............................................................................................
50 1/2 .2 .2 .1 D O S E RA T E ............................................................................................................................................................
50 1/2.2.2.2 DOSE -NOBLE GASES ..........................................................................................................................................
51 1/2.2.2.3 DOSE 131, 1-133, TRITIUM, AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GRE ATER THAN EIGHT DAYS ..........................................................................................................................................
51 1/2.2.2.4 GASEOUS RADW ASTE TREATM ENT ................................................................................................................
52 1/2 .2 .3 T O T A L D O S E .............................................................................................................................................................
52 1/2.3 RADIOLOGICAL ENVIRONM ENTAL M ONITORING
.......................................................................................
53 1/2.3.1 MONITORING PROGRAM .......................................................................................................................................
53 1/2.3.2 LAND USE CENSUS ..................................................................................................................................................
53 1/2.3.3 INTERLABORATORY COM PARISON PROGRAM ..........................................................................................
53 3.0 DEFINITIONS
................................................................................................................................................................
55 3 .1 A C T IO N ...................................................................................................................................................................
5 5 SQN ODCM Revision 57 Page 5 of 179 3.2 CH AN NEL CALIBRA TIO N .....................................................................................................................................
55 3.3 CH ANNEL CH ECK .................................................................................................................................................
55 3.4 CH ANN EL F UN C TIONAL TEST ...........................................................................................................................
55 3.6 CO N TROLLED AREA .............................................................................................................................................
55 3.7 D OSE EQ UIVALEN T 1-131 ....................................................................................................................................
55 3.9 GASEO US RAD W ASTE TREA TM EN T SYSTEM ...............................................................................................
56 3.10 OPERABLE -OPERABILITY.
.....................................................................................................................................
56 3. 11 M OD E .........................................................................................................................................................................
56 3.12 P URGE -P URGIN G ...............................................................................................................................................
56 3.13 RAD IA TION M ONITOR (RM ) OR (R) ...........................................................................................................
56 3.14 RA TED TH ERM PL PO W ER ...................................................................................................................................
56 3.16 RESTRIC TED AREA ...............................................................................................................................................
57 3.17 SITE BO UN DAR Y ...................................................................................................................................................
57 3.18 SO URCE/SENSO R CH ECK ....................................................................................................................................
57 3.19 UNRESTRIC TED AREA/BO UND AR Y ....................................................................................................................
57 3.20 VEN TILA TION EXH A UST TREA TM EN T SYSTEM ..........................................................................................
57 3.21 VEN T FLO W RA TE M ONITOR (F) ........................................................................................................................
57 3.22 VEN TIN G ................................................................................................................................................................
57 TABLE 3.1 FREQ U EN C Y N O TA TIO N ..................................................................................................................................
58 FIGURE 3.1 U N RESTRICTED A REA BO U N D A RY ........................................................................................................
59 5.0 A D M IN IST R A TIV E C O N T R O LS ................................................................................................................................
62 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT ............................................................
62 5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT ..................................................................................
62 5.3 O FFSITE D O SE C A LCU LA TIO N M A N U A L CHA N G ES .......................................................................................
64 5.4 SPECIA L RE PO RTS .........................................................................................................................................................
64 SE C T IO N 6.0 LIQ U ID E FFLU EN T S .................................................................................................................................
66 RE LEA SE PO IN TS .................................................................................................................................................................
66 6.1 LIQ U ID RE LEA SES .........................................................................................................................................................
68 6.1.1 Pre-Release Analyisis
.................................................................................................................................................
68 6.1.2 Effluent Concentration Lim its (ECL)-Suni of the Ratios .......................................................................................
68 6.1.3 Post-Release Analysis .................................................................................................................................................
69 6.2 IN STRU M EN T SETPO IN TS ............................................................................................................................................
70 6.2.1 D ischarge Point M onitor Setpoints (0-RM 133,134,140,141)
.........................................................................
70 6.2.2 Release Point Monitor Setpoints (0-RM-90-122:
0-RMI-90-225:
0-RM-90-212; 1,2-RM-90-120.121)
................
70 6.2.3 Batch Release Point M onitor Setpoint ........................................................................................................................
70 6.3 CUMULATIVE LIQUID EFFLUENT DOSE CALCULATIONS
..............................................................................
72 6.3.1 M onth Do D ose Calculations
........................................................................................................................................
73 6. 3.2 Cum ulative D oses .......................................................................................................................................................
73 6.3.3 Comparison to Lim its .................................................................................................................................................
73 6.4 LIQ U ID RA D W A STE TREA TM EN T SY STEM .......................................................................................................
74 6.5 D O SE PRO JECTIO N S ......................................................................................................................................................
75 6.6 Q U A RTERLY D O SE CA LC U LA TIO N S .........................................................................................................................
76 6.6. 1 W A TER IN GESTIO N ..................................................................................................................................................
76 6.6. 2 FISH IN G ESTION ......................................................................................................................................................
77 6.6.3 SH ORELINE RECREA TION ......................................................................................................................................
77 6.6.4 TO TAL M AX IM UM IND IVID UAL D OSE .................................................................................................................
78.6. 6.5 PO P ULA TIO N D OSES ..............................................................................................................................................
78 6.7 LIQ U ID D O SE FA CTO R EQ U A TIO N S ..........................................................................................................................
81 6.7.1 WA TER IN GESTION .................................................................................................................................................
81 6.7.2 FISH IN G ESTIO N ......................................................................................................................................................
81 6. 7.3 SH O RELIN E RECREA TION ......................................................................................................................................
81 TABLE 6.1 REC EPTO R S FO R LIQ U ID D O SE CA LC U LA TIO N S ...................................................................................
82 TABLE 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA ................................................
83 SQN ODCM Revision 57 Page 6 of 179 TABLE 6.3 DOSE CALCULATION FACTORS .....................................................................................................................
86 TABLE 6.4 INGESTION DOSE FACTORS ...........................................................................................................................
88 TABLE 6.5 BIOACCUM ULATION FACTORS FOR FRESHW ATER FISH ...................................................................
96 TABLE 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND ..................................
97 FIGuRE 6.1 LIQUID EFFLUENT RELEASE POINTS .....................................................................................................
99 FIGURE 6.2 LIQUID RADW ASTE SYSTEM .......................................................................................................................
100 SECTION 7.0 GASEOUS EFFLUENTS
...........................................................................................................................
102 RE LEASE POINTS DESCRIPTION
....................................................................................................................................
102 7.1 IN STRUM ENT SETPOINTS
..........................................................................................................................................
103 7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-131, O-RM-90-118)
..................................................................
103 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-131)
..............................................................................
103 7.1.1.2 Waste Gas Decay Tank Effl uent Monitor (0-RM-90-118)
.....................................................................................
103 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, O-RM-90-101, O-RM-90-132, 1,2-RM-90-99,119)
.........
105 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119)
...........................................................................................
105 7.2 GASEOUS EFFLUENTS
-DOSE RATES .....................................................................................................................
106 7.2 .1 (D e le te d) ...................................................................................................................................................................
1 0 6 7.2.2 RELEASE SAM PLING .............................................................................................................................................
106 7.2.3 NOBLE GAS DOSE RATES .....................................................................................................................................
106 7.2.3.1 Total BodyD Dose Rate ............................................................................................................................................
106 7.2 .3 .2 S k in D ose R a te .......................................................................................................................................................
10 7 7.2.4 1-13 1, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS- ORGAN DOSE RATE ................................
...............
..............
...............
108 7.3 DOSE -NOBLE GASES .................................................................................................................................................
109 7.3 .1 G am m a dose to a ir ...................................................................................................................................................
10 9 7.3 .2 B eta d ose to a ir .........................................................................................................................................................
10 9 7.3.3 Cumulative Dose -Noble Gas ..................................................................................................................................
110 7.3.4 C om p a riso n to L im its ...............................................................................................................................................
1 10 7.4 DOSE DUE TO 1-131,1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GRE ATER THAN 8 DAYS ................................................................................................................................
111 7.4.1 O rg a n dose C a lculta tio n ...........................................................................................................................................
111 7.4 .2 C u m u la tive D oses .....................................................................................................................................................
1 12 7.4.3 C o m p a riso n to L im its ...............................................................................................................................................
11 2 7.5 DOSE PROJECTIONS
....................................................................................................................................................
113 7.5.1 GASEOUS RAD WASTE TREA TMENT SYSTEM DESCRIPTION
...........................................................................
113 7.6 QUARTERLY DOSE CALCULATIONS
.......................................................................................................................
114 7.6.1 NOBLE GAS -GAMMA AIR DOSE .........................................................................................................................
114 7.6.2 NOBLE GAS -BETA AIR DOSE ..............................................................................................................................
114 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE .............................
115 7.6.3 RADIOIODINE, PARTICULA TE, CARBON- 14 AND TRITIUM -M4XIMUM ORGAN DOSE .............................
116 7.6. 4 POPULATION DOSES ............................................................................................................................................
117 7.6.4 POPULATION DOSES (continued)
.........................................................................................................................
118 7.6.5 RE PORTING OF DOSES .........................................................................................................................................
118 7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED or RESTRICTED AREA BOUNDARY]
18 7.7 GASEOUS RE LEASES -DOSE FACTORS .......................................................................................................................
119 7.7.1 PASTURE GRASS-CO W/GOA T-MJLK INGESTION DOSE FA CTORS .................................................................
119 7.7.2 STORED FEED-CO W/GOA T-MJLK INGESTION DOSE FACTORS .....................................................................
120 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS .......................................................................................
121 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS ..........................................................................................
122 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS ................................................................................
123 7.7.6 STORED VEGET4BLE INGESTION DOSE FACTORS ..........................................................................................
124 7.7.7 TRITIUM-PASTURE GRASS-COW/GOA T-MILK DOSE FACTOR ........................................................................
125 7. 7.8 TRITIUM-STORED FEED-CO W/GOA T-MILK DOSE FA CTOR ...........................................................................
125 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR .............................................................................................
126 SQN ODCM Revision 57 Page 7 of 179 7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR ...............................................................................................
126 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR ..................................................................................
127 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR ............................................................................................
128 7.7.13 CARBON 14 -PASTURE GRASS-COW/GOAT MILK DOSE FACTOR -RCPC14 ...............................................
129 7.7.14 CARBON 14 -STORED FEED-COW/GOAT MILK DOSE FACTOR -RCSC14 ...................................................
130 7.7.15 CARBON 14 -PASTURE GRASS-BEEF DOSE FACTOR -RMC14 ......................................................................
131 7.7.16 CARBON 14 -SRORED FEED-BEEF DOSE FACTOR -RMSC14 .......................................................................
132 7.7.17 CARBON 14 -FRESH LEAFY VEGETABLE DOSE FACTOR -R VFCI4 .............................................................
133 7.7.18 CARBON 14-STORED VEGETABE DOSE FACTOR -RVSC14 ...........................................................................
134 7.7.19 IN H ALA TIO N D O SE FA C TO RS ............................................................................................................................
135 7.7.20 GR O UN D PLAN E D O SE FA C TO RS .....................................................................................................................
135 7.8 D ISPERSIO N M ETTH O D O L O G Y ................................................................................................................................
136 7.8.1 A IR C O N C E N TRA TIO N ..........................................................................................................................................
136 7.8.2 RELA TIVE C O N CEN TRA TIO N ...............................................................................................................................
137 7.8.3 RE LA TIVE D E P O SITIO N ........................................................................................................................................
138 TABLE 7.1 SEQUOYAH MAXIMUM QUARTERLY X/Q (1999-2008)
SORTED BY QUARTER ......................................................
139 TABLE 7.2 SEQUOYAH MAXIMUM QUARTERLY D/Q (1999-2008)
SORTED BY QUARTER ......................................................
140 TABLE 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES .............................................................................
141 TABLE 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES ...............................................................
142 TABLE 7.5 POPULATION WITHIN EACH SECTOR ELEMENT ......................................................................................
143 TABLE 7.6 IN H A LA TIO N D O SE FA CTO RS ......................................................................................................................
144 FIGURE 7.1 GASEOUS EFFLUENT RELEASE POINTS ....................................................................................................
152 FIGURE 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL) ...........................................................................
154 FIGURE 7.3 GASEOUS RADWASTE TREATMENT SYSTEM ..........................................................................................
155 FIGURE 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES ..........................................................
156 FIGURE 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME ..........................................................
157 FIGURE 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES .....................................................................
158 SECTION 8.0 TOTAL DOSE ............................................................................................................................................
160 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES -TOTAL REPORTED DOSE .............................................................
160 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ..............................................
162 9.1 M O N IT O R IN G PR O G R A M ...........................................................................................................................................
162 9.2 D ET E C T IO N C A PA B IL IT IE S .......................................................................................................................................
162 9 .3 L A N D U S E C E N S U S ......................................................................................................................................................
162 9.4 INTERLABORATORY COMPARISON PROGRAM ...................................................................................................
162 TABLE 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM .............................................................
163 TABLE 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS
.................
167 TABLE 9.3 THERMOLUMINESCENT DOSIMETRY LOCATIONS
.................................................................................
168 FIGURE 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT .........................
170 FIGURE 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT ..... 171 FIGURE 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT. 172 APPENDIX A -SQN ODCM REVISION PROCESS .......................................................................................................
173 SQN ODCM Revision 57 Page 8 of 179 INTRODUCTION This Offsite Dose Calculation Manual (ODCM) is in support of the Tennessee Valley Authority (TVA)facility operating licenses for a two-unit nuclear power plant located approximately
7.5 miles
northeast of Chattanooga at the Sequoyah site in Hamilton County, Tennessee.
This facility has been designated the Sequoyah Nuclear Plant (SQN). The plant has been designed, built, and is operated by TVA. Each of the two identical units employs a Pressurized Water Reactor Nuclear Steam Supply System (NSSS) with four coolant loops furnished by Westinghouse Electric Corporation.
Each of the two reactor cores is rated at 3,455 MWt and, at this core power, the NSSS will operate at 3,467 MWt. The additional 12 MWt is due to the contribution of heat of the Primary Coolant System from nonreactor sources, primarily reactor coolant pump heat. Each of the reactor cores has an Engineered Safeguards Design rating of 3577 MWt and at this core power, the NSSS will operate at 3565 MWt. The net electrical output is 1211 Mwe for Unit 1 and 1188 Mwe for Unit 2 at the rated core power. All plant safety systems, including containment and engineered safety features, are designed and evaluated at the higher power level. In addition, the higher power rating is used in the analysis of postulated accidents having as a consequence the release of fission product activity to the environment.
The containment for each of the reactors consists of a freestanding steel vessel with an ice condenser and separate reinforced concrete shield building.
The freestanding steel vessel and the concrete shield building were designed by TVA and the ice condenser was furnished by the Westinghouse Electric Corporation.
Unit 1 began commercial operation on July 1, 1981. Unit 2 began commercial operation on June 1, 1982.
SQN ODCM Revision 57 Page 9 of 179 The ODCM is divided into two major parts. The first part of the ODCM contains: 1. Radioactive Effluent Controls required by Section 6.8.4.f of the SQN Technical Specifications;
- 2) Radiological Environmental Monitoring Controls;3) descriptions of the information that should be included in the Annual Radiological Environmental Operating and Annual Radioactive Effluent Release Reports required by SQN Technical Specifications 6.9.1.6 and 6.9.1.8; and, 4) Administrative Controls for the ODCM requirements.
The second part of the ODCM contains the methodologies used to: 1) calculate offsite doses resulting from radioactive gaseous and liquid effluents to the unrestricted area/boundary and the Tennessee River; 2) calculate gaseous and liquid effluent monitor Alarm/Trip setpoints; and, 3) conduct the Environmental Radiological Monitoring Program.The SQN ODCM will be maintained for use as a reference guide on accepted methodologies and calculations.
Changes in the calculation methods or parameters will be incorporated into the ODCM in order to assure that the ODCM represents the present methodology in all applicable areas. Any licensee initiated ODCM changes will be implemented in accordance with SQN Technical Specification 6.14 and ODCM Administrative Control 5.3.
SQN ODCM Revision 57 Page 10 of 179 SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS SQN ODCM Revision 57 Page 11 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.0 APPLICABILITY CONTROLS 1.0.1 Compliance with the Controls contained in the succeeding controls is required during the OPERATIONAL MODES or other conditions specified therein; except that upon failure to meet the Control, the associated ACTION requirements shall be met.1.0.2 Noncompliance with a Control shall exist when the requirements of the Control and associated ACTION requirements are not met within the specified time intervals.
If the Control is restored prior to the expiration of the specified intervals, completion of the ACTION requirements is not required.1.0.3 When a Control is not met, except as provided in the associated ACTION requirements, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> action shall be initiated to place the unit in a MODE in which the Control does not apply by placing it, as applicable, in: a. At least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, b. At least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, and c. At least COLD shutdown within the subsequent 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.1.0.4 Entry into an OPERATIONAL MODE or other specified condition shall not be made when the conditions for the Control are not met and the associated ACTION requires a shutdown if they are not met within a specified time interval.
Entry into an OPERATIONAL MODE or specified condition may be made in accordance with ACTION requirements when conformance to them permits continued operation of the facility for an unlimited period of time. This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with the ACTION requirements.
Exceptions to these requirements are stated in the individual Controls.
SQN ODCM Revision 57 Page 12 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.0 APPLICABILITY SURVEILLANCE REQUIREMENTS
2.0.1 Surveillance
Requirements shall be met during the OPERATIONAL MODES or other conditions specified for individual Controls unless otherwise stated in the individual Surveillance Requirement.
2.0.2 Each Surveillance Requirement shall be performed within the specified time interval with a maximum allowable extension not to exceed 25% of the specified surveillance interval.If an ACTION requires periodic performance on a "once per..." basis, the above frequency extension applies to each performance after the initial performance.
2.0.3 Failure
to perform a Surveillance Requirement within the specified time interval shall constitute a failure to meet the OPERABILITY requirements for a Control. The time limits of the ACTION requirements are applicable at the time it is identified that a Surveillance Requirement has not been performed.
The ACTION requirements may be delayed for up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to permit the completion of the surveillance when the allowable outage time limits of the ACTION requirements are less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Surveillance Requirements do not have to be performed on inoperable equipment.
2.0.4 Entry
into an OPERATIONAL MODE or other specified applicable condition shall not be made unless the Surveillance Requirement(s) associated with the Control has been performed within the applicable surveillance interval or as otherwise specified.
This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with ACTION requirements.
Exceptions to these requirements are stated in the individual Controls.
SQN ODCM Revision 57 Page 13 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.1 INSTRUMENTATION 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.1 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive liquid effluent monitoring instrumentation channels shown in Table 1.1-1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.1.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 6.2.APPLICABILITY:
This requirement is applicable during all releases via these pathways.ACTION: a. With a radioactive liquid effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive liquid effluents monitored by the affected channel or declare the channel inoperable, or change the setpoint so that it is acceptably conservative.
- b. With less than the minimum number of radioactive liquid effluent monitoring instrumentation channels OPERABLE, take the action shown in Table 1.1-1. Restore the inoperable instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2, why the inoperability could not be corrected within 30 days.c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
Report all deviations in the Annual Radioactive Effluent Release Report.SURVEILLANCE REQUIREMENTS 2.1.1. Each radioactive liquid effluent monitoring channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-1.
SQN ODCM Revision 57 Page 14 of 179 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Page 1 of 2)Minimum Instrument Channels Action OPERABLE 1. Gross Radioactivity Monitors Providing Automatic Termination of Release a. Liquid Radwaste Effluent Line (0-RM-90-122) 1 30 b. Steam Generator Blowdown Effluent Line 1 31 (1,2-RM-90-120A,121A)
- c. Condensate Demineralizer Effluent Line 1 30 (0-RM-90-225A)_
- 2. Gross Radioactivity Monitors a. Essential Raw Cooling Water Effluent Header** 1 32 (0-RM-90-133A,-1 34A,-140A,-141A)
- b. Turbine Building Sump Effluent Line 1 31 (0-RM-90-212A)
- 3. Flow Rate Measurement Devices a. Liquid Radwaste Effluent Line 1 33 (0-FI-77-42)
- b. Steam Generator Blowdown Effluent Line 1 33 (1,2-F-1 5-44,_1,2-F-15-43)
- c. Condensate Demineralizer Effluent Line 1 33 (0-FR-14-456, 0-F-14-185, 0-F-14-192)
- d. Cooling Tower Blowdown Effluent Line 1 33 Available Dilution Flow is provided on ICS computer point 0F2102DIF*.
- If Gate Structure
- 1 weir is overflowing with cooling towers not in service, indicated value on ICS point must be corrected by subtracting the estimated weir flow. If Cooling Towers are in service then verification of flow by other means is acceptable.
N/A If ERCW Maintenance activities were to limit the indicated ERCW Flow values <17,000 gpm and this ICS Computer Point is functional, other means of verifying total discharge into the Cold Water Channel are Acceptable.
- e. 1,2-FT-67-61 and 62. 1 33 f. Turbine Building Sump Discharge 1 36 0-F-40-3.
_5. Continuous Composite Sampler and Sample Flow Monitor a. Condensate Demineralizer Regenerant Effluent 1 35 Line (0-FI-14-466)
- Requires minimum of 1 Channel/Header to be OPERABLE.
SQN ODCM Revision 57 Page 15 of 179 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 2) TABLE NOTATION ACTION 30 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that prior to initiating a release: a. At least two independent samples of the tank's contents obtained by two technically qualified members of the facility staff are analyzed, and At least two technically qualified members of the Facility Staff independently verify the release rate calculations and;b. At least two technically qualified members of the Facility Staff independently verify the discharge valve lineup.Otherwise, suspend release of radioactive effluents via this pathway.ACTION 31 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are analyzed for principal gamma emitters in accordance with SR 2.2.1.1.1 and 2.2.1.1.2.
- a. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the specific activity of the secondary coolant is greater than or equal to 0.01 [tCi/g DOSE EQUIVALENT 1-131.b. At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the specific activity of the secondary coolant is less than 0.01 pCi/g DOSE EQUIVALENT 1-131.ACTION 32-With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided that, at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples are collected and analyzed for principal gamma emitters at a limit of detection of at least 5.0x10-7 O Ci/ml.ACTION 33 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases.
Pump curves or the change in tank level indication, if applicable, may be used to estimate flow.ACTION 35 ACTION 36 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided representative batch samples of each tank to be released are taken prior to release and composited for analysis according to Table 2.2-1, footnote g.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases in accordance with plant procedures.
SQN ODCM Revision 57 Page 16 of 179 Table 2.1-1 -RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2)I SOURCE/ CHANNEL CHANNEL CHANNEL SENSOR CALIBRA- FUNCTIONAL Instrument CHECK CHECK_ TION TEST 1. Gross Beta or Gamma Radioactivity Monitors Providing Alarm and Automatic Termination of Release a. Liquid Radwaste Effluent Line D P R(3) S(1)(0-RM-90-122)
- b. Steam Generator Blowdown Effluent D M R(3) S(5)Line (1,2-RM-90-120A,121A)
- c. Condensate Demineralizer Effluent D M R(3) S(5)Line (0-RM-90-225A)
- 2. Gross Beta or Gamma Radioactivity Monitors Providing Alarm But Not Providing Automatic Termination of Release a. Essential Raw Cooling Water Effluent D M R(3) S(2)Line (0-RM-90-133A, 134A,140A, 141A)b. Turbine Building Sump Effluent Line D M R(3) S(2)(0-RM-90-212A)
- 3. Flow Rate Measurement Devices a. Liquid Radwaste Effluent Line D(4) N.A. R Q (0-FI-77-42)
- b. Steam Generator Blowdown Effluent D(4) N.A. R Q Line (1,2-Fl-1 5-44, 1,2-F-1 5-43)c. Condensate Demineralizer Effluent D(4) N.A. R Q Line (0-FR-14-456,0-F-14-192, 0-F-14-185)
- d. Cooling Tower Blowdown Effluent D(4) N.A. N.A N.A Line Available Dilution Flow is provide by ICS Computer Point OF2102DIF.
This computer point receives input From flow transmitters 1,2-FT-67-61 and 1,2-FT-67-62.
- e. 1,2-FT-67-61 and 62. N.A. N.A. R N.A.f. Turbine Building Sump Discharge D(4) N.A R. N.A 0-F-40-3 4. Continuous Composite Sampler and Sample Flow Monitor[a. Condensate Dernineralizer Regenerant_]
P [_N.A. R N.A.
SQN ODCM Revision 57 Page 17 of 179 Table 2.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2)(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above the alarm/trip setpoint.2. Circuit failure.3. Downscale failure.(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above an alarm setpoint.2. Circuit failure.3. Downscale failure.(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) or using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.(4) CHANNEL CHECK shall consist of verifying indication of flow during periods of release. CHANNEL CHECK shall be made at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> on days on which continuous periodic, or batch releases are made.(5) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions occur: 1. Instrument indicates measured levels above an alarm/trip setpoint.2. Circuit failure.The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room annunciation occurs if the following condition occurs: 1. Downscale failure.
SQN ODCM Revision 57 Page 18 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.1 INSTRUMENTATION 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.2 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive gaseous effluent monitoring instrumentation channels shown in Table 1.1-2 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.2.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 7.1.APPLICABILITY:
As shown in Table 1.1-2.ACTION: a. With a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive gaseous effluents monitored by the affected channel, declare the channel inoperable, or change the setpoint so it is acceptably conservative.
- b. With less than the minimum number of radioactive gaseous effluent monitoring instrumentation channels OPERABLE take the ACTION shown in Table 1.1-2. Restore the inoperable instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Report, pursuant to ODCM Administrative Control 5.2, why the inoperability could not be corrected within 30 days.c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
Report all deviations in the Annual Radioactive Effluent Release Report.SURVEILLANCE REQUIREMENTS 2.1.2 Each radioactive gaseous effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-2.
SQN ODCM Revision 57 Page 19 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING (Page 1 of 3)INSTRUMENTATION Minimum Channels Instrument OPERABLE Applicability Action 1. WASTE GAS DISPOSAL SYSTEM a. Noble Gas Activity Monitor (0-RM-90-118A) 1
- 40 b. Waste Decay Tanks Effluent Flow Rate 1
- 41 Measuring Device (0-FI-77-230)
- 2. CONDENSER VACUUM EXHAUST SYSTEM a. Noble Gas Activity Monitor (1,2-RM-90-99,119) 1
- 42 b. I Vent Flow Rate Monitor (1,2-F-2-256,257) 1 141 3. SHIELD BUILDING EXHAUST SYSTEM a. Noble Gas Vent Rate Activity Monitor 1** 43 (1,2-R-90-400 ,Eff)b. Iodine Sampler (1,2-FLT-90-402A or 402B) 1 *** 43,44 c. Particulate Sampler (1,2-FLT-90-402A or 402B) 1 *** 43,44 d. Vent Flow Rate Monitor (1,2-FM-90-400),(1,2-1.. 41,43 RI-90-400 Monitor Item 029 or 1,2-FI-90-400)
- e. Sampler Flow Rate Monitor (1,2-RI-90-400 1 45 Monitor Item 028 or 1,2-FI-90-400A)
- f. Primary Sampling Pumps (1,2-PMP-90-452A or 1"* 46 452B)4. AUXILIARY BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM-90-101B) 1
- 42 b. Iodine Sampler (0-FLT-90-101) 1 4* 4 c. Particulate Sampler (0-FLT-90-101) 1 4* 4 d. Vent Flow Rate Monitor (0-F-30-174) 1
- 41 e. Sampler Flow Rate Monitor (0-FIS-90-101) 1
- 45 5. SERVICE BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM-90-132B) 1
- 42 b. Vent Flow Rate Monitor (0-F-90-5132A) 1
- 41 6. LOWER CONTAINMENT AIRBORNE ACTIVITY FOR VENTING a. I Noble gas Activity Monitor (1,2-RM-90-106B,112B) 1 Modes 1-4 47 I (~durnn venting 7. CONTAINMENT AIRBORNE ACTIVITY FOR PURGING a. INoble gas Activity Monitor (1,2-RM-90-106B, 112B) 1 (for compartment Modes 1-4"*** 48 being purged)* At all times.** Operability of shield building noble gas vent rate activity monitor (Eff) requires primary sample pumps, vent flow rate and"Low Rng" radiation inputs since the high radiation alarm is only on the effluent channel (pCi/s). When the vent flow rate monitor is inoperable only the "Low Rng" radiation monitor is still capable of providing noble gas indication.
Its associated malfunction alarm on M-30 will alert Operations to any secondary failures such as loss of sample flow or detector failure. Therefore as long as the "Low Rng" is selected and the malfunction alarm is monitored RE-90-400 can be used to meet ODCM Noble gas and Particulate/Iodine sampler requirements.
Mid or High range channels do not have any ODCM requirements.
The vent flow rate monitor can be OPERABLE without the noble gas vent rate activity monitor.During exhaust system operation.
1,2-F-2-256 is the low range flow element (0-100 cfm). 1,2 -F-2-257 is a mid (0-1000)cfm flow element which should only be used for abnormal conditions.
SQN ODCM Revision 57 Page 20 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 3)TABLE NOTATION ACTION 40 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, the contents of the tank(s) may be released to the environment provided that prior to initiating the release: a. At least two independent samples of the tank's contents obtained by two technically qualified members of the facility staff are analyzed, and b. At least two technically qualified members of the Facility Staff independently verify the release rate calculations and;c. At least two technically qualified members of the Facility Staff independently verify the discharge valve lineup.Otherwise, suspend release of radioactive effluents via this pathway.ACTION 41 -ACTION 42 -ACTION 43 -ACTION 44 -ACTION 45 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity.Alarm Window M-5C-29, Vent Flow Rate only Inoperable
-With any inoperable vent flow monitor on a discharge pathway where a fan is operating (Purge A, Purge B, ABGTS, or EGTS), effluent release may continue provided: (a) "Low Rng" on RI-90-400 is selected instead of "Eff"; and (b) at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated instrument malfunction, M-30-15, is verified not annunciated; and (c) a reading from "Low Rng" on RE-90-400 is obtained at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The High Rad alarm on M-30 will not be operable under this alignment.
Also Action 41 must be complied with.Alarm Window M-30-15, Radiation Monitor Inoperable
-With the low range channel inoperable, effluent releases may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity.
Also Action 44 must be complied with.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via the affected pathway may continue provided that within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after the channel has been declared inoperable samples are continuously collected as required in Table 2.2-2. Also Action 45 must be complied with.With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, effluent releases via this pathway may continue provided the sampler flow rate is verified at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
SQN ODCM Revision 57 Page 21 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 3 of 3) TABLE NOTATION ACTION 46 With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, effluent releases via this pathway may continue provided (a) RM-90-400 is placed in manual sample flow control per SO-90-2, (b) "Low Rng" on RI-90-400 is selected instead of "Eff", and (c) at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated instrument malfunction is verified not annunciated; and (d) a reading from "Low Rng" on RE-90-400 is obtained at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The High Rad alarm on M-30 will not be operable under this alignment.
Action 46 does not apply if complying with Action 43 with RM-90-400 inoperable.
ACTION 47 With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, containment venting may continue provided a grab sample of the lower containment atmosphere is analyzed prior to each vent.ACTION 48 With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, containment purging may continue provided a grab sample of the compartment to be purged is analyzed prior to each purge. IF purging the incore instrument room, the purge sample shall be obtained at the shield building exhaust radiation monitor between 20 and 25 minutes following initiation of the incore instrument room PURGE or at the peak of the discharge based on the radiation monitor response.
SQN ODCM Revision 57 Page 22 of 179 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2)MODE in SOURCE/ CHANNEL CHANNEL Which Surveil-CHANNEL SENSOR CALIBRA- FUNCTIONAL lance Instrument CHECK CHECK TION TEST Required 1. WASTE GAS DISPOSAL SYSTEM a. Noble Gas Activity Monitor P P R(3) S(1)(0-RM-90-118A)
- b. Flow Rate Monitor (0-FI-77-230)
D N.A. R Q 2. CONDENSER VACUUM EXHAUST SYSTEM a. Noble Gas Activity Monitor D(5) M(4) R(3) S(2)(1,2-RM-90-99,119)
- b. Vent Flow Rate Monitor D N.A. R Q (1,2-F-2-256,257)
- 3. SHIELD BUILDING EXHAUST SYSTEM a. Noble Gas Vent Rate Activity D M R(3) S(2)Monitor (1,2-R-90-400AEff)
- b. Iodine Sampler W N.A. N.A. N.A.(1,2-FLT-90-402A or 402B)C. Particulate Sampler W N.A. N.A. N.A.(1,2-FLT-90-402A or 402B)d. Vent Flow Rate Monitor D N.A. R Q (1,2-FM-90-400 or 1,2-FI-90-400)
- e. Sampler Flow Rate Monitor D N.A. R Q (1,2-RI-90-400 or 1,2-FI-90-400A)
- f. Primary Sample Pumps W N.A N.A N.A (1,2-PMP-90-452A, 452B)4. AUXILIARY BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor D M R(3) S(2)(0-RM-90-101B)
- b. Iodine Sampler (0-FLT-90-101)
W N.A. N.A. N.A.c. Particulate Sampler (0-FLT-90-101)
W N.A. N.A. N.A. *d. Vent Flow Rate Monitor D N.A. R Q *(0-F-30-174)
- e. Sampler Flow Rate Monitor D N.A. R *(0-FIS-90-101)
- 5. SERVICE BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM D M R(3) S(2)132B)b. Vent Flow Rate Monitor (0-F-90-5132A)
D N.A. R Q 6. CONTAINMENT AIRBORNE ACTIVITY a. Noble Gas Activity Monitor D N.A. R N.A. 1-4 (1,2-RM-90-106B, 112B)7. CONTAINMENT AIRBORNE ACTIVITY a. Noble Gas Activity Monitor D 1 N.A. R N.A. 1-4 (1,2-RM-90-106B, 112B)
SQN ODCM Revision 57 Page 23 of 179 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2)TABLE NOTATION* At all times.During shield building exhaust system operation.
During waste gas releases.(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above the alarm/trip setpoint.2. Circuit failure.3. Downscale failure.(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above an alarm setpoint.2. Circuit failure.3. Downscale failure.(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.For the auxiliary building ventilation system only, at least once every 18 months, the CHANNEL CALIBRATION TEST shall also demonstrate automatic isolation of this pathway if the instrument indicates measured levels above the alarm/trip setpoint.(4) The SOURCE/SENSOR CHECK for the Condenser Vacuum Exhaust Monitor will be accomplished using an LED sensor check source or a radioactive source.(5) Applicable only to in-service monitor. Either 99 or 119 monitor will be in service for each unit.
SQN ODCM Revision 57 Page 24 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.1 CONCENTRATION CONTROLS 1.2.1.1 In accordance with SQN Technical Specifications 6.8.4.f.2 and 3, the concentration of radioactive material released through the diffuser piping to UNRESTRICTED AREAS (see Figure 3.1) shall be limited at all times to ten times the concentrations specified in 10 CFR Part 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 2X10" 4 ýtCi/ml total activity.APPLICABILITY:
At all times.ACTION: a. With the concentration of radioactive material released to UNRESTRICTED AREAS exceeding the above limits, immediately, restore the concentration to within the above limits.b. If samples or analyses required by Table 2.2-1 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.1.1 Radioactive liquid wastes shall be sampled and analyzed according to the sampling and analysis program of Table 2.2-1.2.2.1.1.2 The results of the radioactivity analysis shall be used in accordance with the methods in ODCM Section 6.1 to assure that the concentration at the point of release is maintained within the limits stated above.
SQN ODCM Revision 57 Page 25 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)Minimum Lower Limit of Sampling Analysis Type of Activity Detection (LLD)Liquid Release Type Frequency Frequency Analysis (ACi/ml)a A. Batch Waste Release Tanksd P P Principal Garnma 5x10-'1. Cask Decontamination Each Batch Each Batch Emitters Tank 2. Laundry Tanks (2) 1-131 1xl0-6 3. Chemical Drain Tank 5 4. Monitor Tank P M Dissolved/
1x10_One Batch/M Entrained Gases (Gamma Emitters)5 P M H-3 1x10_Each Batch Compositeb Gross Alpha 1x10-7 P Q Each Batch Compositeb Sr-89, Sr-90 5x10-8 Fe-55 Ixi1-6 B. Continuous Releasese D W Principal Gamma 5x10-1. Steam Generator Grab Sample Compositec Emittersf Blowdownh 2. Turbine Building Sumph M M 1-131 1x10 5-Grab Sample Dissolved/
1x10_Entrained Gases (Gamma Emitters)D M H-3 lx10i7 Grab Sample Compositec Gross Alpha 1x10-D Q 8 Grab Sample Compositec Sr-89, Sr-90 5x10-Fe-55 1x10-6 C. Periodic Continuous Continuousg W Principal Garpma 5x10-'Releasese,h Compositec Emitters 1. Non-Reclaimable Waste Tank M 9 M 1-131 lx10-6 2. High Crud Tanks (2) Grab Sample Dissolved/
1x10o-3. Neutralizer Tank Entrained Gases (Gamma Emitters)Continuousg M H-3 Compositec Gross Alpha 1x10-7 8 Continuous' Q Sr-89, Sr-90 5x10-6 1 Compositec Fe-55 1x10-SQN ODCM Revision 57 Page 26 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 2 of 3) TABLE NOTATION a The LLD is defined for the purpose of these specifications as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95%probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66s b LLD =E V 2.22x10 6 Y exp (-XkAt)Where: LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x10 6 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable), X is the radioactive decay constant for the particular radionuclide, and At for plant effluents is the elapsed time between midpoint of sample collection and time of counting (midpoint).
It should be recognized that the LLD is defined as an a priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
b A composite sample is one in which the quantity of liquid sampled is proportional to the quantity of liquid waste discharged and in which the method of sampling employed results in a specimen which is representative of the liquids released.c Prior to analyses, all samples taken for the composite shall be thoroughly mixed in order for the composite sample to be representative of the effluent release.
SQN ODCM Revision 57 Page 27 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 3 of 3) TABLE NOTATION d A batch release is the discharge of liquid wastes of a discrete volume. Prior to sampling for analyses, each batch shall be isolated, and then thoroughly mixed, by the method described in ODCM Section 6.1.1, to assure representative sampling.e A continuous release is the discharge of liquid wastes of a nondiscrete volume; e.g., from a volume or system that has an input flow during the continuous release.f The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:
Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, and Ce-141. Ce-144 shall also be measured with an LLD of 5x10-6.This list does not mean that only these nuclides are to be detected and reported.
Other peaks which are measurable and identifiable, together with the above nuclides, shall also be identified and reported.g Releases from these tanks are continuously composited during releases.
With the composite sampler or the sampler flow monitor inoperable, the sampling frequency shall be changed to require representative batch samples from each tank to be released to be taken prior to release and manually composited for these analyses.h Applicable only during periods of primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is set to alarm if activity in the stream exceeds a routine normal background, or compensatory requirements associated with applicable inoperable monitors are met.
SQN ODCM Revision 57 Page 28 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.2 DOSE CONTROLS 1.2.1.2 In accordance with SQN Technical Specification 6.8.4.f.4 and 5, the dose or dose commitment to a member of the public from radioactive materials in liquid effluents released to UNRESTRICTED AREAS shall be limited from each reactor unit: a. During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and b. During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.APPLICABILITY:
At all times.ACTION: a. With the calculated dose from the release of radioactive materials in liquid effluents exceeding any of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits. This Special Report shall also include (1) the results of radiological analyses of the drinking water source and (2) the radiological impact on finished drinking water supplies with regard to the requirements of 40 CFR 141 (applicable only if drinking water supply is taken from the receiving water body within three miles downstream of the plant discharge).
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.2 Cumulative dose contributions from liquid effluents for the current calendar quarter and current calendar year shall be determined in accordance with the methodology and parameters in ODCM Section 6.3 at least once per 31 days.
SQN ODCM Revision 57 Page 29 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM CONTROLS 1.2.1.3 In accordance with SQN Technical Specification 6.8.4.f.6, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge when the projected doses due to the liquid effluent to UNRESTRICTED AREAS (see Figure 3.1) would exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period.APPLICABILITY:
At all times.ACTION: a. With radioactive liquid waste being discharged without treatment and in excess of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
- 1. Identification of the inoperable equipment or subsystems and the reason for inoperability, 2. Action(s) taken to restore the inoperable equipment to OPERABLE status, and 3. Summary description of action(s) taken to prevent a recurrence.
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.3 Doses due to liquid releases from each unit to UNRESTRICTED AREAS shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 6.5.
SQN ODCM Revision 57 Page 30 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.1 DOSE RATE CONTROLS 1.2.2.1 In accordance with SQN Technical Specification 6.8.4.f.7, the dose rate at any time due to radioactive materials released in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be in accordance with the following:
- a. For noble gases: Less than or equal to a dose rate of 500 mrem/yr to the whole body and less than or equal to a dose rate of 3000 mrem/yr to the skin, and b. For Iodine-131, Iodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days: Less than or equal to a dose rate of 1500 mrem/yr to any organ.APPLICABILITY:
At all times.ACTION: a. With dose rate(s) exceeding the above limits, without delay restore the release rate to within the above limit(s).b. If samples or analyses required by Table 2.2-2 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.1.1 The dose rate due to noble gases in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.3, and 2.2.2.1.2 The dose rate due to lodine-131, lodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.4 and by obtaining representative samples and performing analyses in accordance with the sampling and analysis program specified in Table 2.2-2.
SQN ODCM Revision 57 Page 31 of 179 Table 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)Lower Limit of Sampling Minimum Analysis Detection (LLD)Gaseous Release Type Frequency Frequency Type of Activity Analysis (P.Cilml)a A. Waste Gas Storage P P Principal Gamma lx10-4 Tank Each Tank Each Tank Emittersg Grab B. Containment Pi Pi Principal Gamma lxl0-4 1. PURGE Each PURGE Each PURGE Emittersg Grab Sample H-3 lx10-6 2. Vent Wi Wi Principal Gamma lx10-4 Grab Sample Emittersg H-3 lx10-6 C. Noble Gases and M M Principal Gamma lx10-4 Tritium Grab Sample Emittersg 1. Condenser Vacuum Exhausth H-3 lx10-6 2. Auxiliary Building Exhaustb,e
- 3. Service Bldg.Exhaust 4. Shield Bldg.Exhaustb,c,h D. Iodine and Particulates Continuous Wd 1-131 lx10-1 2 1. Auxiliary Building Samplerf Charcoal Sample Exhaust 2. Shield Building Continuous Wd Principle Gamma lx10-11 Exhaust h Sampler f Particulate Emittersg Sample (1-131, Others)M Continuous Composite Gross Alpha 1x10-1 1 Sampler Particulate Sampler Q Continuous Composite Sr-89, Sr-90 1x10-1 1 Samplerf Particulate Sample E. Noble Gases Continuous Noble Gas Noble Gases lx10-6 All Release types Monitorf Monitor Gross Beta or Gamma as listed in C SQN ODCM Revision 57 Page 32 of 179 Table 2.2-2 (Page 2 of 3)RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66sb LLD =-------------------------------------------
E V 2.22x10 6 Y exp (-X At)Where: LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x1 06 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable), X is the radioactive decay constant for the particular radionuclide, and At is the elapsed time between midpoint of sample collection and time of counting (midpoint) in minutes.It should be noted that the LLD is defined as an a priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
b Sampling and analysis shall also be performed following shutdown, startup, or a thermal power change exceeding 15% of RATED THERMAL POWER within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> unless (1) analysis shows that the DOSE EQUIVALENT 1-131 concentration in the primary coolant has not increased more than a factor of 3 and (2)the containment noble gas activity monitor (RE-90-106 or RE-90-112) shows that the radioactivity has not increased by more than a factor of 3.c Tritium grab samples shall be taken periodically when the refueling canal is flooded.
SQN ODCM Revision 57 Page 33 of 179 Table 2.2-2 -RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION (Page 3 of 3)d Samples shall be changed at least once per 7 days. Sampling shall also be performed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for at least 2 days following each shutdown from >15% RATED THERMAL POWER, startup of >15%RATED THERMAL POWER or THERMAL POWER change exceeding 15% of RATED THERMAL POWER in one hour. Only one set of samples will be required in a 24-hour period. When samples collected for <24 hours are analyzed, the corresponding LLD's may be increased by a factor of 10.e Tritium grab samples shall be taken periodically from the ventilation exhaust from the spent fuel pool area, whenever spent fuel is in the spent fuel pool.f The ratio of the sample flow rate to the sampled stream flow rate shall be known for the time period covered by each dose or dose rate calculation made in accordance with ODCM Sections 7.2, 7.3, and 7.4.g The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:
Kr-87, Kr-88, Xe-1 33, Xe-1 33m, Xe-135, and Xe-1 38 for noble gases and Mn-54, Fe-59, I-131, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141 and Ce-144 for particulate principal gamma emitters.
This list does not mean that only these nuclides are to be detected and reported.
Other gamma peaks which are measurable and identifiable, together with the above nuclides, shall also be analyzed and reported in the Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.h During releases via this exhaust system.PURGING -Applicable in MODES 1, 2, 3 and 4, the upper and lower compartments of the containment shall be sampled prior to PURGING. Prior to breaking containment integrity in MODE 5 or 6, the upper and lower compartments of the containment shall be sampled. The incore instrument room purge sample shall be obtained at the shield building exhaust between 20 and 25 minutes following initiation of the incore instrument room PURGE or at the peak of the discharge based on the radiation monitor response.VENTING -Applicable in MODES 1, 2, 3, and 4; the containment will be VENTED to the containment annulus and then to the auxiliary building via containment annulus fans. The lower containment compartment shall be sampled weekly and the lower containment radiation monitor response will be recorded daily when VENTING is to occur to account for the radioactivity being discharged from the VENTING process. The lower containment will be re-sampled when the reading on the lower containment radiation monitor (RE-90-106 or 112), increases by 50% from the initial value. If the lower containment noble gas monitor (RE-90-106 or 112) is inoperable, noble gas grab samples may be used to perform this comparison.
SQN ODCM Revision 57 Page 34 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.2 DOSE -NOBLE GASES CONTROLS 1.2.2.2 In accordance with SQN Technical Specification 6.8.4.f.8, the air dose due to noble gases released in gaseous effluents from each reactor unit to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation and b. During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.
APPLICABILITY:
At all times.ACTION: a. With the calculated air dose from radioactive noble gases in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.2 Cumulative dose contributions for the current calendar quarter and current calendar year for noble gases shall be determined in accordance with the methodology and parameters in ODCM Section 7.3 at least once per 31 days.
SQN ODCM Revision 57 Page 35 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.3 DOSE 131.1-133.
TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS CONTROLS 1.2.2.3 In accordance with SQN Technical Specification 6.8.4.f.9, the dose to a member of the public from I-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following from each reactor unit: a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ and, b. During any calendar year: Less than or equal to 15 mrem to any organ.APPLICABILITY:
At all times.ACTION: a. With the calculated dose from the release of 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days, in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.3 Cumulative dose contributions for the current calendar quarter and current calendar year for 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days shall be determined in accordance with the methodology and parameters in ODCM Section 7.4 at least once per 31 days.
SQN ODCM Revision 57 Page 36 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.4 GASEOUS RADWASTE TREATMENT CONTROLS 1.2.2.4 In accordance with SQN Technical Specification 6.8.4.f.5 and 6, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected gaseous effluent doses due to gaseous effluent releases to areas at or beyond the SITE BOUNDARY (see Figure 3.1), when averaged over 31 days, would exceed 0.2 mrad per unit for gamma radiation, and 0.4 mrad per unit for beta radiation.
The appropriate portions of the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected doses due to gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (See Figure 3.1) when averaged over 31 days would exceed 0.3 mrem per unit to any organ.ACTION: a. With the radioactive gaseous waste being discharged without treatment for more than 31 days and in excess of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
- 1. Identification of the inoperable equipment or subsystems and the reason for inoperability.
- 2. Action(s) taken to restore the inoperable equipment to OPERABLE status.3. Summary description of action(s) taken to prevent a recurrence.
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.4 Doses due to gaseous releases from the site shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 7.5.
SQN ODCM Revision 57 Page 37 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.3 TOTAL DOSE CONTROLS 1.2.3 In accordance with SQN Technical Specification 6.8.4.f.10, the annual (calendar year) dose or dose commitment to any member of the public, beyond the site boundary due to releases of radioactivity from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or any organ (except the thyroid, which shall be limited to less than or equal to 75 mrem).APPLICABILITY:
At all times.ACTION: a. With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM Control 1.2.1.2, 1.2.2.2, or 1.2.2.3, calculations should be made to determine whether the above limits have been violated.
If such is the case, prepare and submit a Special Report to the Director, Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission, Washington D.C. 20555, within 30 days, which defines the corrective action to be taken to reduce subsequent releases to prevent recurrence of exceeding the limits above. This Special Report, as defined in 10 CFR Part 20.2203, shall include an analysis which estimates the radiation dose to a member of the public beyond the site boundary from uranium fuel cycle sources (including all effluent pathways and direct radiation) for a calendar year that includes the release(s) covered by this report. If the estimated dose(s) exceeds the above limits, and if the release condition resulting in violation of 40 CFR Part 190 has not already been corrected, the Special Report shall include a request for a variance in accordance with the provisions of 40 CFR Part 190 and include the specified information of Section 190.11 (b). Submittal of the report is considered a timely request, and a variance is granted until the staff action on the request is complete.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS
2.2.3 Cumulative
dose contributions from liquid and gaseous effluents shall be determined in accordance with the methodology and parameters in ODCM Sections 6.3, 7.3, and 7.4.
SQN ODCM Revision 57 Page 38 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM CONTROLS 1.3.1 The radiological environmental monitoring program shall be conducted as specified in Table 2.3-1.APPLICABILITY:
At all times.ACTION: a. With the radiological environmental monitoring program not being conducted as specified in Table 2.3-1, prepare and submit to the Commission, in the Annual Radiological Environmental Operating Report, a description of the reasons for not conducting the program as required and the plans for preventing a recurrence.
- b. With the level of radioactivity in an environmental sampling medium exceeding the reporting levels of Table 2.3-2 when averaged over any calendar quarter, prepare and submit to the Commission within 30 days from the end of the affected quarter, pursuant to ODCM Administrative Control 5.4, a Special Report that identifies the cause(s) for exceeding the limit(s) and defines the corrective actions to be taken to reduce radioactive effluents so that the potential annual dose to a member of the public is less than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2 and 1.2.2.3. When one or more of the radionuclides in Table 2.3-2 is detected in the sampling medium, this report shall be submitted if: concentration(1) concentration(2)
+ +...>1.0 limit level(1 ) limit level(2)When radionuclides other than those in Table 2.3-2 are detected and are the result of plant effluents, this report shall be submitted if the potential annual dose to a member of the public from all radionuclides is equal to or greater than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2, and 1.2.2.3. This report is not required if the measured level of radioactivity was not the result of plant effluents; however, in such an event, the condition shall be reported and described in the Annual Radiological Environmental Operating Report.
SQN ODCM Revision 57 Page 39 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM ACTION (CONTINUED):
- c. With milk or fresh leafy vegetable samples unavailable from one or more of the sample locations required by Table 2.3-1, identify locations for obtaining replacement samples and add them to the radiological environmental monitoring program within 30 days. The specified locations from which samples were unavailable may then be deleted from the monitoring program. Pursuant to ODCM Administrative Control 5.1, identify the new locations for obtaining replacement samples in the Annual Radiological Environmental Operating Report. A revised figure(s) and table(s) for the ODCM reflecting the new location(s) shall be included in the next Annual Effluent Release Report pursuant to ODCM Administrative Control 5.2.d. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.3.1 The radiological environmental monitoring samples shall be collected pursuant to Table 2.3-1 from the locations given in the tables and figures given in ODCM Section 9.0 and shall be analyzed pursuant to the requirements of Table 2.3-1 and the detection capabilities required by Table 2.3-3.
SQN ODCM Revision 57 Page 40 of 179 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 2)I Location of Frequency Analysis Minimum of 5 locations W Continuous sampler**Radioiodine canister: Weekly 1-131 Particulate sampler: Analyze for gross beta activity > 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following filter change.Perform gamma isotopic analysis on each sample when gross beta activity is >10 times the yearly mean of control samples Q: Perform gamma isotopic analysis on composite ( by location) sample.DIRECT RADIATION 35 to 40 locations Q Q: Gamma Dose with > 2 dosimeters for continuously measuring and recording dose rate at each location.WATERBORNE Surface 2 locations M Gamma isotopic Composite***
sample Each composite sample Tritium analysis Ground 2 locations Q Gamma isotopic and tritium analyses of each sample.Gross beta and gamma isotopic analysis Drinking Minimum of 1 M Q location Composite***
sample Tritium analysis M 2 locations Grab sample Gross beta and gamma isotopic analysis Shoreline Minimum of 2 S Gamma isotopic analysis Sediment locations from each sample.locations*Sample locations are given in Table 9.1.**Continuous sampling with sample collection as required by dust loading, but at least once per 7 days.***Composite samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
SQN ODCM Revision 57 Page 41 of 179 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 2)INGESTION Milk Milk from 3 B**** Gamma isotopic and 1-131 locations, analysis of each sample.Samples of broad leaf vegetation at offsite locations of highest D/Q if no milk samples are available.
Fish 2 locations One sample in Gamma isotopic analysis on season, or at least edible portions.once per 184 days if not seasonal.One sample representing a commercially important species and one sample representing a recreationally important species.Food Minimum of 2 At time of harvest. Gamma isotopic analysis on Products locations One sample of each edible portions.of the following or similar classes of food products, as available 1. Lettuce and/or cabbage 2. Corn 3. Beans 4. Tomatoes**** When animals are on pasture, at least once per 31 days at other times.
SQN ODCM Revision 57 Page 42 of 179 Table 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES Analysis H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 1-131 Cs-1 34 Cs-137 Ba-La-140 Water Airborne (pCi/L) Particulate or gases (pCi/mn 3)2 x 1 0 4(a)1 x103 4 x 102 1 x 10 3 3 x 102 3 x 102 4 x 102 2 (b)30 50 2 x 102 N.A N.A.N.A.N.A.N.A.N.A.N.A.0.9 10 20 N.A.Fish (pCi/kg, wet)N.A 3 x 104 1 x 104 3 x 104 1 x 10 4 2 x 104 N.A.N.A.1x103 2x10 3 N.A.Milk (pCi/L)N.A.N.A.N.A.N.A.N.A.N.A.N.A.3 60 70 3 x 102 Food Products (pCi/kg, wet)N.A.N.A.N.A.N.A.N.A.N.A.N.A.lx102 lx103 2x10 3 N.A.(a) For drinking water samples. This is 40 CFR Part 141 value.(b) If no drinking water pathway exists, a value of 20 pCi/L may be used.
SQN ODCM Revision 57 Page 43 of 179 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)a,b (Page 1 of 2)Airborne Particulate Fish Food Water or Gases (pCi/kg, Milk Products Sediment Analysis (pCi/L) (pCi/m 3) wet) (pCi/L) (pCi/kg,wet) (pCi/kg,dry) gross beta 4 lx10-2 N.A. N.A N.A. N.A.H-3 2000* N.A N.A N.A N.A. N.A.Mn-54 15 N.A. 130 N.A. N.A. N.A.Fe-59 30 N.A. 260 N.A. N.A. N.A.Co-58,60 15 N.A. 130 N.A. N.A. N.A.Zn-65 30 N.A. 260 N.A. N.A. N.A.Zr-95 30 N.A. N.A. N.A. N.A. N.A.Nb-95 15 N.A. N.A. N.A. N.A. N.A.1-131 1 ** 7x1 0-2 N.A. 1 60 N.A.Cs-134 15 5x10-2 130 15 60 150 Cs-137 18 6x10-2 150 18 80 180 Ba-140 60 N.A. N.A. 60 N.A. N.A.La-140 15 N.A. N.A. 15 N.A. N.A.* If no drinking water pathway exists, a value of 3000 pCi/L may be used.** If no drinking water pathway exists, a value of 15 pCi/L may be used.
SQN ODCM Revision 57 Page 44 of 179 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)a,b (Page 2 of 2) TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66sb LLD =----------------------------------
E V 2.22 Y exp(-XAt)where: LLD is the "a priori" lower limit of detection as defined above in picocurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22 is the number of disintegrations per minute per picocurie, Y is the fractional radiochemical yield (when applicable), X is the radioactive decay constant for the particular radionuclide, and At for environmental samples is the elapsed time between sample collection (or end of the sample collection period) and time of counting.It should be recognized that the LLD is defined as an a orio (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
Analysis will be performed in such a manner that the stated LLDs will be achieved under routine conditions.
b Other peaks which are measurable and identifiable, together with the radionuclides above, shall be identified and reported.Table 2.3-4 DETECTION CAPABILITIES FOR GROUNDWATER HARD-TO-DETECT NUCLIDES LOWER LIMITS OF DETECTION (LLD)ANALYSIS WATER (pCi/L) 1 Fe-55 200 Ni-63 30 Sr-89 5 Sr-90 1 Gross Alpha 4 Multiply the values in this column by 10-9 to convert to units of pCi/ml SQN ODCM Revision 57 Page 45 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.2 LAND USE CENSUS CONTROLS 1.3.2 A Land Use Census shall be conducted and shall identify within a distance of 8 km (5 miles) the location in each of the 16 meteorological sectors of the nearest milk animal, the nearest residence, and the nearest gardena of greater than 50 m 2 (500 ft 2) producing fresh leafy vegetables.
aBroad leaf vegetation sampling of at least three different kinds of vegetation may be performed at the site boundary in each of two different direction sectors with the highest predicted D/Qs in lieu of the garden census.Specifications for broad leaf vegetation sampling in Table 2.3-1 shall be followed, including analysis of control samples.APPLICABILITY:
At all times.ACTION: a. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment 20%greater than at a location from which doses are currently being calculated in ODCM Section 7.3 and 7.4 identify the new location(s) in the next Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.b. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment (via the same pathway) 20% greater than at a location from which samples are currently being obtained in accordance with the requirements of ODCM Control 1.3.1, add the new location(s) within 30 days to the radiological environmental monitoring program given in ODCM Section 9.0, if samples are available.
The sampling location(s), excluding the control station location, having the lowest calculated dose or dose commitment(s), via the same exposure pathway, may be deleted from this monitoring program after October 31 of the year in which this Land Use Census was conducted.
Pursuant to ODCM Administrative Controls 5.2 and 5.3, submit in the next Annual Radioactive Effluent Release Report documentation for a change in the ODCM including a revised figure(s) and table(s) for the ODCM reflecting the new location(s) with the information supporting the change in sampling locations.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SQN ODCM Revision 57 Page 46 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.2 LAND USE CENSUS SURVEILLANCE REQUIREMENTS 2.3.2 The Land Use Census shall be conducted during the growing season at least once per 12 months using that information that will provide the best results, such as by a door-to-door survey, mail survey, telephone survey, aerial survey, or by consulting local agricultural authorities.
The results of the Land Use Census shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.
SQN ODCM Revision 57 Page 47 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM CONTROLS 1.3.3 Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the Commission.
APPLICABILITY:
At all times.ACTION: a. With analyses not being performed as required above, report the corrective actions being taken to prevent a recurrence to the Commission in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.3.3 A summary of the results obtained as a part of the above required Interlaboratory Comparison Program and in accordance with the guidance below shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.
SQN ODCM Revision 57 Page 48 of 179 BASES FOR SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS NOTE The BASES contained in succeeding pages summarize the reasons for the Controls in Sections 1.0 and 2.0, but are not part of these Controls.
SQN ODCM Revision 57 Page 49 of 179 BASES INSTRUMENTATION 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION The radioactive liquid effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in liquid effluents during actual or potential releases of liquid effluents.
The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 6.2 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION The radioactive gaseous effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in gaseous effluents during actual or potential releases of gaseous effluents.
The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 7.1 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1.1 CONCENTRATION This Control is provided to ensure that the concentration of radioactive materials released at any time in liquid waste effluents to UNRESTRICTED AREAS will be less than ten times the concentration levels specified in 10 CFR Part 20, Appendix B, Table 2, Column 2. This limitation provides additional assurance that the levels of radioactive materials in bodies of water in UNRESTRICTED AREAS will result in exposures within (1) the Section Il.A design objectives of Appendix I, 10 CFR 50, and (2) the limits of 10 CFR 20.1301(a)(1) to a member of the public. The concentration limit for dissolved or entrained noble gases is based upon the assumption that Xe-135 is the controlling radioisotope and its MPC in air (submersion) was converted to an equivalent concentration in water using the methods described in International Commission of Radiological Protection (ICRP) Publication 2.1/2.2.1.2 DOSE This Control is provided to implement the requirements of Sections II.A, Ill.A, and IV.A of Appendix 1, 10 CFR Part 50. The requirement implements the guide set forth in Section I.A of Appendix I. The action statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." Also, for fresh water sites with drinking water supplies which can be potentially affected by plant operations, there is reasonable assurance that the operation of the facility will not result in radionuclide concentrations in the finished drinking water that are in excess of the requirements of 40 CFR Part 141. The dose calculations in ODCM Section 6.3 implement the requirements in Section III.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data, such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to substantially underestimated.
The equations specified in Section 6.3 for calculating the doses due to the actual release rates of radioactive SQN ODCM Revision 57 Page 50 of 179 BASES 1/2.2.1.2 DOSE (continued) materials in liquid effluents are consistent with the methodology provided in Regulatory Guide 1.109,"Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.113, "Estimating Aquatic Dispersion of Effluents from Accidental and Routine Reactor Releases for the Purpose of Implementing Appendix I," April 1977.This Control applies to the release of liquid effluents from each reactor at the site. For units with shared radwaste treatment systems, the liquid effluents from the shared systems are proportioned among the units sharing that system.Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301 (a)(1) per 56 FR 23374.1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM The Control that the appropriate portions of this system be used when specified provides assurance that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." This requirement implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objective given in 10 CFR Part 50Appendix I, Section lI.D. The specified limits governing the use of appropriate portions of the liquid radwaste system were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I, Section II.A, for liquid effluents.
1/2.2.2.1 DOSE RATE This Control provides reasonable assurance that radioactive material discharged in gaseous effluents will not result in the exposure of a member of the public in an UNRESTRICTED AREA in excess of the design objectives of Appendix I to 10 CFR 50. This Control is provided to ensure that gaseous effluents from all units on the site will be appropriately controlled.
It provides operational flexibility for releasing gaseous effluents to satisfy the Section I.A and II.C design objectives of Appendix Ito 10 CFR 50. For members of the public who may at times be within the CONTROLLED or RESTRICTED AREAS, the occupancy of that member of the public will usually be sufficiently low to compensate for the reduced atmospheric dispersion relative to that for the UNRESTRICTED AREA BOUNDARY.
Examples of calculations for such members of the public, with the appropriate occupancy factors, shall be given in the ODCM. The specified release rate limits restrict, at all times, the corresponding gamma and beta dose rates above background to a member of the public at or beyond the UNRESTRICTED AREA BOUNDARY to 500 mrem/y to the total body or to 3000 mrem/y to the skin.These limits also restrict, at all times, the corresponding thyroid dose rate above background to a child via the inhalation pathway to <1500 mrem/y. This Control does not affect the requirement to comply with the annual limitations of 10 CFR 20.1301 (a).This requirement applies to the release of radioactive material in gaseous effluents from all reactors at the site.
SQN ODCM Revision 57 Page 51 of 179 BASES 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2.2 DOSE -NOBLE GASES This requirement is provided to implement the requirements of 10 CFR Part 50 Appendix I, Sections II.B,III.A and IV.A. The requirement implements the guides set forth in Appendix I Section lI.B Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." The surveillance implements the requirements in Section III.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to be substantially underestimated.
The dose calculations established in ODCM Section 7.3 for calculating the doses due to the actual release rates of radioactive noble gases in gaseous effluents are consistent with the methodology provided in Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.111, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977. The ODCM equations provided for determining the air doses at the UNRESTRICTED AREA BOUNDARY are based upon the historical average atmospheric conditions.
1/2.2.2.3 DOSE 131. 1-133, TRITIUM. AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS This Control is provided to implement the requirements 10 CFR Part 50 Appendix I Sections II.C, III.A and IV.A.The requirement implements the guides set forth in Appendix I Section II.C. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Appendix I Section IV.A to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." Section 7.4 calculational methods implement the requirements in Appendix I Section III.A that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to be substantially underestimated.
Section 7.4 calculational methods for calculating the doses due to the actual release rates of the subject materials are consistent with the methodologies provided in NUREG/CR-1004, "A Statistical Analysis of Selected Parameters for Predicting Food Chain Transport and Internal Dose of Radionuclides," October 1979 and Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.111, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977.These equations also provide for determining the actual doses based upon the historical average atmospheric conditions.
The release rate specifications for lodine-131, Iodine -133, tritium and all radionuclides in particulate form with half-lives greater than 8 days are dependent on the existing radionuclide pathways to man, beyond the UNRESTRICTED AREA BOUNDARY.
The pathways which were examined in the development of these calculations were: 1) individual inhalation of airborne radionuclides, 2) deposition of radionuclides onto green leafy vegetation with subsequent consumption by man, 3) deposition onto grassy areas where milk animals and meat producing animals graze with consumption of the milk and meat by man, and 4) deposition on the ground with subsequent exposure of man.
SQN ODCM Revision 57 Page 52 of 179 BASES 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2.4 GASEOUS RADWASTE TREATMENT This Control that the appropriate portions of these systems be used, when specified, provides reasonable assurance that the releases of radioactive materials in gaseous effluents will be kept "as low as reasonably achievable." This Control implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objectives given in 10 CFR Part 50 Appendix I Section ll.D. The specified limits governing the use of appropriate portions of the systems were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I Section 11.B and II.C, for gaseous effluents.
1/2.2.3 TOTAL DOSE This Control is provided to meet the dose limitations of 40 CFR Part 190 that have been incorporated into 10 CFR Part 20 by 46 FR 18525. Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374. The ACTION requires the preparation and submittal of a Special Report whenever the calculated doses due to releases of radioactivity and to radiation from uranium fuel cycle sources exceed 25 mrem to the total body or any other organ except thyroid, which shall be limited to less than or equal to 75 mrem. For sites containing up to 4 reactors, it is highly unlikely that the resultant dose to a member of the public will exceed the dose limits of 40 CFR Part 190 if the individual reactors remain within twice the dose design objectives of Appendix I and if direct radiation doses from the units and from outside storage tanks are kept small. The Special Report will describe a course of action that should result in the limitation of annual dose to a member of the public to within the 40 CFR Part 190 limits. For the purposes of the Special Report, it may be assumed that the dose commitment to the member of the public from other uranium fuel cycle sources is negligible, with the exception that dose contributions from other nuclear fuel cycle facilities at the same site or within a radius of 8 km must be considered.
If the dose to any member of the public is estimated to exceed the requirements of 40 CFR Part 190, the Special Report with a request for a variance (provide the release conditions resulting in violation of 40 CFR Part 190 have not already been corrected), in accordance with the provisions of 40 CFR Part 190.11 and 10 CFR Part 20.2203, is considered to be a timely request and fulfills the requirements of 40 CFR Part 190 until NRC staff action is completed.
The variance only relates to the limits of 40 CFR Part 190, and does not apply in any way to the other requirements for dose limitation of 10 CFR Part 20, as addressed in ODCM Controls 1.2.1.1 and 1.2.2.1. An individual is not considered a member of the public during any period in which he/she is engaged in carrying out any operation that is a part of the nuclear fuel cycle.
SQN ODCM Revision 57 Page 53 of 179 BASES 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 112.3.1 MONITORING PROGRAM The radiological environmental monitoring program required by this Control provides representative measurements of radiation and of radioactive materials in those exposure pathways and for those radionuclides that lead to the highest potential radiation exposures of members of the public resulting from the station operation.
This monitoring program implementsSection IV.B.2 of Appendix I to 10 CFR Part 50 and thereby supplements the radiological effluent monitoring program by verifying that the measurable concentration of radioactive materials and levels of radiation are not higher than expected on the basis of the effluent measurements and modeling of the environmental exposure pathways.
Guidance for this monitoring program is provided by the Radiological Assessment Branch Technical Position on Environmental Monitoring.
The required detection capabilities for environmental sample analyses are tabulated in terms of the lower limits of detection (LLDs). The LLDs required by Table 2.3-3 are considered optimum for routine environmental measurements in industrial laboratories.
It should be recognized that the LLD is defined as an a griori (before the fact) limit representing the capability of a measurement system and not as a posteriori (after the fact) limit for a particular measurement.
Detailed description of the LLD, and other detection limits can be found in HASL Procedures Manual, HASL-300 (revised annually), Curie, L. A., "Limits for Qualitative Detection and Quantitative Determination
-Application to Radiochemistry," Anal. Chem. 40, 586-93 (1968), and Hartwell, J. K., "Detection Limits for Radioanalytical Counting Techniques," Atlantic Richfield Hanford Company Report ARH-SA-215 (June 1975).1/2.3.2 LAND USE CENSUS This Control is provided to ensure that changes in the use of unrestricted areas are identified and that modifications to the monitoring program are made if required by the results of that census. The best survey information from the door-to-door, aerial, or consulting with local agricultural authorities shall be used. This census satisfies the requirements of Section IV.B.3 of Appendix I to 10 CFR Part 50. Restricting the census to gardens of greater than 500 ft 2 provides assurance that significant exposure pathways via leafy vegetables will be identified and monitored since a garden of this size is the minimum required to provide the quantity (26 kg/yr)of leafy vegetables assumed in Regulatory Guide 1.109 for consumption by a child. To determine this minimum garden size, the following assumptions were used, 1) that 20% of the garden was used for growing broad leaf vegetation (i.e., similar to lettuce and cabbage), and 2) a vegetation yield of 2 kg/m 2.1/2.3.3 INTERLABORATORY COMPARISON PROGRAM The requirement for participation in an Interlaboratory Comparison Program is provided to ensure that independent checks on the precision and accuracy of the measurements of radioactive material in environmental sample matrices are performed as part of the quality assurance program for environmental monitoring in order to demonstrate that the results are reasonably valid.
SQN ODCM Revision 57 Page 54 of 179 SECTION 3.0 DEFINITIONS SQN ODCM Revision 57 Page 55 of 179 3.0 DEFINITIONS The defined terms in this section appear in capitalized type in the text and are applicable throughout the ODCM.3.1 ACTION ACTION shall be that part of a Control that prescribes remedial measures required under designated conditions.
3.2 CHANNEL
CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel output such that it responds with the necessary range and accuracy to known values of the parameter which the channel monitors.
The CHANNEL CALIBRATION shall encompass the entire channel including the sensor and alarm and/or trip functions, and shall include the CHANNEL FUNCTIONAL TEST. The CHANNEL CALIBRATION may be performed by any series of sequential, overlapping, or total channel steps such that the entire channel is calibrated.
3.3 CHANNEL
CHECK A channel check shall be the qualitative assessment of channel behavior during operation by observation.
