| * e | | * e ATTACHMENT I Supplemental Technical Specification Change Surry Power Station Units I and 2 |
| * ATTACHMENT I Supplemental Technical Specification Change Surry Power Station Units I and 2
| |
| ( | | ( |
| --****-. - --- --.---~----- | | --****-. - --- --.---~----- |
| 8807260307 880718 PDR ADOCK 05000280 P PDC | | 8807260307 880718 PDR ADOCK 05000280 P PDC |
|
| |
|
| e TS 3.8-1 | | e TS 3.8-1 3.8 CONTAINMENT App 1i cabil i ty Applies to the integrity and operating pressure of the reactor containment. |
| '
| |
| 3.8 CONTAINMENT App 1i cabil i ty Applies to the integrity and operating pressure of the reactor containment. | |
| Objective To define the 1imiting operating status of the reactor containment for unit operation. | | Objective To define the 1imiting operating status of the reactor containment for unit operation. |
| Specification A. Containment Integrity and Operating Pressure | | Specification A. Containment Integrity and Operating Pressure |
Line 36: |
Line 33: |
| * In the event of failure of the personnel airlock inner door seal to meet the leakage test acceptance criteria, the outer personnel airlock door may be opened for a period of ti me not to exceed fifteen minutes with an annual cumulative time not to exceed one hour per year to allow access for the repair and retest of the inner door. | | * In the event of failure of the personnel airlock inner door seal to meet the leakage test acceptance criteria, the outer personnel airlock door may be opened for a period of ti me not to exceed fifteen minutes with an annual cumulative time not to exceed one hour per year to allow access for the repair and retest of the inner door. |
|
| |
|
| ,._ .
| |
| ATTACHMENT 2 Discussion of Supplemental Change | | ATTACHMENT 2 Discussion of Supplemental Change |
|
| |
|
| ...'-'
| |
| e Discussion of Supplemental Change Discussion of Proposed Change As discussed in our submittal, Serial 88-100, dated April 26, 1988, access to the containment while in a subatmospheric condition is performed by equalizing and opening the airlock outer door and then closing and sealing the outer door. The pressure in the airlock is then equalized with the containment and the inner door is opened for the final access. This method ensures that at least one door on the personnel airlock is properly closed and sealed whenever the containment is in a subatmospheric condition. Interlocks provide additional assurance that the doors cannot be opened simultaneously while in a subatmospheric condition. | | e Discussion of Supplemental Change Discussion of Proposed Change As discussed in our submittal, Serial 88-100, dated April 26, 1988, access to the containment while in a subatmospheric condition is performed by equalizing and opening the airlock outer door and then closing and sealing the outer door. The pressure in the airlock is then equalized with the containment and the inner door is opened for the final access. This method ensures that at least one door on the personnel airlock is properly closed and sealed whenever the containment is in a subatmospheric condition. Interlocks provide additional assurance that the doors cannot be opened simultaneously while in a subatmospheric condition. |
| Fo 11 owing the final use of the airlock, the seals on the inner and outer personnel airlock doors are tested at equal to or greater than the peak calculated accident pressure. If the seal on the outer door fails to pass the acceptance criteria of the test, the inner door is verified to be properly closed and sealed and the outer door seal is repaired and retested. If the inner door seal fails, the outer door is verified to be properly closed and sealed. However, the on 1y accept ab 1e method for repair and retest of the inner seal is by reopening the outer door to a11 ow access to the inner door seal . During this brief period, the containment integrity requirements as defined in T. S. Section 