- 05000313/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20072F625)
- 05000395/LER-1983-047-03, /03L-0:on 830517,w/plant in Mode 4,turbine Bldg Sump Radiation Monitor (RM-L8) Removed from Svc Because of Inadequate Sample Pump Flow.Caused by Sludge Buildup.Pump Disassembled & Cleaned + (ML20072F627)
- 05000293/LER-1983-026-03, /03L-0:on 830515,during Insp of Control Rod Drive Piping,Number of Vent Valve Plugs Discovered Missing.No Leaks Observed.Caused by Inadequate Procedures.Missing Plugs Replaced.Procedures Modified + (ML20072F629)
- ML20072F639 + (ML20072F639)
- ML20072F642 + (ML20072F642)
- ML20072F648 + (ML20072F648)
- 05000313/LER-1983-004-03, /03L-0:on 830214,RCS Pressure Transmitters PT-1040 & PT-1020 Found Out of Tolerance.Caused by Transmitter Drift.Transmitter Recalibr & Left within Allowable Tolerance + (ML20072F649)
- 05000261/LER-1983-002, Forwards LER 83-002/03L-0 + (ML20072F656)
- ML20072F659 + (ML20072F659)
- ML20072F661 + (ML20072F661)
- 05000237/LER-1982-043, Forwards Updated LER 82-043/01X-2 + (ML20072F666)
- ML20072F668 + (ML20072F668)
- 05000443/LER-1994-013, :on 940515,determined That Both Trains of Fuel Storage Bldg Emergency Air Cleaning Sys Inoperable Since 940509 Due to Inadequate Review of Associated Work Request. Work Request Procedure Will Be Revised + (ML20072F673)
- ML20072F674 + (ML20072F674)
- ML20072F676 + (ML20072F676)
- ML20072F678 + (ML20072F678)
- ML20072F680 + (ML20072F680)
- ML20072F681 + (ML20072F681)
- 05000261/LER-1983-002-03, /03L-0:on 830215,safety Injection Pump a Tripped After Being Started for Routine Filling of Accumulators. Caused by Faulty Pump Breaker.Overcurrent Trip Device Replaced.Evaluation of Event Continuing + (ML20072F686)
- ML20072F687 + (ML20072F687)
- ML20072F693 + (ML20072F693)
- ML20072F694 + (ML20072F694)
- ML20072F697 + (ML20072F697)
- 05000237/LER-1982-043-01, Sightglass Isolation & Vent Valves Reported Open W/No Indication of Excess Make Up. Caused by Operator Error.Valves Immediately Closed. Sightglass Isolation Valves Locked Closed + (ML20072F704)
- ML20072F709 + (ML20072F709)
- 05000316/LER-1983-022, Forwards LER 83-022/03L-0 + (ML20072F712)
- ML20072F725 + (ML20072F725)
- ML20072F733 + (ML20072F733)
- 05000327/LER-1983-029, Forwards LER 83-029/03L-0 + (ML20072F747)
- 05000327/LER-1983-029-03, /03L-0:on 830219,ice Condenser Lower Inlet Door Zone D Limit Switches Indicated Open Door.Caused by Misadjustment of Microswitch Limit Switch Model LSH1A for Ice Condenser Bays 9 & 11.Limit Switches Adjusted + (ML20072F755)
- 05000334/LER-1983-015-03, /03L-0:on 830524,during Normal Power Operation, Relay 5I-VD106X Experienced Spurious Actuation,Causing Inadvertent Isolation of Emergency Bus 1DF from Normal Supply.Caused by Personnel Error + (ML20072F758)
- 05000387/LER-1983-080-03, /03L-0:on 830513,setpoint for PDIS-E-11-INO19B (Shutdown Cooling High Flow) Found Out of Tolerance.Caused by Setpoint Drift.Switch Recalibr & Returned to Svc + (ML20072F760)
- 05000302/LER-1994-004, :on 940701,noticed That ATWS Turb AMSAC Low Flux Bypass Annunciator Began to Alarm Every Few Seconds Due to Personnel Error.Setpoints for ATWS-AMSAC Arming Reset & Surveillance Performed + (ML20072F770)
- ML20072F772 + (ML20072F772)
- 05000373/LER-1983-015, Forwards LER 83-015/03L-0.Detailed Event Analysis Encl + (ML20072F778)
- 05000373/LER-1983-015-03, /03L-0:on 830217,while Testing Diesel Generator 1B Per LOS-DG-M3,diesel Tripped While Being Off Loaded.Diesel Restarted & Speed Varied Between 400 & 900 Rpm.Caused by Bad Connection at Run Solenoid.Connection Reconnected + (ML20072F796)
- PY-CEI-NRR-0053, Responds to Generic Ltr 83-18, NRC Review of BWR Owners Group Control Room Survey Program. Plant-specific Info to Be Addressed Listed + (ML20072F798)
- ML20072F799 + (ML20072F799)
- 05000219/LER-1994-011, :on 940718,discovered That Control Panels Er 8A & Er 8B Housing Control Logic for Portions of ADS & CSS Did Not Meet Seismic Criteria Due to Original Design.Seismic Plates Installed to Limit Control Panel Motion + (ML20072F801)
- ML20072F807 + (ML20072F807)
- ML20072F811 + (ML20072F811)
- 05000263/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20072F818)
- 05000416/LER-1982-172-99, Penetration AE154C in Auxiliary Bldg Opened to Perform Planned Maint.Penetration Opened to Pull Cable Through.Limiting Condition for Operation Initiated & Hourly Fire Watch Established + (ML20072F823)
- ML20072F829 + (ML20072F829)
- 05000263/LER-1983-005-03, /03L-0:on 830216,RHR Pump 14 Made Inoperable to Investigate Head Capacity Reduction.Caused by Mophead in Pump Suction,Probably Entering RHR Sys During Maint or Const Projects.Mophead Removed + (ML20072F832)
- 05000318/LER-1983-028-03, /03L-0:on 830516,accumulator 12 on MSIV 21 Found to Have Ruptured Bladder.No Cause Stated.Accumulator Repaired & MSIV Declared Operable.Msiv 21,accumulator 5,will Be Replaced During Next Hot Shutdown + (ML20072F834)
- ML20072F835 + (ML20072F835)
- ML20072F846 + (ML20072F846)
- ML20072F849 + (ML20072F849)
- ML20072F850 + (ML20072F850)
- ML20072F863 + (ML20072F863)