| | {{#Wiki_filter:A Systematic Engineering Approach to Degraded Voltage Harvey Leake Palo Verde Nuclear Generating g Station IEEE Subcommittee 4 IEEE 741 Working Group Degraded Grid Voltage Protection Workshop June 28-29, 2011 |
| | |
| | General Principles Our regulatory system must protect public health, welfare, safety, and our environment. It must be based on the best available science science (Executive Order 13563) |
| | Regulations should be based on the best available knowledge from research and operational experience. (NRC Principles of Good Regulation) 2 |
| | |
| | Definitions Degraded Voltage: Voltage < minimum needed to ensure essential load equipment operates without damage or malfunction DVR Dropout Setting: Nominal setpoint at which, during a decrease in voltage, the degraded voltage relay begins timing out DVR Reset Setting: Nominal setpoint at which, during an increase in voltage, the degraded voltage relay ceases timing out Interrupted Flow Event: Design basis event in which injection is established from offsite power supply, then interrupted 3 |
| | |
| | LOCA with Degraded Voltage Draft RIS Approach DVR dropout voltage 1 |
| | 2 Questions to consider: |
| | Voltage at Safety Bus LOCA / degraded voltage occcurs |
| | : 1. Is flat voltage profile credible? |
| | B Bounding? |
| | di ? |
| | : 2. Is assumed timing of DVR actuation 3 (accident analysis time) credible? |
| | : 3. Injection flow established prior to DVR timeout will be interrupted. |
| | Accident analysis for this event? |
| | Will resequencing be successful? |
| | Assume loads resequence onto diesel generator DVR timeout Time |
| | |
| | LOCA with Degraded Voltage Components of Voltage Profile Switchyard Voltage Degradation due to Generator Trip (Millstone effect) 1 Voltage 0.8 0 40 Time (seconds) |
| | Energization of Safety Loads 1 |
| | Voltage 0.9 0 40 Time (seconds) |
| | Fast Bus Transfer 1 |
| | Voltage 0.9 0 40 Time (seconds) 5 |
| | |
| | LOCA with Degraded Voltage Considering Best Available Science 1 DVR reset voltage 2 |
| | DVR dropout voltage Voltage at Safety Bus Insights: |
| | : 1. V 1 Voltage lt profile fil iis ttransient, i t nott fl flatt LOCA occurs |
| | : 2. DVR timeout unlikely to start at T=0, so actuation time > time delay setting 3 |
| | : 3. How to analyze interrupted flow effect? |
| | - Accident analysis is for simultaneous LOOP/LOCA, not interrupted flow scenario |
| | - Hydraulic effects (GSI-171)? |
| | - Will safety equipment successfully resequence onto EDG?(GSI-171)? |
| | Time DVR timeout 6 |
| | |
| | LOCA with Degraded Voltage Conclusions DVRs provide unsatisfactory protection against this scenario |
| | - Actuation would result in an unanalyzed interrupted flow event Preventative strategy: |
| | - Interrupted flow events |
| | - Degraded voltage events 7 |
| | |
| | Prevention Strategy Considering Best Available Science DVR reset voltage DVR dropout voltage Voltage at Safety Bus |
| | * Criteria LOCA occurs Minimum credible steady-state voltage following automatic load actuation DVR reset voltage setting Longest transient voltage excursions below reset voltage setting < DVR time delay setting |
| | * Effectively prevents interrupted flow scenario Time 8 |
| | |
| | DVR Voltage Setting Analysis Draft RIS Guidance calculation of voltages at terminals or contacts of all safety related equipment with the voltage at the DVR monitored bus at the DVR dropout setting, setting providing the necessary design basis for the DVR voltage settings. In this manner, the DVR ensures adequate operational (starting and running) voltage to all safety related equipment. |
