- 05000269/LER-1982-002-01, /01T-0:on 820222,control Operator Moved Group 8 Control Rods Into Tech Spec Restricted Area to Clear Core Axial Imbalance Alarm.Caused by Operator Error.Rod Position Corrected & Computer Alarms Modified to Include Group 8 + (15:11:13, 18 December 2024)
- 05000295/LER-1982-011-01, /01T-0:on 820317,RHR Suction Pressure Transmitter 1PT-403 Failed High & Suction Valve 1MOV-RH8702 Started to Close.Caused by Piece of Sheet Metal Accidentally Dropped on Inverter 111 Output Breaker.Breaker Reclosed + (15:11:16, 18 December 2024)
- ML20050B054 + (15:11:18, 18 December 2024)
- 05000263/LER-1981-001-03, While Performing Surveillance Test Mo 2035,HPCI Outboard Steam Supply Isolation Valve Failed to Close.Caused by Opened Limitorque SMB-O,240-volt Dc & Torque Switches.Switches Replaced + (15:11:19, 18 December 2024)
- 05000295/LER-1982-011, Forwards LER 82-011/01T-0 + (15:11:21, 18 December 2024)
- ML20050B049 + (15:11:22, 18 December 2024)
- ML20050B047 + (15:11:23, 18 December 2024)
- ML20050B046 + (15:11:24, 18 December 2024)
- A02190, Comments on 811223 Draft Evaluation for SEP Topic VIII-4, Electrical Penetrations of Reactor Containment. Containment Integrity Will Be Maintained During Fault or Overcurrent Event W/Primary Protective Device Failure + (15:11:25, 18 December 2024)
- ML20050B040 + (15:11:27, 18 December 2024)
- 05000263/LER-1981-001, Forwards Updated LER 81-001/03X-1 + (15:11:29, 18 December 2024)
- ML20050B035 + (15:11:33, 18 December 2024)
- 05000269/LER-1982-002, Forwards LER 82-002/01T-0.Detailed Event Analysis Encl + (15:11:35, 18 December 2024)
- ML20050B031 + (15:11:40, 18 December 2024)
- 05000325/LER-1982-036-01, /01T-0:on 820308,valve Operator Motor from 1-E11-F002A Removed from Valve W/O Following Appropriate Procedures,Rendering RHR Svc Water Subsystem Inoperable. Caused by Communication Breakdown Among Maint Personnel + (15:11:41, 18 December 2024)
- ML20050B028 + (15:11:42, 18 December 2024)
- ML20050B026 + (15:11:43, 18 December 2024)
- 05000325/LER-1982-036, Forwards LER 82-036/01T-0 + (15:11:44, 18 December 2024)
- ML20050B023 + (15:11:45, 18 December 2024)
- ML20050B022 + (15:11:46, 18 December 2024)
- ML20050B020 + (15:11:48, 18 December 2024)
- 05000287/LER-1982-002-03, /03L-0:on 820210,reactor Protection Sys Channel B Hot Leg Temp Readings Were Lower than Those of Channels A,C & D.Caused by Failure of Liner Bridge in Input Circuitry for Channel B Indication.Bridge Replaced + (15:11:51, 18 December 2024)
- W3P82-0652, Discusses Resolution of Hydrological & Geotechnical Engineering Branch Concerns Re Availability of Installed Sump Pumps in Dry Cooling Towers During Intense Precipitation Events.Portable Pump Will Be Provided + (15:11:52, 18 December 2024)
- ML20050B015 + (15:11:55, 18 December 2024)
- IR 05000334/1981019 + (15:11:56, 18 December 2024)
- 05000315/LER-1982-013-03, /03L-0:on 820302,control Switch for Containment Pressure Equalization Fan in Stop & Backdraft Damper for Opposite Fan Was Open.Cause Could Not Be Determined.Startup Procedures Revised + (15:12:01, 18 December 2024)