1. H. 4 cannot be met s i nee the inner door wi 11 be closed but may not be properly sealed. | | Fo 11 owing the final use of the airlock, the seals on the inner and outer personnel airlock doors are tested at equal to or greater than the peak calculated accident pressure. If the seal on the outer door fails to pass the acceptance criteria of the test, the inner door is verified to be properly closed and sealed and the outer door seal is repaired and retested. If the inner door seal fails, the outer door is verified to be properly closed and sealed. However, the on 1y accept ab 1e method for repair and retest of the inner seal is by reopening the outer door to a11 ow access to the inner door seal . During this brief period, the containment integrity requirements as defined in T. S. Section 1. H. 4 cannot be met s i nee the inner door wi 11 be closed but may not be properly sealed. |
Latest revision as of 23:31, 2 February 2020
Proposed Revised Tech Specs,Specifying Time Limit for Entry Into Containment Personnel Airlock During Power Operations to Make Repairs on Inner Door of Personnel AirlockML18152B059 |
Person / Time |
---|
Site: |
Surry |
---|
Issue date: |
07/18/1988 |
---|
From: |
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
---|
To: |
|
---|
Shared Package |
---|
ML18152B058 |
List: |
---|
References |
---|
NUDOCS 8807260307 |
Download: ML18152B059 (5) |
|
Similar Documents at Surry |
---|
Category:TECHNICAL SPECIFICATIONS
MONTHYEARML18152B3591999-08-23023 August 1999 Revised Tech Specs Basis Pages for TS 3.1.B,deleting Reactor Vessel Toughness Data Duplicated in UFSAR & Includes Ref to Applicable UFSAR Section ML18152B6591999-04-28028 April 1999 Proposed Tech Specs Re Refueling Water Chemical Addition Tank Min Vol ML18152A2131999-02-16016 February 1999 Proposed Tech Specs,Consolidating AFW cross-connect Requirements by Relocation of Electrical Power Requirements from TS 3.16 to TS 3.6 ML18152B5451999-02-16016 February 1999 Proposed Tech Specs Pages,Revising Augmented Insp Requirements for Reactor Coolant Pump Flywheels ML18152B6151998-11-0404 November 1998 Proposed Tech Specs 4.6.A.1.b,re EDG Start & Load Time Testing Requirements & TS 3.16 Bases Re EDG Ratings ML18153A3311998-09-24024 September 1998 Proposed Tech Specs Modifying Testing Requirements for Reactor Trip Bypass Breaker ML18153A3351998-09-24024 September 1998 Proposed Tech Specs Pages Affected by Suppl to 960912 Resubmittal of Change Request Re Relocation of Fire Protection Requirements from TS to UFSAR ML18152B7551998-06-19019 June 1998 Proposed Tech Specs Establishing Requirements for Use of Temporary Supply Line (Jumper) to Provide Svc Water to Component Cooling Heat Exchangers ML18152A3651998-03-25025 March 1998 Proposed Tech Specs Revising Station Mgt Titles to Reflect New Positions Approved by Vepc Board of Directors on 980220 ML18153A3481997-12-18018 December 1997 Proposed Tech Specs Clarifying Terminology Used for Describing Equipment Surveillances Conducted on Refueling Interval Frequency.Clarification Consistent W/Info Contained in Rev 1 to NUREG-1431 ML18153A1761997-11-0505 November 1997 Proposed Tech Specs Re Temporary Svc Water Supply Line to Component Cooling Heat Exchangers ML18153A3941997-11-0505 November 1997 Proposed Tech Specs Re Change for Increased Enrichment of Reload Fuel ML18153A5231997-04-24024 April 1997 Proposed Corrected Tech Specs Pages 6.1-3 & 6.1-8 Re Relocation of Fire Protection TS to Updated Final Safety Analysis Rept ML18153A5031997-03-18018 March 1997 Proposed Tech Specs Rev to Section 4.15 for Surry Power Station to Include Pp Inadvertently Omitted from 970203 Request for Amend to Licenses DPR-32 & DPR-37 ML18153A4921997-02-0303 February 1997 Proposed Tech Specs Re Deletion of Specific ASME Section XI Code Ref ML18153A6351996-11-26026 November 1996 Proposed Tech Specs Re Removal of Record Retention Requirements,Per GL 95-06 & Administrative Ltr 95-06 