This determination shall include, where possible, comparison of the channel indication and/or status with other indications and/or status derived from independent instrument channels measuring the same parameter.
3.4 CHANNEL
FUNCTIONAL TEST A CHANNEL FUNCTIONAL TEST shall be: a. Analog channels -the injection of a simulated signal into the channel as close to the sensor as practicable to verify OPERABILITY including alarm and/or trip functions.
- b. Bistable channel -the injection of a simulated signal into the sensor to verify OPERABILITY including alarm and/or trip function.c. Digital channels -the injection of a simulated signal into the channel as close to the sensor input to the processor as practicable or the manipulation of a setpoint below existing background to verify operability including alarm and/or trip function.3.5 CIRCUIT FAILURE shall be defined as the loss of circuit power to the monitor.3.6 CONTROLLED AREA A CONTROLLED AREA, as defined in 10 CFR 20, is the area outside the RESTRICTED AREA but inside the 10 CFR 20 defined UNRESTRICTED AREA BOUNDARY, access to which can be limited by the licensee for any reason (See Figure 3.1).3.7 DOSE EQUIVALENT 1-131 DOSE EQUIVALENT 1-131 shall be that concentration of 1-131 (jiCi/gram) which alone would produce the same thyroid dose as the quantity and isotopic mixture of 1-131, 1-132, 1-133, 1-134, and 1-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table III of TID-14844, "Calculation of Distance Factors for Power and Test Reactor Sites."
SQN ODCM Revision 57 Page 56 of 179 3.0 DEFINITIONS (continued)
3.8 FREQUENCY
NOTATION The FREQUENCY NOTATION specified for the Surveillance Requirements shall correspond to the intervals defined in Table 3.1.3.9 GASEOUS RADWASTE TREATMENT SYSTEM A GASEOUS RADWASTE TREATMENT SYSTEM is any system designed and installed to reduce radioactive gaseous effluents by collecting primary coolant system offgases from the primary system and providing for delay or holdup for the purpose of reducing the total radioactivity prior to release to the environment.
3.10 OPERABLE -OPERABILITY A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified function(s), and when all necessary attendant instrumentation, controls, a normal or an emergency electrical power source, cooling or seal water, lubrication or other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its function(s) are also capable of performing their related support function.3.11 MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, and average reactor coolant temperature specified in Table 1.1 of the SQN Technical Specifications.
3.12 PURGE -PURGING PURGE or PURGING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration or other operating condition, in such a manner that replacement air or gas is required to purify the confinement.
3.13 RADIATION MONITOR (RM) OR (R)A radiation monitor is identified by "RM" under instrumentation.
To be OPERABLE, it is minimally defined as an instrumentation channel that includes the radiation detector, associated sample delivery system, signal processing electronics, malfunction alarm, high radiation alarm, and at least one indicator (main control room, local, or computer point).3.14 RATED THERMAL POWER RATED THERMAL POWER shall be a total reactor core heat transfer rate to the reactor coolant of 3455 RTP 3.15 REPORTABLE EVENT A REPORTABLE EVENT shall be any of those conditions specified in Section 50.73 of 10 CFR 50.
SQN ODCM Revision 57 Page 57 of 179 3.0 DEFINITIONS (continued) 3.16 RESTRICTED AREA The RESTRICTED AREA, as defined in 10 CFR Part 20, is that area, access to which is limited by the licensee for the purposes of protecting individuals against undue risks from exposure to radiation and radioactive materials.
The permanent RESTRICTED AREA is shown on Figure 3.1, but temporary restricted areas outside the permanent RESTRICTED AREA may be defined by SQN.3.17 SITE BOUNDARY The site boundary is defined in 10 CFR 20 as that line beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.3.18 SOURCE/SENSOR CHECK A SOURCE/SENSOR CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a radioactive source or other channel sensor internal test circuit.3.19 UNRESTRICTED AREA/BOUNDARY An UNRESTRICTED AREA/BOUNDARY, as used for calculations performed pursuant to 10 CFR Part 50.36a, shall be an area at or beyond the site boundary which is utilized in the ODCM Controls to keep levels of radioactive materials in liquid and gaseous effluents as low as is reasonably achievable.
The UNRESTRICTED AREA does not include areas over water bodies (See Figure 3.1).3.20 VENTILATION EXHAUST TREATMENT SYSTEM A VENTILATION EXHAUST TREATMENT SYSTEM is any system designed and installed to reduce gaseous radioiodine or radioactive material in particulate form in effluents by passing ventilation or vent exhaust gases through charcoal adsorbers and/or HEPA filters for the purpose of removing iodines or particulates from the gaseous exhaust stream prior to the release to the environment (such a system is not considered to have any effect on noble gas effluents).
Engineered Safety Feature (ESF) atmospheric cleanup systems are not considered to be VENTILATION EXHAUST TREATMENT SYSTEM components.
3.21 VENT FLOW RATE MONITOR (F)The vent flow rate monitors are identified by "F" under instrumentation.
To be OPERABLE is minimally defined as an instrumentation channel that includes the flow sensor, processing electronics and at least one indicator (main control room, local or computer point).3.22 VENTING VENTING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration, or other operating condition, in such a manner that replacement air or gas is not provided or required during VENTING. Vent, used in system names, does not imply a VENTING process.
SQN ODCM Revision 57 Page 58 of 179 Table 3.1 FREQUENCY NOTATION NOTATION FREQUENCY P Completed prior to each release D At least once per day W At least once per 7 days B At least once per 15 days M At least once per 31 days Q At least once per 92 days R At least once per 18 months S At least semi-annual NA Not Applicable SQN ODCM Revision 57 Page 59 of 179 Figure 3.1 UNRESTRICTED AREA BOUNDARY Restricted Areas At Sequoyah Nuclear Plant Filled areas indicate Restricted Areas At Sequoyah Nuclear Plant$Power Stores Radioactive Materail Storage Area Old St.-G..ecetor Storcee Soldaig U,2 RWST M PWSk 1- RWST adPWST IndependentuSpent DG3Ratr uWar uxlar'&Fuel Storage Facility ---Dry Ato Wt. hBddc ad Yod Doi-,try C.I&rio. FST Fcility~~ ~Lo- L-1e Ldccoacto' Wacta Stoceg Ferility Filled areas indicate Restricted Areas.
SQN ODCM Revision 57 Page 60 of 179 SECTION 4.0 (NOT USED)
SQN ODCM Revision 57 Page 61 of 179 SECTION 5.0 ADMINISTRATIVE CONTROLS SQN ODCM Revision 57 Page 62 of 179 5.0 ADMINISTRATIVE CONTROLS 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT As required by SQN Technical Specification 6.9.1.6, the Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted prior to May 1 of each year.The annual radiological environmental operating reports shall include summaries, interpretations, and an analysis of trends of the results of the radiological environmental surveillance activities for the report period, including a comparison with preoperational studies, operational controls (as appropriate), and previous environmental surveillance reports and an assessment of the observed impacts of the plant operation on the environment.
The reports shall also include the results of land use censuses required by ODCM Control 1.3.2 and a listing of the new locations for dose calculations and/or environmental monitoring identified by the land use census. If harmful effects or evidence of irreversible damage are detected by the monitoring, the report shall provide an analysis of the problems and a planned course of action to alleviate the problem.The annual radiological environmental operating reports shall include summarized and tabulated results in the format of Regulatory Guide 4.8, December 1975 of all radiological environmental samples taken during the report period. In the event that some results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted as soon as possible in a supplementary report.The reports shall also include the following:
a summary description of the radiological environmental monitoring program; a map of all sampling locations keyed to a table giving distances and directions from one reactor; and the results of licensee participation in the Interlaboratory Comparison Program required by ODCM Control 1.3.3.5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT As required by SQN Technical Specification 6.9.1.8, an Annual Radioactive Effluent Release Report covering the operation of the site during the previous calendar year of operation shall be submitted prior to May 1 of each year.Annual radioactive release reports shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the site as outlined in Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants," Revision 1, June 1974, with data summarized on a quarterly basis following the format of Appendix B thereof.The annual radioactive release report shall include unplanned releases from the site to unrestricted areas and shall also include any changes made to the ODCM pursuant to ODCM Administrative Control 5.3.
SQN ODCM Revision 57 Page 63 of 179 5.0 ADMINISTRATIVE CONTROLS 5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT (continued)
The annual radioactive effluent release report shall include information for solid waste as outlined in the Process Control Program, and shall also include any changes made to the PCP during the reporting period, to the ODCM pursuant to ODCM Administrative Control 5.3, as well as any major changes to Liquid, Gaseous, or Solid Radwaste Treatment Systems, pursuant to SQN Technical Specifications.
It shall also include a listing of new location for dose calculations and/or environmental monitoring identified by the Land Use Census pursuant to ODCM Control 1.3.2.The radioactive effluent release reports shall also include the following:
an explanation as to why the inoperability of liquid or gaseous effluent monitoring instrumentation was not corrected within the time specified in ODCM Controls 1.1.1 or 1.1.2 respectively.
The annual radioactive effluent release report (Radiological Impact) shall include an annual summary of hourly meteorological data collected over the previous year. This annual summary may be either in the form of an hour-by-hour listing of wind speed, wind direction, atmospheric stability, and precipitation (if measured) on magnetic tape, or in the form of joint frequency distributions of wind speed, wind direction, and atmospheric stability.
In lieu of submission with the annual radioactive effluent release report, this summary of required meteorological data may be retained on site in a file that shall be provided to NRC upon request).
This same report shall include an assessment of the radiation doses due to radioactive liquid and gaseous effluents released from the unit or station during the previous calendar year. This same report shall also include an assessment of the radiation doses from radioactive liquid and gaseous effluents to members of the public due to their activities inside the UNRESTRICTED AREA BOUNDARY (Figure 3.1) during the report period. All assumptions used in making these assessments (i.e., specific activity, exposure time, and location) shall be included in these reports.The meteorological conditions concurrent with the time of release of radioactive materials in gaseous effluents (as determined by sampling frequency and measurement) shall be used for determining the gaseous pathway doses. The assessment of radiation doses shall be performed in accordance with Sections 6.6 and 7.6.The annual radioactive effluent release report to be submitted after January 1 of each year shall also include an assessment of radiation doses to the likely most exposed members of the public from reactor releases and other nearby uranium fuel cycle sources (including doses from primary effluent pathways and direct radiation) for the previous calendar year to show conformance with 40 CFR 190, Environmental Radiation Protection Standards for Nuclear Power Operation, in accordance with ODCM Section 8.0. Acceptable methods for calculating the dose contribution from liquid and gaseous effluents are given in Regulatory Guide 1.109, Revision 1.The Radioactive Effluent Release Report shall include results from any groundwater samples obtained in accordance with the Radiological Environmental monitoring Program during the reporting period that are not described in the ODCM.The Radioactive Effluent Release Report shall include any assigned doses that were performed as a result of a spill or leak from the site that occurred during the reporting period.The Radioactive Effluent Release Report shall include a summary of any on-site spills, leaks, and/or on-site ground water monitoring wells above ODCM reporting thresolds that occurred during the reporting period that were communicated to offsite agencies.
SQN ODCM Revision 57 Page 64 of 179 5.0 ADMINISTRATIVE CONTROLS 5.3 OFFSITE DOSE CALCULATION MANUAL CHANGES As required by SQN Technical Specification 6.14 and Appendix A, changes to the ODCM: 1. Shall be documented and records of reviews performed shall be retained in a manner convenient for review.This documentation shall contain: a. Sufficient information to support the change together with the appropriate analyses or evaluations justifying the change(s) and b. A determination that the change will maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 10 CFR Part 50.36a, and Appendix I to 10 CFR Part 50 and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations.
- 2. Shall become effective after review and acceptance by the process described in TVA-NQA-PLN89-A.
- 3. Shall be submitted to the Commission in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Annual Radioactive Effluent Release Report for the period of the report in which any change to the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month/year) the change was implemented.
Changes to the ODCM shall be performed in accordance with the requirements of Appendix A.5.4 SPECIAL REPORTS Special Reports shall be submitted within the time period specified for each report, in accordance with 10 CFR Part 50.4.
SQN ODCM Revision 57 Page 65 of 179 SECTION 6.0 LIQUID EFFLUENTS SQN ODCM Revision 57 Page 66 of 179 SECTION 6.0 LIQUID EFFLUENTS RELEASE POINTS There are four systems from which liquid effluents are released to the environment.
These are the Liquid Radwaste System, the Condensate Demineralizer System, the Turbine Building Sump (TBS), and the Units 1 and 2 Steam Generator Blowdown.
Figure 6.1 provides an outline of the liquid release paths and discharge points with associated flow rates and radiation monitors.All liquid effluents are ultimately discharged to the Diffuser Pond which releases to the Tennessee River where they are evaluated for offsite dose. The Essential Raw Cooling Water (ERCW) continuously supplies the Cold Water Channel which routinely provides dilution for liquid effluents at a minimum flow rate of 15,000 gpm.However, a minimum 17,000 gpm operational requirement is in place utilizing the ICS computer point 0F2120DIF to ensure the 15,000 gpm requirement is adhered. ERCW flow is monitored by radiation monitors 0-RM-90-133, -134, -140, -141.Releases are made as either batch or continuous release. Releases from Radwaste Tanks are made as batch releases.
The TBS and SGBD are continuous releases when flow exists. The Condensate Demineralizer tanks are routinely released as continuous release to the TBS, but can be released as batch release to the CTBD.For batch releases, any tank to be released is sampled for activity, as described in ODCM Section 6.1.1. The tank contents are analyzed to determine the maximum allowable release flow rates to ensure compliance with concentration limits of ODCM Control 1.2.1.1 as described in ODCM Section 6.1.2. The sampling results are also used to determine a setpoint for the associated radiation monitor for the release in accordance with ODCM Section 6.2.3. Pre-release calculations are performed assuming the minimum dilution of 15,000 gpm.For continuous releases, the pathways are sampled for radioactivity periodically, as described in ODCM Section 6.1.1. The samples are analyzed to ensure compliance with concentration limits of ODCM Control 1.2.1.1, as described in ODCM Section 6.1.2. The sampling results are also used to determine a setpoint for the associated radiation monitor for the release in accordance with ODCM Section 6.2.3. Pre-release calculations for points other than the Turbine Building Sump are performed assuming the minimum dilution flow of 15,000 gpm. The pre-release calculation for SGBD may be performed using 0 for the dilution flow and SGBD may be in-service to the CTBD with no dilution flow when the ECL for the SGBD is < 10.Liquid Radwaste System The Liquid Radwaste System processes liquid from the Reactor Building and Auxiliary Building Floor Drains and the laundry/hot shower and chemical drain tanks. Figure 6.2 provides a schematic of the Liquid Radwaste System, showing the liquid pathways, flow rate and radiation monitors.
The normal release points for liquid radwaste are the Monitor Tank and the Cask Decontamination Collector Tank (CDCT). The Monitor Tank has a capacity of 22,000 gal and is released routinely at a flow rate of 125 gpm. The CDCT has a capacity of 15,000 gal and is also released routinely at a flow rate of 125 gpm. The Monitor Tank and CDCT discharge to the Cooling Tower Blowdown (CTBD) line as a batch release and are monitored by radiation monitor 0-RM-90-122.
SQN ODCM Revision 57 Page 67 of 179 Condensate Demineralizer System The Condensate Demineralizer System processes liquid wastes coming from the High Crud Tanks (HCT-1 and -2), the Neutralization Tank, and the Non-Reclaimable Waste Tank (NRWT). The HCTs have a capacity of 20,000 gal and a maximum discharge flow rate of 245 gpm. The Neutralization Tank has a capacity of 19,000 gal and a maximum discharge flow rate of 245 gpm. The NRWT has a capacity of 11,000 gal and a maximum discharge flow rate of 245 gpm. The Condensate Demineralizer System is routinely released as continuous releases during periods of low radioactivity levels to the TBS, but can be released to the CTBD and is monitored by radiation monitor 0-RM-90-225.
Turbine Building Sump The Turbine Building Sump (TBS) normally releases to the Low Volume Waste Treatment Pond (LVWTP) but can be released to the Yard Pond. The TBS has a capacity of 30,000 gal and a design discharge release rate of 1,750 gpm per pump. TBS releases are monitored by radiation monitor 0-RM-90-212.
Steam Generator Blowdown The Steam Generator Blowdown (SGBD) is processed in the Steam Generator Draindown Flash Tanks or SGBD Heat Exchangers.
The SGBD discharge has a maximum flow rate of 80 gpm per steam generator.
SGBD discharges to the CTBD line are continuous and are monitored by radiation monitors 1,2-RM-90-120, -121.
SQN ODCM Revision 57 Page 68 of 179 6.1 LIQUID RELEASES 6.1.1 Pre-Release Analysis To ensure representative sampling, radwaste tanks will be recirculated for a procedurally established length of time, or through two volumes. Periodically, checks will be made to ensure a representative mixing of tank contents.
All radwaste tanks will be released as "batch" releases.Releases from condensate demineralizer tanks are routinely continuous releasesa and utilize a composite sampler to obtain a representative sample while being discharged.
In the event of an inoperable composite sampler, the releases will be made as a batch release, and will be recirculated for a procedurally established length of time or through two volumes to ensure representative sampling.Steam generator blowdown and turbine building sumpa are considered continuous and grab sampled daily during releases.Prior to any batch release, a grab sample will be taken and analyzed to determine the concentration, 1 iCi/ml, of each gamma-emitting nuclide. For continuous releases, daily grab or composite samples will be taken on days when releases are being made and analyzed to determine the concentration, piCi/ml, of each gamma-emitting nuclide. Composite samples are maintained during periods of radioactive discharge from all pathways (as required by Table 2.2-1) to determine the concentration of certain nuclides (H-3, Fe-55, Sr-89, Sr-90, and alpha emitters).
For those nuclides whose activities are determined from composite samples, the concentrations for the previous composite period can be assumed as the concentration for the next period to perform the calculations in Sections 6.3 and 6.5. The actual measured concentrations will be used for the dose calculations described in Section 6.6.a Sampling requirements for these release points are applicable only during periods of significant primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is at a LLD of <1 E-06 pCi/ml and allowing for background radiation during periods when primary to secondary leakage is occurring.
Sampling and analysis is routinely performed versus utilizing the radiation monitor at this LLD.6.1.2 Effluent Concentration Limits (ECL)-Sum of the Ratios The sum of the ratios (Ri) for each release point will be calculated by the following relationship.
Ci Rj = Y .........
(6.1)i ECLi where: Rj = the sum of the ratios for release point j.ECLi = the ECL of radionuclide i, pCi/ml, from 10 CFR Part 20, Appendix B, Table 2, Column 2.Ci = concentration of radionuclide i, pCi/ml.The sum of the ECL ratios must be < 10 following dilution at the Cooling Tower Blowdown due to the releases from any or all of the release points described above. The ECL ratios for releases from the Turbine Building Sump will be < 10 at the sump.
SQN ODCM Revision 57 Page 69 of 179 The following relationship is used to ensure that this criterion is met: fiR 1 + f 2 R 2 + f 3 R 3 + f 4 R 4 (6.2)RTBS + < 10.0 F where RTBs = sum of the ECL ratios of the turbine building sump as determined by equation 6.1.fl,f 2 ,f 3 ,f 4 = effluent flow rate for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, gpm.R 1 ,R 2 ,R 3 ,R 4 = sum of ECL ratios for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, as determined by equation 6.1.F = dilution flow rate for CTBD, routinely 15,000 gpm.6.1.3 Post-Release Analysis A post-release evaluation will be done using actual release data to ensure that the limits specified in ODCM Control 1.2.1.1 were not exceeded.
This analysis will include an evaluation of the noble gas concentration with regard to ODCM Control 1.2.1.1.A composite list of concentrations (Ci), by isotope, will be used with the actual waste (f) and dilution (F) flow rates (or volumes) during the release. The data will be evaluated to demonstrate compliance with the limits in ODCM Control 1.2.1.1.
SQN ODCM Revision 57 Page 70 of 179 6.2 INSTRUMENT SETPOINTS Liquid effluent monitor setpoints are determined to ensure that the concentration of radioactive material released at any time from the site to UNRESTRICTED AREAS does not exceed ten times the ECL limits referenced in ODCM Control 1.2.1.1 and to identify any unexpected releases.
The essential raw cooling water (ERCW) will be used for dilution for liquid effluents; however, the very large dilution factors afforded by the circulating coolant will not be used to allow high concentrations of liquid radioactive waste to be discharged from the plant.6.2.1 Discharge Point Monitor Setpoints (0-RM-90-133,134,140,141)
The setpoints for the ERCW monitors (RM-90-133, 134, 140, 141) are set to ensure that the concentration of radioactive materials released at any time from the site do not exceed the limits given in ODCM Control 1.2.1.1.The setpoints for these monitors will be set at a small value above background to ensure that any radioactivity is identified.
Site procedures will document and control this value.6.2.2 Release Point Monitor Setpoints (0-RM-90-122; 0-RM-90-225; O-RM-90-212; 1,2-RM-90-120,121)
There are five liquid release point effluent monitors:
the Liquid Radwaste System radiation monitor 0-RM-90-122; the Condensate Demineralizer System radiation monitor 0-RM-90-225; the Turbine Building Sump radiation monitor 0-RM-90-212; and the Steam Generator Blowdown (SGBD) radiation monitors 1,2-RM 120,121.The batch release points, the Liquid Radwaste System and the Condensate Demineralizer System (if being released in a batch mode), are looking at an undiluted waste stream as it comes out of a tank. The purpose of the monitor setpoints for these batch releases is to identify any release that is larger than expected and would have the potential to exceed the limits after dilution.
Setpoints are calculated as described in Section 6.2.3 and may be set at a default value. Site procedures will document and control this value.The continuous release points, the Condensate Demineralizer System, the Steam Generator Blowdowns, and the Turbine Building Sump, will not be releasing radioactivity unless there is or has been a primary to secondary leak. When there is no identified primary to secondary leakage, these release points are monitored to indicate the presence of elevated activity levels in these systems. The setpoints for these monitors will be set to alarm if the activity in the stream exceeds a routine nominal background.
These setpoints are controlled by site instructions.
When there is identified significant primary to secondary leakage, the continuous release points are monitored to identify any release that is larger than expected or would have the potential to exceed the 10 CFR Part 20 limits after dilution.
The monitor setpoints are calculated in the same manner as the batch release point monitor setpoints (described in Section 6.2.3) when this is the case. When these release points are being treated in this manner, a single batch release is defined as all effluent released through this point on a continuous bases for a period of time (usually one week).6.2.3 Batch Release Point Monitor Setpoint For each release from a release point, two setpoints are calculated:
one based on the monitor response to the contents of the effluent stream multiplied by an administrative factor to account for monitor fluctuations; and another based on the predicted response of the monitor to the activity in the release stream if it were large enough to exceed ten times the 10 CFR Part 20 limits after dilution.
The expected monitor response, R in cpm, is calculated using equation 6.3 below.The maximum calculated setpoint, Smax, is calculated using Equation 6.4 below. A comparison is made between these two calculated setpoints to determine which is used. The actual monitor setpoint for the release SQN ODCM Revision 57 Page 71 of 179 is set equal to X times the expected radioactivity response plus background, or to the maximum calculated setpoint, whichever is less. X is an administrative factor designed to account for expected variations in monitor response (it will be defined in approved plant instructions).
The X times expected response setpoint allows for the identification of any release of radioactivity above the expected amount. The maximum calculated setpoint ensures that the release will be stopped if it exceeds ten times the 10 CFR Part 20 concentration limits after dilution.
If default setpoints are used then a comparison is made between the calculated setpoints and the default setpoint as described below to choose the appropriate setpoint for the monitor during the release ( after the release, the monitor is normally returned to the default setpoint).
- 1. If SER "- Sdefault < Smax Reported = Sdefault 2. If SER < Smax < Sdefault Reported = SER 3. If SER - Smax Reported = Smax Expected response / Expected Response Setpoint (Ser)R = B + E Effi
- Ci (6.3)i Ser = X
- R where B = monitor background, cpm.Effi = monitor efficiency for nuclide i, cpm per pCi/ml.Ci = tank concentration of nuclide i, VCi/ml.X = Administrative Factor designed to account for expected variations in monitor response and background (The range of values is 1.5 < X < 2.0).Calculated Maximum Monitor Setpoint 10 FS (Fw + (A
- Fdil))Smax = (R- B) + B (6.4)Fw Rj where FS = fluctuation safety factor for the monitor, which is set at 1.0 < SF < 1.5. The fluctuation safety factor is set to account for minor changes in monitor response and background.
Fw = flow of waste stream, gpm.FdiI = flow of the dilution stream, routinely set @ 15,000 gpm.A = fraction of dilution flow allocated to this release point. For the TBS, this fraction is zero. The fractions for the remaining 4 release points are defined as the ratio of the allocated CTBD flow for that release point to the total CTBD flow. The CTBD flow allocation fractions for these release points are routinely:
Radwaste 0.60 Condensate demineralizer 0.20 Steam Generator Blowdown (U1) 0.10 Steam Generator Blowdown (U2) 0.10 NOTE: These allocation factors may be adjusted for a particular release if it is known that there are no releases being made through other release points into the CTBD. For example, if there are no releases being made through the Condensate Demineralizer or either Steam Generator Blowdown, the allocation factor for the Radwaste System may be set equal to one.R. = sum of the ECL ratios for release point j as calculated in Section 6.1.2.R = expected monitor response, cpm, as calculated above.B = background, cpm.10 = ECL ratio limit at the Cooling Tower Blowdown discharge.
SQN ODCM Revision 57 Page 72 of 179 6.3 CUMULATIVE LIQUID EFFLUENT DOSE CALCULATIONS Doses due to liquid effluents are calculated for each release for all age groups: adult (_17 years of age), teen (1 1, but <17 years), child (_1, but <11 years) and infant (0-1 years) and organs: bone, liver, total body, thyroid, skin, kidney, lung and GI tract. Pathways considered are ingestion of drinking water, fish consumption and recreation-shoreline.
The maximum individual dose from drinking water is assumed to be that calculated at the location immediately downstream from the diffuser in the Tennessee River. The maximum individual dose from fish ingestion is assumed to be that calculated for the consumption of fish caught anywhere between the plant and the first downstream dam (Chickamauga Dam). The maximum potential recreation dose is calculated for a location immediately downstream of the plant outfall. Dose factors for these age groups and pathways are calculated as described in Section 6.7. For pathways with no age or organ specific dose factors (i.e. shoreline recreation), the total body dose will be added to the internal organ doses for all age groups.The general equation for the dose calculations is: Dose = Xi Ait T Ci D (6.5)where: Ait = the total dose factor to the total body or any organ t for nuclide i, mrem/hr per pCi/ml. The total dose factor is the sum of the dose factors for water ingestion, fish ingestion, and shoreline recreation, as defined in Section 6.7.T =the length of time period over which the concentrations and the flows are averaged for the liquid release, hours.Ci =the average concentration of radionuclide i, in undiluted liquid effluent during the time period T from any liquid release, ýtCi/ml.D = the near field average dilution factor for Ci during any effluent release. D is calculated by the following equation: FLOWW D-=0.60 RF where: FLOWw= maximum undiluted liquid waste flow during the release, cfs. For TBS releases, this term is the diluted waste flow into the pond.0.60 = mixing factor of effluent in river, defined as the percentage of the river flow which is available for dilution of the release.RF = default riverflow, cfs. For each release, this value is set to 7900 cfs (the lowest average quarterly riverflow recorded from the period 1978-1988).
From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The total body and maximum organ doses for the critical age group are used in the calculation of the monthly dose described in Section 6.3.1.
SQN ODCM Revision 57 Page 73 of 179 6.3.1 Monthly Dose Calculations At the end of each month, the actual average riverflow for the month is used to recalculate the liquid doses. The monthly cumulative dose is defined as the sum of the doses for the critical age group for each release during the month. Thus, the monthly cumulative dose will be a conservative value, consisting of doses belonging to various age groups depending on the mix of radionuclides.
These doses are multiplied by the ratio of the default riverflow (7900 cfs) to the actual monthly average riverflow to obtain the monthly dose. The total body and maximum organ doses determined in this manner are then used to determine the cumulative quarterly and annual doses described in Section 6.3.2, and for the dose projections described in Section 6.5.6.3.2 Cumulative Doses Quarterly and annual sums of all doses are determined at the end of each month to compare to the limits given in ODCM Control 1.2.1.2. These quarterly and annual sums will be the sum of the monthly cumulative doses described in Section 6.3.1 for the appropriate months in the quarter or year. These doses will be used in the comparison to the limits.6.3.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to the limits in ODCM Control 1.2.1.2 once per 31 days to determine compliance.
SQN ODCM Revision 57 Page 74 of 179 6.4 LIQUID RADWASTE TREATMENT SYSTEM The liquid radwaste treatment system described below shall be maintained and operated to keep releases ALARA.A flow diagram for the LRTS is given in Figure 6.2. The system consists of one reactor coolant drain tank with two pumps and a floor and equipment drain sump inside the containment of each unit and the following shared equipment inside the auxiliary building:
one sump tank and pumps, one tritiated drain collector tank with two pumps and one filter, one floor drain collector tank with two pumps and one filter, a waste condensate tank filter, three waste condensate tanks and two pumps, a chemical drain tank and pump, two laundry and hot shower tanks and pump, a spent resin storage tank, a cask decontamination tank with two pumps and two filters, Auxiliary Building floor end equipment drain sump and pumps, and evaporator with two distillate tanks, a Mobile Waste Demineralizer System (if needed) and the associated piping, valves and instrumentation.
SQN ODCM Revision 57 Page 75 of 179 6.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.1.3, dose projections will be performed by averaging the two previous month's doses as determined in Section 6.3.1. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.The projected doses are compared to the limits of ODCM Control 1.2.1.3. If the projected doses exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge to UNRESTRICTED AREAS.D= a+b 2 where: D = the 31-day dose projection, mrem a = the cumulative dose for the previous month, mrem b = the cumulative dose for the present month, mrem SQN ODCM Revision 57 Page 76 of 179 6.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated liquid releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel.
The releases are assumed, for this calculation, to be continuous over the 90 day period.The average dilution factor, D, used for the quarterly calculations is: 1 D = (for receptors upstream (6.6)RF
- 0.60 of Chickamauga Dam)and 1 D = (for receptors downstream (6.7)RF of Chickamauga Dam)where: RF = the average actual riverflow for the location at which the dose is being determined, cfs.0.60 = the fraction of the riverflow available for dilution in the near field, dimensionless.
6.6.1 WATER
INGESTION Water ingestion doses are calculated for each water supply identified within a 50 mile radius downstream of SQN (Table 6.1). The summation of water ingestion doses are calculated for the total body and each internal organ as described below: Dor = 106 9.80E-09 0.2 5YAwit Qi D exp(-8.64E+04 ki td) (6.8)where 106 = conversion factor, pCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.0.25 = fraction of the yearly water consumption in one quarter, dimensionless Awit = dose factor for water ingestion for nuclide i, age group t, mrem/h per pCi/ml, as calculated in Section 6.7.1.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs-1.k'i = radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for water ingestion, equal to the travel time from the plant to the water supply plus one day to account for the time of processing at the water supply (per Regulatory Guide 1.109), d.8.64E+04 = conversion factor, seconds per day.
SQN ODCM Revision 57 Page 77 of 179 6.6.2 FISH INGESTION Fish ingestion doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). The summation of individual fish ingestion doses are calculated for the total body and each internal organ as described below: Dorg = 106 9.80E-09 0.25 EAFit Qi D exp(-8.64E+04 Xi td) (6.9)where 106 = conversion factor, [tCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.0.25 = fraction of the yearly fish consumption eaten in one quarter, dimensionless.
AFit = dose factor for fish ingestion for nuclide i, age group t, mrem/h per ViCi/ml, as calculated in Section 6.7.2.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs-1.Xi = radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for fish ingestion, equal to the travel time from the plant to the center of the reach plus one day to account for transit through the food chain and food preparation time (per Regulatory Guide 1.109), d.8.64E+04 = conversion factor, seconds per day.6.6.3 SHORELINE RECREATION Recreation doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). It is assumed that the maximum exposed individual spends 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> per year on the shoreline at a location immediately downstream from the diffusers.
The summation of individual recreation shoreline doses are calculated for the total body and skin as described below: Dorg = 106 9.80E-09 rf ,ARit Qi D exp(-8.64E+04 ki td) (6.10)where 106 = conversion factor, pCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.rf = recreation factor, used to account for the fact that the same amount of time will not be spent at a recreation site during each quarter. Recreation factors used are: 1st quarter -0.1 2nd quarter -0.3 3rd quarter -0.4 4th quarter- 0.2.ARit = dose factor for shoreline recreation for nuclide i, age group t, mrem/h per ptCi/ml, as calculated in Section 6.7.3.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs-1)1i = radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for recreation, equal to the travel time from the plant to the center of the reach, d.8.64E+04 = conversion factor, seconds per day.
SQN ODCM Revision 57 Page 78 of 179 6.6.4 TOTAL MAXIMUM INDIVIDUAL DOSE The total maximum individual total body dose is obtained by summing the following for each age group: the highest total body water ingestion dose from among all the public water supplies; the highest total body fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual organ dose is obtained by summing the following for each organ and each age group: that organ's highest water ingestion dose from among all the public water supplies; that organ's highest fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual skin dose is that skin dose calculated for the maximum shoreline dose.6.6.5 POPULATION DOSES For determining population doses to the 50-mile population around the plant, an average dose is calculated for each age group and each pathway and then multiplied by the population.
For water ingestion, the general equation used for calculating the population doses, POPWTR, in man-rem for a given PWS is: 4 4 POPWTRt = 10-3 Z pop Y POPa ATMWa TWDOSamt (6.11)m=1 a=1 where: POPWTRt = water ingestion population dose to organ t, man-rem.POPa = fraction of population in each age group a (from NUREG CR-1004, table 3.39).Adult = 0.665 Child = 0.168 Infant = 0.015 Teen = 0.153 POPm = population at PWS m. The 4 PWSs and their populations are listed in Table 6.1.ATMWa = ratio of average to maximum water ingestion rates for each age group a. Maximum water ingestion rates are given in Table 6.3. Average water ingestion rates, in I/year, (from R.G. 1.109 Table E-4) are: Adult = 370 Child = 260 Infant = 260 Teen = 260 TWDOSamt = total individual water ingestion dose to organ t at PWS m, to the age group a, as described in Section 6.6.1, mrem.10-3 = conversion factor for rem/mrem.
SQN ODCM Revision 57 Page 79 of 179 For population doses resulting from fish ingestion the calculation assumes that all fish caught within a 50-mile radius downstream of SQN are consumed by local population.
The general equation for calculating population doses, POPF, in man-rem from fish ingestion of all fish caught within a 50-mile radius downstream is: 453.6 HVST APR 4 3 TFDOSart POPa POPFt = I YX (6.12)103 103 r=1 a=1 FISHa POPa where: POPFt = total fish ingestion population dose to organ t, man-rem.HVST = fish harvest for the Tennessee River, 3.04 lbs/acre/y.
APR = size of reach, acres (Table 6.1).TFDOSart = total fish ingestion dose to organ t for reach r, for the age group a, as described in Section 6.6.2, mrem.Popp = fraction of population in each age group a, as given above.FISHa = amount of fish ingested by each age group a, kg/y. Average fish ingestion rates (R.G. 1.109 Table E-4) are: Adult = 6.9 Child = 2.2 Teen = 5.2 453.6 = conversion factor, g/lb.103 = conversion factor, mrem/rem.103 = conversion factor, g/kg.
SQN ODCM Revision 57 Page 80 of 179 For recreation shoreline, the general equation used for calculating the population doses, POPR, in man-rem is: REQFRA 4 POPRt = Y_ TSHDOSt SHVISr HRSVISr 103 8760 r=1 (6.13)where: POPRt =REQFRA =TSHDOSrt =SHVISr =HRSVISr 103 =8760 =total recreation population dose for all reaches to organ t, man-rem.fraction of yearly recreation which occurs in that quarter, as given in Section 6.6.3.total shoreline dose rate for organ t, in reach r, mrem/h.shoreline visits per year at each reach r, (Table 6.1).length of shoreline recreation visit at reach r, 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.conversion factor, mrem/rem.conversion factor, hours per year.
SQN ODCM Revision 57 Page 81 of 179 6.7 LIQUID DOSE FACTOR EQUATIONS 6.7.1 WATER INGESTION Awit (mrem/h per p.Ci/ml)DFLiat Uwa 106 103 Awit =8760 where: DFLiat= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).Uwa = water consumption rate for age group a, L/y, (Table 6.3).106 = conversion factor, pCi/pCi.103 = conversion factor, mill.8760 = conversion factor, hours per year.6.7.2 FISH INGESTION AFit (mrem/h per 1 iCi/ml)DFLiat Ufa Bi 106 103 AFit =8760 where: DFLiat= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).Ufa = fish consumption rate for age group a, kg/y, (Table 6.3).Bi = bioaccumulation factor for nuclide i, pCi/kg per pCi/L, (Table 6.5).106 = conversion factor, pCi/pCi.103 = conversion factor, milL.8760 = conversion factor, hours per year.6.7.3 SHORELINE RECREATION ARit (mrem/h per IiCi/ml).DFGit K, M W 10 3 10 6 U ARit= [1 -exp(-;kitb)]
8760
- 3600 ki where: DFGit= dose conversion factor for standing on contaminated ground for nuclide i and organ t (total body and skin), mrem/h per pCi/m 2 , (Table 6.6).Kc = transfer coefficient from water to shoreline sediment, L/kg-h, (Table 6.3).M = mass density of sediment, kg/m 2 , (Table 6.3).W = shoreline width factor, dimensionless, (Table 6.3).103 = conversion factor, mil/L.106 = conversion factor, pCi/tCi.3600 = conversion factor, s/h.ki = decay constant for nuclide i, s-1, (Table 6.2).tb = time shoreline is exposed to the concentration on the water, s, (Table 6.3).U = usage factor, 500 h/y.8760 = conversion factor, hours per year.
SQN ODCM Revision 57 Page 82 of 179 Table 6.1 RECEPTORS FOR LIQUID DOSE CALCULATIONS Tennessee River Reaches Within 50 Mile Radius Downstream of SQN Beginning Ending Size Recreation Name TRM TRM (acres) visits/year Chickamauga Lake 484 471 9939 5,226,700 below SQN Nickajack Lake 471 435 6510 240,700 (Chickamauga Dam to TRM 435)Nickajack Lake 435 425 5326 607,600 (TRM 435 to Nickajack Dam)Guntersville Lake 425 400 6766 104,000 (Nickajack Dam to SQN 50 mi. Radius)Public Water Supplies Within 50 Mile Radius Downstream of SQN Name East Side Utility (Formally C.F. Industries)
Chattanooga, TN South Pittsburg, TN Bridgeport, AL TRM 473.0 465.3 418.0 413.6 Population 35000 224,000 4,898 4,650 SQN ODCM Revision 57 Page 83 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 1 of 3)Half-Life Biv Fmi Fmi Ffi (minutes) (l/s) (cow) (Qoat (beef)H-3 6.46E+06 1.79E-09 4.80E+00 1.OOE-02 1.70E-01 1.20E-02 C-14 3.01E+09 3.84E-12 5.50E+00 1.20E-02 1.OOE-01 3.1OE-02 Na-24 9.OOE+02 1.28E-05 5.20E-02 4.OOE-02 4.OOE-02 3.OOE-02 P-32 2.06E+04 5.61E-07 1.1OE+00 2.50E-02 2.50E-01 4.60E-02 Cr-51 3.99E+04 2.90E-07 2.50E-04 2.20E-03 2.20E-03 2.40E-03 Mn-54 4.50E+05 2.57E-08 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Mn-56 1.55E+02 7.45E-05 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Fe-55 1.42E+06 8.13E-09 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Fe-59 6.43E+04 1.80E-07 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Co-57 3.90E+05 2.96E-08 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Co-58 1.02E+05 1.13E-07 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Co-60 2.77E+06 4.17E-09 9.40E-03 1.O0E-03 1.OOE-03 1.30E-02 Ni-63 5.27E+07 2.19E-10 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Ni-65 1.51E+02 7.65E-05 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Cu-64 7.62E+02 1.52E-05 1.20E-01 1.40E-02 1.30E-02 9.70E-04 Zn-65 3.52E+05 3.28E-08 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69m 8.26E+02 1.40E-05 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69 5.56E+01 2.08E-04 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Br-82 2.12E+03 5.45E-06 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-83 1.43E+02 8.08E-05 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-84 3.18E+01 3.63E-04 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-85 2.87E+00 4.02E-03 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Rb-86 2.69E+04 4.29E-07 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Rb-88 1.78E+01 6.49E-04 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Rb-89 1.54E+01 7.50E-04 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Sr-89 7.28E+04 1.59E-07 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-90 1.50E+07 7.70E-10 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-91 5.70E+02 2.03E-05 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-92 1.63E+02 7.09E-05 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Y-90 3.85E+03 3.OOE-06 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-91m 4.97E+01 2.32E-04 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-91 8.43E+04 1.37E-07 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-92 2.12E+02 5.45E-05 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-93 6.06E+02 1.91 E-05 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Zr-95 9.22E+04 1.25E-07 1.70E-04 5.OOE-06 5.OOE-06 3.40E-02 Zr-97 1.01E+03 1.14E-05 1.70E-04 5.OOE-06 5.OOE-06 3.40E-02 Nb-95 5.05E+04 2.29E-07 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Nb-97 7.21E+01 1.60E-04 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Mo-99 3.96E+03 2.92E-06 1.20E-01 7.50E-03 7.50E-03 1.10E-03 Tc-99m 3.61 E+02 3.20E-05 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Tc-101 1.42E+01 8.13E-04 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Ru-103 5.67E+04 2.04E-07 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 Ru-105 2.66E+02 4.34E-05 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 Ru-106 5.30E+05 2.18E-08 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 SQN ODCM Revision 57 Page 84 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 2 of 3)Half-Life "I Biv Fmi Fmi Ff, (minutes) (l/s) (cow) (goat) (beef)Ag-110m 3.60E+05 3.21E-08 1.50E-01 5.00E-02 5.OOE-02 1.70E-02 Sb-124 8.67E+04 1.33E-07 N/A 1.50E-03 1.50E-03 N/A Sb-125 1.46E+06 7.91E-09 N/A 1.50E-03 1.50E-03 N/A Sn-125 1.39E+04 8.32E-07 N/A N/A N/A N/A Te-125m 8.35E+04 1.38E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127m 1.57E+05 7.36E-08 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127 5.61E+02 2.06E-05 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129m 4.84E+04 2.39E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129 6.96E+01 1.66E-04 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-131m 1.80E+03 6.42E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-131 2.50E+01 4.62E-04 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-132 4.69E+03 2.46E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 1-130 7.42E+02 1.56E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-131 1.16E+04 9.96E-07 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-132 1.38E+02 8.37E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-133 1.25E+03 9.24E-06 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-134 5.26E+01 2.20E-04 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-135 3.97E+02 2.91E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 Cs-134 1.08E+06 1.06E-08 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-136 1.90E+04 6.08E-07 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-137 1.59E+07 7.26E-10 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-138 3.22E+01 3.59E-04 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Ba-139 8.31E+01 1.39E-04 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-140 1.84E+04 6.28E-07 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-141 1.83E+01 6.31E-04 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-142 1.07E+01 1.08E-03 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 La-140 2.41 E+03 4.79E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 La-142 9.54E+01 1.21 E-04 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 Ce-141 4.68E+04 2.47E-07 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-143 1.98E+03 5.83E-06 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-144 4.09E+05 2.82E-08 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Pr-143 1.95E+04 5.92E-07 2.50E-03 5.OOE-06 5.OOE-06 4.70E-03 Pr-144 1.73E+01 6.68E-04 2.50E-03 5.OOE-06 5.OOE-06 4.70E-03 Nd-147 1.58E+04 7.31E-07 2.40E-03 5.OOE-06 5.OOE-06 3.30E-03 W-187 1.43E+03 8.08E-06 1.80E-02 5.OOE-04 5.OOE-04 1.30E-03 Np-239 3.39E+03 3.41 E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 Ar-41 1.10E+02 1.05E-04 N/A N/A N/A N/A Kr-83m 1.10E+02 1.05E-04 N/A N/A N/A N/A Kr-85m 2.69E+02 4.29E-05 N/A N/A N/A N/A Kr-85 5.64E+06 2.05E-09 N/A N/A N/A N/A Kr-87 7.63E+01 1.51 E-04 N/A N/A N/A N/A Kr-88 1.70E+02 6.79E-05 N/A N/A N/A N/A Kr-89 3.16E+00 3.66E-03 N/A N/A N/A N/A Kr-90 5.39E-01 2.14E-02 N/A N/A N/A N/A Xe-131m 1.70E+04 6.79E-07 N/A N/A N/A N/A SQN ODCM Revision 57 Page 85 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 3 of 3)Xe-133m Xe-1 33 Xe-1 35m Xe-1 35 Xe-137 Xe-138 Half-Life (minutes)3.15E+03 7.55E+03 1.54E+01 5.47E+02 3.83E+00 1.41E+01 x 3.67E-06 1.53E-06 7.50E-04 2.11 E-05 3.02E-03 8.19E-04 Biv N/A N/A N/A N/A N/A N/A Fmi (cow)N/A N/A N/A N/A N/A N/A Fmi (goat)N/A N/A N/A N/A N/A N/A Ffi (beef)N/A N/A N/A N/A N/A N/A
References:
Half lives for all nuclides:
DOE-TIC-1 1026, "Radioactive Decay Data Tables -A handbook of Decay Data for Application to Radiation Dosimetry and Radiological Assessment," D. C. Kocher, 1981.Transfer factors for Sb- isotopes are from ORNL 4992, "Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment," March 1976, Table 2-7.Cow-milk transfer factors for Iodine, Strontium, and Cesium nuclides are from NUREG/CR-1004, Table 3.17.Goat-milk transfer factors for Iodine nuclides are from NUREG/CR-1 004, Table 3.17.Beef transfer factors for Iron, Copper, Molybdenum, and Cesium nuclides are from NUREG/CR-1 004, Table 3.18.All other nuclides' transfer factors are from Regulatory Guide 1.109, Tables E-1 and E-2.
SQN ODCM Revision 57 Page 86 of 179 Table 6.3 DOSE CALCULATION FACTORS (Page 1 of 2)Factor BRa (infant)BRa (child)BRa (teen)BRa (adult)fp Sf H KC M P Qf (cow)Qf (goat)r tb tcb tcsf te tep tesf tfm thc ts tsv Uam (infant)Uam (child)Uam (teen)Uam (adult)Uap (infant)Uap (child)Uap (teen)Uap (adult)Ufa(infant)
Ufa(child)
Ufa(teen)Value 1400 5500 8000 8100 1 1 1 0 9 0.072 40 240 64 08 0.47 4.73E+08 (15 years)7.78E+06 (90 days)1.56E+07 (180 days)5.18E+06 (60 days)2.59E+06 (30 days)7.78E+06 (90 days)8.64E+04 (1 day)8.64E+04 (1 day)1.12E+06 (13 days)2.38E+07 (275 days)0 41 65 110 330 330 400 310 0 6.9 16 Units m 3/year m 3/year m 3/year m 3/year g/m 3 L/kg-h kg/m2 kg/m2 kg/d kg/d seconds seconds seconds seconds seconds seconds seconds seconds seconds seconds kg/year kg/year kg/year kg/year I/year I/year I/year I/year kg/year kg/year kg/year Reference ICRP 23 ICRP 23 ICRP 23 ICRP 23 TVA Assumption R. G. 1.109 (Table E-15)TVA Assumption TVA Assumption TVA Value R. G. 1.109 (Section 2.C.)R. G. 1.109 (Section 2.C.)R. G. 1.109 (Table E-15)NUREG/CR-1004 (Sect. 3.4)NUREG/CR-1004 (Sect. 3.4)NUREG/CR-1004 (Sect. 3.2)R. G. 1.109 (Table E-15)SQN FSAR Section 11.3.9.1 SQN FSAR Section 11.3.9.1 R. G. 1.109 (Table E-15)R. G. 1.109 (Table E-15)R. G. 1.109 (Table E-15)SQN FSAR Section 11.3.9.1 NUREG/CR-1004, Table 3.40 NUREG/CR-1004, Table 3.40 SQN FSAR Section 11.3.9.1 R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)1.109 (Table E-5)
SQN ODCM Revision 57 Page 87 of 179 Table 6.3 DOSE CALCULATION FACTORS (Page 2 of 2)Factor Ufa(adult)
Ufla (infant)Ufla (child)Ufa (teen)Ufla (adult)Usa (infant)Usa (child)Usa (teen)Usa (adult)Uwa(infant)
Uwa(child)
Uwa(teen)Uwa(adult) w Yf Yp Y s f Ysv xw (iodines)Xw (particulates)
Value 21 0 26 42 64 0 520 630 520 330 510 510 730 0.3 kg/year kg/year kg/year kg/year kg/year kg/year kg/year kg/year kg/year L/year L/year L/year L/year none kg/m 2 kg/m 2 kg/m 2 kg/m 2 sec-1 sec-1 Units Reference R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table A-2)NUREG/CR-1004 (Table 3.4)NUREG/CR-1004 (Table 3.3)NUREG/CR-1004 (Table 3.3)NUREG/CR-1004 (Table 3.4)(value selected is for non-leafy vegetables)
NUREG/CR-1004 (Table 3.10)NUREG/CR-1004 (Table 3.10)1.85 1.18 0.64 0.57 7.71 E-07 (10.4 d half-life) 5.21 E-07 (15.4 d half-life)
SQN ODCM Revision 57 Page 88 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 1 of 8)ADULT bone liver t body thyroid kidney lung gi-Ili H-3 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 C-14 2.84E-06 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 Na-24 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 P-32 1.93E-04 1.20E-05 7.46E-06 0.OOE+00 O.OOE+00 0.OOE+00 2.17E-05 Cr-51 0.O0E+00 0.OOE+00 2.66E-09 1.59E-09 5.86E-10 3.53E-09 6.69E-07 Mn-54 0.O0E+00 4.57E-06 8.72E-07 0.OOE+00 1.36E-06 O.OOE+00 1.40E-05 Mn-56 0.OOE+00 1.15E-07 2.04E-08 0.OOE+00 1.46E-07 0.OOE+00 3.67E-06 Fe-55 2.75E-06 1.90E-06 4.43E-07 O.OOE+00 O.OOE+00 1.06E-06 1.09E-06 Fe-59 4.34E-06 1.02E-05 3.91 E-06 0.OOE+00 0.OOE+00 2.85E-06 3.40E-05 Co-57 0.OOE+00 1.75E-07 2.91 E-07 0.OOE+00 0.OOE+00 0.OOE+00 4.44E-06 Co-58 0.OOE+00 7.45E-07 1.67E-06 0.OOE+00 O.OOE+00 0.OOE+00 1.51 E-05 Co-60 O.OOE+00 2.14E-06 4.72E-06 0.OOE+00 O.OOE+00 0.OOE+00 4.02E-05 Ni-63 1.30E-04 9.01E-06 4.36E-06 O.OOE+00 0.OOE+00 0.OOE+00 1.88E-06 Ni-65 5.28E-07 6.86E-08 3.13E-08 0.OOE+00 0.OOE+00 O.OOE+00 1.74E-06 Cu-64 0.OOE+00 8.33E-08 3.91E-08 0.OOE+00 2.1OE-07 0.OOE+00 7.1OE-06 Zn-65 4.84E-06 1.54E-05 6.96E-06 0.OOE+00 1.03E-05 0.OOE+00 9.70E-06 Zn-69 1.03E-08 1.97E-08 1.37E-09 O.OOE+00 1.28E-08 0.OOE+00 2.96E-09 Zn-69m 1.70E-07 4.08E-07 3.73E-08 O.OOE+00 2.47E-07 0.OOE+00 2.49E-05 Br-82 0.OOE+00 0.OOE+00 2.26E-06 0.OOE+00 0.OOE+00 O.OOE+00 2.59E-06 Br-83 0.OOE+00 0.OOE+00 4.02E-08 0.OOE+00 0.OOE+00 O.OOE+00 5.79E-08 Br-84 0.00E+00 0.OOE+00 5.21E-08 0.OOE+00 O.OOE+00 O.OOE+00 4.09E-13 Br-85 0.OOE+00 0.OOE+00 2.14E-09 0.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 Rb-86 0.OOE+00 2.11E-05 9.83E-06 0.OOE+00 0.OOE+00 O.OOE+00 4.16E-06 Rb-88 0.OOE+00 6.05E-08 3.21E-08 O.OOE+00 0.OOE+00 O.OOE+00 8.36E-19 Rb-89 0.OOE+00 4.01 E-08 2.82E-08 0.OOE+00 0.OOE+00 O.OOE+00 2.33E-21 Sr-89 3.08E-04 0.OOE+00 8.84E-06 0.OOE+00 0.OOE+00 0.OOE+00 4.94E-05 Sr-90 7.58E-03 O.OOE+00 1.86E-03 0.OOE+00 0.OOE+00 0.OOE+00 2.19E-04 Sr-91 5.67E-06 0.OOE+00 2.29E-07 0.OOE+00 0.OOE+00 O.OOE+00 2.70E-05 Sr-92 2.15E-06 0.OOE+00 9.30E-08 O.OOE+00 0.OOE+00 0.OOE+00 4.26E-05 Y-90 9.62E-09 O.OOE+00 2.58E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.02E-04 Y-91m 9.09E-11 0.OOE+00 3.52E-12 0.OOE+00 0.OOE+00 0.OOE+00 2.67E-10 Y-91 1.41E-07 0.OOE+00 3.77E-09 O.OOE+00 O.OOE+00 0.OOE+00 7.76E-05 Y-92 8.45E-10 0.OOE+00 2.47E-11 0.OOE+00 0.OOE+00 O.OOE+00 1.48E-05 Y-93 2.68E-09 0.OOE+00 7.40E-11 0.OOE+00 0.OOE+00 0.OOE+00 8.50E-05 Zr-95 3.04E-08 9.75E-09 6.60E-09 O.OOE+00 1.53E-08 0.OOE+00 3.09E-05 Zr-97 1.68E-09 3.39E-10 1.55E-10 0.OOE+00 5.12E-10 O.OOE+00 1.05E-04 Nb-95 6.22E-09 3.46E-09 1.86E-09 0.OOE+00 3.42E-09 0.OOE+00 2.1OE-05 Nb-97 5.22E-11 1.32E-11 4.82E-12 0.O0E+00 1.54E-11 0.OOE+00 4.87E-08 Mo-99 0.OOE+00 4.31 E-06 8.20E-07 0.OOE+00 9.76E-06 O.OOE+00 9.99E-06 Tc-99m 2.47E-10 6.98E-10 8.89E-09 0.OOE+00 1.06E-08 3.42E-10 4.13E-07 Tc-101 2.54E-10 3.66E-10 3.59E-09 0.OOE+00 6.59E-09 1.87E-10 1.1OE-21 Ru-103 1.85E-07 0.OOE+00 7.97E-08 0.OOE+00 7.06E-07 0.OOE+00 2.16E-05 Ru-105 1.54E-08 0.OOE+00 6.08E-09 0.OOE+00 1.99E-07 0.OOE+00 9.42E-06 Ru-106 2.75E-06 O.OOE+00 3.48E-07 0.OOE+00 5.31E-06 0.OOE+00 1.78E-04 SQN ODCM Revision 57 Page 89 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 2 of 8)ADULT Ag-110m Sb-1i24 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-1 31 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-1 37 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 1.60E-07 2.80E-06 1.79E-06 8.33E-06 2.68E-06 6.77E-06 1.10E-07 1.15E-05 3.14E-08 1.73E-06 1.97E-08 2.52E-06 7.56E-07 4.16E-06 2.03E-07 1.42E-06 1.06E-07 4.43E-07 6.22E-05 6.51 E-06 7.97E-05 5.52E-08 9.70E-08 2.03E-05 4.71 E-08 2.13E-08 2.50E-09 1.28E-10 9.36E-09 1.65E-09 4.88E-07 9.20E-09 3.01 E-11 6.29E-09 1.03E-07 1.19E-09 liver 1.48E-07 5.29E-08 2.OOE-08 1.68E-07 9.71 E-07 2.42E-06 3.95E-08 4.29E-06 1.18E-08 8.46E-07 8.23E-09 1.63E-06 2.23E-06 5.95E-06 5.43E-07 2.47E-06 2.88E-07 1.16E-06 1.48E-04 2.57E-05 1.09E-04 1.09E-07 6.91 E-11 2.55E-08 3.56E-1 1 2.19E-1 1 1.26E-09 5.82E-1 1 6.33E-09 1.22E-06 2.04E-07 3.69E-09 1.25E-1 1 7.27E-09 8.61 E-08 1.17E-10 t body 8.79E-08 1.11E-06 4.26E-07 3.78E-07 3.59E-07 8.25E-07 2.38E-08 1.82E-06 7.65E-09 7.05E-07 6.22E-09 1.53E-06 8.80E-07 3.41 E-06 1.90E-07 7.53E-07 1.03E-07 4.28E-07 1.21E-04 1.85E-05 7.14E-05 5.40E-08 2.84E-09 1.33E-06 1.59E-09 1.34E-09 3.33E-10 1.45E-1 1 7.18E-10 1.35E-10 2.62E-08 4.56E-10 1.53E-12 4.35E-10 3.01 E-08 6.45E-1 1 thyroid 0.00E+00 6.79E-09 1.82E-09 1.39E-07 8.06E-07 1.73E-06 8.15E-08 3.95E-06 2.41 E-08 1.34E-06 1.62E-08 1.80E-06 1.89E-04 1.95E-03 1.90E-05 3.63E-04 4.99E-06 7.65E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 kidney 2.91 E-07 0.00E-00 0.00E-00 0.00E-00 1.09E-05 2.75E-05 4.48E-07 4.80E-05 1.32E-07 8.57E-06 8.63E-08 1.57E-05 3.48E-06 1.02E-05 8.65E-07 4.31 E-06 4.58E-07 1.86E-06 4.79E-05 1.43E-05 3.70E-05 8.01 E-08 6.46E-11 8.67E-09 3.31 E-1 1 1.85E-11 0.OOE+00 0.00E+00 2.94E-09 5.37E-10 1.21 E-07 2.13E-09 7.05E-12 4.25E-09 0.OOE+00 3.65E-1 0 lung 0.OOE+00 2.18E-06 1.38E-06 0.OOE-00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.59E-05 1.96E-06 1.23E-05 7.91 E-09 3.92E-1 1 1.46E-08 2.02E-1 1 1.24E-11 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 6.04E-05 7.95E-05 1.97E-05 1.04E-04 1.07E-05 2.27E-05 8.68E-06 5.79E-05 2.37E-08 8.40E-05 2.79E-09 7.71 E-05 1.92E-06 1.57E-06 1.02E-07 2.22E-06 2.51E-10 1.31 E-06 2.59E-06 2.92E-06 2.11 E-06 4.65E-13 1.72E-07 4.18E-05 2.22E-17 3.OOE-26 9.25E-05 4.25E-07 2.42E-05 4.56E-05 1.65E-04 4.03E-05 4.33E-18 3.49E-05 2.82E-05 2.40E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-11.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 57 Page 90 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 3 of 8)TEEN bone liver t body thyroid kidney lung gi-Ili H-3 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 C-14 4.06E-06 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 Na-24 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 P-32 2,76E-04 1.71 E-05 1.07E-05 0.OOE+00 0.OOE+00 0.OOE+00 2.32E-05 Cr-51 0.OOE+00 0.OOE+00 3.60E-09 2.OOE-09 7.89E-10 5.14E-09 6.05E-07 Mn-54 0.OOE+00 5.90E-06 1.17E-06 0.OOE+00 1.76E-06 O.OOE+00 1.21E-05 Mn-56 0.OOE+00 1.58E-07 2.81 E-08 0.OOE+00 2.OOE-07 0.OOE+00 1.04E-05 Fe-55 3.78E-06 2.68E-06 6.25E-07 0.OOE+00 0.OOE+00 1.70E-06 1.16E-06 Fe-59 5.87E-06 1.37E-05 5.29E-06 0.00E+00 0.OOE+00 4.32E-06 3.24E-05 Co-57 0.OOE+00 2.38E-07 3.99E-07 O.OOE+00 0.OOE+00 0.OOE+00 4.44E-06 Co-58 0.0OE+00 9.72E-07 2.24E-06 0.OOE+00 O.OOE+00 0.OOE+00 1.34E-05 Co-60 0.OOE+00 2.81E-06 6.33E-06 O.OOE+00 0.OOE+00 0.OOE+00 3.66E-05 Ni-63 1.77E-04 1.25E-05 6.OOE-06 0.OOE+00 O.OOE+00 0.OOE+00 1.99E-06 Ni-65 7.49E-07 9.57E-08 4.36E-08 O.OOE+00 0.OOE+00 0.OOE+00 5.19E-06 Cu-64 O.OOE+00 1.15E-07 5.41E-08 0.OOE+00 2.91E-07 O.00E+00 8.92E-06 Zn-65 5.76E-06 2.OOE-05 9.33E-06 0.OOE+00 1.28E-05 0.OOE+00 8.47E-06 Zn-69 1.47E-08 2.80E-08 1.96E-09 O.OOE+00 1.83E-08 0.OOE+00 5.16E-08 Zn-69m 2.40E-07 5.66E-07 5.19E-08 0.OOE+00 3.44E-07 0.OOE+00 3.11E-05 Br-82 O.OOE+00 O.OOE+00 3.04E-06 0.OOE+00 O.OOE+00 0.OOE+00 O.OOE+00 Br-83 0.OOE+00 0.OOE+00 5.74E-08 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-84 O.OOE+00 0.OOE+00 7.22E-08 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-85 O.OOE+00 0.OOE+00 3.05E-09 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Rb-86 O.OOE+00 2.98E-05 1.40E-05 0.OOE+00 O.OOE+00 0.OOE+00 4.41 E-06 Rb-88 0.OOE+00 8.52E-08 4.54E-08 0.OOE+00 0.OOE+00 0.OOE+00 7.30E-15 Rb-89 0.OOE+00 5.50E-08 3.89E-08 0.OOE+00 0.OOE+00 0.OOE+00 8.43E-17 Sr-89 4.40E-04 0.OOE+00 1.26E-05 0.OOE+00 0.OOE+00 0.OOE+00 5.24E-05 Sr-90 8.30E-03 O.OOE+00 2.05E-03 0.OOE+00 O.OOE+00 0.OOE+00 2.33E-04 Sr-91 8.07E-06 O.OOE+00 3.21E-07 0.OOE+00 0.OOE+00 O.OOE+00 3.66E-05 Sr-92 3.05E-06 0.OOE+00 1.30E-07 0.OOE+00 O.OOE+00 0.OOE+00 7.77E-05 Y-90 1.37E-08 0.OOE+00 3.69E-10 0.OOE+00 O.OOE+00 0.OOE+00 1.13E-04 Y-91m 1.29E-10 0.OOE+00 4.93E-12 O.OOE+00 0.OOE+00 0.OOE+00 6.09E-09 Y-91 2.01 E-07 O.00E+00 5.39E-09 0.OOE+00 0.OOE+00 0.OOE+00 8.24E-05 Y-92 1.21E-09 O.OOE+00 3.50E-11 0.OOE+00 0.OOE+00 0.OOE+00 3.32E-05 Y-93 3.83E-09 0.OOE+00 1.05E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.17E-04 Zr-95 4.12E-08 1.30E-08 8.94E-09 0.OOE+00 1.91E-08 0.OOE+00 3.OOE-05 Zr-97 2.37E-09 4.69E-10 2.16E-10 O.OOE+00 7.11E-10 0.OOE+00 1.27E-04 Nb-95 8.22E-09 4.56E-09 2.51 E-09 0.OOE+00 4.42E-09 0.OOE+00 1.95E-05 Nb-97 7.37E-11 1.83E-11 6.68E-12 0.OOE+00 2.14E-11 0.OOE+00 4.37E-07 Mo-99 0.OOE+00 6.03E-06 1.15E-06 0.OOE+00 1.38E-05 0.OOE+00 1.08E-05 Tc-99m 3.32E-10 9.26E-10 1.20E-08 0.OOE+00 1.38E-08 5.14E-10 6.08E-07 Tc-101 3.60E-10 5.12E-10 5.03E-09 0.OOE+00 9.26E-09 3.12E-10 8.75E-17 Ru-103 2.55E-07 0.OOE+00 1.09E-07 0.OOE+00 8.99E-07 0.OOE+00 2.13E-05 Ru-105 2.18E-08 0.OOE+00 8.46E-09 0.OOE+00 2.75E-07 0.OOE+00 1.76E-05 Ru-106 3.92E-06 0.OOE+00 4.94E-07 0.OOE+00 7.56E-06 0.OOE+00 1.88E-04 SQN ODCM Revision 57 Page 91 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 4 of 8)Ag-110m Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 2.05E-07 3.87E-06 2.48E-06 1.19E-05 3.83E-06 9.67E-06 1.58E-07 1.63E-05 4.48E-08 2.44E-06 2.79E-08 3.49E-06 1.03E-06 5.85E-06 2.79E-07 2.01 E-06 1.46E-07 6.1 OE-07 8.37E-05 8.59E-06 1.12E-04 7.76E-08 1.39E-07 2.84E-05 6.71 E-08 2.99E-08 3.48E-09 1.79E-10 1.33E-08 2.35E-09 6.96E-07 1.31 E-08 4.30E-1 1 9.38E-09 1.46E-07 1.76E-09 liver 1.94E-07 7.13E-08 2.71 E-08 2.37E-07 1.38E-06 3.43E-06 5.60E-08 6.05E-06 1.67E-08 1.17E-06 1.15E-08 2.21 E-06 2.98E-06 8.19E-06 7.30E-07 3.41 E-06 3.87E-07 1.57E-06 1.97E-04 3.38E-05 1.49E-04 1.49E-07 9.78E-11 3.48E-08 5.01 E-11 2.99E-11 1.71 E-09 7.95E-1 1 8.88E-09 1.71 E-06 2.88E-07 5.23E-09 1.76E-1 1 1.02E-08 1.19E-07 1.66E-10 t body 1.18E-07 1.51 E-06 5.80E-07 5.37E-07 5.12E-07 1.15E-06 3.40E-08 2.58E-06 1.09E-08 9.76E-07 8.72E-09 2.08E-06 1.19E-06 4.40E-06 2.62E-07 1.04E-06 1.39E-07 5.82E-07 9.14E-05 2.27E-05 5.19E-05 7.45E-08 4.05E-09 1.83E-06 2.24E-09 1.84E-09 4.55E-10 1.98E-11 1.02E-09 1.91E-10 3.74E-08 6.52E-10 2.18E-12 6.11E-10 4.17E-08 9.22E-11 TEEN thyroid 0.00E+00 8.78E-09 2.37E-09 1.86E-07 1.07E-06 2.30E-06 1.09E-07 5.26E-06 3.20E-08 1.76E-06 2.15E-08 2.33E-06 2.43E-04 2.39E-03 2.46E-05 4.76E-04 6.45E-06 1.01 E-04 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.00E+00 kidney 3.70E-07 0.OOE-00 0.OOE+00 0.OOE+00 0.OOE+00 3.92E-05 6.40E-07 6.82E-05 1.88E-07 1.22E-05 1.22E-07 2.12E-05 4.59E-06 1.41 E-05 1.15E-06 5.98E-06 6.1 OE-07 2.48E-06 6.26E-05 1.84E-05 5.07E-05 1.10E-07 9.22E- 11 1.18E-08 4.65E-1 1 2.53E-11 0.00E+00 0.00E+00 4.18E-09 7.67E-10 1.72E-07 3.04E-09 1.01E-11 5.99E-09 0.OOE+00 5.21E-10 lung 0.OOE+00 3.38E-06 2.18E-06 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 2.39E-05 2.90E-06 1.97E-05 1.28E-08 6.74E-11 2.34E-08 3.43E-1 1 1.99E- 11 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 gi-Ili 5.45E-05 7.80E-05 1.93E-05 1.12E-04 1.13E-05 2.41 E-05 1.22E-05 6.12E-05 2.45E-07 9.39E-05 2.29E-09 7.OOE-05 2.29E-06 1.62E-06 3.18E-07 2.58E-06 5.1 OE-09 1.74E-06 2.45E-06 2.72E-06 2.12E-06 6.76E-1 1 1.24E-06 4.38E-05 1.43E-13 9.18E-20 9.82E-05 2.42E-06 2.54E-05 5.14E-05 1.75E-04 4.31 E-05 4.74E-14 3.68E-05 3.22E-05 2.67E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-12.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 57 Page 92 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 5 of 8)CHILD bone liver t body thyroid kidney lung gi-Ili H-3 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 C-14 1.21E-05 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 Na-24 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 P-32 8.25E-04 3.86E-05 3.18E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.28E-05 Cr-51 O.OOE+00 O.OOE+00 8.90E-09 4.94E-09 1.35E-09 9.02E-09 4.72E-07 Mn-54 O.OOE+00 1.07E-05 2.85E-06 O.OOE+00 3.OOE-06 O.OOE+00 8.98E-06 Mn-56 O.OOE+00 3.34E-07 7.54E-08 O.OOE+00 4.04E-07 O.OOE+00 4.84E-05 Fe-55 1.15E-05 6.1OE-06 1.89E-06 O.OOE+00 O.OOE+00 3.45E-06 1.13E-06 Fe-59 1.65E-05 2.67E-05 1.33E-05 O.OOE+00 O.OOE+00 7.74E-06 2.78E-05 Co-57 O.OOE+00 4.93E-07 9.98E-07 O.OOE+00 O.OOE+00 O.OOE+00 4.04E-06 Co-58 O.OOE+00 1.80E-06 5.51 E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.05E-05 Co-60 O.OOE+00 5.29E-06 1.56E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.93E-05 Ni-63 5.38E-04 2.88E-05 1.83E-05 O.OOE+00 O.OOE+00 O.OOE+00 1.94E-06 Ni-65 2.22E-06 2.09E-07 1.22E-07 O.OOE+00 O.OOE+00 O.OOE+00 2.56E-05 Cu-64 O.OOE+00 2.45E-07 1.48E-07 O.OOE+00 5.92E-07 O.OOE+00 1.15E-05 Zn-65 1.37E-05 3.65E-05 2.27E-05 O.OOE+00 2.30E-05 O.OOE+00 6.41E-06 Zn-69 4.38E-08 6.33E-08 5.85E-09 O.OOE+00 3.84E-08 0.OOE+00 3.99E-06 Zn-69m 7.1OE-07 1.21E-06 1.43E-07 O.OOE+00 7.03E-07 O.OOE+00 3.94E-05 Br-82 O.OOE+00 O.OOE+00 7.55E-06 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 1.71E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 1.98E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.OOE+00 O.OOE+00 9.12E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 O.OOE+00 6.70E-05 4.12E-05 O.OOE+00 O.OOE+00 O.OOE+00 4.31E-06 Rb-88 O.OOE+00 1.90E-07 1.32E-07 Q.OOE+00 O.OOE+00 O.OOE+00 9.32E-09 Rb-89 O.OOE+00 1.17E-07 1.04E-07 O.OOE+00 O.OOE+00 O.OOE+00 1.02E-09 Sr-89 1.32E-03 O.OOE+00 3.77E-05 O.OOE+00 O.OOE+00 Q.OOE+00 5.11E-05 Sr-90 1.70E-02 O.OOE+00 4.31E-03 O.OOE+00 O.OOE+00 O.OOE+00 2.29E-04 Sr-91 2.40E-05 O.OOE+00 9.06E-07 O.OOE+00 O.OOE+00 O.OOE+00 5.30E-05 Sr-92 9.03E-06 O.OOE+00 3.62E-07 O.OOE+00 O.OOE+00 O.OOE+00 1.71E-04 Y-90 4.11E-08 O.OOE+00 1.10E-09 O.OOE+00 O.OOE+00 O.OOE+00 1.17E-04 Y-91m 3.82E-10 O.OOE+00 1.39E-11 O.OOE+00 O.OOE+00 O.OOE+00 7.48E-07 Y-91 6.02E-07 O.OOE+00 1.61E-08 O.OOE+00 O.OOE+00 O.OOE+00 8.02E-05 Y-92 3.60E-09 O.OOE+00 1.03E-10 O.OOE+00 O.OOE+00 O.OOE+00 1.04E-04 Y-93 1.14E-08 O.OOE+00 3.13E-10 O.OOE+00 O.OOE+00 O.OOE+00 1.70E-04 Zr-95 1.16E-07 2.55E-08 2.27E-08 O.OOE+00 3.65E-08 O.OOE+00 2.66E-05 Zr-97 6.99E-09 1.01E-09 5.96E-10 O.OOE+00 1.45E-09 O.OOE+00 1.53E-04 Nb-95 2.25E-08 8.76E-09 6.26E-09 O.OOE+00 8.23E-09 O.OOE+00 1.62E-05 Nb-97 2.17E-10 3.92E-11 1.83E-11 O.OOE+00 4.35E-11 O.OOE+00 1.21E-05 Mo-99 O.OOE+00 1.33E-05 3.29E-06 O.OOE+00 2.84E-05 O.OOE+00 1.10E-05 Tc-99m 9.23E-10 1.81E-09 3.OOE-08 O.OOE+00 2.63E-08 9.19E-10 1.03E-06 Tc-101 1.07E-09 1.12E-09 1.42E-08 O.OOE+00 1.91E-08 5.92E-10 3.56E-09 Ru-103 7.31E-07 O.OOE+00 2.81E-07 O.OOE+00 1.84E-06 O.OOE+00 1.89E-05 Ru-105 6.45E-08 O.OOE+00 2.34E-08 O.OOE+00 5.67E-07 O.OOE+00 4.21E-05 Ru-106 1.17E-05 O.OOE+00 1.46E-06 O.OOE+00 1.58E-05 O.OOE+00 1.82E-04 SQN ODCM Revision 57 Page 93 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 6 of 8)CHILD Ag-110m Sb-1 24 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 5.39E-07 1.11E-05 7.16E-06 3.55E-05 1.14E-05 2.89E-05 4.71 E-07 4.87E-05 1.34E-07 7.20E-06 8.30E-08 1.01E-05 2.92E-06 1.72E-05 8.OOE-07 5.92E-06 4.19E-07 1.75E-06 2.34E-04 2.35E-05 3.27E-04 2.28E-07 4.14E-07 8.31 E-05 2.00E-07 8.74E-08 1.01 E-08 5.24E-1 0 3.97E-08 6.99E-09 2.08E-06 3.93E-08 1.29E-10 2.79E-08 4.29E-07 5.25E-09 liver 3.64E-07 1.44E-07 5.52E-08 5.35E-07 3.09E-06 7.78E-06 1.27E-07 1.36E-05 3.74E-08 2.49E-06 2.53E-08 4.47E-06 5.90E-06 1.73E-05 1.47E-06 7.32E-06 7.78E-07 3.15E-06 3.84E-04 6.46E-05 3.13E-04 3.17E-07 2.21 E-1 0 7.28E-08 1.12E-10 6.29E- 11 3.53E-09 1.67E-10 1.98E-08 3.79E-06 6.52E-07 1.18E-08 3.99E-1 1 2.26E-08 2.54E-07 3.77E-1 0 t body 2.91 E-07 3.89E-06 1.50E-06 1.59E-06 1.52E-06 3.43E-06 1.01 E-07 7.56E-06 3.18E-08 2.65E-06 2.47E-08 5.40E-06 3.04E-06 9.83E-06 6.76E-07 2.77E-06 3.58E-07 1.49E-06 8.1 OE-05 4.18E-05 4.62E-05 2.01 E-07 1.20E-08 4.85E-06 6.51 E-09 4.88E-09 1.19E-09 5.23E-1 1 2.94E-09 5.49E-10 1.11E-07 1.95E-09 6.49E-12 1.75E-09 1.14E-07 2.65E-10 thyroid 0.OOE+00 2.45E-08 6.63E-09 5.55E-07 3.20E-06 6.91 E-06 3.26E-07 1.57E-05 9.56E-08 5.12E-06 6.35E-08 6.51 E-06 6.50E-04 5.72E-03 6.82E-05 1.36E-03 1.79E-05 2.79E-04 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 6.78E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 8.24E-05 1.34E-06 1.43E-04 3.92E-07 2.41 E-05 2.51 E-07 4.15E-05 8.82E-06 2.84E-05 2.25E-06 1.22E-05 1.19E-06 4.83E-06 1.19E-04 3.44E-05 1.02E-04 2.23E-07 1.93E-10 2.37E-08 9.69E-1 1 5.09E-1 1 0.OOE+00 0.OOE+00 8.68E-09 1.59E-09 3.61 E-07 6.39E-09 2.11E-11 1.24E-08 0.OOE+00 1.09E-09 lung 0.OOE+00 6.16E-06 3.99E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 4.27E-05 5.13E-06 3.67E-05 2.40E-08 1.30E-10 4.34E-08 6.58E-10 3.70E-1 1 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 4.33E-05 6.94E-05 1.71 E-05 1.10E-05 1.10E-05 2.34E-05 1.84E-05 5.94E-05 8.34E-06 1.01E-04 4.36E-07 4.50E-05 2.76E-06 1.54E-06 1.73E-06 2.95E-06 5.16E-07 2.40E-06 2.07E-06 2.27E-06 1.96E-06 1.46E-07 2.39E-05 4.21 E-05 1.14E-07 1.14E-09 9.84E-05 3.31 E-05 2.47E-05 5.55E-05 1.70E-04 4.24E-05 8.59E-08 3.58E-05 3.57E-05 2.79E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-13.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 57 Page 94 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 7 of 8)INFANT bone liver t body thyroid kidney lung gi-Ili H-3 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 C-14 2.37E-05 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 Na-24 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 P-32 1.70E-03 1.OOE-04 6.59E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.30E-05 Cr-51 O.OOE+00 O.OOE+00 1.41E-08 9.20E-09 2.01E-09 1.79E-08 4.11E-07 Mn-54 O.OOE+00 1.99E-05 4.51E-06 O.OOE+00 4.41E-06 O.OOE+00 7.31E-06 Mn-56 O.OOE+00 8.18E-07 1.41E-07 O.OOE+00 7.03E-07 O.OOE+00 7.43E-05 Fe-55 1.39E-05 8.98E-06 2.40E-06 O.OOE+00 O.OOE+00 4.39E-06 1.14E-06 Fe-59 3.08E-05 5.38E-05 2.12E-05 O.OOE+00 O.OOE+00 1.59E-05 2.57E-05 Co-57 O.OOE+00 1.15E-06 1.87E-06 O.OOE+00 O.OOE+00 O.OOE+00 3.92E-06 Co-58 O.OOE+00 3.60E-06 8.98E-06 O.OOE+00 O.OOE+00 O.OOE+00 8.97E-06 Co-60 O.OOE+00 1.08E-05 2.55E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.57E-05 Ni-63 6.34E-04 3.92E-05 2.20E-05 0.OOE+00 O.OOE+00 O.OOE+00 1.95E-06 Ni-65 4.70E-06 5.32E-07 2.42E-07 O.OOE+00 O.OOE+00 O.OOE+00 4.05E-05 Cu-64 O.OOE+00 6.09E-07 2.82E-07 O.OOE+00 1.03E-06 O.OOE+00 1.25E-05 Zn-65 1.84E-05 6.31E-05 2.91E-05 O.OOE+00 3.06E-05 O.OOE+00 5.33E-05 Zn-69 9.33E-08 1.68E-07 1.25E-08 O.OOE+00 6.98E-08 O.OOE+00 1.37E-05 Zn-69m 1.50E-06 3.06E-06 2.79E-07 O.OOE+00 1.24E-06 O.OOE+00 4.24E-05 Br-82 O.OOE+00 O.OOE+00 1.27E-05 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 3.63E-07 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 3.82E-07 Q.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.OOE+00 O.OOE+00 1.94E-08 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 O.OOE+00 1.70E-04 8.40E-05 O.OOE+00 O.OOE+00 O.OOE+00 4.35E-06 Rb-88 O.OOE+00 4.98E-07 2.73E-07 O.OOE+00 O.OOE+00 O.OOE+00 4.85E-07 Rb-89 O.OOE+00 2.86E-07 1.97E-07 O.OOE+00 O.OOE+00 O.OOE+00 9.74E-08 Sr-89 2.51E-03 O.OOE+00 7.20E-05 O.OOE+00 O.OOE+00 O.OOE+00 5.16E-05 Sr-90 1.85E-02 O.OOE+00 4.71E-03 O.OOE+00 O.OOE+00 O.OOE+00 2.31E-04 Sr-91 5.OOE-05 O.OOE+00 1.81E-06 O.OOE+00 O.OOE+00 O.OOE+00 5.92E-05 Sr-92 1.92E-05 O.OOE+00 7.13E-07 O.OOE+00 O.OE+00 O.OOE+00 2.07E-04 Y-90 8.69E-08 O.OOE+00 2.33E-09 O.OOE+00 O.OOE+00 O.OE+00 1.20E-04 Y-91m 8.10E-10 O.OOE+00 2.76E-11 O.OOE+00 O.OOE+00 O.OOE+00 2.70E-06 Y-91 1.13E-06 O.OOE+00 3.01E-08 O.OE+00 O.OOE+00 O.OOE+00 8.1OE-05 Y-92 7.65E-09 O.OOE+00 2.15E-10 O.OOE+00 O.OOE+00 O.00E+00 1.46E-04 Y-93 2.43E-08 O.OOE+00 6.62E-10 O.OOE+00 O.OOE+00 O.OOE+00 1.92E-04 Zr-95 2.06E-07 5.02E-08 3.56E-08 O.OOE+00 5.41E-08 O.OOE+00 2.50E-05 Zr-97 1.48E-08 2.54E-09 1.16E-09 O.OOE+00 2.56E-09 O.OOE+00 1.62E-04 Nb-95 4.20E-08 1.73E-08 1.OOE-08 O.OOE+00 1.24E-08 O.OOE+00 1.46E-05 Nb-97 4.59E-10 9.79E-11 3.53E-11 O.OOE+00 7.65E-11 O.QOE+00 3.09E-05 Mo-99 O.OOE+00 3.40E-05 6.63E-06 O.OOE+00 5.08E-05 O.OOE+00 1.12E-05 Tc-99m 1.92E-09 3.96E-09 5.1OE-08 O.OOE+00 4.26E-08 2.07E-09 1.15E-06 Tc-101 2.27E-09 2.86E-09 2.83E-08 O.OOE+00 3.40E-08 1.56E-09 4.86E-07 Ru-103 1.48E-06 O.OOE+00 4.95E-07 O.OOE+00 3.08E-06 O.OOE+00 1.80E-05 Ru-105 1.36E-07 O.OOE+00 4.58E-08 O.OOE+00 1.OOE-06 O.OOE+00 5.41E-05 Ru-106 2.41E-05 O.OOE+00 3.01E-06 O.OOE+00 2.85E-05 O.OOE+00 1.83E-04 SQN ODCM Revision 57 Page 95 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 8 of 8)INFANT Ag-110in Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 9.96E-07 2.14E-05 1.23E-05 7.41 E-05 2.33E-05 5.85E-05 1.OOE-06 1.OOE-04 2.84E-07 1.52E-05 1.76E-07 2.08E-05 6.OOE-06 3.59E-05 1.66E-06 1.25E-05 8.69E-07 3.64E-06 3.77E-04 4.59E-05 5.22E-04 4.81 E-07 8.81 E-07 1.71 E-04 4.25E-07 1.84E-07 2.11 E-08 1.10E-09 7.87E-08 1.48E-08 2.98E-06 8.13E-08 2.74E-10 5.53E-08 9.03E-07 1.11E-08 liver 7.27E-07 3.15E-07 1.19E-07 1.38E-06 7.79E-06 1.94E-05 3.35E-07 3.43E-05 9.79E-08 6.12E-06 6.50E-08 1.03E-05 1.32E-05 4.23E-05 3.37E-06 1.82E-05 1.78E-06 7.24E-06 7.03E-04 1.35E-04 6.11 E-04 7.82E-07 5.84E-10 1.71 E-07 2.91 E-10 1.53E-10 8.32E-09 4.04E-1 0 4.80E-08 9.82E-06 1.22E-06 3.04E-08 1.06E-10 5.68E-08 6.28E-07 9.93E-10 t body 4.81 E-07 6.63E-06 2.53E-06 3.29E-06 3.15E-06 7.08E-06 2.15E-07 1.54E-05 6.63E-08 5.05E-06 4.94E-08 9.61 E-06 5.30E-06 1.86E-05 1.20E-06 5.33E-06 6.33E-07 2.64E-06 7.1OE-05 5.04E-05 4.33E-05 3.79E-07 2.55E-08 8.81 E-06 1.34E-08 9.06E-09 2.14E-09 9.67E-1 1 5.65E-09 1.12E-09 1.67E-07 4.03E-09 1.38E- 11 3.48E-09 2.17E-07 5.61 E-10 thyroid 0.OOE+00 5.68E-08 1.54E-08 1.36E-06 7.84E-06 1.69E-05 8.14E-07 3.84E-05 2.38E-07 1.24E-05 1.57E-07 1.52E-05 1.48E-03 1.39E-02 1.58E-04 3.31 E-03 4.15E-05 6.49E-04 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 1.04E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.44E-04 2.44E-06 2.50E-04 7.07E-07 4.21 E-05 4.50E-07 6.44E-05 1.45E-05 4.94E-05 3.76E-06 2.14E-05 1.99E-06 8.07E-06 1.81E-04 5.38E-05 1.64E-04 3.90E-07 3.51E-10 4.06E-08 1.75E-10 8.81 E-11 0.OOE+00 0.OOE+00 1.48E-08 2.86E-09 4.93E-07 1.13E-08 3.84E-11 2.19E-08 0.OOE+00 1.98E-09 lung 0.OOE+00 1.34E-05 7.72E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 7.42E-05 1.10E-05 6.64E-05 6.09E-08 3.54E-10 1.05E-07 1.77E-10 9.26E-1 1 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 3.77E-05 6.60E-05 1.64E-05 1.11E-04 1.11E-05 2.36E-05 2.1OE-05 5.97E-05 2.27E-05 1.03E-04 7.11E-06 3.81 E-05 2.83E-06 1.51 E-06 2.73E-06 3.08E-06 1.84E-06 2.62E-06 1.91 E-06 2.05E-06 1.91 E-06 1.25E-06 5.58E-05 4.20E-05 5.19E-06 7.59E-07 9.77E-05 6.86E-05 2.48E-05 5.73E-05 1.71E-04 4.29E-05 4.93E-06 3.60E-05 3.69E-05 2.87E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-14.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 57 Page 96 of 179 Table 6.5 BIOACCUMULATION FACTORS FOR FRESHWATER FISH (pCi/kg per pCi/L)H-3 C-14 Na-24 P-32 Cr-51 Mn-54 Mn-56 Fe-55 Fe-59 Co-57 Co-58 Co-60 Ni-63 Ni-65 Cu-64 Zn-65 Zn-69 Zn-69m Br-82 Br-83 Br-84 Br-85 Rb-86 Rb-88 Rb-89 Sr-89 Sr-90 Sr-91 Sr-92 Y-90 9.OE-01 4.6E+03 1.OE+02 1.OE+05 2.OE+02 4.OE+02 4.OE+02 1.OE+02 1.OE+02 5.OE+01 5.OE+01 5.OE+01 1.OE+02 1.OE+02 5.OE+01 2.0E+03 2.OE+03 2.OE+03 4.2E+02 4.2E+02 4.2E+02 4.2E+02 2.OE+03 2.OE+03 2.OE+03 5.6E+01 5.6E+01 5.6E+01 5.6E+01 2.5E+01 Y-91 m Y-91 Y-92 Y-93 Zr-95 Zr-97 Nb-95 Nb-97 Mo-99 Tc-99m Tc-101 Ru-103 Ru-1 05 Ru-1 06 Ag-110m Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-132 1-130 1-131 1-132 1-133 2.5E+01 2.5E+01 2.5E+01 2.5E+01 3.3E+00 3.3E+00 3.0E+04 3.OE+04 1.OE+01 1.5E+01 1.5E+01 1.OE+01 1.OE+01 1.OE+01 2.31 E+00 1.OE+00 1.OE+00 3.OE+03 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+01 4.OE+01 4.0E+01 4.OE+01 1-134 1-135 Cs-134 Cs-1 36 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-144 Ce-141 Ce-143 Ce-144 Pr-144 Pr-143 Nd-147 W-187 Np-239 4.OE+01 4.OE+01 1.9E+03 1.9E+03 1.9E+03 1.9E+03 4.OE+00 4.OE+00 4.OE+00 4.OE+00 2.5E+01 2.5E+01 1.OE+00 1.OE+00 1.OE+00 2.5E+01 2.5E+01 2.5E+01 1.2E+03 1.OE+01
REFERENCES:
Bioaccumulation factors for Ag-11 Oin, Sb-124, Sb-125 and Sn-125 are from ORNL-4992, "A Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment," March 1976, Table 4.12A.Bioaccumulation factors for Iodine, Cesium, and Strontium nuclides are from NUREG/CR-1004, Table 3.2.4.All other nuclides' bioaccumulation factors are from Regulatory Guide 1.109, Table A-I.
SQN ODCM Revision 57 Page 97 of 179 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/m 2)(Page 1 of 2)Nuclide Total Body Skin H-3 0.0 0.0 C-14 0.0 0.0 Na-24 2.50E-08 2.90E-08 P-32 0.0 0.0 Cr-51 2.20E-10 2.60E-10 Mn-54 5.80E-09 6.80E-09 Mn-56 1.10E-08 1.30E-08 Fe-55 0.0 0.0 Fe-59 8.OOE-09 9.40E-09 Co-57 1.77E-09 2.21E-09 Co-58 7.OOE-09 8.20E-09 Co-60 1.70E-08 2.OOE-08 Ni-63 0.0 0.0 Ni-65 3.70E-09 4.30E-09 Cu-64 1.50E-09 1.70E-09 Zn-65 4.OOE-09 4.60E-09 Zn-69 0.0 0.0 Zn-69m 5.50E-09 6.59E-09 Br-82 3.18E-08 3.90E-08 Br-83 6.40E-11 9.30E-11 Br-84 1.20E-08 1.40E-08 Br-85 0.0 0.0 Rb-86 6.30E-10 7.20E-10 Rb-88 3.50E-09 4.OOE-09 Rb-89 1.50E-08 1.80E-08 Sr-89 5.60E-13 6.50E-13 Sr-91 7.1OE-09 8.30E-09 Sr-92 9.OOE-09 1.OOE-08 Y-90 2.20E-12 2.60E-12 Y-91 m 3.80E-09 4.40E-09 Y-91 2.40E-11 2.70E-11 Y-92 1.60E-09 1.90E-09 Y-93 5.70E-10 7.80E-10 Zr-95 5.OOE-09 5.80E-09 Zr-97 5.50E-09 6.40E-09 Nb-95 5.1OE-09 6.OOE-09 Nb-97 8.11E-09 1.OOE-08 Mo-99 1.90E-09 2.20E-09 Tc-99m 9.60E-10 1.10E-09 Tc-101 2.70E-09 3.OOE-09 Ru-1 03 3.60E-09 4.20E-09 Ru-105 4.50E-09 5.1OE-09 Ru-106 1.50E-09 1.80E-09 SQN ODCM Revision 57 Page 98 of 179 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/m 2)(Page 2 of 2)Nuclide Ag-110m Sb-124 Sb-125 Sn-1 25 Te-125m Te-127m Te-127 Te-129m Te-129 Te-1 31 m Te-1 31 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 Total Body 1.80E-08 2.17E-08 5.48E-09 3.58E-09 3.50E-1 1 1.10E-12 1.00E- 11 7.70E-10 7.10E-10 8.40E-09 2.20E-09 1.70E-09 1.40E-08 2.80E-09 1.70E-08 3.70E-09 1.60E-08 1.20E-08 1.20E-08 1.50E-08 4.20E-09 2.1 OE-08 2.40E-09 2.1 OE-09 4.30E-09 7.90E-09 1.50E-08 1.50E-08 5.50E-10 2.20E-09 3.20E-10 0.0 2.OOE-1 0 1.OOE-09 3.1 OE-09 9.50E-1 0 Skin 2.1 OE-08 2.57E-08 6.80E-09 4.51 E-09 4.80E-1 1 1.30E-12 1.10E-11 9.OOE-1 0 8.40E-1 0 9.90E-09 2.60E-06 2.OOE-09 1.70E-08 3.40E-09 2.OOE-08 4.50E-09 1.90E-08 1.40E-08 1.40E-08 1.70E-08 4.90E-09 2.40E-08 2.70E-09 2.40E-09 4.90E-09 9.OOE-09 1.70E-08 1.80E-08 6.20E-1 0 2.50E-09 3.70E-10 0.0 2.30E-10 1.20E-09 3.60E-09 1.10E-09
REFERENCES:
Regulatory Guide 1.109, Table E-6.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from Dose-Rate Conversion Factors for External Exposure to Photon and Electron Radiation from Radionuclides Occurring in Routine Releases from Nuclear Fuel Cycle Facilities, D. C. Kocher, Health Physics Volume 38, April 1980.
SQN ODCM Revision 57 Page 99 of 179 Figure 6.1 LIQUID EFFLUENT RELEASE POINTS"A" Train 0-RE-90-133,140"B" Train O-RE-90-134,141
.1.
SQN ODCM Revision 57 Page 100 of 179 Figure 6.2 LIQUID RADWASTE SYSTEM Laundry and Hot Shower Tanks A& B 2 20 gpm (600 gal)Monitor Tank (22000 gal)125 gpm e routine 0-RM-90-122 125 gpm TO COOLING TOWER BLOWDOWN SQN ODCM Revision 57 Page 101 of 179 SECTION 7.0 GASEOUS EFFLUENTS SQN ODCM Revision 57 Page 102 of 179 SECTION 7.0 GASEOUS EFFLUENTS RELEASE POINTS DESCRIPTION There are six major exhaust pathways at Sequoyah Nuclear Plant that are monitored for airborne effluents.
These are: a Condenser Vacuum Exhaust for each unit, a Service Building Exhaust, an Auxiliary Building Exhaust and a Shield Building Exhaust for each unit. Figure 7.1 provides an outline of the airborne effluent release and discharge points with associated radiation monitor identifications.
All gaseous effluents at Sequoyah are considered ground level for the purpose of evaluating offsite dose and setpoint determination.
Condenser Vacuum Exhaust The Condenser Vacuum Exhausts (CVEs) are located in the turbine building.
The CVE exhaust at a maximum design flow rate of 45 cubic feet per minute. They are monitored for routine releases by radiation monitors 1,2-RM-90-99,119.
Service Buildinq Vent Various low-level sources exhaust to the Service Building Vent. This exhausts at a total design flow of approximately 11,200 cfm. Only a portion of this total flow (9,000 cfm) originating from the Titration Room, the Chemistry Lab, and the RCA Access Control Area is monitored by radiation monitor 0-RM-90-132.
Auxiliary Buildinq Exhaust (see Figure 7.2 for detail)The annulus vacuum priming system exhausts through the containment vent to the Auxiliary Building.
The Auxiliary Building Exhaust consists of the Auxiliary Building General Exhaust System and the Fuel Handling Exhaust and they cumulatively exhaust at a maximum design flow of 228,000 cfm. The exhaust is monitored by radiation monitor 0-RM-90-101.
Shield Buildinq Vent (see Figure 7.2 for detail)The Auxiliary Building Gas Treatment System (ABGTS) draws from the Auxiliary Building and exhausts through the Shield Building Vent. There are nine Waste Gas Decay Tanks (WGDTs) that empty into the waste gas header. Either ABGTS or the Emergency Gas Treatment System (EGTS) is run to release a WGDT. Each WGDT has a design capacity of 600 cubic feet at STP and a design release rate of 22.5 cfm. Both the Containment Purge and the Incore Instrument Room Purge from each unit tie into the waste gas header. The Containment Purge exhausts at a maximum of 28,000 cfm and is monitored by radiation monitors 1,2-RM 130,131. If the Incore Instrument Room Purge is operating exclusively, it exhausts at 800 cfm. Under emergency conditions, and sometimes during normal operation, the EGTS is used to draw a vacuum in the annulus and exhaust to the Shield Building Vent. Auxiliary Building Isolation starts both the ABGTS and EGTS.The common header exhausts to the Shield Building Exhaust. There is one exhaust for each unit. This exhausts at a maximum design flow of 28,000 cfm and is monitored by radiation monitors 1,2-RM-90-400.
SQN ODCM Revision 57 Page 103 of 179 7.1 INSTRUMENT SETPOINTS Airborne effluent monitor setpoints are determined to ensure that the dose rate at the UNRESTRICTED AREA BOUNDARY does not exceed the dose rate limits given in ODCM Control 1.2.2.1 and to identify unexpected releases.7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-131, O-RM-90-118) 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-131)
These monitors are set at a cpm value equal to the Technical Specification Limit of <8.5xl 0-3 pCi/cc as Xe-133 (Technical Specification 3.3.2.1(U1), 3.3.2(U2), Table 3.3-4, and 3.3.3.1, Table 3.3-6). The radiation monitor vacuum setpoint is set at 9 +/- 1 in. of vacuum, T/S Limit = 8.5E-03 pCi/cc, monitor efficiency for Xe-1 33 = 9.08E+ 05 CPM/VCi/cc, Vacuum Correction
= 0.75; therefore the maximum setpoint = (8.5E-03)
(9.08E+05)(0.75)
=5800 CPM.7.1.1.2 Waste Gas Decay Tank Effluent Monitor (0-RM-90-118)
The setpoint for the Waste Gas Decay Tank effluent monitor is routinely set at a Default Setpoint, SDEF. This setpoint uses the site release rate limit and considers the dilution effect of ABGTS during the release process.SDEF for 0-RM-90-118 is 1.88E3 CPM based on the following:
SDEF = DRLIM
- 3.28E+04
- 5.525E-03 2.94E+02
- X/Q
- 472
- RR Where: DRUM is the site dose rate limit = 500mRem/y RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 3.28E+04 cpm/uCi/cc is the radiation monitor's efficiency 5.525E-03 is the max. Dilution flow factor provided by ABGTS (9000cfm)X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1 2.94E+02 = Dose Factor for Xe-133 mRem/y/uCi/m 3 , Table 7.3 472 = Conversion Factor, (28317 cc/ft 3 ,min/60 s)A Maximum Setpoint, Smax can also be calculated for 0-RM-90-118 based on using the radiation monitor as the primary monitor for the release path.Smax for 0-RM-90-118 is 31,879 CPM based on the following:
SMAX = A* DRUM
- 3.28E+04 2.94E+02
- X/Q
- 472 -RR Where: A = the Dose Rate allocation factor for the shield bldg.,0.0955 DRUM is the site dose rate limit = 500mRem/y 3.28E+04 cpm/uCi/cc is the radiation monitor's efficiency for Xe-133 2.94E+02 = Dose Factor for Xe-1 33 mRem/y/uCi/m 3 , Table 7.3 X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1 RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 472 = Conversion Factor, (28317 cc/ft 3_ min/60 s)
SQN ODCM Revision 57 Page 104 of 179 For each release from a waste gas decay tank, two setpoints are evaluated for the monitor: one based on the expected response of the monitor to the radioactivity in the effluent stream and a calculated expected monitor response setpoint.
The expected monitor response is calculated as described below in Equation 7.1. The expected monitor response setpoint is calculated as described below in Equation 7.1a. A comparison is made to verify the expected monitor response and expected monitor response setpoint is less than or equal to the Default Setpoint.
If the expected monitor response or expected monitor response setpoint is greater than Default Setpoint it may be temporarily increased but can not exceed the Maximum Setpoint.
The calculated setpoints ensures that the release will be stopped if it exceeds any dose rate limits.Expected Monitor Response, CPM RCpM = B+ I effiCi i (7.1)Where: RCPM = Expected Monitor Response,CPM B = monitor background, cpm.effi= efficiency factor for the monitor for nuclide i, cpm per pCi/cc.Ci = measured concentration of nuclide i, iCi/cc.Expected Monitor Response, uCi/s Ruci/s = B + 472Ci
- RR Where : Rucj/s = Expected Release Rate, uCi/s B = monitor background,.
uCi/s 472 = Conversion Factor, cc/ft3*m/s Ci = measured concentration of nuclide i, uCi/cc RR = Release Rate, ft 3/min Expected Monitor Response Setpoint, CPM or uCi/s (7.la)The expected monitor response setpoint Ser is calculated for the monitor for each release.Ser =X R where R = expected monitor response, CPM or uCi/s X = administrative factor designed to account for expected variations in monitor response and background The range of values is: 1.0 < X < 2.0 SQN ODCM Revision 57 Page 105 of 179 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, O-RM-90-101, O-RM-90-132, 1,2-RM-90-99,119)
A normal default setpoint, SDEF is utilized for each discharge point monitor as described below. When release permits are generated, the expected response and expected monitor response setpoint is calculated for the appropriate discharge monitor as described in Section 7.1.1.2. A comparison is made between the two setpoints.
If the expected monitor response or expected monitor response setpoint is greater than the default setpoint then the release parameters must be reevaluated.
Worse case conditions will require an evaluation of the allocation factors in section 7.1.1.2.Calculated Default Setpoint The calculated default setpoint, SDef in cpm (0-101,0-132, & 1,2-99,119), corresponding to the dose rate limit is determined using the following equation: SDEF A *.DRIM *.Et* 0.71 (7.2)DRR -472 -2.94E+02
- X/Q Where: A = dose rate allocation factor for the release point, dimensionless.
The dose rate allocation factors for release points are defined as follows based on design flowrates:
Auxiliary Building 0.7779 Shield Building (ea) 0.0955 Service Building 0.0307 Condenser Vacuum Exhaust (ea) 0.00015 0.71 = safety factor for the monitor, dimensionless.
Safety factors for these monitors includes 0.75 for the radiation monitor vacuum correction factor and 0.95 for Xe-1 33 primary isotope mix.DRuim = the dose rate limit, 500 mrem/year to the total body for noble gases.DRR = the design release rate for the release pathway or design approved flow rate.= DRTB for total body (as described in Section 7.2.3.1).472 = Conversion Factor, (28317 cc/ft 3.min/60 s).X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1.Eff = Radiation Monitor Efficiency for Xe-133, 0-101,0-132, 1,2-99,119
@ 2.27E+07 CPM/uCi/cc.
2.94E+02 = Dose Factor for Xe-1 33 mRem/y/uCi/m 3 ,Table 7.3.The calculated default setpoint, SDef in uCi/s (1,2-400), corresponding to the dose rate limit is determined using the following equation: SDEF = A *. DRLM 2.94E+02
- X/Q 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119)
This discharge point effluent monitor is set to ensure compliance with ODCM Control 1.2.2.1 and to identify the presence of primary to secondary leakage of radioactivity.
The default setpoint is determined by Equation 7.2 for Xe-1 33, and then taking a percentage of this value as the setpoint; or by defining the setpoint as a low value above the normal background.
Once a primary to secondary leak is identified, the setpoint on this monitor may be adjusted upward to enable it to be used to identify any further increases in the leak rate but will not be allowed to be set greater than the calculated default value without further evaluation of the allocation factors.
SQN ODCM Revision 57 Page 106 of 179 7.2 GASEOUS EFFLUENTS
-DOSE RATES 7.2.1 (Deleted)7.2.2 RELEASE SAMPLING Prior to each release (excluding an Incore Instrument Room Purge), a grab sample is taken and analyzed to determine the concentration, pCi/cc, of each noble gas nuclide. On at least a weekly basis, filters are analyzed to determine the amount of iodines and particulates released.
Composite samples are maintained (as required by Table 2.2-2) to determine the concentration of certain nuclides (Sr-89, Sr-90, and alpha emitters).
For those nuclides whose activities are determined from composite samples the concentrations for the previous composite period will be assumed as the concentration for the next period to perform the calculations in Sections 7.3, 7.4, and 7.5. The actual measured concentrations will be used for the dose calculations described in Section 7.6.7.2.3 NOBLE GAS DOSE RATES Dose rates are calculated for total body and skin due to submersion within a cloud of noble gases using a semi-infinite cloud model.7.2.3.1 Total Body Dose Rate The dose rate to the total body, DRTB in mrem/year, is calculated using the following equation: DRTB = (X/Q) F Yi Ci DFBi (7.3)where X/Q = relative concentration, s/m 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).F = flowrate of effluent stream, cc/s.Ci = concentration of noble gas nuclide i in effluent stream, jiCi/cc.DFBi = total body dose factor due to gamma radiation for noble gas nuclide i, mrem/y per piCi/m 3 (Table 7.3).
SQN ODCM Revision 57 Page 107 of 179 7.2.3.2 Skin Dose Rate The dose rate to the skin, DRS in mrem/year, is calculated using the following equation: DRs = (X/Q) F Xi Ci(DFSi + 1.11 DF'i) (7.4)where X/Q = relative concentration, s/m 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).F = flowrate of effluent stream, cc/s.Ci = concentration of noble gas nuclide i in effluent stream, pCi/cc.DFSi = skin dose factor due to beta radiation for noble gas nuclide i, mrem/y per PiCi/m 3 (Table 7.3).1.11 = the average ratio of tissue to air energy absorption coefficients, mrem/mrad.
DFYi = dose conversion factor for external gamma for noble gas nuclide i, mrad/y per pCi/m 3 (Table 7.3).
SQN ODCM Revision 57 Page 108 of 179 7.2.41-131,1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS -ORGAN DOSE RATE Organ dose rates due to 1-131, 1-133, Tritium and all radionuclides in particulate form with half-lives of greater than 8 days, DRorg in mrem/y, are calculated for all age groups (adult, teen, child, and infant) and all organs (bone, liver, total body, thyroid, kidney, lung, and GI Tract) using the following equation: DRorg= F [ CT(X/Q)[RIT+RCTP]
+ Yj Ci[(X/Q)Rli
+ (D/Q) [Rcpi + RGi]]] (7.5)where: F = flowrate of effluent stream, cc/s.C.T = concentration of tritium in effluent stream, p.Ci/cc.X/Q = relative concentration, s/m 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).RIT = inhalation dose factor for tritium, mrem/y per iiCi/m 3.Dose factor is calculated as described in Section 7.7.13.RCTP= Grass-cow-milk dose factor for tritium, mrem/y per ýtCi/m 3.Dose factor is calculated as described in Section 7.7.7.Ci = concentration of nuclide i in effluent stream, ptCi/cc.Rli = inhalation dose factor for each identified nuclide i, mrem/y per pCi/m 3.Dose factors are calculated as described in Section 7.7.13.D/Q = relative deposition, 1/m 2.Relative deposition is calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.3 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 1.40E-08 1/m 2 (from Table 7.2).Rcpi = Grass-cow-milk dose factor for each identified nuclide i, m 2-mrem/y per p.Ci/s. Dose factors are calculated as described in Section 7.7.1.RGi = ground plane dose factor for each identified nuclide i, m 2-mrem/y per ptCi/s. Dose factors are calculated as described in Section 7.7.14.The maximum organ dose rate is selected from among the dose rates calculated for all the organs and all age groups.
SQN ODCM Revision 57 Page 109 of 179 7.3 DOSE -NOBLE GASES Doses to be calculated are gamma and beta air doses due to exposure to an infinite cloud of noble gases.These doses will be calculated from the unrestricted area boundary locations with the highest X/Qs for each quarter from 1999-2008.
Dispersion factors are calculated using the methodology described in Section 7.8.2.No credit is taken for radioactive decay.7.3.1 Gamma dose to air The gamma air dose, Dy in mrad, is calculated for each release using the following equation: Dy = 1.9E-06 (X/Q)_IX Qi DFyi T (7.6)where: 1.9E-06= conversion factor, y/min.X/Q = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.14x10-6 s/m 3 (from Table 7.1).Qi = release rate for nuclide i, itCi/s.DFyi = dose conversion factor for external gamma for nuclide i (Table 7.3), mrad/y per liCi/m 3.T = duration of release, min.The gamma-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.7.3.2 Beta dose to air The beta air dose, D, in mrad, is calculated for each release using the following equation: D13 = 1.9E-06 (X/Q) Y~i Qi DFpj T (7.7)where: 1.9E-06= conversion factor, y/min.X/Q = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.14x10-6 s/M 3 (from Table 7.1).Qi = release rate for nuclide i, pCi/s.DFi = dose conversion factor for external beta for nuclide i, mrad/y per jiCi/m 3 (from Table 7.3).T = duration of release, min.The beta-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.
SQN ODCM Revision 57 Page 110 of 179 7.3.3 Cumulative Dose -Noble Gas Monthly, quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.2.For noble gases, cumulative doses are calculated for gamma and beta air doses. Doses due to each release are summed with the doses for all previous release in the quarter or year to obtain cumulative quarterly and annual doses.7.3.4 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.
SQN ODCM Revision 57 Page 111 of 179 7.4 DOSE DUE TO 1-131, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS 7.4.1 Organ dose Calculation Organ doses due to 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives of greater than 8 days are calculated for each release for the critical receptors.
Carbon-14 production and effluent source term is based on EPRI methodology provided in EPRI Report 1021106, Estimation of Carbon-14 in Nuclear Power Plant Gaseous Effluents, December 2010. The critical receptors are defined as the unrestricted area boundary in the sectors with the highest quarterly XIQ and D/Q for each quarter from 1999-2008.
The X/Q and D/Q are calculated using the methodology in Sections 7.8.2 and 7.8.3 using the historical 1999-2008 meteorological data (Table 7.2). Pathways considered to exist at this location are inhalation, ground plane exposure, grass-cow-milk ingestion, grass-cow-beef ingestion and fresh leafy and stored vegetable ingestion.
All age groups are considered (adult, teen, child and infant). Dose factors for these age groups and pathways are calculated as described in Section 7.7. For the ground exposure pathway, which has no age or organ specific dose factors, the total body dose will be added to the internal organ doses for all age groups. No credit is taken for radioactive decay.The general equation for the calculation of organ dose is: Dorg = 3.17E-08 T Ii P Rpi [ Wp Qi] (7.8)where: 3.17E-08 = conversion factor, y/s T = duration of release, s.Rpi = dose factor for pathway P for each identified nuclide i, m 2-mrem/y per 1 aCi/s for ground plane, grass-cow-milk, grass-cow-meat, and vegetation pathways, and mrem/y per 1 iCi/m 3 for inhalation, tritium ingestion and carbon-14 pathways.
Equations for calculating these dose factors are given in Section 7.7.Wp = dispersion factor for the location and pathway,= X/Q for the inhalation , tritium ingestion and carbon-14 pathways,= 6.94E-06 s/m 3.= D/Q for the food and ground plane pathways,= 1.30E-08 m-2 Qi = release rate for radionuclide i, ýtCi/s From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The organ doses for the critical age group will be used in the cumulative doses discussed in Section 7.4.2.
SQN ODCM Revision 57 Page 112 of 179 7.4.2 Cumulative Doses Quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.3.For maximum organ dose, cumulative quarterly and annual doses are maintained for each of the eight organs considered.
The cumulative dose is obtained by summing the doses for each organ of the critical age group (as calculated in Section 7.4.1) as determined for each release with the organ doses for all previous releases in the quarter or year to obtain the cumulative quarterly and annual doses. Thus, the cumulative organ doses will be conservative values, consisting of doses belonging to various age groups depending on the mix of radionuclides.
The highest of these cumulative organ doses is used for the comparison to the limits described in ODCM Control 1.2.2.3.7.4.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.
SQN ODCM Revision 57 Page 113 of 179 7.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.2.4, dose projections will be performed by averaging the two previous month's doses as determined in Section 7.3.3. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.The projected doses are compared to the limits of ODCM Control 1.2.2.4. The limits are 0.2 mrad per unit for gamma radiation, 0.4 mrad per unit for beta radiation, or 0.3 mrem per unit to any organ.D= a+b 2 where: D = the 31-day dose projection, mrad a = the cumulative gamma, beta, or organ dose for the previous month, mrad b = the cumulative gamma, beta, or organ dose for the present month, mrad If the projected doses exceed any of these limits, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY.7.5.1 GASEOUS RADWASTE TREATMENT SYSTEM DESCRIPTION The GASEOUS RADWASTE TREATMENT SYSTEM (GRTS) described below shall be maintained and operated to keep releases ALARA.A flow diagram for the GRTS is given in Figure 7.3. The system consists of two waste-gas compressor packages, nine gas decay tanks, and the associated piping, valves, and instrumentation.
Gaseous wastes are received from the following:
degassing of the reactor coolant and purging of the volume control tank prior to a cold shutdown, displacing of cover gases caused by liquid accumulation in the tanks connected to the vent header, and boron recycle process operation.
SQN ODCM Revision 57 Page 114 of 179 7.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated gaseous releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel.
All real pathways and receptor locations identified by the most recent land use survey are considered.
In addition, actual meteorological data representative of a ground level release for each corresponding calendar quarter will be used. For iodine releases, it is assumed that half the iodine released is in organic form. Organic iodine causes a dose only by inhalation.
For cow-milk and beef ingestion doses, the fraction of the time the animals are on stored feed (identified in the survey) is used in the calculation.
The highest organ dose for a real receptor is determined by summing the dose contribution from all identified pathways for each receptor including ground contamination, inhalation, vegetable ingestion (for identified garden locations), cow and/or goat milk ingestion (if a cow or goat is identified for the location), beef ingestion (the beef ingestion dose for the location of highest beef dose for all receptors will be considered the beef dose for all receptors).
7.6.1 NOBLE
GAS -GAMMA AIR DOSE Gamma air doses due to exposure to noble gases, D. in mrad, are calculated using the following equation: D: = Xim DFYi (7.9)where: Xim = concentration of nuclide i at location m, p.Ci/m 3.Air concentrations are calculated as described by Equation 7.14.DFYi = dose conversion factor for external gamma for nuclide i, mrad/y per PCi/m 3 (Table 7.3).7.6.2 NOBLE GAS -BETA AIR DOSE Beta air doses due to exposure to noble gases, D, in mrad, are calculated using the following equation: DP = Xim DFp 3 i (7.10)where: xim = concentration of nuclide i at location m, pCi/m 3.Air concentrations are calculated as described by Equation 7.14.DFpi = dose conversion factor for external beta for nuclide i, mrad/y per VCi/m 3 (Table 7.3).
SQN ODCM Revision 57 Page 115 of 179 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE Organ doses due to radioiodine, particulate, tritium, and Carbon-14 releases, Dorg in mrem, are calculated using the following equation: Dorg -3.17E -08 [E (D/Q E Rp, + D/Q RGi +x/QR, 1)Qi +1:(X/Q RPT )QT i P P+ E-- (X/Q R PC,4 )QC,4]P (7.11)where: 3.17E-08 = conversion factor, y/s.X/Q = Relative concentration for location under consideration, s/m 3.Relative concentrations are calculated as described by Equation 7.15.RpT = ingestion dose factor for pathway P for tritium, m 2-mrem/y per 1 iCi/s. Ingestion pathways available for consideration are the same as those listed above for Rpi. Equations for calculating ingestion dose factors for tritium are given in Sections 7.7.7 through 7.7.12.QT = adjusted release rate for tritium for location under consideration, piCi/s. Calculated in the same manner as Qi above.QC14 = adjusted release rate for Carbon-14 for location under consideration, jiCi/s.Rpi = ingestion dose factor for pathway P for each identified nuclide i (except tritium), m 2-mrem/y per pCi/s. Ingestion pathways available for consideration include: pasture grass-cow-milk ingestion stored feed-cow-milk ingestion pasture grass-goat-milk ingestion stored feed-goat-milk ingestion pasture grass-beef ingestion stored feed-beef ingestion fresh leafy vegetable ingestion stored vegetable ingestion Equations for calculating these ingestion dose factors are given in Sections 7.7.1 through 7.7.6.D/Q = Relative deposition for location under consideration, m-2.Relative deposition is calculated as described in Equation 7.16.RG = Dose factor for standing on contaminated ground, m 2-mrem/y per p.Ci/s. The equation for calculating the ground plane dose factor is given in Section 7.7.14.Rli = Inhalation dose factor, mrem/y per ptCi/m 3.The equation for calculating the inhalation dose factor is given in Section 7.7.13.Rpc1 4 = Ingestion dose factor for pathway P for carbon-14, mrem/y per pCi/s. Ingestion pathways available for consideration are the same for those listed above for Rpi. Equations for calculating ingestion dose factors for carbon-14 are given in Sections 7.7.13 through 7.7.18.Qi = adjusted release rate for nuclide i for location under consideration, jiCi/s. The initial release rate is adjusted to account for decay between the release point and the location, depending on the frequency of wind speeds applicable to that sector. Hence, the adjusted release rate is equal to the actual release rate decayed for an average travel time during the period.
SQN ODCM Revision 57 Page 116 of 179 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE (continued) 9 Qi =Qi0 Z_ fj exp(-Xi x/uj) (7.12)j=1 where Qi0 = initial average release rate for nuclide i over the period, VCi/s.fi = joint relative frequency of occurrence of winds in windspeed class j blowing toward this exposure point, expressed as a fraction.ki = radiological decay constant for nuclide i, s-1.x = downwind distance, meters.uj = midpoint value of wind speed class interval j, m/s.
SQN ODCM Revision 57 Page 117 of 179 7.6.4 POPULATION DOSES For determining population doses to the 50-mile population around the plant, each compass sector is broken down into elements.
These elements are defined in Table 7.4. For each of these sector elements, an average dose is calculated, and then multiplied by the population in that sector element. Dispersion factors are calculated for the midpoint of each sector element (see Table 7.4).For population doses resulting from ingestion, it is conservatively assumed that all food eaten by the average individual is grown locally.The general equation used for calculating the population dose in a given sector element is: Dosepop = Y RATIOp
- POPN
- AGE
- 0.001
- DOSEp (7.13)P where RATIOp = ratio of average to maximum dose for pathway P. (Average ingestion rates are obtained from Regulatory Guide 1.109, Table E-4.)= 0.5 for submersion and ground exposure pathways, a shielding/occupancy factor.= 1.0 for the inhalation pathway.= 0.515, 0.515, 0.5, and 0.355 for milk, for infant, child, teen and adult, respectively. (It is assumed that the ratio of average to maximum infant milk ingestion rates is the same as that for child.)= 1.0, 0.90, 0.91, 0.86 for beef ingestion, for infant, child, teen and adult, respectively.
= 1.0, 0.38, 0.38, 0.37 for vegetable ingestion, for infant, child, teen and adult, respectively. (It is assumed that the average individual eats no fresh leafy vegetables, only stored vegetables.)
POPN = the population of the sector element, persons (Table 7.5).AGE = fraction of the population belonging to each age group.= 0.015, 0.168, 0.153, 0.665 for infant, child, teen and adult, respectively (fractions taken from NUREG/CR-1004, Table 3.39).0.001 = conversion from mrem to rem.DOSEp = the dose for pathway P to the maximum individual at the location under consideration, mrem. For ingestion pathways, this dose is multiplied by an average decay correction to account for decay as the food is moved through the food distribution cycle. This average decay correction, ADC, is defined as follows: For milk and vegetables, ADC = exp(-Xit)where -1 Xi = decay constant for nuclide i, s t = distribution time for food product under consideration (values from Regulatory Guide 1.109, Table D-1).= 1.21 E+06 s (14 d) for vegetables.
= 3.46E+05 s (4 d) for milk.
SQN ODCM Revision 57 Page 118 of 179 7.6.4 POPULATION DOSES (continued) exp(-?Xit)
Xitcb For meat, ADC =1 -exp(-kitcb)
(7.14)where ki = decay constant for nuclide i, s.t = additional distribution time for meat, over and above the time for slaughter to consumption described in Section 7.7.3, 7 d.tcb = time to consume a whole beef, as described in Section 7.7.3.For beef ingestion, the additional factors in the calculation of ADC negate the integration of the dose term over the period during which a whole beef is consumed, for the calculation of population dose. In other words, this assumes that the maximum individual freezes and eats a whole beef, while the average individual buys smaller portions at a time.Population doses are summed over all sector elements to obtain a total population dose for the 50-mile population.
7.6.5 REPORTING
OF DOSES The calculated quarterly doses and calculated population doses described in this section are reported in the Annual Radiological Effluent Release Report as required by ODCM Administrative Control 5.2.7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED or RESTRICTED AREA BOUNDARY The Basis for ODCM Control 1.2.2.1 states that for members of the public who may at times be within the UNRESTRICTED or RESTRICTED AREA BOUNDARY, the occupancy factor of that member of the public will usually be sufficiently low to compensate for any increase in the atmospheric dispersion factor above that for the UNRESTRICTED AREA BOUNDARY.
This basis also states that examples of calculations for such members of the public will be given in the ODCM.The determination presented here assumes that the most exposed member of the public will be an adult TVA employee who works just outside the restricted area fence for the entire workyear (2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br />). Results from onsite dosimeter measurements from the years 1990-1992 indicate that the highest onsite external dose was 72.6 mrem. Using this value, subtracting an annual background value of 55 mrem/year, and multiplying by the ratio of the occupancy times, the highest external dose to a MEMBER OF THE PUBLIC inside the UNRESTRICTED AREA BOUNDARY is 4 mrem. Historical records show that the total dose contribution from effluent releases is normally less than 2 mrem. The combination of the measured direct dose (part of which is from effluent releases) and the calculated effluent dose will be below both the 10 CFR Part 20 limit of 100 mrem/year and the 40 CFR Part 190 limit of 25 mrem/year.
In addition to this analysis, the dose to this hypothetical member of the public will be determined on an annual basis (using the methodology above) to ensure that the actual dose to any individual is less than 100 mrem/year.
The results of this review will be included in the Annual Radiological Effluent Release Report pursuant to ODCM Administrative Control 5.2.
SQN ODCM Revision 57 Page 119 of 179 7.7 GASEOUS RELEASES -Dose Factors 7.7.1 PASTURE GRASS-COW/GOAT-MILK INGESTION DOSE FACTORS (m 2-mrem/y per gCi/s)Rcpi = 106DFLiaoUapFmiQfexp(-Xim)fp
+ Bi(1-exp(-Xit).}
(7.15)Yp ?1E P ki where: 106 = conversion factor, pCi/[tCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uap = milk ingestion rate for age group a, L/y.Fmi = transfer factor for nuclide i from animal's feed to milk, d/L(Table 6.2).Qf = animal's consumption rate, kg/d.k'i -= decay constant for nuclide i, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.fp = fraction of time animal spends on pasture, dimensionless.
r = fraction of activity retained on pasture grass, dimensionless.
?1E = the effective decay constant, due to radioactive decay and weathering, s-1, equal to 'i + Xw" X)w = weathering decay constant for leaf and plant surfaces, s-1.tep = time pasture is exposed to deposition, s.Yp = agricultural productivity by unit area of pasture grass, kg/m 2.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 120 of 179 7.7.2 STORED FEED-COW/GOAT-MILK INGESTION DOSE FACTORS (m 2-mrem/y per gCi/s)Rcsi = 106 DFLiaoUapFmiQf fsexp(-jitfm)
(1-exp(-t-sf)-)
{r(l-exp(-
t-Esf-l + Biv(1-exp(--itb.)-}
(7.16)tcsf ki Ysf kE P Xi where: 106 = conversion factor, pCi/pCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uap = milk ingestion rate for age group a, L/y.Fmi = transfer factor for nuclide i from animal's feed to milk, d/L (Table 6.2).Qf = animal's consumption rate, kg/d.fs = fraction of time animal spends on stored feed, dimensionless.
ki = decay constant for nuclide i, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.tcsf = time between harvest of stored feed and consumption by animal, s.r = fraction of activity retained on pasture grass, dimensionless.
XE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to ,i+k,.kw = weathering decay constant for leaf and plant surfaces, s-1 tesf = time stored feed is exposed to deposition, s.Ysf = agricultural productivity by unit area of stored feed, kg/m2.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 121 of 179 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS (m 2-mrem/y per pjCi/s)RmPi = 106 DFLiaoUamFFiQF (1-exp(-ijt cb). exp(-Xits) fp {r(1-exp(-kEte_
+ Bv(1-exp(-Xtb_)}
(7.17)?Xi tcb Yp kE P kj where: 106 = conversion factor, pCi/ICi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uam = beef ingestion rate for age group a, kg/y.FR = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.?,j = decay constant for nuclide i, s-1 (Table 6.2).tcb = time for receptor to consume a whole beef, s.ts = transport time from slaughter to consumer, s.fp = fraction of time cow spends on pasture, dimensionless.
r = fraction of activity retained on pasture grass, dimensionless.
kE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to ,i+?,w?w = weathering decay constant for leaf and plant surfaces, s-1 tep = time pasture is exposed to deposition, s.Yp P = agricultural productivity by unit area of pasture grass, kg/m2.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 122 of 179 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS (m 2-mrem/y per pCi/s)RMsi = 106 DFLiao Uam FFi QF (1-exp(-Xit-bj exp(-Xits) fs (1-exp(-Xit-cf)
{r(1-exp(-XEt-esfl
+Xi tcb ki tcsf Ysf XE BEiv(1 -exDp(-XjtbFj}
(7.18)P Xi where: 106 = conversion factor, pCi/iCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uam = beef ingestion rate for age group a, kg/y.FFi = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Xi = decay constant for nuclide i, s-1 (Table 6.2).tcb = time for receptor to consume a whole beef, s.ts = transport time from slaughter to consumer, s.f, = fraction of time cow spends on stored feed, dimensionless.
tcsf = time between harvest of stored feed and consumption by cow, s.r = fraction of activity retained on pasture grass, dimensionless.
tesf = time stored feed is exposed to deposition, s.Ysf = agricultural productivity by unit area of stored feed, kg/m 2.XE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to Xi+Xw X, = weathering decay constant for leaf and plant surfaces, s-1.Bi j, = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 123 of 179 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS (m 2-mrem/y per piCi/s)RvFi = 106 DFLiao exp(-Xithc)
UFLafL {r(1-e(-XEte_)
+ Bkv(L-e(-Xtb)_)}
(7.20)YF kE P where: 106 conversion factor, pCi/pCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).?,i = decay constant for nuclide i, s-1 (Table 6.2).thc = average time between harvest of vegetables and their consumption and/or storage, s.UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
r = fraction of deposited activity retained on vegetables, dimensionless.
XE = the effective decay constant, due to radioactive decay and weathering, s-1,),j' + ?,w kw = decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.te = exposure time in garden for fresh leafy and/or stored vegetables, s.YF = agricultural yield for fresh leafy vegetables, kg/m 2.Biv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 124 of 179 7.7.6 STORED VEGETABLE INGESTION DOSE FACTORS m 2-mrem/y per pCi/s)Rvsi = 106 DFLiao exp(-Xithc)
Usfg (1-ex(-Xit-S).)
{r(l-exp(-XEk e)- + Biv(L-exp(-Xi-b}
(7.21)ki tsv Ysv XE P kj where: 106 = conversion factor, pCi/pCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Xi = decay constant for nuclide i, s-1 (Table 6.2).thc = average time between harvest of vegetables and their consumption and/or storage, s.Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg = fraction of stored vegetables grown locally, dimensionless.
tsv = time between storage of vegetables and their consumption, s.r = fraction of deposited activity retained on vegetables, dimensionless.)XE = the effective decay constant, due to radioactive decay and weathering, s-1.= Xj + kXw kw = decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.te = exposure time in garden for fresh leafy and/or stored vegetables, s.Ysv = agricultural yield for stored vegetables, kg/m 2.B3iv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 125 of 179 7.7.7 TRITIUM-PASTURE GRASS-COW/GOAT-MILK DOSE FACTOR (mrem/y per 3)RCTP = 103 106 DFLTao FmT QF Uap [0.75(0.5/H)]
fp exp(-XTtfm)
(7.22)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).FmT = transfer factor for tritium from animal's feed to milk, d/L (Table 6.2).QF = animal's consumption rate, kg/d.Ua = milk ingestion rate for age group a, L/y.0.f5 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fp = fraction of time animal spends on pasture, dimensionless.
?IT = decay constant for tritium, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.7.7.8 TRITIUM-STORED FEED-COW/GOAT-MILK DOSE FACTOR (mrem/y per p.Ci/m 3)RcTS = 103 106 DFLTao FFT QF Uam [0.75(0.5/H)]
fs exp(-XTtS)
(1-exp(-XTtcsf))
(1-exp(-XTtcb).-
(7.23)?T tcsf ?T tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/ýCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fs = fraction of time cow spends on stored feed, dimensionless.
?IT = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time to consume stored feed, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 126 of 179 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR (mrem/y per ptCi/m 3)RMTp = 103106 DFLTaoFFTQF Uam [0.75(0.5/H)]
fp exp(-XTtS)
(1-exp(-XTte._
(1-exp(-XTtcb))
(7.24)XT tep XT tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/pCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = beef ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fp = fraction of time cow spends on pasture, dimensionless.
kT = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tep = time pasture is exposed to deposition, s.tcb = time for receptor to consume a whole beef, s.7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR (mrem/y per p.Ci/m 3)RMTS = 103 106 DFLTaoFFTQFUam[O.
7 5(0.5/H)]
fs exp(-X)Tts)
(1-exp(-XT6sf)) (L-exp(-XTtb__
(7.25)XT tcsf X'T tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/pCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = beef ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fs = fraction of time cow spends on stored feed, dimensionless.
kT = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time to consume stored feed, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 127 of 179 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR (mrem/y per 1 iCi/m 3)RVTF = 103 106 DFLTao [0.75(0.5/H)]
UFLa fL exp(-XTthc)
(7.26)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/tCi.DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).0.75 = the fraction of total vegetation that is water.0.5 = the ratio of the specific activity of the vegetables water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
?IT = decay constant for tritium, s-1 (Table 6.2).thc = time between harvest of vegetables and their consumption and/or storage, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 128 of 179 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR (mrem/year per PtCi/m3)RvTs = 103 106 DFLTao [0.75(0.5/H)]
Usafg (1-exp(-X-Tdstv exp(-XTthc)
(7.27)XT tSv where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/tCi.DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).0.75 = the fraction of total vegetation that is water.0.5 = the ratio of the specific activity of the vegetation water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg = fraction of stored vegetables grown locally, dimensionless.
k'T = decay constant for tritium, s-1 (Table 6.2).tsv = time between harvest of stored vegetables and their consumption and/or storage, s.thc = time between harvest of vegetables and their storage, s.
SQN ODCM Revision 57 Page 129 of 179 7.7.13 CARBON 14 -PASTURE GRASS-COW/GOAT MILK DOSE FACTOR -Rcpc14 (mrem/y per ýtCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D=DFL Uap exp(-)Xthc)QC1 4 x [0.111 Q L0.16 (.7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is: 101106 (7.31 RcPc 1 4 =10 3 10 6 DFLC, 4 aj FmC,4 Qf Uap [L I-] fp exp(- XCl4tfm) (7.31)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/1 iCi.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).Fmc14 =transfer factor for carbon 14 from cow's feed to milk, d/L (Table 6.2).Qf = animal's consumption rate, kg/d.Uap = milk ingestion rate for age group a, L/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fp = fraction of time animal spends on pasture, dimensionless.
AC1 4 =decay constant for carbon 14, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 57 Page 130 of 179 7.7.14 CARBON 14 -STORED FEED-COW/GOAT MILK DOSE FACTOR -RCSCl4 (mrem/y per 1 iCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D=DFL Uap exp(- Xthc)Qc, 4 x [0.11]Q _0. 16 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the feed is stored (this term assumes that the feed is being eaten during the storage period) (Reference 10). The resulting dose factor is: RCSC410 106 DFLC 4 a Fm 4 Q Uap [0.1O ] f exp(- kCI 4 tfm ){'1 -cl4tc]f (7.32)Rco,=10 16DFc,, FcQrU1 0.16 J kC,4tcf where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/ýtCi.DFLc14aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).Ffc14 =transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = animal's consumption rate, kg/d.Uap = milk ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.f, = fraction of time animal spends on stored feed, dimensionless.
\C 1 4 =decay constant for carbon 14, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time between harvest of stored feed and consumption by animal, s.tfm = transport time from milking to receptor, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 57 Page 131 of 179 7.7.15 CARBON 14 -PASTURE GRASS-BEEF DOSE FACTOR -RMc14 (mrem/y per pýCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D=DFL Uap exp(- "thc)Qc 1 4 0.1](. 11 Q _0. 16 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is: RMCI4 = 103 106 DFLC14aj Ffc14 Qf Uanm _0.111 fp exp(- Xc 1 4 t)L 0.16], [1 exp(- X 1 4 tep )]t } [1 -exp(_ ?c.4 tb)] (7.33)L XCI4tep X C14t Cb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/pCi.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).Ffc14 = transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fp P = fraction of time cow spends on pasture, dimensionless.
AC 1 4 =decay constant for carbon 14, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tep = time pasture is exposed to deposition, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 57 Page 132 of 179 7.7.16 CARBON 14 -SRORED FEED-BEEF DOSE FACTOR -RMSCl4 (mrem/y per jiCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D =DFL U.P exp(-
x [0.16_]Q L 0.16 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the feed is stored (this term assumes that the feed is being eaten during the storage period) (Reference 10). The resulting dose factor is: R MSC14 =103 106 DFLCI 4 ,aj Frc 1 4 Qf Uam 0.161 f, exp(-Xkc 4 t.)[1 CIX(_X4tcsf
[ exp(-XC!1 4 t. 1.1 (7.34)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/[Ci.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).FfC14 =transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fs = fraction of time cow spends on stored feed, dimensionless.
/c1 4 =decay constant for carbon 14, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time between harvest of stored feed and consumption by animal, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 57 Page 133 of 179 7.7.17 CARBON 14 -FRESH LEAFY VEGETABLE DOSE FACTOR -RVFC14 (mrem/y per ýtCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D = DFL Uap exp(- Xthc)Qc 1 4 Q [0.11]Q 0. 16_ (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is:[0.111]R VFCI4 =103 106 DFLC1 4 aj L. 16] U FL. fL exp(- Xkt,) (7.35)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/V.Ci.DFLC14aj=
ingestion dose conversion factor for Carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m 3 UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
XLC14 = decay constant for Carbon 14, s-1 (Table 6.2).thc = time between harvest of vegetables and their consumption and/or storage, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 57 Page 134 of 179 7.7.18 CARBON 14-STORED VEGETABE DOSE FACTOR -Rvscl4 (mrem/y per ptCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D =DFLUap exp(-)Xthc)Qcl 4 x [0.11]Q 0.-16J (7.30.)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the vegetables are stored (this term assumes that the vegetables are being eaten during the storage period) (Reference 10). The resulting dose factor is: 10 106 D.[ USa fg{ exp (- c1 4 ts t)l}exp(-
kCl4thC) (7.36)RVSC14 =1316DFLc1aaj L0.16_11 s kCfg where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/pCi.DFLc14aj=
ingestion dose conversion factor for Carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m 3 Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg = fraction of stored vegetables grown locally, dimensionless.
ýcU4 = decay constant for Carbon 14, s-1 (Table 6.2).tsv = time between harvest of stored vegetables and their consumption and/or storage, s.thc = time between harvest of vegetables and their storage, s.
SQN ODCM Revision 57 Page 135 of 179 7.7.19 INHALATION DOSE FACTORS (mrem/y per ptCi/m 3)Rii = DFAiao BRa 106 (7.37)where: DFAiao = inhalation dose conversion factor for nuclide i, age group a and organ o, mrem/pCi (Table 7.6).BRa = breathing rate for age group a, m 3/y (Table 6.3).106 = conversion factor, pCi/tCi.7.7.20 GROUND PLANE DOSE FACTORS (m 2-mrem/y per ptCi/s)RGi = DFGi 0 1/Xi 106 8760 [1 -exp(-?.itb)]
(7.38)where: DFGjo = dose conversion factor for standing on contaminated ground for nuclide i and organ o (total body and skin), mrem/hr per pCi/m 2 (Table 6.6).xi = decay constant of nuclide i, s-1 (Table 6.2).106 = conversion factor, pCi/gCi.8760 = conversion factor, h/y.tb = time period over which the ground accumulation is evaluated, s (Table 6.3).
SQN ODCM Revision 57 Page 136 of 179 7.8 DISPERSION METHODOLOGY Dispersion factors are calculated for radioactive effluent releases using hourly average meteorological data consisting of wind speed and direction measurements at 10m and temperature measurements at 9m and 46m.A sector-average dispersion equation consistent with Regulatory Guide 1.111 is used. The dispersion model considers plume depletion (using information from Figure 7.4), and building wake effects. Terrain effects on dispersion are not considered.
Hourly average meteorological data are expressed as a joint-frequency distribution of wind speed, wind direction, and atmospheric stability.
A joint-frequency distribution for each quarter from 1986-1995 is used for calculations described in Section 7.2, 7.3, 7.4, and 7.5. A joint-frequency distribution using the actual hourly-average meteorological data is used for calculations described in Section 7.6.The wind speed classes that are used are as follows: Number 1 2 3 4 5 6 7 8 9 Ranaie (m/s)<0.3 0.3-0.6 0.7-1.5 1.6-2.4 2.5-3.3 3.4-5.5 5.6-8.2 8.3-10.9>10.9 Midpoint (m/s)0.13 0.45 1.10 1.99 2.88 4.45 6.91 9.59 10.95 The stability classes that will be used are the standard A through correspond to A=1, B=2 ..., G=7.G classifications.
The stability classes 1-7 will 7.8.1 AIR CONCENTRATION Air concentrations of nuclides at downwind locations are calculated using the following equation: 9 7= X2/)1 1 2 ikQ..... exp(-ki x/uj)j=1lk=1 YEA Uj (27rx/n)(7.39)where Qi p= joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction.= release rate of radionuclide i, pCi/s.= fraction of radionuclide remaining in plume (Figure 7.4).
SQN ODCM Revision 57 Page 137 of 179 T-zk = vertical dispersion coefficient for stability class k which includes a building wake adjustment,= (0zk 2 + cA/h)1/2 , or = (3)1/2 azk, whichever is smaller.where 0 zk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2).uj = midpoint value of wind speed class interval j, m/s.x = downwind distance, m.n = number of sectors, 16.Xi = radioactive decay coefficient of radionuclide i, s-1 27Ex/n = sector width at point of interest, m.7.8.2 RELATIVE CONCENTRATION Relative concentrations of nuclides at downwind locations are calculated using the following equation: 9 7 x/Q = Y_ Y_ (2/7c)1/2 fik. (7.40)j=1 k=1 Uj (21rx/n)where fjk = joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction.Xzk = vertical dispersion coefficient for stability class k which includes a building wake adjustment,= ('zk 2 + cA/7r)1/2 , or = (3)1/2 zk, whichever is smaller.where Azk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2)uj J = midpoint value of wind speed class interval j, m/s.x = downwind distance, m.n = number of sectors, 16.2iTx/n = sector width at point of interest, m.
SQN ODCM Revision 57 Page 138 of 179 7.8.3 RELATIVE DEPOSITION Relative deposition of nuclides at downwind locations is calculated using the following equation: 9 7 fjk DR D/Q = Y. Y -(7.41)j=1 k=1 (2Tcx/n)where fjk = joint relative frequency of occurrence of winds in windspeed class j and stability class k, blowing toward this exposure point, expressed as a fraction.DR = relative deposition rate, m-1 (from Figure 7.6).x = downwind distance, m.n = number of sectors, 16.2nx/n = sector width at point of interest, m.