| | 9 |
| | |
| | DVR Voltage Setting Analysis Bottom Up Approach DVR dropout voltage Voltage at Safety Bus |
| | * Does not demonstrate that the DVR ensures adequate operational (starting and running) voltage to all safety related equipment? |
| | LOCA occurs DVR assumed not to actuate |
| | * Flat voltage profile provides no insight regarding protection during transient conditions Motor starting LOCA/generator trip Time 10 |
| | |
| | DVR Voltage Setting Analysis Consequence if DVR Does Not Reset DVR reset voltage DVR dropout voltage Voltage at Safety Bus |
| | * Interrupted flow event will occur if steady-state LOCA occurs voltage following automatic load actuation is < DVR reset voltage setting |
| | * Draft RIS suggests LOCA with degraded voltage should be analyzed, but does not discuss transient voltage characteristic nor interrupted flow effect Time DVR timeout 11 |
| | |
| | Systematic Engineering Approach |
| | : 1. Begin with clear descriptions of postulated initiating events and conditions |
| | * Consider operating experience Generator trip was the initiating event for the 1976 Millstone event |
| | : 2. Identify design requirements and objectives 2 |
| | : 3. Perform necessary research to obtain pertinent information |
| | * Develop credible and bounding voltage profiles for each postulated scenario |
| | : 4. Establish viability of proposed solutions by analyzing effect of voltage profile 12 |
| | |
| | Probabilistic Considerations Example Figure studies conducted during resolution of the issue showed that the contribution to CDF from the sequence of events was far less than originally anticipated Thus, the issue was RESOLVED with no new requirements. (GSI-171) 105 Probability of being at given steady-100 state voltage following sequencing Voltage (% |
| | %) |
| | Probability of consequential LOOP & interrupted flow not high enough to be a concern per GSI-171 95 90 DVR Tolerance Band Should consequential degraded voltage region be a concern? |
| | 85 0 0.2 0.4 0.6 0.8 1 Probability (given a postulated accident) 13}} |
|
---|
Category:Slides and Viewgraphs
MONTHYEARML24262A1052024-09-20020 September 2024 Pre-Submittal Presentation Slides - 1R25 Pzr Nozzle Life of Repair - Relief Request 73 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML24236A7032024-08-22022 August 2024 Pre-Submittal Meeting Slides to Support August 29, 2024 Aps/Westinghouse Thermal Design Procedure (Wtdp) Meeting ML24212A3392024-08-0101 August 2024 August 1, 2024, Public Meeting on Potential Palisades Nuclear Plant Restart Presentation ML24192A3262024-07-12012 July 2024 Licensee Slides to Support Pre-Submittal Meeting – Relief Request 71 Slides ML24192A3402024-07-12012 July 2024 Licensee to Support Pre-Submittal Meeting - Relief Request 72 Slides ML24275A2332024-06-28028 June 2024 APS Slides Supporting Preapplication Meeting Regarding Safety Injection Tank Pressure Band ML24155A2112024-06-0707 June 2024 VRR-02: Exercise Test Frequency Reduction (Slides) ML24155A2122024-06-0707 June 2024 VRR-03: SOV Test Criteria (Slides) ML24038A1742024-02-0707 February 2024 Pre-submittal Meeting Slides ML24019A1512024-01-22022 January 2024 Slides - Modification of Browns Ferry Technical Specifications to Eliminate LCO 3.3.2.1 Actions C.2.1.1 and C.2.1.2 for Rod Worth ML24003A8532024-01-0303 January 2024 January 4, 2024 Presubmittal Meeting Presentation-Risk Informed Process