ML20084S909 | 31 May 1976 | Ao:On 770527,HPCI Pressure Switches E41-PSH-NO12 A,B,C & D Exceeded Tech Spec Calibr Limits.Switches Immediately Recalibr | |
ML20084S912 | 25 March 1977 | Telecopy Ao:On 770324,containmet Spray Pump a Out of Svc During Training Startup,Violating Tech Spec | |
ML20085D062 | 17 July 1973 | Ao:On 730628-0705 & 09-10,changes Performed on Safeguards Equipment W/O Demonstrating Operability of Redundant Equipment Before Removal.Safety Injection Pumps B & C Tripped & Circuit Breaker Tripped,Respectively | |
ML20085D066 | 11 July 1973 | Telecopy Ao:On 730709,two Safety Injection Pumps Experienced Overcurrent Trips.Caused by New Overcurrent Trip Devices Tripping at Lower than Desired Value.Trip Setting Increased | |
ML20085D072 | 10 July 1973 | Telecopy Ao:On 730710,circuit Breaker for Containment Cooler Fan Tripped.Caused by Instantaneous Overcurrent Due to Misalignment of Calibr Spring in Overcurrent Trip Device. Spring Realigned | |
ML20085D077 | 10 July 1973 | Telecopy Ao:On 730710,circuit Breaker for Containment Cooler Fan 2 Tripped.Caused by Overcurrent Due to Misalignment of Calibr Spring in Overcurrent Trip Device.Spring Realigned | |
ML20085D084 | 9 July 1973 | Telecopy Ao:On 730709,two Safety Injection Pumps Experienced Overcurrent Trips.Caused by Overcurrent Trip Devices Tripping at Lower than Desired Value.Trip Setting Increased | |
ML20085D105 | 21 June 1973 | Telecopy Ao:On 730620,during Test of Turbine Redundant Overspeed Trip Sys,Turbine Trip Occurred.Caused by High Pressurizer Pressure.Turbine Stop Valve Limit Switch Adjusted | Overspeed trip |
ML20085D109 | 21 June 1973 | Telecopy Ao:On 730620,during Test of Turbine Redundant Overspeed Trip Sys,Turbine Trip Occurred.Caused by High Pressurizer Pressure.Turbine Stop Valve Limit Switch Adjusted | Overspeed trip |
ML20085D117 | 22 June 1973 | Ao:On 720119,0221,0320 & 0920,pressurizer Level Reactor Trip Occurred,On 720320,0421,0518,0620,0720,0823 & 0920, Pressurizer High Pressure Reactor Trip Occurred & on 720119 Pressurizer Low Pressure Reactor Trip Occurred | |
ML20085D133 | 14 June 1973 | Ao:On 730605,erroneous Indication of Containment Vessel Pressure Transmitter PI-950B Reported on Plant Trouble Ticket.Caused by Vent Valves Open to Environ.Plugs Installed in Valves | |
ML20085D157 | 6 June 1973 | Telecopy Ao:On 730605,vent Valves on Pressure Sensing Line to Containment Pressure Transmitters Found Open.Plugs Installed & Valves Added to Check Off Sheet | |
ML20085D167 | 6 June 1973 | Telecopy Ao:On 730605,vent Valves on Pressure Sensing Line to Containment Pressure Transmitters Found Open.Plugs Installed & Valves Added to Check Off Sheet | |
ML20085D226 | 18 April 1973 | Telecopy Ao:On 780410,inadvertent Liquid Release Occurred Resulting in Release of Small Amount of Particulate & Tritium Activity to Storm Drain Sys | |
ML20085D296 | 6 November 1972 | Telecopy Ao:On 721105,power Operated Release Valve UR-2 Was Opened & Failed to Close.Ltr to Be Forwarded within 10 Days | |
ML20085D370 | 27 October 1972 | Telecopy Ao:On 721027,containment Integrity Violated Due to Outer Door of Personnel Hatch Opened for Approx 10 W/Inner Door Open 4 Inches.Violation Necessary to Permit Technicians Exit from Hatch | |