ML18153A0671996-09-12012 September 1996 Proposed Tech Specs Re Relocation of Fire Protection Requirements ML18153A6901996-04-15015 April 1996 Proposed Tech Specs,Clarifying Applicability of Quadrant Power Tilt Ration Requirements ML18153A5391996-03-21021 March 1996 Proposed Tech Specs Re Charcoal Filter Testing Clarification ML18153A5271996-03-14014 March 1996 Proposed Tech Specs,Permitting Use of 10CFR50 App J,Option B,performance-based Containment Lrt ML18153A5801996-01-30030 January 1996 Proposed Tech Specs Re Reactor Coolant Sys Liquid Sampling ML18153A6761995-11-20020 November 1995 Proposed Tech Specs Re App J Option B,performance-based Containment Leakage Rate Testing ML18153A7141995-07-20020 July 1995 Proposed Tech Specs Establishing New Setpoint Limit for SG high-high Level & Provides More Restrictive Setting Limits for Certain Rps/Esfas Setpoints ML18153A6991995-07-14014 July 1995 Proposed Tech Specs,Providing Two H Allowed Outage Time for One RHR Pump to Accommodate Plant Safety,Emergency Power Sys Surveillance Testing & Permit Depressurizing SI Accumulators in Lieu of Accumulator Isolation ML18153A8371995-06-0808 June 1995 Proposed Tech Specs,Incorporating Revised Pressure/Temp Limits & Associated Ltops Setpoint That Will Be Valid to end-of-license ML18153B2301995-02-14014 February 1995 Proposed Tech Specs Re App J Testing Requirements ML18153B2131995-01-24024 January 1995 Proposed Tech Specs,Modifying as-found Test Acceptance Criterion for Pressurizer Safety Valves ML18153B1621994-11-29029 November 1994 Proposed Tech Specs Implementing Zirlo Fuel Cladding ML18153B1581994-11-22022 November 1994 Proposed Tech Specs,Deleting Unnecessary Descriptive Phrases Re Number of Cells in Station & EDG Batteries ML18153B1501994-11-10010 November 1994 Proposed Tech Specs Re Changes to TS Will Clarify SR for Reactor Protection & Engineered Safeguard Sys Instrumentation & Actuation Logic ML18153B0941994-10-11011 October 1994 Proposed Tech Specs Surveillance Frequencies for Hydrogen Analyzers ML18152A5061994-09-0606 September 1994 Proposed Tech Specs Re Mgt Safety Review Committee & Station Nuclear Safety & Operating Committee Responsibilities ML18152A1191994-08-30030 August 1994 Proposed Tech Specs to Accomodate Core Uprating ML18153B0061994-07-14014 July 1994 Proposed Tech Specs Changes Will Eliminate Remaining References to cycle-specific Parameters in Surry TS ML18152A1821994-06-0909 June 1994 Proposed TS Re Chemical & Vol Control Sys & Safety Injection Sys ML20065P6111994-04-19019 April 1994 Proposed Tech Specs,Modifying Control Rod Movement Surveillance Frequency ML18153A8821994-02-25025 February 1994 Proposed Tech Specs Modifying Surveillance Frequency of Nozzles in Containment & Recirculation Spray Sys ML18153B4321993-12-27027 December 1993 Proposed Tech Specs Reflecting Revised Review Responsibilities of Station Nuclear Safety & Operating Committee & Mgt Safety Review Committee ML18153B4081993-12-10010 December 1993 Proposed Tech Specs,Establishing Upper Limit on Allowable COLR Mtc Values ML18153B4021993-12-10010 December 1993 Proposed Tech Specs,Modifying Surveillance Frequency of Auxiliary Feedwater Sys Pumps from Monthly to Quarterly Per Generic Ltr 93-05 & NUREG-1431 ML18153B4051993-12-10010 December 1993 Proposed Tech Specs,Updating Augmented Insp Program for Sensitized Stainless Steel by Incorporating Newer Code Requirements,While Maintaining Augmented Insp Philosophy ML18153B3751993-11-15015 November 1993 Proposed Tech Specs Implementing Revised 10CFR20,revising Frequency Radiological Release Repts from Semiannual to Annual & Clarifying Site Maps ML18153B3501993-10-19019 October 1993 Proposed Tech Specs for RSHX Svc Water Outlet Radiation Monitors ML18153B3321993-09-29029 September 1993 Proposed Tech Specs Modifying Required Insp Frequency of Low Pressure Turbine Blades to Permit Blade Insp to Be Performed Concurrent W/Disk & Hub Insp ML18152A0481993-07-20020 July 1993 