for Evaluations (RIPE) License Amendment Request for Safety Injection Tank (SIT) LCO (EPID: L?2023?LRM-0108) ML23296A0162023-10-20020 October 2023 October 20, 2023 Presubmittal Meeting Presentation - 1R24 Pressurizer Nozzle Repair - RR-70 (EPID: L?2023?LLR-0057) ML23240A3232023-08-31031 August 2023 APS Presentation Slides for Pre-Submittal Meeting on 8/31/23, Alloy-600 Management Program Plan ML23192A0102023-07-11011 July 2023 NRC RIPE 7-11-23 Public Meeting Presentation Slides ML23144A0252023-05-25025 May 2023 APS Presentation Slides for Pre-Submittal Meeting on 5/25/23, Przr Surge Line ML23093A0252023-04-30030 April 2023 April 5, 2023, Presubmittal Meeting Presentation - Containment Temperature and Safety Injection Tank Volume Requirements LAR ML23055B0572023-03-0101 March 2023 March 1, 2023 Presubmittal Meeting Presentation - Request for Use of Mururoa V4F1 and MTH2 Supplied Air Suits (EPID: L?2023?LRM-0012) ML22312A5952022-11-0808 November 2022 Independent Spent Fuel Storage Installation, Submittal of Annual Financial Reports 2021 ML22299A1812022-10-26026 October 2022 Presubmittal Meeting Presentation - License Amendment Request - Adoption of TSTF-107-A Separate Control Rods That Are Untrippable Versus Inoperable and Change to TS 3.1.5 Condition B (EPID: L?2021?LRM-0081) ML22096A0052022-04-0606 April 2022 TSTF-487 LAR Pre-submittal Public Meeting Presentation Slides ML22025A0012022-01-25025 January 2022 1/25/22 Pre-submittal Meeting Presentation Slides for RR-69 to Extend Containment Tendon Inspection by Three Months Beyond 2/8/22 ML21342A0502021-12-0808 December 2021 TSTF-567 LAR Pre-submittal Public Meeting Presentation Slides ML21320A1032021-11-17017 November 2021 RIPE Exemption 11-17-21 Pre-submittal Public Meeting Presentation Slides ML21278B0912021-10-0606 October 2021 Presubmittal Meeting with Arizona Public Service Company Regarding Relief Request No. 68 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 (EPID L-2021-LRM-0104) (Slides) ML21243A5432021-09-0101 September 2021 Request for Partial Exemption from 10 CFR 50.62(c)(1) Risk-Informed Process for Evaluations (RIPE) ML21194A2502021-08-10010 August 2021 RIC 2021 - Ai EPRI-Artificial Intelligence and Development at EPRI ML21165A1832021-06-14014 June 2021 RR-67 6-16-21 Pre-Submittal Public Meeting Presentation Slides ML21130A6462021-05-13013 May 2021 Pre-Submittal Meeting with NRC on May 13, 2021 Application for Transfer of Minority Interests in Palo Verde Nuclear Generating Station, Units 1 and 2 Subject to Expiring Leases ML21131A0132021-05-13013 May 2021 License Transfer from Pnm to SRP, 5-13-21 Pre-submittal Public Meeting Presentation Slides ML21055A8502021-02-24024 February 2021 Public Meeting Summary ML21025A0032021-01-26026 January 2021 Risk-Informed Process for Evaluations (RIPE) - NEI Public Meeting Presentation Slides ML21025A0042021-01-25025 January 2021 Risk-Informed Process for Evaluations (RIPE) - NRC Public Meeting Presentation Slides ML21011A2752021-01-0606 January 2021 License Amendment Request (LAR) to Revise Containment Leakage Rate Testing Program Frequencies - NRC Pre-Submittal Meeting, January 6, 2021 (Presentation Slides) ML20171A2352020-06-24024 June 2020 Inservice Testing - Supplemental Position Indication Relief Request - NRC Pre-Application Meeting - June 24, 2020 ML19060A2982019-03-0101 March 2019 Transmittal of Audit Presentation Slides Regarding License Amendment Request and Exemption Request to Support the Implementation of Framatome CE16HTP Fuel ML17003A0762017-01-10010 