ML20085D473 | 16 June 1972 | Ao:Containment Spray Pump a Would Not Rotate Freely When Turned by Hand.Caused by Galled Impeller Ring Binding on Casing Alignment Seal Ring.Impeller & Casing Alignment & Impeller Alignment Seal Rings Replaced | |
ML20085D484 | 7 June 1972 | Telecopy Ao:Containment Spray Pump Found to Be Binding.Pump Being Disassembled for Repairs | |
ML20085D514 | 16 May 1972 | Ao:On 720508,HX B Isolated for Leakage Following Alarm & Increase in Component Surge Tank Level.Hx Will Be Inspected & Repaired | |
ML20085D532 | 25 February 1972 | Ao:On 720213,emergency Diesel Generator 2A Failed to Start.Caused by Momentary Indication of High Crankcase Pressure.Diesel Trip Signals Bypassed by Key Switch for Each Engine Listed | Overspeed trip |
ML20085D549 | 20 January 1972 | Ao:On 720117,emergency Diesel Generator 2A Tripped After Manual Start Initiated.Caused by High Crankcase Pressure. Alarm Reset & Diesel Restarted | |
ML20085D578 | 14 January 1972 | Ao:On 720103,emergency Diesel Generator B Failed to Start. Caused by Dirt Particles in Starting Air Solenoid Valve. Valve Cleaned | |
ML20086B103 | 30 November 1971 | Ao:On 711124,alarm Received on Radiation Monitoring Sys Channel R-17.Leak Determined to Be in Pressurizer Liquid Space Sample HX | |
ML20086B110 | 21 December 1971 | Ao:On 711130,alarm on Radiation Monitoring Sys Indicated That Sample HX Developed Leak.Defective HX Replaced. Westinghouse to Investigate Repeated Failures & Make Recommendations Re Adequate Design for Sample HX | |
ML20086D421 | 9 February 1976 | AO 50-261/76-3:on 760128,high Level Alarm Received on Safety Injection Accumulator B.Caused by Check Valve 875 Leaking Resulting in Dilution.Accumulator Partially Drained & Refilled | |
ML20086D427 | 29 January 1976 | Telecopy Ao:On 760128,sample of Safety Injection Accumulator B Indicated Boron Concentration of 1,939 Ppm,Below Tech Specs.Accumulator Partially Drained,Refilled & Verified | |
ML20086D439 | 22 January 1976 | Ao:On 760124 & 22,discovered That Reactor Trip Relay RT3 in Reactor Protection Logic Train a Operating Erratically. Further Investigation Revealed That Relays RT-4 & RT-8 on Logic Train B Defective.Relays Replaced | |
ML20086D442 | 2 February 1976 | AO 50-261/76-2:on 760121 & 22,failure of One & Delayed Operation of Two Reactor Trip Relays Occurred.Caused by Open Coil Winding.Three Defective Relays Replaced | |
ML20086D447 | 13 January 1976 | AO 50-261/76-1:on 760102,failure of Boric Acid Transfer Pump Resulted in Failure of One ESF Component That Caused or Threatened to Render Sys Incapable of Functioning.Caused by Damaged Rotor | Boric Acid |
ML20086F516 | 8 December 1975 | Ao:On 751208,boron Sample from Safety Injection Accumulator B Indicated 1,915 ppm,35 Ppm Below Tech Specs.Cause Unknown. Accumulator Partially Drained & Refilled from Refueling Water Storage Tank | |
ML20086F521 | 2 January 1976 | Ao:On 760102,boric Acid Pump B Stopped Running.Caused by Defective Stator & Damaged Rear Bearing.Investigation Continuing | Boric Acid |
ML20086F529 | 4 November 1975 | Ao:On 751102,motor Driven Auxiliary Feedwater Pump a Failed to Start.Remote Electrical Contacts Cleaned | |
ML20086F540 | 3 November 1975 | Ao:On 751101,containment Integrity Broken for Approx 10 Minutes Due to Simultaneous Opening of Both Personnel Air Lock Doors | |
