- 05000389/LER-1983-005-01, /01T-0:on 830507,while Reviewing Plant Status Following Mode Change to Hot Shutdown,Discovered Safety Injection Tanks Had Remained Isolated.Caused by Personnel Error.Operators Counseled on Procedures + (ML20076E708)
- 05000369/LER-1983-021-03, /03L-0:on 830419,while in Mode 5,nuclear Svc Water Sys Valve 1RN-69 Actuator W/Mechanical Latch Replaced by Actuator Requiring Electrical Antihammer Circuit.Caused by Deficient Procedure + (ML20076E709)
- AECM-83-0298, RO 83-035/0:on 830415,Fire Door 1A401 Blocked Open to Prevent Possibility of Personnel Injury Due to High Differential Pressure Across Door as Result of Secondary Containment Boundary.Door to Be Closed 830630 + (ML20076E711)
- ML20076E714 + (ML20076E714)
- ML20076E722 + (ML20076E722)
- ML20076E727 + (ML20076E727)
- 1CAN058306, Withdraws Request for Exemption from Requirements to Install Reactor Vessel Head Vents,As Installation of Vents Subsequently Decided Upon & Completed During Fifth Refueling Outage + (ML20076E728)
- ML20076E729 + (ML20076E729)
- ML20076E730 + (ML20076E730)
- ML20076E734 + (ML20076E734)
- 05000318/LER-1983-024-03, /03L-0:on 830418,charging Pump 22 Removed from Svc Upon Discovery of Leak on Discharge Relief Valve Line.Caused by Crack in Socket Weld Between Coupling & Inlet Pipe of Relief Valve,Due to Vibration.Weld Repaired + (ML20076E736)
- 05000387/LER-1983-068-03, /03L-0:on 830419,during Surveillance Testing to Demonstrate Diesel Generator Operability Following Maint, Diesel Generator a Failed to Start within Required 10 S. Caused by Lines Drained During Maint + (ML20076E742)
- ML20076E744 + (ML20076E744)
- ML20076E755 + (ML20076E755)
- ML20076E756 + (ML20076E756)
- ML20076E758 + (ML20076E758)
- 05000334/LER-1981-083-03, Nuclear Instrumentation Power Range Monitor N44 Failed Low Due to Power Supply Problems.Power Supply Replaced.Failed Monitor Sent to Westinghouse for Repair + (ML20076E761)
- ML20076E771 + (ML20076E771)
- ML20076E774 + (ML20076E774)
- 05000318/LER-1981-050-03, Reactor Protective Sys Channel B Thermal Margin/Low Pressure Trip Unit Bypassed for Maint After Receiving Spurious Asymmetric Steam Generator Trips.Caused by Failed Signal Isolator + (ML20076E776)
- 05000317/LER-1983-015-03, /03L-0:on 830415,plant Computer Failed,Rendering in-core Detector Monitoring Sys Inoperable.Caused by out-of- Step Selection of Multiple Analog Inputs to Analog Control Board,Resulting in Blown Power Fuse + (ML20076E778)
- 05000317/LER-1983-023-03, /03L-0:on 830419,containment Pump (CS) Alarm Would Not Clear,Rendering Sump Inoperable Per Tech Spec 3.4.6.1. Sump Drained Until Alarm Cleared.Cause Not Determined + (ML20076E806)
- ML20076E812 + (ML20076E812)
- 05000333/LER-1980-006-03, Core Spray Injection Valve 14-MOV-12A Improperly Operated During 791221 Surveillance Test.Caused by Misoperation of Valve Circuit Breaker Overload Trip Device + (ML20076E823)
- ML20076E827 + (ML20076E827)
- AECM-83-0483, Forwards Rev to Special Test Procedure 4, Balance of Plant Vibration Monitoring Program, Per 830721 Submittal & GE Approval of Acceptance Criteria Mod for Startup Test Procedure 05, Control Rod Drive Sys + (ML20076E831)
- 05000293/LER-1983-019-03, /03L-0:on 830410,sprinkler Head Supply Pipe on Top of Turbine Stop Valves Found Severed W/Water Running from Pipe.Probably Caused by Pipe Fatigue Due to Vibration.Pipe Threaded,Installed & Visually Inspected + (ML20076E840)
- ML20076E849 + (ML20076E849)
- ML20076E852 + (ML20076E852)
- ML20076E855 + (ML20076E855)
- ML20076E860 + (ML20076E860)
- ML20076E861 + (ML20076E861)