January 2017 Regulatory Audit Report for the November 2-3, 2016, Audit at the Westinghouse Facility in Rockville, MD, for the License Amendment and Exemption Requests Associated with Next Generation Fuel (CAC Nos. MF8076-MF8081) ML17003A0352017-01-0404 January 2017 Summary of Pre-Application Meeting with Arizona Public Service to Discuss a Proposed Second Emergency License Amendment Request to Revise Technical Specification 3.8.1, AC (Alternating Current) Sources - Operating, for Palo Verde Nuclear ML17003A0332016-12-29029 December 2016 Enclosure 2 - APS Meeting Slides ML17003A0862016-11-0303 November 2016 Enclosure 2 Slides Regulatory Audit Report for November 2-3, 2016 ML16253A4112016-09-0707 September 2016 Palo Verde Nuclear Generating Station Generic Letter 2004-02 - September 7, 2016 ML16083A4722016-03-24024 March 2016 NRC Subsequent Pre-Submittal Meeting Next Generation Fuel - Palo Verde, Units 1, 2, and 3 ML16014A1102016-01-20020 January 2016 Draft APS Slides for January 20, 2015, Public Meeting with APS Regarding Upcoming Next Generation Fuel License Amendment Request for Palo Verde, Units 1, 2, and 3 ML15348A0542015-12-15015 December 2015 Slides for December 17, 2015 Public Meeting with APS on Resolution of GL 2004-02 ML15244B2632015-08-27027 August 2015 Slides for Public Meeting with Arizona Public Service Company to Discuss License Amendment Request for Palo Verde Regarding Revised Methodology for Spent Fuel Pool Criticality Analysis ML15236A1342015-08-26026 August 2015 Presentation Slides for Public Meeting with Arizona Public Service Generic Letter 2004-02 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML15159B2972015-06-0909 June 2015 Near-Term Task Force Recommendation 2.1 (R2.1) Seismic Hazard Evaluation - Arizona Public Service, Palo Verde Nuclear Generating Station Public Meeting - June 9, 2015 ML15156B3312015-06-0909 June 2015 Public Meeting Slides on R2.1 Seismic Hazard Re-Evaluation ML15134A3592015-05-11011 May 2015 5/11/2015, Meeting Slide Regarding Pre-Submittal Meeting for Palo Verde Unit 1, 2, and 3 Updated Spent Fuel Pool Criticality Analysis ML15126A2072015-05-11011 May 2015 Presentation Slides for Prelicensing Meeting with Arizon Public Service Company to Discuss License Amendment Request for Palo Verde, Units 1, 2, and 3, ML15103A2882015-04-0909 April 2015 Presentation on Potential Relief Request About Pressure Boundary Leakage on Reactor Coolant Pump 2A Pipe Nozzle 2024-09-20
[Table view] Category:Meeting Briefing Package/Handouts
MONTHYEARML24262A1052024-09-20020 September 2024 Pre-Submittal Presentation Slides - 1R25 Pzr Nozzle Life of Repair - Relief Request 73 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML24236A7032024-08-22022 August 2024 Pre-Submittal Meeting Slides to Support August 29, 2024 Aps/Westinghouse Thermal Design Procedure (Wtdp) Meeting ML24212A3392024-08-0101 August 2024 August 1, 2024, Public Meeting on Potential Palisades Nuclear Plant Restart Presentation ML24192A3262024-07-12012 July 2024 Licensee Slides to Support Pre-Submittal Meeting – Relief Request 71 Slides ML24192A3402024-07-12012 July 2024 Licensee to Support Pre-Submittal Meeting - Relief Request 72 Slides ML24275A2332024-06-28028 June 2024 APS Slides Supporting Preapplication Meeting Regarding Safety Injection Tank Pressure Band ML24155A2112024-06-0707 June 2024 VRR-02: Exercise Test Frequency Reduction (Slides) ML24155A2122024-06-0707 June 2024 VRR-03: SOV Test Criteria (Slides) ML24038A1742024-02-0707 February 2024 