ML20086F549 | 29 October 1975 | Ao:On 751028,sequence of Switch Operations Resulted in Breakers for Both Svc Water Booster Pumps a & B Tripping on Overload | |
ML20086F561 | 22 September 1975 | Ao:On 750921,urgent Failure Alarm Received.Caused by Phase Failure in Cabinet 1AC Which Rendered 12 Rods Inoperable. Reactor Manually Tripped | |
ML20086F579 | 12 May 1975 | AO 50-261/75-9:on 750501,reactor Coolant Pump Seal Failed, Resulting in Discharge of Reactor Coolant Fluid to Containment Floor.New Seal & Associated Parts Being Installed.Parts Shall Be Certified | |
ML20086F596 | 16 July 1975 | Telecopy Ao:On 750715,steam Drive Auxiliary Feedwater Pump Discharge Valve V2-14B to Steam Generator B Failed to Open Electrically | |
ML20086F608 | 26 June 1975 | Telecopy Ao:On 750625,boric Acid Transfer Pump a Noted Off. Caused by Pump Shaft Being Broken at Keyway.Also on 750625, Employee Received Whole Body Dose of 3,080 Mrem for Quarter Ending 750630 | Boric Acid |
ML20086F615 | 14 July 1975 | Ao:On 750711,control Rod L-5 Dropped,Causing Load Runback to Approx 70% Power.Caused by Defective Stationary Gripper Coil | |
ML20086F620 | 6 June 1975 | AO 50-261/75-11:on 750527,RCS Oxygen Concentration Noted to Be 0.16 Ppm,Exceeding Limit.Caused by Mixture of Hydrogen & Nitrogen in Vol Control Tank,Limiting Hydrogen to Rcs.Vol Control Tank Vented | |
ML20086F623 | 27 May 1975 | Ao:On 750527,RCS Sample Indicated 0.16 Ppm Oxygen,Exceeding Tech Specs.No Cause Stated.Concentration Reduced | |
ML20086F627 | 2 June 1975 | AO 50-261/75-10:on 750521,boric Acid Transfer Pump B Failed.Caused by Shaft Being Broken at Keyway & Worn Pump Bearing.Pump Rebuilt | Boric Acid |
ML20086F630 | 21 May 1975 | Ao:On 750521,boric Acid Pump B Stopped.Caused by Broken Shaft in Keyway Area | Boric Acid |
ML20086F644 | 9 May 1975 | AO 50-261/75-8:on 750429,RHR Pump Suction Valve RHR-862A Failed.Caused by Torque Switch on SMB-O Motor Operator Being Out of Adjustment.Torque Switch Adjusted.On 750430,complete Insp of Operator Found Excess Grease.Grease Removed | |
ML20086F647 | 29 April 1975 | Ao:On 750429,valve RHR-862A Failed to Open from RTGB When RHR Sys Being Aligned.Cause Under Investigation.Valve Opened Locally Using Manual Operator & All Flow Paths Restored | |
ML20086F674 | 12 June 1975 | Revised AO 50-261/75-9:on 750501,reactor Coolant Pump Seal Failed,Resulting in Discharge of Reactor Coolant Fluid to Containment Floor.Caused by Pump Running W/Seal Leaking. Seals,Shaft,Impeller & Hearings Replaced | |
ML20086F691 | 2 May 1975 | Telecopy Ao:On 750501,seal 1 on Reactor Coolant Pump C Failed,Producing Leak to Containment Floor.Seal 2 Failed on 750502.Cooldown Initiated.Rcs Depressurized & Drained to Below Pump Seals | |
ML20086F696 | 1 April 1975 | Telecopy Ao:On 750331,emergency Diesel B Tripped.Caused by Low Lube Oil Pressure.Filters Changed & Unit Returned to Svc | |
ML20086F698 | 10 April 1975 | AO 50-261/75-7:on 750331,diesel B Tripped Due to Low Lube Oil Pressure.Caused by Lube Oil Filter High Differential Pressure Resulting from Dirty Filters.Lube Oil Filters Replaced | |
ML20086F699 | 27 March 1975 | AO 50-261/75-6:on 750314,contractor Personnel Exposed to Radiation in Excess of Limits.Caused by Exceeding Stay Time in Localized Field of High radiation.Chem-Nuclear,Inc & Util Investigating Use of Addl Shielding | High Radiation Area |