SQN ODCM Revision 57 Page 139 of 179 Table 7.1 Sequoyah Maximum Quarterly X/Q (1999-2008)
Sorted by Quarter QUARTER 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 YEAR 1999 1999 1999 1999 2000 2000 2000 2000 2001 2001 2001 2001 2002 2002 2002 2002 2003 2003 2003 2003 2004 2004 2004 2004 2005 2005 2005 2005 2006 2006 2006 2006 2007 2007 2007 2007 2008 2008 2008 2008 MAXIMUM SECTOR SSW NW N NNW N N S SSW NW N N SSW N N N N N N N SSW NNW N S N N NW S SSW N N N SSW N N N SSW N N S SSW DISTANCE (METERS)1840 660 950 730 950 950 1570 1840 660 950 950 1840 950 950 950 950 950 950 950 1840 730 950 1570 950 950 660 1570 1840 950 950 950 1840 950 950 950 1840 950 950 1570 1840 Average XIQ(1999-2008)=,Y/Q(10.6 S/M3)5.10 6.08 6.48 9.75 6.08 6.68 6.32 7.36 5.10 6.95 6.40 8.85 5.12 5.85 7.06 6.56 4.46 6.83 6.54 5.23 4.74 7.96 6.47 7.44 4.79 8.47 5.92 5.23 5.26 4.91 5.97 6.22 4.94 6.21 6.14 5.81 4.38 5.37 5.81 4.68 6.14 x 10.6 SQN ODCM Revision 57 Page 140 of 179 Table 7.2 Sequoyah Maximum Quarterly D/Q (1999-2008)
Sorted by Quarter QUARTER 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 YEAR 1999 1999 1999 1999 2000 2000 2000 2000 2001 2001 2001 2001 2002 2002 2002 2002 2003 2003 2003 2003 2004 2004 2004 2004 2005 2005 2005 2005 2006 2006 2006 2006 2007 2007 2007 2007 2008 2008 2008 2008 MAXIMUM SSW N N N N N N SSW S N N N N N N N N N N N SSW N N N SSW N N SSW N N N SSW N N N N N N N S DISTANCE 1840 950 950 950 950 950 950 1840 1570 950 950 950 950 950 950 950 950 950 950 950 1840 950 950 950 1840 950 950 1840 950 950 950 1840 950 950 950 950 950 950 950 1570 Average D/Q(1999-2008)=
D/Q(10-8 I/M2)1.13 1.86 1.38 1.28 1.33 1.69 1.29 1.23 1.13 1.49 1.86 1.46 1.04 1.61 2.02 1.49 0.95 1.64 1.64 1.24 1.15 2.24 1.32 1.64 1.09 1.27 1.48 1.20 1.32 1.24 1.70 1.22 1.27 1.31 1.31 1.26 1.39 1.60 1.41 0.98 1.40 x 10-8 SQN ODCM Revision 57 Page 141 of 179 Table 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES Kr-83m Kr-85m Kr-85 Kr-87 Kr-88 Kr-89 Kr-90 Xe-1 31 m Xe-1i33m Xe-1 33 Xe-135m Xe-135 Xe-137 Xe-138 Ar-41 Submersion dose mrem/y per ýtCi/m 3 DFBi DFSi 7.56E-02 ---1.17E+03 1.46E+03 1.61E+01 1.34E+03 5.92E+03 9.73E+03 1.47E+04 2.37E+03 1.66E+04 1.01E+04 1.56E+04 7.29E+03 9.15E+01 4.76E+02 2.51 E+02 9.94E+02 2.94E+02 3.06E+02 3.12E+03 7.11E+02 1.81 E+03 1.86E+03 1.42E+03 1.22E+04 8.83E+03 4.13E+03 8.84E+03 2.69E+03 Air dose mrad/y per pjCi/m 3 DFyi DFri 1.93E+01 2.88E+02 1.23E+03 1.97E+03 1.72E+01 1.95E+03 6.17E+03 1.03E+04 1.52E+04 2.93E+03 1.73E+04 1.06E+04 1.63E+04 7.83E+03 1.56E+02 1.11E+03 3.27E+02 1.48E+03 3.53E+02 1.05E+03 3.36E+03 7.39E+02 1.92E+03 2.46E+03 1.51E+03 1.27E+04 9.21 E+03 4.75E+03 9.30E+03 3.28E+03
Reference:
Regulatory Guide 1.109, Table B-1.
SQN ODCM Revision 57 Page 142 of 179 Table 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES Range of Midpoint of Sector Element Sector Element Unrestricted Area boundary -1 mile 0.8 mile 1 -2 miles 1.5 miles 2 -3 miles 2.5 miles 3 -4 miles 3.5 miles 4 -5 miles 4.5 miles 5 -10 miles 7.5 miles 10 -20 miles 15 miles 20 -30 miles 25 miles 30 -40 miles 35 miles 40 -50 miles 45 miles SQN ODCM Revision 57 Page 143 of 179 Table 7.5 POPULATION WITHIN EACH SECTOR ELEMENT Sector Midpoint (miles)0.8 1.5 2.5 3.5 4.5 7.5 15 25 35 45 N 20 41 213 129 66 1784 5453 3470 2610 11145 NNE 0 30 123 182 62 600 0628 4910 8250 10625 NE 0 0 67 67 94 581 2884 6998 7047 18080 ENE 0 11 24 222 300 773 4707 5747 29477 18679 E 0 70 11 191 137 918 7440 6808 5072 4129 ESE 0 118 113 194 137 1849 46521 5044 1896 3624 SE 0 179 322 168 205 1507 6005 5461 15641 3417 SSE 0 125 370 750 601 2347 13242 8596 34279 1648 S 0 67 143 229 811 3930 28008 26690 19642 11622 SSW 0 82 140 400 170 8927 96966 55597 21349 11978 SW 0 10 306 634 194 9787 94225 23455 11641 11109 WSW 20 190 642 1124 1669 19089 28405 4106 15081 9548 W 10 20 233 657 657 5225 1580 6350 5699 7707 WNW 10 30 365 598 598 2622 6540 4920 6699 2450 NW 50 80 292 569 336 2696 1410 1750 1217 15856 NNW 10 263 80 75 213 1610 471 3130 2835 5719 SQN ODCM Revision 57 Page 144 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 1 of 8)ADULT H-3 C-14 Na-24 P-32 Cr-51 Mn-54 Mn-56 Fe-55 Fe-59 Co-57 Co-58 Co-60 Ni-63 Ni-65 Cu-64 Zn-65 Zn-69 Zn-69m Br-82 Br-83 Br-84 Br-85 Rb-86 Rb-88 Rb-89 Sr-89 Sr-90 Sr-91 Sr-92 Y-90 Y-91m Y-91 Y-92 Y-93 Zr-95 Zr-97 Nb-95 Nb-97 Mo-99 Tc-99m Tc-101 Ru-103 Ru-1 05 Ru-106 Ag-110m 1.58E-0 2.27E-0 1.28E-0'1.65E-0.0.OOE+0 0.OOE+0 0.OOE+0 3.07E-0 1.47E-0 0.OOE+0 0.OOE+0 0.OOE+0 5.40E-0 1.92E-1(0.OOE+0 4.05E-04 4.23E-1, 1.02E-0 0.00E+0 0.00E+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.00E+0 3.80E-0, 1.24E-0;7.74E-0, 8.43E-1(2.61 E-0 3.26E-1 5.78E-0, 1.29E-0.1.18E-0 1.34E-0 1.21 1.76E-04 2.78E-1 0.00E+0 1.29E-1, 5.22E-1 1.91 E-0 9.88E-1 8.64E-0l 1.35E-0I bone liver 7 1.58E-07 12.6 4.26E-07 4.: 6 1.28E-06 1.;4 9.64E-06 6.;10 0.OOE+00 1.: 10 4.95E-06 7.1 10 1.55E-10 2.;6 2.12E-06 4.6 3.47E-06 1.;10 8.65E-08 8.:]0 1.98E-07 2.1 40 1.44E-06 1.1 5 3.93E-06 1.1 0 2.62E-11 1.10 1.83E-10 7.6 1.29E-05 5.2 8.14E-12 5.9 2.45E-09 2.: 40 0.OOE+00 1.4 40 O.OOE+00 3.4 40 0.OOE+00 3.40 0.OOE+00 1.4 40 1.69E-05 7.: 40 4.84E-08 2., 40 3.20E-08 2.5 0.OOE+00 1.4 2 0.OOE+00 7.4 9 0.OOE+00 3.0 0.OOE+00 3.4 7 0.OOE+00 7.4 1 0.OOE+00 1.: 5 0.OOE+00 1 .9 0.OOE+00 3.8 0.OOE+00 3.: 5 4.30E-06 2.1 8 2.45E-09 1.6 9.77E-07 5.;1 7.03E-12 2.!40 1.51E-08 2.1 3 3.64E-13 4.1 5 7.52E-15 7.7 0.OOE+00 8.1 0.OOE+00 3.1 6 0.OOE+00 1.4 6 1.25E-06 7.t 58E-07 26E-07 28E-06 26E-06 25E-08 87E-07 29E-11 93E-07 32E-06 39E-08 59E-07 85E-06 81E-06 14E-11 69E-11 82E-06 65E-13 24E-10 69E-06 01E-08 91E-08 60E-09 37E-06 41E-08 12E-08 09E-06 62E-04 13E-10 64E-11 01E-09 27E-12 55E-06 77E-11 26E-10 91E-06 13E-09 26E-07 56E-12 87E-09 63E-12 38E-14 23E-08 89E-11 09E-06 43E-07 body th 1.58E-07 4.26E-07 1.28E-06 0.OOE+00 7.44E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 yroid kidney 1.58E-07 4.26E-07 1.28E-06 0.OOE+00 2.85E-09 1.23E-06 1.63E-10 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 5.78E-10 8.62E-06 5.27E-12 1.48E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 6.77E-06 3.71 E-09 9.67E-07 8.18E-12 3.64E-08 5.52E-12 1.35E-13 7.29E-07 1.27E-10 1.67E-05 2.46E-06 1.58E-0 4.26E-0 1.28E-0 0.OOE+0 1.80E-0 1.75E-0 1.18E-0 9.01 E-0 1.27E-0 4.62E-0 1.16E-0 7.46E-0 2.23E-0 7.OOE-0 8.48E-0 1.08E-0.1.15E-0 2.38E-0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 1.75E-0.1.20E-0 4.56E-0 2.06E-0 2.12E-0 2.40E-0 2.13E-0 1.96E-0'6.06E-0'2.21 E-0.9.84E-0'6.31 E-0 3.OOE-0 1.14 E-0, 9.55E-0 4.99E-0 6.31 E-0 1.37E-0'1.17E-0.5.79E-0.lung gi-Ili 7 1.58E-07 7 4.26E-07 6 1.28E-06)0 1.08E-05 6 4.15E-07 4 9.67E-06 6 2.53E-06 6 7.54E-07 4 2.35E-05 5 3.93E-06 4 1.33E-05 4 3.56E-05 5 1.67E-06 7 1.54E-06 7 6.12E-06 4 6.68E-06 7 2.04E-09 6 1.71E-05 10 1.30E-06 10 2.90E-08 10 2.05E-13 10 0.OOE+00 10 2.08E-06 10 4.18E-19 10 1.16E-21 4 4.37E-05 3 9.02E-05 6 2.39E-05 6 5.38E-06 5 6.32E-05 7 1.66E-10 4 4.81E-05 6 9.19E-06 6 5.27E-05 4 1.88E-05 6 6.54E-05 5 1.30E-05 7 3.02E-08 5 3.10E-05 8 5.20E-07 8 1.36E-21 5 1.38E-05 6 6.02E-06 3 1.14E-04 4 3.78E-05 SQN ODCM Revision 57 Page 145 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 2 of 8)ADULT Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te- 132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-1 34 Cs-136 Cs-137 Cs-1 38 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 3.90E-06 6.67E-06 1.16E-06 4.27E-07 1.58E-06 1.75E-10 1.22E-06 6.22E-12 8.74E-09 1.39E-12 3.25E-08 5.72E-07 3.15E-06 1.45E-07 1.08E-06 8.05E-08 3.35E-07 4.66E-05 4.88E-06 5.98E-05 4.14E-08 1.17E-10 4.88E-06 1.25E-1 1 3.29E-12 4.30E-08 8.54E-1 1 2.49E-06 2.33E-08 4.29E-04 1.17E-06 3.76E-1 2 6.59E-07 1.06E-09 2.87E-08 liver 7.36E-08 7.44E-08 3.12E-08 1.98E-07 7.21 E-07 8.03E-1 1 5.84E-07 2.99E-12 5.45E-09 7.44E-13 2.69E-08 1.68E-06 4.47E-06 4.07E-07 1.85E-06 2.16E-07 8.73E-07 1.06E-04 1.83E-05 7.76E-05 7.76E-08 8.32E-14 6.13E-09 9.41 E-15 3.38E-15 2.17E-08 3.88E-1 1 1.69E-06 1.72E-08 1.79E-04 4.69E-07 1.56E-12 7.62E-07 8.85E-10 2.82E-09 t body 1.55E-06 1.58E-06 7.03E-08 5.84E-08 1.96E-07 3.87E- 11 1.98E-07 1.55E-12 3.63E-09 4.49E-13 2.02E-08 6.60E-07 2.56E-06 1.45E-07 5.65E-07 7.69E-08 3.21 E-07 9.1OE-05 1.38E-05 5.35E-05 4.05E-08 3.42E-12 3.21 E-07 4.20E-13 2.07E-1 3 5.73E-09 9.65E-12 1.91 E-07 1.91 E-09 2.30E-05 5.80E-08 1.91E-13 4.56E-08 3.10E-10 1.55E-09 thyroid 9.44E-09 6.75E-09 2.59E-08 1.31 E-07 4.11 E-07 1.32E-10 4.30E-07 4.87E-12 6.88E-09 1.17E-12 2.37E-08 1.42E-04 1.49E-03 1.43E-05 2.69E-04 3.73E-06 5.60E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 0.OOE+00 0.OOE+00 0.OOE+00 1.55E-06 5.72E-06 6.37E-10 4.57E-06 2.34E-1 1 3.86E-08 5.46E-12 1.82E-07 2.61 E-06 7.66E-06 6.48E-07 3.23E-06 3.44E-07 1.39E-06 3.59E-05 1.07E-05 2.78E-05 6.OOE-08 7.78E-14 2.09E-09 8.75E-1 5 2.86E-1 5 O.OOE+00 0.OOE+00 7.83E-07 7.60E-09 1.06E-04 2.70E-07 8.81E-13 4.45E-07 0.OOE+00 8.75E-09 lung 3.1 OE-04 2.18E-04 7.37E-05 3.92E-05 1.20E-04 8.14E-07 1.45E-04 2.42E-07 1.82E-05 1.74E-07 3.60E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.22E-05 1.50E-06 9.40E-06 6.07E-09 4.70E-07 1.59E-04 2.42E-07 1.49E-07 1.70E-05 7.91 E-07 4.52E-05 9.97E-06 9.72E-04 3.51 E-05 1.27E-07 2.76E-05 3.63E-06 4.70E-06 gi-Ili 5.08E-05 1.26E-05 6.81 E-05 8.83E-06 1.87E-05 7.17E-06 4.79E-05 1.96E-08 6.95E-05 2.30E-09 6.37E-05 9.61 E-07 7.85E-07 5.08E-08 1.11E-06 1.26E-10 6.56E-07 1.30E-06 1.46E-06 1.05E-06 2.33E-13 1.12E-07 2.73E-05 1.45E-17 1.96E-26 5.73E-05 2.64E-07 1.50E-05 2.83E-05 1.02E-04 2.50E-05 2.69E-18 2.16E-05 1.94E-05 1.49E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-7.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 57 Page 146 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 3 of 8)TEEN bone liver t body thyroid kidney lung gi-Ili H-3 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 C-14 3.25E-06 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 Na-24 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 P-32 2.36E-04 1.37E-05 8.95E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.16E-05 Cr-51 O.OOE+00 O.OOE+00 1.69E-08 9.37E-09 3.84E-09 2.62E-06 3.75E-07 Mn-54 O.OOE+00 6.39E-06 1.05E-06 O.OOE+00 1.59E-06 2.48E-04 8.35E-06 Mn-56 O.OOE+00 2.12E-10 3.15E-11 O.OOE+00 2.24E-10 1.90E-06 7.18E-06 Fe-55 4.18E-06 2.98E-06 6.93E-07 O.OOE+00 O.OOE+00 1.55E-05 7.99E-07 Fe-59 1.99E-06 4.62E-06 1.79E-06 O.OOE+00 O.OOE+00 1.91E-04 2.23E-05 Co-57 O.OOE+00 1.18E-07 1.15E-07 O.OOE+00 O.OOE+00 7.33E-05 3.93E-06 Co-58 O.OOE+00 2.59E-07 3.47E-07 O.OOE+00 O.OOE+00 1.68E-04 1.19E-05 Co-60 O.OOE+00 1.89E-06 2.48E-06 O.OOE+00 O.OOE+00 1.09E-03 3.24E-05 Ni-63 7.25E-05 5.43E-06 2.47E-06 O.OOE+00 O.OOE+00 3.84E-05 1.77E-06 Ni-65 2.73E-10 3.66E-11 1.59E-11 O.OOE+00 O.OOE+00 1.17E-06 4.59E-06 Cu-64 O.OOE+00 2.54E-10 1.06E-10 O.OOE+00 8.01E-10 1.39E-06 7.68E-06 Zn-65 4.82E-06 1.67E-05 7.80E-06 O.OOE+00 1.08E-05 1.55E-04 5.83E-06 Zn-69 6.04E-12 1.15E-11 8.07E-13 O.OOE+00 7.53E-12 1.98E-07 3.56E-08 Zn-69m 1.44E-09 3.39E-09 3.11E-10 O.OOE+00 2.06E-09 3.92E-06 2.14E-05 Br-82 O.OOE+00 O.OOE+00 2.28E-06 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-83 0.OOE+00 O.OOE+00 4.30E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 5.41E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.OOE+00 O.OOE+00 2.29E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 O.OOE+00 2.38E-05 1.05E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.21 E-06 Rb-88 O.OOE+00 6.82E-08 3.40E-08 O.OOE+00 O.OOE+00 O.OOE+00 3.65E-15 Rb-89 O.OOE+00 4.40E-08 2.91E-08 O.OOE+00 O.OOE+00 0.00E+00 4.22E-17 Sr-89 5.43E-05 O.OOE+00 1.56E-06 O.OOE+00 O.OOE+00 3.02E-04 4.64E-05 Sr-90 1.35E-02 O.OOE+00 8.35E-04 O.OOE+00 O.OOE+00 2.06E-03 9.56E-05 Sr-91 1.10E-08 O.OOE+00 4.39E-10 O.OOE+00 O.OOE+00 7.59E-06 3.24E-05 Sr-92 1.19E-09 O.OOE+00 5.08E-11 O.OOE+00 O.OOE+00 3.43E-06 1.49E-05 Y-90 3.73E-07 O.OOE+00 1.OOE-08 O.OOE+00 O.OOE+00 3.66E-05 6.99E-05 Y-91m 4.63E-11 O.OOE+00 1.77E-12 O.OOE+00 O.OOE+00 4.OOE-07 3.77E-09 Y-91 8.26E-05 O.OOE+00 2.21E-06 O.OOE+00 O.OOE+00 3.67E-04 5.11E-05 Y-92 1.84E-09 O.OOE+00 5.36E-11 O.OOE+00 O.OOE+00 3.35E-06 2.06E-05 Y-93 1.69E-08 O.OOE+00 4.65E-10 O.OOE+00 O.OOE+00 1.04E-05 7.24E-05 Zr-95 1.82E-05 5.73E-06 3.94E-06 O.OOE+00 8.42E-06 3.36E-04 1.86E-05 Zr-97 1.72E-08 3.40E-09 1.57E-09 O.OOE+00 5.15E-09 1.62E-05 7.88E-05 Nb-95 2.32E-06 1.29E-06 7.08E-07 O.OOE+00 1.25E-06 9.39E-05 1.21 E-05 Nb-97 3.92E-11 9.72E-12 3.55E-12 O.OOE+00 1.14E-11 4.91E-07 2.71E-07 Mo-99 O.OOE+00 2.11E-08 4.03E-09 O.OOE+00 5.14E-08 1.92E-05 3.36E-05 Tc-99m 1.73E-13 4.83E-13 6.24E-12 O.OOE+00 7.20E-12 1.44E-07 7.66E-07 Tc-101 7.40E-15 1.05E-14 1.03E-13 O.OOE+00 1.90E-13 8.34E-08 1.09E-16 Ru-103 2.63E-07 O.OOE+00 7.70E-07 O.OOE+00 9.29E-07 9.79E-05 1.36E-05 Ru-105 1.40E-10 O.OOE+00 5.42E-11 O.OOE+00 1.76E-10 2.27E-06 1.13E-05 Ru-106 1.23E-05 O.OOE+00 1.55E-06 O.OOE+00 2.38E-05 2.01E-03 1.20E-04 Ag-110m 1.73E-06 1.64E-06 9.99E-07 O.OOE+00 3.13E-06 8.44E-04 3.41E-05 SQN ODCM Revision 57 Page 147 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 4 of 8)TEEN Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 5.38E-06 9.23E-06 1.66E-06 6.1 OE-07 2.25E-06 2.51 E-10 1.74E-06 8.87E-12 1.23E-08 1.97E-12 4.50E-08 7.80E-07 4.43E-06 1.99E-07 1.52E-06 1.11E-07 4.62E-07 6.28E-05 6.44E-06 8.38E-05 5.82E-08 1.67E-10 6.84E-06 1.78E-11 4.62E-12 5.99E-08 1.20E-10 3.55E-06 3.32E-08 6.11 E-04 1.67E-06 5.37E-12 9.83E-07 1.50E-09 4.23E-08 liver 9.92E-08 1.01E-07 4.42E-08 2.80E-07 1.02E-06 1.14E-10 8.23E-07 4.22E-1 2 7.51 E-09 1.04E-12 3.63E-08 2.24E-06 6.14E-06 5.47E-07 2.56E-06 2.90E-07 1.18E-06 1.41E-04 2.42E-05 1.06E-04 1.07E-07 1.18E-13 8.38E-09 1.32E-14 4.63E-15 2.95E-08 5.31 E-11 2.37E-06 2.42E-08 2.53E-04 6.64E-07 2.20E-1 2 1.07E-06 1.22E-09 3.99E-09 t body 2.1 OE-06 2.15E-06 9.99E-08 8.34E-08 2.73E-07 5.52E-1 1 2.81 E-07 2.20E-12 5.03E-09 6.30E-13 2.74E-08 8.96E-07 3.30E-06 1.97E-07 7.78E-07 1.05E-07 4.36E-07 6.86E-05 1.71 E-05 3.89E-05 5.58E-08 4.87E-12 4.40E-07 5.93E-13 2.84E-13 7.82E-09 1.32E-11 2.71 E-07 2.70E-09 3.28E-05 8.28E-08 2.72E-13 6.41 E-08 4.29E-10 2.21 E-09 thyroid 1.22E-08 8.80E-09 3.45E-08 1.75E-07 5.48E-07 1.77E-10 5.72E-07 6.48E-12 9.06E-09 1.55E-12 3.07E-08 1.86E-04 1.83E-03 1.89E-05 3.65E-04 4.94E-06 7.76E-05 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 kidney 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 8.17E-06 9.10E-10 6.49E-06 3.32E-11 5.49E-08 7.72E-12 2.44E-07 3.44E-06 1.05E-05 8.65E-07 4.49E-06 4.58E-07 1.86E-06 4.69E-05 1.38E-05 3.80E-05 8.28E-08 1.11E-13 2.85E-09 1.23E-14 3.92E-15 0.OOE+00 0.OOE+00 1.11E-06 1.08E-08 1.51 E-04 3.86E-07 1.26E-12 6.28E-07 0.00E+00 1.25E-08 lung 4.81 E-04 3.42E-04 1.26E-04 6.70E-05 2.07E-04 1.40E-06 2.47E-04 4.12E-07 2.97E-05 2.92E-07 5.61 E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 1.83E-05 2.22E-06 1.51 E-05 9.84E-09 8.08E-07 2.54E-04 4.11 E-07 2.39E-07 2.68E-05 1.27E-06 7.67E-05 1.63E-05 1.67E-03 6.04E-05 2.19E-07 4.65E-05 5.92E-06 8.11 E-06 gi-Ili 4.98E-05 1.24E-05 7.29E-05 9.38E-06 1.99E-05 1.01E-05 5.06E-05 2.02E-07 7.76E-05 1.89E-09 5.79E-05 1.14E-06 8.11E-07 1.59E-07 1.29E-06 2.55E-09 8.69E-07 1.22E-06 1.36E-06 1.06E-06 3.38E-1 1 8.06E-07 2.86E-05 9.33E-14 5.99E-20 6.09E-05 1.50E-06 1.58E-05 3.19E-05 1.08E-04 2.67E-05 2.94E-14 2.28E-05 2.21 E-05 1.65E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-8.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 57 Page 148 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 5 of 8)CHILD bone liver t body thyroid kidney lung gi-Ili H-3 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 C-14 9.70E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 Na-24 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 P-32 7.04E-04 3.09E-05 2.67E-05 O.OOE+00 O.OOE+00 0.OOE+00 1.14E-05 Cr-51 0.OOE+00 0.OOE+00 4.17E-08 2.31E-08 6.57E-09 4.59E-06 2.93E-07 Mn-54 0.OOE+00 1.16E-05 2.57E-06 O.OOE+00 2.71E-06 4.26E-04 6.19E-06 Mn-56 O.OOE+00 4.48E-10 8.43E-11 0.OOE+00 4.52E-10 3.55E-06 3.33E-05 Fe-55 1.28E-05 6.80E-06 2.1OE-06 0.OOE+00 O.OOE+00 3.OOE-05 7.75E-07 Fe-59 5.59E-06 9.04E-06 4.51 E-06 0.OOE+00 0.OOE+00 3.43E-04 1.91 E-05 Co-57 0.OOE+00 2.44E-07 2.88E-07 0.OOE+00 0.OOE+00 1.37E-04 3.58E-06 Co-58 0.OOE+00 4.79E-07 8.55E-07 0.OOE+00 0.OOE+00 2.99E-04 9.29E-06 Co-60 O.OOE+00 3.55E-06 6.12E-06 0.OOE+00 O.OOE+00 1.91E-03 2.60E-05 Ni-63 2.22E-04 1.25E-05 7.56E-06 0.OOE+00 0.OOE+00 7.43E-05 1.71 E-06 Ni-65 8.08E-10 7.99E-11 4.44E-11 O.OOE+00 O.OOE+00 2.21E-06 2.27E-05 Cu-64 0.OOE+00 5.39E-10 2.90E-10 0.OOE+00 1.63E-09 2.59E-06 9.92E-06 Zn-65 1.15E-05 3.06E-05 1.90E-05 0.OOE+00 1.93E-05 2.69E-04 4.41E-06 Zn-69 1.81E-11 2.61E-11 2.41E-12 0.OOE+00 1.58E-11 3.84E-07 2.75E-06 Zn-69m 4.26E-09 7.28E-09 8.59E-10 0.OOE+00 4.22E-09 7.36E-06 2.71E-05 Br-82 0.OOE+00 0.OOE+00 5.66E-06 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 1.28E-07 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-84 O.OOE+00 O.OOE+0O 1.48E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 O.OOE+00 6.84E-09 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Rb-86 O.OOE+00 5.36E-05 3.09E-05 O.OE+00 0.OOE+00 0.OOE+00 2.16E-06 Rb-88 0.OOE+00 1.52E-07 9.90E-08 0.OOE+00 0.OOE+00 0.OOE+00 4.66E-09 Rb-89 0.OOE+00 9.33E-08 7.83E-08 0.OOE+00 O.OOE+00 0.OOE+00 5.11E-10 Sr-89 1.62E-04 0.OOE+00 4.66E-06 O.OOE+00 O.OOE+00 5.83E-04 4.52E-05 Sr-90 2.73E-02 O.OOE+00 1.74E-03 0.OOE+00 0.OOE+00 3.99E-03 9.28E-05 Sr-91 3.28E-08 0.OOE+00 1.24E-09 0.OOE+00 0.OOE+00 1.44E-05 4.70E-05 Sr-92 3.54E-09 O.OOE+00 1.42E-10 0.OOE+00 0.OOE+00 6.49E-06 6.55E-05 Y-90 1.11E-06 0.OOE+00 2.99E-08 0.OOE+00 O.OOE+00 7.07E-05 7.24E-05 Y-91m 1.37E-10 O.OOE+00 4.98E-12 O.OOE+00 0.OOE+00 7.60E-07 4.64E-07 Y-91 2.47E-04 0.OOE+00 6.59E-06 0.OOE+00 0.OOE+00 7.10E-04 4.97E-05 Y-92 5.50E-09 0.OOE+00 1.57E-10 0.OOE+00 O.OOE+00 6.46E-06 6.46E-05 Y-93 5.04E-08 0.OOE+00 1.38E-09 0.OOE+00 0.OOE+00 2.01 E-05 1.05E-04 Zr-95 5.13E-05 1.13E-05 1.OOE-05 0.OOE+00 1.61E-05 6.03E-04 1.65E-05 Zr-97 5.07E-08 7.34E-09 4.32E-09 0.OOE+00 1.05E-08 3.06E-05 9.49E-05 Nb-95 6.35E-06 2.48E-06 1.77E-06 0.OOE+00 2.33E-06 1.66E-04 1.OOE-05 Nb-97 1.16E-10 2.08E-11 9.74E-12 0.OOE+00 2.31E-11 9.23E-07 7.52E-06 Mo-99 0.OOE+00 4.66E-08 1.15E-08 0.OOE+00 1.06E-07 3.66E-05 3.42E-05 Tc-99m 4.81E-13 9.41E-13 1.56E-11 0.OOE+00 1.37E-11 2.57E-07 1.30E-06 Tc-101 2.19E-14 2.30E-14 2.91E-13 0.OOE+00 3.92E-13 1.58E-07 4.41E-09 Ru-103 7.55E-07 O.OOE+00 2.90E-07 0.OOE+00 1.90E-06 1.79E-04 1.21E-05 Ru-105 4.13E-10 0.OOE+00 1.50E-10 0.OOE+00 3.63E-10 4.30E-06 2.69E-05 Ru-106 3.68E-05 O.OOE+00 4.57E-06 0.OOE+00 4.97E-05 3.87E-03 1.16E-04 Ag-110m 4.56E-06 3.08E-06 2.47E-06 0.OOE+00 5.74E-06 1.48E-03 2.71E-05 SQN ODCM Revision 57 Page 149 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 6 of 8)CHILD Sb-1i24 Sb-1i25 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 1.55E-05 2.66E-05 4.95E-06 1.82E-06 6.72E-06 7.49E-10 5.19E-06 2.64E-1 1 3.63E-08 5.87E-12 1.30E-07 2.21 E-06 1.30E-05 5.72E-07 4.48E-06 3.17E-07 1.33E-06 1.76E-04 1.76E-05 2.45E-04 1.71 E-07 4.98E-10 2.00E-05 5.29E-1 1 1.35E-11 1.74E-07 3.50E-1 0 1.06E-05 9.89E-08 1.83E-03 4.99E-06 1.61 E-11 2.92E-06 4.41 E-09 1.26E-07 liver 2.00E-07 2.05E-07 9.94E-08 6.29E-07 2.31 E-06 2.57E-10 1.85E-06 9.45E-12 1.60E-08 2.28E-12 7.36E-08 4.43E-06 1.30E-05 1.10E-06 5.49E-06 5.84E-07 2.36E-06 2.74E-04 4.62E-05 2.23E-04 2.27E-07 2.66E-13 1.75E-08 2.95E-14 9.73E-15 6.08E-08 1.11E-10 5.28E-06 5.37E-08 5.72E-04 1.50E-06 4.99E-12 2.36E-06 2.61 E-09 9.04E-09 t body 5.41 E-06 5.59E-06 2.95E-07 2.47E-07 8.16E-07 1.65E-10 8.22E-07 6.44E-12 1.37E-08 1.78E-12 7.12E-08 2.28E-06 7.37E-06 5.07E-07 2.08E-06 2.69E-07 1.12E-06 6.07E-05 3.14E-05 3.47E-05 1.50E-07 1.45E-1 1 1.17E-06 1.72E-12 7.54E-1 3 2.04E-08 3.49E-1 1 7.83E-07 7.77E-09 9.77E-05 2.47E-07 8.10E-13 1.84E-07 1.17E-09 6.35E-09 thyroid 3.41 E-08 2.46E-08 1.03E-07 5.20E-07 1.64E-06 5.30E-10 1.71 E-06 1.93E-11 2.64E-08 4.59E-12 8.58E-08 4.99E-04 4.39E-03 5.23E-05 1.04E-03 1.37E-05 2.14E-04 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 kidney 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.72E-05 1.91 E-09 1.36E-05 6.94E-1 1 1.08E-07 1.59E-11 4.79E-07 6.61 E-06 2.13E-05 1.69E-06 9.13E-06 8.92E-07 3.62E-06 8.93E-05 2.58E-05 7.63E-05 1.68E-07 2.33E-13 5.71 E-09 2.56E-14 7.87E-15 0.00E+00 0.OOE+00 2.31 E-06 2.26E-08 3.17E-04 8.11 E-07 2.64E-1 2 1.30E-06 0.00E+00 2.63E-08 lung 8.76E-04 6.27E-04 2.43E-04 1.29E-04 4.OOE-04 2.71 E-06 4.76E-04 7.93E-07 5.56E-05 5.55E-07 1.02E-04 0.OOE+00 0.00E+00 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 3.27E-05 3.93E-06 2.81 E-05 1.84E-08 1.56E-06 4.71 E-04 7.89E-07 4.44E-07 4.94E-05 2.35E-06 1.47E-04 3.12E-05 3.23E-03 1.17E-04 4.23E-07 8.87E-05 1.11E-05 1.57E-05 gi-Ili 4.43E-05 1.09E-05 7.17E-05 9.13E-06 1.93E-05 1.52E-05 4.91 E-05 6.89E-06 8.32E-05 3.60E-07 3.72E-05 1.38E-06 7.68E-07 8.65E-07 1.48E-06 2.58E-07 1.20E-06 1.04E-06 1.13E-06 9.78E-07 7.29E-08 1.56E-05 2.75E-05 7.44E-08 7.41 E-10 6.10E-05 2.05E-05 1.53E-05 3.44E-05 1.05E-04 2.63E-05 5.32E-08 2.22E-05 2.46E-05 1.73E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-9.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 57 Page 150 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 7 of 8)INFANT bone liver t body thyroid kidney lung gi-Ili H-3 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 C-14 1.89E-05 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 Na-24 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 P-32 1.45E-03 8.03E+05 5.53E-05 0.OOE+00 0.OOE+00 0.OOE+00 1.15E-05 Cr-51 O.OOE+00 0.OOE+00 6.39E-08 4.11E-08 9.45E-09 9.17E-06 2.55E-07 Mn-54 0.OOE+00 1.81E-05 3.56E-06 0.OOE+00 3.56E-06 7.14E-04 5.04E-06 Mn-56 0.OOE+00 1.10E-09 1.58E-10 0.OOE+00 7.86E-10 8.95E-06 5.12E-05 Fe-55 1.41 E-05 8.39E-06 2.38E-06 0.OOE+00 O.OOE+00 6.21 E-05 7.82E-07 Fe-59 9.69E-06 1.68E-05 6.77E-06 0.OOE+00 0.OOE+00 7.25E-04 1.77E-05 Co-57 0.OOE+00 4.65E-07 4.58E-07 0.OOE+00 0.OOE+00 2.71E-04 3.47E-06 Co-58 0.OOE+00 8.71E-07 1.30E-06 O.OOE+00 0.OOE+00 5.55E-04 7.95E-06 Co-60 0.OOE+00 5.73E-06 8.41E-06 0.OOE+00 O.OOE+00 3.22E-03 2.28E-05 Ni-63 2.42E-04 1.46E-05 8.29E-06 0.OOE+00 0.OOE+00 1.49E-04 1.73E-06 Ni-65 1.71E-09 2.03E-10 8.79E-11 O.OOE+00 0.OOE+00 5.80E-06 3.58E-05 Cu-64 0.OOE+00 1.34E-09 5.53E-10 O.OOE+00 2.84E-09 6.64E-06 1.07E-05 Zn-65 1.38E-05 4.47E-05 2.22E-05 O.OOE+00 2.32E-05 4.62E-04 3.67E-05 Zn-69 3.85E-11 6.91E-11 5.13E-12 0.OOE+00 2.87E-11 1.05E-06 9.44E-06 Zn-69m 8.98E-09 1.84E-08 1.67E-09 O.OOE+00 7.45E-09 1.91 E-05 2.92E-05 Br-82 0.OOE+00 0.OOE+00 9.49E-06 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 2.72E-07 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 Br-84 0.OOE+00 0.OOE+00 2.86E-07 O.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 Br-85 0.OOE+00 0.OOE+00 1.46E-08 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 Rb-86 0.OOE+00 1.36E-04 6.30E-05 0.OOE+00 0.OOE+00 0.OOE+00 2.17E-06 Rb-88 O.OOE+00 3.98E-07 2.05E-07 O.OOE+00 0.OOE+00 0.OOE+00 2.42E-07 Rb-89 0.OOE+00 2.29E-07 1.47E-07 0.OOE+00 0.OOE+00 0.OOE+00 4.87E-08 Sr-89 2.84E-04 0.OOE+00 8.15E-06 O.OOE+00 0.OOE+00 1.45E-03 4.57E-05 Sr-90 2.92E-02 0.OOE+00 1.85E-03 0.OOE+00 0.00E+00 8.03E-03 9.36E-05 Sr-91 6.83E-08 O.OOE+00 2.47E-09 O.OOE+00 0.OOE+00 3.76E-05 5.24E-05 Sr-92 7.50E-09 0.OOE+00 2.79E-10 0.OOE+00 O.OOE+00 1.70E-05 1.OOE-04 Y-90 2.35E-06 O.OOE+00 6.30E-08 0.OOE+00 0.OOE+00 1.92E-04 7.43E-05 Y-91m 2.91E-10 O.OOE+00 9.90E-12 O.OOE+00 0.OOE+00 1.99E-06 1.68E-06 Y-91 4.20E-04 O.OOE+00 1.12E-05 0.OOE+00 0.OOE+00 1.75E-03 5.02E-05 Y-92 1.17E-08 0.OOE+00 3.29E-10 O.OOE+00 O.OOE+00 1.75E-05 9.04E-05 Y-93 1.07E-07 0.OOE+00 2.91E-09 O.OOE+00 0.OOE+00 5.46E-05 1.19E-04 Zr-95 8.24E-05 1.99E-05 1.45E-05 O.OOE+00 2.22E-05 1.25E-03 1.55E-05 Zr-97 1.07E-07 1.83E-08 8.36E-09 O.OOE+00 1.85E-08 7.88E-05 1.OOE-04 Nb-95 1.12E-05 4.59E-06 2.70E-06 0.OOE+00 3.37E-06 3.42E-04 9.05E-06 Nb-97 2.44E-10 5.21E-11 1.88E-11 0.OOE+00 4.07E-11 2.37E-06 1.92E-05 Mo-99 0.OOE+00 1.18E-07 2.31E-08 0.OOE+00 1.89E-07 9.63E-05 3.48E-05 Tc-99m 9.98E-13 2.06E-12 2.66E-11 O.OOE+00 2.22E-11 5.79E-07 1.45E-06 Tc-101 4.65E-14 5.88E-14 5.80E-13 0.OOE+00 6.99E-13 4.17E-07 6.03E-07 Ru-103 1.44E-06 0.OOE+00 4.85E-07 0.OOE+00 3.03E-06 3.94E-04 1.15E-05 Ru-105 8.74E-10 0.OOE+00 2.93E-10 0.OOE+00 6.42E-10 1.12E-05 3.46E-05 Ru-106 6.20E-05 0.OOE+00 7.77E-06 O.OOE+00 7.61E-05 8.26E-03 1.17E-04 Ag-110m 7.13E-06 5.16E-06 3.57E-06 0.OOE+00 7.80E-06 2.62E-03 2.36E-05 SQN ODCM Revision 57 Page 151 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 8 of 8)INFANT Sb-1i24 Sb-1i25 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-1 31 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 2.71 E-05 3.69E-05 1.01E-05 3.40E-06 1.19E-05 1.59E-09 1.01E-05 5.63E-1 1 7.62E-08 1.24E-11 2.66E-07 4.54E-06 2.71 E-05 1.21 E-06 9.46E-06 6.58E-07 2.76E-06 2.83E-04 3.45E-05 3.92E-04 3.61 E-07 1.06E-09 4.00E-05 1.12E-10 2.84E-11 3.61 E-07 7.36E-1 0 1.98E-05 2.09E-07 2.28E-03 1.00E-05 3.42E-11 5.67E-06 9.26E-09 2.65E-07 liver 3.97E-07 3.41 E-07 2.51 E-07 1.42E-06 4.93E-06 6.81E-10 4.35E-06 2.48E-1 1 3.93E-08 5.87E-12 1.69E-07 9.91 E-06 3.17E-05 2.53E-06 1.37E-05 1.34E-06 5.43E-06 5.02E-04 9.61 E-05 4.37E-04 5.58E-07 7.03E-13 4.00E-08 7.70E-14 2.36E-14 1.43E-07 2.69E-10 1.19E-05 1.38E-07 8.65E-04 3.74E-06 1.32E-11 5.81 E-06 6.44E-09 2.37E-08 t body 8.56E-06 7.78E-06 6.00E-07 4.70E-07 1.48E-06 3.49E-10 1.59E-06 1.34E-11 2.59E-08 3.57E-12 1.26E-07 3.98E-06 1.40E-05 8.99E-07 4.00E-06 4.75E-07 1.98E-06 5.32E-05 3.78E-05 3.25E-05 2.84E-07 3.07E-11 2.07E-06 3.55E-12 1.40E-12 3.68E-08 6.46E-1 1 1.42E-06 1.58E-08 1.26E-04 4.99E-07 1.72E-12 3.57E-07 2.23E-09 1.34E-08 thyroid 7.18E-08 4.45E-08 2.47E-07 1.16E-06 3.48E-06 1.32E-09 3.91 E-06 4.82E-11 6.38E-08 1.13E-11 1.99E-07 1.14E-03 1.06E-02 1.21 E-04 2.54E-03 3.18E-05 4.97E-04 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.00E+00 0.00E+00 0.00E+00 O.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 kidney 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 2.68E-05 3.47E-09 2.27E-05 1.25E-10 1.89E-07 2.85E-1 1 7.39E-07 1.09E-05 3.70E-05 2.82E-06 1.60E-05 1.49E-06 6.05E-06 1.36E-04 4.03E-05 1.23E-04 2.93E-07 4.23E-1 3 9.59E-09 4.64E-14 1.36E-14 0.00E+00 0.00E+00 3.75E-06 4.03E-08 3.84E-04 1.41E-06 4.80E-12 2.25E-06 0.OOE+00 4.73E-08 lung 1.89E-03 1.17E-03 6.43E-04 3.19E-04 9.37E-04 7.39E-06 1.20E-03 2.14E-06 1.42E-04 1.47E-06 2.43E-04 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 5.69E-05 8.40E-06 5.09E-05 4.67E-08 4.25E-06 1.14E-03 2.12E-06 1.11E-06 1.20E-04 5.87E-06 3.69E-04 8.30E-05 7.03E-03 3.09E-04 1.15E-06 2.30E-04 2.83E-05 4.25E-05 gi-Ili 4.22E-05 1.05E-05 7.26E-05 9.22E-06 1.95E-05 1.74E-05 4.93E-05 1.88E-05 8.51 E-05 5.87E-06 3.15E-05 1.42E-06 7.56E-07 1.36E-06 1.54E-06 9.21 E-07 1.31 E-06 9.53E-07 1.02E-06 9.53E-07 6.26E-07 3.64E-05 2.74E-05 3.39E-06 4.95E-07 6.06E-05 4.25E-05 1.54E-05 3.55E-05 1.06E-04 2.66E-05 3.06E-06 2.23E-05 2.54E-05 1.78E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-10.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 57 Page 152 of 179 Figure 7.1 GASEOUS EFFLUENT RELEASE POINTS Service Building Vent 1,2-RE-90-99 1,2-RE-90-119 o-t Machine Office and Genil Area O-RE-90-1 32 Geea A~rea inside RCA jC~hemistry Lab Titration Room SERVICE BUILDING TURBINE AUXILIARY SHIELD BUILDING BUILDING BUILDING SQN ODCM Revision 57 Page 153 of 179 Condenser Auxiliary Vacuum Building S,
- Vent Service Building Vent SERVICE TURBINE BUILDING BUILDING AUXILIARY SHIELD BUILDING BUILDING SQN ODCM Revision 57 Page 154 of 179 Figure 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL)(All Vents Are Considered Ground Level)Shield Building Vent i SQN ODCM Revision 57 Page 155 of 179 Figure 7.3 GASEOUS RADWASTE TREATMENT SYSTEM (All Vents Are Considered Ground Level)RCUT-unit I K->W W23= Gas-T",ýx*:tý(1-ý a(7)=aý SQN ODCM Revision 57 Page 156 of 179 Figure 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES (All Stability Classes)I I 1111111 1.t!1!II I JILl! ffZi~qi ~ ii 111111 _____-___ i~ij. lB Ji~ .---~ It I H I 11111111 11111111.1 11111111 I IlIllill I Iiiiiiii I'- I 1111111 1.1 1111111 11 0~ '.0 .0.0 '~.0 2W0 0 , 1.0 ,0.0 SQN ODCM Revision 57 Page 157 of 179 Figure 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME w w 6 I I 1X V11 I Il I111 jl,ý I 1 11 IQI I IA I I 1 1.I 10l 10ia udr eitono ~r2 n2P~n ii;er deot Pajii Stabit Class'at.
SQN ODCM Revision 57 Page 158 of 179 Figure 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES (All Stability Classes)w uJ C-C 0 C-Lu 0 I I ill I 1 1 111111 1 _1_1_H I___________
________ I HIM_____I I I I r",< I I II I I I f l I II t 'll I1 I1I1 1111111 I~~~~~ I 111i f I II HIM%=47V 0.1A------------IU.LJ ME4 Th.Av-= DIST"LCE (XL0MET=-S) 0002cc.0;:ý_U R.o irm Depmitiz izr Gcr--,,3ý P-wa&,K (AJ Ar=s;r- matzkY C-)
SQN ODCM Revision 57 Page 159 of 179 SECTION 8.0 TOTAL DOSE SQN ODCM Revision 57 Page 160 of 179 SECTION 8.0 TOTAL DOSE 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES -TOTAL REPORTED DOSE To determine compliance with 40 CFR 190 as required in ODCM Administrative Control 5.2, the annual dose contributions to the maximum individual from SQN radioactive effluents and all other nearby uranium fuel cycle sources will be considered.
The annual dose to the maximum individual will be conservatively estimated by first, summing the quarterly total body air submersion dose, the quarterly critical organ dose from gaseous effluents, the quarterly total body dose from liquid effluents, the quarterly critical organ dose from liquid effluents, and the direct radiation monitoring program, and then taking the sum for each quarter and summing over the four quarters.
The table below represents the above verbal description and relative values: First Second Third Fourth Dose Quarter Quarter Quarter Quarter Total Body or any Organ (except thyroid)Total body air submersion 9.79E-04 9.OOE-04 1.65E-03 4.27E-04 Critical organ dose (air) 9.48E-03 9.40E-03 3.77E-03 9.37E-03 Total body dose (liquid) 4.8E-03 2.1E-02 3.8E-02 6.5E-03 Maximum organ dose (liquid) 5.8E-03 2.6E-02 5.OE-02 2.OE-02 Direct Radiation Dose 0.OE-00 0.OE-00 O.OE-00 0.OOE-00 Total 2.1E-02 5.7E-02 9.3E-02 3.6E-02 Cumulative Total Dose (Total body or any other organ) mrem 2.1E-01 Annual Dose Limit (mrem) 2.50E+01 Percent of Limit <1%
SQN ODCM Revision 57 Page 161 of 179 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM SQN ODCM Revision 57 Page 162 of 179 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM 9.1 MONITORING PROGRAM An environmental radiological monitoring program shall be conducted in accordance with ODCM Control 1.3.1.The monitoring program described in Tables 9.1, 9.2, and 9.3, and in Figures 9.1, 9.2 and 9.3 shall be conducted.
Results of this program shall be reported in accordance with ODCM Administrative Control 5.1.The atmospheric environmental radiological monitoring program shall consist of monitoring stations from which samples of air particulates and atmospheric radioiodine shall be collected.
The terrestrial monitoring program shall consist of the collection of milk, soil, ground water, drinking water, and food crops. In addition, direct gamma radiation levels will be measured in the vicinity of the plant.The reservoir sampling program shall consist of the collection of samples of surface water, sediment, clams, and fish.Deviations are permitted from the required sampling schedule if specimens are unobtainable due to hazardous conditions, sample unavailability, or to malfunction of sampling equipment.
If the latter, every effort shall be made to complete corrective action prior to the end of the next sampling period.9.2 DETECTION CAPABILITIES Analytical techniques shall be such that the detection capabilities listed in Table 2.3-3 are achieved.9.3 LAND USE CENSUS A land use survey shall be conducted in accordance with Control 1.3.2. The results of the survey shall be reported in the Annual Radiological Environmental Operating Report.9.4 INTERLABORATORY COMPARISON PROGRAM Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the NRC. A summary of the results obtained in the intercomparison shall be included in the Annual Radiological Environmental Operating Report (or the EPA program code designation may be provided).
If analyses are not performed as required corrective actions taken to prevent a recurrence shall be reported in the Annual Radiological Environmental Operating Report.
SQN ODCM Revision 57 Page 163 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 4)Exposure Pathway and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
AIRBORNE Particulates 4 samples from locations (in different sectors) at or near the site boundary (LM-2,3,4,and 5)4 samples from communities approximately 6-10 miles distance from the plant.(PM-2,3,8,and 9)4 samples from control locations greater than 10 miles from the plant (RM-1,2,3,and 4)Continuous sampler operation with sample collection once per 7 d (more frequently if required by dust loading)Analyze for gross beta radioactivity
> 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following filter change.Perform gamma isotopic analysis on each sample if gross beta > 10 times yearly mean of control sample.Composite at least once per 31 d (by location for gamma scan)Radioiodine Samples from same Continuous sampler 1-131 at least once per location as air particulates operation with filter 7 d collection once per 7 d Soil Samples from same Once per year Gamma scan, Sr-89, locations as air Sr-90 once per year particulates DIRECT RADIATION 2 or more DOSIMETER's Once per 92 d Gamma dose at least placed at locations (in once per 92 d different sectors at or near the site boundary) in each of the 16 sectors.* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3 SQN ODCM Revision 57 Page 164 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 4)Exposure Pathway and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
DIRECT RADIATION (continued) 2 or more DOSIMETER's placed at stations located approximately 5 miles from the plant in each of the 16 sectors 2 or more dosimeters in at least 8 additional locations of special interest.WATERBORNE Surface TRM 503.8*** Collected by Gamma scan of each TRM 483.4 automatic sequential composite sample.type sampler**
with Composite for H-3 composite samples analysis at least once collected at least per 92 d.once per 31 d.Ground 1 sample adjacent to At least once per 92 d Gross beta and gamma plant (location W-6) scan and H-3 analysis at least once per 92 d.1 sample from groundwater source up-gradient* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.Sample used as control for surface water and drinking water.
SQN ODCM Revision 57 Page 165 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 3 of 4)Exposure Pathway and/or Sample Sampling and Collection Freauencv Type and Frequency of Analysis Sample Locations*
WATERBORNE (continued)
Drinking 1 sample at the first potable water supply downstream from the plant (TRM 473.0)1 sample at the next 2 downstream potable surface water supplies (greater than 10 miles downstream)(TRM 469.9 and 465.3)1 sample at a control location upstream from the plant (TRM 503.8)***Collected by automatic sequential type sampler**with composite samples collected at least once per 31 d Grab sample once per 31 d.Samples collected by automatic sequential type sampler**
with composite sample collected at least once per 31 d.Gross beta and gamma scan of each composite sample.Composite for H-3, at least once per 92 d.Shoreline TRM 485, TRM 480, TRM At least once per 184 d Gamma scan of Sediment 479 each sample.INGESTION Milk 1 sample from milk producing At least once per 15 d. Gamma isotopic animals in each of 1-3 areas and 1-131 analysis indicated by the cow census of each sample.where doses are calculated to Sr-89, Sr-90 once be highest. per year.If samples are not available from a milk animal location, doses to that area will be estimated by projecting the doses from concentrations detected in milk from other sectors or samples of vegetation will be taken monthly when milk is not available.
At least 1 sample from a control location.Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.*** Sample location is considered a control for drinking water and surface water.
SQN ODCM Revision 57 Page 166 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 4 of 4)Exposure Pathway and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
INGESTION
.. ..Fish 1 sample each from At least once per 184 Gamma scan on edible Chickamauga and Watts d. One sample portion.Bar Reservoirs.
representing a commercially important species and one sample representing a recreationally important species.Food 1 sample each of At least once per 365 d Gamma scan on edible Products principle food products at time of harvest. The portion.grown at private gardens types of foods and/or farms in the available for sampling vicinity of the plant. will vary. Following is a list of typical foods which may be available:
Cabbage and/or lettuce Corn Green Beans Potatoes Tomatoes Vegetation**
Samples from farms At least once per 31 d 1-131 and gamma scan producing milk but not at least once per 31 d providing a milk sample Control Sample from one control dairy farm* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Vegetation sampling is applicable only for farms that meet the criteria for milk sampling and when implementation of milk sampling is not possible.
SQN ODCM Revision 57 Page 167 of 179 Table 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS Map Location Numbera 2 3 4 5 7 8 9 10 11 12 13 14 Station LM-2 LM-3 LM-4 LM-5 PM-2 PM-3 PM-8 PM-9 RM-1 RM-2 RM-3 RM-4 Sector N SSW NE NNE SW W SSW WSW SW NNE ESE NW Approximate Distance 0.7 2.0 1.5 1.8 3.8 5.6 8.7 2.6 16.7 17.8 11.3 20.0 Indicator (I)or Control C C C C Samples Collectedb AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S 19 21 23 24 25 31 32 33 34 35 37 38 40 44 46 47 Farm HW Farm HS Farm EH Well No. 6 Farm K TRM 473.0 East Side Utility ( Formally C. F. Industries)
TRM 469.9 (E. I. DuPont)TRM 465.3 (Chattanooga)
Deleted (R 40)TRM 503.8 (Dayton)TRM 485.0 TRM 483.4 TRM 479.0 TRM 480.0 Chickamauga Reservoir Watts Bar Reservoir NW E ENE NNE NE 1.2 4.6 9.5 0.15 40 10.7 C I C I M, W M M W M PW PW PW.. 13.8__ 18.4-- 20.1-- 1.3-- 0.3-- 4.7-- 3.7 SW,PW C C SS SW SS SS F F b See figures 9.1,9.2, and 9.3 Sample Codes: AP = Air particulate filter CF = Charcoal filter M = Milk PW = Public water R = Rainwater SS = Shoreline sediment SW = Surface water C d A control for well water.TRM = Tennessee River Mile.e Distance from plant discharge (TRM 483.7) in river miles.Sample also used as a control for public water and surface water.F = Fish S = Soil W = Well water SQN ODCM Revision 57 Page 168 of 179 Map Location Number 3 4 5 7 8 9 10 11 12 13 14 49 50 51 52 53 55 56 57 58 59 60 62 63 66 67 68 69 70 71 72 73 74 Sta SS'NE NN SWA W-: SS\WS SW\NN ES NWA N-1 N-2 N-3 N-4 NN NE NE EN EN E-1 E-2 ES ES SE SE SE SS SS S-1 S-2 SS SS Table 9.3 THERMOLUMINESCENT DOSIMETRY (Page 1 of 2)Approximate Distance tion Sector (Miles)W-1C SSW 2.0-1A NE 1.5 E-1 NNE 1.8 (-2 SW 3.8 3 W 5.6 W-3 SSW 8.7;W-2A WSW 2.6 (-3 SW 16.7 E-4 NNE 17.8 E-3 ESE 11.3 V-3 NW 20.0 N 0.6 N 2.1 N 5.2 N 10.0 E-2 NNE 5.3-1 NE 2.4-2 NE 4.1 E-1 ENE 0.2 E-2 ENE 5.1 E 1.2 E 5.2 E-1 ESE 1.2 E-2 ESE 4.9-1 SE 1.4-2 SE 1.9-4 SE 5.2 E-1 SSE 1.6 E-2 SSE 4.6 S 1.5 S 4.7 W-1 SSW 0.6 W-2 SSW 4.0 LOCATIONS (Onsite )a or Offsite (Off)On On On Off Off Off Off Off Off Off Off On Off Off Off Off Off Off On Off On Off On Off On On Off On Off On Off On Off aDOSIMETERs designated onsite are those located two miles or less from the plant.DOSIMETERs designated offsite are those located more than two miles from the plant.
SQN ODCM Revision 57 Page 169 of 179 Table 9.3 THERMOLUMINESCENT DOSIMETRY LOCATIONS (Page 2 of 2)Map Location Number 75 76 77 78 79 81 82 83 84 85 86 87 88 89 90 Station SW-1 WSW-1 WSW-2 WSW-3 WSW-4 W-1 W-2 WNW-1 WNW-2 NW-1 NW-2 NNW-1 NNW-2 NNW-3 SSW-1B Sector SW WSW WSW WSW WSW W W WNW WNW NW NW NNW NNW NNW SSW Approximate Distance (Miles)0.7 0.9 2.5 5.7 7.8 0.6 4.3 0.4 5.3 0.4 5.2 0.6 1.7 5.3 1.5 Onsite (On)a or Offsite (Off)On On Off Off Off On Off On Off On Off On On Off On aDOSIMETERs designated onsite are those located two miles or less from the plant.DOSIMETERs designated offsite are those located more than two miles from the plant.
SQN ODCM Revision 57 Page 170 of 179 Figure 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT Scale 0 MIile 0 Mile I SQN ODCM Revision 57 Page 171 of 179 Figure 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT NWn N n1n WNW1-.78j$5 28.75"Is-112 8CALE MILES SQN ODCM Revision 57 Page 172 of 179 Figure 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT SCALE o --- 1 l 20 2-SQN ODCM Revision 57 Page 173 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 1 of 7)This Appendix establishes the minimum requirements for preparation, review, and approval of the Sequoyah Nuclear Plant Offsite Dose Calculation Manual. This Appendix also implements the requirements of ODCM Section 5.3 and SQN TS.1.0 Reviewer Responsibilities
1.1 Affected
Organization Review (AOR)The identification of affected organizations is the responsibility of the Sponsor and applies to all revisions of the ODCM.The affected organizations shall ensure that their reviewers have adequate understanding of the requirements and intent of the ODCM and access to pertinent background information.
The AO reviews the draft for impact on the organization and adequate interface
-not technical content.1.2 Independent Qualified Review (IQR)An independent qualified review is the process of independent technical review by Qualified Reviewers of activities potentially affecting nuclear safety.The IQR shall NOT be the person who prepared the ODCM revision.An IQR is performed by an individual designated by responsible department level managers to perform an independent technical review of activities potentially affecting nuclear safety.The IQR must be qualified to perform 10 CFR 50.59 review.1.3 Cross Disciplinary Review (CDR)The need for a CDR is determined by the IQR.CDR is a technical review by disciplines other than those responsible for the document preparation.
The CDR is responsible for only the technical aspects of the areas specified by the IQR and any portions of the document that support or justify those areas.Persons performing CDR do not have to be IQR qualified.
1.4 Plant
Operations Review Committee (PORC) Review The PORC reviews the ODCM.
SQN ODCM Revision 57 Page 174 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 2 of 7)1.5 Approval Authority The Plant Manager or designee will approve all revisions to the ODCM as required by Technical Specifications.
2.0 Processing
ODCM Revisions 2.1 Requester (If other than the Sponsor)Identify the need for an ODCM improvement.
Prepare a justification for the ODCM revision.Attach a marked-up copy of the existing ODCM.Forward the requested ODCM revision to the sponsoring organization.
2.2 0DCM Sponsor Evaluate requested changes and determine if necessary.
If the requested change is not necessary, return the request to the requester with explanation why the change is not needed.Incorporate all changes in a draft revision on BSL.Complete the top portion of Attachment B for each organization.
Distribute Attachment B to each Affected Organization and request completion of the review prior to expected PORC review date.Obtain appropriate reviews of the ODCM revision in BSL.2.3 Reviews 2.3.1 IQR Review the ODCM using all questions on Attachment C as a guideline and forward comments to the Sponsor.Identify discipline or organization to perform CDR, if needed.
SQN ODCM Revision 57 Page 175 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 3 of 7)2.3.2 Affected Organization Reviewer Review the proposed changes on BSL and provide comments to the ODCM Sponsor.Review the ODCM for impact on assigned organization, identify procedures/documents which require revision to implement the ODCM revision on the Attachment B, and return the Attachment B to the ODCM Sponsor.2.4 Sponsor If revision includes surveillance requirement or performance frequency changes then review SI/SR matrix for impact.Resolve comments and obtain reviewer's concurrence in BSL. Escalate any unresolved comments to appropriate management.
Ensure ODCM has been reviewed by sponsor and IQR in accordance with Attachment C.Ensure all Affected Organizations have reviewed the ODCM change and have identified the affected procedures on Attachment B.Ensure all IQR and CDR review requirements have been met.Assign an Effective Date typically 60 calendar days forward UNLESS there is reasonable justification for making it effective earlier, such as plant operating conditions, test schedules, commitment or corrective action deadlines, or implementation of upper-tier requirements, or lack of affected procedures identified on Attachment B.2.5 PORC Review Changes and document recommendation for approval in BSL.2.6 Plant Manager Approve the ODCM revision in BSL.2.7 ODCM Sponsor Record the ODCM approval date and implementation date on each completed Attachment B provided by the affected organizations.
Return the Attachment B to each affected organization.
2.8 Affected
Organization Revise procedures identified on the Attachment B and assign an effective date which matches that of the ODCM revision.Complete the Attachment B and return to the ODCM Sponsor.
SQN ODCM Revision 57 Page 176 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 4 of 7)2.9 ODCM Sponsor Ensure all Affected Organizations have completed and returned Attachment B prior to the effective date of the ODCM.Forward the approved ODCM change to Management Services at least three working days before the implementation date.The completed Attachments B and C are QA records, and are handled in accordance with the Document Control and Records Management Program.Forward a completed copy of each revision to Licensing to be filed and forwarded to the NRC in the Annual Radiological Effluent Release Report.2.10 Management Services Issue the ODCM and implementing procedures on the effective date of the ODCM revision.
SQN ODCM Revision 57 Page 177 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 5 of 7)Attachment B ODCM Affected Organization Review/Implementation Proposed ODCM Revision No.Expected PORC Review Date: Expected Effective Date: Affected Organization:
[ Operations
[] RADCON[ Chemistry
[] Maintenance Technical Support [ ] Scheduling Engineering
[ Licensing Operations Training [] Technical Training[ Emergency Preparedness
[ ] Other The following procedures/documents will require revision to implement this ODCM change: PROCEDURE/DOCUMENT PROCEDURE/DOCUMENT ODCM Approval Date: ODCM Effective Date: The required procedure/document revisions to support this ODCM revision have been completed and have an implementation date which matches that given above for the ODCM revision./Affected Organization Date SQN ODCM Revision 57 Page 178 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 6 of 7)Attachment C ODCM Review Checklist All questions of this checklist are considered by the ODCM preparer and reviewed by the Independent Qualified Reviewer (IQR). Only the revised portion of the ODCM should be evaluated.
Changes to Section(s) 1.0-5.0 YES NO N/A 1. Does the revision meet the intent of the guidance provided in NUREG-1301 for radiological effluent and environmental monitoring controls/surveillance requirements?
- 2. Do definitions in Section 3.0 match those provided in the SQN TS, NUREG-1301, or other NRC guidance?3. Do Administrative Controls in Section 5.0 match those provided in SQN TS, NUREG-1301, or other NRC guidance?4. Does the ODCM fulfill the requirements of TVA, Federal or State Laws, SQN FSAR, and any other referenced requirements documents?
- 5. Does the numbering of the Control and its accompanying Surveillance Requirement correspond?
- 6. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
- 7. Does nomenclature accurately describe the equipment and correspond to label identifiers?
- 8. Are referenced documents applicable, valid, and listed in the reference section?9. Does this change maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 1- CFR Part 50.36a, and Appendix I to 10 CFR Part 50? Provide justification for answer: 10. Are there methodologies given in Sections 6.0 through 9.0 which implement the applicable ODCM Controls?11. Are references to ODCM Controls and Surveillance Requirements accurate and correct?12. Are changes to setpoint calculation methodologies consistent with the guidance provided in NUREG-0133?
SQN ODCM Revision 57 Page 179 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 7 of 7)Attachment C ODCM Review Checklist (continued)
Changes to Section(s) 6.0-11.0 YES NO N/A 13. Are changes to liquid effluent concentration compliance methodologies consistent with the guidance provided in NUREG-0133 and 10 CFR Part 20?14. Are changes to gaseous effluent dose rate calculation/compliance methodologies consistent with the guidance provided in NUREG-0133 and/or Regulatory Guide 1.109?15. Are changes to dose or dose projection calculation/compliance methodologies consistent with the guidance provided in NUREG-0133 and/or Regulatory Guide 1.109?16. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
- 17. Are referenced documents applicable, valid, and listed in the references?
- 18. Are ODCM Sections numbered consistently and consecutively?
- 19. Are references to other ODCM Sections correct?20. Are references to ODCM Tables and Figures accurate and correct?21. Are any new acronyms defined in Appendix A?22. Are equations numbered consecutively?
- 23. Does dimensional analysis yield the correct units for equations?
- 24. Are terms used in equations defined after the equation (and in Appendix A) and the proper units given for that term?25. Do units on equation terms which reference tables match the units used for that term in the Table?26. Are references given for table and other values correct and accurate?27. Do data values given match those in the reference?
- 28. Do text descriptions of release/discharge points in Sections 6.0 and 7.0 correspond with the Figures referenced in those sections?29 Will change affect the NOUE and ALERT calculation values in SQS20247.30. The change does not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations?
Provide justification for answer:/Preparer Date/IQR Date SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL Revision 58 Prepared By: George D. Flaherty Sponsor: Toney Cross Date: 12/06/2012 PORC Review:
nigm-rrmann r%ý#: 12/10/2012 Approval--Plant Manager: Paul Simmons Date: 12/13/2012 Effective Date: 12/17/2012 SQN ODCM Revision 58 Page 2 of 179 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL REVISION LOG (Page 1 of 2)Revision Effective Description of Revision Number Date 51 11/24/2006 DCN 21837 Turbine Building Sump Radiation Monitor (0-RM-90-212)
Replacement also provides Flow on ICS. ICS Computer Point (0-F-4300A) is being made a compliance point.52 01/04/2007 Replaced thermoluminescent dosimeter with dosimeter.
WARL is switching to Vendor supplied dosimeter.
53 04/30/2008 Deleted 30,000 pCi/L Tritium non drinking water pathway, based on new NEI reporting guidelines for Tritium in groundwater.
Added wording to allow 0-RE-90-122 setpoint to be set at a default setpoint.54 12/05/2008 Added containment radiation monitors as compliance instruments due to Exigent TSC 08-07 request. Added reporting requirements for NEI-07-07 compliance.
55 02/17/2009 Added clarification to action 48 on page 22 for purging containment if containment radiation is not operable.56 09/21/2010 Page 15 added clarification for weir overflowing.Page 45 Added Table 2.3-4 LLD's for HTD nuclides for groundwater.
Pages 104, 106, 107, 108, 109, 110 updated x/Q. Page 109 updated D/Q. Pages 107, 108, 109, 110 and 112 updated dates for x/Q and or D/Q. Page 132 and 133 updated meteorological data for x/Q and D/Q. Page 171 added to checklist to check if revision affects NOUE and ALERT calculation values in SQS20247.57 05/30/2012 PER 361162 corrected date range on Table 7.1 and 7.2 header, pages 139 and 140. PER 361162 corrected schematic page 152. PER 463540 changed radiation monitor testing frequency from quarterly to semi-annually, pages 16 and 22. OPS request to clarify applicability note for page 19, item 2.b. Add C-14 to dose calculations to meet NRC requirement to incorporate C-14 in Site Annual Report.Added statement that C-14 will be estimated using EPRI methodology, EPRI report 1021106. NRC has accepted this method for providing C-14 estimates.
This updates pages 111,115,116,&129-134.
Correction made to Sr-89 and Sr-90 LLD on page 44.58 12/17/2012 PER 622625 removes thermoluminescent from pages 7, 168& 169.
SQN ODCM Revision 58 Page 3 of 179 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL REVISION LOG (Page 1 of 2)Revision Approval Date Revision Approval Date Effective Date Original ODCM 2/29/801 Revision 28 9/22/926 12/1/92 Revision 1 4/15/80' Revision 29 3/30/932 Revision 2 10/7/802 Revision 30 9/30/932 Revision 3 11/3/80, 2/10181, Revision 31 10/13/93z 4/8/81, 6/4/812 Revision 4 10/22/81, 11/28/81, Revision 32 11/29/932 1/1/94 4/29/82, 11/22/822 Revision 5 10/21/82z Revision 33 2/25/942 Revision 6 1/20/832 Revision 34 4/29/94z 5/15/94 Revision 7 3/23/832 Revision 35 10/20/94" 11/15/94 Revision 8 12/16/832 Revision 36 7/20/956 8/4/95 Revision 9 3/7/84z Revision 37 10/26/955 11/6/95 Revision 10 4/24/842 Revision 38 2/1 5/96 2/23/96 Revision 11 8/21/84 Revision 39 11/12/96b 1/17/97 Revision 12 2/19/852 Revision 40 4/2/98j 4/23/98 Revision 13 12/02/852 Revision 41 8/7/98 8/11/98 Revision 14 4/14/86z Revision 42 4/29/99 4/30/99 Revision 15 11/5/863 Revision 43 4/29/99 4/30/99 Revision 16 1/16/872 Revision 44 6/17/99" 6/21/99 Revision 17 10/28/87z Revision 45 2/17/00' 3/1/00 Revision 18 1/5/882 Revision 46 10/6/01 10/9/01 Revision 19 3/30/88z Revision 47 1/13/03 1/15/03 Revision 20 7/19/88' Revision 48 8/21/05 8/21/05 Revision 20A 12/14/882 Revision 49 5/17/06 5/23/06 Revision 21 2/15/892 Revision 50 9/29/06 9/29/06 Revision 22 6/1/892 See footnote 7 Revision 23 6/28/89, 9/15/89 _Revision 25 11/2/90, 4/24/912 Revision 26 1/17/92_ _Revision 27 4/15/922 Revision 28 9/22/926' Low power license for Sequoyah Unit 1.2 RARC Meeting Date.3 Date approved by RARC Chairman.4 Revision 23 implements the Nuclear Data Effluent Management Software.
This ODCM revision and the software will be implemented concurrently on October 9, 1989. Releases made during the month of October prior to the software implementation will be backfitted to comply with this revision.5 Revision 26 was recommended for approval by the SQN RARC at the October 2, 1991 meeting.The revision date is January 17, 1992. The final implementation date for Revision 26 will be March 17, 1992.6 PORC Meeting Date.7 New revision log started.
SQN ODCM Revision 58 Page 4 of 179 INTRODUCTION
...................................................................................................................................................................
8 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS
.........................................................................................
11 1/2 .0 A P P L IC A B IL IT Y .........................................................................................................................................................
11 1 I/2.1 IN ST R U M E N T A T IO N ..................................................................................................................................................
13 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION
................................................
13 TABLE 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION
.........................................
14 TABLE 2.1-1 -RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE R E Q U IRE M E N T S ..................................................................................................................................................................
16 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
...........................................
18 TABLE 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
....................................
19 TABLE 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE RE Q U IRE M E N T S ..................................................................................................................................................................
22 1/2.2 RADIOACTIVE EFFLUENTS
......................................................................................................................................
24 1/2 .2.1 L IQ U ID E F FL U E N T S ................................................................................................................................................
24 1/2.2.1.1 C O N C E N T R A T IO N ................................................................................................................................................
24 TABLE 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM .......................................
25 1/2 .2 .1.2 D O S E .......................................................................................................................................................................
2 8 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM ..............................................................................................
29 1/2.2.2 G A SE O U S E F FL U E N T S ............................................................................................................................................
30 1/2 .2 .2.1 D O SE RA T E ............................................................................................................................................................
30 TABLE 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM ...... 31 1/2.2.2.2 D O SE -N O B L E G A SE S ..........................................................................................................................................
34 1/2.2.2.3 DOSE 131, 1-133, TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS ..........................................................................................................................................