Proposed Tech Specs Deleting Requirement for Station Nuclear Safety & Operating Committee & Audit Frequencies ML18153D3921993-07-16016 July 1993 Proposed Tech Specs for Operation W/Three Degree Increase in Svc Water Temp Limit for Containment Air Partial Pressures of 9.1,9.2 & 9.35 Psia ML18152A0461993-07-16016 July 1993 Proposed Tech Specs Implementing Revised 10CFR20,revise Frequency of Radiological Effluent Release Repts from semi-annual to Annual,& Clarify Site Maps ML18152A4511993-07-0202 July 1993 Proposed Tech Specs to Include COLR Which Presents reload- Specific Limits for Key Core Operating Parameters ML18153D3811993-07-0202 July 1993 Proposed TS Table 4.2-1 Re Miscellaneous Insps & Sensitized Stainless Steel Exams ML18153D3331993-05-0606 May 1993 Proposed Tech Specs Supporting Operation of Unit 2 w/100 Psi Reduction in RCS Nominal Operating Pressure Through End of Operating Cycle 12 1999-08-23
[Table view] Category:TECHNICAL SPECIFICATIONS & TEST REPORTS
MONTHYEARML18152B3591999-08-23023 August 1999 Revised Tech Specs Basis Pages for TS 3.1.B,deleting Reactor Vessel Toughness Data Duplicated in UFSAR & Includes Ref to Applicable UFSAR Section ML18151A6641999-08-0606 August 1999 Rev 0 to Surry Unit 2 Cycle 16 Startup Physics Tests Rept. ML18152B6591999-04-28028 April 1999 Proposed Tech Specs Re Refueling Water Chemical Addition Tank Min Vol ML18152A2131999-02-16016 February 1999 Proposed Tech Specs,Consolidating AFW cross-connect Requirements by Relocation of Electrical Power Requirements from TS 3.16 to TS 3.6 ML18152B5451999-02-16016 February 1999 Proposed Tech Specs Pages,Revising Augmented Insp Requirements for Reactor Coolant Pump Flywheels ML18151A5511999-02-10010 February 1999 to NE-1187, Surry Unit 1,Cycle 16 Startup Physics Tests Rept. ML18152B6151998-11-0404 November 1998 Proposed Tech Specs 4.6.A.1.b,re EDG Start & Load Time Testing Requirements & TS 3.16 Bases Re EDG Ratings ML18153A3351998-09-24024 September 1998 Proposed Tech Specs Pages Affected by Suppl to 960912 Resubmittal of Change Request Re Relocation of Fire Protection Requirements from TS to UFSAR ML18153A3311998-09-24024 September 1998 Proposed Tech Specs Modifying Testing Requirements for Reactor Trip Bypass Breaker ML18152B7551998-06-19019 June 1998 Proposed Tech Specs Establishing Requirements for Use of Temporary Supply Line (Jumper) to Provide Svc Water to Component Cooling Heat Exchangers ML20249B9911998-05-0606 May 1998 Analysis of Capsule X Virginia Power Surry Unit 1 Reactor Vessel Matl Surveillance Program. W/Evaluation of Surry Unit 1 Surveillance Capsule X Results & Response to NRC RAI Re GL 92-01,rev 1,suppl 1 ML18151A1931998-05-0404 May 1998 Rev 1 to Summary of Changes to Surry Units 1 & 2 Third Interval IST Program. ML18152A3651998-03-25025 March 1998 Proposed Tech Specs Revising Station Mgt Titles to Reflect New Positions Approved by Vepc Board of Directors on 980220 ML20199B0711998-01-0505 January 1998 Rev 0 to NE-1148, Surry Unit 2,Cycle 15 Startup Physics Test Rept ML18153A3481997-12-18018 December 1997 Proposed Tech Specs Clarifying Terminology Used for Describing Equipment Surveillances Conducted on Refueling Interval Frequency.Clarification Consistent W/Info Contained in Rev 1 to NUREG-1431 ML18150A4661997-12-16016 December 1997 ISI Plan for Third Insp Interval,Vol 2,Rev 9 for Components & Component Supports,940510-040510, for Surry Power Station,Unit 2 ML18153A3941997-11-0505 November 1997 Proposed Tech Specs Re Change for Increased Enrichment of Reload Fuel ML18153A1761997-11-0505 November 1997 Proposed Tech Specs Re Temporary Svc Water Supply Line to Component Cooling Heat Exchangers ML18150A4641997-10-27027 October 1997 Risk-Informed ISI (RI-ISI) Pilot Program Submittal. ML18151A3911997-10-16016 October 1997 Rev 8 to VPAP-2103, Odcm. ML18151A7231997-08-0707 August 1997 Rev 1 to Nuclear Safety Analysis Manual Part Iv,Chapter a Probabilistic Safety Assessment