ML11137A043: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 05/12/2011
| issue date = 05/12/2011
| title = Request for a List of Documentation to Determine There Are No CASS ASME III Class 1 Valve Less than Four Inches Installed at Columbia
| title = Request for a List of Documentation to Determine There Are No CASS ASME III Class 1 Valve Less than Four Inches Installed at Columbia
| author name = Mostala A A
| author name = Mostala A
| author affiliation = Energy Northwest
| author affiliation = Energy Northwest
| addressee name = Cunanan A D
| addressee name = Cunanan A
| addressee affiliation = NRC/NRR/DLR
| addressee affiliation = NRC/NRR/DLR
| docket = 05000397
| docket = 05000397

Revision as of 17:21, 10 July 2019

Request for a List of Documentation to Determine There Are No CASS ASME III Class 1 Valve Less than Four Inches Installed at Columbia
ML11137A043
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 05/12/2011
From: Mostala A
Energy Northwest
To: Cunanan A
Division of License Renewal
References
Download: ML11137A043 (3)


Text

1 NRR-PMDAPEm Resource From: Mostala, Abbas A. [AAMOS TALA@energy-northwest.com]

Sent: Thursday, May 12, 2011 2:48 PM To: Cunanan, Arthur Cc: Min, Seung; Mostala, Abbas A.

Subject:

RE: Request for a list of documentation to determine there are no CASS ASME III Class 1 valve less than four inches installed at Columbia Hello Arthur, The documents reviewed to determ ine if there are any CASS va lves less than 4 inches installed at Columbia were: system fl ow diagrams for ASME III Class 1, valve drawings, system design specifications, purchasing requirements, and valve design specifications. This review did not identify any CASS valves less than 4 inches installed at Columbia.

The original LRA assumed that there were ASME III Class 1 CASS valves less than 4 inches because the valve design specificati on allowed the use of CASS valves as an alternate.

To determine the number of installed ASM E III Class 1 CASS valves less than 4 inches at Columbia , the system flow diagrams were reviewed for ASME III Class 1 lines that had valves less than 4 inches . Valve drawings or purchasing requirements were reviewed for these valv es to determine the material. No ASME III Class 1 CASS valves less than 4 inches were identified.

Action Request 234294 Assignment 17 will revise the valve Design Specification to only allow the future use of CASS valves as an alternate at Columbia with certain requirements associated with License R enewal, such as a new Aging Management Program per NUREG 1801 (GALL). Thanks & Regards, Abbas Mostala, , PE License Renewal Project ManagerEnergy NorthwestColumbia Genera ting Station From: Cunanan, Arthur [1]

Sent: Wednesday, May 11, 2011 9:54 AM To: Mostala, Abbas A.

Cc: Min, Seung

Subject:

Request for a list of documentation to determine there are no CASS ASME III Class 1 valve less than four inches installed at Columbia Abbas, 2 By letter dated April 21, 2011 (GO2-11-083) (ADAM accession number: ML11115A098) the applicant stated:

DuringtheconferencecalldiscussedinReference4,EnergyNorthwestagreedtoamendtheLicenseRenewalApplication(LRA)toaddresstheexaminationsofthecastausteniticstainlesssteel(CASS)valvesincludedintheSmallBorePipingProgram(ReferenceRAI3.1.2.3 01).However,duringthereviewofdocumentation,EnergyNorthwestdeterminedthattherearenoCASSASMEIIIclass1valveslessthanfourinchesinstalledatColumbia.Amendment31isprovidedintheEnclosuretoremovethematerialandenvironmentcombinationfromtheLRA. Please provide the staff a list of the documents that the applicant reviewed to determine that there are no

CASS ASME III Class 1 valve less than four inches installed at Columbia.

Response via e-mail is acceptable. The response e-mail will be documented in ADAMS.

Sincerely, Arthur Cunanan Project Manager Division of License Renewal U.S. Nuclear Regulatory Commission 301-415-3897 arthur.cunanan@nrc.gov

Hearing Identifier: NRR_PMDA Email Number: 30 Mail Envelope Properties (11F5592341C9044B8FD83A755C2DA9F70602229C)

Subject:

RE: Request for a list of documentat ion to determine there are no CASS ASME III Class 1 valve less than four inches installed at Columbia Sent Date: 5/12/2011 2:47:45 PM Received Date: 5/12/2011 2:48:03 PM From: Mostala, Abbas A.

Created By: AAMOSTALA@energy-northwest.com Recipients: "Min, Seung" <Seung.Min@nrc.gov> Tracking Status: None "Mostala, Abbas A." <AAMOSTALA@energy-northwest.com> Tracking Status: None "Cunanan, Arthur" <Arthur.Cunanan@nrc.gov> Tracking Status: None Post Office: SERVER153.domain1.energy-northwest.com

Files Size Date & Time MESSAGE 2814 5/12/2011 2:48:03 PM

Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date: Recipients Received: