- 05000416/LER-1983-040-03, /03L-0:on 830127,smoke Detector in Zone Covering Elevation 139 Ft in Auxiliary Bldg Covered to Perform Welding in Area & Prevent Actuation of Alarm.Caused by Planned Maint Activities.Smoke Detector Uncovered + (04:00:15, 15 December 2024)
- 05000416/LER-1983-090-01, Inlet Valve to Reactor Water Cleanup Sys Nonregenerative HX Discovered Closed. Caused by Valve Isolation When Relay Removed During Limiting Safety Sys Setting Troubleshooting + (04:00:17, 15 December 2024)
- 05000416/LER-1983-040, Forwards LER 83-040/03L-0 + (04:00:18, 15 December 2024)
- 05000237/LER-1983-083-03, /03L-0:on 831226,while Lowering Suppression Pool Level,Lpci 1501-3B Valve Tripped Thermally.Caused by Underrated Overload Heaters (GE CR 123 L1.74A) in Valve Motor Overload Assembly.Heaters Replaced + (04:00:20, 15 December 2024)
- ML20079N613 + (04:00:21, 15 December 2024)
- ML20079N610 + (04:00:21, 15 December 2024)
- ML20079N609 + (04:00:22, 15 December 2024)
- ML20079N603 + (04:00:23, 15 December 2024)
- ML20079N601 + (04:00:23, 15 December 2024)
- 0CAN028316, Application for Amend to Licenses DPR-51 & NPF-6,changing Tech Specs Section 6 to Require Annual Reporting of Safety & Relief Valve Challenges,In Response to NRC 820920 Generic Ltr 82-16 + (04:00:24, 15 December 2024)
- ML20079N595 + (04:00:24, 15 December 2024)
- ML20079N593 + (04:00:25, 15 December 2024)
- ML20079N590 + (04:00:26, 15 December 2024)
- A830027, Forwards Public Version of Rev 2 to Emergency Plan Implementing Procedure 5.7.2, Notification of Unusual Event. W/O Encl + (04:00:27, 15 December 2024)
- ML20079N582 + (04:00:28, 15 December 2024)
- 05000348/LER-1983-007-03, /03L-0:on 830114,electrical Penetration Q1T52B038-B Failed Local Leak Rate Test.Caused by O-ring Damage at Inner Seal from Repairs During Previous Refueling outage.O-rings Replaced + (04:00:29, 15 December 2024)
- 2CAN028316, Responds to Re Schedule for Core Protection Computer Mods to Correct Low Power Density Penalty Factor.Correction Will Be Provided During Next Software Update.Schedule Should Be Available by 830530 + (04:00:30, 15 December 2024)
- 05000321/LER-1983-113-03, /03L-0:on 831220,surveillance Personnel Noted Reactor Bldg Exhaust Vent Radiation Monitors 1D11-K609 A,B & C Inoperable.Caused by Monitors 1D11-K609 A,B & C Out of Calibr.Monitors Recalibr + (04:00:32, 15 December 2024)
- 05000348/LER-1983-007, Forwards LER 83-007/03L-0 + (04:00:33, 15 December 2024)
- ML20079N573 + (04:00:33, 15 December 2024)
- 05000416/LER-1983-039-99, /99X-0:on 830112,during Cold Shutdown,Halon Panel 1H13P911 Detector a Alarmed & Would Not Reset.Hourly Fire Watch Established.Corrective Maint Underway + (04:00:35, 15 December 2024)
- ML20079N561 + (04:00:36, 15 December 2024)
- 05000366/LER-1983-137-03, /03L-0:on 831221 & 22,personnel Determined Safety Relief Valve Tailpipe Temp Recorder 2B21-R614 Inoperable. Caused by Failed Chart Drive Motor & Failed Chart Drive Idler Gear.Replacement Parts Installed + (04:00:40, 15 December 2024)
- ML20079N557 + (04:00:41, 15 December 2024)