35 1/2.2.2.4 GASEOUS RADWASTE TREATMENT
..........................................................................................................
36 1/2 .2 .3 T O T A L D O S E .............................................................................................................................................................
3 7 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING
.......................................................................................
38 1/2.3.1 MONITORING PROGRA M .......................................................................................................................................
38 TABLE 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ...............
40 TABLE 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES42 TABLE 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)A,B .......................................
43 1/2 .3.2 L A N D U SE C E N SU S ..................................................................................................................................................
45 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM ..........................................................................................
47 BASES ....................................................................................................................................................................................
49 IN ST R U M E N T A T IO N ..... .......................................................................................................................................................
49 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION
................................................
49 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION
...........................................
49 1/2.2 RA DIOACTIVE EFFLUENTS
......................................................................................................................................
49 1/2.2.1.1 C O N C E N T RA T IO N ................................................................................................................................................
49 1/2 .2 .1.2 D O S E .......................................................................................................................................................................
4 9 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM ..............................................................................................
50 1/2 .2 .2 .1 D O S E RA T E ............................................................................................................................................................
50 1/2.2.2.2 D O SE -N O B L E G A SE S ..........................................................................................................................................
5 1 1/2.2.2.3 DOSE 131, 1-133, TRITIUM, AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS ..........................................................................................................................................
51 1/2.2.2.4 GASEOUS RADWASTE TREATMENT
................................................................................
........ 52 1/2 .2 .3 T O T A L D O S E .............................................................................................................................................................
52 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING
.......................................................................................
53 1/2.3.1 MONITORING PROGRA M .......................................................................................................................................
53 1/2.3.2 L A N D U SE C E N SU S ..................................................................................................................................................
53 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM ..........................................................................................
53 3.0 DEFINITIONS
................................................................................................................................................................
55 3 .1 A C T IO N ..................................................................................................................................................................
5 5 SQN ODCM Revision 58 Page 5 of 179 3.2 CHANN EL CALIBRATION
..................................................................................................................................
55 3.3 CHA NN EL CHECK ...............................................................................................................................................
55 3.4 CHANNEL FUNCTIONAL TEST .....................................................................................
............
55 3.6 CONTROLLED AREA ...........................................................................................................................................
55 3.7 DO SE EQUIVALENT 1-131 ..................................................................................................................................
55 3.9 GASEOUS RADW ASTE TREATM ENT SYSTEM ..........................................................................................
56 3. 10 OPERA BLE -OPERAB ILITY ...................................................................................................................................
56 3.11 M ODE .........................................................................................................................................................................
56 3.12 PURG E -PUR GIN G ...............................................................................................................................................
56 3.13 RADIATION M ON ITOR (RM ) OR (R) .................................................................................................................
56 3.14 RA TED THERM AL POW ER .................................................................................................................................
56 3.16 RESTRICTED AREA .............................................................................................................................................
57 3.1 7 SITE BOUN DARY .................................................................................................................................................
57 3.18 SOURCE/SEN SOR CHECK ..................................................................................................................................
57 3.19 UN RESTRICTED AREA/BOUND A RY ....................................................................................
57 3.20 VENTILATION EXHA UST TREATM ENT SY STEM ...................................................................................
57 3.21 VENT FLOW RATE M ONITOR (F) .....................................................................................................................
57 3.22 VENTIN G ...............................................................................................................................................................
57 TABLE 3.1 FRE QUENCY NOTATION ..................................................................................................................................
58 FIGuRE 3.1 UN RESTRICTED AREA BOUN DARY ........................................................................................................
59 5.0 ADM IN ISTRATIV E CO NTRO LS ................................................................................................................................
62 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT ............................................................
62 5.2 ANNUA L RADIOACTIVE EFFLUENT RELEA SE REPO RT ..................................................................................
62 5.3 OFFSITE DOSE CALCULATION M ANUAL CHA NGES .......................................................................................
64 5.4 SPECIAL RE PORTS .........................................................................................................................................................
64 SECTIO N 6.0 LIQ UID EFFLUENTS
.................................................................................................................................
66 RE LEA SE POINTS .................................................................................................................................................................
66 6.1 LIQUID RE LEASES .........................................................................................................................................................
68 6. 1.1 Pre-Release Analysis ..................................................................................................................................................
68 6.1.2 Effluent Concentration Lim its (ECL)-Sum of the Ratios .....................................................................................
68 6.1.3 Post-Release Analysis ................................................................................................................................................
69 6.2 IN STRUM ENT SETPOIN TS ............................................................................................................................................
70 6.2.1 Discharge Point M onitor Setpoints (0-RM 133,134,140,141)
..........................................................................
70 6.2.2 Release Point Monitor Setpoints (0-RM-90-122; 0-RM-90-225; 0-RM-90-212; 1,2-RM-90-120,121)
...............
70 6.2.3 Batch Release Point M onitor Setpoint ........................................................................................................................
70 6.3 CUM ULATIV E LIQUID EFFLUENT DO SE CALCULATION S ..............................................................................
72 6.3.1 M onthly Dose Calculations
........................................................................................................................................
73 6.3.2 Cum ulative Doses .......................................................................................................................................................
73 6.3.3 Com parison to Lim its .................................................................................................................................................
73 6.4 LIQUID RADW ASTE TREATM ENT SYSTEM .......................................................................................................
74 6.5 DOSE PROJECTION S ......................................................................................................................................................
75 6.6 QUARTERLY DOSE CALCULATION S .........................................................................................................................
76 6.6.1 W ATER IN GESTION ...............................................................................................................................................
76 6.6.2 FISH INGESTION
.....................................................................................................................................................
77 6.6.3 SHORELIN E RE CRE ATION ....................................................................................................................................
77 6.6.4 TOTAL M AXIM UM INDIVIDUAL DOSE .......................................................................................................
78 6.6.5 POPULATION DOSES .............................................................................................................................................
78 6.7 LIQUID DOSE FACTOR EQUATION S ..........................................................................................................................
81 6.7.1 W ATER IN GESTION ...............................................................................................................................................
81 6.7.2 FISH IN GESTION .....................................................................................................................................................
81 6.7.3 SHORE LIN E RE CRE ATION ....................................................................................................................................
81 TABLE 6.1 RECEPTORS FOR LIQUID DOSE CALCULATION S ...................................................................................
82 TABLE 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA ...............................................
83 SQN ODCM Revision 58 Page 6 of 179 TABLE 6.3 DOSE CALCULATION FACTORS .....................................................................................................................
86 TABLE 6.4 INGESTION DOSE FACTORS ...........................................................................................................................
88 TABLE 6.5 BIOACCUMULATION FACTORS FOR FRESHWATER FISH ...................................................................
96 TABLE 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND ..................................
97 FIGURE 6.1 LIQUID EFFLUENT RELEASE POINTS .....................................................................................................
99 FIGURE 6.2 LIQUID RADWASTE SYSTEM .......................................................................................................................
100 SECTION 7.0 GASEOUS EFFLUENTS
...........................................................................................................................
102 RELEASE POINTS DESCRIPTION
....................................................................................................................................
102 7.1 INSTRUMENT SETPOINTS
..........................................................................................................................................
103 7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-13 1, 0-RM-90-118)
.................................................................
103 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-i131)
..............................................................................
103 7.1.1,2 Waste Gas Decay Tank Effluent Monitor (0-RM-90-118)
....................................................................................
103 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, 0-RM-90-101, 0-RM-90-132, 1,2-RM-90-99,119)
........ 105 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119)
..........................................................................................
105 7.2 GASEOUS EFFLUENTS
-DOSE RATES .....................................................................................................................
106 7 .2 .1 (D eleted ) ...................................................................................................................................................................
10 6 7.2.2 RELEASE SAMPLING ...........................................................................................................................................
106 7.2.3 NOBLE GAS DOSE RA TES ...................................................................................................................................
106 7.2 .3.1 T otal B ody D ose R ate ...........................................................................................................................................
106 7 .2 .3 .2 S k in D o se R ate ......................................................................................................................................................
10 7 7.2.4 1-13 1, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS -ORGAN DOSE RATE .....................................................................................................
108 7.3 D O SE -N O B L E G A SE S .................................................................................................................................................
109 7 .3 .1 G am m a do se to air ....................................................................................................................................................
10 9 7 .3 .2 B eta d o se to air .........................................................................................................................................................
10 9 7.3.3 C um ulative D ose -N oble G as ..................................................................................................................................
110 7.3 .4 C om parison to L im its ...............................................................................................................................................
110 7.4 DOSE DUE TO 1-131, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS ................................................................................................................................
IIl 7 .4 .1 O rgan dose C alcu lation ............................................................................................................................................
111 7 .4 .2 C u m u lativ e D o ses .....................................................................................................................................................
112 7 .4 .3 C om parison to L im its ...............................................................................................................................................
112 7.5 D O S E P R O JE C T IO N S ....................................................................................................................................................
113 7.5.1 GASEOUS RADWASTE TREATMENT SYSTEM DESCRIPTION
....................................................................
113 7.6 QUARTERLY DOSE CALCULATIONS
.......................................................................................................................
114 7.6.1 NOBLE GAS -GAMMA AIR DOSE .....................................................................................................................
114 7.6.2 NOBLE GAS -BETA AIR DOSE ...........................................................................................................................
114 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE .....................
115 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMIUM ORGAN DOSE .....................
116 7.6.4 PO P U L A T IO N D O SE S ...........................................................................................................................................
117 7.6.4 POPULATION DOSES (continued)
........................................................................................................................
118 7.6.5 REPORTING OF DOSES ........................................................................................................................................
118 7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED or RESTRICTED AREA B O U N D A R Y ....................................................................................................................................................................
1 18 7.7 GASEOUS RELEASES -DOSE FACTORS .......................................................................................................................
119 7.7.1 PASTURE GRASS-COW/GOAT-MILK INGESTION DOSE FACTORS ............................................................
119 7.7.2 STORED FEED-COW/GOAT-MILK INGESTION DOSE FACTORS .................................................................
120 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS ...................................................................................
121 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS ........................................................................................
122 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS ...........................................................................
123 7.7.6 STORED VEGETABLE INGESTION DOSE FACTORS ......................................................................................
124 7.7.7 TRITIUM-PASTURE GRASS-COW/GOAT-MILK DOSE FACTOR ..................................................................
125 7.7.8 TRITIUM-STORED FEED-COW/GOAT-MILK DOSE FACTOR .......................................................................
125 SQN ODCM Revision 58 Page 7 of 179 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR .........................................................................................
126 7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR .............................................................................................
126 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR .............................................................................
127 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR ........................................................................................
128 7.7.13 CARBON 14 -PASTURE GRASS-COW/GOAT MILK DOSE FACTOR -RCpC14 .........................................
129 7.7.14 CARBON 14 -STORED FEED-COW/GOAT MILK DOSE FACTOR -RCSC 14 ..............................................
130 7.7.15 CARBON 14 -PASTURE GRASS-BEEF DOSE FACTOR -RMC 14 .................................................................
131 7.7.16 CARBON 14 -SRORED FEED-BEEF DOSE FACTOR -RMSC14 ....................................................................
132 7.7.17 CARBON 14 -FRESH LEAFY VEGETABLE DOSE FACTOR -RVFC14 ........................................................
133 7.7.18 CARBON 14-STORED VEGETABE DOSE FACTOR -RVSC14 ......................................................................
134 7.7.19 IN H A LA TIO N D O SE FA C TO R S .........................................................................................................................
135 7.7.20 GROUND PLANE DOSE FACTORS ...................................................................................................................
135 7.8 D ISPER SIO N M ETH O D O LO G Y ..............................................................................................................................
136 7.8.1 A IR C O N C EN T RA T IO N ........................................................................................................................................
136 7.8.2 RE LA TIV E CO N CEN TRA TIO N ............................................................................................................................
137 7.8.3 R E L A T IV E D E PO SIT IO N ......................................................................................................................................
138 TABLE 7.1 SEQUOYAH MAXIMUM QUARTERLY X/Q (1999-2008)
SORTED BY QUARTER ......................................................
139 TABLE 7.2 SEQUOYAH MAXIMUM QUARTERLY D/Q (1999-2008)
SORTED BY QUARTER ......................................................
140 TABLE 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES .............................................................................
141 TABLE 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES ...............................................................
142 TABLE 7.5 POPULATION WITHIN EACH SECTOR ELEMENT ......................................................................................
143 TABLE 7.6 INHALATION DOSE FACTORS ......................................................................................................................
144 FIGURE 7.1 GASEOUS EFFLUENT RELEASE POINTS ....................................................................................................
152 FIGURE 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL) ...........................................................................
154 FIGURE 7.3 GASEOUS RADWASTE TREATMENT SYSTEM ..........................................................................................
155 FIGURE 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES .............................................................
156 FIGURE 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME ..........................................................
157 FIGURE 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES .....................................................................
158 SECTION 8.0 TOTAL DOSE ............................................................................................................................................
160 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES -TOTAL REPORTED DOSE .............................................................
160 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ..............................................
162 9.1 M O N ITO R IN G PR O G RA M ...........................................................................................................................................
162 9.2 D ET E C T IO N C A PA B IL IT IE S .......................................................................................................................................
162 9.3 L A N D U SE C E N SU S ......................................................................................................................................................
162 9.4 INTERLABORATORY COMPARISON PROGRAM ...................................................................................................
162 TABLE 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM .............................................................
163 TABLE 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS
.................
167 TABLE 9.3 D O SIM ETR Y LO C A TIO N S ...............................................................................................................................
168 FIGURE 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT .........................
170 FIGURE 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT ..... 171 FIGURE 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT. 172 APPENDIX A -SQN ODCM REVISION PROCESS .......................................................................................................
173 SQN ODCM Revision 58 Page 8 of 179 INTRODUCTION This Offsite Dose Calculation Manual (ODCM) is in support of the Tennessee Valley Authority (TVA)facility operating licenses for a two-unit nuclear power plant located approximately
7.5 miles
northeast of Chattanooga at the Sequoyah site in Hamilton County, Tennessee.
This facility has been designated the Sequoyah Nuclear Plant (SQN). The plant has been designed, built, and is operated by TVA. Each of the two identical units employs a Pressurized Water Reactor Nuclear Steam Supply System (NSSS) with four coolant loops furnished by Westinghouse Electric Corporation.
Each of the two reactor cores is rated at 3,455 MWt and, at this core power, the NSSS will operate at 3,467 MWt. The additional 12 MWt is due to the contribution of heat of the Primary Coolant System from nonreactor sources, primarily reactor coolant pump heat. Each of the reactor cores has an Engineered Safeguards Design rating of 3577 MWt and at this core power, the NSSS will operate at 3565 MWt. The net electrical output is 1211 Mwe for Unit 1 and 1188 Mwe for Unit 2 at the rated core power. All plant safety systems, including containment and engineered safety features, are designed and evaluated at the higher power level. In addition, the higher power rating is used in the analysis of postulated accidents having as a consequence the release of fission product activity to the environment.
The containment for each of the reactors consists of a freestanding steel vessel with an ice condenser and separate reinforced concrete shield building.
The freestanding steel vessel and the concrete shield building were designed by TVA and the ice condenser was furnished by the Westinghouse Electric Corporation.
Unit 1 began commercial operation on July 1, 1981. Unit 2 began commercial operation on June 1, 1982.
SQN ODCM Revision 58 Page 9 of 179 The ODCM is divided into two major parts. The first part of the ODCM contains: 1. Radioactive Effluent Controls required by Section 6.8.4.f of the SQN Technical Specifications;
- 2) Radiological Environmental Monitoring Controls;3) descriptions of the information that should be included in the Annual Radiological Environmental Operating and Annual Radioactive Effluent Release Reports required by SQN Technical Specifications 6.9.1.6 and 6.9.1.8; and, 4) Administrative Controls for the ODCM requirements.
The second part of the ODCM contains the methodologies used to: 1) calculate offsite doses resulting from radioactive gaseous and liquid effluents to the unrestricted area/boundary and the Tennessee River; 2) calculate gaseous and liquid effluent monitor Alarm/Trip setpoints; and, 3) conduct the Environmental Radiological Monitoring Program.The SQN ODCM will be maintained for use as a reference guide on accepted methodologies and calculations.
Changes in the calculation methods or parameters will be incorporated into the ODCM in order to assure that the ODCM represents the present methodology in all applicable areas. Any licensee initiated ODCM changes will be implemented in accordance with SQN Technical Specification 6.14 and ODCM Administrative Control 5.3.
SQN ODCM Revision 58 Page 10 of 179 SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS SQN ODCM Revision 58 Page 11 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.0 APPLICABILITY CONTROLS 1.0.1 Compliance with the Controls contained in the succeeding controls is required during the OPERATIONAL MODES or other conditions specified therein; except that upon failure to meet the Control, the associated ACTION requirements shall be met.1.0.2 Noncompliance with a Control shall exist when the requirements of the Control and associated ACTION requirements are not met within the specified time intervals.
If the Control is restored prior to the expiration of the specified intervals, completion of the ACTION requirements is not required.1.0.3 When a Control is not met, except as provided in the associated ACTION requirements, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> action shall be initiated to place the unit in a MODE in which the Control does not apply by placing it, as applicable, in: a. At least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, b. At least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, and c. At least COLD shutdown within the subsequent 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.1.0.4 Entry into an OPERATIONAL MODE or other specified condition shall not be made when the conditions for the Control are not met and the associated ACTION requires a shutdown if they are not met within a specified time interval.
Entry into an OPERATIONAL MODE or specified condition may be made in accordance with ACTION requirements when conformance to them permits continued operation of the facility for an unlimited period of time. This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with the ACTION requirements.
Exceptions to these requirements are stated in the individual Controls.
SQN ODCM Revision 58 Page 12 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.0 APPLICABILITY SURVEILLANCE REQUIREMENTS
2.0.1 Surveillance
Requirements shall be met during the OPERATIONAL MODES or other conditions specified for individual Controls unless otherwise stated in the individual Surveillance Requirement.
2.0.2 Each Surveillance Requirement shall be performed within the specified time interval with a maximum allowable extension not to exceed 25% of the specified surveillance interval.If an ACTION requires periodic performance on a "once per..." basis, the above frequency extension applies to each performance after the initial performance.
2.0.3 Failure
to perform a Surveillance Requirement within the specified time interval shall constitute a failure to meet the OPERABILITY requirements for a Control. The time limits of the ACTION requirements are applicable at the time it is identified that a Surveillance Requirement has not been performed.
The ACTION requirements may be delayed for up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to permit the completion of the surveillance when the allowable outage time limits of the ACTION requirements are less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Surveillance Requirements do not have to be performed on inoperable equipment.
2.0.4 Entry
into an OPERATIONAL MODE or other specified applicable condition shall not be made unless the Surveillance Requirement(s) associated with the Control has been performed within the applicable surveillance interval or as otherwise specified.
This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with ACTION requirements.
Exceptions to these requirements are stated in the individual Controls.
SQN ODCM Revision 58 Page 13 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.1 INSTRUMENTATION 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.1 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive liquid effluent monitoring instrumentation channels shown in Table 1.1-1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.1.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 6.2.APPLICABILITY:
This requirement is applicable during all releases via these pathways.ACTION: a. With a radioactive liquid effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive liquid effluents monitored by the affected channel or declare the channel inoperable, or change the setpoint so that it is acceptably conservative.
- b. With less than the minimum number of radioactive liquid effluent monitoring instrumentation channels OPERABLE, take the action shown in Table 1.1-1. Restore the inoperable instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2, why the inoperability could not be corrected within 30 days.c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
Report all deviations in the Annual Radioactive Effluent Release Report.SURVEILLANCE REQUIREMENTS 2.1.1. Each radioactive liquid effluent monitoring channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-1.
SQN ODCM Revision 58 Page 14 of 179 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Paae 1 of 2)Minimum Instrument Channels Action OPERABLE 1. Gross Radioactivity Monitors Providing Automatic Termination of Release a. Liquid Radwaste Effluent Line (0-RM-90-122) 1 30 b. Steam Generator Blowdown Effluent Line 1 31 (1,2-RM-90-120A,121A)
- c. Condensate Demineralizer Effluent Line 1 30 (0-RM-90-225A)
- 2. Gross Radioactivity Monitors a. Essential Raw Cooling Water Effluent Header** 1 32 (0-RM-90-133A,-1 34A,-140A,-141A)
- b. Turbine Building Sump Effluent Line 1 31 (0-RM-90-212A)
- 3. Flow Rate Measurement Devices a. Liquid Radwaste Effluent Line 1 33 (0-F1-77-42)
- b. Steam Generator Blowdown Effluent Line 1 33 (1,2-Fl-1 5-44, 1,2-F-1 5-43)c. Condensate Demineralizer Effluent Line 1 33 (0-FR-14-456, 0-F-14-185, 0-F-14-192)
- d. Cooling Tower Blowdown Effluent Line 1 33 Available Dilution Flow is provided on ICS computer point OF2102DIF*.
- If Gate Structure
- 1 weir is overflowing with cooling towers not in service, indicated value on ICS point must be corrected by subtracting the estimated weir flow. If Cooling Towers are in service then verification of flow by other means is acceptable.
N/A If ERCW Maintenance activities were to limit the indicated ERCW Flow values <17,000 gpm and this ICS Computer Point is functional, other means of verifying total discharge into the Cold Water Channel are Acceptable.
- e. 1,2-FT-67-61 and 62. 1 33 f. Turbine Building Sump Discharge 1 36 0-F-40-3.5. Continuous Composite Sampler and Sample Flow Monitor a. Condensate Demineralizer Regenerant Effluent 1 35 Line (0-Fl-14-466)
- Requires minimum of 1 Channel/Header to be OPERABLE.
SQN ODCM Revision 58 Page 15 of 179 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 2) TABLE NOTATION-With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that prior to initiating a release: ACTION 30 a. At least two independent samples of the tank's contents obtained by two technically qualified members of the facility staff are analyzed, and At least two technically qualified members of the Facility Staff independently verify the release rate calculations and;b. At least two technically qualified members of the Facility Staff independently verify the discharge valve lineup.Otherwise, suspend release of radioactive effluents via this pathway.ACTION 31 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are analyzed for principal gamma emitters in accordance with SR 2.2.1.1.1 and 2.2.1.1.2.
- a. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the specific activity of the secondary coolant is greater than or equal to 0.01 pCi/g DOSE EQUIVALENT 1-131.b. At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the specific activity of the secondary coolant is less than 0.01 pCi/g DOSE EQUIVALENT 1-131.ACTION 32 -ACTION 33 -ACTION 35 -ACTION 36 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided that, at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples are collected and analyzed for principal gamma emitters at a limit of detection of at least 5.0x1 0-7 gCi/ml.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases.
Pump curves or the change in tank level indication, if applicable, may be used to estimate flow.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided representative batch samples of each tank to be released are taken prior to release and composited for analysis according to Table 2.2-1, footnote g.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases in accordance with plant procedures.
SQN ODCM Revision 58 Page 16 of 179 Table 2.1-1 -RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2)1 SOURCE/I CHANNEL CHANNEL CHANNEL SENSOR CALIBRA- FUNCTIONAL Instrument CHECK CHECK _ TION TEST 1. Gross Beta or Gamma Radioactivity Monitors Providing Alarm and Automatic Termination of Release a. Liquid Radwaste Effluent Line D P R(3) S(1)(0-RM-90-122)
- b. Steam Generator Blowdown Effluent D M R(3) S(5)Line (1,2-RM-90-120A,121A)
- c. Condensate Demineralizer Effluent D M R(3) S(5)Line (0-RM-90-225A)
- 2. Gross Beta or Gamma Radioactivity Monitors Providing Alarm But Not Providing Automatic Termination of Release a. Essential Raw Cooling Water Effluent D M R(3) S(2)Line (0-RM-90-133A, 1 34A, 1 40A, 141 A)b. Turbine Building Sump Effluent Line D M R(3) S(2)(0-RM-90-212A)
- 3. Flow Rate Measurement Devices a. Liquid Radwaste Effluent Line D(4) N.A. R Q (0-FI-77-42)
- b. Steam Generator Blowdown Effluent D(4) N.A. R Q Line (1,2-Fl-1 5-44, 1,2-F-1 5-43)c. Condensate Demineralizer Effluent D(4) N.A. R Q Line (0-FR-14-456,0-F-14-192, 0-F-14-185)
- d. Cooling Tower Blowdown Effluent D(4) N.A. N.A N.A Line Available Dilution Flow is provide by ICS Computer Point OF2102DIF.
This computer point receives input From flow transmitters 1,2-FT-67-61 and 1,2-FT-67-62.
- e. 1,2-FT-67-61 and 62. N.A. N.A. R N.A.f. Turbine Building Sump Discharge D(4) N.A R. N.A 0-F-40-3 4. Continuous Composite Sampler and Sample Flow Monitor a._ Condensate Demineralizer Regenerant_]
P [__N.A. R N.A.
SQN ODCM Revision 58 Page 17 of 179 Table 2.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2)(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above the alarm/trip setpoint.2. Circuit failure.3. Downscale failure.(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above an alarm setpoint.2. Circuit failure.3. Downscale failure.(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) or using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.(4) CHANNEL CHECK shall consist of verifying indication of flow during periods of release. CHANNEL CHECK shall be made at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> on days on which continuous periodic, or batch releases are made.(5) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions occur: 1. Instrument indicates measured levels above an alarm/trip setpoint.2. Circuit failure.The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room annunciation occurs if the following condition occurs: 1. Downscale failure.
SQN ODCM Revision 58 Page 18 of 179 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.1 INSTRUMENTATION 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.2 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive gaseous effluent monitoring instrumentation channels shown in Table 1.1-2 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.2.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 7.1.APPLICABILITY:
As shown in Table 1.1-2.ACTION: a. With a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive gaseous effluents monitored by the affected channel, declare the channel inoperable, or change the setpoint so it is acceptably conservative.
- b. With less than the minimum number of radioactive gaseous effluent monitoring instrumentation channels OPERABLE take the ACTION shown in Table 1.1-2. Restore the inoperable instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Report, pursuant to ODCM Administrative Control 5.2, why the inoperability could not be corrected within 30 days.c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
Report all deviations in the Annual Radioactive Effluent Release Report.SURVEILLANCE REQUIREMENTS 2.1.2 Each radioactive gaseous effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-2.
SQN ODCM Revision 58 Page 19 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING (Paae 1 of 3)INSTRUMENTATION Minimum Channels Instrument OPERABLE Applicability Action 1. WASTE GAS DISPOSAL SYSTEM a. Noble Gas Activity Monitor (0-RM-90-118A) 1 ***]40 b. Waste Decay Tanks Effluent Flow Rate 1
- 41 Measuring Device (0-FI-77-230)
- 2. CONDENSER VACUUM EXHAUST SYSTEM a. J Noble Gas Activity Monitor (1,2-RM-90-99,119) 1 ***]42 b. Vent Flow Rate Monitor (1,2-F-2-256,257) 1 ***]41 3. SHIELD BUILDING EXHAUST SYSTEM a. Noble Gas Vent Rate Activity Monitor 1** 43 (1,2-R-90-400 ,Eff)b. Iodine Sampler (1,2-FLT-90-402A or 402B) 1 43,44 c. Particulate Sampler (1,2-FLT-90-402A or 402B) 1 43,44 d. Vent Flow Rate Monitor (1,2-FM-90-400),(1,2-1.. 41,43 RI-90-400 Monitor Item 029 or 1,2-FI-90-400)
- e. Sampler Flow Rate Monitor (1,2-RI-90-400 1 45 Monitor Item 028 or 1,2-FI-90-400A)
- f. Primary Sampling Pumps (1,2-PMP-90-452A or 1** 46 452B)4. AUXILIARY BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM-90-101B) 1
- 42 b. Iodine Sampler (0-FLT-90-101) 1
- 44 c. Particulate Sampler (0-FLT-90-101) 1
- 44 d. Vent Flow Rate Monitor (0-F-30-174) 1
- 41 e. Sampler Flow Rate Monitor (0-FIS-90-101) 1
- 45 5. SERVICE BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM-90-132B) 1
- 42 b. I Vent Flow Rate Monitor (0-F-90-5132A) 1
- 41 6. LOWER CONTAINMENT AIRBORNE ACTIVITY FOR VENTING a. Noble gas Activity Monitor (1,2-RM-90-106B,1 12B) 1 Modes 1-4 47 I during venting 7. CONTAINMENT AIRBORNE ACTIVITY FOR PURGING a. Noble gas Activity Monitor (1,2-RM-90-106B,1 12B) 1 (for compartment Modes 1-4*** 48 IT I being purged)* At all times.** Operability of shield building noble gas vent rate activity monitor (Eff) requires primary sample pumps, vent flow rate and"Low Rng" radiation inputs since the high radiation alarm is only on the effluent channel (pCi/s). When the vent flow rate monitor is inoperable only the "Low Rng" radiation monitor is still capable of providing noble gas indication.
Its associated malfunction alarm on M-30 will alert Operations to any secondary failures such as loss of sample flow or detector failure. Therefore as long as the "Low Rng" is selected and the malfunction alarm is monitored RE-90-400 can be used to meet ODCM Noble gas and Particulate/Iodine sampler requirements.
Mid or High range channels do not have any ODCM requirements.
The vent flow rate monitor can be OPERABLE without the noble gas vent rate activity monitor.During exhaust system operation.
1,2-F-2-256 is the low range flow element (0-100 cfm). 1,2 -F-2-257 is a mid (0-1000)cfm flow element which should only be used for abnormal conditions.
SQN ODCM Revision 58 Page 20 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 3)TABLE NOTATION ACTION 40 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, the contents of the tank(s) may be released to the environment provided that prior to initiating the release: a. At least two independent samples of the tank's contents obtained by two technically qualified members of the facility staff are analyzed, and b. At least two technically qualified members of the Facility Staff independently verify the release rate calculations and;c. At least two technically qualified members of the Facility Staff independently verify the discharge valve lineup.Otherwise, suspend release of radioactive effluents via this pathway.ACTION 41 -ACTION 42 -ACTION 43 -ACTION 44 -ACTION 45 -With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity.Alarm Window M-5C-29, Vent Flow Rate only Inoperable
-With any inoperable vent flow monitor on a discharge pathway where a fan is operating (Purge A, Purge B, ABGTS, or EGTS), effluent release may continue provided: (a) "Low Rng" on RI-90-400 is selected instead of "Eff"; and (b) at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated instrument malfunction, M-30-15, is verified not annunciated; and (c) a reading from "Low Rng" on RE-90-400 is obtained at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The High Rad alarm on M-30 will not be operable under this alignment.
Also Action 41 must be complied with.Alarm Window M-30-15, Radiation Monitor Inoperable
-With the low range channel inoperable, effluent releases may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity.
Also Action 44 must be complied with.With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via the affected pathway may continue provided that within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after the channel has been declared inoperable samples are continuously collected as required in Table 2.2-2. Also Action 45 must be complied with.With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, effluent releases via this pathway may continue provided the sampler flow rate is verified at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
SQN ODCM Revision 58 Page 21 of 179 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 3 of 3) TABLE NOTATION ACTION 46 With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, effluent releases via this pathway may continue provided (a) RM-90-400 is placed in manual sample flow control per SO-90-2, (b) "Low Rng" on RI-90-400 is selected instead of "Eff", and (c) at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated instrument malfunction is verified not annunciated; and (d) a reading from "Low Rng" on RE-90-400 is obtained at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The High Rad alarm on M-30 will not be operable under this alignment.
Action 46 does not apply if complying with Action 43 with RM-90-400 inoperable.
ACTION 47 ACTION 48 between 20 With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, containment venting may continue provided a grab sample of the lower containment atmosphere is analyzed prior to each vent.With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, containment purging may continue provided a grab sample of the compartment to be purged is analyzed prior to each purge. IF purging the incore instrument room, the purge sample shall be obtained at the shield building exhaust radiation monitor and 25 minutes following initiation of the incore instrument room PURGE or at the peak of the discharge based on the radiation monitor response.
SQN ODCM Revision 58 Page 22 of 179 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2)MODE in SOURCE/ CHANNEL CHANNEL Which Surveil-CHANNEL SENSOR CALIBRA- FUNCTIONAL lance Instrument CHECK CHECK TION TEST Required 1. WASTE GAS DISPOSAL SYSTEM a. Noble Gas Activity Monitor P P R(3) S(1)(0-RM-90-118A)
- b. Flow Rate Monitor (0-FI-77-230)
D N.A. R Q 2. CONDENSER VACUUM EXHAUST SYSTEM a. Noble Gas Activity Monitor D(5) M(4) R(3) S(2)(1,2-RM-90-99,119)
- b. Vent Flow Rate Monitor D N.A. R 0 (1,2-F-2-256,257)
- 3. SHIELD BUILDING EXHAUST SYSTEM a. Noble Gas Vent Rate Activity D M R(3) S(2)Monitor (1,2-R-90-400A,Eff)
- b. Iodine Sampler W N.A. N.A. N.A.(1,2-FLT-90-402A or 402B)C. Particulate Sampler W N.A. N.A. N.A.(1,2-FLT-90-402A or 402B)d. Vent Flow Rate Monitor D N.A. R Q (1,2-FM-90-400 or 1,2-FI-90-400)
- e. Sampler Flow Rate Monitor D N.A. R Q (1,2-RI-90-400 or 1,2-FI-90-400A)
- f. Primary Sample Pumps W N.A N.A N.A (1,2-PMP-90-452A, 452B)4. AUXILIARY BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor D M R(3) S(2)(0-RM-90-101B)
- b. Iodine Sampler (0-FLT-90-101)
W N.A. N.A. N.A.c. Particulate Sampler (0-FLT-90-101)
W N.A. N.A. N.A..d. Vent Flow Rate Monitor D N.A. R Q *(0-F-30-174)
- e. Sampler Flow Rate Monitor 0 N.A. R Q (0-FIS-90-101)
- 5. SERVICE BUILDING VENTILATION SYSTEM a. Noble Gas Activity Monitor (0-RM D M R(3) S(2)132B)b. Vent Flow Rate Monitor (0-F-90-5132A)
D N.A. R Q 6. CONTAINMENT AIRBORNE ACTIVITY a. Noble Gas Activity Monitor D N.A. R N.A. 1-4 (1,2-RM-90-106B, 112B) _7. CONTAINMENT AIRBORNE ACTIVITY a. Noble Gas Activity Monitor D N.A. R N.A. 1-4 (1,2-RM-90-106B, 112B)
SQN ODCM Revision 58 Page 23 of 179 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2)TABLE NOTATION* At all times.During shield building exhaust system operation.
During waste gas releases.(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above the alarm/trip setpoint.2. Circuit failure.3. Downscale failure.(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists: 1. Instrument indicates measured levels above an alarm setpoint.2. Circuit failure.3. Downscale failure.(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.For the auxiliary building ventilation system only, at least once every 18 months, the CHANNEL CALIBRATION TEST shall also demonstrate automatic isolation of this pathway if the instrument indicates measured levels above the alarm/trip setpoint.(4) The SOURCE/SENSOR CHECK for the Condenser Vacuum Exhaust Monitor will be accomplished using an LED sensor check source or a radioactive source.(5) Applicable only to in-service monitor. Either 99 or 119 monitor will be in service for each unit.
SQN ODCM Revision 58 Page 24 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.1 CONCENTRATION CONTROLS 1.2.1.1 In accordance with SQN Technical Specifications 6.8.4.f.2 and 3, the concentration of radioactive material released through the diffuser piping to UNRESTRICTED AREAS (see Figure 3.1) shall be limited at all times to ten times the concentrations specified in 10 CFR Part 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 2X10-4 gCi/ml total activity.APPLICABILITY:
At all times.ACTION: a. With the concentration of radioactive material released to UNRESTRICTED AREAS exceeding the above limits, immediately, restore the concentration to within the above limits.b. If samples or analyses required by Table 2.2-1 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.1.1 Radioactive liquid wastes shall be sampled and analyzed according to the sampling and analysis program of Table 2.2-1.2.2.1.1.2 The results of the radioactivity analysis shall be used in accordance with the methods in ODCM Section 6.1 to assure that the concentration at the point of release is maintained within the limits stated above.
SQN ODCM Revision 58 Page 25 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)Minimum Lower Limit of Sampling Analysis Type of Activity Detection (LLD)Liquid Release Type Frequency Frequency Analysis (lgCilml)a A. Batch Waste Release Tanksd P P Principal Ganma 5x10" 1. Cask Decontamination Each Batch Each Batch Emitters Tank 2. Laundry Tanks (2) 1-131 1x10-, 3. Chemical Drain Tank 5 4. Monitor Tank P M Dissolved/
1x10_One Batch/M Entrained Gases (Gamma Emitters)5 P M H-3 1x10_Each Batch Compositeb Gross Alpha lxi 0.P Q Each Batch Compositeb Sr-89, Sr-90 5x10-8 Fe-55 lx106 B. Continuous Releasese D W Principal Gamma 5x10" 1. Steam Generator Grab Sample Compositec Emittersf Blowdownh 2. Turbine Building Sumph M M 1-131 1xl0o-Grab Sample Dissolved/
1x10" Entrained Gases (Gamma Emitters) 5 D M H-3 lx10"7 Grab Sample Compositec Gross Alpha 1x10" D Q 8 Grab Sample Compositec Sr-89, Sr-90 5x10-Fe-55 1x10-6 C. Periodic Continuous Continuous9 W Principal Garpma 5x10-Releasese,h Compositec Emitters 1. Non-Reclaimable Waste Tank M M 1-131 lx10" 6 2. High Crud Tanks (2) Grab Sample Dissolved/
1x10o-3. Neutralizer Tank Entrained Gases (Gamma Emitters)Continuousg M H-3 7xl0'Compositec Gross Alpha 1x10" 8 Continuousg Q Sr-89, Sr-90 5x10" 6 Compositec Fe-55 1x10_
SQN ODCM Revision 58 Page 26 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 2 of 3) TABLE NOTATION a The LLD is defined for the purpose of these specifications as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95%probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66sb LLD =E V 2.22x10 6 Y exp (-XAt)Where: LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x10 6 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable), X is the radioactive decay constant for the particular radionuclide, and At for plant effluents is the elapsed time between midpoint of sample collection and time of counting (midpoint).
It should be recognized that the LLD is defined as an a orio (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
b A composite sample is one in which the quantity of liquid sampled is proportional to the quantity of liquid waste discharged and in which the method of sampling employed results in a specimen which is representative of the liquids released.c Prior to analyses, all samples taken for the composite shall be thoroughly mixed in order for the composite sample to be representative of the effluent release.
SQN ODCM Revision 58 Page 27 of 179 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 3 of 3) TABLE NOTATION d A batch release is the discharge of liquid wastes of a discrete volume. Prior to sampling for analyses, each batch shall be isolated, and then thoroughly mixed, by the method described in ODCM Section 6.1.1, to assure representative sampling.e A continuous release is the discharge of liquid wastes of a nondiscrete volume; e.g., from a volume or system that has an input flow during the continuous release.f The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:
Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, and Ce-141. Ce-144 shall also be measured with an LLD of 5x10-6.This list does not mean that only these nuclides are to be detected and reported.
Other peaks which are measurable and identifiable, together with the above nuclides, shall also be identified and reported.g Releases from these tanks are continuously composited during releases.
With the composite sampler or the sampler flow monitor inoperable, the sampling frequency shall be changed to require representative batch samples from each tank to be released to be taken prior to release and manually composited for these analyses.h Applicable only during periods of primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is set to alarm if activity in the stream exceeds a routine normal background, or compensatory requirements associated with applicable inoperable monitors are met.
SQN ODCM Revision 58 Page 28 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 112.2.1.2 DOSE CONTROLS 1.2.1.2 In accordance with SQN Technical Specification 6.8.4.f.4 and 5, the dose or dose commitment to a member of the public from radioactive materials in liquid effluents released to UNRESTRICTED AREAS shall be limited from each reactor unit: a. During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and b. During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.APPLICABILITY:
At all times.ACTION: a. With the calculated dose from the release of radioactive materials in liquid effluents exceeding any of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits. This Special Report shall also include (1) the results of radiological analyses of the drinking water source and (2) the radiological impact on finished drinking water supplies with regard to the requirements of 40 CFR 141 (applicable only if drinking water supply is taken from the receiving water body within three miles downstream of the plant discharge).
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.2 Cumulative dose contributions from liquid effluents for the current calendar quarter and current calendar year shall be determined in accordance with the methodology and parameters in ODCM Section 6.3 at least once per 31 days.
SQN ODCM Revision 58 Page 29 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM CONTROLS 1.2.1.3 In accordance with SQN Technical Specification 6.8.4.f.6, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge when the projected doses due to the liquid effluent to UNRESTRICTED AREAS (see Figure 3.1) would exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period.APPLICABILITY:
At all times.ACTION: a. With radioactive liquid waste being discharged without treatment and in excess of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
- 1. Identification of the inoperable equipment or subsystems and the reason for inoperability, 2. Action(s) taken to restore the inoperable equipment to OPERABLE status, and 3. Summary description of action(s) taken to prevent a recurrence.
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.1.3 Doses due to liquid releases from each unit to UNRESTRICTED AREAS shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 6.5.
SQN ODCM Revision 58 Page 30 of 179 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.1 DOSE RATE CONTROLS 1.2.2.1 In accordance with SQN Technical Specification 6.8.4.f.7, the dose rate at any time due to radioactive materials released in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be in accordance with the following:
- a. For noble gases: Less than or equal to a dose rate of 500 mrem/yr to the whole body and less than or equal to a dose rate of 3000 mrem/yr to the skin, and b. For Iodine-131, Iodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days: Less than or equal to a dose rate of 1500 mrem/yr to any organ.APPLICABILITY:
At all times.ACTION: a. With dose rate(s) exceeding the above limits, without delay restore the release rate to within the above limit(s).b. If samples or analyses required by Table 2.2-2 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.1.1 The dose rate due to noble gases in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.3, and 2.2.2.1.2 The dose rate due to Iodine-131, Iodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.4 and by obtaining representative samples and performing analyses in accordance with the sampling and analysis program specified in Table 2.2-2.
SQN ODCM Revision 58 Page 31 of 179 Table 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)Lower Limit of Sampling Minimum Analysis Detection (LLD)Gaseous Release Type Frequency Frequency Type of Activity Analysis (ILCi/ml)a A. Waste Gas Storage P P Principal Gamma lx10" 4 Tank Each Tank Each Tank Emittersg Grab B. Containment Pi Pi Principal Gamma lx10-4 1. PURGE Each PURGE Each PURGE Emittersg Grab Sample H-3 1x10-6 2. Vent Wi Wi Principal Gamma lx10" 4 Grab Sample Emittersg H-3 lx10" 6 C. Noble Gases and M M Principal Gamma 1x10" 4 Tritium Grab Sample Emittersg 1. Condenser Vacuum Exhausth H-3 lx10-6 2. Auxiliary Building Exhaustb,e
- 3. Service Bldg.Exhaust 4. Shield Bldg.Exhaustb,c,h D. Iodine and Particulates Continuous Wd 1-131 lx10-1 2 1. Auxiliary Building Samplerf Charcoal Sample Exhaust 2. Shield Building Continuous Wd Principle Gamma 1x10" 1 1 Exhaust h Sampler f Particulate Emittersg Sample (1-131, Others)M Continuous Composite Gross Alpha 1x10-1 1 Sampler Particulate Sampler Q Continuous Composite Sr-89, Sr-90 1x10-1 1 Samplerf Particulate Sample E. Noble Gases Continuous Noble Gas Noble Gases lx10" 6 All Release types Monitorf Monitor Gross Beta or Gamma as listed in C SQN ODCM Revision 58 Page 32 of 179 Table 2.2-2 (Page 2 of 3)RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66sb LLD =-------------------------------------------
E V 2.22x10 6 Y exp(-XAt)Where: LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x10 6 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable), X is the radioactive decay constant for the particular radionuclide, and At is the elapsed time between midpoint of sample collection and time of counting (midpoint) in minutes.It should be noted that the LLD is defined as an a orio (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
b Sampling and analysis shall also be performed following shutdown, startup, or a thermal power change exceeding 15% of RATED THERMAL POWER within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> unless (1) analysis shows that the DOSE EQUIVALENT 1-131 concentration in the primary coolant has not increased more than a factor of 3 and (2)the containment noble gas activity monitor (RE-90-106 or RE-90-112) shows that the radioactivity has not increased by more than a factor of 3.c Tritium grab samples shall be taken periodically when the refueling canal is flooded.
SQN ODCM Revision 58 Page 33 of 179 Table 2.2-2 -RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION (Page 3 of 3)d Samples shall be changed at least once per 7 days. Sampling shall also be performed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for at least 2 days following each shutdown from >15% RATED THERMAL POWER, startup of >15%RATED THERMAL POWER or THERMAL POWER change exceeding 15% of RATED THERMAL POWER in one hour. Only one set of samples will be required in a 24-hour period. When samples collected for <24 hours are analyzed, the corresponding LLD's may be increased by a factor of 10.e Tritium grab samples shall be taken periodically from the ventilation exhaust from the spent fuel pool area, whenever spent fuel is in the spent fuel pool.f The ratio of the sample flow rate to the sampled stream flow rate shall be known for the time period covered by each dose or dose rate calculation made in accordance with ODCM Sections 7.2, 7.3, and 7.4.g The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:
Kr-87, Kr-88, Xe-133, Xe-133m, Xe-135, and Xe-138 for noble gases and Mn-54, Fe-59, I-131, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141 and Ce-144 for particulate principal gamma emitters.
This list does not mean that only these nuclides are to be detected and reported.
Other gamma peaks which are measurable and identifiable, together with the above nuclides, shall also be analyzed and reported in the Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.h During releases via this exhaust system.PURGING -Applicable in MODES 1, 2, 3 and 4, the upper and lower compartments of the containment shall be sampled prior to PURGING. Prior to breaking containment integrity in MODE 5 or 6, the upper and lower compartments of the containment shall be sampled. The incore instrument room purge sample shall be obtained at the shield building exhaust between 20 and 25 minutes following initiation of the incore instrument room PURGE or at the peak of the discharge based on the radiation monitor response.VENTING -Applicable in MODES 1, 2, 3, and 4; the containment will be VENTED to the containment annulus and then to the auxiliary building via containment annulus fans. The lower containment compartment shall be sampled weekly and the lower containment radiation monitor response will be recorded daily when VENTING is to occur to account for the radioactivity being discharged from the VENTING process. The lower containment will be re-sampled when the reading on the lower containment radiation monitor (RE-90-106 or 112), increases by 50% from the initial value. If the lower containment noble gas monitor (RE-90-106 or 112) is inoperable, noble gas grab samples may be used to perform this comparison.
SQN ODCM Revision 58 Page 34 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.2 DOSE -NOBLE GASES CONTROLS 1.2.2.2 In accordance with SQN Technical Specification 6.8.4.f.8, the air dose due to noble gases released in gaseous effluents from each reactor unit to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation and b. During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.
APPLICABILITY:
At all times.ACTION: a. With the calculated air dose from radioactive noble gases in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.2 Cumulative dose contributions for the current calendar quarter and current calendar year for noble gases shall be determined in accordance with the methodology and parameters in ODCM Section 7.3 at least once per 31 days.
SQN ODCM Revision 58 Page 35 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.3 DOSE 131.1-133.
TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS CONTROLS 1.2.2.3 In accordance with SQN Technical Specification 6.8.4.f.9, the dose to a member of the public from I-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following from each reactor unit: a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ and, b. During any calendar year: Less than or equal to 15 mrem to any organ.APPLICABILITY:
At all times.ACTION: a. With the calculated dose from the release of 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days, in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.3 Cumulative dose contributions for the current calendar quarter and current calendar year for 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days shall be determined in accordance with the methodology and parameters in ODCM Section 7.4 at least once per 31 days.
SQN ODCM Revision 58 Page 36 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 112.2.2.4 GASEOUS RADWASTE TREATMENT CONTROLS 1.2.2.4 In accordance with SQN Technical Specification 6.8.4.f.5 and 6, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected gaseous effluent doses due to gaseous effluent releases to areas at or beyond the SITE BOUNDARY (see Figure 3.1), when averaged over 31 days, would exceed 0.2 mrad per unit for gamma radiation, and 0.4 mrad per unit for beta radiation.
The appropriate portions of the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected doses due to gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (See Figure 3.1) when averaged over 31 days would exceed 0.3 mrem per unit to any organ.ACTION: a. With the radioactive gaseous waste being discharged without treatment for more than 31 days and in excess of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
- 1. Identification of the inoperable equipment or subsystems and the reason for inoperability.
- 2. Action(s) taken to restore the inoperable equipment to OPERABLE status.3. Summary description of action(s) taken to prevent a recurrence.
- b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.2.2.4 Doses due to gaseous releases from the site shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 7.5.
SQN ODCM Revision 58 Page 37 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 112.2.3 TOTAL DOSE CONTROLS 1.2.3 In accordance with SQN Technical Specification 6.8.4.f. 10, the annual (calendar year) dose or dose commitment to any member of the public, beyond the site boundary due to releases of radioactivity from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or any organ (except the thyroid, which shall be limited to less than or equal to 75 mrem).APPLICABILITY:
At all times.ACTION: a. With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM Control 1.2.1.2, 1.2.2.2, or 1.2.2.3, calculations should be made to determine whether the above limits have been violated.
If such is the case, prepare and submit a Special Report to the Director, Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission, Washington D.C. 20555, within 30 days, which defines the corrective action to be taken to reduce subsequent releases to prevent recurrence of exceeding the limits above. This Special Report, as defined in 10 CFR Part 20.2203, shall include an analysis which estimates the radiation dose to a member of the public beyond the site boundary from uranium fuel cycle sources (including all effluent pathways and direct radiation) for a calendar year that includes the release(s) covered by this report. If the estimated dose(s) exceeds the above limits, and if the release condition resulting in violation of 40 CFR Part 190 has not already been corrected, the Special Report shall include a request for a variance in accordance with the provisions of 40 CFR Part 190 and include the specified information of Section 190.11 (b). Submittal of the report is considered a timely request, and a variance is granted until the staff action on the request is complete.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS
2.2.3 Cumulative
dose contributions from liquid and gaseous effluents shall be determined in accordance with the methodology and parameters in ODCM Sections 6.3, 7.3, and 7.4.
SQN ODCM Revision 58 Page 38 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM CONTROLS 1.3.1 The radiological environmental monitoring program shall be conducted as specified in Table 2.3-1.APPLICABILITY:
At all times.ACTION: a. With the radiological environmental monitoring program not being conducted as specified in Table 2.3-1, prepare and submit to the Commission, in the Annual Radiological Environmental Operating Report, a description of the reasons for not conducting the program as required and the plans for preventing a recurrence.
- b. With the level of radioactivity in an environmental sampling medium exceeding the reporting levels of Table 2.3-2 when averaged over any calendar quarter, prepare and submit to the Commission within 30 days from the end of the affected quarter, pursuant to ODCM Administrative Control 5.4, a Special Report that identifies the cause(s) for exceeding the limit(s) and defines the corrective actions to be taken to reduce radioactive effluents so that the potential annual dose to a member of the public is less than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2 and 1.2.2.3. When one or more of the radionuclides in Table 2.3-2 is detected in the sampling medium, this report shall be submitted if: concentration(1) concentration(2)
+ +. >1.0 limit level(l) limit level(2)When radionuclides other than those in Table 2.3-2 are detected and are the result of plant effluents, this report shall be submitted if the potential annual dose to a member of the public from all radionuclides is equal to or greater than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2, and 1.2.2.3. This report is not required if the measured level of radioactivity was not the result of plant effluents; however, in such an event, the condition shall be reported and described in the Annual Radiological Environmental Operating Report.
SQN ODCM Revision 58 Page 39 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM ACTION (CONTINUED):
- c. With milk or fresh leafy vegetable samples unavailable from one or more of the sample locations required by Table 2.3-1, identify locations for obtaining replacement samples and add them to the radiological environmental monitoring program within 30 days. The specified locations from which samples were unavailable may then be deleted from the monitoring program. Pursuant to ODCM Administrative Control 5.1, identify the new locations for obtaining replacement samples in the Annual Radiological Environmental Operating Report. A revised figure(s) and table(s) for the ODCM reflecting the new location(s) shall be included in the next Annual Effluent Release Report pursuant to ODCM Administrative Control 5.2.d. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.3.1 The radiological environmental monitoring samples shall be collected pursuant to Table 2.3-1 from the locations given in the tables and figures given in ODCM Section 9.0 and shall be analyzed pursuant to the requirements of Table 2.3-1 and the detection capabilities required by Table 2.3-3.
SQN ODCM Revision 58 Page 40 of 179 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 2)Exposure Number and Sampling and Pathway Location of Collection Type and Frequency of and/or Samples* Frequency Analysis Sample AIRBORNE Radioiodine Minimum of 5 W Radioiodine canister: and locations Continuous sampler**
Weekly 1-131 Particulates Particulate sampler: Analyze for gross beta activity L 24 hours following filter change.Perform gamma isotopic analysis on each sample when gross beta activity is >10 times the yearly mean of control samples Q: Perform gamma isotopic analysis on composite ( by location) sample.DIRECT RADIATION 35 to 40 locations Q Q: Gamma Dose with > 2 dosimeters for continuously measuring and recording dose rate at each location.WATERBORNE Surface 2 locations M Gamma isotopic Composite***
sample Each composite sample Tritium analysis Ground 2 locations Q Gamma isotopic and tritium analyses of each sample.Gross beta and gamma isotopic analysis Drinking Minimum of 1 M Q location Composite***
sample Tritium analysis M 2 locations Grab sample Gross beta and gamma isotopic analysis Shoreline Minimum of 2 S Gamma isotopic analysis Sediment locations from each sample.locations*Sample locations are given in Table 9.1.**Continuous sampling with sample collection as required by dust loading, but at least once per 7 days.***Composite samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
SQN ODCM Revision 58 Page 41 of 179 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 2)1 Milk Milk from 3 locations.
Samples of broad leaf vegetation at offsite locations of highest D/Q if no milk samples are available.
B**Gamma isotopic and 1-131 analysis of each sample.Fish 2 locations One sample in season, or at least once per 184 days if not seasonal.One sample representing a commercially important species and one sample representing a recreationally important species.Gamma isotopic analysis on edible portions.Food Minimum of 2 At time of harvest. Gamma isotopic analysis on Products locations One sample of each edible portions.of the following or similar classes of food products, as available 1. Lettuce and/or cabbage 2. Corn 3. Beans 4. Tomatoes**** When animals are on pasture, at least once per 31 days at other times.
SQN ODCM Revision 58 Page 42 of 179 Table 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES Analysis H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 1-131 Cs-134 Cs-1 37 Ba-La-140 Water (pCi/L)2 x 1 0 4(a)1 x i03 4 x 102 1 x 103 3 x 102 3 x 102 4 x 102 2 (b)30 50 2 x 102 Airborne Particulate or gases (pCi/m 3)N.A N.A.N.A.N.A.N.A.N.A.N.A.0.9 10 20 N.A.Fish (pCi/kg, wet)N.A 3 x 104 1 x 104 3 x 104 1 x 10 4 2 x 104 N.A.N.A.lx103 2x10 3 N.A.Milk (pCi/L)N.A.N.A.N.A.N.A.N.A.N.A.N.A.3 60 70 3 x 102 Food Products (pCi/kg, wet)N.A.N.A.N.A.N.A.N.A.N.A.N.A.lx102 lx103 2x10 3 N.A.(a) For drinking water samples. This is 40 CFR Part 141 value.(b) If no drinking water pathway exists, a value of 20 pCi/L may be used.
SQN ODCM Revision 58 Page 43 of 179 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)a,b (Page 1 of 2)Analysis gross beta H-3 Mn-54 Fe-59 Co-58,60 Zn-65 Zr-95 Nb-95 1-131 Cs-134 Cs-1 37 Ba-140 La-140 Water (pCi/L)4 2000*15 30 15 30 30 15 1**15 18 60 15 Airborne Particulate or Gases (pCi/m 3)lx10-2 N.A N.A.N.A.N.A.N.A.N.A.N.A.7x10-2 5x10-2 6x10-2 N.A.N.A.Fish (pCi/kg, wet)N.A.N.A 130 260 130 260 N.A.N.A.N.A.130 150 N.A.N.A.Milk (pCi/L)N.A N.A N.A.N.A.N.A.N.A.N.A.N.A.1 15 18 60 15 Food Products (pCi/kg,wet)
N.A.N.A.N.A.N.A.N.A.N.A.N.A.N.A.60 60 80 N.A.N.A.Sediment (pCi/kg,dry)
N.A.N.A.N.A.N.A.N.A.N.A.N.A.N.A.N.A.150 180 N.A.N.A.* If no drinking water pathway exists, a value of 3000 pCi/L may be used.** If no drinking water pathway exists, a value of 15 pCi/L may be used.
SQN ODCM Revision 58 Page 44 of 179 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)a,b (Page 2 of 2) TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.For a particular measurement system (which may include radiochemical separation):
4.66sb LLD =----------------------------------
E V 2.22 Y exp(-.At)where: LLD is the "a priori" lower limit of detection as defined above in picocurie per unit mass or volume, sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute), E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22 is the number of disintegrations per minute per picocurie, Y is the fractional radiochemical yield (when applicable), k is the radioactive decay constant for the particular radionuclide, and At for environmental samples is the elapsed time between sample collection (or end of the sample collection period) and time of counting.It should be recognized that the LLD is defined as an a priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.
Analysis will be performed in such a manner that the stated LLDs will be achieved under routine conditions.
b Other peaks which are measurable and identifiable, together with the radionuclides above, shall be identified and reported.Table 2.3-4 DETECTION CAPABILITIES FOR GROUNDWATER HARD-TO-DETECT NUCLIDES LOWER LIMITS OF DETECTION (LLD)ANALYSIS WATER (pCilLQ1 Fe-55 200 Ni-63 30 Sr-89 5 Sr-90 1 Gross Alpha 4 Multiply the values in this column by 10.9 to convert to units of iiCi/ml SQN ODCM Revision 58 Page 45 of 179 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.2 LAND USE CENSUS CONTROLS 1.3.2 A Land Use Census shall be conducted and shall identify within a distance of 8 km (5 miles) the location in each of the 16 meteorological sectors of the nearest milk animal, the nearest residence, and the nearest gardena of greater than 50 m 2 (500 ft 2) producing fresh leafy vegetables.
aBroad leaf vegetation sampling of at least three different kinds of vegetation may be performed at the site boundary in each of two different direction sectors with the highest predicted D/Qs in lieu of the garden census.Specifications for broad leaf vegetation sampling in Table 2.3-1 shall be followed, including analysis of control samples.APPLICABILITY:
At all times.ACTION: a. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment 20%greater than at a location from which doses are currently being calculated in ODCM Section 7.3 and 7.4 identify the new location(s) in the next Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.b. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment (via the same pathway) 20% greater than at a location from which samples are currently being obtained in accordance with the requirements of ODCM Control 1.3.1, add the new location(s) within 30 days to the radiological environmental monitoring program given in ODCM Section 9.0, if samples are available.
The sampling location(s), excluding the control station location, having the lowest calculated dose or dose commitment(s), via the same exposure pathway, may be deleted from this monitoring program after October 31 of the year in which this Land Use Census was conducted.
Pursuant to ODCM Administrative Controls 5.2 and 5.3, submit in the next Annual Radioactive Effluent Release Report documentation for a change in the ODCM including a revised figure(s) and table(s) for the ODCM reflecting the new location(s) with the information supporting the change in sampling locations.
- c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SQN ODCM Revision 58 Page 46 of 179 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 112.3.2 LAND USE CENSUS SURVEILLANCE REQUIREMENTS 2.3.2 The Land Use Census shall be conducted during the growing season at least once per 12 months using that information that will provide the best results, such as by a door-to-door survey, mail survey, telephone survey, aerial survey, or by consulting local agricultural authorities.
The results of the Land Use Census shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.
SQN ODCM Revision 58 Page 47 of 179 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM CONTROLS 1.3.3 Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the Commission.
APPLICABILITY:
At all times.ACTION: a. With analyses not being performed as required above, report the corrective actions being taken to prevent a recurrence to the Commission in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 2.3.3 A summary of the results obtained as a part of the above required Interlaboratory Comparison Program and in accordance with the guidance below shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.
SQN ODCM Revision 58 Page 48 of 179 BASES FOR SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS NOTE The BASES contained in succeeding pages summarize the reasons for the Controls in Sections 1.0 and 2.0, but are not part of these Controls.
SQN ODCM Revision 58 Page 49 of 179 BASES INSTRUMENTATION 112.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION The radioactive liquid effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in liquid effluents during actual or potential releases of liquid effluents.
The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 6.2 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.112.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION The radioactive gaseous effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in gaseous effluents during actual or potential releases of gaseous effluents.
The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 7.1 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.1.1 CONCENTRATION This Control is provided to ensure that the concentration of radioactive materials released at any time in liquid waste effluents to UNRESTRICTED AREAS will be less than ten times the concentration levels specified in 10 CFR Part 20, Appendix B, Table 2, Column 2. This limitation provides additional assurance that the levels of radioactive materials in bodies of water in UNRESTRICTED AREAS will result in exposures within (1) the Section II.A design objectives of Appendix I, 10 CFR 50, and (2) the limits of 10 CFR 20.1301(a)(1) to a member of the public. The concentration limit for dissolved or entrained noble gases is based upon the assumption that Xe-135 is the controlling radioisotope and its MPC in air (submersion) was converted to an equivalent concentration in water using the methods described in International Commission of Radiological Protection (ICRP) Publication 2.1/2.2.1.2 DOSE This Control is provided to implement the requirements of Sections II.A, Ill.A, and IV.A of Appendix 1, 10 CFR Part 50. The requirement implements the guide set forth in Section II.A of Appendix I. The action statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." Also, for fresh water sites with drinking water supplies which can be potentially affected by plant operations, there is reasonable assurance that the operation of the facility will not result in radionuclide concentrations in the finished drinking water that are in excess of the requirements of 40 CFR Part 141. The dose calculations in ODCM Section 6.3 implement the requirements in Section III.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data, such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to substantially underestimated.
The equations specified in Section 6.3 for calculating the doses due to the actual release rates of radioactive SQN ODCM Revision 58 Page 50 of 179 BASES 1/2.2.1.2 DOSE (continued) materials in liquid effluents are consistent with the methodology provided in Regulatory Guide 1.109,"Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.113, "Estimating Aquatic Dispersion of Effluents from Accidental and Routine Reactor Releases for the Purpose of Implementing Appendix I," April 1977.This Control applies to the release of liquid effluents from each reactor at the site. For units with shared radwaste treatment systems, the liquid effluents from the shared systems are proportioned among the units sharing that system.Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374.1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM The Control that the appropriate portions of this system be used when specified provides assurance that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." This requirement implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objective given in 10 CFR Part 50Appendix I, Section lI.D. The specified limits governing the use of appropriate portions of the liquid radwaste system were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I, Section II.A, for liquid effluents.
1/2.2.2.1 DOSE RATE This Control provides reasonable assurance that radioactive material discharged in gaseous effluents will not result in the exposure of a member of the public in an UNRESTRICTED AREA in excess of the design objectives of Appendix I to 10 CFR 50. This Control is provided to ensure that gaseous effluents from all units on the site will be appropriately controlled.
It provides operational flexibility for releasing gaseous effluents to satisfy the Section IL.A and II.C design objectives of Appendix Ito 10 CFR 50. For members of the public who may at times be within the CONTROLLED or RESTRICTED AREAS, the occupancy of that member of the public will usually be sufficiently low to compensate for the reduced atmospheric dispersion relative to that for the UNRESTRICTED AREA BOUNDARY.
Examples of calculations for such members of the public, with the appropriate occupancy factors, shall be given in the ODCM. The specified release rate limits restrict, at all times, the corresponding gamma and beta dose rates above background to a member of the public at or beyond the UNRESTRICTED AREA BOUNDARY to <500 mrem/y to the total body or to 3000 mrem/y to the skin.These limits also restrict, at all times, the corresponding thyroid dose rate above background to a child via the inhalation pathway to <1500 mrem/y. This Control does not affect the requirement to comply with the annual limitations of 10 CFR 20.1301 (a).This requirement applies to the release of radioactive material in gaseous effluents from all reactors at the site.
SQN ODCM Revision 58 Page 51 of 179 BASES 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2.2 DOSE -NOBLE GASES This requirement is provided to implement the requirements of 10 CFR Part 50 Appendix I, Sections II.B,lII.A and IV.A. The requirement implements the guides set forth in Appendix I Section lI.B Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." The surveillance implements the requirements in Section III.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to be substantially underestimated.
The dose calculations established in ODCM Section 7.3 for calculating the doses due to the actual release rates of radioactive noble gases in gaseous effluents are consistent with the methodology provided in Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.111, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977. The ODCM equations provided for determining the air doses at the UNRESTRICTED AREA BOUNDARY are based upon the historical average atmospheric conditions.
1/2.2.2.3 DOSE 131.1-133.
TRITIUM. AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS This Control is provided to implement the requirements 10 CFR Part 50 Appendix I Sections II.C, III.A and IV.A.The requirement implements the guides set forth in Appendix I Section II.C. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Appendix I Section IV.A to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." Section 7.4 calculational methods implement the requirements in Appendix I Section III.A that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a member of the public through appropriately modeled pathways is unlikely to be substantially underestimated.
Section 7.4 calculational methods for calculating the doses due to the actual release rates of the subject materials are consistent with the methodologies provided in NUREG/CR-1004, "A Statistical Analysis of Selected Parameters for Predicting Food Chain Transport and Internal Dose of Radionuclides," October 1979 and Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.111, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977.These equations also provide for determining the actual doses based upon the historical average atmospheric conditions.
The release rate specifications for Iodine-131, Iodine -133, tritium and all radionuclides in particulate form with half-lives greater than 8 days are dependent on the existing radionuclide pathways to man, beyond the UNRESTRICTED AREA BOUNDARY.
The pathways which were examined in the development of these calculations were: 1) individual inhalation of airborne radionuclides, 2) deposition of radionuclides onto green leafy vegetation with subsequent consumption by man, 3) deposition onto grassy areas where milk animals and meat producing animals graze with consumption of the milk and meat by man, and 4) deposition on the ground with subsequent exposure of man.
SQN ODCM Revision 58 Page 52 of 179 BASES 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2.4 GASEOUS RADWASTE TREATMENT This Control that the appropriate portions of these systems be used, when specified, provides reasonable assurance that the releases of radioactive materials in gaseous effluents will be kept "as low as reasonably achievable." This Control implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objectives given in 10 CFR Part 50 Appendix I Section ll.D. The specified limits governing the use of appropriate portions of the systems were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I Section 1I.B and II.C, for gaseous effluents.
1/2.2.3 TOTAL DOSE This Control is provided to meet the dose limitations of 40 CFR Part 190 that have been incorporated into 10 CFR Part 20 by 46 FR 18525. Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301 (a)(1) per 56 FR 23374. The ACTION requires the preparation and submittal of a Special Report whenever the calculated doses due to releases of radioactivity and to radiation from uranium fuel cycle sources exceed 25 mrem to the total body or any other organ except thyroid, which shall be limited to less than or equal to 75 mrem. For sites containing up to 4 reactors, it is highly unlikely that the resultant dose to a member of the public will exceed the dose limits of 40 CFR Part 190 if the individual reactors remain within twice the dose design objectives of Appendix I and if direct radiation doses from the units and from outside storage tanks are kept small. The Special Report will describe a course of action that should result in the limitation of annual dose to a member of the public to within the 40 CFR Part 190 limits. For the purposes of the Special Report, it may be assumed that the dose commitment to the member of the public from other uranium fuel cycle sources is negligible, with the exception that dose contributions from other nuclear fuel cycle facilities at the same site or within a radius of 8 km must be considered.
If the dose to any member of the public is estimated to exceed the requirements of 40 CFR Part 190, the Special Report with a request for a variance (provide the release conditions resulting in violation of 40 CFR Part 190 have not already been corrected), in accordance with the provisions of 40 CFR Part 190.11 and 10 CFR Part 20.2203, is considered to be a timely request and fulfills the requirements of 40 CFR Part 190 until NRC staff action is completed.
The variance only relates to the limits of 40 CFR Part 190, and does not apply in any way to the other requirements for dose limitation of 10 CFR Part 20, as addressed in ODCM Controls 1.2.1.1 and 1.2.2.1. An individual is not considered a member of the public during any period in which he/she is engaged in carrying out any operation that is a part of the nuclear fuel cycle.
SQN ODCM Revision 58 Page 53 of 179 BASES 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM The radiological environmental monitoring program required by this Control provides representative measurements of radiation and of radioactive materials in those exposure pathways and for those radionuclides that lead to the highest potential radiation exposures of members of the public resulting from the station operation.
This monitoring program implementsSection IV.B.2 of Appendix I to 10 CFR Part 50 and thereby supplements the radiological effluent monitoring program by verifying that the measurable concentration of radioactive materials and levels of radiation are not higher than expected on the basis of the effluent measurements and modeling of the environmental exposure pathways.
Guidance for this monitoring program is provided by the Radiological Assessment Branch Technical Position on Environmental Monitoring.
The required detection capabilities for environmental sample analyses are tabulated in terms of the lower limits of detection (LLDs). The LLDs required by Table 2.3-3 are considered optimum for routine environmental measurements in industrial laboratories.
It should be recognized that the LLD is defined as an a riori (before the fact) limit representing the capability of a measurement system and not as a posteriori (after the fact) limit for a particular measurement.
Detailed description of the LLD, and other detection limits can be found in HASL Procedures Manual, HASL-300 (revised annually), Curie, L. A., "Limits for Qualitative Detection and Quantitative Determination
-Application to Radiochemistry," Anal. Chem. 40, 586-93 (1968), and Hartwell, J. K., "Detection Limits for Radioanalytical Counting Techniques," Atlantic Richfield Hanford Company Report ARH-SA-215 (June 1975).1/2.3.2 LAND USE CENSUS This Control is provided to ensure that changes in the use of unrestricted areas are identified and that modifications to the monitoring program are made if required by the results of that census. The best survey information from the door-to-door, aerial, or consulting with local agricultural authorities shall be used. This census satisfies the requirements of Section IV.B.3 of Appendix I to 10 CFR Part 50. Restricting the census to gardens of greater than 500 ft 2 provides assurance that significant exposure pathways via leafy vegetables will be identified and monitored since a garden of this size is the minimum required to provide the quantity (26 kg/yr)of leafy vegetables assumed in Regulatory Guide 1.109 for consumption by a child. To determine this minimum garden size, the following assumptions were used, 1) that 20% of the garden was used for growing broad leaf vegetation (i.e., similar to lettuce and cabbage), and 2) a vegetation yield of 2 kg/m 2.1/2.3.3 INTERLABORATORY COMPARISON PROGRAM The requirement for participation in an Interlaboratory Comparison Program is provided to ensure that independent checks on the precision and accuracy of the measurements of radioactive material in environmental sample matrices are performed as part of the quality assurance program for environmental monitoring in order to demonstrate that the results are reasonably valid.