Pre-submittal Meeting Slides ML24019A1512024-01-22022 January 2024 Slides - Modification of Browns Ferry Technical Specifications to Eliminate LCO 3.3.2.1 Actions C.2.1.1 and C.2.1.2 for Rod Worth ML24003A8532024-01-0303 January 2024 January 4, 2024 Presubmittal Meeting Presentation-Risk Informed Process for Evaluations (RIPE) License Amendment Request for Safety Injection Tank (SIT) LCO (EPID: L?2023?LRM-0108) ML23240A3232023-08-31031 August 2023 APS Presentation Slides for Pre-Submittal Meeting on 8/31/23, Alloy-600 Management Program Plan ML23192A0102023-07-11011 July 2023 NRC RIPE 7-11-23 Public Meeting Presentation Slides ML23144A0252023-05-25025 May 2023 APS Presentation Slides for Pre-Submittal Meeting on 5/25/23, Przr Surge Line ML23093A0252023-04-30030 April 2023 April 5, 2023, Presubmittal Meeting Presentation - Containment Temperature and Safety Injection Tank Volume Requirements LAR ML23090A1392023-04-0404 April 2023 April 4, 2023 Presubmittal Meeting Presentation - LAR to Adopt TSTF-266, Eliminate the Remote Shutdown System Table of Instrumentation and Controls (EPID: L?2023?LRM-0017) ML23055B0572023-03-0101 March 2023 March 1, 2023 Presubmittal Meeting Presentation - Request for Use of Mururoa V4F1 and MTH2 Supplied Air Suits (EPID: L?2023?LRM-0012) ML22096A0052022-04-0606 April 2022 TSTF-487 LAR Pre-submittal Public Meeting Presentation Slides ML22025A0012022-01-25025 January 2022 1/25/22 Pre-submittal Meeting Presentation Slides for RR-69 to Extend Containment Tendon Inspection by Three Months Beyond 2/8/22 ML21342A0502021-12-0808 December 2021 TSTF-567 LAR Pre-submittal Public Meeting Presentation Slides ML21320A1032021-11-17017 November 2021 RIPE Exemption 11-17-21 Pre-submittal Public Meeting Presentation Slides ML21194A2502021-08-10010 August 2021 RIC 2021 - Ai EPRI-Artificial Intelligence and Development at EPRI ML21131A0132021-05-13013 May 2021 License Transfer from Pnm to SRP, 5-13-21 Pre-submittal Public Meeting Presentation Slides ML21025A0032021-01-26026 January 2021 Risk-Informed Process for Evaluations (RIPE) - NEI Public Meeting Presentation Slides ML21025A0042021-01-25025 January 2021 Risk-Informed Process for Evaluations (RIPE) - NRC Public Meeting Presentation Slides ML20171A2352020-06-24024 June 2020 Inservice Testing - Supplemental Position Indication Relief Request - NRC Pre-Application Meeting - June 24, 2020 ML19192A0972019-07-11011 July 2019 License Amendment Request for Emergency Plan, July 11, 2019 ML18299A0722018-09-26026 September 2018 Ionizing Radiation Factsheet-Veterans - Information for Veterans and Their Families ML17320A1932017-11-15015 November 2017 NRC Public Meeting, Treatment of Mitigating Strategies in Risk Informed Decision Making ML17003A0332016-12-29029 December 2016 Enclosure 2 - APS Meeting Slides ML16357A6872016-12-20020 December 2016 One-Time License Amendment Request Unit 3 Train B Diesel Generator ML17003A0862016-11-0303 November 2016 Enclosure 2 Slides Regulatory Audit Report for November 2-3, 2016 ML16253A4112016-09-0707 September 2016 Palo Verde Nuclear Generating Station Generic Letter 2004-02 - September 7, 2016 ML16083A4722016-03-24024 March 2016 NRC Subsequent Pre-Submittal Meeting Next Generation Fuel - Palo Verde, Units 1, 2, and 3 ML16014A1102016-01-20020 January 2016 Draft APS Slides for January 20, 2015, Public Meeting with APS Regarding Upcoming Next Generation Fuel License Amendment Request for Palo Verde, Units 1, 2, and 3 ML15244B2632015-08-27027 August 2015 Slides for Public Meeting with