- ML19338G163 + (18:08:28, 25 December 2024)
- 05000213/LER-1980-015-03, /03L-0:on 801020,while Boiling Down Aerated Drains Tank Waste Evaporator in Preparation for Drumming,Level Indication Was Lost.Caused by Failed Gasket on Discharge Piping of Reboiler Pump.Gasket Replaced + (18:08:30, 25 December 2024)
- 05000267/LER-1980-053, Forwards LER 80-053/03L-0 + (18:08:32, 25 December 2024)
- 05000213/LER-1980-014-03, /03L-0:on 800926,during Surveillance Testing of Diesel Fire Pump,Pump Discharge Pressure at 2500 RPM Found Below Tech Spec Limit.Caused by Low Operating RPM of Diesel Motor.Adjustments Made to Increase Motor RPM + (18:08:34, 25 December 2024)
- 05000313/LER-1980-037, Forwards LER 80-037/03L-0 + (18:08:35, 25 December 2024)
- 05000334/LER-1980-075-01, /01T-0:on 801008,determined That Overstress Condition Exists on Reactor Coolant Fill Header from High Head Charging Pumps.Cause Unknown.Necessary Mods Made Prior to Start Up + (18:08:38, 25 December 2024)
- 05000267/LER-1980-054, Forwards LER 80-054/03L-0 + (18:08:42, 25 December 2024)
- 05000259/LER-1980-074-03, /03L-0:on 800924,during Normal Operation,Seismic Monitor SMA2 Found Inoperable.Caused by Failed Printed Wiring Board 100935.Assembly Repaired,Tested & Returned to Svc.Failure Considered Random.No Further Action Planned + (18:08:43, 25 December 2024)
- ML19338G149 + (18:08:47, 25 December 2024)
- 05000293/LER-1980-073-03, /03L-0:on 800917,mgt Review of Records Revealed That Monthly Surveillance Test SP74-41,visual Insp of Energy Piping Outside Containment,Was Not Performed within Required Interval.Caused by Scheduling Error + (18:08:48, 25 December 2024)
- 05000348/LER-1980-057-03, /03L-0:on 800922,during Startup,Rhr Sys Was Removed from Svc & Isolated from RCS at 250 F.Caused by Operator Error.Tech Specs Changed to Clarify Svc Procedure + (18:08:50, 25 December 2024)
- ML19338G146 + (18:08:51, 25 December 2024)
- ML19338G145 + (18:08:55, 25 December 2024)
- 05000293/LER-1980-073, Forwards LER 80-073/03L-0 + (18:08:56, 25 December 2024)
- ML19338G142 + (18:09:04, 25 December 2024)
- 05000293/LER-1980-070-01, /01T-0:on 801010,480 Volt Breaker 52-204 Tripped Twice within 10 Minutes de-energizing 480 Volt Bus B14, Disabling Loop a of Rbccw.Cause Unknown.Breaker Closed,Bus Returned to Svc & Loop a Returned to Normal + (18:09:05, 25 December 2024)
- ML19338G140 + (18:09:07, 25 December 2024)
- 05000293/LER-1980-070, Forwards LER 80-070/01T-0 + (18:09:08, 25 December 2024)
- ML19338G137 + (18:09:09, 25 December 2024)
- ML19338G135 + (18:09:10, 25 December 2024)
- ML19338G136 + (18:09:10, 25 December 2024)
- ML19338G134 + (18:09:11, 25 December 2024)
- 05000267/LER-1980-055-03, /03L-0:on 800918,sampling Requirements of SR Nr 1.1 Were Not Met for Night Shift.Caused by Personnel Oversight.Personnel Have Been Reinstructed as to Procedure Importance + (18:09:13, 25 December 2024)
- 05000366/LER-1980-137-03, /03L-0:on 800929,during Plant Shutdown,While Performing HPCI Turbine Exhaust Diaphragm Functional Test & Calibr,Pressure Switch Actuated Contrary to Tech Spec.Caused by Setpoint Drift.Switch Recalibr & Functionally Tested + (18:09:14, 25 December 2024)
- 05000267/LER-1980-055, Forwards LER 80-055/03L-0 + (18:09:16, 25 December 2024)
- ML19338G129 + (18:09:17, 25 December 2024)
- 05000133/LER-1980-005-03, /03L-0:on 800926,w/plant Shutdown,Water Seepage Observed Through Cracks in Pavement 4 Ft Above 10-inch Line Connecting Screen Wash Pumps in Fossil & Nuclear Units. Caused by Faulty Installation.Broken Section to Be Replaced + (18:09:18, 25 December 2024)
- 05000366/LER-1980-137, Forwards LER 80-137/03L-0 + (18:09:20, 25 December 2024)
- 05000259/LER-1980-074, Forwards LER 80-074/03L-0 + (18:09:22, 25 December 2024)
- 05000133/LER-1980-006-03, /03L-0:on 800926,w/plant Shut Down,Leak Observed in Gate Valve Housing at Screen Wash Pump Discharge 6.Caused by Corrosion & Erosion,Due to Natural end-of-life.Valve Will Be Replaced W/Pratt Monoflange Mk II Butterfly Valve + (18:09:25, 25 December 2024)
- ML19338G120 + (18:09:28, 25 December 2024)
- ML19338G119 + (18:09:28, 25 December 2024)
- 05000348/LER-1980-057, Forwards LER 80-057/03L-0 + (18:09:30, 25 December 2024)
- ML19338G115 + (18:09:31, 25 December 2024)
- 05000213/LER-1980-015, Forwards LER 80-015/03L-0 + (18:09:34, 25 December 2024)
- ML19338G112 + (18:09:36, 25 December 2024)
- 05000213/LER-1980-014, Forwards LER 80-014/03L-0 + (18:09:37, 25 December 2024)
- ML19338G109 + (18:09:39, 25 December 2024)
- 05000334/LER-1980-075, Forwards LER 80-075/01T-0 + (18:09:40, 25 December 2024)
- ML19338G104 + (18:09:47, 25 December 2024)
- ML19338G102 + (18:09:48, 25 December 2024)
- ML19338G103 + (18:09:48, 25 December 2024)
- 05000313/LER-1980-035, Forwards LER 80-035/99X-0 + (18:09:50, 25 December 2024)
- ML19338G099 + (18:09:52, 25 December 2024)
- ML19338G097 + (18:09:52, 25 December 2024)
- ML19338G096 + (18:09:57, 25 December 2024)
- ML19338G094 + (18:09:58, 25 December 2024)
- ML19338G093 + (18:09:59, 25 December 2024)
- ML19338G092 + (18:09:59, 25 December 2024)
- ML19338G090 + (18:10:00, 25 December 2024)
- 05000333/LER-1980-036-01, /01X-1:on 800417,during Normal Operation,Average Power Range Monitor F Found Operating W/One Level C Low Power Range Monitor Input.Caused by Failure to Declare Monitor F Inoperable After Low Power Monitor 800409 Calibr + (18:10:01, 25 December 2024)