SQN ODCM Revision 58 Page 54 of 179 SECTION 3.0 DEFINITIONS SQN ODCM Revision 58 Page 55 of 179 3.0 DEFINITIONS The defined terms in this section appear in capitalized type in the text and are applicable throughout the ODCM.3.1 ACTION ACTION shall be that part of a Control that prescribes remedial measures required under designated conditions.
3.2 CHANNEL
CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel output such that it responds with the necessary range and accuracy to known values of the parameter which the channel monitors.
The CHANNEL CALIBRATION shall encompass the entire channel including the sensor and alarm and/or trip functions, and shall include the CHANNEL FUNCTIONAL TEST. The CHANNEL CALIBRATION may be performed by any series of sequential, overlapping, or total channel steps such that the entire channel is calibrated.
3.3 CHANNEL
CHECK A channel check shall be the qualitative assessment of channel behavior during operation by observation.
This determination shall include, where possible, comparison of the channel indication and/or status with other indications and/or status derived from independent instrument channels measuring the same parameter.
3.4 CHANNEL
FUNCTIONAL TEST A CHANNEL FUNCTIONAL TEST shall be: a. Analog channels -the injection of a simulated signal into the channel as close to the sensor as practicable to verify OPERABILITY including alarm and/or trip functions.
- b. Bistable channel -the injection of a simulated signal into the sensor to verify OPERABILITY including alarm and/or trip function.c. Digital channels -the injection of a simulated signal into the channel as close to the sensor input to the processor as practicable or the manipulation of a setpoint below existing background to verify operability including alarm and/or trip function.3.5 CIRCUIT FAILURE shall be defined as the loss of circuit power to the monitor.3.6 CONTROLLED AREA A CONTROLLED AREA, as defined in 10 CFR 20, is the area outside the RESTRICTED AREA but inside the 10 CFR 20 defined UNRESTRICTED AREA BOUNDARY, access to which can be limited by the licensee for any reason (See Figure 3.1).3.7 DOSE EQUIVALENT 1-131 DOSE EQUIVALENT 1-131 shall be that concentration of 1-131 (gCi/gram) which alone would produce the same thyroid dose as the quantity and isotopic mixture of 1-131, 1-132, 1-133, 1-134, and 1-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table III of TID-14844, "Calculation of Distance Factors for Power and Test Reactor Sites."
SQN ODCM Revision 58 Page 56 of 179 3.0 DEFINITIONS (continued)
3.8 FREQUENCY
NOTATION The FREQUENCY NOTATION specified for the Surveillance Requirements shall correspond to the intervals defined in Table 3.1.3.9 GASEOUS RADWASTE TREATMENT SYSTEM A GASEOUS RADWASTE TREATMENT SYSTEM is any system designed and installed to reduce radioactive gaseous effluents by collecting primary coolant system offgases from the primary system and providing for delay or holdup for the purpose of reducing the total radioactivity prior to release to the environment.
3.10 OPERABLE -OPERABILITY A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified function(s), and when all necessary attendant instrumentation, controls, a normal or an emergency electrical power source, cooling or seal water, lubrication or other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its function(s) are also capable of performing their related support function.3.11 MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, and average reactor coolant temperature specified in Table 1.1 of the SQN Technical Specifications.
3.12 PURGE -PURGING PURGE or PURGING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration or other operating condition, in such a manner that replacement air or gas is required to purify the confinement.
3.13 RADIATION MONITOR (RM) OR (R)A radiation monitor is identified by "RM" under instrumentation.
To be OPERABLE, it is minimally defined as an instrumentation channel that includes the radiation detector, associated sample delivery system, signal processing electronics, malfunction alarm, high radiation alarm, and at least one indicator (main control room, local, or computer point).3.14 RATED THERMAL POWER RATED THERMAL POWER shall be a total reactor core heat transfer rate to the reactor coolant of 3455 RTP 3.15 REPORTABLE EVENT A REPORTABLE EVENT shall be any of those conditions specified in Section 50.73 of 10 CFR 50.
SQN ODCM Revision 58 Page 57 of 179 3.0 DEFINITIONS (continued) 3.16 RESTRICTED AREA The RESTRICTED AREA, as defined in 10 CFR Part 20, is that area, access to which is limited by the licensee for the purposes of protecting individuals against undue risks from exposure to radiation and radioactive materials.
The permanent RESTRICTED AREA is shown on Figure 3.1, but temporary restricted areas outside the permanent RESTRICTED AREA may be defined by SQN.3.17 SITE BOUNDARY The site boundary is defined in 10 CFR 20 as that line beyond which the land or property is not owned, leased, or otherwise controlled by the licensee.3.18 SOURCE/SENSOR CHECK A SOURCE/SENSOR CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a radioactive source or other channel sensor internal test circuit.3.19 UNRESTRICTED AREA/BOUNDARY An UNRESTRICTED AREA/BOUNDARY, as used for calculations performed pursuant to 10 CFR Part 50.36a, shall be an area at or beyond the site boundary which is utilized in the ODCM Controls to keep levels of radioactive materials in liquid and gaseous effluents as low as is reasonably achievable.
The UNRESTRICTED AREA does not include areas over water bodies (See Figure 3.1).3.20 VENTILATION EXHAUST TREATMENT SYSTEM A VENTILATION EXHAUST TREATMENT SYSTEM is any system designed and installed to reduce gaseous radioiodine or radioactive material in particulate form in effluents by passing ventilation or vent exhaust gases through charcoal adsorbers and/or HEPA filters for the purpose of removing iodines or particulates from the gaseous exhaust stream prior to the release to the environment (such a system is not considered to have any effect on noble gas effluents).
Engineered Safety Feature (ESF) atmospheric cleanup systems are not considered to be VENTILATION EXHAUST TREATMENT SYSTEM components.
3.21 VENT FLOW RATE MONITOR (F)The vent flow rate monitors are identified by "F" under instrumentation.
To be OPERABLE is minimally defined as an instrumentation channel that includes the flow sensor, processing electronics and at least one indicator (main control room, local or computer point).3.22 VENTING VENTING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration, or other operating condition, in such a manner that replacement air or gas is not provided or required during VENTING. Vent, used in system names, does not imply a VENTING process.
SQN ODCM Revision 58 Page 58 of 179 Table 3.1 FREQUENCY NOTATION NOTATION FREQUENCY P Completed prior to each release D At least once per day W At least once per 7 days B At least once per 15 days M At least once per 31 days Q At least once per 92 days R At least once per 18 months S At least semi-annual NA Not Applicable SQN ODCM Revision 58 Page 59 of 179 Figure 3.1 UNRESTRICTED AREA BOUNDARY Restricted Areas At Sequoyah Nuclear Plant Filled areas indicate Restricted Areas At Sequoyah Nuclear Plant Power Stores Radioactive Materail Storage Area Old Stema Gaee-lo, Stoese WNetdo.)CTB U-1 RWST .odPWST U-2 RWSTa- I Independent Spent /Fuel Storage Facility Dry Active W.st. Bildig asd Yard Facility I II~ ~ I Lo 1 ar eedioactive WooS. Stoup~ Forility Filled areas indicate Restricted Areas.
SQN ODCM Revision 58 Page 60 of 179 SECTION 4.0 (NOT USED)
SQN ODCM Revision 58 Page 61 of 179 SECTION 5.0 ADMINISTRATIVE CONTROLS SQN ODCM Revision 58 Page 62 of 179 5.0 ADMINISTRATIVE CONTROLS 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT As required by SQN Technical Specification 6.9.1.6, the Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted prior to May 1 of each year.The annual radiological environmental operating reports shall include summaries, interpretations, and an analysis of trends of the results of the radiological environmental surveillance activities for the report period, including a comparison with preoperational studies, operational controls (as appropriate), and previous environmental surveillance reports and an assessment of the observed impacts of the plant operation on the environment.
The reports shall also include the results of land use censuses required by ODCM Control 1.3.2 and a listing of the new locations for dose calculations and/or environmental monitoring identified by the land use census. If harmful effects or evidence of irreversible damage are detected by the monitoring, the report shall provide an analysis of the problems and a planned course of action to alleviate the problem.The annual radiological environmental operating reports shall include summarized and tabulated results in the format of Regulatory Guide 4.8, December 1975 of all radiological environmental samples taken during the report period. In the event that some results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted as soon as possible in a supplementary report.The reports shall also include the following:
a summary description of the radiological environmental monitoring program; a map of all sampling locations keyed to a table giving distances and directions from one reactor; and the results of licensee participation in the Interlaboratory Comparison Program required by ODCM Control 1.3.3.5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT As required by SQN Technical Specification 6.9.1.8, an Annual Radioactive Effluent Release Report covering the operation of the site during the previous calendar year of operation shall be submitted prior to May 1 of each year.Annual radioactive release reports shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the site as outlined in Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants," Revision 1, June 1974, with data summarized on a quarterly basis following the format of Appendix B thereof.The annual radioactive release report shall include unplanned releases from the site to unrestricted areas and shall also include any changes made to the ODCM pursuant to ODCM Administrative Control 5.3.
SQN ODCM Revision 58 Page 63 of 179 5.0 ADMINISTRATIVE CONTROLS 5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT (continued)
The annual radioactive effluent release report shall include information for solid waste as outlined in the Process Control Program, and shall also include any changes made to the PCP during the reporting period, to the ODCM pursuant to ODCM Administrative Control 5.3, as well as any major changes to Liquid, Gaseous, or Solid Radwaste Treatment Systems, pursuant to SQN Technical Specifications.
It shall also include a listing of new location for dose calculations and/or environmental monitoring identified by the Land Use Census pursuant to ODCM Control 1.3.2.The radioactive effluent release reports shall also include the following:
an explanation as to why the inoperability of liquid or gaseous effluent monitoring instrumentation was not corrected within the time specified in ODCM Controls 1.1.1 or 1.1.2 respectively.
The annual radioactive effluent release report (Radiological Impact) shall include an annual summary of hourly meteorological data collected over the previous year. This annual summary may be either in the form of an hour-by-hour listing of wind speed, wind direction, atmospheric stability, and precipitation (if measured) on magnetic tape, or in the form of joint frequency distributions of wind speed, wind direction, and atmospheric stability.
In lieu of submission with the annual radioactive effluent release report, this summary of required meteorological data may be retained on site in a file that shall be provided to NRC upon request).
This same report shall include an assessment of the radiation doses due to radioactive liquid and gaseous effluents released from the unit or station during the previous calendar year. This same report shall also include an assessment of the radiation doses from radioactive liquid and gaseous effluents to members of the public due to their activities inside the UNRESTRICTED AREA BOUNDARY (Figure 3.1) during the report period. All assumptions used in making these assessments (i.e., specific activity, exposure time, and location) shall be included in these reports.The meteorological conditions concurrent with the time of release of radioactive materials in gaseous effluents (as determined by sampling frequency and measurement) shall be used for determining the gaseous pathway doses. The assessment of radiation doses shall be performed in accordance with Sections 6.6 and 7.6.The annual radioactive effluent release report to be submitted after January 1 of each year shall also include an assessment of radiation doses to the likely most exposed members of the public from reactor releases and other nearby uranium fuel cycle sources (including doses from primary effluent pathways and direct radiation) for the previous calendar year to show conformance with 40 CFR 190, Environmental Radiation Protection Standards for Nuclear Power Operation, in accordance with ODCM Section 8.0. Acceptable methods for calculating the dose contribution from liquid and gaseous effluents are given in Regulatory Guide 1.109, Revision 1.The Radioactive Effluent Release Report shall include results from any groundwater samples obtained in accordance with the Radiological Environmental monitoring Program during the reporting period that are not described in the ODCM.The Radioactive Effluent Release Report shall include any assigned doses that were performed as a result of a spill or leak from the site that occurred during the reporting period.The Radioactive Effluent Release Report shall include a summary of any on-site spills, leaks, and/or on-site ground water monitoring wells above ODCM reporting thresolds that occurred during the reporting period that were communicated to offsite agencies.
SQN ODCM Revision 58 Page 64 of 179 5.0 ADMINISTRATIVE CONTROLS 5.3 OFFSITE DOSE CALCULATION MANUAL CHANGES As required by SQN Technical Specification 6.14 and Appendix A, changes to the ODCM: 1. Shall be documented and records of reviews performed shall be retained in a manner convenient for review.This documentation shall contain: a. Sufficient information to support the change together with the appropriate analyses or evaluations justifying the change(s) and b. A determination that the change will maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 10 CFR Part 50.36a, and Appendix I to 10 CFR Part 50 and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations.
- 2. Shall become effective after review and acceptance by the process described in TVA-NQA-PLN89-A.
- 3. Shall be submitted to the Commission in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Annual Radioactive Effluent Release Report for the period of the report in which any change to the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month/year) the change was implemented.
Changes to the ODCM shall be performed in accordance with the requirements of Appendix A.5.4 SPECIAL REPORTS Special Reports shall be submitted within the time period specified for each report, in accordance with 10 CFR Part 50.4.
SQN ODCM Revision 58 Page 65 of 179 SECTION 6.0 LIQUID EFFLUENTS SQN ODCM Revision 58 Page 66 of 179 SECTION 6.0 LIQUID EFFLUENTS RELEASE POINTS There are four systems from which liquid effluents are released to the environment.
These are the Liquid Radwaste System, the Condensate Demineralizer System, the Turbine Building Sump (TBS), and the Units 1 and 2 Steam Generator Blowdown.
Figure 6.1 provides an outline of the liquid release paths and discharge points with associated flow rates and radiation monitors.All liquid effluents are ultimately discharged to the Diffuser Pond which releases to the Tennessee River where they are evaluated for offsite dose. The Essential Raw Cooling Water (ERCW) continuously supplies the Cold Water Channel which routinely provides dilution for liquid effluents at a minimum flow rate of 15,000 gpm.However, a minimum 17,000 gpm operational requirement is in place utilizing the ICS computer point OF2120DIF to ensure the 15,000 gpm requirement is adhered. ERCW flow is monitored by radiation monitors 0-RM-90-133, -134, -140, -141.Releases are made as either batch or continuous release. Releases from Radwaste Tanks are made as batch releases.
The TBS and SGBD are continuous releases when flow exists. The Condensate Demineralizer tanks are routinely released as continuous release to the TBS, but can be released as batch release to the CTBD.For batch releases, any tank to be released is sampled for activity, as described in ODCM Section 6.1.1. The tank contents are analyzed to determine the maximum allowable release flow rates to ensure compliance with concentration limits of ODCM Control 1.2.1.1 as described in ODCM Section 6.1.2. The sampling results are also used to determine a setpoint for the associated radiation monitor for the release in accordance with ODCM Section 6.2.3. Pre-release calculations are performed assuming the minimum dilution of 15,000 gpm.For continuous releases, the pathways are sampled for radioactivity periodically, as described in ODCM Section 6.1.1. The samples are analyzed to ensure compliance with concentration limits of ODCM Control 1.2.1.1, as described in ODCM Section 6.1.2. The sampling results are also used to determine a setpoint for the associated radiation monitor for the release in accordance with ODCM Section 6.2.3. Pre-release calculations for points other than the Turbine Building Sump are performed assuming the minimum dilution flow of 15,000 gpm. The pre-release calculation for SGBD may be performed using 0 for the dilution flow and SGBD may be in-service to the CTBD with no dilution flow when the ECL for the SGBD is < 10.Liquid Radwaste System The Liquid Radwaste System processes liquid from the Reactor Building and Auxiliary Building Floor Drains and the laundry/hot shower and chemical drain tanks. Figure 6.2 provides a schematic of the Liquid Radwaste System, showing the liquid pathways, flow rate and radiation monitors.
The normal release points for liquid radwaste are the Monitor Tank and the Cask Decontamination Collector Tank (CDCT). The Monitor Tank has a capacity of 22,000 gal and is released routinely at a flow rate of 125 gpm. The CDCT has a capacity of 15,000 gal and is also released routinely at a flow rate of 125 gpm. The Monitor Tank and CDCT discharge to the Cooling Tower Blowdown (CTBD) line as a batch release and are monitored by radiation monitor 0-RM-90-122.
SQN ODCM Revision 58 Page 67 of 179 Condensate Demineralizer System The Condensate Demineralizer System processes liquid wastes coming from the High Crud Tanks (HCT-1 and -2), the Neutralization Tank, and the Non-Reclaimable Waste Tank (NRWT). The HCTs have a capacity of 20,000 gal and a maximum discharge flow rate of 245 gpm. The Neutralization Tank has a capacity of 19,000 gal and a maximum discharge flow rate of 245 gpm. The NRWT has a capacity of 11,000 gal and a maximum discharge flow rate of 245 gpm. The Condensate Demineralizer System is routinely released as continuous releases during periods of low radioactivity levels to the TBS, but can be released to the CTBD and is monitored by radiation monitor 0-RM-90-225.
Turbine Building Sump The Turbine Building Sump (TBS) normally releases to the Low Volume Waste Treatment Pond (LVWTP) but can be released to the Yard Pond. The TBS has a capacity of 30,000 gal and a design discharge release rate of 1,750 gpm per pump. TBS releases are monitored by radiation monitor 0-RM-90-212.
Steam Generator Blowdown The Steam Generator Blowdown (SGBD) is processed in the Steam Generator Draindown Flash Tanks or SGBD Heat Exchangers.
The SGBD discharge has a maximum flow rate of 80 gpm per steam generator.
SGBD discharges to the CTBD line are continuous and are monitored by radiation monitors 1,2-RM-90-120, -121.
SQN ODCM Revision 58 Page 68 of 179 6.1 LIQUID RELEASES 6.1.1 Pre-Release Analysis To ensure representative sampling, radwaste tanks will be recirculated for a procedurally established length of time, or through two volumes. Periodically, checks will be made to ensure a representative mixing of tank contents.
All radwaste tanks will be released as "batch" releases.Releases from condensate demineralizer tanks are routinely continuous releasesa and utilize a composite sampler to obtain a representative sample while being discharged.
In the event of an inoperable composite sampler, the releases will be made as a batch release, and will be recirculated for a procedurally established length of time or through two volumes to ensure representative sampling.Steam generator blowdown and turbine building sumpa are considered continuous and grab sampled daily during releases.Prior to any batch release, a grab sample will be taken and analyzed to determine the concentration, laCi/ml, of each gamma-emitting nuclide. For continuous releases, daily grab or composite samples will be taken on days when releases are being made and analyzed to determine the concentration, pCi/ml, of each gamma-emitting nuclide. Composite samples are maintained during periods of radioactive discharge from all pathways (as required by Table 2.2-1) to determine the concentration of certain nuclides (H-3, Fe-55, Sr-89, Sr-90, and alpha emitters).
For those nuclides whose activities are determined from composite samples, the concentrations for the previous composite period can be assumed as the concentration for the next period to perform the calculations in Sections 6.3 and 6.5. The actual measured concentrations will be used for the dose calculations described in Section 6.6.a Sampling requirements for these release points are applicable only during periods of significant primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is at a LLD of <1 E-06 ICi/ml and allowing for background radiation during periods when primary to secondary leakage is occurring.
Sampling and analysis is routinely performed versus utilizing the radiation monitor at this LLD.6.1.2 Effluent Concentration Limits (ECL)-Sum of the Ratios The sum of the ratios (Ri) for each release point will be calculated by the following relationship.
Ci aj = I ---------
(6.1)i ECLi where: Ri = the sum of the ratios for release point j.ECLi = the ECL of radionuclide i, gCi/ml, from 10 CFR Part 20, Appendix B, Table 2, Column 2.Ci = concentration of radionuclide i, VCi/ml.The sum of the ECL ratios must be < 10 following dilution at the Cooling Tower Blowdown due to the releases from any or all of the release points described above. The ECL ratios for releases from the Turbine Building Sump will be < 10 at the sump.
SQN ODCM Revision 58 Page 69 of 179 The following relationship is used to ensure that this criterion is met: fiR 1 + f 2 R 2 + f 3 R 3 + f 4 R 4 (6.2)RTBS + < 10.0 F where RTBS = sum of the ECL ratios of the turbine building sump as determined by equation 6.1.fl,f2,f3,f4
= effluent flow rate for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, gpm.R1,R2,R3,R4
= sum of ECL ratios for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, as determined by equation 6.1.F = dilution flow rate for CTBD, routinely 15,000 gpm.6.1.3 Post-Release Analysis A post-release evaluation will be done using actual release data to ensure that the limits specified in ODCM Control 1.2.1.1 were not exceeded.
This analysis will include an evaluation of the noble gas concentration with regard to ODCM Control 1.2.1.1.A composite list of concentrations (Ci), by isotope, will be used with the actual waste (f) and dilution (F) flow rates (or volumes) during the release. The data will be evaluated to demonstrate compliance with the limits in ODCM Control 1.2.1.1.
SQN ODCM Revision 58 Page 70 of 179 6.2 INSTRUMENT SETPOINTS Liquid effluent monitor setpoints are determined to ensure that the concentration of radioactive material released at any time from the site to UNRESTRICTED AREAS does not exceed ten times the ECL limits referenced in ODCM Control 1.2.1.1 and to identify any unexpected releases.
The essential raw cooling water (ERCW) will be used for dilution for liquid effluents; however, the very large dilution factors afforded by the circulating coolant will not be used to allow high concentrations of liquid radioactive waste to be discharged from the plant.6.2.1 Discharge Point Monitor Setpoints (0-RM-90-133,134,140,141)
The setpoints for the ERCW monitors (RM-90-133, 134, 140, 141) are set to ensure that the concentration of radioactive materials released at any time from the site do not exceed the limits given in ODCM Control 1.2.1.1.The setpoints for these monitors will be set at a small value above background to ensure that any radioactivity is identified.
Site procedures will document and control this value.6.2.2 Release Point Monitor Setpoints (0-RM-90-122; O-RM-90-225; O-RM-90-212; 1,2-RM-90-120,121)
There are five liquid release point effluent monitors:
the Liquid Radwaste System radiation monitor 0-RM-90-122; the Condensate Demineralizer System radiation monitor 0-RM-90-225; the Turbine Building Sump radiation monitor 0-RM-90-212; and the Steam Generator Blowdown (SGBD) radiation monitors 1,2-RM 120,121.The batch release points, the Liquid Radwaste System and the Condensate Demineralizer System (if being released in a batch mode), are looking at an undiluted waste stream as it comes out of a tank. The purpose of the monitor setpoints for these batch releases is to identify any release that is larger than expected and would have the potential to exceed the limits after dilution.
Setpoints are calculated as described in Section 6.2.3 and may be set at a default value. Site procedures will document and control this value.The continuous release points, the Condensate Demineralizer System, the Steam Generator Blowdowns, and the Turbine Building Sump, will not be releasing radioactivity unless there is or has been a primary to secondary leak. When there is no identified primary to secondary leakage, these release points are monitored to indicate the presence of elevated activity levels in these systems. The setpoints for these monitors will be set to alarm if the activity in the stream exceeds a routine nominal background.
These setpoints are controlled by site instructions.
When there is identified significant primary to secondary leakage, the continuous release points are monitored to identify any release that is larger than expected or would have the potential to exceed the 10 CFR Part 20 limits after dilution.
The monitor setpoints are calculated in the same manner as the batch release point monitor setpoints (described in Section 6.2.3) when this is the case. When these release points are being treated in this manner, a single batch release is defined as all effluent released through this point on a continuous bases for a period of time (usually one week).6.2.3 Batch Release Point Monitor Setpoint For each release from a release point, two setpoints are calculated:
one based on the monitor response to the contents of the effluent stream multiplied by an administrative factor to account for monitor fluctuations; and another based on the predicted response of the monitor to the activity in the release stream if it were large enough to exceed ten times the 10 CFR Part 20 limits after dilution.
The expected monitor response, R in cpm, is calculated using equation 6.3 below.The maximum calculated setpoint, Smax, is calculated using Equation 6.4 below. A comparison is made between these two calculated setpoints to determine which is used. The actual monitor setpoint for the release SQN ODCM Revision 58 Page 71 of 179 is set equal to X times the expected radioactivity response plus background, or to the maximum calculated setpoint, whichever is less. X is an administrative factor designed to account for expected variations in monitor response (it will be defined in approved plant instructions).
The X times expected response setpoint allows for the identification of any release of radioactivity above the expected amount. The maximum calculated setpoint ensures that the release will be stopped if it exceeds ten times the 10 CFR Part 20 concentration limits after dilution.
If default setpoints are used then a comparison is made between the calculated setpoints and the default setpoint as described below to choose the appropriate setpoint for the monitor during the release (after the release, the monitor is normally returned to the default setpoint).
- 1. If SER < Sdefault < Smax Reported = Sdefault 2. If SER < Smax < Sdefault Reported = SER 3. If SER > Smax Reported = Smax Expected response / Expected Response Setpoint (Ser)R = B + Y Effi
- Ci (6.3)i Ser = X
- R where B = monitor background, cpm.Effi = monitor efficiency for nuclide i, cpm per pCi/ml.Ci = tank concentration of nuclide i, jiCi/ml.X = Administrative Factor designed to account for expected variations in monitor response and background (The range of values is 1.5 < X < 2.0).Calculated Maximum Monitor Setpoint 10 FS (Fw + (A
- Fdil))Smax = (R- B)+ B (6.4)Fw Rj where FS = fluctuation safety factor for the monitor, which is set at 1.0 < SF < 1.5. The fluctuation safety factor is set to account for minor changes in monitor response and background.
Fw = flow of waste stream, gpm.Fdil = flow of the dilution stream, routinely set @ 15,000 gpm.A = fraction of dilution flow allocated to this release point. For the TBS, this fraction is zero. The fractions for the remaining 4 release points are defined as the ratio of the allocated CTBD flow for that release point to the total CTBD flow. The CTBD flow allocation fractions for these release points are routinely:
Radwaste 0.60 Condensate demineralizer 0.20 Steam Generator Blowdown (Ul) 0.10 Steam Generator Blowdown (U2) 0.10 NOTE: These allocation factors may be adjusted for a particular release if it is known that there are no releases being made through other release points into the CTBD. For example, if there are no releases being made through the Condensate Demineralizer or either Steam Generator Blowdown, the allocation factor for the Radwaste System may be set equal to one.R. = sum of the ECL ratios for release pointj as calculated in Section 6.1.2.= expected monitor response, cpm, as calculated above.B = background, cpm.10 = ECL ratio limit at the Cooling Tower Blowdown discharge.
SQN ODCM Revision 58 Page 72 of 179 6.3 CUMULATIVE LIQUID EFFLUENT DOSE CALCULATIONS Doses due to liquid effluents are calculated for each release for all age groups: adult (_17 years of age), teen (_1 1, but <17 years), child (1, but <11 years) and infant (0-1 years) and organs: bone, liver, total body, thyroid, skin, kidney, lung and GI tract. Pathways considered are ingestion of drinking water, fish consumption and recreation-shoreline.
The maximum individual dose from drinking water is assumed to be that calculated at the location immediately downstream from the diffuser in the Tennessee River. The maximum individual dose from fish ingestion is assumed to be that calculated for the consumption of fish caught anywhere between the plant and the first downstream dam (Chickamauga Dam). The maximum potential recreation dose is calculated for a location immediately downstream of the plant outfall. Dose factors for these age groups and pathways are calculated as described in Section 6.7. For pathways with no age or organ specific dose factors (i.e. shoreline recreation), the total body dose will be added to the internal organ doses for all age groups.The general equation for the dose calculations is: Dose = Ij Ait T Ci D (6.5)where: Ait = the total dose factor to the total body or any organ t for nuclide i, mrem/hr per iCi/ml. The total dose factor is the sum of the dose factors for water ingestion, fish ingestion, and shoreline recreation, as defined in Section 6.7.T =the length of time period over which the concentrations and the flows are averaged for the liquid release, hours.Ci =the average concentration of radionuclide i, in undiluted liquid effluent during the time period T from any liquid release, iCi/ml.D = the near field average dilution factor for Ci during any effluent release. D is calculated by the following equation: FLOWW D-=0.60 RF where: FLOWw= maximum undiluted liquid waste flow during the release, cfs. For TBS releases, this term is the diluted waste flow into the pond.0.60 = mixing factor of effluent in river, defined as the percentage of the river flow which is available for dilution of the release.RF = default riverflow, cfs. For each release, this value is set to 7900 cfs (the lowest average quarterly riverflow recorded from the period 1978-1988).
From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The total body and maximum organ doses for the critical age group are used in the calculation of the monthly dose described in Section 6.3.1.
SQN ODCM Revision 58 Page 73 of 179 6.3.1 Monthly Dose Calculations At the end of each month, the actual average riverflow for the month is used to recalculate the liquid doses. The monthly cumulative dose is defined as the sum of the doses for the critical age group for each release during the month. Thus, the monthly cumulative dose will be a conservative value, consisting of doses belonging to various age groups depending on the mix of radionuclides.
These doses are multiplied by the ratio of the default riverflow (7900 cfs) to the actual monthly average riverflow to obtain the monthly dose. The total body and maximum organ doses determined in this manner are then used to determine the cumulative quarterly and annual doses described in Section 6.3.2, and for the dose projections described in Section 6.5.6.3.2 Cumulative Doses Quarterly and annual sums of all doses are determined at the end of each month to compare to the limits given in ODCM Control 1.2.1.2. These quarterly and annual sums will be the sum of the monthly cumulative doses described in Section 6.3.1 for the appropriate months in the quarter or year. These doses will be used in the comparison to the limits.6.3.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to the limits in ODCM Control 1.2.1.2 once per 31 days to determine compliance.
SQN ODCM Revision 58 Page 74 of 179 6.4 LIQUID RADWASTE TREATMENT SYSTEM The liquid radwaste treatment system described below shall be maintained and operated to keep releases ALARA.A flow diagram for the LRTS is given in Figure 6.2. The system consists of one reactor coolant drain tank with two pumps and a floor and equipment drain sump inside the containment of each unit and the following shared equipment inside the auxiliary building:
one sump tank and pumps, one tritiated drain collector tank with two pumps and one filter, one floor drain collector tank with two pumps and one filter, a waste condensate tank filter, three waste condensate tanks and two pumps, a chemical drain tank and pump, two laundry and hot shower tanks and pump, a spent resin storage tank, a cask decontamination tank with two pumps and two filters, Auxiliary Building floor end equipment drain sump and pumps, and evaporator with two distillate tanks, a Mobile Waste Demineralizer System (if needed) and the associated piping, valves and instrumentation.
SQN ODCM Revision 58 Page 75 of 179 6.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.1.3, dose projections will be performed by averaging the two previous month's doses as determined in Section 6.3.1. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.The projected doses are compared to the limits of ODCM Control 1.2.1.3. If the projected doses exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge to UNRESTRICTED AREAS.D= a+b 2 where: D = the 31-day dose projection, mrem a = the cumulative dose for the previous month, mrem b = the cumulative dose for the present month, mrem SQN ODCM Revision 58 Page 76 of 179 6.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated liquid releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel.
The releases are assumed, for this calculation, to be continuous over the 90 day period.The average dilution factor, D, used for the quarterly calculations is: 1 D = (for receptors upstream (6.6)RF
- 0.60 of Chickamauga Dam)and 1 D = (for receptors downstream (6.7)RF of Chickamauga Dam)where: RF = the average actual riverflow for the location at which the dose is being determined, cfs.0.60 = the fraction of the riverflow available for dilution in the near field, dimensionless.
6.6.1 WATER
INGESTION Water ingestion doses are calculated for each water supply identified within a 50 mile radius downstream of SQN (Table 6.1). The summation of water ingestion doses are calculated for the total body and each internal organ as described below: Dorg = 106 9.80E-09 0.2 5,Awit Qi D exp(-8.64E+04 Xi td) (6.8)where 106 = conversion factor, giCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.0.25 = fraction of the yearly water consumption in one quarter, dimensionless Awit = dose factor for water ingestion for nuclide i, age group t, mrem/h per gCi/ml, as calculated in Section 6.7.1.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs-1.k'i -= radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for water ingestion, equal to the travel time from the plant to the water supply plus one day to account for the time of processing at the water supply (per Regulatory Guide 1.109), d.8.64E+04 = conversion factor, seconds per day.
SQN ODCM Revision 58 Page 77 of 179 6.6.2 FISH INGESTION Fish ingestion doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). The summation of individual fish ingestion doses are calculated for the total body and each internal organ as described below: D = 106 9.80E-09 0.25 -Fit Qi D exp(-8.64E+04
?'i td) (6.9)where 106 = conversion factor, gCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.0.25 = fraction of the yearly fish consumption eaten in one quarter, dimensionless.
AFit = dose factor for fish ingestion for nuclide i, age group t, mrem/h per j.Ci/ml, as calculated in Section 6.7.2.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs-1.ki = radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for fish ingestion, equal to the travel time from the plant to the center of the reach plus one day to account for transit through the food chain and food preparation time (per Regulatory Guide 1.109), d.8.64E+04 = conversion factor, seconds per day.6.6.3 SHORELINE RECREATION Recreation doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). It is assumed that the maximum exposed individual spends 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> per year on the shoreline at a location immediately downstream from the diffusers.
The summation of individual recreation shoreline doses are calculated for the total body and skin as described below: Dorg =10 6 9.80E-09 rf ,.ARit Qi D exp(-8.64E+04 Xi td) (6.10)where 106 = conversion factor, gCi/Ci.9.80E-09 = conversion factor, cfs per ml/h.rf = recreation factor, used to account for the fact that the same amount of time will not be spent at a recreation site during each quarter. Recreation factors used are: 1st quarter -0.1 2nd quarter -0.3 3rd quarter -0.4 4th quarter -0.2.ARit = dose factor for shoreline recreation for nuclide i, age group t, mrem/h per pCi/ml, as calculated in Section 6.7.3.Qi = Quantity of nuclide i released during the quarter, Ci.D = dilution factor, as described above, cfs" 1 X. = radiological decay constant of nuclide i, s-1 (Table 6.2).td = decay time for recreation, equal to the travel time from the plant to the center of the reach, d.8.64E+04 = conversion factor, seconds per day.
SQN ODCM Revision 58 Page 78 of 179 6.6.4 TOTAL MAXIMUM INDIVIDUAL DOSE The total maximum individual total body dose is obtained by summing the following for each age group: the highest total body water ingestion dose from among all the public water supplies; the highest total body fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual organ dose is obtained by summing the following for each organ and each age group: that organ's highest water ingestion dose from among all the public water supplies; that organ's highest fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual skin dose is that skin dose calculated for the maximum shoreline dose.6.6.5 POPULATION DOSES For determining population doses to the 50-mile population around the plant, an average dose is calculated for each age group and each pathway and then multiplied by the population.
For water ingestion, the general equation used for calculating the population doses, POPWTR, in man-rem for a given PWS is: 4 4 POPWTRt = 10-3 y popm Z POPa ATMWa TWDOSamt (6.11)m=1 a=1 where: POPWTRt = water ingestion population dose to organ t, man-rem.POPa = fraction of population in each age group a (from NUREG CR-1004, table 3.39).Adult = 0.665 Child = 0.168 Infant = 0.015 Teen = 0.153 POPm = population at PWS m. The 4 PWSs and their populations are listed in Table 6.1.ATMWa = ratio of average to maximum water ingestion rates for each age group a. Maximum water ingestion rates are given in Table 6.3. Average water ingestion rates, in I/year, (from R.G. 1.109 Table E-4) are: Adult = 370 Child = 260 Infant = 260 Teen = 260 TWDOSamt = total individual water ingestion dose to organ t at PWS m, to the age group a, as described in Section 6.6.1, mrem.10-3 = conversion factor for rem/mrem.
SQN ODCM Revision 58 Page 79 of 179 For population doses resulting from fish ingestion the calculation assumes that all fish caught within a 50-mile radius downstream of SQN are consumed by local population.
The general equation for calculating population doses, POPF, in man-rem from fish ingestion of all fish caught within a 50-mile radius downstream is: 453.6 HVST APR 4 3 TFDOSart POPa POPFt= I 1 (6.12)103 103 r=1 a=1 FISHa POPa where: POPFt = total fish ingestion population dose to organ t, man-rem.HVST = fish harvest for the Tennessee River, 3.04 lbs/acre/y.
APR = size of reach, acres (Table 6.1).TFDOSart = total fish ingestion dose to organ t for reach r, for the age group a, as described in Section 6.6.2, mrem.Popp = fraction of population in each age group a, as given above.FISHa = amount of fish ingested by each age group a, kg/y. Average fish ingestion rates (R.G. 1.109 Table E-4) are: Adult = 6.9 Child = 2.2 Teen = 5.2 453.6 = conversion factor, g/lb.103 = conversion factor, mrem/rem.103 = conversion factor, g/kg.
SQN ODCM Revision 58 Page 80 of 179 For recreation shoreline, the general equation used for calculating the population doses, POPR, in man-rem is: REQFRA 4 POPRt = I__ TSHDOSrt SHVISr HRSVISr 103 8760 r=1 (6.13)where: POPRt =REQFRA =TSHDOSrt =SHVISr =HRSVISr 103 =8760 =total recreation population dose for all reaches to organ t, man-rem.fraction of yearly recreation which occurs in that quarter, as given in Section 6.6.3.total shoreline dose rate for organ t, in reach r, mrem/h.shoreline visits per year at each reach r, (Table 6.1).length of shoreline recreation visit at reach r, 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.conversion factor, mrem/rem.conversion factor, hours per year.
SQN ODCM Revision 58 Page 81 of 179 6.7 LIQUID DOSE FACTOR EQUATIONS 6.7.1 WATER INGESTION Awit (mrem/h per gCi/ml)DFLiat Uwa 106 103 Awit =': 8760 where: DFLiat= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).U = water consumption rate for age group a, L/y, (Table 6.3).10 = conversion factor, pCi/pCi.103 = conversion factor, ml/l.8760 = conversion factor, hours per year.6.7.2 FISH INGESTION AFit (mrem/h per pCi/ml)DFLiat Ufa Bi 106 10 3 AFit = _ _ _ _ _ _ _ _ _ _8760 where: DFLiat= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).Ufa = fish consumption rate for age group a, kg/y, (Table 6.3).Bi = bioaccumulation factor for nuclide i, pCi/kg per pCi/L, (Table 6.5).106 = conversion factor, pCi/pCi.103 = conversion factor, mil/L.8760 = conversion factor, hours per year.6.7.3 SHORELINE RECREATION ARt (mrem/h per g.Ci/ml).DFGit Kc M W 103 106 U ARit= [1 -exp(-kitb)]
8760
- 3600 ki where: DFGit= dose conversion factor for standing on contaminated ground for nuclide i and organ t (total body and skin), mrem/h per pCi/m 2 , (Table 6.6).Kc = transfer coefficient from water to shoreline sediment, L/kg-h, (Table 6.3).M = mass density of sediment, kg/m 2 , (Table 6.3).W = shoreline width factor, dimensionless, (Table 6.3).103 = conversion factor, mil/L.106 = conversion factor, pCi/jiCi.3600 = conversion factor, s/h.ki = decay constant for nuclide i, s-1 , (Table 6.2).tb = time shoreline is exposed to the concentration on the water, s, (Table 6.3).U = usage factor, 500 h/y.8760 = conversion factor, hours per year.
SQN ODCM Revision 58 Page 82 of 179 Table 6.1 RECEPTORS FOR LIQUID DOSE CALCULATIONS Tennessee River Reaches Within 50 Mile Radius Downstream of SQN Beginning Ending Size Recreation Name TRM TRM (acres) visits/year Chickamauga Lake 484 471 9939 5,226,700 below SQN Nickajack Lake 471 (Chickamauga Dam to TRM 435)Nickajack Lake 435 (TRM 435 to Nickajack Dam)Guntersville Lake 425 (Nickajack Dam to SQN 50 mi. Radius)435 425 400 6510 5326 6766 240,700 607,600 104,000 Public Water Supplies Within 50 Mile Radius Downstream of SQN Name East Side Utility (Formally C.F. Industries)
Chattanooga, TN South Pittsburg, TN Bridgeport, AL TRM 473.0 465.3 418.0 413.6 Population 35000 224,000 4,898 4,650 SQN ODCM Revision 58 Page 83 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 1 of 3)Half-Life X Biv Fmi Fmi Ffi (minutes) (l/s) (cow) (igoat) (beef)H-3 6.46E+06 1.79E-09 4.80E+00 1.OOE-02 1.70E-01 1.20E-02 C-14 3.01E+09 3.84E-12 5.50E+00 1.20E-02 1.OOE-01 3.1OE-02 Na-24 9.OOE+02 1.28E-05 5.20E-02 4.OOE-02 4.OOE-02 3.OOE-02 P-32 2.06E+04 5.61 E-07 1.10E+00 2.50E-02 2.50E-01 4.60E-02 Cr-51 3.99E+04 2.90E-07 2.50E-04 2.20E-03 2.20E-03 2.40E-03 Mn-54 4.50E+05 2.57E-08 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Mn-56 1.55E+02 7.45E-05 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Fe-55 1.42E+06 8.13E-09 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Fe-59 6.43E+04 1.80E-07 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Co-57 3.90E+05 2.96E-08 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Co-58 1.02E+05 1.13E-07 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Co-60 2.77E+06 4.17E-09 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Ni-63 5.27E+07 2.19E-10 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Ni-65 1.51 E+02 7.65E-05 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Cu-64 7.62E+02 1.52E-05 1.20E-01 1.40E-02 1.30E-02 9.70E-04 Zn-65 3.52E+05 3.28E-08 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69m 8.26E+02 1.40E-05 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69 5.56E+01 2.08E-04 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Br-82 2.12E+03 5.45E-06 7.60E-01 5.OOE-02 5.OOE-02 2'60E-02 Br-83 1.43E+02 8.08E-05 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-84 3.18E+01 3.63E-04 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-85 2.87E+00 4.02E-03 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Rb-86 2.69E+04 4.29E-07 1.30E-01 3.OOE-02 3.OOE-02 3.10E-02 Rb-88 1.78E+01 6.49E-04 1.30E-01 3.OOE-02 3.OOE-02 3.10E-02 Rb-89 1.54E+01 7.50E-04 1.30E-01 3.OOE-02 3.OOE-02 3.10E-02 Sr-89 7.28E+04 1.59E-07 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-90 1.50E+07 7.70E-10 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-91 5.70E+02 2.03E-05 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-92 1.63E+02 7.09E-05 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Y-90 3.85E+03 3.OOE-06 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-91m 4.97E+01 2.32E-04 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-91 8.43E+04 1.37E-07 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-92 2.12E+02 5.45E-05 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-93 6.06E+02 1.91 E-05 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Zr-95 9.22E+04 1.25E-07 1.70E-04 5.O0E-06 5.OOE-06 3.40E-02 Zr-97 1.01E+03 1.14E-05 1.70E-04 5.OOE-06 5.OOE-06 3.40E-02 Nb-95 5.05E+04 2.29E-07 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Nb-97 7.21 E+01 1.60E-04 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Mo-99 3.96E+03 2.92E-06 1.20E-01 7.50E-03 7.50E-03 1.1OE-03 Tc-99m 3.61E+02 3.20E-05 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Tc-101 1.42E+01 8.13E-04 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Ru-103 5.67E+04 2.04E-07 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 Ru-105 2.66E+02 4.34E-05 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 Ru-106 5.30E+05 2.18E-08 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 SQN ODCM Revision 58 Page 84 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 2 of 3)Half-Life X Biv Fmi Fmi Ffi (minutes) (l/s) (cow) (goat) (beef)Ag-110m 3.60E+05 3.21E-08 1.50E-01 5.OOE-02 5.OOE-02 1.70E-02 Sb-124 8.67E+04 1.33E-07 N/A 1.50E-03 1.50E-03 N/A Sb-125 1.46E+06 7.91E-09 N/A 1.50E-03 1.50E-03 N/A Sn-1 25 1.39E+04 8.32E-07 N/A N/A N/A N/A Te-125m 8.35E+04 1.38E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127m 1.57E+05 7.36E-08 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127 5.61E+02 2.06E-05 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129m 4.84E+04 2.39E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129 6.96E+01 1.66E-04 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-131m 1.80E+03 6.42E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-131 2.50E+01 4.62E-04 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-1 32 4.69E+03 2.46E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 1-130 7.42E+02 1.56E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-131 1.16E+04 9.96E-07 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-132 1.38E+02 8.37E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-133 1.25E+03 9.24E-06 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-134 5.26E+01 2.20E-04 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-135 3.97E+02 2.91 E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 Cs-134 1.08E+06 1.06E-08 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-136 1.90E+04 6.08E-07 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-137 1.59E+07 7.26E-10 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-138 3.22E+01 3.59E-04 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Ba-1 39 8.31E+01 1.39E-04 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-140 1.84E+04 6.28E-07 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-141 1.83E+01 6.31 E-04 5.OOE-03 4.OOE-04 4.O0E-04 3.20E-03 Ba-142 1.07E+01 1.08E-03 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 La-140 2.41E+03 4.79E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 La-142 9.54E+01 1.21 E-04 2.50E-03 5.OOE-06 5.OOE-06 2.O0E-04 Ce-141 4.68E+04 2.47E-07 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-143 1.98E+03 5.83E-06 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-144 4.09E+05 2.82E-08 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Pr-143 1.95E+04 5.92E-07 2.50E-03 5.OOE-06 5.OOE-06 4.70E-03 Pr-144 1.73E+01 6.68E-04 2.50E-03 5.OOE-06 5.OOE-06 4.70E-03 Nd-147 1.58E+04 7.31 E-07 2.40E-03 5.OOE-06 5.OOE-06 3.30E-03 W-1 87 1.43E+03 8.08E-06 1.80E-02 5.OOE-04 5.OOE-04 1.30E-03 Np-239 3.39E+03 3.41 E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 Ar-41 1.1OE+02 1.05E-04 N/A N/A N/A N/A Kr-83m 1.1OE+02 1.05E-04 N/A N/A N/A N/A Kr-85m 2.69E+02 4.29E-05 N/A N/A N/A N/A Kr-85 5.64E+06 2.05E-09 N/A N/A N/A N/A Kr-87 7.63E+01 1.51 E-04 N/A N/A N/A N/A Kr-88 1.70E+02 6.79E-05 N/A N/A N/A N/A Kr-89 3.16E+00 3.66E-03 N/A N/A N/A N/A Kr-90 5.39E-01 2.14E-02 N/A N/A N/A N/A Xe-131m 1.70E+04 6.79E-07 N/A N/A N/A N/A SQN ODCM Revision 58 Page 85 of 179 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 3 of 3)Half-Life x Biv Fmi Fmi Ffi (minutes) (l/s) (cow) (goat) (beef)Xe-133m 3.15E+03 3.67E-06 N/A N/A N/A N/A Xe-133 7.55E+03 1.53E-06 N/A N/A N/A N/A Xe-135m 1.54E+01 7.50E-04 N/A N/A N/A N/A Xe-135 5.47E+02 2.11E-05 N/A N/A N/A N/A Xe-137 3.83E+00 3.02E-03 N/A N/A N/A N/A Xe-138 1.41E+01 8.19E-04 N/A N/A N/A N/A
References:
Half lives for all nuclides:
DOE-TIC-1 1026, "Radioactive Decay Data Tables -A handbook of Decay Data for Application to Radiation Dosimetry and Radiological Assessment," D. C. Kocher, 1981.Transfer factors for Sb- isotopes are from ORNL 4992, "Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment," March 1976, Table 2-7.Cow-milk transfer factors for Iodine, Strontium, and Cesium nuclides are from NUREG/CR-1004, Table 3.17.Goat-milk transfer factors for Iodine nuclides are from NUREG/CR-1004, Table 3.17.Beef transfer factors for Iron, Copper, Molybdenum, and Cesium nuclides are from NUREG/CR-1004, Table 3.18.All other nuclides' transfer factors are from Regulatory Guide 1.109, Tables E-1 and E-2.
SQN ODCM Revision 58 Page 86 of 179 Table 6.3 DOSE CALCULATION FACTORS (Page 1 of 2)Factor BRa (infant)BRa (child)BRa (teen)BRa (adult)fL f S H Kc M P Qf (cow)Qf (goat)r tb tcb tcsf te tep tesf tf6 thc ts tsv Uam (infant)Uam (child)Uam (teen)Uam (adult)Uap (infant)Uap (child)Uap (teen)Uap (adult)Ufa(infant)
Ufa(child)
Ufa(teen)Value 1400 5500 8000 8100 1 1 1 0 9 0.072 40 240 64 08 0.47 4.73E+08 (15 years)7.78E+06 (90 days)1.56E+07 (180 days)5.18E+06 (60 days)2.59E+06 (30 days)7.78E+06 (90 days)8.64E+04 (1 day)8.64E+04 (1 day)1.12E+06 (13 days)2.38E+07 (275 days)0 41 65 110 330 330 400 310 0 6.9 16 Units m 3/year m 3/year m 3/year m 3/year g/m 3 L/kg-h kg/m2 kg/m2 kg/d kg/d seconds seconds seconds seconds seconds seconds seconds seconds seconds seconds kg/year kg/year kg/year kg/year I/year I/year I/year I/year kg/year kg/year kg/year Reference ICRP 23 ICRP 23 ICRP 23 ICRP 23 TVA Assumption R. G. 1.109 (Table E-15)TVA Assumption TVA Assumption TVA Value R. G. 1.109 (Section 2.C.)R. G. 1.109 (Section 2.C.)R. G. 1.109 (Table E-15)NUREG/CR-1004 (Sect. 3.4)NUREG/CR-1004 (Sect. 3.4)NUREG/CR-1004 (Sect. 3.2)R. G. 1.109 (Table E-15)SQN FSAR Section 11.3.9.1 SQN FSAR Section 11.3.9.1 R. G. 1.109 (Table E-15)R. G. 1.109 (Table E-15)R. G. 1.109 (Table E-15)SQN FSAR Section 11.3.9.1 NUREG/CR-1004, Table 3.40 NUREG/CR-1004, Table 3.40 SQN FSAR Section 11.3.9.1 R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.R. G.1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table 1.109 (Table E-5)E-5)E-5)E-5)E-5)E-5)E-5)E-5)E-5)E-5)E-5)
SQN ODCM Revision 58 Page 87 of 179 Table 6.3 DOSE CALCULATION FACTORS (Page 2 of 2)Factor Ufa(adult)
Ufla (infant)Ufla (child)Ufla (teen)Ufla (adult)Usa (infant)Usa (child)Usa (teen)Usa (adult)Uwa(infant)
Uwa(child)
Uwa(teen)Uwa(adult) w Yf Yp Ysf Ysv Xw (iodines)(particulates)
Value 21 kg/year 0 kg/year 26 kg/year 42 kg/year 64 kg/year 0 kg/year 520 kg/year 630 kg/year 520 kg/year 330 L/year 510 L/year 510 L/year 730 L/year 0.3 none 1.85 kg/m 2 1.18 kg/m2 0.64 kg/m2 0.57 kg/m 2 7.71 E-07 sec" 1 (10.4 d half-life) 5.21 E-07 sec" 1 (15.4 d half-life)
Units Reference R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table E-5)R. G. 1.109 (Table A-2)NUREG/CR-1004 (Table 3.4)NUREG/CR-1004 (Table 3.3)NUREG/CR-1004 (Table 3.3)NUREG/CR-1004 (Table 3.4)(value selected is for non-leafy vegetables)
NUREG/CR-1004 (Table 3.10)NUREG/CR-1004 (Table 3.10)
SQN ODCM Revision 58 Page 88 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 1 of 8)ADULT bone liver t body thyroid kidney lung gi-Ili H-3 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 C-14 2.84E-06 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 Na-24 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 P-32 1.93E-04 1.20E-05 7.46E-06 0.OOE+00 0.OOE+00 0.OOE+00 2.17E-05 Cr-51 O.OOE+00 O.OOE+00 2.66E-09 1.59E-09 5.86E-10 3.53E-09 6.69E-07 Mn-54 0.OOE+00 4.57E-06 8.72E-07 O.OOE+00 1.36E-06 0.OOE+00 1.40E-05 Mn-56 0.OOE+00 1.155E-07 2.04E-08 0.OOE+00 1.46E-07 0.OOE+00 3.67E-06 Fe-55 2.75E-06 1.90E-06 4.43E-07 0.O0E+00 0.OOE+00 1.06E-06 1.09E-06 Fe-59 4.34E-06 1.02E-05 3.91 E-06 0.OOE+00 0.OOE+00 2.85E-06 3.40E-05 Co-57 O.OOE+00 1.75E-07 2.91 E-07 0.OOE+00 O.OOE+00 O.OOE+00 4.44E-06 Co-58 0.OOE+00 7.45E-07 1.67E-06 0.OOE+00 0.OOE+00 0.OOE+00 1.51E-05 Co-60 0.OOE+00 2.14E-06 4.72E-06 0.OOE+00 0.OOE+00 0.OOE+00 4.02E-05 Ni-63 1.30E-04 9.01E-06 4.36E-06 0.OOE+00 0.OOE+00 0.OOE+00 1.88E-06 Ni-65 5.28E-07 6.86E-08 3.13E-08 0.OOE+00 0.OOE+00 O.OOE+00 1.74E-06 Cu-64 0.OOE+00 8.33E-08 3.91 E-08 0.OOE+00 2.1OE-07 0.OOE+00 7.1OE-06 Zn-65 4.84E-06 1.54E-05 6.96E-06 0.OOE+00 1.03E-05 0.OOE+00 9.70E-06 Zn-69 1.03E-08 1.97E-08 1.37E-09 0.OOE+00 1.28E-08 0.OOE+00 2.96E-09 Zn-69m 1.70E-07 4.08E-07 3.73E-08 0.OOE+00 2.47E-07 0.OOE+00 2.49E-05 Br-82 O.OOE+00 O.OOE+00 2.26E-06 0.OOE+00 0.OOE+00 0.OOE+00 2.59E-06 Br-83 0.OOE+00 0.OOE+00 4.02E-08 0.OOE+00 0.OOE+00 0.OOE+00 5.79E-08 Br-84 0.OOE+00 0.OOE+00 5.21E-08 0.OOE+00 0.OOE+00 0.OOE+00 4.09E-13 Br-85 O.00E+00 0.OOE+00 2.14E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rb-86 O.OOE+00 2.11E-05 9.83E-06 0.OOE+00 0.OOE+00 0.OOE+00 4.16E-06 Rb-88 0.OOE+00 6.05E-08 3.21E-08 0.OOE+00 0.OOE+00 0.OOE+00 8.36E-19 Rb-89 0.OOE+00 4.01 E-08 2.82E-08 0.OOE+00 0.OOE+00 0.OOE+00 2.33E-21 Sr-89 3.08E-04 0.OOE+00 8.84E-06 0.OOE+00 O.OOE+00 0.OOE+00 4.94E-05 Sr-90 7.58E-03 O.OOE+00 1.86E-03 0.OOE+00 O.OOE+00 0.OOE+00 2.19E-04 Sr-91 5.67E-06 0.OOE+00 2.29E-07 0.OOE+00 O.OOE+00 0.OOE+00 2.70E-05 Sr-92 2.15E-06 O.OOE+00 9.30E-08 0.OOE+00 0.OOE+00 0.OOE+00 4.26E-05 Y-90 9.62E-09 O.OOE+00 2.58E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.02E-04 Y-91m 9.09E-11 O.OOE+00 3.52E-12 O.OOE+00 0.OOE+00 O.OOE+00 2.67E-10 Y-91 1.41 E-07 0.OOE+00 3.77E-09 0.OOE+00 0.OOE+00 O.OOE+00 7.76E-05 Y-92 8.45E-10 O.OOE+00 2.47E-11 0.OOE+00 0.OOE+00 O.OOE+00 1.48E-05 Y-93 2.68E-09 0.OOE+00 7.40E-1 1 0.OOE+00 0.OOE+00 O.OOE+00 8.50E-05 Zr-95 3.04E-08 9.75E-09 6.60E-09 O.OOE+00 1.53E-08 0.OOE+00 3.09E-05 Zr-97 1.68E-09 3.39E-10 1.55E-10 0.OOE+00 5.12E-10 O.OOE+00 1.05E-04 Nb-95 6.22E-09 3.46E-09 1.86E-09 0.OOE+00 3.42E-09 0.OOE+00 2.1OE-05 Nb-97 5.22E-11 1.32E-11 4.82E-12 0.OOE+00 1.54E-11 0.OOE+00 4.87E-08 Mo-99 0.OOE+00 4.31 E-06 8.20E-07 0.OOE+00 9.76E-06 0.OOE+00 9.99E-06 Tc-99m 2.47E-10 6.98E-10 8.89E-09 0.OOE+00 1.06E-08 3.42E-10 4.13E-07 Tc-101 2.54E-10 3.66E-10 3.59E-09 0.OOE+00 6.59E-09 1.87E-10 1.10E-21 Ru-103 1.85E-07 O.OOE+00 7.97E-08 O.OOE+00 7.06E-07 0.OOE+00 2.16E-05 Ru-105 1.54E-08 O.OOE+00 6.08E-09 0.OOE+00 1.99E-07 0.OOE+00 9.42E-06 Ru-106 2.75E-06 0.OOE+00 3.48E-07 0.OOE+00 5.31E-06 0.OOE+00 1.78E-04 SQN ODCM Revision 58 Page 89 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 2 of 8)ADULT Ag-11im Sb-1i24 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-1 31 m Te-131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-1 37 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 1.60E-07 2.80E-06 1.79E-06 8.33E-06 2.68E-06 6.77E-06 1.10E-07 1.15E-05 3.14E-08 1.73E-06 1.97E-08 2.52E-06 7.56E-07 4.16E-06 2.03E-07 1.42E-06 1.06E-07 4.43E-07 6.22E-05 6.51 E-06 7.97E-05 5.52E-08 9.70E-08 2.03E-05 4.71 E-08 2.13E-08 2.50E-09 1.28E-10 9.36E-09 1.65E-09 4.88E-07 9.20E-09 3.01E-11 6.29E-09 1.03E-07 1.19E-09 liver 1.48E-07 5.29E-08 2.OOE-08 1.68E-07 9.71 E-07 2.42E-06 3.95E-08 4.29E-06 1.18E-08 8.46E-07 8.23E-09 1.63E-06 2.23E-06 5.95E-06 5.43E-07 2.47E-06 2.88E-07 1.16E-06 1.48E-04 2.57E-05 1.09E-04 1.09E-07 6.91 E-11 2.55E-08 3.56E-11 2.19E-11 1.26E-09 5.82E-1 1 6.33E-09 1.22E-06 2.04E-07 3.69E-09 1.25E-1 1 7.27E-09 8.61 E-08 1.17E-10 t body 8.79E-08 1.11E-06 4.26E-07 3.78E-07 3.59E-07 8.25E-07 2.38E-08 1.82E-06 7.65E-09 7.05E-07 6.22E-09 1.53E-06 8.80E-07 3.41 E-06 1.90E-07 7.53E-07 1.03E-07 4.28E-07 1.21E-04 1.85E-05 7.14E-05 5.40E-08 2.84E-09 1.33E-06 1.59E-09 1.34E-09 3.33E-10 1.45E-11 7.18E-10 1.35E-10 2.62E-08 4.56E-10 1.53E-12 4.35E-10 3.01 E-08 6.45E-1 1 thyroid 0.00E+00 6.79E-09 1.82E-09 1.39E-07 8.06E-07 1.73E-06 8.15E-08 3.95E-06 2.41 E-08 1.34E-06 1.62E-08 1.80E-06 1.89E-04 1.95E-03 1.90E-05 3.63E-04 4.99E-06 7.65E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 kidney 2.91 E-07 0.OOE-00 0.OOE-00 0.OOE-00 1.09E-05 2.75E-05 4.48E-07 4.80E-05 1.32E-07 8.57E-06 8.63E-08 1.57E-05 3.48E-06 1.02E-05 8.65E-07 4.31 E-06 4.58E-07 1.86E-06 4.79E-05 1.43E-05 3.70E-05 8.01 E-08 6.46E- 11 8.67E-09 3.31E-11 1.85E-11 0.OOE+00 0.OOE+00 2.94E-09 5.37E-10 1.21 E-07 2.13E-09 7.05E-12 4.25E-09 0.OOE+00 3.65E-1 0 lung 0.OOE+00 2.18E-06 1.38E-06 0.OOE-00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.59E-05 1.96E-06 1.23E-05 7.91 E-09 3.92E-1 1 1.46E-08 2.02E-11 1.24E-11 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 6.04E-05 7.95E-05 1.97E-05 1.04E-04 1.07E-05 2.27E-05 8.68E-06 5.79E-05 2.37E-08 8.40E-05 2.79E-09 7.71 E-05 1.92E-06 1.57E-06 1.02E-07 2.22E-06 2.51E-10 1.31 E-06 2.59E-06 2.92E-06 2.11 E-06 4.65E-13 1.72E-07 4.18E-05 2.22E-17 3.OOE-26 9.25E-05 4.25E-07 2.42E-05 4.56E-05 1.65E-04 4.03E-05 4.33E-18 3.49E-05 2.82E-05 2.40E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-11.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 58 Page 90 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 3 of 8)TEEN bone liver t body thyroid kidney lung gi-Ili H-3 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 C-14 4.06E-06 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 Na-24 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 P-32 2.76E-04 1.71 E-05 1.07E-05 0.OOE+00 0.OOE+00 0.OOE+00 2.32E-05 Cr-51 0.OOE+00 O.OOE+00 3.60E-09 2.OOE-09 7.89E-10 5.14E-09 6.05E-07 Mn-54 0.OOE+00 5.90E-06 1.17E-06 O.OOE+00 1.76E-06 0.OOE+00 1.21E-05 Mn-56 0.OOE+00 1.58E-07 2.81E-08 0.OOE+00 2.OOE-07 0.OOE+00 1.04E-05 Fe-55 3.78E-06 2.68E-06 6.25E-07 0.OOE+00 0.OOE+00 1.70E-06 1.16E-06 Fe-59 5.87E-06 1.37E-05 5.29E-06 0.OOE+00 0.OOE+00 4.32E-06 3.24E-05 Co-57 0.OOE+00 2.38E-07 3.99E-07 0.OOE+00 0.OOE+00 0.OOE+00 4.44E-06 Co-58 0.OOE+00 9.72E-07 2.24E-06 0.OOE+00 0.OOE+00 0.OOE+00 1.34E-05 Co-60 0.OOE+00 2.81 E-06 6.33E-06 0.OOE+00 0.OOE+00 0.OOE+00 3.66E-05 Ni-63 1.77E-04 1.25E-05 6.OOE-06 0.OOE+00 0.OOE+00 0.OOE+00 1.99E-06 Ni-65 7.49E-07 9.57E-08 4.36E-08 0.OOE+00 0.OOE+00 0.OOE+00 5.19E-06 Cu-64 0.OOE+00 1.15E-07 5.41E-08 0.OOE+00 2.91E-07 0.OOE+00 8.92E-06 Zn-65 5.76E-06 2.OOE-05 9.33E-06 0.OOE+00 1.28E-05 0.OOE+00 8.47E-06 Zn-69 1.47E-08 2.80E-08 1.96E-09 O.OOE+00 1.83E-08 0.OOE+00 5.16E-08 Zn-69m 2.40E-07 5.66E-07 5.19E-08 0.OOE+00 3.44E-07 0.OOE+00 3.11E-05 Br-82 0.OOE+00 0.OOE+00 3.04E-06 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 5.74E-08 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-84 0.OOE+00 0.00E+00 7.22E-08 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 0.OOE+00 3.05E-09 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rb-86 0.OOE+00 2.98E-05 1.40E-05 0.OOE+00 0.OOE+00 0.OOE+00 4.41 E-06 Rb-88 0.OOE+00 8.52E-08 4.54E-08 0.OOE+00 0.OOE+00 0.OOE+00 7.30E-15 Rb-89 0.OOE+00 5.50E-08 3.89E-08 0.OOE+00 0.OOE+00 O.OOE+00 8.43E-17 Sr-89 4.40E-04 0.OOE+00 1.26E-05 0.OOE+00 0.OOE+00 O.OOE+00 5.24E-05 Sr-90 8.30E-03 0.OOE+00 2.05E-03 0.OOE+00 O.OOE+00 O.OOE+00 2.33E-04 Sr-91 8.07E-06 0.OOE+00 3.21E-07 0.OOE+00 0.OOE+00 0.OOE+00 3.66E-05 Sr-92 3.05E-06 0.OOE+00 1.30E-07 0.OOE+00 0.OOE+00 O.OOE+00 7.77E-05 Y-90 1.37E-08 0.OOE+00 3.69E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.13E-04 Y-91m 1.29E-10 O.OOE+00 4.93E-12 0.OOE+00 0.OOE+00 0.OOE+00 6.09E-09 Y-91 2.01 E-07 0.OOE+00 5.39E-09 0.OOE+00 0.OOE+00 0.OOE+00 8.24E-05 Y-92 1.21E-09 0.OOE+00 3.50E-11 0.OOE+00 0.00E+00 0.OOE+00 3.32E-05 Y-93 3.83E-09 0.OOE+00 1.05E-1 0.OOE+00 0.OOE+00 0.OOE+00 1.17E-04 Zr-95 4.12E-08 1.30E-08 8.94E-09 O.OOE+00 1.91E-08 0.OOE+00 3.OOE-05 Zr-97 2.37E-09 4.69E-10 2.16E-10 0.OOE+00 7.11E-10 0.OOE+00 1.27E-04 Nb-95 8.22E-09 4.56E-09 2.51 E-09 0.OOE+00 4.42E-09 0.OOE+00 1.95E-05 Nb-97 7.37E-11 1.83E-11 6.68E-12 0.OOE+00 2.14E-11 0.OOE+00 4.37E-07 Mo-99 0.OOE+00 6.03E-06 1.15E-06 0.OOE+00 1.38E-05 0.OOE+00 1.08E-05 Tc-99m 3.32E-10 9.26E-10 1.20E-08 0.OOE+00 1.38E-08 5.14E-10 6.08E-07 Tc-101 3.60E-10 5.12E-10 5.03E-09 0.OOE+00 9.26E-09 3.12E-10 8.75E-17 Ru-103 2.55E-07 0.OOE+00 1.09E-07 0.OOE+00 8.99E-07 0.OOE+00 2.13E-05 Ru-105 2.18E-08 O.OOE+00 8.46E-09 0.OOE+00 2.75E-07 0.OOE+00 1.76E-05 Ru-106 3.92E-06 0.OOE+00 4.94E-07 0.OOE+00 7.56E-06 O.OOE+00 1.88E-04 SQN ODCM Revision 58 Page 91 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 4 of 8)Ag-110m Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La- 142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 2.05E-07 3.87E-06 2.48E-06 1.19E-05 3.83E-06 9.67E-06 1.58E-07 1.63E-05 4.48E-08 2.44E-06 2.79E-08 3.49E-06 1.03E-06 5.85E-06 2.79E-07 2.01 E-06 1.46E-07 6.10E-07 8.37E-05 8.59E-06 1 .12E-04 7.76E-08 1.39E-07 2.84E-05 6.71 E-08 2.99E-08 3.48E-09 1.79E-10 1.33E-08 2.35E-09 6.96E-07 1.31 E-08 4.30E-1 1 9.38E-09 1.46E-07 1.76E-09 liver 1.94E-07 7.13E-08 2.71 E-08 2.37E-07 1.38E-06 3.43E-06 5.60E-08 6.05E-06 1.67E-08 1.17E-06 1.15E-08 2.21 E-06 2.98E-06 8.19E-06 7.30E-07 3.41 E-06 3.87E-07 1.57E-06 1.97E-04 3.38E-05 1.49E-04 1.49E-07 9.78E-1 1 3.48E-08 5.01 E-11 2.99E-1 1 1.71 E-09 7.95E- 1I 8.88E-09 1.71 E-06 2.88E-07 5.23E-09 1.76E-1 1 1.02E-08 1.19E-07 1.66E-10 t body 1.18E-07 1.51 E-06 5.80E-07 5.37E-07 5.12E-07 1.15E-06 3.40E-08 2.58E-06 1.09E-08 9.76E-07 8.72E-09 2.08E-06 1.19E-06 4.40E-06 2.62E-07 1.04E-06 1.39E-07 5.82E-07 9.14E-05 2.27E-05 5.19E-05 7.45E-08 4.05E-09 1.83E-06 2.24E-09 1.84E-09 4.55E-10 1.98E-1 1 1.02E-09 1.91E-10 3.74E-08 6.52E-10 2.18E-12 6.11E-10 4.17E-08 9.22E-1 1 TEEN thyroid 0.OOE+00 8.78E-09 2.37E-09 1.86E-07 1.07E-06 2.30E-06 1.09E-07 5.26E-06 3.20E-08 1.76E-06 2.15E-08 2.33E-06 2.43E-04 2.39E-03 2.46E-05 4.76E-04 6.45E-06 1.01E-04 0.00E+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 3.70E-07 0.OOE-00 0.OOE+00 0.OOE+00 0.OOE+00 3.92E-05 6.40E-07 6.82E-05 1.88E-07 1.22E-05 1.22E-07 2.12E-05 4.59E-06 1.41 E-05 1.15E-06 5.98E-06 6.10E-07 2.48E-06 6.26E-05 1.84E-05 5.07E-05 1.10E-07 9.22E-1 1 1.18E-08 4.65E-1 1 2.53E-1 1 0.OOE+00 0.OOE+00 4.18E-09 7.67E-10 1.72E-07 3.04E-09 1.01E-11 5.99E-09 0.OOE+00 5.21E-10 lung 0.OOE+00 3.38E-06 2.18E-06 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 2.39E-05 2.90E-06 1.97E-05 1.28E-08 6.74E-1 1 2.34E-08 3.43E-1 1 1.99E-1 1 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 5.45E-05 7.80E-05 1.93E-05 1.12E-04 1.13E-05 2.41 E-05 1.22E-05 6.12E-05 2.45E-07 9.39E-05 2.29E-09 7.OOE-05 2.29E-06 1.62E-06 3.18E-07 2.58E-06 5.1OE-09 1.74E-06 2.45E-06 2.72E-06 2.12E-06 6.76E-11 1.24E-06 4.38E-05 1.43E-13 9.18E-20 9.82E-05 2.42E-06 2.54E-05 5.14E-05 1.75E-04 4.31 E-05 4.74E-14 3.68E-05 3.22E-05 2.67E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-12.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-1 24 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 58 Page 92 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 5 of 8)CHILD bone liver t body thyroid kidney lung gi-Ili H-3 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 C-14 1.21 E-05 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 Na-24 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 P-32 8.25E-04 3.86E-05 3.18E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.28E-05 Cr-51 O.OOE+00 O.OOE+00 8.90E-09 4.94E-09 1.35E-09 9.02E-09 4.72E-07 Mn-54 O.OOE+00 1.07E-05 2.85E-06 O.OOE+00 3.OOE-06 O.OOE+00 8.98E-06 Mn-56 O.OOE+00 3.34E-07 7.54E-08 O.OOE+00 4.04E-07 O.OOE+00 4.84E-05 Fe-55 1.15E-05 6.10E-06 1.89E-06 O.OOE+00 O.OOE+00 3.45E-06 1.13E-06 Fe-59 1.65E-05 2.67E-05 1.33E-05 O.OOE+00 O.OOE+00 7.74E-06 2.78E-05 Co-57 O.OOE+00 4.93E-07 9.98E-07 O.OOE+00 O.OOE+00 O.OOE+00 4.04E-06 Co-58 O.OOE+00 1.80E-06 5.51 E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.05E-05 Co-60 O.OOE+00 5.29E-06 1.56E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.93E-05 Ni-63 5.38E-04 2.88E-05 1.83E-05 O.OOE+00 O.OOE+00 O.OOE+00 1.94E-06 Ni-65 2.22E-06 2.09E-07 1.22E-07 O.OOE+00 O.OOE+00 O.OOE+00 2.56E-05 Cu-64 O.OOE+00 2.45E-07 1.48E-07 O.OOE+00 5.92E-07 O.OOE+00 1.15E-05 Zn-65 1.37E-05 3.65E-05 2.27E-05 O.OOE+00 2.30E-05 O.OOE+00 6.41 E-06 Zn-69 4.38E-08 6.33E-08 5.85E-09 O.OOE+00 3.84E-08 O.OOE+00 3.99E-06 Zn-69m 7.1OE-07 1.21E-06 1.43E-07 O.OOE+00 7.03E-07 O.OOE+00 3.94E-05 Br-82 O.OOE+00 O.OOE+00 7.55E-06 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 1.71E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 1.98E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.OOE+00 O.OOE+00 9.12E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 O.OOE+00 6.70E-05 4.12E-05 O.OOE+00 O.OOE+00 O.OOE+00 4.31E-06 Rb-88 O.OOE+00 1.90E-07 1.32E-07 O.OOE+00 O.OOE+00 O.OOE+00 9.32E-09 Rb-89 O.OOE+00 1.17E-07 1.04E-07 O.OOE+00 O.OOE+00 O.OOE+00 1.02E-09 Sr-89 1.32E-03 O.OOE+00 3.77E-05 O.OOE+00 O.OOE+00 O.OOE+00 5.11E-05 Sr-90 1.70E-02 O.OOE+00 4.31 E-03 O.OOE+00 O.OOE+00 O.OOE+00 2.29E-04 Sr-91 2.40E-05 O.OOE+00 9.06E-07 O.OOE+00 O.OOE+00 O.OOE+00 5.30E-05 Sr-92 9.03E-06 O.OOE+00 3.62E-07 O.OOE+00 O.OOE+00 O.OOE+00 1.71E-04 Y-90 4.11E-08 O.OOE+00 1.10E-09 O.OOE+00 O.OOE+00 O.OOE+00 1.17E-04 Y-91m 3.82E-10 O.OOE+00 1.39E-11 O.OOE+00 O.OOE+00 O.OOE+00 7.48E-07 Y-91 6.02E-07 O.OOE+00 1.61E-08 O.OOE+00 O.OOE+00 O.OOE+00 8.02E-05 Y-92 3.60E-09 O.OOE+00 1.03E-10 O.OOE+00 O.OOE+00 O.OOE+00 1.04E-04 Y-93 1.14E-08 O.OOE+00 3.13E-10 O.OOE+00 O.OOE+00 O.OOE+00 1.70E-04 Zr-95 1.16E-07 2.55E-08 2.27E-08 O.OOE+00 3.65E-08 O.OOE+00 2.66E-05 Zr-97 6.99E-09 1.01E-09 5.96E-10 O.OOE+00 1.45E-09 O.OOE+00 1.53E-04 Nb-95 2.25E-08 8.76E-09 6.26E-09 O.OOE+00 8.23E-09 O.OOE+00 1.62E-05 Nb-97 2.17E-10 3.92E-11 1.83E-11 O.OOE+00 4.35E-11 O.OOE+00 1.21E-05 Mo-99 Q.OOE+00 1.33E-05 3.29E-06 O.OOE+00 2.84E-05 O.OOE+00 1.10E-05 Tc-99m 9.23E-10 1.81E-09 3.OOE-08 O.OOE+00 2.63E-08 9.19E-10 1.03E-06 Tc-101 1.07E-09 1.12E-09 1.42E-08 O.OOE+00 1.91E-08 5.92E-10 3.56E-09 Ru-103 7.31E-07 O.OOE+00 2.81E-07 O.OOE+00 1.84E-06 O.OOE+00 1.89E-05 Ru-105 6.45E-08 O.OOE+00 2.34E-08 O.OOE+00 5.67E-07 O.OOE+00 4.21 E-05 Ru-106 1.17E-05 O.OOE+00 1.46E-06 O.OOE+00 1.58E-05 O.OOE+00 1.82E-04 SQN ODCM Revision 58 Page 93 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 6 of 8)CHILD Ag-110m Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131rm Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 5.39E-07 1.11 E-05 7.16E-06 3.55E-05 1.14E-05 2.89E-05 4.71 E-07 4.87E-05 1.34E-07 7.20E-06 8.30E-08 1.01E-05 2.92E-06 1.72E-05 8.00E-07 5.92E-06 4.19E-07 1.75E-06 2.34E-04 2.35E-05 3.27E-04 2.28E-07 4.14E-07 8.31 E-05 2.00E-07 8.74E-08 1.01 E-08 5.24E-10 3.97E-08 6.99E-09 2.08E-06 3.93E-08 1.29E-10 2.79E-08 4.29E-07 5.25E-09 liver 3.64E-07 1.44E-07 5.52E-08 5.35E-07 3.09E-06 7.78E-06 1.27E-07 1.36E-05 3.74E-08 2.49E-06 2.53E-08 4.47E-06 5.90E-06 1.73E-05 1.47E-06 7.32E-06 7.78E-07 3.15E-06 3.84E-04 6.46E-05 3.13E-04 3.17E-07 2.21 E-10 7.28E-08 1.12E-10 6.29E- 1I 3.53E-09 1.67E-10 1.98E-08 3.79E-06 6.52E-07 1.18E-08 3.99E-1 1 2.26E-08 2.54E-07 3.77E-10 t body 2.91 E-07 3.89E-06 1.50E-06 1.59E-06 1.52E-06 3.43E-06 1.01 E-07 7.56E-06 3.18E-08 2.65E-06 2.47E-08 5.40E-06 3.04E-06 9.83E-06 6.76E-07 2.77E-06 3.58E-07 1.49E-06 8.10E-05 4.18E-05 4.62E-05 2.01 E-07 1.20E-08 4.85E-06 6.51 E-09 4.88E-09 1.19E-09 5.23E-1 1 2.94E-09 5.49E-10 1.11 E-07 1.95E-09 6.49E-12 1.75E-09 1.14E-07 2.65E-10 thyroid 0.OOE+00 2.45E-08 6.63E-09 5.55E-07 3.20E-06 6.91 E-06 3.26E-07 1.57E-05 9.56E-08 5.12E-06 6.35E-08 6.51 E-06 6.50E-04 5.72E-03 6.82E-05 1.36E-03 1.79E-05 2.79E-04 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 6.78E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 8.24E-05 1.34E-06 1.43E-04 3.92E-07 2.41 E-05 2.51 E-07 4.15E-05 8.82E-06 2.84E-05 2.25E-06 1.22E-05 1.19E-06 4.83E-06 1.19E-04 3.44E-05 1.02E-04 2.23E-07 1.93E-10 2.37E-08 9.69E-1 1 5.09E-1 1 0.OOE+00 0.OOE+00 8.68E-09 1.59E-09 3.61 E-07 6.39E-09 2.11E-11 1.24E-08 0.OOE+00 1.09E-09 lung 0.OOE+00 6.16E-06 3.99E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 4.27E-05 5.13E-06 3.67E-05 2.40E-08 1.30E-10 4.34E-08 6.58E-10 3.70E-1 1 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 4.33E-05 6.94E-05 1.71E-05 1.1OE-05 1.1OE-05 2.34E-05 1.84E-05 5.94E-05 8.34E-06 1.01 E-04 4.36E-07 4.50E-05 2.76E-06 1.54E-06 1.73E-06 2.95E-06 5.16E-07 2.40E-06 2.07E-06 2.27E-06 1.96E-06 1.46E-07 2.39E-05 4.21 E-05 1.14E-07 1.14E-09 9.84E-05 3.31 E-05 2.47E-05 5.55E-05 1.70E-04 4.24E-05 8.59E-08 3.58E-05 3.57E-05 2.79E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-13.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 58 Page 94 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 7 of 8)INFANT bone liver t body thyroid kidney lung gi-Ili H-3 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 C-14 2.37E-05 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 Na-24 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 P-32 1.70E-03 1.OOE-04 6.59E-05 0.OOE+00 0.OOE+00 O.OOE+00 2.30E-05 Cr-51 0.OOE+00 0.OOE+00 1.41 E-08 9.20E-09 2.01 E-09 1.79E-08 4.11 E-07 Mn-54 0.OOE+00 1.99E-05 4.51 E-06 0.OOE+00 4.41E-06 0.OOE+00 7.31 E-06 Mn-56 O.OOE+00 8.18E-07 1.41 E-07 0.OOE+00 7.03E-07 0.OOE+00 7.43E-05 Fe-55 1.39E-05 8.98E-06 2.40E-06 0.OOE+00 0.OOE+00 4.39E-06 1.14E-06 Fe-59 3.08E-05 5.38E-05 2.12E-05 0.OOE+00 0.OOE+00 1.59E-05 2.57E-05 Co-57 0.OOE+00 1.15E-06 1.87E-06 0.OOE+00 0.OOE+00 0.OOE+00 3.92E-06 Co-58 O.OOE+00 3.60E-06 8.98E-06 0.OOE+00 0.OOE+00 O.OOE+00 8.97E-06 Co-60 0.OOE+00 1.08E-05 2.55E-05 0.OOE+00 0.OOE+00 0.OOE+00 2.57E-05 Ni-63 6.34E-04 3.92E-05 2.20E-05 0.OOE+00 0.OOE+00 0.OOE+00 1.95E-06 Ni-65 4.70E-06 5.32E-07 2.42E-07 0.OOE+00 0.OOE+00 O.OOE+00 4.05E-05 Cu-64 0.OOE+00 6.09E-07 2.82E-07 0.OOE+00 1.03E-06 0.OOE+00 1.25E-05 Zn-65 1.84E-05 6.31E-05 2.91E-05 0.OOE+00 3.06E-05 0.OOE+00 5.33E-05 Zn-69 9.33E-08 1.68E-07 1.25E-08 0.OOE+00 6.98E-08 0.OOE+00 1.37E-05 Zn-69m 1.50E-06 3.06E-06 2.79E-07 0.OOE+00 1.24E-06 0.OOE+00 4.24E-05 Br-82 0.OOE+00 0.OOE+00 1.27E-05 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 3.63E-07 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Br-84 0.OOE+00 0.OOE+00 3.82E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 0.OOE+00 1.94E-08 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rb-86 0.OOE+00 1.70E-04 8.40E-05 0.OOE+00 0.OOE+00 O.OOE+00 4.35E-06 Rb-88 0.OOE+00 4.98E-07 2.73E-07 0.OOE+00 0.OOE+00 O.OOE+00 4.85E-07 Rb-89 0.OOE+00 2.86E-07 1.97E-07 O.OOE+00 0.OOE+00 0.OOE+00 9.74E-08 Sr-89 2.51 E-03 0.OOE+00 7.20E-05 0.OOE+00 0.OOE+00 0.OOE+00 5.16E-05 Sr-90 1.85E-02 0.OOE+00 4.71E-03 0.OOE+00 0.OOE+00 O.OOE+00 2.31 E-04 Sr-91 5.OOE-05 0.OOE+00 1.81 E-06 0.OOE+00 0.OOE+00 0.OOE+00 5.92E-05 Sr-92 1.92E-05 0.OOE+00 7.13E-07 0.OOE+00 O.OOE+00 0.OOE+00 2.07E-04 Y-90 8.69E-08 0.OOE+00 2.33E-09 0.OOE+00 O.OOE+00 0.OOE+00 1.20E-04 Y-91m 8.10E-10 0.OOE+00 2.76E-11 O.OOE+00 O.OOE+00 0.OOE+00 2.70E-06 Y-91 1.13E-06 0.OOE+00 3.01E-08 0.OOE+00 O.OOE+00 0.OOE+00 8.1OE-05 Y-92 7.65E-09 0.OOE+00 2.15E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.46E-04 Y-93 2.43E-08 0.OOE+00 6.62E-10 0.OOE+00 0.OOE+00 0.OOE+00 1.92E-04 Zr-95 2.06E-07 5.02E-08 3.56E-08 0.OOE+00 5.41E-08 0.OOE+00 2.50E-05 Zr-97 1.48E-08 2.54E-09 1.16E-09 0.OOE+00 2.56E-09 0.OOE+00 1.62E-04 Nb-95 4.20E-08 1.73E-08 1.OOE-08 0.OOE+00 1.24E-08 O.OOE+00 1.46E-05 Nb-97 4.59E-10 9.79E-11 3.53E-11 0.OOE+00 7.65E-11 0.OOE+00 3.09E-05 Mo-99 0.OOE+00 3.40E-05 6.63E-06 0.OOE+00 5.08E-05 0.OOE+00 1.12E-05 Tc-99m 1.92E-09 3.96E-09 5.1OE-08 0.OOE+00 4.26E-08 2.07E-09 1.15E-06 Tc-101 2.27E-09 2.86E-09 2.83E-08 0.OOE+00 3.40E-08 1.56E-09 4.86E-07 Ru-1 03 1.48E-06 O.OOE+00 4.95E-07 0.OOE+00 3.08E-06 0.OOE+00 1.80E-05 Ru-105 1.36E-07 0.OOE+00 4.58E-08 0.OOE+00 1.OOE-06 0.OOE+00 5.41 E-05 Ru-106 2.41 E-05 0.OOE+00 3.01E-06 0.OOE+00 2.85E-05 O.OOE+00 1.83E-04 SQN ODCM Revision 58 Page 95 of 179 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)(Page 8 of 8)INFANT Ag-110m Sb-1i24 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131im Te- 131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 9.96E-07 2.14E-05 1.23E-05 7.41 E-05 2.33E-05 5.85E-05 1.OOE-06 1.00E-04 2.84E-07 1.52E-05 1.76E-07 2.08E-05 6.OOE-06 3.59E-05 1.66E-06 1.25E-05 8.69E-07 3.64E-06 3.77E-04 4.59E-05 5.22E-04 4.81 E-07 8.81 E-07 1.71 E-04 4.25E-07 1.84E-07 2.11 E-08 1.1OE-09 7.87E-08 1.48E-08 2.98E-06 8.13E-08 2.74E-10 5.53E-08 9.03E-07 1.11E-08 liver 7.27E-07 3.15E-07 1.19E-07 1.38E-06 7.79E-06 1.94E-05 3.35E-07 3.43E-05 9.79E-08 6.12E-06 6.50E-08 1.03E-05 1.32E-05 4.23E-05 3.37E-06 1.82E-05 1.78E-06 7.24E-06 7.03E-04 1.35E-04 6.11 E-04 7.82E-07 5.84E-10 1.71 E-07 2.91 E-10 1.53E-10 8.32E-09 4.04E-1 0 4.80E-08 9.82E-06 1.22E-06 3.04E-08 1.06E-10 5.68E-08 6.28E-07 9.93E-10 t body 4.81 E-07 6.63E-06 2.53E-06 3.29E-06 3.15E-06 7.08E-06 2.15E-07 1.54E-05 6.63E-08 5.05E-06 4.94E-08 9.61 E-06 5.30E-06 1.86E-05 1.20E-06 5.33E-06 6.33E-07 2.64E-06 7.1OE-05 5.04E-05 4.33E-05 3.79E-07 2.55E-08 8.81 E-06 1.34E-08 9.06E-09 2.14E-09 9.67E-1 1 5.65E-09 1.12E-09 1.67E-07 4.03E-09 1.38E-1 1 3.48E-09 2.17E-07 5.61E-10 thyroid 0.OOE+00 5.68E-08 1.54E-08 1.36E-06 7.84E-06 1.69E-05 8.14E-07 3.84E-05 2.38E-07 1.24E-05 1.57E-07 1.52E-05 1.48E-03 1.39E-02 1.58E-04 3.31 E-03 4.15E-05 6.49E-04 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 1.04E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.44E-04 2.44E-06 2.50E-04 7.07E-07 4.21 E-05 4.50E-07 6.44E-05 1.45E-05 4.94E-05 3.76E-06 2.14E-05 1.99E-06 8.07E-06 1.81 E-04 5.38E-05 1.64E-04 3.90E-07 3.51E-10 4.06E-08 1.75E-10 8.81 E-11 0.OOE+00 0.OOE+00 1.48E-08 2.86E-09 4.93E-07 1.13E-08 3.84E-1 1 2.19E-08 0.OOE+00 1.98E-09 lung 0.OOE+00 1.34E-05 7.72E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 7.42E-05 1.1OE-05 6.64E-05 6.09E-08 3.54E-10 1.05E-07 1.77E-10 9.26E-1 1 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 gi-Ili 3.77E-05 6.60E-05 1.64E-05 1.11E-04 1.11E-05 2.36E-05 2.1 OE-05 5.97E-05 2.27E-05 1.03E-04 7.11 E-06 3.81 E-05 2.83E-06 1.51 E-06 2.73E-06 3.08E-06 1.84E-06 2.62E-06 1.91 E-06 2.05E-06 1.91 E-06 1.25E-06 5.58E-05 4.20E-05 5.19E-06 7.59E-07 9.77E-05 6.86E-05 2.48E-05 5.73E-05 1.71 E-04 4.29E-05 4.93E-06 3.60E-05 3.69E-05 2.87E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
REFERENCES:
Regulatory Guide 1.109, Table E-14.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,, November, 1977, Table 4.