- 05000287/LER-1982-002, Forwards LER 82-002/03L-0.Detailed Event Analysis Encl + (15:12:02, 18 December 2024)
- ML20050B009 + (15:12:03, 18 December 2024)
- 05000338/LER-1982-010-03, /03L-0:on 820223,post-reactor Trip Specific Activity Samples of RCS Indicated Dose Equivalent I-131 Level Greater than Tech Spec Limit.Caused by Fuel Element Defect.Sampling Frequency Accelerated + (15:12:05, 18 December 2024)
- ML20050B006 + (15:12:06, 18 December 2024)
- ML20050B005 + (15:12:10, 18 December 2024)
- 05000409/LER-1982-003-03, /03L-0:on 820313,during Type B Leakage Test on Personnel Airlock,Manometer Read Incorrectly.Caused by Inadequate Tightening of Strongbacks on Inner Door.Need for Tight Installation Emphasized & Procedure Revised + (15:12:18, 18 December 2024)
- 05000315/LER-1982-012-03, /03L-0:on 820303,turbine Driven Auxiliary Feedwater Pump Trip/Throttle Valve Tripped Shut When Manually Started.No Problems Found.Surveillance Test Completed.Pump Returned to Svc.No Further Action Planned + (15:12:20, 18 December 2024)
- ML20050B000 + (15:12:22, 18 December 2024)
- ML20050A994 + (15:12:27, 18 December 2024)
- 05000260/LER-1982-011-03, /03L-0:on 820215,during Operation,While Performing Chamber Water check,2-LI-64-66 Indicated Improper Torus & Level & Declared Inoperable.Caused by Instrument Drift & Possible Air in Ref Leg.Transmitter Calibr + (15:12:28, 18 December 2024)
- 05000335/LER-1982-009-03, /03L-0:on 820317,while Operating at 98% Power, Weekly Surveillance of Core Barrel Movement Required by Tech Spec 3.4.11 Was Not Performed.Surveillance Was Inadvertently Overlooked.Personnel Instructed to Perform Surveillance + (15:12:30, 18 December 2024)
- ML20050A991 + (15:12:31, 18 December 2024)
- 05000260/LER-1982-011, Forwards LER 82-011/03L-0 + (15:12:33, 18 December 2024)
- 05000327/LER-1982-028-03, /03L-0:on 820214 & 15,in Mode 3,cold Leg Accumulator 4 Declared Inoperable Due to Low Boron Concentration.Caused by Leak Through in Flow Control Leak Test & Fill Line Valves.Five Valves Investigated & Repaired + (15:12:34, 18 December 2024)
- IR 05000293/1982008 + (15:12:36, 18 December 2024)
- 05000409/LER-1982-003, Forwards LER 82-003/03L-0.Detailed Event Analysis Submitted + (15:12:38, 18 December 2024)
- ML20050A984 + (15:12:39, 18 December 2024)
- ML20050A983 + (15:12:40, 18 December 2024)
- 05000335/LER-1982-009, Forwards LER 82-009/03L-0 + (15:12:42, 18 December 2024)
- 05000327/LER-1982-028, Forwards LER 82-028/03L-0 + (15:12:45, 18 December 2024)
- ML20050A976 + (15:12:46, 18 December 2024)
- ML20050A975 + (15:12:47, 18 December 2024)
- ML20050A972 + (15:12:49, 18 December 2024)
- 05000287/LER-1982-003-01, /01T-0:on 820211,steam Generator Tube Leak of Approx 0.01 Gpm Indicated by Condensate Steam Air Ejector Offgas Monitor.Caused by Erosion of Tube at Point 31 Inches Above Fifteenth Tube Support Plate.Tube Explosively Plugged + (15:12:50, 18 December 2024)
- 05000315/LER-1982-011-03, /03L-0:on 820223,during Surveillance Per Tech Spec 4.8.2.5.2B,three Cells of N Train Battery Found to Have Electrolyte Gravity Less than 1.200 Min Limit.Caused by Low Readings & Loss of Acid.Acid Added & Battery Tested + (15:12:53, 18 December 2024)