Arizona Public Service Company to Discuss License Amendment Request for Palo Verde Regarding Revised Methodology for Spent Fuel Pool Criticality Analysis ML15236A1342015-08-26026 August 2015 Presentation Slides for Public Meeting with Arizona Public Service Generic Letter 2004-02 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML15159B2972015-06-0909 June 2015 Near-Term Task Force Recommendation 2.1 (R2.1) Seismic Hazard Evaluation - Arizona Public Service, Palo Verde Nuclear Generating Station Public Meeting - June 9, 2015 ML15156B3312015-06-0909 June 2015 Public Meeting Slides on R2.1 Seismic Hazard Re-Evaluation ML15156B3522015-06-0404 June 2015 Draft Slides for Public Meeting with Arizona Public Service Company Ongoing Resolution of Generic Letter 2004-02 for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML15126A2072015-05-11011 May 2015 Presentation Slides for Prelicensing Meeting with Arizon Public Service Company to Discuss License Amendment Request for Palo Verde, Units 1, 2, and 3, ML15134A3592015-05-11011 May 2015 5/11/2015, Meeting Slide Regarding Pre-Submittal Meeting for Palo Verde Unit 1, 2, and 3 Updated Spent Fuel Pool Criticality Analysis ML15103A2882015-04-0909 April 2015 Presentation on Potential Relief Request About Pressure Boundary Leakage on Reactor Coolant Pump 2A Pipe Nozzle ML15070A2522015-02-18018 February 2015 Pre-Submittal Public Meeting Final Slides on Risk-Informed Completion Times. ML15042A4152015-02-11011 February 2015 Pre-Submittal Public Meeting Draft Slides on Risk- Informed Completion Times ML14184B4112014-06-11011 June 2014 Nrc/Nei/Utility MTG 6/11/14 ML14149A5092014-04-23023 April 2014 4/23/14 Meeting Slide for Palo Verde Nuclear Generating Station, Units 1, 2, and 3 Re. Sig Tube Inspection ML14098A1832014-04-0202 April 2014 4/2/2014 Meeting Slide for Bottom-Mounted Instrument (Bmi) Relief Request 52 Pre-Submittal Meeting ML13309A7202013-11-0505 November 2013 Meeting Presentation for November 5, 2013 Public Meeting Regarding Incorporation of NEI 11-04 Into the QA Program at Palo Verde Nuclear Generating Station, Units 1, 2, and 3 ML13308C3402013-11-0404 November 2013 SG Unit 3 Telephone Call 2024-09-20
[Table view] |
Text
A Systematic Engineering Approach to Degraded Voltage Harvey Leake Palo Verde Nuclear Generating g Station IEEE Subcommittee 4 IEEE 741 Working Group Degraded Grid Voltage Protection Workshop June 28-29, 2011
General Principles Our regulatory system must protect public health, welfare, safety, and our environment. It must be based on the best available science science (Executive Order 13563)
Regulations should be based on the best available knowledge from research and operational experience. (NRC Principles of Good Regulation) 2
Definitions Degraded Voltage: Voltage < minimum needed to ensure essential load equipment operates without damage or malfunction DVR Dropout Setting: Nominal setpoint at which, during a decrease in voltage, the degraded voltage relay begins timing out DVR Reset Setting: Nominal setpoint at which, during an increase in voltage, the degraded voltage relay ceases timing out Interrupted Flow Event: Design basis event in which injection is established from offsite power supply, then interrupted 3
LOCA with Degraded Voltage Draft RIS Approach DVR dropout voltage 1
2 Questions to consider:
Voltage at Safety Bus LOCA / degraded voltage occcurs
- 1. Is flat voltage profile credible?
B Bounding?
di ?
- 2. Is assumed timing of DVR actuation 3 (accident analysis time) credible?
