- GO2-89-065, Forwards Amends 3,4,& 5 to Offsite Dose Calculation Manual Re Tech Spec Section 6.14.2a, Administrative Controls. Amends Cover Semiannual Reporting Requirements & near-field Dilution Factor + (10:57:58, 8 January 2025)
- IR 05000397/1989009 + (10:58:00, 8 January 2025)
- 05000397/LER-1989-007, :on 890316,discovered That Two Tech Spec Surveillance Procedures Re Fire Protection Zones for Standby Svc Water Pump Houses & Power Generation Control Cabinet Inconsistent.Action Statements Implemented + (10:58:02, 8 January 2025)
- GO2-89-064, Forwards Status of Implementation of TMI Action Plan Items for Plant,Per 890414 Request.Implementation of Issue II.F.1.2.B Considered by Util to Be Complete Based on Last Ltr to NRC + (10:58:03, 8 January 2025)
- GO2-89-061, Responds to NRC Re Violations Noted in Insp Rept 50-397/89-09.Corrective Action:Radiological Posting Restored to Correct Configuration.Health Physics Personnel Performing Tour of Plant for Compliance W/Radiological Control Progra + (10:58:04, 8 January 2025)
- ML17285A396 + (10:58:05, 8 January 2025)
- GO2-89-059, Application for Amend to License NPF-21,reducing Age Factor of Div 1 250-volt Dc Battery Sys to 20%,per 10CFR50.59,in Tech Spec 3/4.8.2, DC Sources + (10:58:06, 8 January 2025)
- GO2-89-058, Forwards Proposed Change to NPDES Permit WA-002515-1 Re Monitoring of Residual Chlorine in Cooling Water Blowndown. Evaluation Council Will Consider Request as Formal Permit Mod + (10:58:07, 8 January 2025)
- ML17285A392 + (10:58:08, 8 January 2025)
- GO2-89-055, Confirms Commitments for Compliance W/Atws Rule 10CFR50.62 Re Recirculating Pump Trip,Per 890303 Telcon.Recirculating Pump Trip Logic Trip Scheme Will Be Redesign as Indicated in Encl Diagram + (10:58:09, 8 January 2025)
- IR 05000397/1989004 + (10:58:12, 8 January 2025)
- ML17285A375 + (10:58:14, 8 January 2025)
- ML17285A378 + (10:58:14, 8 January 2025)
- 05000397/LER-1989-004, :on 890226,mobile Crane Brought within Reach of safety-related Structures & Components W/O Safety Evaluation Being Performed.Caused by Lack of Procedures Controlling Use of Mobile Cranes.Crane Removed from Area + (10:58:16, 8 January 2025)
- GO2-89-050, Submits Supplemental Info Re Request for Amend to License Condition 2.C.14 & Removal of Fire Protection Requirements from Tech Specs.Util Requests That NRC Not Act on Request to Delete Paragraphs 6.5.2.8.e & H & 6.8.1.g from Tech Specs + (10:58:17, 8 January 2025)
- GO2-89-054, Submits List of Property & Liability Insurance Coverage in Force for Facility + (10:58:18, 8 January 2025)
- ML17285A366 + (10:58:20, 8 January 2025)
- GO2-89-053, Submits Revised Response to NRC Re Violation B Noted in Insp Rept 50-397/88-24.Corrective Actions: Troubleshooting Procedure Will Be Revised.Addl Info Re Verbal Procedure Deviations Also Encl,Per Request + (10:58:21, 8 January 2025)
- ML17285A364 + (10:58:21, 8 January 2025)
- GO2-89-051, Application for Amend to License NPF-21,revising Tech Specs 3/4.2.6 Re Power Flow Instability & 3/4.2.7 Re Neutron Flux Noise Monitoring in Support of Supply Sys Response to NRC Bulletin 88-007,Suppl 1 + (10:58:23, 8 January 2025)
- ML17285A360 + (10:58:23, 8 January 2025)
- GO2-89-049, Responds to NRC Bulletin 88-010, Nonconforming Molded-Case Circuit Breakers. Measures Taken to Ensure That Only molded-case Circuit Breakers Procured Under 10CFR50,App B QA Program Maintained as Stored Spares + (10:58:25, 8 January 2025)