Products. ML20210J5031997-07-31031 July 1997 Rev 0 to NE-1132, Surry Unit 1,Cycle 15 Startup Physics Tests Rept ML18150A4441997-06-0909 June 1997 Vol 2,Rev 8 to ISI Plan for Third Insp Interval for Components & Component Supports,Oct 14,1993-Oct 13,2003. ML18153A5231997-04-24024 April 1997 Proposed Corrected Tech Specs Pages 6.1-3 & 6.1-8 Re Relocation of Fire Protection TS to Updated Final Safety Analysis Rept ML18153A5031997-03-18018 March 1997 Proposed Tech Specs Rev to Section 4.15 for Surry Power Station to Include Pp Inadvertently Omitted from 970203 Request for Amend to Licenses DPR-32 & DPR-37 ML18153A4921997-02-0303 February 1997 Proposed Tech Specs Re Deletion of Specific ASME Section XI Code Ref ML18153A6351996-11-26026 November 1996 Proposed Tech Specs Re Removal of Record Retention Requirements,Per GL 95-06 & Administrative Ltr 95-06 ML18153A0671996-09-12012 September 1996 Proposed Tech Specs Re Relocation of Fire Protection Requirements ML18151A9761996-08-13013 August 1996 Cycle 14 Startup Physics Test Rept. W/960830 Ltr ML20134J9861996-07-30030 July 1996 /Unit 2 Fuel Assembly Insp Program ML18152A4701996-06-13013 June 1996 Cycle 13 Control Rod Performance Test Results. ML18153A6901996-04-15015 April 1996 Proposed Tech Specs,Clarifying Applicability of Quadrant Power Tilt Ration Requirements ML18153A5391996-03-21021 March 1996 Proposed Tech Specs Re Charcoal Filter Testing Clarification ML18153A5271996-03-14014 March 1996 Proposed Tech Specs,Permitting Use of 10CFR50 App J,Option B,performance-based Containment Lrt ML18153A5801996-01-30030 January 1996 Proposed Tech Specs Re Reactor Coolant Sys Liquid Sampling ML18152A0571995-12-20020 December 1995 Startup Physics Test Rept,Surry Unit 1,Cycle 14. W/960111 Ltr ML18153A6761995-11-20020 November 1995 Proposed Tech Specs Re App J Option B,performance-based Containment Leakage Rate Testing ML18151A6421995-08-0101 August 1995 Change 3 to Rev 0 to Third Interval IST Program ML18153A7141995-07-20020 July 1995 Proposed Tech Specs Establishing New Setpoint Limit for SG high-high Level & Provides More Restrictive Setting Limits for Certain Rps/Esfas Setpoints ML18153A6991995-07-14014 July 1995 Proposed Tech Specs,Providing Two H Allowed Outage Time for One RHR Pump to Accommodate Plant Safety,Emergency Power Sys Surveillance Testing & Permit Depressurizing SI Accumulators in Lieu of Accumulator Isolation ML18153A8371995-06-0808 June 1995 Proposed Tech Specs,Incorporating Revised Pressure/Temp Limits & Associated Ltops Setpoint That Will Be Valid to end-of-license ML20083C9951995-05-0808 May 1995 Rev 0 to Surry Unit 2,Cycle 13 Startup Physics Tests Rept ML18153B2301995-02-14014 February 1995 Proposed Tech Specs Re App J Testing Requirements ML18153B2131995-01-24024 January 1995 Proposed Tech Specs,Modifying as-found Test Acceptance Criterion for Pressurizer Safety Valves ML18153B1621994-11-29029 November 1994 Proposed Tech Specs Implementing Zirlo Fuel Cladding ML18153B1581994-11-22022 November 1994 Proposed Tech Specs,Deleting Unnecessary Descriptive Phrases Re Number of Cells in Station & EDG Batteries ML18153B1501994-11-10010 November 1994 Proposed Tech Specs Re Changes to TS Will Clarify SR for Reactor Protection & Engineered Safeguard Sys Instrumentation & Actuation Logic ML18153B0941994-10-11011 October 1994 Proposed Tech Specs Surveillance Frequencies for Hydrogen Analyzers ML18152A5061994-09-0606 September 1994 Proposed Tech Specs Re Mgt Safety Review Committee & Station Nuclear Safety & Operating Committee Responsibilities ML18152A1191994-08-30030 August 1994 Proposed Tech Specs to Accomodate Core Uprating 1999-08-06
[Table view] |
Text
I
- e ATTACHMENT I Supplemental Technical Specification Change Surry Power Station Units I and 2
(
--****-. - --- --.---~-----
8807260307 880718 PDR ADOCK 05000280 P PDC
e TS 3.8-1 3.8 CONTAINMENT App 1i cabil i ty Applies to the integrity and operating pressure of the reactor containment.