SQN ODCM Revision 58 Page 96 of 179 Table 6.5 BIOACCUMULATION FACTORS FOR FRESHWATER FISH (pCi/kg per pCi/L)H-3 C-14 Na-24 P-32 Cr-51 Mn-54 Mn-56 Fe-55 Fe-59 Co-57 Co-58 Co-60 Ni-63 Ni-65 Cu-64 Zn-65 Zn-69 Zn-69m Br-82 Br-83 Br-84 Br-85 Rb-86 Rb-88 Rb-89 Sr-89 Sr-90 Sr-91 Sr-92 Y-90
REFERENCES:
9.OE-01 4.6E+03 1.0E+02 1.OE+05 2.OE+02 4.OE+02 4.OE+02 1.OE+02 1.0E+02 5.0E+01 5.OE+01 5.0E+01 1.0E+02 1.0E+02 5.OE+01 2.OE+03 2.OE+03 2.OE+03 4.2E+02 4.2E+02 4.2E+02 4.2E+02 2.OE+03 2.OE+03 2.OE+03 5.6E+01 5.6E+01 5.6E+01 5.6E+01 2.5E+01 Y-91m Y-91 Y-92 Y-93 Zr-95 Zr-97 Nb-95 Nb-97 Mo-99 Tc-99m Tc-101 Ru-103 Ru-105 Ru-106 Ag-11Orn Sb-1i24 Sb-1i25 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-132 1-130 1-131 1-132 1-133 2.5E+01 2.5E+01 2.5E+01 2.5E+01 3.3E+00 3.3E+00 3.OE+04 3.OE+04 1.OE+01 1.5E+01 1.5E+01 1.0E+01 1.OE+01 1.OE+01 2.31 E+00 1.OE+00 1.OE+00 3.OE+03 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.OE+02 4.0E+02 4.OE+02 4.OE+02 4.OE+01 4.OE+01 4.OE+01 4.OE+01 1-134 1-135 Cs-1 34 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-144 Ce-141 Ce-143 Ce-144 Pr-144 Pr-143 Nd-147 W-187 Np-239 4.OE+01 4.OE+01 1.9E+03 1.9E+03 1.9E+03 1.9E+03 4.OE+00 4.OE+00 4.OE+00 4.OE+00 2.5E+01 2.5E+01 1.0E+00 1.OE+00 1.01E+00 2.5E+01 2.5E+01 2.5E+01 1.2E+03 1.OE+01 Bioaccumulation factors for Ag-11 On, Sb-124, Sb-125 and Sn-125 are from ORNL-4992, "A Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment," March 1976, Table 4.12A.Bioaccumulation factors for Iodine, Cesium, and Strontium nuclides are from NUREG/CR-1 004, Table 3.2.4.All other nuclides' bioaccumulation factors are from Regulatory Guide 1.109, Table A-I.
SQN ODCM Revision 58 Page 97 of 179 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/m 2)(Page 1 of 2)Nuclide Total Body Skin H-3 0.0 0.0 C-14 0.0 0.0 Na-24 2.50E-08 2.90E-08 P-32 0.0 0.0 Cr-51 2.20E-10 2.60E-10 Mn-54 5.80E-09 6.80E-09 Mn-56 1.10E-08 1.30E-08 Fe-55 0.0 0.0 Fe-59 8.OOE-09 9.40E-09 Co-57 1.77E-09 2.21E-09 Co-58 7.OOE-09 8.20E-09 Co-60 1.70E-08 2.00E-08 Ni-63 0.0 0.0 Ni-65 3.70E-09 4.30E-09 Cu-64 1.50E-09 1.70E-09 Zn-65 4.OOE-09 4.60E-09 Zn-69 0.0 0.0 Zn-69m 5.50E-09 6.59E-09 Br-82 3.18E-08 3.90E-08 Br-83 6.40E-11 9.30E-11 Br-84 1.20E-08 1.40E-08 Br-85 0.0 0.0 Rb-86 6.30E-10 7.20E-10 Rb-88 3.50E-09 4.OOE-09 Rb-89 1.50E-08 1.80E-08 Sr-89 5.60E-13 6.50E-13 Sr-91 7.1OE-09 8.30E-09 Sr-92 9.OOE-09 1.OOE-08 Y-90 2.20E-12 2.60E-12 Y-91 m 3.80E-09 4.40E-09 Y-91 2.40E-11 2.70E-11 Y-92 1.60E-09 1.90E-09 Y-93 5.70E-10 7.80E-10 Zr-95 5.OOE-09 5.80E-09 Zr-97 5.50E-09 6.40E-09 Nb-95 5.10E-09 6.OOE-09 Nb-97 8.11 E-09 1.OOE-08 Mo-99 1.90E-09 2.20E-09 Tc-99m 9.60E-10 1.1OE-09 Tc-101 2.70E-09 3.OOE-09 Ru-1 03 3.60E-09 4.20E-09 Ru-105 4.50E-09 5.1OE-09 Ru-106 1.50E-09 1.80E-09 SQN ODCM Revision 58 Page 98 of 179 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/m 2)(Page 2 of 2)Nuclide Ag-110m Sb-124 Sb-125 Sn-125 Te- 125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-1 34 Cs-136 Cs-1 37 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 Total Body 1.80E-08 2.17E-08 5.48E-09 3.58E-09 3.50E-1i1 1.10E-12 1.OOE- 11 7.70E-10 7.10E-10 8.40E-09 2.20E-09 1.70E-09 1.40E-08 2.80E-09 1.70E-08 3.70E-09 1.60E-08 1.20E-08 1.20E-08 1.50E-08 4.20E-09 2.10E-08 2.40E-09 2.1 OE-09 4.30E-09 7.90E-09 1.50E-08 1.50E-08 5.50E-10 2.20E-09 3.20E-10 0.0 2.OOE-10 1.OOE-09 3.1 OE-09 9.50E-10 Skin 2.1OE-08 2.57E-08 6.80E-09 4.51 E-09 4.80E-1 1 1.30E-12 1.10E-11 9.OOE-10 8.40E-10 9.90E-09 2.60E-06 2.OOE-09 1.70E-08 3.40E-09 2.OOE-08 4.50E-09 1.90E-08 1.40E-08 1.40E-08 1.70E-08 4.90E-09 2.40E-08 2.70E-09 2.40E-09 4.90E-09 9.OOE-09 1.70E-08 1.80E-08 6.20E-10 2.50E-09 3.70E-10 0.0 2.30E-10 1.20E-09 3.60E-09 1.10E-09
REFERENCES:
Regulatory Guide 1.109, Table E-6.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from Dose-Rate Conversion
- Factors for External Exposure to Photon and Electron Radiation from Radionuclides Occurring in Routine Releases from Nuclear Fuel Cycle Facilities, D. C. Kocher, Health Physics Volume 38, April 1980.
SQN ODCM Revision 58 Page 99 of 179 Figure 6.1 LIQUID EFFLUENT RELEASE POINTS"A" Train O-RE-90-133,140"B" Train 0-RE-90-1 34,141 DLA SQN ODCM Revision 58 Page 100 of 179 Figure 6.2 LIQUID RADWASTE SYSTEM 125 gpm routine 0-RM-90-1 22 TO COOLING TOWER BLOWDOWN SQN ODCM Revision 58 Page 101 of 179 SECTION 7.0 GASEOUS EFFLUENTS SQN ODCM Revision 58 Page 102 of 179 SECTION 7.0 GASEOUS EFFLUENTS RELEASE POINTS DESCRIPTION There are six major exhaust pathways at Sequoyah Nuclear Plant that are monitored for airborne effluents.
These are: a Condenser Vacuum Exhaust for each unit, a Service Building Exhaust, an Auxiliary Building Exhaust and a Shield Building Exhaust for each unit. Figure 7.1 provides an outline of the airborne effluent release and discharge points with associated radiation monitor identifications.
All gaseous effluents at Sequoyah are considered ground level for the purpose of evaluating offsite dose and setpoint determination.
Condenser Vacuum Exhaust The Condenser Vacuum Exhausts (CVEs) are located in the turbine building.
The CVE exhaust at a maximum design flow rate of 45 cubic feet per minute. They are monitored for routine releases by radiation monitors 1,2-RM-90-99,119.
Service Buildinq Vent Various low-level sources exhaust to the Service Building Vent. This exhausts at a total design flow of approximately 11,200 cfm. Only a portion of this total flow (9,000 cfm) originating from the Titration Room, the Chemistry Lab, and the RCA Access Control Area is monitored by.radiation monitor 0-RM-90-132.
Auxiliary Building Exhaust (see Figure 7.2 for detail)The annulus vacuum priming system exhausts through the containment vent to the Auxiliary Building.
The Auxiliary Building Exhaust consists of the Auxiliary Building General Exhaust System and the Fuel Handling Exhaust and they cumulatively exhaust at a maximum design flow of 228,000 cfm. The exhaust is monitored by radiation monitor 0-RM-90-101.
Shield Building Vent (see Figure 7.2 for detail)The Auxiliary Building Gas Treatment System (ABGTS) draws from the Auxiliary Building and exhausts through the Shield Building Vent. There are nine Waste Gas Decay Tanks (WGDTs) that empty into the waste gas header. Either ABGTS or the Emergency Gas Treatment System (EGTS) is run to release a WGDT. Each WGDT has a design capacity of 600 cubic feet at STP and a design release rate of 22.5 cfm. Both the Containment Purge and the Incore Instrument Room Purge from each unit tie into the waste gas header. The Containment Purge exhausts at a maximum of 28,000 cfm and is monitored by radiation monitors 1,2-RM 130,131. If the Incore Instrument Room Purge is operating exclusively, it exhausts at 800 cfm. Under emergency conditions, and sometimes during normal operation, the EGTS is used to draw a vacuum in the annulus and exhaust to the Shield Building Vent. Auxiliary Building Isolation starts both the ABGTS and EGTS.The common header exhausts to the Shield Building Exhaust. There is one exhaust for each unit. This exhausts at a maximum design flow of 28,000 cfm and is monitored by radiation monitors 1,2-RM-90-400.
SQN ODCM Revision 58 Page 103 of 179 7.1 INSTRUMENT SETPOINTS Airborne effluent monitor setpoints are determined to ensure that the dose rate at the UNRESTRICTED AREA BOUNDARY does not exceed the dose rate limits given in ODCM Control 1.2.2.1 and to identify unexpected releases.7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-131, O-RM-90-118) 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-131)
These monitors are set at a cpm value equal to the Technical Specification Limit of <8.5xl 0-3 gCi/cc as Xe-1 33 (Technical Specification 3.3.2.1(U1), 3.3.2(U2), Table 3.3-4, and 3.3.3.1, Table 3.3-6). The radiation monitor vacuum setpoint is set at 9 +/- 1 in. of vacuum, T/S Limit = 8.5E-03 gCi/cc, monitor efficiency for Xe-1 33 = 9.08E+ 05 CPM/pCi/cc, Vacuum Correction
= 0.75; therefore the maximum setpoint = (8.5E-03)
(9.08E+05)(0.75)
=5800 CPM.7.1.1.2 Waste Gas Decay Tank Effluent Monitor (0-RM-90-118)
The setpoint for the Waste Gas Decay Tank effluent monitor is routinely set at a Default Setpoint, SDEF. This setpoint uses the site release rate limit and considers the dilution effect of ABGTS during the release process.SDEF for 0-RM-90-118 is 1.88E3 CPM based on the following:
SDEF = DRUM
- 3.28E+04
- 5.525E-03 2.94E+02
- X/Q
- 472
- RR Where: DRUM is the site dose rate limit = 500mRem/y RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 3.28E+04 cpm/uCi/cc is the radiation monitor's efficiency 5.525E-03 is the max. Dilution flow factor provided by ABGTS (9000cfm)X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1 2.94E+02 = Dose Factor for Xe-1 33 mRem/y/uCi/m 3 , Table 7.3 472 = Conversion Factor, (28317 cc/ft 3.min/60 s)A Maximum Setpoint, Smax can also be calculated for 0-RM-90-118 based on using the radiation monitor as the primary monitor for the release path.Smax for 0-RM-90-118 is 31,879 CPM based on the following:
SMAX =!6A* RLM* 3.28E+04 2.94E+02
- X/Q
- 472 -RR Where: A = the Dose Rate allocation factor for the shield bldg.,0.0955 DRUM is the site dose rate limit = 500mRem/y 3.28E+04 cpm/uCi/cc is the radiation monitor's efficiency for Xe-1 33 2.94E+02 = Dose Factor for Xe-133 mRem/y/uCi/m 3 , Table 7.3 X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1 RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 472 = Conversion Factor, (28317 cc/ft 3.min/60 s)
SQN ODCM Revision 58 Page 104 of 179 For each release from a waste gas decay tank, two setpoints are evaluated for the monitor: one based on the expected response of the monitor to the radioactivity in the effluent stream and a calculated expected monitor response setpoint.
The expected monitor response is calculated as described below in Equation 7.1. The expected monitor response setpoint is calculated as described below in Equation 7.1a. A comparison is made to verify the expected monitor response and expected monitor response setpoint is less than or equal to the Default Setpoint.
If the expected monitor response or expected monitor response setpoint is greater than Default Setpoint it may be temporarily increased but can not exceed the Maximum Setpoint.
The calculated setpoints ensures that the release will be stopped if it exceeds any dose rate limits.Expected Monitor Response, CPM RCPM = B + Y- effi Ci i (7.1)Where: RCPM = Expected Monitor Response,CPM B = monitor background, cpm.effi= efficiency factor for the monitor for nuclide i, cpm per gCi/cc.Ci = measured concentration of nuclide i, pCi/cc.Expected Monitor Response, uCi/s Rucils = B + 472Ci, RR Where : RuCi/s = Expected Release Rate, uCi/s B = monitor background,.
uCi/s 472 = Conversion Factor, cc/ft3,m/s Ci = measured concentration of nuclide i, uCi/cc RR = Release Rate, ft 3/min Expected Monitor Response Setpoint, CPM or uCi/s (7.1 a)The expected monitor response setpoint Ser is calculated for the monitor for each release.Ser = X. R where R = expected monitor response, CPM or uCi/s X = administrative factor designed to account for expected variations in monitor response and background The range of values is: 1.0 < X < 2.0 SQN ODCM Revision 58 Page 105 of 179 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, O-RM-90-101, O-RM-90-132, 1,2-RM-90-99,119)
A normal default setpoint, SDEF is utilized for each discharge point monitor as described below. When release permits are generated, the expected response and expected monitor response setpoint is calculated for the appropriate discharge monitor as described in Section 7.1.1.2. A comparison is made between the two setpoints.
If the expected monitor response or expected monitor response setpoint is greater than the default setpoint then the release parameters must be reevaluated.
Worse case conditions will require an evaluation of the allocation factors in section 7.1.1.2.Calculated Default Setpoint The calculated default setpoint, SDef in cpm (0-101,0-132, & 1,2-99,119), corresponding to the dose rate limit is determined using the following equation: SDEF =A_* DRULM* Eff_2 0.71 (7.2)DRR* 472 -2.94E+02* (X/Q Where: A = dose rate allocation factor for the release point, dimensionless.
The dose rate allocation factors for release points are defined as follows based on design flowrates:
Auxiliary Building 0.7779 Shield Building (ea) 0.0955 Service Building 0.0307 Condenser Vacuum Exhaust (ea) 0.00015 0.71 = safety factor for the monitor, dimensionless.
Safety factors for these monitors includes 0.75 for the radiation monitor vacuum correction factor and 0.95 for Xe-133 primary isotope mix.DRuim = the dose rate limit, 500 mrem/year to the total body for noble gases.DRR = the design release rate for the release pathway or design approved flow rate.= DRTB for total body (as described in Section 7.2.3.1).472 = Conversion Factor, (28317 cc/ft 3.min/60 s).X/Q = 6.14E-06 S/M 3 , Section 7.2.3.1.Eff = Radiation Monitor Efficiency for Xe-133, 0-101,0-132, 1,2-99,119
@ 2.27E+07 CPM/uCi/cc.
2.94E+02 = Dose Factor for Xe-1 33 mRem/y/uCi/m 3 ,Table 7.3.The calculated default setpoint, SDef in uCi/s (1,2-400), corresponding to the dose rate limit is determined using the following equation: SDEF = AL* 2.94E+02
- X/Q 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119)
This discharge point effluent monitor is set to ensure compliance with ODCM Control 1.2.2.1 and to identify the presence of primary to secondary leakage of radioactivity.
The default setpoint is determined by Equation 7.2 for Xe-1 33, and then taking a percentage of this value as the setpoint; or by defining the setpoint as a low value above the normal background.
Once a primary to secondary leak is identified, the setpoint on this monitor may be adjusted upward to enable it to be used to identify any further increases in the leak rate but will not be allowed to be set greater than the calculated default value without further evaluation of the allocation factors.
SQN ODCM Revision 58 Page 106 of 179 7.2 GASEOUS EFFLUENTS
-DOSE RATES 7.2.1 (Deleted)7.2.2 RELEASE SAMPLING Prior to each release (excluding an Incore Instrument Room Purge), a grab sample is taken and analyzed to determine the concentration, gCi/cc, of each noble gas nuclide. On at least a weekly basis, filters are analyzed to determine the amount of iodines and particulates released.
Composite samples are maintained (as required by Table 2.2-2) to determine the concentration of certain nuclides (Sr-89, Sr-90, and alpha emitters).
For those nuclides whose activities are determined from composite samples the concentrations for the previous composite period will be assumed as the concentration for the next period to perform the calculations in Sections 7.3, 7.4, and 7.5. The actual measured concentrations will be used for the dose calculations described in Section 7.6.7.2.3 NOBLE GAS DOSE RATES Dose rates are calculated for total body and skin due to submersion within a cloud of noble gases using a semi-infinite cloud model.7.2.3.1 Total Body Dose Rate The dose rate to the total body, DRTB in mrem/year, is calculated using the following equation: DRTB = (X/Q) F Y-i Ci DFBi (7.3)where X/Q = relative concentration, s/M 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).F = flowrate of effluent stream, cc/s.Ci = concentration of noble gas nuclide i in effluent stream, gICi/cc.DFBi = total body dose factor due to gamma radiation for noble gas nuclide i, mrem/y per igCi/m 3 (Table 7.3).
SQN ODCM Revision 58 Page 107 of 179 7.2.3.2 Skin Dose Rate The dose rate to the skin, DRs in mrem/year, is calculated using the following equation: DR, = (X/Q) F _i Ci(DFSi + 1.11 DFý1) (7.4)where X/Q = relative concentration, s/m 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).F = flowrate of effluent stream, cc/s.Ci = concentration of noble gas nuclide i in effluent stream, iCi/cc.DFSi = skin dose factor due to beta radiation for noble gas nuclide i, mrem/y per pCi/m 3 (Table 7.3).1.11 = the average ratio of tissue to air energy absorption coefficients, mrem/mrad.
DFlo = dose conversion factor for external gamma for noble gas nuclide i, mrad/y per gCi/m 3 (Table 7.3).
SQN ODCM Revision 58 Page 108 of 179 7.2.4 1-131, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS -ORGAN DOSE RATE Organ dose rates due to 1-131, 1-133, Tritium and all radionuclides in particulate form with half-lives of greater than 8 days, DRorg in mrem/y, are calculated for all age groups (adult, teen, child, and infant) and all organs (bone, liver, total body, thyroid, kidney, lung, and GI Tract) using the following equation: DRorg= F [ CT(X/Q)[RIT+RcTP]
+ 1j Ci[(X/Q)Rli
+ (D/Q) [Rcpi + RG 1]]] (7.5)where: F = flowrate of effluent stream, cc/s.C.T = concentration of tritium in effluent stream, giCi/cc.X/Q = relative concentration, s/m 3.Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 6.14E-06 s/m 3 (from Table 7.1).RIT = inhalation dose factor for tritium, mrem/y per gCi/m 3.Dose factor is calculated as described in Section 7.7.13.RCTP= Grass-cow-milk dose factor for tritium, mrem/y per jLCi/m 3.Dose factor is calculated as described in Section 7.7.7.Ci = concentration of nuclide i in effluent stream, gCi/cc.Ri = inhalation dose factor for each identified nuclide i, mrem/y per ptCi/m 3.Dose factors are calculated as described in Section 7.7.13.D/Q = relative deposition, 1/M 2.Relative deposition is calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.3 from quarterly meteorological data from 1999-2008 (40 quarters).
For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.= 1.40E-08 1/M 2 (from Table 7.2).RCpi = Grass-cow-milk dose factor for each identified nuclide i, m 2-mrem/y per jiCi/s. Dose factors are calculated as described in Section 7.7.1.RGi = ground plane dose factor for each identified nuclide i, m 2-mrem/y per liCi/s. Dose factors are calculated as described in Section 7.7.14.The maximum organ dose rate is selected from among the dose rates calculated for all the organs and all age groups.
SQN ODCM Revision 58 Page 109 of 179 7.3 DOSE -NOBLE GASES Doses to be calculated are gamma and beta air doses due to exposure to an infinite cloud of noble gases.These doses will be calculated from the unrestricted area boundary locations with the highest X'Qs for each quarter from 1999-2008.
Dispersion factors are calculated using the methodology described in Section 7.8.2.No credit is taken for radioactive decay.7.3.1 Gamma dose to air The gamma air dose, D. in mrad, is calculated for each release using the following equation: DY = 1.9E-06 (X/Q) Ii Qj DF,ý T (7.6)where: 1.9E-06= conversion factor, y/min.X/Q = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.14x10" 6 s/m 3 (from Table 7.1).Qi = release rate for nuclide i, piCi/s.DF~I = dose conversion factor for external gamma for nuclide i (Table 7.3), mrad/y per !lCi/m 3.T = duration of release, min.The gamma-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.7.3.2 Beta dose to air The beta air dose, D13 in mrad, is calculated for each release using the following equation: DP = 1.9E-06 (X/Q) ,_i Qi DFpj T (7.7)where: 1.9E-06= conversion factor, y/min.X/Q = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.14x10-6 s/m 3 (from Table 7.1).Qi = release rate for nuclide i, gCi/s.DFpj = dose conversion factor for external beta for nuclide i, mrad/y per pCi/m 3 (from Table 7.3).T = duration of release, min.The beta-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.
SQN ODCM Revision 58 Page 110 of 179 7.3.3 Cumulative Dose -Noble Gas Monthly, quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.2.For noble gases, cumulative doses are calculated for gamma and beta air doses. Doses due to each release are summed with the doses for all previous release in the quarter or year to obtain cumulative quarterly and annual doses.7.3.4 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.
SQN ODCM-Revision 58 Page 111 of 179 7.4 DOSE DUE TO 1-131. 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS 7.4.1 Organ dose Calculation Organ doses due to 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives of greater than 8 days are calculated for each release for the critical receptors.
Carbon-14 production and effluent source term is based on EPRI methodology provided in EPRI Report 1021106, Estimation of Carbon-14 in Nuclear Power Plant Gaseous Effluents, December 2010. The critical receptors are defined as the unrestricted area boundary in the sectors with the highest quarterly X/Q and D/Q for each quarter from 1999-2008.
The X/Q and D/Q are calculated using the methodology in Sections 7.8.2 and 7.8.3 using the historical 1999-2008 meteorological data (Table 7.2). Pathways considered to exist at this location are inhalation, ground plane exposure, grass-cow-milk ingestion, grass-cow-beef ingestion and fresh leafy and stored vegetable ingestion.
All age groups are considered (adult, teen, child and infant). Dose factors for these age groups and pathways are calculated as described in Section 7.7. For the ground exposure pathway, which has no age or organ specific dose factors, the total body dose will be added to the internal organ doses for all age groups. No credit is taken for radioactive decay.The general equation for the calculation of organ dose is: Dorg = 3.17E-08 T Ti Tp Rpi [ Wp Q] (7.8)where: 3.17E-08 = conversion factor, y/s T = duration of release, s.Rpi = dose factor for pathway P for each identified nuclide i, m 2-mrem/y per giCi/s for ground plane, grass-cow-milk, grass-cow-meat, and vegetation pathways, and mrem/y per igCi/m 3 for inhalation, tritium ingestion and carbon-14 pathways.
Equations for calculating these dose factors are given in Section 7.7.Wp = dispersion factor for the location and pathway,= X/Q for the inhalation , tritium ingestion and carbon-14 pathways,= 6.94E-06 s/m 3.= D/Q for the food and ground plane pathways,= 1.30E-08 m-2 Qi = release rate for radionuclide i, pCi/s From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The organ doses for the critical age group will be used in the cumulative doses discussed in Section 7.4.2.
SQN ODCM Revision 58 Page 112 of 179 7.4.2 Cumulative Doses Quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.3.For maximum organ dose, cumulative quarterly and annual doses are maintained for each of the eight organs considered.
The cumulative dose is obtained by summing the doses for each organ of the critical age group (as calculated in Section 7.4.1) as determined for each release with the organ doses for all previous releases in the quarter or year to obtain the cumulative quarterly and annual doses. Thus, the cumulative organ doses will be conservative values, consisting of doses belonging to various age groups depending on the mix of radionuclides.
The highest of these cumulative organ doses is used for the comparison to the limits described in ODCM Control 1.2.2.3.7.4.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.
SQN ODCM Revision 58 Page 113 of 179 7.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.2.4, dose projections will be performed by averaging the two previous month's doses as determined in Section 7.3.3. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.The projected doses are compared to the limits of ODCM Control 1.2.2.4. The limits are 0.2 mrad per unit for gamma radiation, 0.4 mrad per unit for beta radiation, or 0.3 mrem per unit to any organ.D= a+b 2 where: D = the 31-day dose projection, mrad a = the cumulative gamma, beta, or organ dose for the previous month, mrad b = the cumulative gamma, beta, or organ dose for the present month, mrad If the projected doses exceed any of these limits, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY.7.5.1 GASEOUS RADWASTE TREATMENT SYSTEM DESCRIPTION The GASEOUS RADWASTE TREATMENT SYSTEM (GRTS) described below shall be maintained and operated to keep releases ALARA.A flow diagram for the GRTS is given in Figure 7.3. The system consists of two waste-gas compressor packages, nine gas decay tanks, and the associated piping, valves, and instrumentation.
Gaseous wastes are received from the following:
degassing of the reactor coolant and purging of the volume control tank prior to a cold shutdown, displacing of cover gases caused by liquid accumulation in the tanks connected to the vent header, and boron recycle process operation.
SQN ODCM Revision 58 Page 114 of 179 7.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated gaseous releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel.
All real pathways and receptor locations identified by the most recent land use survey are considered.
In addition, actual meteorological data representative of a ground level release for each corresponding calendar quarter will be used. For iodine releases, it is assumed that half the iodine released is in organic form. Organic iodine causes a dose only by inhalation.
For cow-milk and beef ingestion doses, the fraction of the time the animals are on stored feed (identified in the survey) is used in the calculation.
The highest organ dose for a real receptor is determined by summing the dose contribution from all identified pathways for each receptor including ground contamination, inhalation, vegetable ingestion (for identified garden locations), cow and/or goat milk ingestion (if a cow or goat is identified for the location), beef ingestion (the beef ingestion dose for the location of highest beef dose for all receptors will be considered the beef dose for all receptors).
7.6.1 NOBLE
GAS -GAMMA AIR DOSE Gamma air doses due to exposure to noble gases, Dr in mrad, are calculated using the following equation: Dr = xim DFy (7.9)where: xim = concentration of nuclide i at location m, pjCi/m 3.Air concentrations are calculated as described by Equation 7.14.DF.i = dose conversion factor for external gamma for nuclide i, mrad/y per giCi/m 3 (Table 7.3).7.6.2 NOBLE GAS -BETA AIR DOSE Beta air doses due to exposure to noble gases, Do in mrad, are calculated using the following equation: Do = DFpi (7.10)where: xim = concentration of nuclide i at location m, gCi/im 3.Air concentrations are calculated as described by Equation 7.14.DFp3i = dose conversion factor for external beta for nuclide i, mrad/y per gCi/m 3 (Table 7.3).
SQN ODCM Revision 58 Page 115 of 179 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE Organ doses due to radioiodine, particulate, tritium, and Carbon-14 releases, Dorg in mrem, are calculated using the following equation: oDrg = 3.17E-08[1 (D/Q IR pi + D/Q R G +X/QR, 1)Q, +Z(X/Q RPT )QT i P p+IE (.X/Q R pc,4 )Qc14]P (7.11)where: 3.17E-08 = conversion factor, y/s.X/Q = Relative concentration for location under consideration, s/m 3.Relative concentrations are calculated as described by Equation 7.15.RpT = ingestion dose factor for pathway P for tritium, m 2-mrem/y per IaCi/s. Ingestion pathways available for consideration are the same as those listed above for Rpi. Equations for calculating ingestion dose factors for tritium are given in Sections 7.7.7 through 7.7.12.QT = adjusted release rate for tritium for location under consideration, IaCi/s. Calculated in the same manner as Qi above.QC14 = adjusted release rate for Carbon-14 for location under consideration, laCi/s.Rpi = ingestion dose factor for pathway P for each identified nuclide i (except tritium), m 2-mrem/y per pCi/s. Ingestion pathways available for consideration include: pasture grass-cow-milk ingestion stored feed-cow-milk ingestion pasture grass-goat-milk ingestion stored feed-goat-milk ingestion pasture grass-beef ingestion stored feed-beef ingestion fresh leafy vegetable ingestion stored vegetable ingestion Equations for calculating these ingestion dose factors are given in Sections 7.7.1 through 7.7.6.D/Q = Relative deposition for location under consideration, m-2.Relative deposition is calculated as described in Equation 7.16.RGi = Dose factor for standing on contaminated ground, m 2-mrem/y per jICi/s. The equation for calculating the ground plane dose factor is given in Section 7.7.14.Rli = Inhalation dose factor, mrem/y per g.Ci/m 3.The equation for calculating the inhalation dose factor is given in Section 7.7.13.Rpc14 = Ingestion dose factor for pathway P for carbon-14, mrem/y per gCi/s. Ingestion pathways available for consideration are the same for those listed above for Rpi. Equations for calculating ingestion dose factors for carbon-14 are given in Sections 7.7.13 through 7.7.18.Qi = adjusted release rate for nuclide i for location under consideration, jaCi/s. The initial release rate is adjusted to account for decay between the release point and the location, depending on the frequency of wind speeds applicable to that sector. Hence, the adjusted release rate is equal to the actual release rate decayed for an average travel time during the period.
SQN ODCM Revision 58 Page 116 of 179 7.6.3 RADIOIODINE, PARTICULATE, CARBON-14 AND TRITIUM -MAXIMUM ORGAN DOSE (continued) 9 Q i =Qi 0 I fi exp(-Xi x/uj) (7.12)j=1 where Qi0 = initial average release rate for nuclide i over the period, !iCi/s.fj = joint relative frequency of occurrence of winds in windspeed class j blowing toward this exposure point, expressed as a fraction.ki = radiological decay constant for nuclide i, s-1.x = downwind distance, meters.uj = midpoint value of wind speed class interval j, m/s.
SQN ODCM Revision 58 Page 117 of 179 7.6.4 POPULATION DOSES For determining population doses to the 50-mile population around the plant, each compass sector is broken down into elements.
These elements are defined in Table 7.4. For each of these sector elements, an average dose is calculated, and then multiplied by the population in that sector element. Dispersion factors are calculated for the midpoint of each sector element (see Table 7.4).For population doses resulting from ingestion, it is conservatively assumed that all food eaten by the average individual is grown locally.The general equation used for calculating the population dose in a given sector element is: Dosepop = X RATIOp
- POPN
- AGE
- 0.001
- DOSEp (7.13)P where RATIOp = ratio of average to maximum dose for pathway P. (Average ingestion rates are obtained from Regulatory Guide 1.109, Table E-4.)= 0.5 for submersion and ground exposure pathways, a shielding/occupancy factor.= 1.0 for the inhalation pathway.= 0.515, 0.515, 0.5, and 0.355 for milk, for infant, child, teen and adult, respectively. (It is assumed that the ratio of average to maximum infant milk ingestion rates is the same as that for child.)= 1.0, 0.90, 0.91, 0.86 for beef ingestion, for infant, child, teen and adult, respectively.
= 1.0, 0.38, 0.38, 0.37 for vegetable ingestion, for infant, child, teen and adult, respectively. (It is assumed that the average individual eats no fresh leafy vegetables, only stored vegetables.)
POPN = the population of the sector element, persons (Table 7.5).AGE = fraction of the population belonging to each age group.= 0.015, 0.168, 0.153, 0.665 for infant, child, teen and adult, respectively (fractions taken from NUREG/CR-1004, Table 3.39).0.001 = conversion from mrem to rem.DOSEp = the dose for pathway P to the maximum individual at the location under consideration, mrem. For ingestion pathways, this dose is multiplied by an average decay correction to account for decay as the food is moved through the food distribution cycle. This average decay correction, ADC, is defined as follows: For milk and vegetables, ADC = exp(-kit)where -1 ki = decay constant for nuclide i, s t = distribution time for food product under consideration (values from Regulatory Guide 1.109, Table D-1).= 1.21 E+06 s (14 d)for vegetables.
= 3.46E+05 s (4 d) for milk.
SQN ODCM Revision 58 Page 118 of 179 7.6.4 POPULATION DOSES (continued) exp(-X.it)
Xitcb For meat, ADC =1 -exp(-Xitcb)
(7.14)where X'i = decay constant for nuclide i, s.t = additional distribution time for meat, over and above the time for slaughter to consumption described in Section 7.7.3, 7 d.tcb = time to consume a whole beef, as described in Section 7.7.3.For beef ingestion, the additional factors in the calculation of ADC negate the integration of the dose term over the period during which a whole beef is consumed, for the calculation of population dose. In other words, this assumes that the maximum individual freezes and eats a whole beef, while the average individual buys smaller portions at a time.Population doses are summed over all sector elements to obtain a total population dose for the 50-mile population.
7.6.5 REPORTING
OF DOSES The calculated quarterly doses and calculated population doses described in this section are reported in the Annual Radiological Effluent Release Report as required by ODCM Administrative Control 5.2.7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED or RESTRICTED AREA BOUNDARY The Basis for ODCM Control 1.2.2.1 states that for members of the public who may at times be within the UNRESTRICTED or RESTRICTED AREA BOUNDARY, the occupancy factor of that member of the public will usually be sufficiently low to compensate for any increase in the atmospheric dispersion factor above that for the UNRESTRICTED AREA BOUNDARY.
This basis also states that examples of calculations for such members of the public will be given in the ODCM.The determination presented here assumes that the most exposed member of the public will be an adult TVA employee who works just outside the restricted area fence for the entire workyear (2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br />). Results from onsite dosimeter measurements from the years 1990-1992 indicate that the highest onsite external dose was 72.6 mrem. Using this value, subtracting an annual background value of 55 mrem/year, and multiplying by the ratio of the occupancy times, the highest external dose to a MEMBER OF THE PUBLIC inside the UNRESTRICTED AREA BOUNDARY is 4 mrem. Historical records show that the total dose contribution from effluent releases is normally less than 2 mrem. The combination of the measured direct dose (part of which is from effluent releases) and the calculated effluent dose will be below both the 10 CFR Part 20 limit of 100 mrem/year and the 40 CFR Part 190 limit of 25 mrem/year.
In addition to this analysis, the dose to this hypothetical member of the public will be determined on an annual basis (using the methodology above) to ensure that the actual dose to any individual is less than 100 mrem/year.
The results of this review will be included in the Annual Radiological Effluent Release Report pursuant to ODCM Administrative Control 5.2.
SQN ODCM Revision 58 Page 119 of 179 7.7 GASEOUS RELEASES -Dose Factors 7.7.1 PASTURE GRASS-COWlGOAT-MILK INGESTION DOSE FACTORS (m 2-mrem/y per gCi/s)Rcpi = 10 6 DFLiaoUapFmiQfexp(-Xitfm)fp
{r(L-exp(-_Et!e_
+ Bil-exD(-X,_t__}
(7.15)Yp ?E P Xi where: 106 = conversion factor, pCi/[Ci.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uap = milk ingestion rate for age group a, L/y.Fmi = transfer factor for nuclide i from animal's feed to milk, d/L(Table 6.2).Qf = animal's consumption rate, kg/d.Xji -- decay constant for nuclide i, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.fp = fraction of time animal spends on pasture, dimensionless.
r = fraction of activity retained on pasture grass, dimensionless.
XE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to ki + Xw.Xw = weathering decay constant for leaf and plant surfaces, s-1.tep = time pasture is exposed to deposition, s.Yp = agricultural productivity by unit area of pasture grass, kg/m 2.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 120 of 179 7.7.2 STORED FEED-COW/GOAT-MILK INGESTION DOSE FACTORS (m 2-mrem/y per gCi/s)Rcsi = 106 DFLiaoUapFmiQf fsexp(-Xitfm)
(1-exp(-Xit
{r(1-exp(-Etesf)-
+ Biv(l-exD(-tb)-}
(7.16)tcsf ?i jYsf XE P ?Xj where: 106 = conversion factor, pCi/lgCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uap = milk ingestion rate for age group a, L/y.Fmi = transfer factor for nuclide i from animal's feed to milk, d/L (Table 6.2).Qf = animal's consumption rate, kg/d.fs = fraction of time animal spends on stored feed, dimensionless.
?,j = decay constant for nuclide i, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.tcsf = time between harvest of stored feed and consumption by animal, s.r = fraction of activity retained on pasture grass, dimensionless.
X'E = the effective decay constant, due to radioactive decay and weathering, s-1, equal to Xi+Xw.= weathering decay constant for leaf and plant surfaces, s-1 tesf = time stored feed is exposed to deposition, s.Ysf = agricultural productivity by unit area of stored feed, kg/m2.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 121 of 179 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS (m 2-mrem/y per gICi/s)Rmpi = 106 DFLiaoUamFFiQF (1-exp(- itcb) exp(-?,its) fp {r(l-exp(-XEte..
+
(7.17)xi tcb Yp PXE P where: 106 = conversion factor, pCi/gCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uam = beef ingestion rate for age group a, kg/y.FRi = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Xi = decay constant for nuclide i, s-1 (Table 6.2).tcb = time for receptor to consume a whole beef, s.ts = transport time from slaughter to consumer, s.fp = fraction of time cow spends on pasture, dimensionless.
r = fraction of activity retained on pasture grass, dimensionless.)E = the effective decay constant, due to radioactive decay and weathering, s-1, equal to Xi+Xw kw = weathering decay constant for leaf and plant surfaces, s-1 tep = time pasture is exposed to deposition, s.Yp P = agricultural productivity by unit area of pasture grass, kg/m2.13hv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 122 of 179 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS (m 2-mrem/y per [tCi/s)Rmsi = 106 DFLiao Uam FFi QF (1-exp(-.itcb) exp(-Xits) fs (1-exp(-.itcsf)l
{r(1-exp(-XEtsf.
+Xi tcb X-i tcsf Ysf XE Bi 1-exj(-,_tb))}
(7.18)P X'i where: 106 = conversion factor, pCi/pCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Uam = beef ingestion rate for age group a, kg/y.FR = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.kji = decay constant for nuclide i, s-1 (Table 6.2).tcb = time for receptor to consume a whole beef, s.ts = transport time from slaughter to consumer, s.fs = fraction of time cow spends on stored feed, dimensionless.
tcsf = time between harvest of stored feed and consumption by cow, s.r = fraction of activity retained on pasture grass, dimensionless.
tesf = time stored feed is exposed to deposition, s.Ysf = agricultural productivity by unit area of stored feed, kg/m 2.XE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to kj+Xw Xw = weathering decay constant for leaf and plant surfaces, s-1.Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 123 of 179 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS (m 2-mrem/y per RCi/s)RVFi = 106 DFLiao exp(-Pithc)
UFLafL {rUt-ei-_ýEW
+ Bi (1-eei-Xt,_fb}
(7.20)YF XE P i(where: 106 conversion factor, pCi/pCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).Xji = decay constant for nuclide i, s-1 (Table 6.2).thc = average time between harvest of vegetables and their consumption and/or storage, s.UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
r = fraction of deposited activity retained on vegetables, dimensionless.
XE = the effective decay constant, due to radioactive decay and weathering, s-1, X- i + XV X = decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.te = exposure time in garden for fresh leafy and/or stored vegetables, s.YF = agricultural yield for fresh leafy vegetables, kg/m 2.Biv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 124 of 179 7.7.6 STORED VEGETABLE INGESTION DOSE FACTORS m 2-mrem/y per pCi/s)Rvsi = 106 DFLiao exp(-Xithc)
Usafg (1-exp(- itSv) {r(l-exp(-t.eh
+ Biv(1-exD(-X4b__}
(7.21)Xi tsv Ysv XE P Xi where: 106 = conversion factor, pCi/gCi.DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).X'i = decay constant for nuclide i, s-1 (Table 6.2).thc = average time between harvest of vegetables and their consumption and/or storage, s.Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg = fraction of stored vegetables grown locally, dimensionless.
tsv = time between storage of vegetables and their consumption, s.r = fraction of deposited activity retained on vegetables, dimensionless.
kE = the effective decay constant, due to radioactive decay and weathering, s-1.= Xi + Xw Xw = decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.te = exposure time in garden for fresh leafy and/or stored vegetables, s.Ysv = agricultural yield for stored vegetables, kg/m 2.Biv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).tb = time period over which accumulation on the ground is evaluated, s.P = effective surface density of soil, kg/m 2.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 125 of 179 7.7.7 TRITIUM-PASTURE GRASS-COW/GOAT-MILK DOSE FACTOR (mrem/y per gCi/m 3)RcTp = 103 106 DFLTao FmT QF Uap [0.75(0.5/H)]
fp exp(-XTtfm)
(7.22)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).FmT = transfer factor for tritium from animal's feed to milk, d/L (Table 6.2).QF = animal's consumption rate, kg/d.U = milk ingestion rate for age group a, L/y.0.15 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fp P = fraction of time animal spends on pasture, dimensionless.
X'T = decay constant for tritium, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.7.7.8 TRITIUM-STORED FEED-COW/GOAT-MILK DOSE FACTOR (mrem/y per igCi/m 3)RCTS = 103 106 DFLTao FFT QF Uam [0.75(0.5/H)]
fs exp(-XTtS) (l-expL-XTtcsf)-
(7.23)XT tcsf XT tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/lCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fs = fraction of time cow spends on stored feed, dimensionless.
XT = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time to consume stored feed, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 126 of 179 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR (mrem/y per jaCi/m 3)RMTP = 103106 DFLTaoFFTQF Uam [0.75(0.5/H)]
fp exp(-XTtS)
(1-exp(-kTXt_e_.L (L-exp(-XTt)cb)
(7.24)XT tep XT tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = beef ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fp P = fraction of time cow spends on pasture, dimensionless.
XT = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tep = time pasture is exposed to deposition, s.tcb = time for receptor to consume a whole beef, s.7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR (mrem/y per gCi/m 3)RMTS = 103 106 DFLTaoFFTQFUam[0.
7 5 (0.5/H)] fs exp(-XTts)
(1-exp(- Ttcsf)) (L-exp(-XTcb)l (7.25)XT tcsf X'T tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4).FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2).QF = cow's consumption rate, kg/d.Uam = beef ingestion rate for age group a, kg/y.0.75 = the fraction of total feed that is water.0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.fs = fraction of time cow spends on stored feed, dimensionless.
X'T = decay constant for tritium, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time to consume stored feed, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 127 of 179 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR (mrem/y per gCi/m 3)RVTF = 103 106 DFLTao [0.75(0.5/H)]
UFLa fL exp(-?'Tthc)
(7.26)where: 10 3 = conversion factor, g/kg.106 = conversion factor, DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).0.75 = the fraction of total vegetation that is water.0.5 = the ratio of the specific activity of the vegetables water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
X'T = decay constant for tritium, s-1 (Table 6.2).thc = time between harvest of vegetables and their consumption and/or storage, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 128 of 179 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR (mrem/year per luCi/m3)RvTS = 10 3 106 DFLTao [0.75(0.5/H)]
Usafg exp(-XTthc)
(7.27)XT tsv where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/1 iCi.DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4).0.75 = the fraction of total vegetation that is water.0.5 = the ratio of the specific activity of the vegetation water to the atmospheric water.H = absolute humidity of the atmosphere, g/m 3.Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg9 = fraction of stored vegetables grown locally, dimensionless.
fXgT = decay constant for tritium, s-1 (Table 6.2).tsv = time between harvest of stored vegetables and their consumption and/or storage, s.thc = time between harvest of vegetables and their storage, s.
SQN ODCM Revision 58 Page 129 of 179 7.7.13 CARBON 14 -PASTURE GRASS-COW/GOAT MILK DOSE FACTOR -RcPc1 4 (mrem/y per gCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D = DFL Uap exp(-X thc)Qcl 4 Q [0.161 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is: RCPCI 4 =103 106 DFLct 4 aj FmC14 Qf Uap L 0.16 ]fp exp(-X c 4 tfi) (7.31)where: 10 3 = conversion factor, g/kg.106 = conversion factor, pCi/pCi.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).FmC14 =transfer factor for carbon 14 from cow's feed to milk, d/L (Table 6.2).Qf = animal's consumption rate, kg/d.Uap = milk ingestion rate for age group a, L/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fp P = fraction of time animal spends on pasture, dimensionless.
AC 1 4 =decay constant for carbon 14, s-1 (Table 6.2).tfm = transport time from milking to receptor, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 58 Page 130 of 179 7.7.14 CARBON 14-STORED FEED-COW/GOAT MILK DOSE FACTOR -Rcsc 1 4 (mrem/y per pCi/M 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
x F0.,11 D = DFL Uap exp(- thc )Qc 4 Q [0.16] (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the feed is stored (this term assumes that the feed is being eaten during the storage period) (Reference 10). The resulting dose factor is: RCSC 1 4 =0 3 106 DFLc1 4 aj FmCI 4 Qf Uap I]1f. exp(- -cI 4 tfm) (7.32)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLC14aJ = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).Ffc14 =transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = animal's consumption rate, kg/d.Uap = milk ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.f, = fraction of time animal spends on stored feed, dimensionless.
AC 1 4 =decay constant for carbon 14, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time between harvest of stored feed and consumption by animal, s.tfm = transport time from milking to receptor, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 58 Page 131 of 179 7.7.15 CARBON 14 -PASTURE GRASS-BEEF DOSE FACTOR -RMC14 (mrem/y per VCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D=DFL Uap exp(-X thc)QCl 4 X[0.11 Q L0.161 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is: RMCI4 =103 106 DFLC]4aj Ftr14 Q f Uam 0.111 fp exp(- ý'cl4t)Cl~aj C am L.16i.[1 -exp(_ kcl 4 tep & f exp(- lcl 4 tcb )] (7.33)XCl4tep J [l XC14tcb where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).Ffc14 = transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fp P = fraction of time cow spends on pasture, dimensionless.
'C1 4 =decay constant for carbon 14, s-1 (Table 6.2).t S = transport time from slaughter to consumer, s.tep = time pasture is exposed to deposition, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 58 Page 132 of 179 7.7.16 CARBON 14 -SRORED FEED-BEEF DOSE FACTOR -RMscl4 (mrem/y per gCi/M 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D = DFL Uap exp(-X ýthc)Qcl 4 x 0.11]Q 0. 16(7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the feed is stored (this term assumes that the feed is being eaten during the storage period) (Reference 10). The resulting dose factor is: 10 160.11 fex (- c4t,)R MSCI4 -10 10 DFLCi4aj FfC 1 4 Qf Uam I[_ .6 exp(-__exp(_ ,c_14_tcsf A_ _ exp(_ kcI 4 tcb )]S 1 tcsf )k[1 Cl 4 tcb where: 10 3 = conversion factor, g/kg.106 = conversion factor, pCi/lCi.DFLc1 4 aj = ingestion dose conversion factor for carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).FfC14 =transfer factor for carbon 14 from cow's feed to meat, d/kg (Table 6.2).Qf = cow's consumption rate, kg/d.Uam = meat ingestion rate for age group a, kg/y.0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m3.fs = fraction of time cow spends on stored feed, dimensionless.
Ac 1 4 =decay constant for carbon 14, s-1 (Table 6.2).ts = transport time from slaughter to consumer, s.tcsf = time between harvest of stored feed and consumption by animal, s.tcb = time for receptor to consume a whole beef, s.NOTE: Factors defined above which do not reference a table for their numerical values, are listed in Table 6.3.
SQN ODCM Revision 58 Page 133 of 179 7.7.17 CARBON 14 -FRESH LEAFY VEGETABLE DOSE FACTOR -RVFC14 (mrem/y per jiCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D =DFL U.p exp(-X 2thc)Qct 4 Q [0.16]Q 0. 16(7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. The resulting dose factor is: RVFC14 =101 106 DFLcI 4 aj [0.11] UFLa fL exp(-XCthc)
(7.35)where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLC14aj=
ingestion dose conversion factor for Carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m 3 UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y.fL = fraction of fresh leafy vegetables grown locally, dimensionless.
XC14 = decay constant for Carbon 14, s-1 (Table 6.2).thc = time between harvest of vegetables and their consumption and/or storage, s.NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.
SQN ODCM Revision 58 Page 134 of 179 7.7.18 CARBON 14-STORED VEGETABE DOSE FACTOR -Rvsc 1 4 (mrem/y per gCi/m 3)The general dose equation stated in Regulatory Guide 1.109 for calculating the annual dose from consuming foods containing atmospherically released radionuclides (Equation C-13) is: Dose(D) = Dose Conversion Factor(DFL)*Usage Rate(U)*Radionuclide Concentration in Media(C)For the vegetable pathway, Regulatory Guide 1.109 Equation C-9 is inserted into the above equation to yield the following:
D = DFL Uap exp(- thc)QC, 4 x [0.111 (-Q L0.161 (7.30)Since the dose equation in Sections 7.4 and 7.7.3 (Equations 7.9 and 7.14) contain the variables for the release rate (Q) and the dispersion factor (X/Q), the factors remaining in the above equation are defined as the dose factor. An additional decay term is added to account for the decay during the time the vegetables are stored (this term assumes that the vegetables are being eaten during the storage period) (Reference 10). The resulting dose factor is: R 1 10 106 DFLCi 4 aj [11] U fg { exp(-c4 t v )]}exp(-,C,4t hc) (7.36)Rvcl =0310 O~caa10.16 XCst.where: 103 = conversion factor, g/kg.106 = conversion factor, pCi/gCi.DFLC14aj=
ingestion dose conversion factor for Carbon 14 for age group a, organ j, mrem/pCi (Table 6.4).0.11 = the fraction of total plant mass that is natural carbon, dimensionless.
0.16 = is equal to the concentration of natural carbon in the atmosphere, in g/m 3 Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y.fg = fraction of stored vegetables grown locally, dimensionless.
XC14 = decay constant for Carbon 14, s-1 (Table 6.2).tsv = time between harvest of stored vegetables and their consumption and/or storage, s.thc = time between harvest of vegetables and their storage, s.
SQN ODCM Revision 58 Page 135 of 179 7.7.19 INHALATION DOSE FACTORS (mrem/y per giCi/m 3)Rli = DFAiao BRa 106 (7.37)where: DFAiao = inhalation dose conversion factor for nuclide i, age group a and organ o, mrem/pCi (Table 7.6).BRa = breathing rate for age group a, m 3/y (Table 6.3).1046 = conversion factor, pCi/[LCi.7.7.20 GROUND PLANE DOSE FACTORS (m 2-mrem/y per gCi/s)RGi = DFGi 0 1/ki 106 8760 [1 -exp(-kitb)]
(7.38)where: DFGio = dose conversion factor for standing on contaminated ground for nuclide i and organ o (total body and skin), mrem/hr per pCi/m 2 (Table 6.6).k.i = decay constant of nuclide i, s-1 (Table 6.2).106 = conversion factor, pCi/lCi.8760 = conversion factor, h/y.tb = time period over which the ground accumulation is evaluated, s (Table 6.3).
SQN ODCM Revision 58 Page 136 of 179 7.8 DISPERSION METHODOLOGY Dispersion factors are calculated for radioactive effluent releases using hourly average meteorological data consisting of wind speed and direction measurements at 10m and temperature measurements at 9m and 46m.A sector-average dispersion equation consistent with Regulatory Guide 1.111 is used. The dispersion model considers plume depletion (using information from Figure 7.4), and building wake effects. Terrain effects on dispersion are not considered.
Hourly average meteorological data are expressed as a joint-frequency distribution of wind speed, wind direction, and atmospheric stability.
A joint-frequency distribution for each quarter from 1986-1995 is used for calculations described in Section 7.2, 7.3, 7.4, and 7.5. A joint-frequency distribution using the actual hourly-average meteorological data is used for calculations described in Section 7.6.The wind speed classes that are used are as follows: Number 1 2 3 4 5 6 7 8 9 Ran-oe (m/s)<0.3 0.3-0.6 0.7-1.5 1.6-2.4 2.5-3.3 3.4-5.5 5.6-8.2 8.3-10.9>10.9 Midpoint (m/s)0.13 0.45 1.10 1.99 2.88 4.45 6.91 9.59 10.95 The stability classes that will be used are the standard A through G classifications.