- 3. Injection flow established prior to DVR timeout will be interrupted.
Accident analysis for this event?
Will resequencing be successful?
Assume loads resequence onto diesel generator DVR timeout Time
LOCA with Degraded Voltage Components of Voltage Profile Switchyard Voltage Degradation due to Generator Trip (Millstone effect) 1 Voltage 0.8 0 40 Time (seconds)
Energization of Safety Loads 1
Voltage 0.9 0 40 Time (seconds)
Fast Bus Transfer 1
Voltage 0.9 0 40 Time (seconds) 5
LOCA with Degraded Voltage Considering Best Available Science 1 DVR reset voltage 2
DVR dropout voltage Voltage at Safety Bus Insights:
- 1. V 1 Voltage lt profile fil iis ttransient, i t nott fl flatt LOCA occurs
- 2. DVR timeout unlikely to start at T=0, so actuation time > time delay setting 3
- 3. How to analyze interrupted flow effect?
- Accident analysis is for simultaneous LOOP/LOCA, not interrupted flow scenario
- Hydraulic effects (GSI-171)?
- Will safety equipment successfully resequence onto EDG?(GSI-171)?
Time DVR timeout 6
LOCA with Degraded Voltage Conclusions DVRs provide unsatisfactory protection against this scenario
- Actuation would result in an unanalyzed interrupted flow event Preventative strategy:
- Interrupted flow events
- Degraded voltage events 7
Prevention Strategy Considering Best Available Science DVR reset voltage DVR dropout voltage Voltage at Safety Bus
- Criteria LOCA occurs Minimum credible steady-state voltage following automatic load actuation DVR reset voltage setting Longest transient voltage excursions below reset voltage setting < DVR time delay setting
- Effectively prevents interrupted flow scenario Time 8
DVR Voltage Setting Analysis Draft RIS Guidance calculation of voltages at terminals or contacts of all safety related equipment with the voltage at the DVR monitored bus at the DVR dropout setting, setting providing the necessary design basis for the DVR voltage settings. In this manner, the DVR ensures adequate operational (starting and running) voltage to all safety related equipment.
9
DVR Voltage Setting Analysis Bottom Up Approach DVR dropout voltage Voltage at Safety Bus
- Does not demonstrate that the DVR ensures adequate operational (starting and running) voltage to all safety related equipment?
LOCA occurs DVR assumed not to actuate
- Flat voltage profile provides no insight regarding protection during transient conditions Motor starting LOCA/generator trip Time 10
DVR Voltage Setting Analysis Consequence if DVR Does Not Reset DVR reset voltage DVR dropout voltage Voltage at Safety Bus
- Interrupted flow event will occur if steady-state LOCA occurs voltage following automatic load actuation is < DVR reset voltage setting
- Draft RIS suggests LOCA with degraded voltage should be analyzed, but does not discuss transient voltage characteristic nor interrupted flow effect Time DVR timeout 11
Systematic Engineering Approach
- 1. Begin with clear descriptions of postulated initiating events and conditions
- Consider operating experience Generator trip was the initiating event for the 1976 Millstone event
- 2. Identify design requirements and objectives 2
- 3. Perform necessary research to obtain pertinent information
- Develop credible and bounding voltage profiles for each postulated scenario
- 4. Establish viability of proposed solutions by analyzing effect of voltage profile 12
Probabilistic Considerations Example Figure studies conducted during resolution of the issue showed that the contribution to CDF from the sequence of events was far less than originally anticipated Thus, the issue was RESOLVED with no new requirements. (GSI-171) 105 Probability of being at given steady-100 state voltage following sequencing Voltage (%
%)
Probability of consequential LOOP & interrupted flow not high enough to be a concern per GSI-171 95 90 DVR Tolerance Band Should consequential degraded voltage region be a concern?
85 0 0.2 0.4 0.6 0.8 1 Probability (given a postulated accident) 13