- ML17285A351 + (10:58:28, 8 January 2025)
- ML17285A348 + (10:58:29, 8 January 2025)
- ML17285A347 + (10:58:30, 8 January 2025)
- ML17285A345 + (10:58:31, 8 January 2025)
- GO2-89-047, Application for Amend to License NPF-21,implementing Requirements of Reg Guide 1.97,Rev 2 for Flux Monitoring Prior to Startup Following Fourth Refueling Outage + (10:58:32, 8 January 2025)
- ML17285A342 + (10:58:32, 8 January 2025)
- GO2-89-046, Forwards Amended Response to Notice of Violation Contained in Insp Rept 50-397/88-40.Corrective Actions:Guidance Document Will Be Prepared to Better Understand Processes Associated W/Relief from Tech Specs Re Vital Switchgear + (10:58:34, 8 January 2025)
- 05000397/LER-1988-036, :on 881118,inconsistency Noted Between Channel Functional Test Surveillance Procedure & Tech Specs for Div 1 4.16 Kv Emergency Bus Undervoltage Degraded Voltage.Caused by Inadequate Procedure.Tech Spec Revised + (10:58:36, 8 January 2025)
- GO2-89-040, Forwards Supplemental Info Re Amend 6 to Offsite Dose Calculation Manual.Richland Potable Water Intake Considered Nearest Public Intake.Info Clarified on Page 8 + (10:58:37, 8 January 2025)
- ML17285A332 + (10:58:38, 8 January 2025)
- 05000397/LER-1989-003, :on 890209,control Room Emergency Filtration Sys Adsorber Charcoal Sample Not Taken After 720 H of Operation.Caused by Misinterpretation of Tech Specs.Charcoal Sample Analyzed & Procedure Revised + (10:58:39, 8 January 2025)
- ML17285A329 + (10:58:40, 8 January 2025)
- ML17285A328 + (10:58:41, 8 January 2025)
- PNO-V-89-018, on 890316,discovered Nonconservative Assumptions Used in post-accident Control Room Exposure Calculations.Dose Could Exceed 200 Rem.Unusual Event Declared.Power Level Restricted to 52% Power + (10:58:42, 8 January 2025)
- ML17285A326 + (10:58:43, 8 January 2025)
- ML17285A325 + (10:58:44, 8 January 2025)
- ML17285A324 + (10:58:45, 8 January 2025)
- GO2-89-038, Application for Amend to License NPF-21,revising Tech Spec Table 4.3.2.1-1, Isolation Actuation Instrumentation Surveillance Requirements to Reflect Enhanced Operating Capabilities of Leak Detection Sys Due to New Equipment + (10:58:46, 8 January 2025)
- TAC:72620 + (10:58:46, 8 January 2025)
- ML17285A323 + (10:58:46, 8 January 2025)
- IR 05000397/1988024 + (10:58:51, 8 January 2025)
- GO2-89-035, Provides Revised Schedule Dates for Commitments Made in Response to Violations Noted in Insp Repts 50-397/87-19 & 50-397/88-41.Plant Procedures 10.25.19 & 11.2.1.2 Will Be Issued by 890417 + (10:58:52, 8 January 2025)
- ML17285A317 + (10:59:02, 8 January 2025)
- ML17285A316 + (10:59:03, 8 January 2025)
- ML17285A313 + (10:59:04, 8 January 2025)
- TAC:71390 + (10:59:05, 8 January 2025)
- ML17285A309 + (10:59:06, 8 January 2025)
- 05000397/LER-1989-002, :on 890130,reactor Scram Occurred Due to Turbine Control Valve Fast Closure Actuation of Reactor Protective Sys Logic.Caused by Equipment Design Deficiency. Damaged 500 Kv Insulator Stack Replaced + (10:59:09, 8 January 2025)
- GO2-89-033, Responds to 890217 Telcon Re Requesting Exemption from 10CFR20,App a, Use of GMR-1 Canisters for Protection Against Radiodine. Util Agrees to Change Attachment I,Item A.5 of Ref Ltr as Listed + (10:59:10, 8 January 2025)
- TAC:68268 + (10:59:10, 8 January 2025)