- 05000348/LER-1983-002-03, /03L-0:on 830128,source Range Detector NI-31 Declared Inoperable Due to Low Detector Voltage.Caused by Setpoint Drift.High Voltage Power Supply Adjusted & Detector Returned to Svc + (04:00:42, 15 December 2024)
- ML20079N553 + (04:00:43, 15 December 2024)
- 05000416/LER-1983-039, Forwards LER 83-039/99X-0 + (04:00:44, 15 December 2024)
- ML20079N552 + (04:00:44, 15 December 2024)
- 05000321/LER-1983-124-03, /03L-0:on 831215,transverse in-core Probe B Detector Cable Could Not Be Withdrawn.Caused by Drive Cable Binding in Indexing Tube.Detector B Drive Cable & Indexing Tube Section Replaced + (04:00:46, 15 December 2024)
- 05000348/LER-1983-002, Forwards LER 83-002/03L-0 + (04:00:47, 15 December 2024)
- ML20079N546 + (04:00:48, 15 December 2024)
- 05000316/LER-1983-125-03, /03L-0:on 831229,output from Flux Penalty Module 2NY-441 Found Drifting in Conservative Direction.Cause Not Stated.Flux Penalty Module Calibr & Returned to Svc + (04:00:49, 15 December 2024)
- ML20079N538 + (04:00:50, 15 December 2024)
- ML20079N537 + (04:00:51, 15 December 2024)
- GO2-83-160, Final Deficiency Rept 190 Re Excessive Cable Length Causing Voltage Drop.Initially Reported on 820511.Control Power Transformer Increased from 300 VA to 500 VA to Preclude Voltage Drop + (04:00:54, 15 December 2024)
- ML20079N530 + (04:00:54, 15 December 2024)
- ML20079N524 + (04:00:55, 15 December 2024)
- ML20079N521 + (04:00:55, 15 December 2024)
- 05000315/LER-1983-130-03, /03L-0:on 831230,during Normal Operations,Air Leak Discovered on Steam Generator Blowdown Sample Containment Isolation Valve 4 (DCR-304).Caused by Degraded O-ring Inside Valve operator.O-ring Replaced + (04:00:57, 15 December 2024)
- ML20079N513 + (04:00:58, 15 December 2024)
- ML20079N512 + (04:00:59, 15 December 2024)
- 05000315/LER-1983-129-03, /03L-0:on 831228,during Normal Operation,Fire Door 471 Would Not Fully Close & Latch.Caused by Latch Plate Being Misaligned W/Latch Bolt of Active Leaf.Latch Plate Aligned & Door Closers Adjusted + (04:01:00, 15 December 2024)
- ML20079N506 + (04:01:01, 15 December 2024)
- 05000315/LER-1983-128-03, /03L-0:on 831226,during Performance of Diesel Generator AB Operability Test,Diesel Generator Tripped on Apparent Overspeed Condition.Caused by Loose Ground Wire Associated W/Electronic Tachometer Circuit + (04:01:03, 15 December 2024)
- ML20079N497 + (04:01:04, 15 December 2024)
- 05000395/LER-1983-143-03, /03L-0:on 831224,while in Mode 1,indication for Condensate Storage Tank Level Transmitter LT-3621 Failed High Because of Frozen Instrument Lines.Caused by Abnormally Cold Temp.Heat Trace Setpoints Increased + (04:01:05, 15 December 2024)
- ML20079N492 + (04:01:06, 15 December 2024)
- 05000259/LER-1984-001, :on 840103,RHR Pump 1D Started W/O Receiving Automatic Signal or Manual Start Signal from Control Room. Caused by Laborers Performing Decontamination Work.Laborers Cautioned + (04:01:11, 15 December 2024)
- ML20079N471 + (04:01:12, 15 December 2024)
- ML20079N461 + (04:01:13, 15 December 2024)
- ML20079N467 + (04:01:13, 15 December 2024)
- ML20079N452 + (04:01:14, 15 December 2024)