Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20084P569 + (ML20084P569)
- 05000327/LER-1984-025, :on 840415,sampling of RCS for Boron Concentration Caused Pressurizer Level Transmitter 1-LT-68-320 to Become Inoperable Due to Mod Made During Last Outage Routing Sense Line from Low Side Top + (ML20084P573)
- 05000249/LER-1976-025, :on 761007,during Refueling Outage Local Leak Rate Testing,Feedwater Check Valves 3-820-58B & 62B Exhibited Leakage Rates Above Tech Spec Limit.Caused by Dirt in Seating Area.Valve Cleaned & Retested + (ML20084P579)
- ML20084P584 + (ML20084P584)
- ML20084P592 + (ML20084P592)
- ML20084P594 + (ML20084P594)
- ML20084P597 + (ML20084P597)
- 05000249/LER-1976-024, Following Refueling Outage Surveillance Testing of Diesel Generator,Engine Speed Could Not Be Adjusted from Control Room.Caused by Loose Wire on Diesel Governor Control Circuit + (ML20084P598)
- ML20084P599 + (ML20084P599)
- 05000249/LER-1976-024-01, :on 761009,following Refueling Outage Surveillance Test of Diesel Generator,Engine Speed Could Not Be Regulated from Control Room.Caused by Loose Wire on Diesel Governor Control Circuit.Wire Tightened + (ML20084P613)
- 05000249/LER-1976-023, :on 761007,during Refueling Outage Local Leak Rate Testing,Lpci Primary Isolation Check Valve 3-1501-25B Exhibited Leak Rate Above Tech Spec Limit.Caused by Dirt & Scratches on Valve Seat.Valve Cleaned + (ML20084P617)
- 05000254/LER-1976-020-03, /03L-0:on 760701,loss of Indication & Operability Occurred on Containment Spray Loop B Outboard Valve MO-1-1101-23B.Caused by Loose hold-down Bolts.Bolts tightened.W/760729 Forwarding Ltr + (ML20084P619)
- ML20084P626 + (ML20084P626)
- ML20084P627 + (ML20084P627)
- 05000249/LER-1976-022, :on 760929,during Prerequisite Testing for Refueling Outage LPCI Logic Surveillance,Dpis 261-34A Failed to Trip.Caused by Roller Cam Being Jammed by Microswitch Actuating Arm.Switch Repaired + (ML20084P630)
- 05000249/LER-1976-021, :on 760924,during Routine Insp of Drywell Snubbers,Snubbers 24 & 30 Appeared to Be Inoperable Due to Loss of Fluid.Caused by Leakage Through Grease Fittings. Grease Fittings Replaced + (ML20084P633)
- ML20084P635 + (ML20084P635)
- 05000249/LER-1976-020, :on 760922,during Refueling Outage Local Leak Rate Testing,Vol Bounded by Main Steam Line Drain Valves 3-220-1 & 2 Exhibited Leak Above Tech Specs Limit.Probably Caused by Deteriorated Pressure Seal Ring + (ML20084P642)
- ML20084P648 + (ML20084P648)
- ML20084P651 + (ML20084P651)
- 05000249/LER-1976-020-01, Vol Bounded by Steam Line Drain Valves 3-220-1 & 2 Exhibited Leakage Above Tech Spec Limits.Caused by Deteriorated body-to-bonnet Pressure Seal Ring & Dirt in Seating Area + (ML20084P653)
- ML20084P654 + (ML20084P654)
- ML20084P657 + (ML20084P657)
- ML20084P661 + (ML20084P661)
- ML20084P664 + (ML20084P664)
- ML20084P667 + (ML20084P667)
- ML20084P671 + (ML20084P671)
- 05000249/LER-1976-019, :on 760921,diesel Generator Not Shutdown Following Return to Svc of Bus 34-1 & Engine High Temp Alarm Received. Caused by Partially Clogged Strainer in Lube Oil Circulating Pump.Strainer Cleaned + (ML20084P672)
- ML20084P674 + (ML20084P674)
- ML20084P676 + (ML20084P676)
- 05000249/LER-1976-018, :on 760921,during Refueling Outage Local Leak Rate Testing,Feedwater Check Valves 3-220-58A & 62A Exhibited Leak Rates Above Tech Spec Limit.Caused by Dirt in Seating Area & Worn Disc Assembly Pins + (ML20084P677)
- ML20084P681 + (ML20084P681)
- ML20084P686 + (ML20084P686)
- 05000249/LER-1976-017, :on 760918,during de-inerting of Drywell,Oxygen Concentration Exceeded 4%.Facility Not Shut Down within 24 H Period in Order to Satisfy Min Sys Load Requirements + (ML20084P687)
- 05000249/LER-1976-016, :on 760918,during Local Leak Rate Testing of Drywell & Torus Vent Isolation Valves,Valve 3-1601-23 Exhibited Leak Rate Above Tech Spec Limit.Caused by Packing Failures.Packing Bolts Tightened + (ML20084P693)
- ML20084P694 + (ML20084P694)
- 05000249/LER-1976-015, :on 760912,during Routine Plant Insp,Steam Leak Found in Elbow on Moisture Separator Drain Tank Line B to D Feedwater Heaters.Caused by Failure of Support Bolt Due to Surge in Process Stream.Crack Ground & Welded + (ML20084P696)
- ML20084P712 + (ML20084P712)
- ML20084P719 + (ML20084P719)
- B11165, Forwards Response to Matls Engineering Branch Draft SER Open Item Mteb 250.9 Re Compliance W/Reg Guide 1.50, Ultrasonic Testing of Reactor Vessels During Preservice & Inservice Insp + (ML20084P725)
- ML20084P726 + (ML20084P726)
- ML20084P734 + (ML20084P734)
- ML20084P741 + (ML20084P741)
- ML20084P744 + (ML20084P744)
- 05000254/LER-1976-019-01, /01T-0:on 760617,HPCI Motor Speed Changer Failed to Operate During Monthly Surveillance.Caused by Inadequate Lubrication.Lubrication Schedule established.W/760701 Forwarding Ltr + (ML20084P751)
- ML20084P755 + (ML20084P755)
- 05000265/LER-1976-018-03, /03L-0:on 761114,half Scram Signal Not Received for MSIV AO-2-203-1D & Open Alarm Did Not Annunciate on Control Room Panel 902-5.Caused by Failed Limit Switch. Switch replaced.W/770106 Forwarding Ltr + (ML20084P770)
- ML20084P786 + (ML20084P786)
- ML20084P796 + (ML20084P796)
- 05000249/LER-1976-014, :on 760902,during Startup Operations,Control Room Indication Showed MSIV 3-203-2B Failed to Fully Close.Caused by Slippage of Actuator Arm of position-indicating Limit Switch on Shaft + (ML20084P800)
- ML20084P803 + (ML20084P803)