Objective To define the 1imiting operating status of the reactor containment for unit operation.
Specification A. Containment Integrity and Operating Pressure
- 1. The containment integrity, as defined in TS Section 1.0, shall not be violated unless the reactor is in the cold shutdown condition .. *
- 2. The reactor containment shall not be purged whenever the Reactor Coolant System temperature is above 200°F.
- 3. The inside and outside isolation valves in the steam jet air ejector suction line shall be locked, sealed or otherwise secured closed whenever the Reactor Cool ant System temperature is above 200°F.
- 4. The Reactor Cool ant System temperature and. pressure must not exceed 350°F and 450 psig, respectively, unless the air partial pressure in the containment is at a value equal to, or below, that specified in TS Figure 3.8-1.
- 5. The containment integrity shall not be violated when the reactor vessel head is unbolted unless* a shutdown margin greater than 5 percent fik/k is maintained.
- In the event of failure of the personnel airlock inner door seal to meet the leakage test acceptance criteria, the outer personnel airlock door may be opened for a period of ti me not to exceed fifteen minutes with an annual cumulative time not to exceed one hour per year to allow access for the repair and retest of the inner door.
ATTACHMENT 2 Discussion of Supplemental Change
e Discussion of Supplemental Change Discussion of Proposed Change As discussed in our submittal, Serial 88-100, dated April 26, 1988, access to the containment while in a subatmospheric condition is performed by equalizing and opening the airlock outer door and then closing and sealing the outer door. The pressure in the airlock is then equalized with the containment and the inner door is opened for the final access. This method ensures that at least one door on the personnel airlock is properly closed and sealed whenever the containment is in a subatmospheric condition. Interlocks provide additional assurance that the doors cannot be opened simultaneously while in a subatmospheric condition.
Fo 11 owing the final use of the airlock, the seals on the inner and outer personnel airlock doors are tested at equal to or greater than the peak calculated accident pressure. If the seal on the outer door fails to pass the acceptance criteria of the test, the inner door is verified to be properly closed and sealed and the outer door seal is repaired and retested. If the inner door seal fails, the outer door is verified to be properly closed and sealed. However, the on 1y accept ab 1e method for repair and retest of the inner seal is by reopening the outer door to a11 ow access to the inner door seal . During this brief period, the containment integrity requirements as defined in T. S. Section 1. H. 4 cannot be met s i nee the inner door wi 11 be closed but may not be properly sealed.
The proposed Technical Specifications change will provide for the access to the inner door for repair and retest of the inner door. Upon entry into the personnel airlock, the outer door will be properly closed and sealed prior to initiating repair of the inner door.
Discussion of Supplement The proposed change would permit the outer airlock ~oor to be opened "briefly" to allow access for repair and retest of the inner door. The time that the outer door may be opened for such activities was not explicitly identified in the proposed change. As a result of discussions with the NRC, a time limit of fifteen minutes per entry and an annual cumulative time limit of one hour is proposed as a supplemental clarification to address the concern.
The 50.92 evaluation of the original submittal concluded that the proposed change did not constitute a significant safety hazard. That determination was based in part on the qualitative assessment that the probability of a design base accident occurring during the brief period of time that the outer door is opened for access to repair the inner door seal is insignificant. Clarifying the concept of brief access by specifying a time limit per entry and an annual cumulative time limit is more restrictive than the proposed change and therefore does not alter the conclusions of the initial 50.92 evaluation. As such, the initial 50.92 significant hazards consideration remains bounding.