The stability classes 1-7 will correspond to A=1, B=2 ..., G=7.7.8.1 AIR CONCENTRATION Air concentrations of nuclides at downwind locations are calculated using the following equation: 9 7 Xi = Y_ Y (2/7t)1/2 fAkQip_ exp(-Xi x/uj)j=l k=1 Ezk Uj (2nx/n)(7.39)where fjk Qi P= joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction.= release rate of radionuclide i, laCi/s.= fraction of radionuclide remaining in plume (Figure 7.4).
SQN ODCM Revision 58 Page 137 of 179 Ezk = vertical dispersion coefficient for stability class k which includes a building wake adjustment, o (ozk 2 + cA/t)1/2 , or (3)1/2 Gzk, whichever is smaller.where (Yzk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2).uj = midpoint value of wind speed class interval j, m/s.x = downwind distance, m.n = number of sectors, 16.Xi = radioactive decay coefficient of radionuclide i, s-1 2irx/n = sector width at point of interest, m.7.8.2 RELATIVE CONCENTRATION Relative concentrations of nuclides at downwind locations are calculated using the following equation: 97 X/Q = Y Y_ (2/7r)1/2 fik. (7.40)j=1 k=1 Y-zk Uj (2irx/n)where fik = joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction.Yzk = vertical dispersion coefficient for stability class k which includes a building wake adjustment,= (ozk 2 + cA/It)1/2 , or = (3)1/2 Gzk, whichever is smaller.where GAzk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2)u = midpoint value of wind speed class interval j, m/s.x = downwind distance, m.n = number of sectors, 16.2irx/n = sector width at point of interest, m.
SQN ODCM Revision 58 Page 138 of 179 7.8.3 RELATIVE DEPOSITION Relative deposition of nuclides at downwind locations is calculated using the following equation: 9 7 fjk DR D/Q = IX I_ -(7.41)j=1 k=1 (2nx/n)where fj k = joint relative frequency of occurrence of winds in windspeed class j and stability class k, blowing toward this exposure point, expressed as a fraction.DR = relative deposition rate, m-1 (from Figure 7.6).x = downwind distance, m.n = number of sectors, 16.21rx/n = sector width at point of interest, m.
SQN ODCM Revision 58 Page 139 of 179 Table 7.1 Sequoyah Maximum Quarterly XIQ (1999-2008)
Sorted by Quarter QUARTER 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 YEAR 1999 1999 1999 1999 2000 2000 2000 2000 2001 2001 2001 2001 2002 2002 2002 2002 2003 2003 2003 2003 2004 2004 2004 2004 2005 2005 2005 2005 2006 2006 2006 2006 2007 2007 2007 2007 2008 2008 2008 2008 MAXIMUM SECTOR SSW NW N NNW N N S SSW NW N N SSW N N N N N N N SSW NNW N S N N NW S SSW N N N SSW N N N SSW N N S SSW DISTANCE (METERS)1840 660 950 730 950 950 1570 1840 660 950 950 1840 950 950 950 950 950 950 950 1840 730 950 1570 950 950 660 1570 1840 950 950 950 1840 950 950 950 1840 950 950 1570 1840 Average XIQ(1999-2008)=
v/Q(10-6 S/M 3)5.10 6.08 6.48 9.75 6.08 6.68 6.32 7.36 5.10 6.95 6.40 8.85 5.12 5.85 7.06 6.56 4.46 6.83 6.54 5.23 4.74 7.96 6.47 7.44 4.79 8.47 5.92 5.23 5.26 4.91 5.97 6.22 4.94 6.21 6.14 5.81 4.38 5.37 5.81 4.68 6.14 x 106 SQN ODCM Revision 58 Page 140 of 179 Table 7.2 Sequoyah Maximum Quarterly D/Q (1999-2008)
Sorted by Quarter QUARTER YEAR MAXIMUM DISTANCE D/Q(108 1/M 2 1 1 1999 SSW 1840 1.13 2 1999 N 950 1.86 3 1999 N 950 1.38 4 1999 N 950 1.28 1 2000 N 950 1.33 2 2000 N 950 1.69 3 2000 N 950 1.29 4 2000 SSW 1840 1.23 1 2001 S 1570 1.13 2 2001 N 950 1.49 3 2001 N 950 1.86 4 2001 N 950 1.46 1 2002 N 950 1.04 2 2002 N 950 1.61 3 2002 N 950 2.02 4 2002 N 950 1.49 1 2003 N 950 0.95 2 2003 N 950 1.64 3 2003 N 950 1.64 4 2003 N 950 1.24 1 2004 SSW 1840 1.15 2 2004 N 950 2.24 3 2004 N 950 1.32 4 2004 N 950 1.64 1 2005 SSW 1840 1.09 2 2005 N 950 1.27 3 2005 N 950 1.48 4 2005 SSW 1840 1.20 1 2006 N 950 1.32 2 2006 N 950 1.24 3 2006 N 950 1.70 4 2006 SSW 1840 1.22 1 2007 N 950 1.27 2 2007 N 950 1.31 3 2007 N 950 1.31 4 2007 N 950 1.26 1 2008 N 950 1.39 2 2008 N 950 1.60 3 2008 N 950 1.41 4 2008 S 1570 0.98 Average D/Q(1999-2008)
= 1.40 x 10' SQN ODCM Revision 58 Page 141 of 179 Table 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES Kr-83m Kr-85m Kr-85 Kr-87 Kr-88 Kr-89 Kr-90 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Xe-137 Xe- 138 Ar-41 Submersion dose mrem/y per [pCi/m 3 DFBi DFSi 7.56E-02 ---1.17E+03 1.46E+03 1.61 E+01 1.34E+03 5.92E+03 9.73E+03 1.47E+04 2.37E+03 1.66E+04 1.01E+04 1.56E+04 7.29E+03 9.15E+01 4.76E+02 2.51 E+02 9.94E+02 2.94E+02 3.06E+02 3.12E+03 7.11E+02 1.81 E+03 1.86E+03 1.42E+03 1.22E+04 8.83E+03 4.13E+03 8.84E+03 2.69E+03 Air dose mrad/y per pCi/m3 DF0 DFpi 1.93E+01 2.88E+02 1.23E+03 1.97E+03 1.72E+01 1.95E+03 6.17E+03 1.03E+04 1.52E+04 2.93E+03 1.73E+04 1.06E+04 1.63E+04 7.83E+03 1.56E+02 1.11E+03 3.27E+02 1.48E+03 3.53E+02 1.05E+03 3.36E+03 7.39E+02 1.92E+03 2.46E+03 1.51E+03 1.27E+04 9.21 E+03 4.75E+03 9.30E+03 3.28E+03
Reference:
Regulatory Guide 1.109, Table B-1.
SQN ODCM Revision 58 Page 142 of 179 Table 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES Range of Midpoint of Sector Element Sector Element Unrestricted Area boundary -1 mile 0.8 mile 1 -2 miles 1.5 miles 2 -3 miles 2.5 miles 3 -4 miles 3.5 miles 4 -5 miles 4.5 miles 5 -10 miles 7.5 miles 10 -20 miles 15 miles 20 -30 miles 25 miles 30 -40 miles 35 miles 40 -50 miles 45 miles SQN ODCM Revision 58 Page 143 of 179 Table 7.5 POPULATION WITHIN EACH SECTOR ELEMENT Sector Midpoint (miles)0.8 1.5 2.5 3.5 4.5 7.5 15 25 35 45 N 20 41 213 129 66 1784 5453 3470 2610 11145 NNE 0 30 123 182 62 600 0628 4910 8250 10625 NE 0 0 67 67 94 581 2884 6998 7047 18080 ENE 0 11 24 222 300 773 4707 5747 29477 18679 E 0 70 11 191 137 918 7440 6808 5072 4129 ESE 0 118 113 194 137 1849 46521 5044 1896 3624 SE 0 179 322 168 205 1507 6005 5461 15641 3417 SSE 0 125 370 750 601 2347 13242 8596 34279 1648 S 0 67 143 229 811 3930 28008 26690 19642 11622 SSW 0 82 140 400 170 8927 96966 55597 21349 11978 SW 0 10 306 634 194 9787 94225 23455 11641 11109 WSW 20 190 642 1124 1669 19089 28405 4106 15081 9548 W 10 20 233 657 657 5225 1580 6350 5699 7707 WNW 10 30 365 598 598 2622 6540 4920 6699 2450 NW 50 80 292 569 336 2696 1410 1750 1217 15856 NNW 10 263 80 75 213 1610 471 3130 2835 5719 SQN ODCM Revision 58 Page 144 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 1 of 8)ADULT bone liver H-3 C-14 Na-24 P-32 Cr-51 Mn-54 Mn-56 Fe-55 Fe-59 Co-57 Co-58 Co-60 Ni-63 Ni-65 Cu-64 Zn-65 Zn-69 Zn-69m Br-82 Br-83 Br-84 Br-85 Rb-86 Rb-88 Rb-89 Sr-89 Sr-90 Sr-91 Sr-92 Y-90 Y-91m Y-91 Y-92 Y-93 Zr-95 Zr-97 Nb-95 Nb-97 Mo-99 Tc-99m Tc-101 Ru-103 Ru-105 Ru-106 Ag-110m 1.58E-07 2.27E-06 1.28E-06 1.65E-04 0.OOE+00 0.00E+00 0.00E+00 3.07E-06 1.47E-06 0.00E+00 0.00E+00 0.00E+00 5.40E-05 1.92E-10 0.00E+00 4.05E-06 4.23E-12 1.02E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 3.80E-05 1.24E-02 7.74E-09 8.43E-1 0 2.61E-07 3.26E-11 5.78E-05 1.29E-09 1.18E-08 1.34E-05 1.21E-08 1.76E-06 2.78E-1i1 0.OOE+00 1.29E-13 5.22E-15 1.91 E-07 9.88E-11 8.64E-06 1.35E-06 1.58E-07 4.26E-07 1.28E-06 9.64E-06 0.OOE+00 4.95E-06 1.55E-10 2.12E-06 3.47E-06 8.65E-08 1.98E-07 1.44E-06 3.93E-06 2.62E-i 1 1.83E-10 1.29E-05 8.14E-12 2.45E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.69E-05 4.84E-08 3.20E-08 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 4.30E-06 2.45E-09 9.77E-07 7.03E-12 1.51 E-08 3.64E-13 7.52E-15 0.OOE+00 0.OOE+00 0.OOE+00 1.25E-06 1.58E-07 4.26E-07 1.28E-06 6.26E-06 1.25E-08 7.87E-07 2.29E-11 4.93E-07 1.32E-06 8.39E-08 2.59E-07 1.85E-06 1.81E-06 1.14E-11 7.69E- 11 5.82E-06 5.65E-13 2.24E-10 1.69E-06 3.01 E-08 3.91 E-08 1.60E-09 7.37E-06 2.41 E-08 2.12E-08 1.09E-06 7.62E-04 3.13E-10 3.64E-i 1 7.01 E-09 1.27E-12 1.55E-06 3.77E-1 1 3.26E-10 2.91 E-06 1.13E-09 5.26E-07 2.56E-12 2.87E-09 4.63E-12 7.38E-14 8.23E-08 3.89E-1 1 1.09E-06 7.43E-07 body 1.58E-0 4.26E-0 1.28E-0O 0.OOE+0 7.44E-0 0.OOE+0 0.OOE+C 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+C 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+C 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+C 0.OOE+0 0.OOE+0 0.OOE+0 0.00E+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+O 0.OOE+0 0.OOE+O 0.OOE+O 0.OOE+0 0.OOE+O 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+0 0.OOE+O 0.OOE+O 0.OOE+O 0.OOE+O thyroid kidney lu 7 1.58E-07 1.58E-07 7 4.26E-07 4.26E-07 6 1.28E-06 1.28E-06 0 0.OOE+00 0.OOE+00 9 2.85E-09 1.80E-06 0 1.23E-06 1.75E-04 0 1.63E-10 1.18E-06)0 0.OOE+00 9.01E-06 0 0.OOE+00 1.27E-04 0 0.OOE+00 4.62E-05 0 0.OOE+00 1.16E-04 0 0.OOE+00 7.46E-04 0 0.OOE+00 2.23E-05 0 0.OOE+00 7.OOE-07 0 5.78E-10 8.48E-07 0 8.62E-06 1.08E-04 0 5.27E-12 1.15E-07 0 1.48E-09 2.38E-06 0 0.OOE+00 0.OOE+00 0 0.OOE+00 0.OOE+00 0 0.OOE+00 0.OOE+00 0 0.OOE+00 0.OOE+00 0 0.OOE+00 0.OOE+00)0 0.OOE+00 0.OOE+00'0 0.OOE+00 0.OOE+00'0 0.OOE+00 1.75E-04)0 0.OOE+00 1.20E-03)0 0.OOE+00 4.56E-06 0 0.OOE+00 2.06E-06)0 0.OOE+00 2.12E-05)0 0.OOE+00 2.40E-07)0 0.OOE+00 2.13E-04)0 0.OOE+00 1.96E-06)0 0.OOE+00 6.06E-06)0 6.77E-06 2.21E-04'0 3.71E-09 9.84E-06)0 9.67E-07 6.31E-05'0 8.18E-12 3.OOE-07 0 3.64E-08 1.14E-05'0 5.52E-12 9.55E-08 0 1.35E-13 4.99E-08'0 7.29E-07 6.31E-05 0 1.27E-10 1.37E-06 0 1.67E-05 1.17E-03 0 2.46E-06 5.79E-04 ng gi-Ili 1.58E-07 4.26E-07 1.28E-06 1.08E-05 4.15E-07 9.67E-06 2.53E-06 7.54E-07 2.35E-05 3.93E-06 1.33E-05 3.56E-05 1.67E-06 1.54E-06 6.12E-06 6.68E-06 2.04E-09 1.71E-05 1.30E-06 2.90E-08 2.05E-1 3 0.OOE+00 2.08E-06 4.18E-19 1.16E-21 4.37E-05 9.02E-05 2.39E-05 5.38E-06 6.32E-05 1.66E-10 4.81 E-05 9.19E-06 5.27E-05 1.88E-05 6.54E-05 1.30E-05 3.02E-08 3. 10 E-05 5.20E-07 1.36E-21 1.38E-05 6.02E-06 1.14E-04 3.78E-05 SQN ODCM Revision 58 Page 145 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 2 of 8)ADULT Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te-1 32 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 3.90E-06 6.67E-06 1 .16E-06 4.27E-07 1.58E-06 1.75E-10 1.22E-06 6.22E-12 8.74E-09 1.39E-12 3.25E-08 5.72E-07 3.15E-06 1.45E-07 1.08E-06 8.05E-08 3.35E-07 4.66E-05 4.88E-06 5.98E-05 4.14E-08 1.17E-10 4.88E-06 1.25E- 11 3.29E-12 4.30E-08 8.54E-1 1 2.49E-06 2.33E-08 4.29E-04 1.17E-06 3.76E-12 6.59E-07 1.06E-09 2.87E-08 liver 7.36E-08 7.44E-08 3.12E-08 1.98E-07 7.21 E-07 8.03E-1 1 5.84E-07 2.99E-12 5.45E-09 7.44E-1 3 2.69E-08 1.68E-06 4.47E-06 4.07E-07 1.85E-06 2.16E-07 8.73E-07 1.06E-04 1.83E-05 7.76E-05 7.76E-08 8.32E-14 6.13E-09 9.41E-15 3.38E-15 2.17E-08 3.88E-1 1 1.69E-06 1.72E-08 1.79E-04 4.69E-07 1.56E-12 7.62E-07 8.85E-1 0 2.82E-09 t body 1.55E-06 1.58E-06 7.03E-08 5.84E-08 1.96E-07 3.87E-1 1 1.98E-07 1.55E-12 3.63E-09 4.49E-1 3 2.02E-08 6.60E-07 2.56E-06 1.45E-07 5.65E-07 7.69E-08 3.21 E-07 9.1OE-05 1.38E-05 5.35E-05 4.05E-08 3.42E-12 3.21 E-07 4.20E-13 2.07E-13 5.73E-09 9.65E-12 1.91 E-07 1.91 E-09 2.30E-05 5.80E-08 1.91E-13 4.56E-08 3.1OE-10 1.55E-09 thyroid 9.44E-09 6.75E-09 2.59E-08 1.31E-07 4.11 E-07 1.32E-10 4.30E-07 4.87E-12 6.88E-09 1.17E-12 2.37E-08 1.42E-04 1.49E-03 1.43E-05 2.69E-04 3.73E-06 5.60E-05 O.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 0.OOE+00 0.OOE+00 O.OOE+00 1.55E-06 5.72E-06 6.37E-1 0 4.57E-06 2.34E-11 3.86E-08 5.46E-12 1.82E-07 2.61 E-06 7.66E-06 6.48E-07 3.23E-06 3.44E-07 1.39E-06 3.59E-05 1.07E-05 2.78E-05 6.OOE-08 7.78E-14 2.09E-09 8.75E-1 5 2.86E-1 5 0.OOE+00 0.OOE+00 7.83E-07 7.60E-09 1.06E-04 2.70E-07 8.81 E-13 4.45E-07 0.OOE+00 8.75E-09 lung 3.1 OE-04 2.18E-04 7.37E-05 3.92E-05 1.20E-04 8.14E-07 1.45E-04 2.42E-07 1.82E-05 1.74E-07 3.60E-05 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 1.22E-05 1.50E-06 9.40E-06 6.07E-09 4.70E-07 1.59E-04 2.42E-07 1.49E-07 1.70E-05 7.91 E-07 4.52E-05 9.97E-06 9.72E-04 3.51 E-05 1.27E-07 2.76E-05 3.63E-06 4.70E-06 gi-Ili 5.08E-05 1.26E-05 6.81 E-05 8.83E-06 1.87E-05 7.17E-06 4.79E-05 1.96E-08 6.95E-05 2.30E-09 6.37E-05 9.61 E-07 7.85E-07 5.08E-08 1.11E-06 1.26E-10 6.56E-07 1.30E-06 1.46E-06 1.05E-06 2.33E-13 1.12E-07 2.73E-05 1.45E-17 1.96E-26 5.73E-05 2.64E-07 1.50E-05 2.83E-05 1.02E-04 2.50E-05 2.69E-1 8 2.16E-05 1.94E-05 1.49E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-7.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 58 Page 146 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 3 of 8)TEEN bone liver t body thyroid kidney lung gi-Ili H-3 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 C-14 3.25E-06 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 Na-24 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 P-32 2.36E-04 1.37E-05 8.95E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.16E-05 Cr-51 O.OOE+00 O.OOE+00 1.69E-08 9.37E-09 3.84E-09 2.62E-06 3.75E-07 Mn-54 O.OOE+00 6.39E-06 1.05E-06 O.OOE+00 1.59E-06 2.48E-04 8.35E-06 Mn-56 O.OOE+00 2.12E-10 3.15E-11 O.OOE+00 2.24E-10 1.90E-06 7.18E-06 Fe-55 4.18E-06 2.98E-06 6.93E-07 O.OOE+00 O.OOE+00 1.55E-05 7.99E-07 Fe-59 1.99E-06 4.62E-06 1.79E-06 O.OOE+00 O.OOE+00 1.91E-04 2.23E-05 Co-57 O.OOE+00 1.18E-07 1.15E-07 O.OOE+00 O.OOE+00 7.33E-05 3.93E-06 Co-58 O.OOE+00 2.59E-07 3.47E-07 O.OOE+00 O.OOE+00 1.68E-04 1.19E-05 Co-60 O.OOE+00 1.89E-06 2.48E-06 O.OOE+00 O.OOE+00 1.09E-03 3.24E-05 Ni-63 7.25E-05 5.43E-06 2.47E-06 O.OOE+00 O.OOE+00 3.84E-05 1.77E-06 Ni-65 2.73E-10 3.66E-11 1.59E-11 O.OOE+00 O.OOE+00 1.17E-06 4.59E-06 Cu-64 O.OOE+00 2.54E-10 1.06E-10 O.OOE+00 8.01E-10 1.39E-06 7.68E-06 Zn-65 4.82E-06 1.67E-05 7.80E-06 O.OOE+00 1.08E-05 1.55E-04 5.83E-06 Zn-69 6.04E-12 1.15E-11 8.07E-13 O.OOE+00 7.53E-12 1.98E-07 3.56E-08 Zn-69m 1.44E-09 3.39E-09 3.11E-10 O.OOE+00 2.06E-09 3.92E-06 2.14E-05 Br-82 O.OOE+00 O.OOE+00 2.28E-06 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 4.30E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OQE+00 O.OOE+00 5.41E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.OOE+00 O.OOE+00 2.29E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 Q.OOE+00 2.38E-05 1.05E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.21E-06 Rb-88 O.OOE+00 6.82E-08 3.40E-08 O.OOE+00 O.OOE+00 O.OOE+00 3.65E-15 Rb-89 O.OQE+00 4.40E-08 2.91E-08 O.OOE+00 O.OOE+00 O.OOE+00 4.22E-17 Sr-89 5.43E-05 O.OQE+00 1.56E-06 O.OOE+00 O.OOE+00 3.02E-04 4.64E-05 Sr-90 1.35E-02 O.OOE+00 8.35E-04 O.OOE+00 O.OOE+00 2.06E-03 9.56E-05 Sr-91 1.1OE-08 O.OOE+00 4.39E-10 O.OOE+00 O.OQE+00 7.59E-06 3.24E-05 Sr-92 1.19E-09 O.OOE+00 5.08E-11 O.OOE+00 O.OOE+00 3.43E-06 1.49E-05 Y-90 3.73E-07 O.OOE+00 1.OOE-08 O.OOE+00 O.OQE+00 3.66E-05 6.99E-05 Y-91m 4.63E-11 O.OOE+00 1.77E-12 O.OOE+00 O.OOE+00 4.OOE-07 3.77E-09 Y-91 8.26E-05 O.OE+00 2.21E-06 O.OOE+00 O.OOE+00 3.67E-04 5.11E-05 Y-92 1.84E-09 O.OOE+00 5.36E-11 O.OOE+00 O.OOE+00 3.35E-06 2.06E-05 Y-93 1.69E-08 O.OOE+00 4.65E-10 O.OOE+00 O.OOE+00 1.04E-05 7.24E-05 Zr-95 1.82E-05 5.73E-06 3.94E-06 O.OOE+00 8.42E-06 3.36E-04 1.86E-05 Zr-97 1.72E-08 3.40E-09 1.57E-09 O.OOE+00 5.15E-09 1.62E-05 7.88E-05 Nb-95 2.32E-06 1.29E-06 7.08E-07 O.OOE+00 1.25E-06 9.39E-05 1.21E-05 Nb-97 3.92E-11 9.72E-12 3.55E-12 Q.OOE+00 1.14E-11 4.91E-07 2.71E-07 Mo-99 O.OOE+00 2.11E-08 4.03E-09 O.OOE+00 5.14E-08 1.92E-05 3.36E-05 Tc-99m 1.73E-13 4.83E-13 6.24E-12 O.OOE+00 7.20E-12 1.44E-07 7.66E-07 Tc-101 7.40E-15 1.05E-14 1.03E-13 O.OOE+00 1.90E-13 8.34E-08 1.09E-16 Ru-103 2.63E-07 O.OOE+00 7.70E-07 O.OOE+00 9.29E-07 9.79E-05 1.36E-05 Ru-105 1.40E-10 O.OOE+00 5.42E-11 O.OOE+00 1.76E-10 2.27E-06 1.13E-05 Ru-106 1.23E-05 O.OOE+00 1.55E-06 O.OOE+00 2.38E-05 2.01E-03 1.20E-04 Ag-110m 1.73E-06 1.64E-06 9.99E-07 O.OOE+00 3.13E-06 8.44E-04 3.41E-05 SQN ODCM Revision 58 Page 147 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 4 of 8)TEEN Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te- 131 Te- 132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 5.38E-06 9.23E-06 1.66E-06 6.1 OE-07 2.25E-06 2.51 E-10 1.74E-06 8.87E-12 1.23E-08 1.97E-12 4.50E-08 7.80E-07 4.43E-06 1.99E-07 1.52E-06 1.11E-07 4.62E-07 6.28E-05 6.44E-06 8.38E-05 5.82E-08 1.67E-10 6.84E-06 1.78E- 11 4.62E-12 5.99E-08 1.20E-10 3.55E-06 3.32E-08 6.11E-04 1.67E-06 5.37E-12 9.83E-07 1.50E-09 4.23E-08 liver 9.92E-08 1.01E-07 4.42E-08 2.80E-07 1.02E-06 1.14E-10 8.23E-07 4.22E-12 7.51 E-09 1.04E-12 3.63E-08 2.24E-06 6.14E-06 5.47E-07 2.56E-06 2.90E-07 1.18E-06 1.41 E-04 2.42E-05 1.06E-04 1.07E-07 1.18E-13 8.38E-09 1.32E-14 4.63E-1 5 2.95E-08 5.31 E-11 2.37E-06 2.42E-08 2.53E-04 6.64E-07 2.20E-12 1.07E-06 1.22E-09 3.99E-09 t body 2.1OE-06 2.15E-06 9.99E-08 8.34E-08 2.73E-07 5.52E-1 1 2.81 E-07 2.20E-12 5.03E-09 6.30E-13 2.74E-08 8.96E-07 3.30E-06 1.97E-07 7.78E-07 1.05E-07 4.36E-07 6.86E-05 1.71 E-05 3.89E-05 5.58E-08 4.87E-12 4.40E-07 5.93E-13 2.84E-1 3 7.82E-09 1.32E- 11 2.71 E-07 2.70E-09 3.28E-05 8.28E-08 2.72E-13 6.41 E-08 4.29E-1 0 2.21 E-09 thyroid 1.22E-08 8.80E-09 3.45E-08 1.75E-07 5.48E-07 1.77E-10 5.72E-07 6.48E-12 9.06E-09 1.55E-12 3.07E-08 1.86E-04 1.83E-03 1.89E-05 3.65E-04 4.94E-06 7.76E-05 O.00E+00 O.OOE+00 O.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 kidney 0.00E+00 0.00E+00 0.00E+00 0.00E+00 8.17E-06 9.10E-10 6.49E-06 3.32E-1 1 5.49E-08 7.72E-12 2.44E-07 3.44E-06 1.05E-05 8.65E-07 4.49E-06 4.58E-07 1.86E-06 4.69E-05 1.38E-05 3.80E-05 8.28E-08 1.11E-13 2.85E-09 1.23E-14 3.92E-1 5 0.OOE+00 0.OOE+00 1.11E-06 1.08E-08 1.51 E-04 3.86E-07 1.26E-12 6.28E-07 0.OOE+00 1.25E-08 lung 4.81 E-04 3.42E-04 1.26E-04 6.70E-05 2.07E-04 1.40E-06 2.47E-04 4.12E-07 2.97E-05 2.92E-07 5.61 E-05 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 1.83E-05 2.22E-06 1.51 E-05 9.84E-09 8.08E-07 2.54E-04 4.11E-07 2.39E-07 2.68E-05 1.27E-06 7.67E-05 1.63E-05 1.67E-03 6.04E-05 2.19E-07 4.65E-05 5.92E-06 8.11 E-06 gi-Ili 4.98E-05 1.24E-05 7.29E-05 9.38E-06 1.99E-05 1.01 E-05 5.06E-05 2.02E-07 7.76E-05 1.89E-09 5.79E-05 1.14E-06 8.11 E-07 1.59E-07 1.29E-06 2.55E-09 8.69E-07 1.22E-06 1.36E-06 1.06E-06 3.38E-1 1 8.06E-07 2.86E-05 9.33E-14 5.99E-20 6.09E-05 1.50E-06 1.58E-05 3.19E-05 1.08E-04 2.67E-05 2.94E-14 2.28E-05 2.21 E-05 1.65E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-8.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-1 24 and Sb-125 are from NUREG-0172 Agae Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 58 Page 148 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 5 of 8)CHILD bone liver t body thyroid kidney lung gi-Ili H-3 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 C-14 9.70E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 Na-24 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 P-32 7.04E-04 3.09E-05 2.67E-05 0.OOE+00 0.OOE+00 O.OOE+00 1.14E-05 Cr-51 0.0OE+00 0.OOE+00 4.17E-08 2.31E-08 6.57E-09 4.59E-06 2.93E-07 Mn-54 0.OOE+00 1.16E-05 2.57E-06 0.OOE+00 2.71E-06 4.26E-04 6.19E-06 Mn-56 0.OOE+00 4.48E-10 8.43E-11 0.OOE+00 4.52E-10 3.55E-06 3.33E-05 Fe-55 1.28E-05 6.80E-06 2.1OE-06 0.OOE+00 0.OOE+00 3.OOE-05 7.75E-07 Fe-59 5.59E-06 9.04E-06 4.51 E-06 0.OOE+00 0.OOE+00 3.43E-04 1.91 E-05 Co-57 0.OOE+00 2.44E-07 2.88E-07 O.OOE+00 0.OOE+00 1.37E-04 3.58E-06 Co-58 0.OOE+00 4.79E-07 8.55E-07 0.OOE+00 0.OOE+00 2.99E-04 9.29E-06 Co-60 0.OOE+00 3.55E-06 6.12E-06 0.OOE+00 0.O0E+00 1.91E-03 2.60E-05 Ni-63 2.22E-04 1.25E-05 7.56E-06 0.OOE+00 0.OOE+00 7.43E-05 1.71 E-06 Ni-65 8.08E-10 7.99E-11 4.44E-11 0.OOE+00 0.OOE+00 2.21E-06 2.27E-05 Cu-64 O.OOE+00 5.39E-10 2.90E-10 0.OOE+00 1.63E-09 2.59E-06 9.92E-06 Zn-65 1.15E-05 3.06E-05 1.90E-05 0.OOE+00 1.93E-05 2.69E-04 4.41E-06 Zn-69 1.81E-11 2.61E-11 2.41E-12 0.OOE+00 1.58E-11 3.84E-07 2.75E-06 Zn-69m 4.26E-09 7.28E-09 8.59E-10 0.OOE+00 4.22E-09 7.36E-06 2.71E-05 Br-82 O.OOE+00 0.OOE+00 5.66E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 1.28E-07 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 Br-84 0.OOE+00 O.OOE+00 1.48E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 O.OOE+00 6.84E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rb-86 0.OOE+00 5.36E-05 3.09E-05 0.OOE+00 O.OOE+00 0.OOE+00 2.16E-06 Rb-88 0.OOE+00 1.52E-07 9.90E-08 0.OOE+00 0.OOE+00 0.OOE+00 4.66E-09 Rb-89 0.OOE+00 9.33E-08 7.83E-08 0.OOE+00 0.OOE+00 0.OOE+00 5.11E-10 Sr-89 1.62E-04 0.OOE+00 4.66E-06 0.OOE+00 O.OOE+00 5.83E-04 4.52E-05 Sr-90 2.73E-02 O.OOE+00 1.74E-03 0.OOE+00 0.OOE+00 3.99E-03 9.28E-05 Sr-91 3.28E-08 0.OOE+00 1.24E-09 0.OOE+00 0.OOE+00 1.44E-05 4.70E-05 Sr-92 3.54E-09 O.OOE+00 1.42E-10 0.OOE+00 0.OOE+00 6.49E-06 6.55E-05 Y-90 1.11E-06 0.OOE+00 2.99E-08 0.OOE+00 0.OOE+00 7.07E-05 7.24E-05 Y-91m 1.37E-10 0.OOE+00 4.98E-12 0.OOE+00 0.OOE+00 7.60E-07 4.64E-07 Y-91 2.47E-04 0.OOE+00 6.59E-06 O.OOE+00 0.OOE+00 7.1OE-04 4.97E-05 Y-92 5.50E-09 0.OOE+00 1.57E-10 0.OOE+00 0.OOE+00 6.46E-06 6.46E-05 Y-93 5.04E-08 0.OOE+00 1.38E-09 0.OOE+00 0.OOE+00 2.01 E-05 1.05E-04 Zr-95 5.13E-05 1.13E-05 1.OOE-05 O.OOE+00 1.61E-05 6.03E-04 1.65E-05 Zr-97 5.07E-08 7.34E-09 4.32E-09 0.OOE+00 1.05E-08 3.06E-05 9.49E-05 Nb-95 6.35E-06 2.48E-06 1.77E-06 0.OOE+00 2.33E-06 1.66E-04 1.OOE-05 Nb-97 1.16E-10 2.08E-11 9.74E-12 O.OOE+00 2.31E-11 9.23E-07 7.52E-06 Mo-99 0.OOE+00 4.66E-08 1.15E-08 0.OOE+00 1.06E-07 3.66E-05 3.42E-05 Tc-99m 4.81E-13 9.41E-13 1.56E-11 O.OOE+00 1.37E-11 2.57E-07 1.30E-06 Tc-101 2.19E-14 2.30E-14 2.91E-13 O.OOE+00 3.92E-13 1.58E-07 4.41E-09 Ru-103 7.55E-07 0.OOE+00 2.90E-07 0.OOE+00 1.90E-06 1.79E-04 1.21E-05 Ru-105 4.13E-10 0.OOE+00 1.50E-10 0.OOE+00 3.63E-10 4.30E-06 2.69E-05 Ru-106 3.68E-05 0.OOE+00 4.57E-06 0.OOE+00 4.97E-05 3.87E-03 1.16E-04 Ag-110m 4.56E-06 3.08E-06 2.47E-06 O.OOE+00 5.74E-06 1.48E-03 2.71E-05 SQN ODCM Revision 58 Page 149 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 6 of 8)CHILD Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-131m Te-131 Te- 132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 1.55E-05 2.66E-05 4.95E-06 1.82E-06 6.72E-06 7.49E-10 5.19E-06 2.64E-1 1 3.63E-08 5.87E-12 1.30E-07 2.21 E-06 1.30E-05 5.72E-07 4.48E-06 3.17E-07 1.33E-06 1.76E-04 1.76E-05 2.45E-04 1.71 E-07 4.98E-10 2.00E-05 5.29E-1 1 1.35E-1 1 1.74E-07 3.50E-10 1.06E-05 9.89E-08 1.83E-03 4.99E-06 1.61 E-11 2.92E-06 4.41 E-09 1.26E-07 liver 2.OOE-07 2.05E-07 9.94E-08 6.29E-07 2.31 E-06 2.57E-10 1.85E-06 9.45E-12 1.60E-08 2.28E-12 7.36E-08 4.43E-06 1.30E-05 1.10E-06 5.49E-06 5.84E-07 2.36E-06 2.74E-04 4.62E-05 2.23E-04 2.27E-07 2.66E-13 1.75E-08 2.95E-14 9.73E-1 5 6.08E-08 1.11E-10 5.28E-06 5.37E-08 5.72E-04 1.50E-06 4.99E-12 2.36E-06 2.61 E-09 9.04E-09 t body 5.41 E-06 5.59E-06 2.95E-07 2.47E-07 8.16E-07 1.65E-10 8.22E-07 6.44E-12 1.37E-08 1.78E-12 7.12E-08 2.28E-06 7.37E-06 5.07E-07 2.08E-06 2.69E-07 1.12E-06 6.07E-05 3.14E-05 3.47E-05 1.50E-07 1.45E-1 1 1.17E-06 1.72E-12 7.54E- 13 2.04E-08 3.49E-11 7.83E-07 7.77E-09 9.77E-05 2.47E-07 8.10E-13 1.84E-07 1.17E-09 6.35E-09 thyroid 3.41 E-08 2.46E-08 1.03E-07 5.20E-07 1.64E-06 5.30E-10 1.71 E-06 1.93E-11 2.64E-08 4.59E-12 8.58E-08 4.99E-04 4.39E-03 5.23E-05 1.04E-03 1.37E-05 2.14E-04 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.00E+00 kidney 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 1.72E-05 1.91 E-09 1.36E-05 6.94E-1 1 1.08E-07 1.59E-11 4.79E-07 6.61 E-06 2.13E-05 1.69E-06 9.13E-06 8.92E-07 3.62E-06 8.93E-05 2.58E-05 7.63E-05 1.68E-07 2.33E-13 5.71 E-09 2.56E-14 7.87E-15 0.OOE+00 0.OOE+00 2.31 E-06 2.26E-08 3.17E-04 8.11 E-07 2.64E-12 1.30E-06 O.OOE+00 2.63E-08 lung 8.76E-04 6.27E-04 2.43E-04 1.29E-04 4.OOE-04 2.71 E-06 4.76E-04 7.93E-07 5.56E-05 5.55E-07 1.02E-04 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 3.27E-05 3.93E-06 2.81 E-05 1.84E-08 1.56E-06 4.71 E-04 7.89E-07 4.44E-07 4.94E-05 2.35E-06 1.47E-04 3.12E-05 3.23E-03 1.17E-04 4.23E-07 8.87E-05 1.11E-05 1.57E-05 gi-Ili 4.43E-05 1.09E-05 7.17E-05 9.13E-06 1.93E-05 1.52E-05 4.91 E-05 6.89E-06 8.32E-05 3.60E-07 3.72E-05 1.38E-06 7.68E-07 8.65E-07 1.48E-06 2.58E-07 1.20E-06 1.04E-06 1.13E-06 9.78E-07 7.29E-08 1.56E-05 2.75E-05 7.44E-08 7.41E-10 6.10E-05 2.05E-05 1.53E-05 3.44E-05 1.05E-04 2.63E-05 5.32E-08 2.22E-05 2.46E-05 1.73E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-9.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-1 24 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 58 Page 150 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 7 of 8)INFANT bone liver t body thyroid kidney lung gi-Ili H-3 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 C-14 1.89E-05 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 Na-24 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 P-32 1.45E-03 8.03E+05 5.53E-05 0.OOE+00 0.OOE+00 0.OOE+00 1.15E-05 Cr-51 0.OOE+00 0.OOE+00 6.39E-08 4.11E-08 9.45E-09 9.17E-06 2.55E-07 Mn-54 0.OOE+00 1.81E-05 3.56E-06 0.OOE+00 3.56E-06 7.14E-04 5.04E-06 Mn-56 0.OOE+00 1.1OE-09 1.58E-10 0.OOE+00 7.86E-10 8.95E-06 5.12E-05 Fe-55 1.41E-05 8.39E-06 2.38E-06 0.OOE+00 0.OOE+00 6.21E-05 7.82E-07 Fe-59 9.69E-06 1.68E-05 6.77E-06 0.OOE+00 O.OOE+00 7.25E-04 1.77E-05 Co-57 0.OOE+00 4.65E-07 4.58E-07 O.OOE+00 O.OOE+00 2.71E-04 3.47E-06 Co-58 0.OOE+00 8.71E-07 1.30E-06 0.OOE+00 0.OOE+00 5.55E-04 7.95E-06 Co-60 0.OOE+00 5.73E-06 8.41E-06 O.OOE+00 O.OOE+00 3.22E-03 2.28E-05 Ni-63 2.42E-04 1.46E-05 8.29E-06 0.OOE+00 0.OOE+00 1.49E-04 1.73E-06 Ni-65 1.71E-09 2.03E-10 8.79E-11 0.OOE+00 0.OOE+00 5.80E-06 3.58E-05 Cu-64 0.OOE+00 1.34E-09 5.53E-10 0.OOE+00 2.84E-09 6.64E-06 1.07E-05 Zn-65 1.38E-05 4.47E-05 2.22E-05 O.OOE+00 2.32E-05 4.62E-04 3.67E-05 Zn-69 3.85E-11 6.91E-11 5.13E-12 0.OOE+00 2.87E-11 1.05E-06 9.44E-06 Zn-69m 8.98E-09 1.84E-08 1.67E-09 O.OOE+00 7.45E-09 1.91E-05 2.92E-05 Br-82 0.OOE+00 O.OOE+00 9.49E-06 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-83 0.OOE+00 O.OOE+00 2.72E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-84 0.OOE+00 0.OOE+00 2.86E-07 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 0.OOE+00 1.46E-08 0.OOE+00 0.OOE+00 0.OOE+0O 0.OOE+00 Rb-86 0.OOE+00 1.36E-04 6.30E-05 0.OOE+00 0.OOE+00 0.OOE+00 2.17E-06 Rb-88 0.OOE+00 3.98E-07 2.05E-07 0.OOE+00 0.OOE+00 0.OOE+00 2.42E-07 Rb-89 0.OOE+00 2.29E-07 1.47E-07 0.OOE+00 0.OOE+00 0.OOE+00 4.87E-08 Sr-89 2.84E-04 0.OOE+00 8.15E-06 0.OOE+00 0.OOE+00 1.45E-03 4.57E-05 Sr-90 2.92E-02 0.OOE+00 1.85E-03 O.OOE+00 0.OOE+00 8.03E-03 9.36E-05 Sr-91 6.83E-08 0.OOE+00 2.47E-09 0.OOE+00 0.OOE+00 3.76E-05 5.24E-05 Sr-92 7.50E-09 0.OOE+00 2.79E-10 0.OOE+00 0.OOE+00 1.70E-05 1.OOE-04 Y-90 2.35E-06 0.OOE+00 6.30E-08 0.OOE+00 0.OOE+00 1.92E-04 7.43E-05 Y-91m 2.91E-10 0.OOE+00 9.90E-12 0.OOE+00 0.OOE+00 1.99E-06 1.68E-06 Y-91 4.20E-04 O.OOE+00 1.12E-05 0.OOE+00 0.OOE+00 1.75E-03 5.02E-05 Y-92 1.17E-08 O.OOE+00 3.29E-10 0.OOE+00 0.OOE+00 1.75E-05 9.04E-05 Y-93 1.07E-07 0.OOE+00 2.91E-09 O.OOE+00 O.OOE+00 5.46E-05 1.19E-04 Zr-95 8.24E-05 1.99E-05 1.45E-05 O.OOE+00 2.22E-05 1.25E-03 1.55E-05 Zr-97 1.07E-07 1.83E-08 8.36E-09 O.OOE+00 1.85E-08 7.88E-05 1.00E-04 Nb-95 1.12E-05 4.59E-06 2.70E-06 0.OOE+00 3.37E-06 3.42E-04 9.05E-06 Nb-97 2.44E-10 5.21E-11 1.88E-11 0.OOE+00 4.07E-11 2.37E-06 1.92E-05 Mo-99 0.OOE+00 1.18E-07 2.31E-08 0.OOE+00 1.89E-07 9.63E-05 3.48E-05 Tc-99m 9.98E-13 2.06E-12 2.66E-11 0.OOE+00 2.22E-11 5.79E-07 1.45E-06 Tc-101 4.65E-14 5.88E-14 5.80E-13 O.OOE+00 6.99E-13 4.17E-07 6.03E-07 Ru-103 1.44E-06 0.OOE+00 4.85E-07 0.OOE+00 3.03E-06 3.94E-04 1.15E-05 Ru-105 8.74E-10 0.OOE+00 2.93E-10 0.OOE+00 6.42E-10 1.12E-05 3.46E-05 Ru-106 6.20E-05 0.OOE+00 7.77E-06 0.OOE+00 7.61E-05 8.26E-03 1.17E-04 Ag-110m 7.13E-06 5.16E-06 3.57E-06 0.OOE+00 7.80E-06 2.62E-03 2.36E-05 SQN ODCM Revision 58 Page 151 of 179 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled)(Page 8 of 8)INFANT Sb-124 Sb-125 Sn-125 Te-125m Te-127m Te-127 Te-129m Te-129 Te-1 31 m Te- 131 Te- 132 1-130 1-131 1-132 1-133 1-134 1-135 Cs-134 Cs-136 Cs-137 Cs-138 Ba-139 Ba-140 Ba-141 Ba-142 La-140 La-142 Ce-141 Ce-143 Ce-144 Pr-143 Pr-144 Nd-147 W-187 Np-239 bone 2.71 E-05 3.69E-05 1.01E-05 3.40E-06 1.19E-05 1.59E-09 1.01 E-05 5.63E-11 7.62E-08 1.24E-11 2.66E-07 4.54E-06 2.71 E-05 1.21 E-06 9.46E-06 6.58E-07 2.76E-06 2.83E-04 3.45E-05 3.92E-04 3.61 E-07 1.06E-09 4.OOE-05 1.12E-10 2.84E-1 1 3.61 E-07 7.36E-10 1.98E-05 2.09E-07 2.28E-03 1.OOE-05 3.42E-1 1 5.67E-06 9.26E-09 2.65E-07 liver 3.97E-07 3.41 E-07 2.51 E-07 1.42E-06 4.93E-06 6.81 E-10 4.35E-06 2.48E-1 1 3.93E-08 5.87E-12 1.69E-07 9.91 E-06 3.17E-05 2.53E-06 1.37E-05 1.34E-06 5.43E-06 5.02E-04 9.61 E-05 4.37E-04 5.58E-07 7.03E-13 4.OOE-08 7.70E-14 2.36E-14 1.43E-07 2.69E-10 1.19E-05 1.38E-07 8.65E-04 3.74E-06 1.32E-1 1 5.81 E-06 6.44E-09 2.37E-08 t body 8.56E-06 7.78E-06 6.OOE-07 4.70E-07 1.48E-06 3.49E-10 1.59E-06 1.34E-11 2.59E-08 3.57E-12 1.26E-07 3.98E-06 1.40E-05 8.99E-07 4.OOE-06 4.75E-07 1.98E-06 5.32E-05 3.78E-05 3.25E-05 2.84E-07 3.07E-1 1 2.07E-06 3.55E-12 1.40E-12 3.68E-08 6.46E-1 1 1.42E-06 1.58E-08 1.26E-04 4.99E-07 1.72E-12 3.57E-07 2.23E-09 1.34E-08 thyroid 7.18E-08 4.45E-08 2.47E-07 1.16E-06 3.48E-06 1.32E-09 3.91 E-06 4.82E-11 6.38E-08 1.13E-11 1.99E-07 1.14E-03 1.06E-02 1.21 E-04 2.54E-03 3.18E-05 4.97E-04 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 kidney 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 2.68E-05 3.47E-09 2.27E-05 1.25E-10 1.89E-07 2.85E-1 1 7.39E-07 1.09E-05 3.70E-05 2.82E-06 1.60E-05 1.49E-06 6.05E-06 1.36E-04 4.03E-05 1.23E-04 2.93E-07 4.23E-1 3 9.59E-09 4.64E-14 1.36E-14 0.OOE+00 0.OOE+00 3.75E-06 4.03E-08 3.84E-04 1.41 E-06 4.80E-12 2.25E-06 0.OOE+00 4.73E-08 lung 1.89E-03 1.17E-03 6.43E-04 3.19E-04 9.37E-04 7.39E-06 1.20E-03 2.14E-06 1.42E-04 1.47E-06 2.43E-04 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 5.69E-05 8.40E-06 5.09E-05 4.67E-08 4.25E-06 1.14E-03 2.12E-06 1.11E-06 1.20E-04 5.87E-06 3.69E-04 8.30E-05 7.03E-03 3.09E-04 1.15E-06 2.30E-04 2.83E-05 4.25E-05 gi-Ili 4.22E-05 1.05E-05 7.26E-05 9.22E-06 1.95E-05 1.74E-05 4.93E-05 1.88E-05 8.51 E-05 5.87E-06 3.15E-05 1.42E-06 7.56E-07 1.36E-06 1.54E-06 9.21 E-07 1.31 E-06 9.53E-07 1.02E-06 9.53E-07 6.26E-07 3.64E-05 2.74E-05 3.39E-06 4.95E-07 6.06E-05 4.25E-05 1.54E-05 3.55E-05 1.06E-04 2.66E-05 3.06E-06 2.23E-05 2.54E-05 1.78E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.
Reference:
Regulatory Guide 1.109, Table E-10.Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-1 24 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.
SQN ODCM Revision 58 Page 152 of 179 Figure 7.1 GASEOUS EFFLUENT RELEASE POINTS Service Building Vent 1,2-RE-90-99 1,2-RE-90-119 oFt Mac~hine Shops Office and Genil Area O-RE-90-1 32 FGeneral ýArea Spaces--Ch~emistry Lab Titration Room SERVICE BUILDING TURBINE BUILDING AUXILIARY SHIELD BUILDING BUILDING SQN ODCM Revision 58 Page 153 of 179 Shield Building Condenser Auxiliary Vent cods Building 1,E-40OI Service Vacuum Vent Building Exhaust Vent 0-RE-40-101 1.2-R1M10-130, 43 Ct" Upe Containment X 0 Vn-To n S- N -nuu wauu Ean T-,-E-09 M 0 Upper Containment 1-RE-E0-132 U) m Shops SERVICE TURBINE AUI- IR SIL Office and tien'i Area Control Area RCA Access 0as Control fl itly Area TankReco Chemistry2 Lab ~ t U,, a (I of )E) I Titration M a. 0Lwer Containment Roo X ~~ Annulus Vacuum Fans L<jm mo (2 per unit)SERVICE TURBINE AUXILIARY SHIELD BUILDING BUILDING BUILDING BUILDING SQN ODCM Revision 58 Page 154 of 179 Figure 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL)(All Vents Are Considered Ground Level)Shield Building Vent I l.2-RE-9O-,OO SQN ODCM Revision 58 Page 155 of 179 Figure 7.3 GASEOUS RADWASTE TREATMENT SYSTEM (All Vents Are Considered Ground Level)unt COT UiIOT Y Taj.Tf SQN ODCM Revision 58 Page 156 of 179 Figure 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES (All Stability Classes)I 0 ____________
~ .-.-.----.---.-----.
____ 11111111 I IiII~IiIt-
---...~1 Ii' -4.... II 0.7 I I I liii 1111111 0.j I 1111111 I iii'~i~ii______ II II..............L.....I
$ IIfl II 111111 IlIllIlIl 111111111 I 1-* II liii I.a' 2W 0 a , 1.0 10.0 Pu,.4 ThvF..L =:kw= Oa.06 TERM= a SQN ODCM Revision 58 Page 157 of 179 Figure 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME I -Ln w, w-I i I Fg3 it/ I ~ 1 II ,I I I I V I )3 3 1 /I I3 33 I I1 1 1 I LL / I H IM~2L.........
iiiiii~I Iii HIM 1001___I ti II;I1 1.0 10 Verd=I Stand2rd Deyizton of MzterainJ 2I 2trn Q..ecers denote Pwz.quiO Stbi~ty Class)
SQN ODCM Revision 58 Page 158 of 179 Figure 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES (All Stability Classes)C-" C,-w__11111 I ilil I llt!IH I I illil I I I I E 111111 III}I I 111M I I I ý111 I.i~o c.0.1 1.0 )1Uu PLUME~ -i~- 01-77kNCa NLCOM7FRS 100.0 2co.0 R=M D*P=b= E:r Q---TS-Jý P-d-- (Aj SL-93'hY C--)
SQN ODCM Revision 58 Page 159 of 179 SECTION 8.0 TOTAL DOSE SQN ODCM Revision 58 Page 160 of 179 SECTION 8.0 TOTAL DOSE 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES -TOTAL REPORTED DOSE To determine compliance with 40 CFR 190 as required in ODCM Administrative Control 5.2, the annual dose contributions to the maximum individual from SQN radioactive effluents and all other nearby uranium fuel cycle sources will be considered.
The annual dose to the maximum individual will be conservatively estimated by first, summing the quarterly total body air submersion dose, the quarterly critical organ dose from gaseous effluents, the quarterly total body dose from liquid effluents, the quarterly critical organ dose from liquid effluents, and the direct radiation monitoring program, and then taking the sum for each quarter and summing over the four quarters.
The table below represents the above verbal description and relative values: First Second Third Fourth Dose Quarter Quarter Quarter Quarter Total Body or any Organ (except thyroid)Total body air submersion 9.79E-04 9.OOE-04 1.65E-03 4.27E-04 Critical organ dose (air) 9.48E-03 9.40E-03 3.77E-03 9.37E-03 Total body dose (liquid) 4.8E-03 2.1E-02 3.8E-02 6.5E-03 Maximum organ dose (liquid) 5.8E-03 2.6E-02 5.0E-02 2.OE-02 Direct Radiation Dose 0.0E-00 0.0E-00 0.0E-00 0.OOE-00 Total 2.1E-02 5.7E-02 9.3E-02 3.6E-02 Cumulative Total Dose (Total body or any other organ) mrem 2.1E-01 Annual Dose Limit (mrero) 2.50E+01 Percent of Limit <1%
SQN ODCM Revision 58 Page 161 of 179 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM SQN ODCM Revision 58 Page 162 of 179 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM 9.1 MONITORING PROGRAM An environmental radiological monitoring program shall be conducted in accordance with ODCM Control 1.3.1.The monitoring program described in Tables 9.1, 9.2, and 9.3, and in Figures 9.1, 9.2 and 9.3 shall be conducted.
Results of this program shall be reported in accordance with ODCM Administrative Control 5.1.The atmospheric environmental radiological monitoring program shall consist of monitoring stations from which samples of air particulates and atmospheric radioiodine shall be collected.
The terrestrial monitoring program shall consist of the collection of milk, soil, ground water, drinking water, and food crops. In addition, direct gamma radiation levels will be measured in the vicinity of the plant.The reservoir sampling program shall consist of the collection of samples of surface water, sediment, clams, and fish.Deviations are permitted from the required sampling schedule if specimens are unobtainable due to hazardous conditions, sample unavailability, or to malfunction of sampling equipment.
If the latter, every effort shall be made to complete corrective action prior to the end of the next sampling period.9.2 DETECTION CAPABILITIES Analytical techniques shall be such that the detection capabilities listed in Table 2.3-3 are achieved.9.3 LAND USE CENSUS A land use survey shall be conducted in accordance with Control 1.3.2. The results of the survey shall be reported in the Annual Radiological Environmental Operating Report.9.4 INTERLABORATORY COMPARISON PROGRAM Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the NRC. A summary of the results obtained in the intercomparison shall be included in the Annual Radiological Environmental Operating Report (or the EPA program code designation may be provided).
If analyses are not performed as required corrective actions taken to prevent a recurrence shall be reported in the Annual Radiological Environmental Operating Report.
SQN ODCM Revision 58 Page 163 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 4)Exposure Pathway and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
AIRBORNE Particulates 4 samples from locations (in different sectors) at or near the site boundary (LM-2,3,4,and 5)4 samples from communities approximately 6-10 miles distance from the plant.(PM-2,3,8,and 9)4 samples from control locations greater than 10 miles from the plant (RM-1,2,3,and 4)Continuous sampler operation with sample collection once per 7 d (more frequently if required by dust loading)Analyze for gross beta radioactivity
> 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following filter change.Perform gamma isotopic analysis on each sample if gross beta > 10 times yearly mean of control sample.Composite at least once per 31 d (by location for gamma scan)Radioiodine Samples from same Continuous sampler 1-131 at least once per location as air particulates operation with filter 7 d collection once per 7 d Soil Samples from same Once per year Gamma scan, Sr-89, locations as air Sr-90 once per year particulates DIRECT RADIATION 2 or more DOSIMETER's Once per 92 d Gamma dose at least placed at locations (in once per 92 d different sectors at or near the site boundary) in each of the 16 sectors.* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3 SQN ODCM Revision 58 Page 164 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 4)Exposure Pathway and/or Samole Sampling and Collection Freauencv Type and Frequency of Analvsis Sample Locations*
DIRECT RADIATION (continued) 2 or more DOSIMETER's placed at stations located approximately 5 miles from the plant in each of the 16 sectors 2 or more dosimeters in at least 8 additional locations of special interest.WATERBORN E Surface TRM 503.8*** Collected by Gamma scan of each TRM 483.4 automatic sequential composite sample.type sampler**
with Composite for H-3 composite samples analysis at least once collected at least per 92 d.once per 31 d.Ground 1 sample adjacent to At least once per 92 d Gross beta and gamma plant (location W-6) scan and H-3 analysis at least once per 92 d.1 sample from groundwater source up-gradient* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.Sample used as control for surface water and drinking water.
SQN ODCM Revision 58 Page 165 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 3 of 4)Exposure Pathway and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
WATERBORNE (continued)
Drinking 1 sample at the first potable water supply downstream from the plant (TRM 473.0)1 sample at the next 2 downstream potable surface water supplies (greater than 10 miles downstream)(TRM 469.9 and 465.3)1 sample at a control location upstream from the plant (TRM 503.8)***Collected by automatic sequential type sampler**with composite samples collected at least once per 31 d Grab sample once per 31 d.Samples collected by automatic sequential type sampler**
with composite sample collected at least once per 31 d.Gross beta and gamma scan of each composite sample.Composite for H-3, at least once per 92 d.Shoreline TRM 485, TRM 480, TRM At least once per 184 d Gamma scan of Sediment 479 each sample.INGESTION Milk 1 sample from milk producing At least once per 15 d. Gamma isotopic animals in each of 1-3 areas and 1-131 analysis indicated by the cow census of each sample.where doses are calculated to Sr-89, Sr-90 once be highest. per year.If samples are not available from a milk animal location, doses to that area will be estimated by projecting the doses from concentrations detected in milk from other sectors or samples of vegetation will be taken monthly when milk is not available.
At least 1 sample from a I control location.Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.*** Sample location is considered a control for drinking water and surface water.
SQN ODCM Revision 58 Page 166 of 179 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 4 of 4)Exposure Pathwa)and/or Sample Sampling and Collection Frequency Type and Frequency of Analysis Sample Locations*
INGESTION Fish 1 sample each from At least once per 184 Gamma scan on edible Chickamauga and Watts d. One sample portion.Bar Reservoirs.
representing a commercially important species and one sample representing a recreationally important species.Food 1 sample each of At least once per 365 d Gamma scan on edible Products principle food products at time of harvest. The portion.grown at private gardens types of foods and/or farms in the available for sampling vicinity of the plant. will vary. Following is a list of typical foods which may be available:
Cabbage and/or lettuce Corn Green Beans Potatoes Tomatoes Vegetation**
Samples from farms At least once per 31 d 1-131 and gamma scan producing milk but not at least once per 31 d providing a milk sample Control Sample from one control dairy farm* Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3** Vegetation sampling is applicable only for farms that meet the criteria for milk sampling and when implementation of milk sampling is not possible.
SQN ODCM Revision 58 Page 167 of 179 Table 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS Map Location Numbera 2 3 4 5 7 8 9 10 11 12 13 14 Station LM-2 LM-3 LM-4 LM-5 PM-2 PM-3 PM-8 PM-9 RM-1 RM-2 RM-3 RM-4 Sector N SSW NE NNE SW W SSW WSW SW NNE ESE NW NW E ENE NNE NE Approximate Distance 0.7 2.0 1.5 1.8 3.8 5.6 8.7 2.6 16.7 17.8 11.3 20.0 Indicator (I)or Control C C C C Samples Collectedb AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S AP, CF, S 19 21 23 24 25 31 32 33 34 35 37 38 40 44 46 47 Farm HW Farm HS Farm EH Well No. 6 Farm K TRM 473.0 East Side Utility ( Formally C. F. Industries)
TRM 469.9 (E. I. DuPont)TRM 465.3 (Chattanooga)
Deleted (R 40)TRM 503.8 (Dayton)TRM 485.0 TRM 483.4 TRM 479.0 TRM 480.0 Chickamauga Reservoir Watts Bar Reservoir 1.2 4.6 9.5 0.15 40 10.7 C I C I-- 13.8-- 18.4-- 20.1__ 1.3__ 0.3._ 4.7__ 3.7 M,W M M W M PW PW PW SW,PW SS SW SS SS F F C C a See figures 9.1, 9.2, and 9.3 Sample Codes: AP = Air particulate filter CF = Charcoal filter M = Milk PW = Public water R = Rainwater SS = Shoreline sediment SW = Surface water d A control for well water.TRM = Tennessee River Mile.e Distance from plant discharge (TRM 483.7) in river miles.Sample also used as a control for public water and surface water.F = Fish S = Soil W = Well water SQN ODCM Revision 58 Page 168 of 179 Table 9.3 DOSIMETRY LOCATIONS (Page 1 of 2)Map Location Number Station 3 4 5 7 8 9 10 11 12 13 14 49 50 51 52 53 55 56 57 58 59 60 62 63 66 67 68 69 70 71 72 73 74 SSW-1C NE-1A NNE-1 SW-2 W-3 SSW-3 WSW-2A SW-3 NNE-4 ESE-3 NW-3 N-1 N-2 N-3 N-4 NNE-2 Sector SSW NE NNE SW W SSW WSW SW NNE ESE NW N N N N NNE NE NE ENE ENE E E ESE ESE SE SE SE SSE SSE S S SSW SSW Approximate Distance (Miles)2.0 1.5 1.8 3.8 5.6 8.7 2.6 16.7 17.8 11.3 20.0 0.6 2.1 5.2 10.0 5.3 2.4 4.1 0.2 5.1 1.2 5.2 1.2 4.9 1.4 1.9 5.2 1.6 4.6 1.5 4.7 0.6 4.0 (Onsite )a or Offsite (Off)On On On Off Off Off Off Off Off Off Off On Off Off Off Off Off Off On Off On Off On Off On On Off On Off On Off On Off NE-1 NE-2 ENE-1 ENE-2 E-1 E-2 ESE-1 ESE-2 SE-1 SE-2 SE-4 SSE-1 SSE-2 S-1 S-2 SSW-1 SSW-2 aDOSIMETERs designated onsite are those located two miles or less from the plant.DOSIMETERs designated offsite are those located more than two miles from the plant.
SQN ODCM Revision 58 Page 169 of 179 Table 9.3 DOSIMETRY LOCATIONS, (Page 2 of 2)Map Location Number 75 76 77 78 79 81 82 83 84 85 86 87 88 89 90 Station SW-1 WSW-1 WSW-2 WSW-3 WSW-4 W-1 W-2 WNW-1 WNW-2 NW-1 NW-2 NNW-1 NNW-2 NNW-3 SSW-IB Sector SW WSW WSW WSW WSW W W WNW WNW NW NW NNW NNW NNW SSW Approximate Distance (Miles)0.7 0.9 2.5 5.7 7.8 0.6 4.3 0.4 5.3 0.4 5.2 0.6 1.7 5.3 1.5 Onsite (On)a or Offsite (Off)On On Off Off Off On Off On Off On Off On On Off On aDOSIMETERs designated onsite are those located two miles or less from the plant.DOSIMETERs designated offsite are those located more than two miles from the plant.
SQN ODCM Revision 58 Page 170 of 179 Figure 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT 348.75. N 11.26 s NNW -----NNE WNUCLEAR 2E.7 4 101.25 Scale 0 MileI I a Mile i SQN ODCM Revision 58 Page 171 of 179 Figure 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT 3"a,7 N itas NNWB7 NNE 3282'5 33.281-28 78J.,$W-1 at6 E B.1.0 SCALE MILES SQN ODCM Revision 58 Page 172 of 179 Figure 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT 342.85 N 11.25 NNW ~ CROS SVILLENE 326.25 IRCWO 33.7 NW 303.757 25 6,.25 THENN 281.254 -42E O A 70.75 W" SE A E 80 k AVELAND SCALE Ol-U * -- 2!
SQN ODCM Revision 58 Page 173 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 1 of 7)This Appendix establishes the minimum requirements for preparation, review, and approval of the Sequoyah Nuclear Plant Offsite Dose Calculation Manual. This Appendix also implements the requirements of ODCM Section 5.3 and SQN TS.1.0 Reviewer Responsibilities
1.1 Affected
Organization Review (AOR)The identification of affected organizations is the responsibility of the Sponsor and applies to all revisions of the ODCM.The affected organizations shall ensure that their reviewers have adequate understanding of the requirements and intent of the ODCM and access to pertinent background information.
The AO reviews the draft for impact on the organization and adequate interface
-not technical content.1.2 Independent Qualified Review (IQR)An independent qualified review is the process of independent technical review by Qualified Reviewers of activities potentially affecting nuclear safety.The IQR shall NOT be the person who prepared the ODCM revision.An IQR is performed by an individual designated by responsible department level managers to perform an independent technical review of activities potentially affecting nuclear safety.The IQR must be qualified to perform 10 CFR 50.59 review.1.3 Cross Disciplinary Review (CDR)The need for a CDR is determined by the IQR.CDR is a technical review by disciplines other than those responsible for the document preparation.
The CDR is responsible for only the technical aspects of the areas specified by the IQR and any portions of the document that support or justify those areas.Persons performing CDR do not have to be IQR qualified.
1.4 Plant
Operations Review Committee (PORC) Review The PORC reviews the ODCM.
SQN ODCM Revision 58 Page 174 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 2 of 7)1.5 Approval Authority The Plant Manager or designee will approve all revisions to the ODCM as required by Technical Specifications.
2.0 Processing
ODCM Revisions 2.1 Requester (If other than the Sponsor)Identify the need for an ODCM improvement.
Prepare a justification for the ODCM revision.Attach a marked-up copy of the existing ODCM.Forward the requested ODCM revision to the sponsoring organization.
2.2 ODCM Sponsor Evaluate requested changes and determine if necessary.
If the requested change is not necessary, return the request to the requester with explanation why the change is not needed.Incorporate all changes in a draft revision on BSL.Complete the top portion of Attachment B for each organization.
Distribute Attachment B to each Affected Organization and request completion of the review prior to expected PORC review date.Obtain appropriate reviews of the ODCM revision in BSL.2.3 Reviews 2.3.1 IQR Review the ODCM using all questions on Attachment C as a guideline and forward comments to the Sponsor.Identify discipline or organization to perform CDR, if needed.
SQN ODCM Revision 58 Page 175 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 3 of 7)2.3.2 Affected Organization Reviewer Review the proposed changes on BSL and provide comments to the ODCM Sponsor.Review the ODCM for impact on assigned organization, identify procedures/documents which require revision to implement the ODCM revision on the Attachment B, and return the Attachment B to the ODCM Sponsor.2.4 Sponsor If revision includes surveillance requirement or performance frequency changes then review SI/SR matrix for impact.Resolve comments and obtain reviewer's concurrence in BSL. Escalate any unresolved comments to appropriate management.
Ensure ODCM has been reviewed by sponsor and IQR in accordance with Attachment C.Ensure all Affected Organizations have reviewed the ODCM change and have identified the affected procedures on Attachment B.Ensure all IQR and CDR review requirements have been met.Assign an Effective Date typically 60 calendar days forward UNLESS there is reasonable justification for making it effective earlier, such as plant operating conditions, test schedules, commitment or corrective action deadlines, or implementation of upper-tier requirements, or lack of affected procedures identified on Attachment B.2.5 PORC Review Changes and document recommendation for approval in BSL.2.6 Plant Manager Approve the ODCM revision in BSL.2.7 ODCM Sponsor Record the ODCM approval date and implementation date on each completed Attachment B provided by the affected organizations.
Return the Attachment B to each affected organization.
2.8 Affected
Organization Revise procedures identified on the Attachment B and assign an effective date which matches that of the ODCM revision.Complete the Attachment B and return to the ODCM Sponsor.
SQN ODCM Revision 58 Page 176 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 4 of 7)2.9 ODCM Sponsor Ensure all Affected Organizations have completed and returned Attachment B prior to the effective date of the ODCM.Forward the approved ODCM change to Management Services at least three working days before the implementation date.The completed Attachments B and C are QA records, and are handled in accordance with the Document Control and Records Management Program.Forward a completed copy of each revision to Licensing to be filed and forwarded to the NRC in the Annual Radiological Effluent Release Report.2.10 Management Services Issue the ODCM and implementing procedures on the effective date of the ODCM revision.
SQN ODCM Revision 58 Page 177 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 5 of 7)Attachment B ODCM Affected Organization Review/Implementation Proposed ODCM Revision No.Expected PORC Review Date: Expected Effective Date: Affected Organization:
[ ] Operations
[] RADCON[ Chemistry
[] Maintenance Technical Support [ Scheduling
[ Engineering
[ Licensing[ Operations Training [] Technical Training Emergency Preparedness
[ ] Other The following procedures/documents will require revision to implement this ODCM change: PROCEDURE/DOCUMENT PROCEDURE/DOCUMENT ODCM Approval Date: ODCM Effective Date: The required procedure/document revisions to support this ODCM revision have been completed and have an implementation date which matches that given above for the ODCM revision./Affected Organization Date Affected Organization Date SQN ODCM Revision 58 Page 178 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 6 of 7)Attachment C ODCM Review Checklist All questions of this checklist are considered by the ODCM preparer and reviewed by the Independent Qualified Reviewer (IQR). Only the revised portion of the ODCM should be evaluated.
_ Changes to Section(s) 1.0-5.0 YES NO N/A 1. Does the revision meet the intent of the guidance provided in NUREG-1301 for radiological effluent and environmental monitoring controls/surveillance requirements?
- 2. Do definitions in Section 3.0 match those provided in the SQN TS, NUREG-1301, or other NRC guidance?3. Do Administrative Controls in Section 5.0 match those provided in SQN TS, NUREG-1301, or other NRC guidance?4. Does the ODCM fulfill the requirements of TVA, Federal or State Laws, SQN FSAR, and any other referenced requirements documents?
- 5. Does the numbering of the Control and its accompanying Surveillance I Requirement correspond?
- 6. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
- 7. Does nomenclature accurately describe the equipment and correspond to label identifiers?
- 8. Are referenced documents applicable, valid, and listed in the reference section?9. Does this change maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 1- CFR Part 50.36a, and Appendix I to 10 CFR Part 50? Provide justification for answer: 10. Are there methodologies given in Sections 6.0 through 9.0 which implement the applicable ODCM Controls?11. Are references to ODCM Controls and Surveillance Requirements accurate and correct?12. Are changes to setpoint calculation methodologies consistent with the guidance provided in NUREG-0133?
SQN ODCM Revision 58 Page 179 of 179 APPENDIX A -SQN ODCM REVISION PROCESS (Page 7 of 7)Attachment C ODCM Review Checklist (continued)
Changes to Section(s) 6.0-11.0 YES NO N/A 13. Are changes to liquid effluent concentration compliance methodologies.consistent with the guidance provided in NUREG-0133 and 10 CFR Part 20?14. Are changes to gaseous effluent dose rate calculation/compliance methodologies consistent with the guidance provided in NUREG-0133 and/or Regulatory Guide 1.109?15. Are changes to dose or dose projection calculation/compliance methodologies consistent with the guidance provided in NUREG-01 33 and/or Regulatory Guide 1.109?16. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
- 17. Are referenced documents applicable, valid, and listed in the references?
- 18. Are ODCM Sections numbered consistently and consecutively?
- 19. Are references to other ODCM Sections correct?20. Are references to ODCM Tables and Figures accurate and correct?21. Are any new acronyms defined in Appendix A?22. Are equations numbered consecutively?
- 23. Does dimensional analysis yield the correct units for equations?
- 24. Are terms used in equations defined after the equation (and in Appendix A) and the proper units given for that term?25. Do units on equation terms which reference tables match the units used for that term in the Table?26. Are references given for table and other values correct and accurate?27. Do data values given match those in the reference?
- 28. Do text descriptions of release/discharge points in Sections 6.0 and 7.0 correspond with the Figures referenced in those sections?29 Will change affect the NOUE and ALERT calculation values in SQS20247.30. The change does not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations?
Provide justification for answer:/Preparer Date/IQR Date