ML20086F699

From kanterella
Jump to navigation Jump to search
AO 50-261/75-6:on 750314,contractor Personnel Exposed to Radiation in Excess of Limits.Caused by Exceeding Stay Time in Localized Field of High radiation.Chem-Nuclear,Inc & Util Investigating Use of Addl Shielding
ML20086F699
Person / Time
Site: Robinson 
Issue date: 03/27/1975
From: Utley E
CAROLINA POWER & LIGHT CO.
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
AO-50-261-75-6, MG-75-428, NG-75-428, NUDOCS 8401040586
Download: ML20086F699 (4)


Text

$

V U

.g y

.?.4'11 b4h3 U V *" 23 y y

, C ardrj Nv,er & Leht Cor.jpany March 27, 1975 t

File: NG-3513 (R)

Serial: NG-75-428

\\

J / O

\\

Mr. Norman C. Moseley, Director

'q : ',

U. S. Nuclear Regulatory Commission f,,.../'[fi\\~)(,

Region II, Suite 818

%/

230 Peachtree Street, N. W.

Atlanta, Georgia 30303

Dear Mr. Moseley:

/

H. B. ROBINSON UNIT NO. 2 LICENSE DPR-23 VIOLATION OF ADMINISTRATIVE PROCEDURE EXPOSURE OF CONTRA]CTOR PERSONNEL 'ZO MORE THAN 300 MREM OF RADIATION In accordance with Paragraph 6.6.2.a of the Technical Specifica-tions for H. B. Robinson Unit No. 2, the attached Abnormal Occurrence report is submitted for your information.

This report fulfills the requirement for a written report within ten days of an Abncrmal Occurrence and is in accordance with the format set forth in Regulatory Guide 1.16, Revision 1.

Yours very truly,

/"N.

' /;

~,.Q,/

c'

- ' a f (g E. E.. Ut12\\r

~

kt:e-? resident Bulk Poser Supply

~

DBW:me Attachme'nt

~

cc: Messrs. N. B. Bessac T. E. Bownan P. W. Howe R. E. Jones, ^

D. Knuth J. B. McGirt

,- D. B. Waters y"&,

g[

8401040596 750327 p;

PDR ADOCK 05000261 f

S PDR db31

.%g-e m...

s

,,t,..s 336 Fs/ettexilio S'ri~ ;. P O Dc)x 1551. H3kg;h. N C 27602 retrM SENr REGIONm

r-O v)

V Abnormal Occurrence Renart 1.

Renort No.

50-261/75-6 2a.

Renort Date March 17, 1975 2b.

Occurrence Date March 14, 1975 3

Facility H. B. Robinson Unit No. 2 Hartsville, South Carolina 29550 4

Identification of Occurrence Exposure of contractor personnel to radiation in excess of administrative limits constituting an abnormal occurrence os defined in Section 1.8.g of the Technical Specifications.

5 Conditiens Prior to Occurrence The plant was operating at 100% nuclear power with 696 MW net electrical output. Transfer of spent resin from the Spent Resin Storage Tank to a spent resin transport vehicle had just been completed.

6.

Description of Occurrence At 1130 hours0.0131 days <br />0.314 hours <br />0.00187 weeks <br />4.29965e-4 months <br />, March 14, 1975, the transfer of resin from the Spent Resin Storage Tank to a contractor's spent resin transport vehicle had been completed under Special Radiation Work Permit 3-121. To disconnect the transfer hose an individual was required to mount the eht te end enter a local field of 16 rem / hour. This

' a health physics ' technician employed by Chem was acco mi Nuclear Inc. of Barnwell, South Carolina.

Immediately prior to performing the task the techniciad s pocket chamber was read as 60 mrem (0-500 crem full scale). While performing the disconnect a Carolina Power & Light Company Radiation Control and i

Test Technician covered the work from the base of the vehicle. High I

r O

O v

. range survey instrumentation was in use. After completing the task, 4approximately one to two minutes time),-the individual was checked by the covering Company technician. It was immediately noted that the hair line on the exposed individual's pocket chanber, although visible, was beyond the 500 mrem marking.

The individual was immediately removed from the radiation area and his TLD badge sent special delivery to Raleigh, N. C. for reading.

At 1157, March 17,1975, the result of the TLD reading was received at this facility.

Volume 8, Radiation Protection Manual, paragraph 4.2 states in part:

"Any visitor... chall be limited to a whole body exposure of 300 mrem /

quarter unless the individual's accumulated occupational dose, and the occupational exposure for the current quarter are furnished by the individual or his organization." Since no exposure records existed for the exposed individual at this facility this occurrence constitutes a reportable incident as defined by Section 1.8.g of the Plant Technical Specification.

7.

Desienation of Anparent Cause of the Incident Stay time in a localized field of high radiation was exceeded for the authorized exposure permitted for the individual involved.

8.

Analysin of Occurrence Plant safety was not involved, and at no time was there any danger to the general public. No 10CFR20 limits were exceeded. The individual's total exposure for the quarter was 665 mrem prior to this incident.

F u..

~

O O

. 9.

CorrcctThe Action

~~

A memorandum has been routed to all H. B. Robinson Radiation Control and Test Technicians reemphasizing the hazards of work in high radiation areas and cautioning them of their responsibility to limit and control personnel exposures.

Chem-Nuclear, Inc. and Carolina Power & Light Company are investigating the feasibility of utilizing additional shielding during the hose-disconnect operation.

15additionalshieldingcanbeutilized effectively, appropriate procedures will be implemented to require its use during the hose-disconnect operation.

10.

Failure Data January 15, 1973 Violation of Administrative Procedure (employee exposure to 672 mrem)

August 16, 1973 Violation of Administrative Limit (employee exposure to 824 mrem)

~